AUTOVAR ® FILTER

AUTOMATICALLY SWITCHED MEDIUM VOLTAGE HARMONIC FILTER/POWER FACTOR CORRECTION

http://www.comsprague.com AUTOVAR® MV FILTER BANK Automatic Power Factor Filter Systems

Harmonic compensation and power factor correction system for medium voltage applications with auto- matically switched capacitor stages. • Programmable solid state power factor controller that automatically adds or subtracts capacitor banks to maintain preset target power factor. • Reactors specifically designed for de-tuned, tuned and high pass filter. • Separation barrier between higher operating FEATURES AND SPECIFICATIONS: temperature harmonic reactors and heat sensitive capacitors. CONFIGURATION: Cabinet: 11 Gauge, seam welded NEMA 1, 3R, or 4X : APPLICATIONS ratings; ANSI gray — 61 corrosion resistant enamel; The MV Filter Bank is designed for commercial and Forced air ventilation; Sloped-roof enclosure design industrial power systems to improve power factor, for channeling snow and water; Cubicle doors with reduce harmonic distortion, increase system capacity, view ports main disconnect switch, ground blade, and improve voltage regulation. Autovar-MV Filter capacitor section; Moisture and varmint resistant Banks are power quality devices which reduce base channel design. harmonic distortion (current or voltage), improve Fusing: Main fuses (50KA) for fault current detection power factor, provide voltage support, and increase and overcurrent protection. Individual capacitor cells system capacity. protected with explosion resistant fuses. Harmonic reactors: Tuning reactors custom designed to commercial and industrial applications. Sizing usually results from harmonic spectrum analysis of field measured data. Interrupting device: Vacuum Contactors (oil optional, breaker extra). Keyed Interlock: Standard keyed interlock system interconnects main and ground switch as well as capacitor and reactor cubicle doors. Blown fuse detection: Instrumentation panel light provides alarm status indication for unbalanced neutral voltage or current. Indicator of individual blown capacitor fuses is based on solid-state, microprocessor overcurrent relay. Ground switch system: Visual safety indication through cubicle view ports. Interlockable switch applies solid, safety ground to electrically continuous ground bus to provide additional de-energizing of individual capacitor cells. Controls • Solid state power factor controller with micro- processor and liquid crystal display for power factor metering and indication of energized capacitor stages. • Micro Programmable Logic Controller for sequencing, timing, and controls. – delay (5 minutes typical) for capacitor discharging, capacitor settling or restrike duration.

- 2 - CAPACITORS: • Low loss, all film/foil capacitors • Stainless steel tank and mounting brackets with a light gray finish • Non-PCB dielectric • Internal discharge resistors

STANDARD FEATURES: CSCI provides as standard • Staged capacitors controlled either automatically or manually • On/off (red and green) indicator lights for capacitor stages • Operational counter • Pad mounted design • Heavy duty, welded construction (11 gauge) • Lifting hooks • Control power (120VAC) with indicator light • Durable, laminated instrumentation panel • Weather resistant lock covers • 3 point latch door handle with door stop • Hazard and warning labels

Selection Guide*

4160V 4,160 VOLTS 4160V SINGLE STAGE (1 STEP DESIGN) DOUBLE STAGE (2 OR 3 STEPS) TOTAL DIMENSION (in.) WEIGHT TOTAL (2 STEP DESIGN) (3 STEP DESIGN) DIMENSION (in.) WEIGHT (lbs.) KVAR D H L (lbs.) KVAR FIRST SECOND FIRST SECOND D H L (2 OR 3 STEPS) 450 72 94 84 3250 450 150 300 72 94 126 3750 900 72 94 84 3450 900 450 450 300 600 72 94 126 3950 1050 72 94 84 3650 1350 450 900 72 94 126 4550 1800 900 900 600 1200 72 94 148 4750 2700 900 1800 72 94 148 4950

4160V 12,470 VOLTS-13,800 VOLTS 4160V SINGLE STAGE (1 STEP DESIGN) DOUBLE STAGE (2 OR 3 STEPS) TOTAL DIMENSION (in.) WEIGHT TOTAL (2 STEP DESIGN) (3 STEP DESIGN) DIMENSION (in.) WEIGHT (lbs.) KVAR D H L (lbs.) KVAR FIRST SECOND FIRST SECOND D H L (2 OR 3 STEPS) 450 72 94 84 3250 450 150 300 72 94 126 3850 600 72 94 84 3350 900 300 600 450 450 72 94 126 4150 900 72 94 84 3550 1200 600 600 72 94 126 4500 1200 72 94 84 3750 1350 450 900 72 94 126 4800 1800 72 94 84 3950 1800 600 1200 900 900 72 94 160 5000 2400 1200 1200 72 94 160 5200 2700 900 1800 1350 1350 72 94 160 5400 3000 1500 1500 72 94 160 5600 3600 1200 2400 1800 1800 72 94 160 6000 5400 2700 2700 72 94 180 7000

* For additional design options, contact application engineers at the CSCI factory.

- 3 - Filter Bank

Contact your local Commonwealth Sprague sales representative for details.

Commonwealth Sprague Capacitor, Inc. 1560 Curran Highway, North Adams, MA 01247 http://www.comsprague.com 413-664-4461 (Tel) / 413-664-4465 (Fax)

- 4 - QPC/5/01/MVPF1556