<<

TEC22x7-4 Series LONWORKS® Network Controllers with Two Outputs Part No. 24-9890-1265, Rev. — Installation Instructions Issued February 8, 2010 TEC2227-4, TEC2247-4

Applications North American Emissions Compliance The TEC22x7-4 Series Thermostat Controllers are United States LONWORKS® network devices that provide control of local hydronic reheat , pressure dependent This equipment has been tested and found to (VAV) equipment with or without comply with the limits for a Class A digital device local reheat, or other zoning equipment using an on/off, pursuant to Part 15 of the FCC Rules. These limits floating, or proportional 0 to 10 VDC control input. are designed to provide reasonable protection The technologically advanced TEC22x7-4 Series against harmful interference when this equipment is Thermostat Controllers feature a Building operated in a commercial environment. This equipment generates, uses, and can radiate radio System (BAS) LONWORKS network communication frequency energy, and, if not installed and used in capability that enables remote monitoring and accordance with the instruction manual, may cause programming for efficient space control. harmful interference to radio communications. The TEC22x7-4 Series Thermostat Controllers feature Operation of this equipment in a residential area is an intuitive User Interface (UI) with backlit display that likely to cause harmful interference, in which case makes setup and operation quick and easy. The the user will be required to correct the interference thermostat controllers also employ a unique, at his/her own expense. proportional control algorithm that virtually eliminates temperature offset associated with traditional, Canada differential-based thermostat controllers. This Class (A) digital apparatus meets all the IMPORTANT: The TEC22x7-4 Series Thermostat requirements of the Canadian Interference-Causing Controllers are intended to provide an input to Equipment Regulations. equipment under normal operating conditions. Cet appareil numérique de la Classe (A) respecte Where failure or malfunction of the thermostat toutes les exigences du Règlement sur le matériel controller could lead to personal injury or property brouilleur du Canada. damage to the controlled equipment or other property, additional precautions must be designed Installation into the . Incorporate and maintain other devices, such as supervisory or alarm systems Location Considerations or safety or limit controls, intended to warn of or Locate the TEC22x7-4 Series Thermostat Controller: protect against failure or malfunction of the thermostat controller. • on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature • away from direct sunlight, radiant , outside walls, behind doors, air discharge grills, stairwells, or outside doors • away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference Note: Allow for vertical air circulation to the TEC22x7-4 Series Thermostat Controller.

TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs 1 Installation Instructions To install the thermostat controller: 4. Pull approximately 6 in. (152 mm) of from the wall and insert the wire through the hole in the 1. Use a Phillips-head screwdriver to remove the thermostat controller mounting base. security screw on the bottom of the thermostat controller cover. 5. Align the thermostat controller mounting base on the wall and use the base as a template to mark Note: Normally, the security screw is packaged the two mounting hole locations. separately in a plastic bag with the thermostat controller. Skip this step if the screw is not installed 6. Position the thermostat controller mounting base on the bottom of the cover. so that the arrow on the base points upward to indicate the top of the thermostat controller. 2. Pull the bottom edge of the thermostat controller cover and open the thermostat controller as Note: If you need to install the thermostat on an illustrated in Figure 1. electrical junction box, use 2-1/2 x 4 in. (63 x 101 mm) square boxes with mud ring covers, and avoid smaller 1-1/2 x 4 in. (38 x 101 mm) or 3 x 2 in. (76 x 51 mm) square boxes. This procedure ensures that you have enough space for cabling and end-of-line devices, if needed. Note: For surface-mount applications, use durable mounting hardware such as Molly bolt anchors that cannot be easily pulled out of the mounting surface. 7. Secure the mounting base to the wall surface using two mounting screws as illustrated in Figure 3. Note: Be careful not to overtighten the mounting screws. FIG:cvr_rmvl

Figure 1: Removing the Thermostat Controller Cover

3. Carefully pull the locking tabs on the right side of the thermostat controller mounting base and unlock the (PCB). Open the PCB to the left as illustrated in Figure 2.

s

b

_

t

n

m

:

G

I

F

Figure 3: Securing the Thermostat Controller PCB Mounting Base to the Wall Locking Tabs 8. Swing the PCB back to the right and carefully snap it into the locking tabs on the thermostat controller mounting base.

d

b

_

c

r

i

c

_

p

o

:

G

I

F Figure 2: Opening the Thermostat Controller PCB

2 TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions 9. Remove the screw terminal blocks that are CAUTION: Risk of Electric Shock. attached to a disposable adhesive. Figure 4 Disconnect the power supply before illustrates the locations of the screw terminal making electrical connections to avoid blocks on the thermostat controller. ! electric shock.

CAUTION: Risk of Property Damage. Do not apply power to the system before ! checking all wiring connections. Short circuited or improperly connected may result in permanent damage to the equipment.

IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of

s

k

c

l

b the TEC22x7-4 Series Thermostat Controller.

_

l

n

m

r

t

:

G

I F To wire the thermostat controller:

Figure 4: Removing the Screw Terminal Blocks 1. Strip the ends of each wire 1/4 in. (6 mm) and connect them to the appropriate screw terminals as indicated in Table 1 and Figure 6 through Wiring Figure 19. When an existing thermostat controller is replaced, Note: For more details on wiring the LonWorks remove and label the wires to identify the terminal network, refer to the LON ORKS functions. When a TEC22x7-4 Series Thermostat W Network Layout Controller is replaced, simply remove the old screw Technical Bulletin (LIT-1162150). terminal blocks and reinsert them onto the PCB of the 2. Carefully push any excess wire back into the wall. replacement thermostat controller. Note: Seal the hole in the wall with fireproof The LONWORKS connection does not have a removable material to prevent drafts from affecting the terminal block. It has two screw terminals, one for each ambient temperature readings. of the wires. 3. Reinsert the screw terminal blocks onto the PCB. To replace a thermostat controller: 4. Reattach the LONWORKS communication wires to 1. Unscrew both LONWORKS terminal screws and the terminal block. See Figure 5. remove the wires. Note: If inserting multiple wires in the terminals, 2. Replace the thermostat controller. be sure to properly twist wires together prior to inserting them in the terminal connectors. 3. Reinsert the LONWORKS wires. 5. Reattach the thermostat controller cover to the 4. Tighten the LONWORKS terminal screws, as shown mounting base (top side first). in Figure 5. 6. Use a Phillips-head screwdriver to reinstall the

security screw on the bottom of the thermostat controller cover.

TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions 3 Table 1: Terminal Identification (See Figure 6.) Terminal Terminal Label Function Number TEC2227-4 TEC2247-4 4 24 V~ Hot 24 V~ Hot 24 VAC from 5 24 V~ Com 24 V~ Com 24 VAC (Common) from Transformer 6 BO5 Aux BO5 Aux BO5 Auxiliary Output 7 BO5 Aux BO5 Aux BO5 Auxiliary Output 8 BO3 Blank Open Heat 9 BO4 AO2 Close Heat 10 BO1 AO1 Open Cool 11 BO2 Blank Close Cool 12 BI1 BI1 Configurable Binary Input 1 13 RS RS Remote 14 Scom Scom Sensor Common 15 BI2 BI2 Configurable Binary Input 2 16 UI3 UI3 Configurable Universal Input 3 Blank LONWORKS Bus

Connecting the LONWORKS Network The wiring rules for the LONWORKS network differ from the wiring rules for the Metasys® N2 Bus and the BACnet® MS/TP Bus. For more details on wiring the LONWORKS network, refer to the LONWORKS Network Layout Technical Bulletin (LIT-1162150).

To connect the thermostat controller to the LONWORKS network:

1. Connect the LONWORKS network wires to the LONWORKS network terminal block on the Figure 5: LON Terminal Wiring Connection thermostat controller (Figure 5). The LONWORKS network requires proper termination Note: There is no polarity when connecting the and biasing at the end of a segment (a segment is a LONWORKS network wires to the thermostat physically continuous length of wire). The thermostat controller; however, we recommend keeping the controller is not equipped with the ability to provide this polarity consistent throughout the network. termination; therefore, it cannot be located at the 2. After the LONWORKS network wires are connected physical end of a LONWORKS network segment unless to the first thermostat controller, continue in a a terminator is attached. Refer to the LONWORKS daisy-chained fashion to the next device. Network Layout Technical Bulletin (LIT-1162150) for end-of-line solutions. Note: The LONWORKS network wiring must comprise twisted-pair lines.

Do not run the LONWORKS network wiring in the same conduit as line wiring (higher than 30 VAC) or other wiring that power to highly inductive loads (such as contactors, coils, motors, or generators).

4 TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions

Separate 24 VAC Power Source for Auxiliary Output (24 VAC Maximum)

Two-Pole 24 V~ 24 V~ BO5 BO5 Hot Com Aux Aux Left Top Three-Pole Connector Right Top

Aux 24 V~ 24 V~ Connector Hot Com BO5 BO5 BO3 LON 4 5 Aux Aux LON 678 Eight-Pole Bottom Connector 24 VAC BO4/ BO1/ BO2 BI1 RS Scom BI2 UI3 Thermostat Power AO2 AO1 9 10 11 12 13 14 15 16 Aux Contact (Isolated Common) • Reheat • • On/Off Actuation • Exhaust Same 24 VAC Remote Inputs Voltage-Free Power Source for Auxiliary Output Contact (24 VAC Maximum) • Door • Remote Scom BI2 UI3 BI1 Override • Filter Alarm 24 V~ 24 V~ BO5 BO5 Hot Com Aux Aux • Service Alarm Voltage-Free Aux Voltage-Free Contact Contact • COC/NH • Remote NSB - OR - Normally Heat • Motion Closed Contact • Window = Cold Water • COC/NC Normally Cool SS (Supply Sensor) Closed Contact COS (Change Over Sensor) = Hot Water 24 VAC Thermostat Power LON LON

Supervisory

Controller FIG:tec22x7wrng

Figure 6: Wiring the TEC22x7-4 Series Thermostat Controller (See Table 1.)

TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions 5

Floating Actuator

UI3 COS 24 V~ Com Control Thermostat 24 V~ Hot

(Minimum and Maximum Position l

c

7

2

Adjusted on Actuator) BO1 Open 2

2

c

e

t

:

G

BO2 Close I

F

Figure 7: Wiring the TEC2227-4 Thermostat Controller for Floating Control (Pressure-Dependent VAV Cooling Only)

Proportional 0 to 10 Actuator VDC

UI3 COS 24 V~ Com Room Temperature Control Thermostat 24 V~ Hot

l

c

7

(Minimum and Maximum Position 4 AO1 2

2

c

e

t

Adjusted on Actuator) :

G

I

F

Figure 8: Wiring the TEC2247-4 Thermostat Controller for Proportional 0 to 10 VDC Control (Pressure-Dependent VAV Cooling Only)

Changeover Supply Air Sensor Temperature Sensor

Floating Actuator

UI3 COS 24 V~ Com

r

v

o

g

24 V~ Hot h Room Temperature Control Thermostat c _

c

h

7

(Minimum and Maximum Position BO1 Open 2

2

2

c

e

t

Adjusted on Actuator) :

BO2 Close G

I

F

Figure 9: Wiring the TEC2227-4 Thermostat Controller for Floating Control (Pressure-Dependent VAV Heating/Cooling with Changeover)

6 TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions Changeover Sensor Supply Air Temperature Sensor

Proportional Actuator 0 to 10 VDC

UI3 COS 24 V~ Com

r

v

o

g

h

24 V~ Hot c

Room Temperature Control Thermostat _

c

h

7

(Minimum and Maximum Position 4

2

AO1 2

c

e

t

Adjusted on Actuator) :

G

I

F

Figure 10: Wiring the TEC2247-4 Thermostat Controller for Proportional 0 to 10 VDC Control (Pressure-Dependent VAV Heating/Cooling with Changeover)

Heating/Cooling Supply Air Floating and On/Off Temperature Sensor Actuator Heater C 1

Changeover Sensor UI3 COS 24 V~ Com 24 V~ Hot

h

r

_

r

BO1 Open v

o

g Room Temperature Control Thermostat h c

_

BO2 Close c

h

(Minimum and Maximum Position 7

2

2

2 BO5-Aux c Adjusted on Actuator) e

t

:

G

I BO5-Aux F

Figure 11: Wiring the TEC2227-4 Thermostat Controller for Floating Control (Pressure-Dependent VAV Heating Cooling with Changeover and Reheat)

Supply Air Heating/Cooling Temperature Sensor Proportional and On/Off Actuator Duct Heater C 1

0 to 10 VDC Changeover Sensor UI3 COS 24 V~ Com 24 V~ Hot

h

r

_

r AO1 v o

g

h

c

_ Room Temperature Control Thermostat AO2 c h

7

4

(Minimum and Maximum Position 2

2

c

BO5-Aux e

t Adjusted on Actuator) : G

I BO5-Aux F

Figure 12: Wiring the TEC2247-4 Thermostat Controller for Proportional 0 to 10 VDC Control (Pressure-Dependent VAV Heating/Cooling with Changeover and Reheat)

TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions 7

UI3 COS 24 V~ Com 24 V~ Hot BO1 Open BO2 Close

r

d

Room Temperature y h

_

c

h

Control Thermostat 7

2

2

2

c

e

t

:

G

I

F

Figure 13: Wiring the TEC2227-4 Thermostat Controller for Floating Control (Heating/Cooling Hydronic Control)

UI3 COS 24 V~ Com 24 V~ Hot AO1

0 to 10 VDC

Room Temperature

r

Control Thermostat d

y

h

_

c

h

7

4

2

2

c

e

t

:

G

I

F Figure 14: Wiring the TEC2247-4 Thermostat Controller for Proportional 0 to 10 VDC Control (Heating/Cooling Hydronic Valve Control)

UI3 COS 24 V~ Com 24 V~ Hot Optional Water BO1 Open Supply Sensor BO2 Close Floating Heating/Cooling Valve

r

v

o

g

h

c

_

r

d

y

Room Temperature h

_

c

h

Control Thermostat 7 Supply Water 2

2

2

c

e Temperature Sensor t :

G

I

F

Figure 15: Wiring the TEC2227-4 Thermostat Controller for Floating Control (Heating/Cooling Hydronic Valve Control with Changeover)

8 TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions

UI3 COS 24 V~ Com 24 V~ Hot Optional Water AO1 Supply Sensor Proportional Heating/Cooling 0 to 10 VDC Valve

r

v

o

g

h

c

_

r

d

y

Room Temperature h

_

c

h

Control Thermostat 7 4

2

Supply Water 2

c

e

t

:

Temperature Sensor G I

F

Figure 16: Wiring the TEC2247-4 Thermostat Controller for Proportional 0 to 10 VDC Control (Heating/Cooling Hydronic Valve Control with Changeover)

or or 24 V~ 24 V~ or 24 V~ 24 V~ Hot Com Hot Com Cooling Valve

f

f

o

n

o

_

7

2

2

2

c

e

Heating t

:

G

I

Valve F

Two-Pipe Applications Four-Pipe Applications Figure 17: Wiring the TEC2227-4 Thermostat Controller for On/Off Control

24 V~ 24 V~ BO1 BO2 BO1 BO2 BO3 BO4 24 V~ 24 V~ Hot Com Hot Com Cooling Valve

Heating/Cooling Valve

t

l

f

7

Heating 2

2

2

c

e

t

Valve :

G

I

Two-Pipe Applications Four-Pipe Applications F Figure 18: Wiring the TEC2227-4 Thermostat Controller for Floating Control

TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions 9 24 V~ 24 V~ 24 V~ 24 V~ AO1 AO2 AO1 Hot Com Hot Com

Cooling Valve

Heating/Cooling Heating Valve Valve

p

o

r

p

7

4

2

2

c

e

t

:

G Two-Pipe Applications Four-Pipe Applications I

F Figure 19: Wiring the TEC2247-4 Thermostat Controller for Proportional Control

Setup and Adjustments

Status LED beneath cover indicates network status.

Room Temp Backlit, plain text 70.0ºF Liquid Crystal Display (LCD) is easy to read in any condition. Light-Emitting (LEDs) indicate system activity.

Three keys on the thermostat controller FIG:frnt_vw_22x7 make operation easy and intuitive. Figure 20: Front Cover of Thermostat Controller

Thermostat Controller User Interface Keys Backlit Liquid Crystal Display (LCD) The TEC22x7-4 Series Thermostat Controller user The TEC22x7-4 Series Thermostat Controllers include interface consists of three keys on the front cover a 2-line, 8-character backlit display. Low-level (Figure 20). The function of each key is as follows: backlighting is present during normal operation, and it brightens when any user interface key is pressed. The • OVERRIDE key overrides the unoccupied mode to backlight returns to low level when the thermostat occupied at the local user interface for the controller is left unattended for 45 seconds. specified TOccTime. (TOccTime is defined by selecting the appropriate time period in the Installer Light-Emitting Diodes (LEDs) Configuration Menu.) If one of the binary inputs is Two LEDs are included to call for heat or call for configured to operate as a remote override contact, cooling: this OVERRIDE function is disabled. The OVERRIDE key also allows access to the Installer • The heat LED is on when heating is on. Configuration Menu. See the Configuring the TEC22x7-4 Series Thermostat Controller section. • The cool LED is on when cooling is on. • UP/DOWN arrow keys change the configuration parameters and activate a setpoint adjustment.

10 TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions Status Display Menu Configuring the TEC22x7-4 Series Thermostat The Status Display Menu is displayed during normal Controller thermostat controller operation. This menu The TEC22x7-4 Series Thermostat Controller ships continuously scrolls through the following parameters: from the factory with default settings for all configurable • Room Temperature parameters. The default settings are shown in Table 5. To reconfigure the parameters via the thermostat • System Mode controller, follow the steps in this section. • Occupancy Status 1. To access the Installer Configuration Menu, press (Occupied/Unoccupied/Override) and hold the OVERRIDE key for approximately • Applicable Alarms (The backlight lights up as an 8 seconds. alarm condition is displayed.) Note: If the Password parameter is configured, Note: An option is available within the Installer Password 0 appears on the thermostat controller Configuration Menu to lock out the scrolling display and display indicating that the configured password is show only the Room Temperature parameter. required to proceed. Use the UP/DOWN arrow keys to indicate the configured password, then Status LED press the OVERRIDE key to proceed through the The Status LED shows the operational status of the Installer Configuration Menu parameters. thermostat controller. The Status LED is a small green 2. Once the Installer Configuration Menu begins, light under the thermostat controller cover (under the release and press the OVERRIDE key to scroll LONWORKS daughter board on the left edge when through the parameters listed in Table 5. facing the thermostat controller). 3. When the desired parameter is displayed, use the Table 2: Status LED Explanation UP/DOWN arrow keys to choose the desired Status LED Explanation selection option. Condition 4. Press and release the OVERRIDE key to continue Continuously On The thermostat controller does not scrolling through the parameters. have an application loaded in its memory. When the thermostat controller is in the Installer Flashing at a The thermostat controller has an Configuration Menu and left unattended for 0.5 Hz rate application loaded in its memory but approximately 8 seconds, the thermostat controller is not configured. Use a LONWORKS reverts to the Status Display Menu. network management tool to bind the thermostat controller to a LONWORKS For additional information on commissioning and network. configuring thermostat controllers, adding a thermostat Continuously Off The thermostat controller has an controller to the Network Automation Engine (NAE), application loaded in its memory and thermostat controller mapping, and remote thermostat is bound to a LONWORKS network. controller commanding, refer to the TEC22x7-4 Series LONWORKS Network Thermostat Controllers with Two Outputs Configuration Technical Bulletin (LIT-12011612). Configuring the Thermostat Controller’s Neuron® Identification Press and hold the UP/DOWN arrow keys simultaneously for five seconds to broadcast the thermostat controller’s Neuron Identification on the LONWORKS network. If the cover is removed, you can see the green Status LED under the LONWORKS board flash when the thermostat controller broadcasts the Neuron ID. The Neuron ID is on a label on the Echelon® chip. You cannot send the Neuron ID while in the Installer Configuration menu.

TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions 11 Configuring Inputs BI1, BI2, and UI3 Configuring Sequence of Operation: SeqOpera When BI1 and BI2 are configured for an alarm Choose the appropriate sequence of operation. The condition, an alarm condition is displayed locally when modes presented to the user are dependent on the the input is closed. An alarm message is included on sequence of operation selected. For heat/cool the scrolling Status Display Menu and when the operation from the same output utilizing a changeover message is displayed, the backlight momentarily sensor (COS), choosing 0 = Cooling Only causes lights up. changeover to occur between Cooling Only and Heating Only. Choosing 2 = Cooling with Reheat The UI3 input provides changeover of hot/cold water causes changeover to occur between Cooling with switching, or supply air temperature monitoring at the Reheat and Heating with Reheat. For example thermostat controller. Each input can be configured to sequences of operation, see Figure 21 through the Selection Options included in Table 5. Figure 26. Configuring Output Options: Out1Conf For applications enabling heat/cool operation from the same output, choose Out1Conf = 2.0. For applications enabling heat/cool operation from different outputs, choose Out1Conf = 4.0. Table 3: Control Sequences for Single-Control Output Applications Sequence Control Curves System Parameter: Out1Conf = 2.01 Control = On/Off Control = Floating Control = Proportional 0 = Cooling Only See Figure 21. #10 NO Cool #10 Open Cool #10 Proportional Cool #11 NC Cool #11 Close Cool 1 = Heating Only See Figure 22. #10 NO Heat #10 Open Heat #10 Proportional Heat #11 NC Heat #11 Close Heat 2 = Cooling with See Figure 23. #6 & #7 Reheat #6 & #7 Reheat #6 & #7 Reheat Reheat #10 NO Cool #10 Open Cool #10 Proportional Cool #11 NC Cool #11 Close Cool 3 = Heating with See Figure 24. #6 & #7 Reheat #6 & #7 Reheat #6 & #7 Reheat Reheat #10 NO Heat #10 Open Heat #10 Proportional Heat #11 NC Heat #11 Close Heat

1. Numbers 6, 7, 10, and 11 in the System Parameter columns are terminal block numbers, which are described in Table 1.

Table 4: Control Sequences for Two-Control Output Applications Sequence Control Curves System Parameter: Out1Conf = 4.0 Control = On/Off Control = Floating Control = Proportional 0 = Cooling Only See Figure 21. #10 NO Cool #10 Open Cool #10 Proportional Cool #11 NC Cool #11 Close Coo

12 TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions Table 4: Control Sequences for Two-Control Output Applications Sequence Control Curves System Parameter: Out1Conf = 4.0 Control = On/Off Control = Floating Control = Proportional 1 = Heating Only See Figure 22. #10 NO Heat #10 Open Heat #10 Proportional Heat #11 NC Heat #11 Close Heat 2 = Cooling with See Figure 23. #6 & #7 Reheat #6 & #7 Reheat #6 & #7 Reheat Reheat #10 NO Cool #10 Open Cool #10 Proportional Cool #11 NC Cool #11 Close Cool 3 = Heating with See Figure 24. #6 & #7 Reheat #6 & #7 Reheat #6 & #7 Reheat Reheat #8 NO Heat #8 Open Heat #9 Proportional Heat #9 NC Heat #9 Close Heat 4 = Heating/Cooling See Figure 25. #8 NO Heat #8 Open Heat #9 Analog Heat #9 NC Heat #9 Close Heat #10 Proportional Cool #10 NO Cool #10 Open Cool #11 NC Cool #11 Close Cool 5 = Heating/Cooling See Figure 26. #6 & #7 Reheat #6 & #7 Reheat #6 & #7 Reheat with Reheat #8 NO Heat #8 Open Heat #9 Proportional Heat #9 NC Heat #9 Close Heat #10 Proportional Cool #10 NO Cool #10 Open Cool #11 NC Cool #11 Close Cool

TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions 13 On

y

l

t

n

h

_

l r

c

_

: Cooling Setpoint t

h

G

:

I

G

F

I On Reheat Off F

Device Opened 100%

On/Off, Floating, Off or Proportional Device Closed Output On/Off, Floating, or Proportional Temperature Increase Output ( Increments of 1Foo /0.5C ) 0%

Figure 21: Cooling Only Temperature Increase ( Increments of 1Foo /0.5C )

y

l

n

_ t Figure 24: Heating with Reheat

h

:

G

I Heating Setpoint F On/Off, Floating, Heating Output Device Opened or Proportional Outputs Cooling Output

On/Off, Floating, or Proportional Device Closed Output Heating Setpoint Cooling Setpoint Deadband Temperature Increase Device Device ( Increments of 1Foo /0.5C ) Opened Opened

Figure 22: Heating Only Device Device Closed Closed

t

h

r

On/Off, Floating, Heating Output _ l

c

:

G

or Proportional I Temperature Increase

F

Outputs Cooling Output (Increments of 1F°/0.5C°) FIG:htng_clng Figure 25: Heating/Cooling Heating Setpoint Cooling Setpoint

Deadband On Device Opened On Off On/Off, Floating, Device or Proportional Off Closed Output

Temperature Increase ( Increments of 1Foo /0.5C ) Figure 23: Cooling with Reheat

14 TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions

On/Off, Floating, t

Heating Output h

r

_

t

h

or Proportional l

c Cooling output :

G

I

Outputs F

Heating Setpoint On Cooling Setpoint

Reheat Deadband On Off Device Output Device Opened Opened Off

Device Device Closed Closed

Temperature Increase ( Increments of 1Foo /0.5C ) Figure 26: Heating/Cooling with Reheat

Table 5: Installer Configuration Menu (Part 1 of 6) Parameter Description and Default Selection Options Appearing on Display Pswrd Sets the protective access Range: 0 to 1,000 password to prevent unauthorized access to the Installer Configuration Menu. Default: 0 Note: The default setting does not lock out access to the Installer Configuration Menu. BI1 Configuration of Binary Input 1. (None): No function is associated with an input. Default: None (Rem NSB): Remote Night Setback (NSB) via a time input, an occupancy sensor, or from a voltage-free contact. Contact open = Occupied; contact closed = Unoccupied. (MotionNO*): Temporary occupancy request via a motion detector input. Contact open = Unoccupied. When the contact closes, the thermostat controller goes into the occupied mode for a specified TOccTime. Once the TOccTime begins, the thermostat controller remains in the occupied mode if the contact is open, until the TOccTime expires. (MotionNC*): Temporary occupancy request via a motion detector input. Contact closed = Unoccupied. When the contact opens, the thermostat controller goes into the occupied mode for a specified TOccTime. Once the TOccTime begins, the thermostat controller remains in the occupied mode if the contact is closed, until the TOccTime expires. (Window**): Cancels the thermostat controller heating or cooling action when a window is open. A Window alarm is displayed indicating that the window needs to be closed to resume heating or cooling. * These settings disable any local override function.

TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions 15 Table 5: Installer Configuration Menu (Part 2 of 6) Parameter Description and Default Selection Options Appearing on Display BI2 Configuration of Binary Input 2. (None): No function is associated with an input. Default: None (Door Dry): Door contact only has an effect if BI1 is set to MotionNO or MotionNC. (See the BI1 parameter in this table.) The occupancy is now dictated via BI1 and BI2. Any motion detected sets the zone to Occupied status. The zone remains permanently in occupied mode until the door contact opens momentarily. The thermostat controller then enters stand-by mode. If more movements are detected, the occupied mode resumes. While the door is opened, any movements detected by the remote PIR sensor or the PIR accessory cover are ignored. Use a Normally Closed contact switching device. Contact opened = Door opened, Contact closed = Door closed. (RemOVR): Temporary occupancy request via a remote input. This override function is controlled by a manual remote occupancy override. When enabled, this condition disables the override capability of the thermostat controller. (Filter): A Filter alarm is displayed. This alarm can be connected to a differential pressure switch that monitors a filter. (Service): A Service alarm is displayed on the thermostat controller when the input is energized. This input can be tied into the unit control card, which provides an alarm should there be a malfunction. UI3 Configuration of Universal Input 3. (None): No function is associated with an input. Default: None (COC/NH): Changeover Contact/Normally Heat: A input is used to signal seasonal hot/cold water changeover. The contact closes when cold water is present. Valid only for two-pipe systems. (COC/NC): Changeover Contact/Normally Cool: A dry contact input is used to signal seasonal hot/cold water changeover. The contact closes when hot water is present. Valid only for two-pipe systems. (COS): Changeover Analog Sensor: Used for hot/cold water changeover switching. Valid only for two-pipe systems. Note: Choose the selection option (0): Cooling Only for the SeqOpera parameter to allow changeover to occur between Cooling Only and Heating Only. Choose the selection option (2): Cooling and Reheat to allow changeover to occur between Cooling and Reheat and Heating and Reheat. (SS): Supply Air Sensor Monitoring MenuScro Gives the option of having the (on): The scroll is active. display continuously scroll the (off): The scroll is inactive. parameters. Default: on C or F Provides temperature scale options (°F): Fahrenheit scale for display. (°C): Celsius scale Default: °F

16 TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions Table 5: Installer Configuration Menu (Part 3 of 6) Parameter Description and Default Selection Options Appearing on Display Lockout Selectable Lockout Levels for Lockout Function limiting end user keypad interaction. Level Unoccupied Override Occupied Temperature Default: 0 Setpoints (0) Access Access (1) No Access Access (2*) This lockout level is not used. (3*) This lockout level is not used. (4) Access No Access (5) No Access No Access *If lockout level (2) or (3) is selected, the lockout functions like lockout level (0) or (1), respectively. Out1Conf Defines the type of operation (2.0): Limits the number of sequences of operation available needed for Output 1. from 0 to 3, and enables heat/cool operation from the same output. Default: 4.0 (4.0): Allows access to all sequences of operation from 0 to 5, and enables heat/cool operation from different outputs. CntrlTyp Defines the control output for the (On/Off): For Normally Open (N.O.) or Normally Closed (N.C.) type of valves used in the 24 VAC two-position valves. installation (TEC2227-4 model). (Floating): For proportional three-wire control of 24 VAC floating Default: Floating valves. SeqOpera Determines the sequence of (0): Cooling Only (Off-Cool). The default is Cool. operation. (1): Heating Only (Off-Heat). The default is Heat. Default: 1 (2): Cooling and Reheat (Off-Auto-Heat-Cool). The default is Auto. (3): Heating and Reheat (Off-Heat). The default is Heat. (4*): Cool/Heat Four-Pipe (Off-Auto-Heat-Cool). The default is Auto. (5*): Cool/Heat Four-Pipe and Reheat (Off-Auto-Heat-Cool). The default is Auto. * Selection option (4.0) for Out1Conf only. (See Out1Conf parameter in this table.) Note: Choose the selection option (0): Cooling Only when using a changeover sensor to allow changeover to occur between Cooling Only and Heating Only. Choose the selection option (2): Cooling and Reheat when using a changeover sensor to allow changeover to occur between Cooling and Reheat and Heating and Reheat. St-By TM Sets the Stand-By timer value Time delay between the moment the PIR cover detected the last (PIR models). movement in the area and the time at which the thermostat Default: 0.5 hours controller Stand-By mode and setpoints become active. Range: 0.5 to 24.0 hrs adjustable in 0.5-hour increments Unocc TM Sets the Unoccupied timer value Time delay between the moment the thermostat controller toggled to (PIR models). Stand-By mode and the time at which the thermostat controller Default: 0.0 hours Unoccupied mode and setpoints become active. Setting this parameter to the factory value (0.0 hours) disables the Unoccupied timer. This prevents the thermostat controller from switching from Stand-By mode to Unoccupied mode when PIR functions are used. Range: 0.0 to 24.0 hrs adjustable in 0.5-hour increments

TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions 17 Table 5: Installer Configuration Menu (Part 4 of 6) Parameter Description and Default Selection Options Appearing on Display St-By HT Sets Stand-by heating setpoint; Range: 40.0°F/4.5°C to Note: When adjusting the value is between occupied and 90.0°F/32.0°C temperature, press the unoccupied heating setpoints. UP/DOWN arrow keys to Default: 69.0°F/20.6°C change the temperature in 0.5F°/0.5C° increments; St-By CL Sets Stand-by cooling setpoint limit; Range: 54.0°F/12.0°C to press and hold the value is between occupied and 100.0°F/37.5°C UP/DOWN arrow keys unoccupied cooling setpoints. to change the temperature Default: 78.0°F/25.6°C in 5.0F°/5.0C° increments. Unocc HT Sets the Unoccupied Heating Range: 40.0°F/4.5°C to setpoint value. 90.0°F/32.0°C Default: 62.0°F/16.5°C Unocc CL Sets the Unoccupied Cooling Range: 54.0°F/12.0°C to setpoint value. 100.0°F/37.5°C Default: 80.0°F/26.5°C Heat max Sets the Occupied and Unoccupied Range: 40.0°F/4.5°C to maximum Heating setpoint values. 90.0°F/32.0°C Default: 90.0°F/32.0°C Cool min Sets the Occupied and Unoccupied Range: 54.0°F/12.0°C to minimum Cooling setpoint values. 100.0°F/37.5°C Default: 54.0°F/12.0°C Pband Proportional Band used by the PI Value F Scale Pband/C Scale Pband temperature control loop of the 3 3.0F°/1.7C° thermostat controller. Pband is not converted with C or F 4 4.0F°/2.2C° scale and is always shown with a 5 5.0F°/2.8C° range of 3 to 10. Default: 3 (3F°/1.7C°) 6 6.0F°/3.3C° 7 7.0F°/3.9C° 8 8.0F°/4.4C° 9 9.0F°/5.0C° 10 10.0F°/5.6C° Note: The use of a larger proportional band is not to use the thermostat controller as a discharge air controller device. The use of a larger proportional band can be used to solve issues for flawed HVAC design with basic sizing and thermostat controller location errors that cannot be worked around. Set type Provides the option of temporarily (temporar): Local changes to the heating or cooling setpoints are changing the heating or cooling temporary, and remain effective for the specified TOccTime. setpoint by pressing the UP/DOWN (permnent): Local changes to the heating or cooling setpoints are arrow keys. permanently stored in the thermostat controller memory. Default: permnent TOccTime Sets the duration of the Temporary Range: 0.0 to 24.0 hrs in 1-hour increments Occupancy Time when the heating or cooling setpoints in the Occupied mode are established by: • an Override Function enabled in the Main User Menu (when the thermostat controller is in the Unoccupied mode) • a temporary heating or cooling setpoint Default: 2.0 hrs

18 TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions Table 5: Installer Configuration Menu (Part 5 of 6) Parameter Description and Default Selection Options Appearing on Display Deadband Sets the minimum deadband Range: 2.0F°/1.0C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C° between the heating and cooling increments) setpoints. Default: 2.0F°/1.0C° Cal RS Sets the desired room air sensor Range: -5.0F°/-2.5C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C° calibration (offset). The offset can increments) be added to or subtracted from the actual displayed room temperature. Default: 0.0F°/0.0C° Aux Contact Determines the auxiliary contact (0) Not used, If the Sequence of Operation is set to function and configuration. or used for reheat (SeqOpera = 2, 3, or 5), ignore this Default: 0 reheat parameter. (1) Auxiliary Occupied = contact The output N.O. closed aligns with Unoccupied = contact occupancy. open (2) Auxiliary Occupied = contact open N.C. Unoccupied = contact closed (3) This selection option is not used. (4) This selection option is not used. (5) Auxiliary On/Off control through the The output auxiliary network command. The output aligns with can be commanded through the network the for any required auxiliary functions via a secondary separate and dedicated network network variable. occupancy command. Note: If this NVI is used to remotely command the Auxiliary Output BO5), then the Auxiliary Output must be configured to a value of 5 for this function to operate. FL time Sets the maximum actuator Range: 0.5 to 9.0 min (adjustable in 0.5 minute increments) timing (floating ContrlTyp TEC2227-4 model). Default: 1.5 min Cph Sets the maximum number of cycles Range: 3 to 8 cycles per hour per hour (on/off CntrlTyp TEC2227-4 model). Default: 4 RA/DA Choice of direct or reverse acting (DA): Direct Acting, 0 to 100% = 0 to 10 VDC analog output signal (TEC2247-4 (RA): Reverse Acting, 0 to 100% = -10 to 0 VDC model). Default: DA Reheat Sets the duty cycle time for reheat (0): 15 minutes (four cycles per hour), for various equipment with output (if Option 2, 3, or 5 is chosen mechanical relays or contactors controlling mechanical reheat in the SeqOpera parameter). systems. Default: 0 (1): 10 seconds (six cycles per minute), for various equipment with solid-state relays that withstand short duty cycles such as electric heat.

TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions 19 Table 5: Installer Configuration Menu (Part 6 of 6) Parameter Description and Default Selection Options Appearing on Display UI3 dis Displays the supply or changeover Used as a diagnostic/service help, to troubleshoot and diagnose temperature when UI3 is configured sensor operation. as an analog input (SS or COS). Used as a diagnostic/service help, to troubleshoot and diagnose sensor operation. Default: -40°F/-40°C

Troubleshooting Repairs and Replacement See Table 7 for display messaging and Table 8 for If the TEC22x7-4 Series Thermostat Controller fails to troubleshooting details. operate within its specifications, replace the unit. For a replacement thermostat controller, contact the nearest Accessories representative. All the accessories in Table 6 include mounting hardware; contact the nearest Johnson Controls® representative to order any of these parts. Note: Review the technical specifications of the optional accessories prior to their use in an application. Table 6: Accessories (Order Separately) Code Number Description TEC-7-PIR1 Zone Controller Cover with Occupancy Sensor SEN-600-1 Remote Indoor Air Temperature Sensor SEN-600-4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED TE-6361M-12 Duct Mount Air Temperature Sensor TE-636S-1 Strap-Mount Temperature Sensor

1. The TEC-7-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC22x7-4 Thermostat Controller to provide occupancy sensing capability. 2. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II are available; refer to the TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.

Table 7: Alarm Messages Display Function Service Indicates that there is a service alarm in accordance with the programmable Binary Input (BI2). Filter Indicates that the filter(s) is dirty in accordance with the programmable Binary Input (BI2). Window Indicates that an outside window or door is open and has cancelled the thermostat controller heating or cooling action in accordance with the programmable Binary Input (BI1).

20 TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions Table 8: Troubleshooting Details Symptom Probable Causes Multiple Symptoms Excessive bus errors may be occurring. A device may have been added or changed with a duplicate address (may not be the same address as some devices having problems, and may have happened sometime before the problem was noticed). Wiring errors or wire problems may exist. A download may be in progress. There may be a fault at a device. A repeater may be needed or may be configured incorrectly. Poor Performance See the probable causes listed previously in the Multiple Symptoms section of this table. Excessive bus traffic may exist (bus overload). There may be too many devices on the network. There may be unaccounted devices on the network (not mapped to the NAE). There may be unusually slow devices on the network or devices that are slow to respond. Thermostat See the probable causes listed previously in the Multiple Symptoms section of this table. Controller Goes A power failure or other failure may have occurred at the thermostat controller. Offline Communication may have been disabled at the thermostat controller. Thermostat See the probable causes listed previously in the Multiple Symptoms section of this table. Controller Does Not A thermostat controller may be connected to the wrong bus. Come Online

TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions 21 Technical Specifications TEC22x7-4 Series LONWORKS Network Thermostat Controllers with Two Outputs Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or Safety Extra-Low Voltage (SELV) Triac Output On/Off and 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush Rating (BO1, Floating BO2, BO3, Control BO4) Analog Proportional 0 to 10 VDC into 2k ohm Resistance (Minimum) Output Rating Control Auxiliary Triac Output 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush Output Rating Analog Inputs Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative Temperature Coefficient (NTC) Thermistor Sensors Binary Inputs Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3 Wire Size Unshielded twisted pair - 22 AWG (0.6 mm Diameter) Minimum, 18 AWG (1.0 mm Diameter) Recommended LONWORKS Network Standard 64 Devices Maximum without a Repeater, 127 Devices Maximum with a Repeater; 6,250 ft (1,905 m) Maximum (Bus Topology) Thermostat Controller -40.0°F/-40.0°C to 122.0°F/50.0°C Measurement Range Sensor Type Local 10k ohm NTC Thermistor Resolution ±0.2F°/±0.1C° Control Accuracy ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated Setpoint Heating 40.0°F/4.5°C to 90.0°F/32.0°C in 0.5° Increments Range Cooling 54.0°F/12.0°C to 100.0°F/38.0°C in 0.5° Increments Minimum Deadband 2F°/1C° between Heating and Cooling Ambient Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing Conditions Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing Compliance United States UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating Equipment LONMARK® Certification 3.4 FCC Compliant to CFR 47, Part 15, Subpart B, Class A Canada UL Listed, File E27734, CCN XAPX7, Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment Industry Canada, ICES-003 Europe CE Mark, EMC Directive 2004/108/EC Australia and C-Tick Mark, Australia/NZ Emissions Compliant New Zealand Shipping Weight 0.75 lb (0.34 kg)

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

Building Efficiency 507 E. Michigan Street, Milwaukee, WI 53202 Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc. All other marks herein are the marks of their respective owners. © 2010 Johnson Controls, Inc.

22 TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Installation Instructions

Published in U.S.A. www.johnsoncontrols.com