<<

TEC2245-4 LONWORKS® Network Controller with Single Proportional Output and One-Speed Part No. 24-9890-1257, Rev. — Control Issued February 8, 2010 Installation Instructions

Applications North American Emissions Compliance The TEC2245-4 Thermostat Controller is a United States LONWORKS® network device that provides control of two-pipe fan coils, cabinet unit heaters, or other This equipment has been tested and found to equipment using a proportional 0 to 10 VDC control comply with the limits for a Class A digital device input and one-speed fan control. pursuant to Part 15 of the FCC Rules. These limits The technologically advanced TEC2245-4 Thermostat are designed to provide reasonable protection Controller features a Building against harmful interference when this equipment is operated in a commercial environment. This System (BAS) LONWORKS network communication equipment generates, uses, and can radiate radio capability that enables remote monitoring and frequency energy and, if not installed and used in programming for efficient space control. accordance with the instruction manual, may cause The TEC2245-4 Thermostat Controller features an harmful interference to radio communications. intuitive User Interface (UI) with backlit display that Operation of this equipment in a residential area is makes setup and operation quick and easy. The likely to cause harmful interference, in which case thermostat controller also employs a unique, the user will be required to correct the interference proportional control algorithm that virtually eliminates at his/her own expense. temperature offset associated with traditional, differential-based thermostat controllers. Canada

IMPORTANT: The TEC2245-4 Thermostat This Class (A) digital apparatus meets all the Controller is intended to provide an input to requirements of the Canadian Interference-Causing equipment under normal operating conditions. Equipment Regulations. Where failure or malfunction of the thermostat Cet appareil numérique de la Classe (A) respecte controller could lead to personal injury or property toutes les exigences du Règlement sur le matériel damage to the controlled equipment or other brouilleur du Canada. property, additional precautions must be designed into the . Incorporate and maintain Installation other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or Location Considerations protect against failure or malfunction of the Locate the TEC2245-4 Thermostat Controller: thermostat controller. • on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature • away from direct sunlight, radiant , outside walls, behind doors, air discharge grills, stairwells, or outside doors • away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference Note: Allow for vertical air circulation to the TEC2245-4 Thermostat Controller.

TEC2245-4 LONWORKS® Network Thermostat Controller with Single Proportional 1 Output and One-Speed Fan Control Installation Instructions To install the thermostat controller: 4. Pull approximately 6 in. (152 mm) of from the wall and insert the wire through the hole in the 1. Use a Phillips-head screwdriver to remove the thermostat controller mounting base. security screw on the bottom of the thermostat controller cover. 5. Align the thermostat controller mounting base on the wall and use the base as a template to mark Note: Normally, the security screw is packaged the two mounting hole locations. separately in a plastic bag with the thermostat controller. Skip this step if the screw is not installed 6. Position the thermostat controller mounting base on the bottom of the cover. so that the arrow on the base points upward to indicate the top of the thermostat controller. 2. Pull the bottom edge of the thermostat controller cover and open the thermostat controller as Note: If you need to install the thermostat on an illustrated in Figure 1. electrical junction box, use 2-1/2 x 4 in. (63 x 101 mm) square boxes with mud ring covers, and avoid smaller 1-1/2 x 4 in. (38 x 101 mm) or 3 x 2 in. (76 x 51 mm) square boxes. This procedure ensures that you have enough space for cabling and end-of-line devices, if needed. Note: For surface-mount applications, use durable mounting hardware such as Molly bolt anchors that cannot be easily pulled out of the mounting surface. 7. Secure the base to the wall surface using two mounting screws as illustrated in Figure 3. Note: Be careful not to overtighten the mounting screws. FIG:cvr_rmvl

Figure 1: Removing the Thermostat Controller Cover

3. Carefully pull the locking tabs on the right side of the thermostat controller mounting base and unlock the (PCB). Open the PCB to the left as illustrated in Figure 2. FIG:mtgbs

Figure 3: Securing the Thermostat Controller Mounting Base to the Wall PCB Locking Tabs 8. Swing the PCB back to the right and carefully snap it into the locking tabs on the thermostat controller mounting base. 9. Remove the screw terminal blocks that are attached to a disposable adhesive. Figure 4 FIG:prnctbd Figure 2: Opening the Thermostat Controller PCB illustrates the locations of the screw terminal blocks on the thermostat controller.

2 TEC2245-4 LONWORKS® Network Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions To wire the thermostat controller: 1. Strip the ends of each wire 1/4 in. (6 mm) and connect them to the appropriate screw terminals as indicated in Table 1, and Figure 5 and Figure 6.

Note: For more details on wiring the LONWORKS network, refer to the LONWORKS Network Layout Technical Bulletin (LIT-1162150). 2. Carefully push any excess wire back into the wall. Note: Seal the hole in the wall with fireproof

s material to prevent drafts from affecting the

k

c

l

b

_

l

n ambient temperature readings.

m

r

t

:

G

I F 3. Reinsert the screw terminal blocks onto the PCB.

Figure 4: Removing the Screw Terminal Blocks 4. Reattach the LONWORKS communication to the LON terminal block. Wiring Note: If inserting multiple wires into the terminals, be sure to properly twist wires together prior to CAUTION: Risk of Electric Shock. inserting them in the terminal connectors. Disconnect the power supply before ! making electrical connections to avoid 5. Reattach the thermostat controller cover to the electric shock. mounting base (top side first). 6. Use a Phillips-head screwdriver to reinstall the CAUTION: Risk of Property Damage. security screw on the bottom of the thermostat Do not apply power to the system before controller cover. ! checking all wiring connections. Short circuited or improperly connected wires Three-Pole Two-Pole may result in permanent damage to the Left Top Connector Right Top Connector equipment. 24 V~ 24 V~ BO5 BO5 Fan Hot Com Aux Aux IMPORTANT: Make all wiring connections in 6 7 8 accordance with local, national, and regional 3 4 5

s

regulations. Do not exceed the electrical ratings of k

l

b

_

LON m r

t

the TEC2245-4 Thermostat Controller. :

G

I

F When replacing an existing thermostat controller, LON Six-Pole Bottom Connector remove and label the wires to identify the terminal functions. AO1 BI1 RS Scom BI2 UI3 When replacing a TEC2245-4 Thermostat Controller, remove the old screw terminal blocks and reinsert them 10 12 13 14 15 16 onto the PCB of the replacement thermostat controller. Figure 5: Terminal Blocks The LON connection does not have a removable terminal block. It has two screw terminals, one for each of the two LON wires.

TEC2245-4 LONWORKS® Network Thermostat Controller with Single Proportional Output and One-Speed 3 Fan Control Installation Instructions

Table 1: Terminal Identification PCB Terminal Label Terminal Block Label Function 1 Not used N/A 2 Not used N/A 3 Fan Fan 4 24V~ Hot 24 VAC from 5 24V~ Common 24 VAC Common from Transformer 6 BO5-Aux BO5 Auxiliary Output 7 BO5-Aux BO5 Auxiliary Output 8 N/A N/A 9 Not used N/A 10 AO1 Cool 11 Not used N/A 12 BI1 Configurable Binary Input 1 13 RS Remote 14 Scom Sensor Common 15 BI2 Configurable Binary Input 2 16 UI3 COS/COC/SS Not labeled N/A LON Network

4 TEC2245-4 LONWORKS® Network Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions Aux Contact (Isolated Common) -Free • Reheat Contact • • Door • On/Off Actuation • Remote BI1 Scom BI2 UI3 • Exhaust Fan Override • Filter Alarm Power and Fan • Service Alarm Analog 24 V~ 24 V~ Fan BO5 BO5 Voltage-Free AO1 Hot Com Output Aux Aux Voltage-Free Contact and Contact • COC/NH Aux Fan • Remote NSB - OR - Normally Heat 0 to 10 VDC Load • Motion Closed Contact 24 VAC • Window = Cold Water Com • COC/NC Normally Cool SS (Supply Sensor) Closed Contact COS (Change Over Sensor) = Hot Water 24 VAC Thermostat Power

Separate 24 VAC Power Source for Auxiliary Output (24 VAC Maximum) Remote Inputs

Aux Contact (Isolated Common) • Reheat • Lighting LON • On/Off Actuation Supervisory • Exhaust Fan Controller LON Power and Fan

Analog 24 V~ 24 V~ Fan BO5 BO5 AO1 Hot Com Output Aux Aux LWON ORKS LWON ORKS and Valve Network Wires Aux Network Fan Terminal Block 0 to 10 VDC Load 24 VAC Com Twist wires together before inserting them into the terminals. 24 VAC Thermostat Power

Same 24 VAC Power Source for Auxiliary Output (24 VAC Maximum) Thermostat-to-Network Connection FIG:2245wiring Figure 6: Wiring the TEC2245-4 Thermostat Controller

TEC2245-4 LONWORKS® Network Thermostat Controller with Single Proportional Output and One-Speed 5 Fan Control Installation Instructions Connecting the LONWORKS Network 2. After the LONWORKS network wires are connected The wiring rules for the LONWORKS network differ from to the first thermostat controller, continue in a the wiring rules for the Metasys® N2 Bus and the daisy-chained fashion to the next device. BACnet® MSTP Bus. For more details on wiring the Note: The LONWORKS network wiring must be LONWORKS network, refer to the LONWORKS Network twisted-pair lines. Layout Technical Bulletin (LIT-1162150). Do not run the LONWORKS network wiring in the same To connect the thermostat controller to the LONWORKS conduit as line voltage wiring (30 VAC or above) or network: other wiring that power to highly inductive 1. Connect the LONWORKS network wires to the loads (such as contactors, coils, motors, or LONWORKS network terminal block on the generators). thermostat controller (Figure 6). The LONWORKS network requires proper termination Note: There is no polarity when connecting the and biasing at the end of a segment (a segment is a LONWORKS network wires to the thermostat physically continuous length of wire). The thermostat controller; however, we recommend keeping the controller is not equipped with the ability to provide this polarity consistent throughout the network. termination; therefore, it cannot be located at the physical end of a LONWORKS network segment unless a terminator is attached. Refer to LONWORKS Network Layout Technical Bulletin (LIT-1162150) for end-of-line solutions. Setup and Adjustments

Status LED beneath cover indicates network status.

Backlit, plain text Liquid Crystal Display (LCD) is easy to read in any condition.

Room Temp 70.0ºF Light-Emitting (LEDs) indicate system activity.

Five keys on the thermostat controller make operation easy and intuitive. FIG:TEC2245_frntvw Figure 7: Front Cover of Thermostat Controller

Thermostat Controller User Interface Keys • OVERRIDE key overrides the unoccupied mode to The TEC2245-4 Thermostat Controller UI consists of occupied at the local user interface for the five keys on the front cover (Figure 7). The function of specified TOccTime. (TOccTime is defined by each key is as follows: selecting the appropriate time period in the Installer Configuration Menu.) If one of the binary inputs is • MODE key toggles among the system modes configured to operate as a remote override contact, available, as defined by selecting the appropriate this OVERRIDE function is disabled. The operation sequence in the Installer Configuration OVERRIDE key also allows access to the Installer Menu (Off, Heat, Cool, Auto). Configuration Menu. See the Configuring the • FAN key toggles between ON and AUTO for fan TEC2245-4 Thermostat Controller section. control. ON energizes the fan constantly and • UP/DOWN arrow keys change the Configuration AUTO operates the fan only on a call for heating or parameters and activate a setpoint adjustment. cooling, for both occupied and unoccupied periods.

6 TEC2245-4 LONWORKS® Network Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions Backlit Liquid Crystal Display LCD Configuring the TEC2245-4 Thermostat The TEC2245-4 Thermostat Controller includes a Controller 2-line, 8-character backlit display. Low-level The TEC2245-4 Thermostat Controller ships from the backlighting is present during normal operation, and it factory with default settings for all configurable brightens when any user interface key is pressed. The parameters. The default settings are shown in Table 4. backlight returns to low level when the thermostat To reconfigure the parameters via the thermostat controller is left unattended for 45 seconds. controller, follow the steps in this section. Light-Emitting Diodes (LEDs) 1. To access the Installer Configuration Menu, press Three LEDs are included to indicate the fan status, call and hold the OVERRIDE key for approximately for heat, or call for cooling: 8 seconds. Note: If the Password parameter is configured, • The fan LED is on when the fan is on. Password 0 appears on the thermostat controller display indicating that the configured password is • The heat LED is on when heating is on. required to proceed. Use the UP/DOWN arrow keys to indicate the configured password, then • The cool LED is on when cooling is on. press the MODE key to proceed through the Installer Configuration Menu parameters. Status Display Menu 2. Once the Installer Configuration Menu begins, The Status Display Menu is displayed during normal press and release the OVERRIDE key to scroll thermostat controller operation. This menu through the parameters listed in Table 4. continuously scrolls through the following parameters: 3. When the desired parameter is displayed, use the • UP/DOWN arrow keys to choose the desired • System Mode selection option. • Occupancy Status (Occupied/Unoccupied/ 4. Press and release the OVERRIDE key to continue Override) scrolling through the parameters. • Applicable Alarms (The backlight lights up as an Note: Pressing the FAN key during configuration alarm condition is displayed.) restarts the list of displayed parameters at the first parameter listed in Table 4. Note: An option is available within the Installer Configuration Menu to lock out the scrolling display and When the thermostat controller is in the Installer show only the Room Temperature parameter. Configuration Menu and left unattended for approximately 8 seconds, the thermostat controller Status LED reverts to the Status Display Menu. The status LED shows the operational status of the For additional information on commissioning and thermostat controller. See Table 2. The Status LED is a configuring thermostat controllers, adding thermostat small green light under the thermostat controller cover controllers to a Network Automation Engine (NAE), (under the LONWORKS daughter board on the left edge thermostat controller mapping, and remote thermostat when facing the thermostat controller). commanding, refer to the TEC2245-4 LONWORKS® Table 2: Status LED Explanation Network Thermostat Controller with Single Proportional Status LED Explanation Output and One-Speed Fan Control Technical Bulletin Condition (LIT-12011613). Continuously The thermostat controller does not have Configuring the Thermostat Controller’s Neuron® On an application loaded in its memory. Identification Flashing at a The thermostat controller has an Press and hold the UP/DOWN arrow keys 0.5 Hz Rate application loaded in its memory but is simultaneously for 5 seconds to broadcast the not configured. Use a LONWORKS network management tool to bind the thermostat controller’s Neuron Identification on the thermostat controller to a LONWORKS LONWORKS network. network. If the cover is removed, you can see a green LED Continuously The thermostat controller has an under the LON board flash when the thermostat Off application loaded in its memory and is controller broadcasts the Neuron ID. The Neuron ID is bound to a LONWORKS network. on a label on the Echelon® chip.

TEC2245-4 LONWORKS® Network Thermostat Controller with Single Proportional Output and One-Speed 7 Fan Control Installation Instructions You cannot send the Neuron ID while in the Installer Each input can be configured to the Selection Options Configuration menu. included in Table 4. Configuring Inputs BI1, BI2, and UI3 Configuring the Sequence of Operation When BI1 and BI2 are configured for an alarm (SeqOpera) condition, an alarm condition is displayed locally when Choose the appropriate sequence of operation. See the input is closed. An alarm message is included on Table 3, and Figure 8 through Figure 11. the scrolling Status Display Menu and when the message is displayed, the backlight momentarily Note: The modes presented to the user are lights up. dependent upon the sequence of operation selected. For 2-pipe applications using a Change Over Sensor The UI3 input provides changeover of hot/cold water (COS), choose 0 = Cooling Only. Changeover occurs switching, or supply air temperature monitoring at the between Cooling Only and Heating Only. thermostat controller. Table 3: Selection Options for Sequence of Operation Selection Option Control Curve Terminal Numbers Used (See Table 1 and Figure 6) 0: Cooling Only See Figure 8. 10: Proportional Cooling 1: Heating Only See Figure 9. 10: Proportional Heating 2: Cooling and Reheat See Figure 10. 6 and 7: Reheat 10: Proportional Cooling 3: Heating and Reheat See Figure 11. 6 and 7: Reheat 10: Proportional Heating

On/Off, Floating, Heating Output

n or Proportional

o

_

l

c : Outputs Cooling output

G

I

F

Cooling Setpoint t

h

r

_

l

c

:

Heating Setpoint Cooling Setpoint G

I

F

Device Opened Deadband Device On On/Off, Floating, Opened or Proportional Reheat Off Device Closed Output On Device Off Closed Temperature Increase ( Increments of 1Foo /0.5C ) Temperature Increase ( Increments of 1Foo /0.5C ) Figure 8: Cooling Only Figure 10: Cooling with Reheat

on On Heating Setpoint FIG:ht_ On Reheat Off

Device Opened 100% Off On/Off, Floating, or Proportional Device Closed Output 0% On/Off, Floating, or Proportional Temperature Increase Output ( Increments of 1Foo /0.5C )

Figure 9: Heating Only Temperature Increase oo ( Increments of 1F /0.5C ) FIG:ht_rht Figure 11: Heating with Reheat

8 TEC2245-4 LONWORKS® Network Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions

Table 4: Installer Configuration Menu (Part 1 of 5) Parameter Description and Default Selection Options Appearing on Display Pswrd Sets the protective access Range: 0 to 1,000 password to prevent unauthorized access to the Installer Configuration Menu. Default: 0 Note: The default setting does not lock out access to the Installer Configuration Menu. BI1 Configuration of Binary Input 1. (None): No function is associated with an input. Default: None (Rem NSB): Remote Night Setback (NSB) via a time input, an occupancy sensor, or from a voltage-free contact. Contact open = Occupied; contact closed = Unoccupied. (MotionNO*): Temporary occupancy request via a motion detector input. Contact open = Unoccupied. When the contact closes, the thermostat controller goes into the occupied mode for a specified TOccTime. Once the TOccTime begins, the thermostat controller remains in the occupied mode if the contact is open, until the TOccTime expires. (MotionNC*): Temporary occupancy request via a motion detector input. Contact closed = Unoccupied. When the contact opens, the thermostat controller enters occupied mode for a specified TOccTime. Once the TOccTime begins, the thermostat controller remains in the occupied mode if the contact is closed, until the TOccTime expires. (Window**): Cancels the thermostat controller heating or cooling action when a window is open. A Window alarm is displayed indicating that the window needs to be closed to resume heating or cooling. * These settings disable any local override function. **When this setting is selected, the heating and/or cooling outputs are enabled only when the contact is closed. If the fan is set to Auto, it is enabled only when the contact is closed. If the fan is set to On, it is not affected by this setting. BI2 Configuration of Binary Input 2. (None): No function is associated with an input. Default: None (Door Dry): Door contact only has an effect if BI1 is set to MotionNO or MotionNC. (See the BI1 parameter listed previously in this table.) The occupancy is now dictated via BI1 and BI2. Any motion detected sets the zone to Occupied status. The zone remains permanently in occupied mode until the door contact opens momentarily. The thermostat then enters stand-by mode. If more movements are detected, the occupied mode resumes. While the door is opened, any movements detected by the remote PIR sensor or the PIR accessory cover are ignored. Use a Normally Closed contact switching device. Contact opened = Door opened, Contact closed = Door closed. (RemOVR): Temporary occupancy request via a remote input. This override function is controlled by a manual remote occupancy override. When enabled, this condition disables the override capability of the thermostat controller. (Filter): A Filter alarm is displayed. This alarm can be connected to a differential pressure switch that monitors a filter. (Service): A Service alarm is displayed on the thermostat controller when the input is energized. This input can be tied into the unit control card, which provides an alarm should there be a malfunction.

TEC2245-4 LONWORKS® Network Thermostat Controller with Single Proportional Output and One-Speed 9 Fan Control Installation Instructions Table 4: Installer Configuration Menu (Part 2 of 5) Parameter Description and Default Selection Options Appearing on Display UI3 Configuration of Universal Input 3. (None): No function is associated with an input. Default: None (COC/NH): Change Over Contact/Normally Heat: A input is used to signal seasonal hot/cold water changeover. The contact closes when cold water is present. Valid for two-pipe systems only. (COC/NC): Change Over Contact/Normally Cool: A dry contact input is used to signal seasonal hot/cold water changeover. The contact closes when hot water is present. Valid for two-pipe systems only. (COS): Change Over analog Sensor: Used for hot/cold water changeover switching. Valid for two-pipe systems only. Note: Select (0): Cooling Only for SeqOpera parameter. This allows changeover to occur between Cooling only and Heating only. COS does not operate in Cooling with reheat or Heating with reheat applications. (SS): Supply air sensor monitoring Note: The temperature readings from these can be monitored at the thermostat controller or the supervisory controller. MenuScro Gives the option of having the (on): The scroll is active. display continuously scroll the (off): The scroll is inactive. parameters. Default: on AutoMode Enables the Auto function (if (on): The Auto function is active (Off-Auto-Heat-Cool). Provides Option 2 is chosen in the SeqOpera automatic changeover between heating and cooling. parameter) to be visible within the (off): The auto function is inactive (Off-Heat-Cool). MODE key menu. (The MODE key is the key at the far left of the thermostat controller cover.) Default: off C or F Provides temperature scale options (°F): Fahrenheit scale for display. (°C): Celsius scale Default: °F Lockout Selectable Lockout Levels for Lockout Function limiting end user keypad interaction. Level System Fan Mode Unoccupied Occupied Default: 0 Mode Setting Override Temperature Setting Setpoints (0) Access Access Access Access (1) Access Access No Access Access (2) No Access No Access Access Access (3) No Access No Access No Access Access (4) No Access No Access Access No Access (5) No Access No Access No Access No Access SeqOpera Determines the sequence of (0): Cooling Only (Off-Cool). The default is Cool. operation. (1): Heating Only (Off-Heat). The default is Heat. Default: 1 (2): Cooling and Reheat (Off-Auto*-Heat-Cool). The default is Auto. (3): Heating and Reheat (Off-Heat). The default is Heat. * Auto can be disabled with the AutoMode parameter. Note: Choose the selection option (0): Cooling Only when using a changeover sensor to allow changeover to occur between Cooling Only and Heating Only.

10 TEC2245-4 LONWORKS® Network Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions Table 4: Installer Configuration Menu (Part 3 of 5) Parameter Description and Default Selection Options Appearing on Display St-By TM1 Sets stand-by timer value; time Range: 0.5 to 24.0 hours, in 0.5 hour increments delay between moment where occupancy sensor detected the last movement in the area and the time which the thermostat stand-by mode and setpoints become active. Default: 0.5 hours Unocc TM1 Sets Unoccupied Timer Value; time 0.0 hours or Factory Value: Setting this parameter to its default 0 delay between the moment where value disables the occupied timer and prevents the thermostat the thermostat controller toggles to controller from drifting from stand-by mode to unoccupied mode when stand-by mode and the time which occupancy sensor functions are used. the thermostat controller Range: 0.0 to 24.0 hours in 0.5 hour increments. unoccupied mode and setpoints become active. Default: 0.0 hours St-By HT1 Sets Stand-by heating setpoint; Range: 40.0°F/4.5°C to Note: When adjusting the value is between occupied and 90.0°F/32.0°C temperature, press the UP/ unoccupied heating setpoints. DOWN arrow keys to change Default: 69.0°F/20.6°C the temperature in 0.5F°/0.5C° increments; press St-By CL1 Sets Stand-by cooling setpoint limit; Range: 54.0°F/12.0°C to and hold the value is between occupied and 100.0°F/37.5°C UP/DOWN arrow keys unoccupied cooling setpoints. to change the temperature in Default: 78.0°F/25.6°C 5.0F°/5.0C° increments. Unocc HT Sets the Unoccupied Heating Range: 40.0°F/4.5°C to setpoint value. 90.0°F/32.0°C Default: 62.0°F/16.5°C Unocc CL Sets the Unoccupied Cooling Range: 54.0°F/12.0°C to setpoint value. 100.0°F/37.5°C Default: 80.0°F/26.5°C Heat max Sets the Occupied and Unoccupied Range: 40.0°F/4.5°C to maximum Heating setpoint values. 90.0°F/32.0°C Default: 90.0°F/32.0°C Cool min Sets the Occupied and Unoccupied Range: 54.0°F/12.0°C to minimum Cooling setpoint values. 100.0°F/37.5°C Default: 54.0°F/12.0°C Pband Proportional Band used by the PI Value F Scale Pband/C Scale Pband temperature control loop of the 3 3.0F°/1.7C° thermostat controller. Pband is not converted with C or F 4 4.0F°/2.2C° scale and is always shown with a 5 5.0F°/2.8C° range of 3 to 10. Default: 3 (3F°/1.7C°) 6 6.0F°/3.3C° 7 7.0F°/3.9C° 8 8.0F°/4.4C° 9 9.0F°/5.0C° 10 10.0F°/5.6C° Note: The use of a larger proportional band is not to use the thermostat controller as a discharge air controller device. The use of a larger proportional band can be used to solve issues for flawed HVAC design with basic sizing and thermostat controller location errors that cannot be worked around.

TEC2245-4 LONWORKS® Network Thermostat Controller with Single Proportional Output and One-Speed 11 Fan Control Installation Instructions Table 4: Installer Configuration Menu (Part 4 of 5) Parameter Description and Default Selection Options Appearing on Display Set type Provides the option of temporarily (temporar): Local changes to the heating or cooling setpoints are changing the heating or cooling temporary, and remain effective for the specified TOccTime. setpoint by pressing the UP/DOWN (permnent): Local changes to the heating or cooling setpoints are arrow keys. permanently stored in the thermostat controller memory. Default: permnent Spt Func Determines the operation and (Attch Stp): Single Occupied Setpoint Adjustment. The displayed usage of the local setpoint interface setpoint is the setpoint from the last action taken by the thermostat by the user. controller, or the setpoint currently in use. Both the heating and cooling Default: Dual Stp setpoints are changed simultaneously, while respecting the minimum configured deadband. If one setpoint is desired over the other, use the MODE key to toggle between the two setpoints. (Dual Stp): Dual Occupied Setpoint Adjustment. The displayed setpoint is the setpoint from the last action taken by the thermostat controller, or the setpoint currently in use. The heating and cooling setpoints can be separated individually, allowing the minimum configured deadband to expand. If one setpoint is desired over the other, use the MODE key to toggle between the two setpoints. TOccTime Sets the duration of the Temporary Range: 0.0 to 24.0 hrs in 1-hour increments Occupancy Time when the heating or cooling setpoints in the Occupied mode are established by: • an Override Function enabled in the Main User Menu (when the thermostat controller is in the Unoccupied mode) • a temporary heating or cooling setpoint Default: 2.0 hrs Deadband Sets the minimum deadband Range: 2.0F°/1.0C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C° between the heating and cooling increments) setpoints. Default: 2.0F°/1.0C° Cal RS Sets the desired room air sensor Range: -5.0F°/-2.5C° to 5.0F°/2.5C° (adjustable in 1.0F°/0.5C° calibration (offset). The offset can increments) be added to or subtracted from the actual displayed room temperature. Default: 0.0F°/0.0C° Aux cont Determines the auxiliary contact (0) Not used, If the Sequence of Operation is set to reheat function and configuration. or used for (2 or 3), ignore this parameter. Default: 0 reheat (1) Auxiliary Occupied = contact closed The output N.O. Unoccupied = contact open aligns with occupancy. (2) Auxiliary Occupied = contact open N.C. Unoccupied = contact closed (3) Not used (4) (5) Auxiliary On/Off control through the The output auxiliary network command. The output aligns with can be commanded through the network the for any required auxiliary functions via a secondary separate and dedicated network variable. network occupancy command.

12 TEC2245-4 LONWORKS® Network Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions Table 4: Installer Configuration Menu (Part 5 of 5) Parameter Description and Default Selection Options Appearing on Display RA/DA Choice of direct or reverse acting (DA): Direct acting, 0 to 100% = 0 to 10 VDC analog output signal. (RA): Reverse acting, 0 to 100% = -10 to 0 VDC Default: DA Reheat Sets the duty cycle time for reheat (0): 15 minutes (four cycles per hour), for various equipment with output (if Option 2 or 3 is chosen in mechanical relays or contactors controlling mechanical reheat the SeqOpera parameter). systems. Default: 0 (1): 10 seconds (six cycles per minute), for various equipment with solid-state relays that withstand short duty cycles such as electric heat. UI3 dis Displays the supply or changeover Not applicable. temperature when UI3 is configured as an analog input (SS or COS). Used as a diagnostic/service help, to troubleshoot and diagnose sensor operation. Default: -40°F/-40°C

1. This parameter functions only when the TEC is used in conjunction with an onboard occupancy sensor, or a remote occupancy sensor.

Troubleshooting Repair Information See Table 6 for Display messaging. See Table 7 for If the TEC2245-4 Thermostat Controller fails to operate further troubleshooting details. within its specifications, replace the unit. For a replacement thermostat controller, contact the nearest Accessories representative. All the accessories in Table 5 include mounting hardware; contact the nearest Johnson Controls® representative to order any of these parts. Note: Review the technical specifications of the accessories prior to their use in an application. Table 5: Accessories (Order Separately) Code Number Description TEC-6-PIR1 Commercial Fan Coil Controller Cover with Occupancy Sensor TE-6361M-12 Mount Air Temperature Sensor SEN-600-43 Remote Indoor Air Temperature Sensor with Occupancy Override and LED TE-636S-1 Strap-Mount Temperature Sensor

1. The TEC-6-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC2245-4 Thermostat Controller to provide occupancy sensing capability. 2. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Sensors are available; refer to the TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details. 3. Only the occupancy override function can be accomplished using the SEN-600-4 with the TEC2245-4.

Table 6: Alarm Messages Display Function Service Indicates that there is a service alarm in accordance with the programmable Binary Input (BI2). Filter Indicates that the filter(s) is dirty in accordance with the programmable Binary Input (BI2). Window Indicates that an outside window or door is open and has cancelled the thermostat controller heating or cooling action in accordance with the programmable Binary Input (BI1).

TEC2245-4 LONWORKS® Network Thermostat Controller with Single Proportional Output and One-Speed 13 Fan Control Installation Instructions Table 7: Troubleshooting Details Symptom Probable Causes Multiple Excessive bus errors may be occurring. Symptoms A device may have been added or changed with a duplicate Neuron ID (may not be the same address as some devices having problems, and may have happened sometime before the problem was noticed). Wiring errors or wire problems may exist. A download may be in progress. There may be a fault at a device. A repeater may be needed or may be configured incorrectly. Poor Performance See the probable causes listed previously in the Multiple Symptoms section of this table. Excessive bus traffic may exist (bus overload). There may be too many devices on the network. There may be unaccounted devices on the network (not mapped to the NAE). There may be unusually slow devices on the network or devices that are slow to respond. Thermostat See the probable causes listed previously in the Multiple Symptoms section of this table. Controller Goes A power failure or other failure may have occurred at the thermostat controller. Offline Communication may have been disabled at the thermostat controller. Thermostat See the probable causes listed previously in the Multiple Symptoms section of this table. Controller Does A thermostat controller may be connected to the wrong bus. Not Come Online

Technical Specifications TEC2245-4 LONWORKS Network Thermostat Controller with Single Proportional Output and One-Speed Fan Control (Part 1 of 2) Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals 4 and 5) at 24 VAC Nominal, Class 2 or Safety Extra-Low Voltage (SELV) Analog Output Rating 0 to 10 VDC into 2k ohm Resistance (Minimum) Fan Output Rating 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush Auxiliary Triac Output 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush Output Rating Analog Inputs Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative Temperature Coefficient (NTC) Thermistor Sensors Binary Inputs Voltage-Free Contacts across Terminal Scom to Terminals BI1, BI2, or UI3 Wire Size Unshielded Twisted Pair - 22 AWG (0.6 mm Diameter) Minimum, 18 AWG (1.0 mm Diameter) Recommended LONWORKS Network Standard 64 Devices Maximum without a Repeater, 127 Devices Maximum with a Repeater; 6,250 ft (1,905 m) Maximum (Bus Topology) Thermostat Controller -40.0°F/-40.0°C to 122.0°F/50.0°C Measurement Range Sensor Type Local 10k ohm NTC Thermistor Resolution ±0.2F°/±0.1C° Control Accuracy ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated Control Heating 40.0°F/4.5°C to 90.0°F/32.0°C in 0.5° Increments Range Cooling 54.0°F/12.0°C to 100.0°F/38.0°C in 0.5° Increments Minimum Deadband 2F°/1C° between Heating and Cooling Ambient Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing Conditions Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing

14 TEC2245-4 LONWORKS® Network Thermostat Controller with Single Proportional Output and One-Speed Fan Control Installation Instructions TEC2245-4 LONWORKS Network Thermostat Controller with Single Proportional Output and One-Speed Fan Control (Part 2 of 2) Compliance United States UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class A LONMARK Certification 3.4 Canada UL Listed, File E27734, CCN XAPX7, Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment Industry Canada, ICES-003 Europe CE Mark, EMC Directive 2004/108/EC Australia and C-Tick Mark, Australia/NZ Emissions Compliant New Zealand Shipping Weight 0.75 lb (0.34 kg)

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

Building Efficiency 507 E. Michigan Street, Milwaukee, WI 53202 Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc. All other marks herein are the marks of their respective owners. © 2010 Johnson Controls, Inc.

TEC2245-4 LONWORKS® Network Thermostat Controller with Single Proportional Output and One-Speed 15 Fan Control Installation Instructions Published in U.S.A. www.johnsoncontrols.com