BAS System

Note: Lighting control system furnished by Division 25 (Controls Contractor) and installed by Division 26.

BACnet: CL3P 22/2 Shielded, Low Cap, Max 4,000'

Station/Satellite Network: CL3P 22/4, Max 500'

IP Network: CAT-5e, Max 328'

T BACnet MS/TP Network Terminator

LEVEL-3 T Star Station/Satellite Network Terminator BACnet Router RIXX-00 RKX-XX RPDSXX-XX

MSTP T CTS1RL-XX NAME ADDR: 0 IP: XXX.XXX.XX.XX (TYPICAL 2) LOCATION T SCUI8-00 SCAO8-00 CTS1CH-XX ADDR: 1 T T NAME NAME NAME ADDR: XX ADDR: XX ADDR: XX NAME NAME CTS1CH-XX LOCATION LOCATION LOCATION SLOT: 1 SLOT: 2 LOCATION LOCATION ADDR: 2 T

BAS NETWORK LEVEL-2 T-Tap BACnet Router RPSSXX-XX RPDSXX-XX

MSTP T NAME IP: XXX.XXX.XX.XX LOCATION ZCSS-00-00 CS1 SCSS-00 SCSS-00 SCAO8-00

CTS4CH-XX CTS6CH-XX CTS1CH-XX CTS2CH-XX CTS1RL-XX CTS3CH-XX T ADDR: 0 ADDR: 1 T ADDR: 0 ADDR: 1 T T ADDR: 0 ADDR: 1 NAME T T NAME T T T T NAME T T T ADDR: XX ADDR: XX NAME NAME ADDR: XX NAME LOCATION LOCATION SLOT: 1 SLOT: 2 LOCATION SLOT:1 LOCATION LOCATION LOCATION

LEVEL-1 Daisy Chain BACnet Router

MSTP T ZCDS-00-00 NAME CS1 SCSS-00 SCDS-00 SCDS-00 IP: XXX.XXX.XX.XX Engineering Standards SYS_01.00 LOCATION 1 1 4

CTS2RL-XX CTS1RL-XX CTS1CH-XX CTS2CH-XX CTS3PR-XX 2 CTS6PR-XX 2 5 T T ADDR: 0 ADDR: 1 ADDR: 2 ADDR: 3 ADDR: 4 3 ADDR: 5 3 6 Lighting Control System Riser NAME T ADDR:XX NAME NAME NAME Rev: 4 Type: Reference Date: 01-20-15 Job #: LOCATION SLOT: 1 SLOT: 2 SLOT: 3 LOCATION LOCATION LOCATION Engineered: WCD

Drawn: NB

Checked:

1 of 1

Tech Note 071014_02

Date: July 10, 2014

Product: TK-2.0

Subject: USB Cable and Driver Installation

Note: Recommended USB Installation Procedure

1. Turn the Controller Board Power Switch “Off”. 2. Insert the Standard- USB connector into a USB 2.0 port on your computer. 3. Insert the Micro-B USB connecter into the controller. 4. Turn the Controller Board Power Switch “On”.

1800 Sandy Plains Industrial Parkway, Suite 216, Marietta, GA 30066 800-241-9173 www.BRTint.com

Page 2 of 3

Recommended USB Cable Driver Installation

Computer Requirements Operating System: Windows 7 (32/64-bit) USB: Standard-A USB 2.0 port

1. Click the Start button, then right click on Computer and click Manage. 2. Under “System Tools” click Device Manager. (The cable will populate under “Other Devices”) 3. Right click on BRT Zone Controller and click Update Driver Software.

4. Click Browse my computer for driver software.

1800 Sandy Plains Industrial Parkway, Suite 216, Marietta, GA 30066 800-241-9173 www.BRTint.com

Page 3 of 3

5. Browse for USB driver location and click Next.

6. The Blue Ridge Technologies driver package has not been digitally signed yet, click Install this driver software anyway.

7. In the Update Driver Software pop-up window, Windows has successfully updated your driver software.

1800 Sandy Plains Industrial Parkway, Suite 216, Marietta, GA 30066 800-241-9173 www.BRTint.com

Tech Kit 2.0 Project Part Number Ref.

Data Sheet : Catalog Page 96

Overview Tech Kit 2.0 (TK-2.0) includes all components for USB and Bluetooth wireless configuration of the Aperio Open Control Platform. TK-2.0 facilitates Controller Board setup, programing, firmware updates, and firmware restoration. The kit features Blue Ridge Technologies Essentials (BRT Essentials) software on a 1GB flash drive, a Bluetooth Dongle, a Bluetooth Module, a 12’(3.66m) Tech Cable (TC), a screwdriver, and a Carry Bag.

Features Bluetooth Specifications Configures , RK, RP, ZC and related Satellite/Station components: Dongle Connection Satellite Hardware: Standard-A USB port on computer Capacitive Touch Station (CTS) Wireless: Supports multiple device connections USB and Bluetooth wireless communication Module Connection Complete BRT Essentials software Hardware: Bluetooth Plug on Controller Board Wireless: PTP connection Warranty Wireless Type: Bluetooth v2.0+EDR Class 1 Two (2) year limited manufacturer warranty from date of shipment Wireless Range: Open air 328’ (100m) (extended warranty optional) Wireless Compatibility: BRT Essentials software (API available from Blue Ridge for interface development) Computer Requirements Operating System: Windows 7 (32/64-bit) Tech Cable Specifications Java: Java 1.7 (JRE) or greater Type: USB 2.0 Bluetooth: Microsoft Bluetooth Stack Dimensions: 12’(3.66m)L USB: Standard-A USB 2.0 port Computer Connection: Standard-A USB port Controller Board Connection: Micro-B USB port Flash Drive Specifications Capacity: 1GB Accessory Specifications Contents: Screwdriver BRT Essentials software Type: 0.4 x 2.5mm slot head BRT Essentials Template Files Carry Bag USB Drivers Type: Flat cloth with zipper closure Supporting Documents Dimensions: 7.25”(184mm)H x 9.50”(241mm)W General Architecture

Internet IP

BACnet MS/TP

BAS Router

Field Devices Field Devices Field Devices Field Devices Satellite/Station Network Satellite/Station Network Satellite/Station Network Satellite/Station Network

Zone Control (ZC) Relay Panel (RP) Retrofit Interior (RI) Retrofit Kit (RK)

Satellite/Station Network Field Devices

Field Devices Satellite CTS LVS OCC LS

CTS (Capacitive Touch Station) LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor)

General Architecture

Internet IP

BACnet MS/TP

BAS Router

Field Devices Field Devices Field Devices Field Devices Satellite/Station Network Satellite/Station Network Satellite/Station Network Satellite/Station Network

Zone Control (ZC) Relay Panel (RP) Retrofit Interior (RI) Retrofit Kit (RK)

Satellite/Station Network Field Devices

Field Devices Satellite CTS LVS OCC LS

CTS (Capacitive Touch Station) LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor)

General Architecture

Internet IP

BACnet MS/TP

BAS Router

Field Devices Field Devices Field Devices Field Devices Satellite/Station Network Satellite/Station Network Satellite/Station Network Satellite/Station Network

Zone Control (ZC) Relay Panel (RP) Retrofit Interior (RI) Retrofit Kit (RK)

Satellite/Station Network Field Devices

Field Devices Satellite CTS LVS OCC LS

CTS (Capacitive Touch Station) LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor)

General Architecture

Internet IP

BACnet MS/TP

BAS Router

Field Devices Field Devices Field Devices Field Devices Satellite/Station Network Satellite/Station Network Satellite/Station Network Satellite/Station Network

Zone Control (ZC) Relay Panel (RP) Retrofit Interior (RI) Retrofit Kit (RK)

Satellite/Station Network Field Devices

Field Devices Satellite CTS LVS OCC LS

CTS (Capacitive Touch Station) LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor)

General Architecture

Internet IP

BACnet MS/TP

BAS Router

Field Devices Field Devices Field Devices Field Devices Satellite/Station Network Satellite/Station Network Satellite/Station Network Satellite/Station Network

Zone Control (ZC) Relay Panel (RP) Retrofit Interior (RI) Retrofit Kit (RK)

CANbus Network Field Devices

Field Devices Satellite CTS LVS OCC LS

CTS (Capacitive Touch Station) LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor)

General Architecture

Internet IP

BACnet MS/TP

BAS Router

Field Devices Field Devices Field Devices Field Devices Satellite/Station Network Satellite/Station Network Satellite/Station Network Satellite/Station Network

Zone Control (ZC) Relay Panel (RP) Retrofit Interior (RI) Retrofit Kit (RK)

Satellite/Station Network Field Devices

Field Devices Satellite CTS LVS OCC LS

CTS (Capacitive Touch Station) LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor)

General Architecture

Internet IP

BACnet MS/TP

BAS Router

Field Devices Field Devices Field Devices Field Devices Satellite/Station Network Satellite/Station Network Satellite/Station Network Satellite/Station Network

Zone Control (ZC) Relay Panel (RP) Retrofit Interior (RI) Retrofit Kit (RK)

Satellite/Station Network Field Devices

Field Devices Satellite CTS LVS OCC LS

CTS (Capacitive Touch Station) LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor)

General Architecture

Internet IP

BACnet MS/TP

BAS Router

Field Devices Field Devices Field Devices Field Devices Satellite/Station Network Satellite/Station Network Satellite/Station Network Satellite/Station Network

Zone Control (ZC) Relay Panel (RP) Retrofit Interior (RI) Retrofit Kit (RK)

Satellite/Station Network Field Devices

Field Devices Satellite CTS LVS OCC LS

CTS (Capacitive Touch Station) LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor)

General Architecture

Internet IP

BACnet MS/TP

BAS Router

Field Devices Field Devices Field Devices Field Devices Satellite/Station Network Satellite/Station Network Satellite/Station Network Satellite/Station Network

Zone Control (ZC) Relay Panel (RP) Retrofit Interior (RI) Retrofit Kit (RK)

Satellite/Station Network Field Devices

Field Devices Satellite CTS LVS OCC LS

CTS (Capacitive Touch Station) LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor)

General Architecture

Internet IP

BACnet MS/TP

BAS Router

Field Devices Field Devices Field Devices Field Devices Satellite/Station Network Satellite/Station Network Satellite/Station Network Satellite/Station Network

Zone Control (ZC) Relay Panel (RP) Retrofit Interior (RI) Retrofit Kit (RK)

Satellite/Station Network Field Devices

Field Devices Satellite CTS LVS OCC TechLS Kit 2.0 CTS (Capacitive Touch Station) LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor) www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2014 Blue Ridge Technologies International, LLC All Rights Reserved. TK20-DS-V14.05

General Architecture Data Sheet : Catalog Page 97

Internet IP

BACnet MS/TP

BAS Router

Field Devices Field Devices Field Devices Field Devices Satellite/Station Network Satellite/Station Network Satellite/Station Network Satellite/Station Network

Zone Control (ZC) Relay Panel (RP) Retrofit Interior (RI) Retrofit Kit (RK)

Satellite/Station Network Field Devices

Field Devices Satellite CTS LVS OCC LS

CTS (Capacitive Touch Station) LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor)

General Architecture

Internet IP

BACnet MS/TP

BAS Router

Field Devices Field Devices Field Devices Field Devices Satellite/Station Network Satellite/Station Network Satellite/Station Network Satellite/Station Network

Zone Control (ZC) Relay Panel (RP) Retrofit Interior (RI) Retrofit Kit (RK)

Controller BoardSatellite/Station Terminations Network (ZC) Field DevicesController Board Terminations (RI / RK / RP)

J1

Field Devices Satellite CTS LVS OCC LS

Standard-A USB Plug Micro-B USB Plug CTS (Capacitive Touch Station) LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor)

Bluetooth Module Bluetooth General Architecture Bluetooth Module Internet IP

BACnet MS/TP J3 BAS Router

Field Devices J5 Field Devices Field Devices Field Devices CANbus Network CANbus Network CANbus Network CANbus Network Micro-B USB Plug Standard-A USB Plug Zone Control (ZC) Relay Panel (RP) Retrofit Interior (RI) Retrofit Kit (RK)

CANbus Network Field Devices

Field Devices Satellite CTS LVS OCC LS

SC (Satellite) / CTS (Capacitive Touch Station) LVS (Low Voltage Switch) / OCC (Occupancy Sensor) / LS (Light Sensor)

UL924 Terminations Emergency Bypass Structure

Generator

Emergency Power Emergency G Distribution Panel Transfer Switch

Normal (Utility) Power

Retrofit Interior (RI) / Relay Panel (RP) Ordering Information Part Number Description Lighting Tough Relay UL924 Normal Power TK-2.0 Tech Kit 2.0 (Micro-USB Cable, USB flash drive with BRT Essentials software,(LTR) Bluetooth Dongle, Bluetooth Module, Screwdriver,Distribution Panel and Carry Bag)

Lighting Load

TEST JP2 Test Jumper

JP1 Configuration 1 Jumper 2 3 Power LED LED 1

24VAC 24VDC OUT

RI / RP Transformer Factory Wired for Normal Power 24VDC(-) Normal Power Indicator Lamp* *User installed option. 24VDC(+) Normal Power Indicator Lamp*

LTR Terminations LEXP Terminations

Phillips / Slot / Square Head Screw Terminals GND DI 32 DI 31 DI 30 DI 29 DI 28 DI 27 DI 26 DI 25 GND DI 24 DI 23 DI 22 DI 21 DI 20 DI 19 DI 18 DI 17 Mounting Hole INPUTS 17-32

Line In R DI Jumper J13 J9

TO J26 OF Controller 17-24* DI Jumper Relay Output 25-32* Port POWER Power LED DI Jumper

Manual Override Lever Wire Strip Length Indicator Controller Board

INPUTS 1-16 1-8* ADDRESS B A J18 J4 J5 N

J19 DI Jumper R C D 9-16* Jumper Address DI 1 DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8 DI 9 GND GND DI 11 DI 10 DI 12 DI 13 DI 14 DI 15 DI 16 *DI Jumper Position N(Dry Contact) / R(Externally Powered)

Demo Kit Features

Baud Rate Dip Switch Network Address Rotary Switch 10’s

BACnet (+) In BACnet (-) In Shield In BACnet (+) Out BACnet (-) Out Shield Out Network Address Rotary Switch 1’s BT485 Terminator Plug BT485 Terminator

SW3

10’s 1’s TEST Test Button

Power Switch

Power LED / Run LED

BN+ BN- S J5 BN+ BN- S

J3 Bluetooth Plug

Micro-B USB Port J5 OFF ON

PWR RUN

Light Sensor Simulator LED Lamps

Occupancy Sensor Simulator

Line Voltage Switch (Standard Rocker Switch) Capacitive Touch Station (CTS) 120VAC 8’(2.44m) Power Cord NEMA 5-15 Plug LINE VOLTAGE ENTRY LINE VOLTAGE ENTRY

Off On On Off RO 01 RO 02 RO 03 RO 04 RO 05 RO 06 RO 07 Wire Strip RO 08 RO 09 Length Indicator RO 10 UL924 EMERGENCY BYPASS CONFIGURATION JUMPER RO 11 Line RO 12 ENCLOSURE RO 13 Relay 01 RO 14 JP1 JP1 Load RO 15 RO 16 1 JUMPER: EMERGENCY 1 1-2 JUMPED: EMERGENCY RO 17 Status Indicator & RO 18 2 2 Manual Override ACTION DISABLED ACTION CLOSES ALL RELAYS RO 19 RO 20 3 3 UL924 EMER. RO 21 RO 22 BYPASS RO 23 RO 24 JP1 1 RO 25 RO 26 2-3 JUMPED: EMERGENCY 2 ACTION OPENS ALL RELAYS RO 27 RO 28 3 RO 29 RO 30 RELAY PANEL RO 31 RO 32 CONTROL BOARD RO 33 RELAY VOLTAGE DIVIDERS RO 34 (RPCB) (RPRVD) TEST JUMPER RO 35 RO 36 RO 37 RO 38 JP2 RO 39 RO 40 NO JUMPER: RO 41 RO 42 SIMULATED POWER LOSS RO 43 RO 44 RO 45 RPCB RO 46 RO 47 RO 48 UL924 EMERGENCY BYPASS RO 49 RO 50 RO 51 RO 52 POWER IN: 24VAC IN +/-10%, 30VA, 50-60 Hz, Factory RO 53 RO 54 TEST Wired for Normal Power RO 55 RO 56 JP2 RO 57 RO 58 POWER OUT: 24VDC for Normal Power Indicator Lamp UL924 RO 59 RO 60 (User Installed Option) RO 61 RO 62 JP1 T +24VAC -24VAC 1 BLK EMERGENCY CB-XX POWER AVAILABLE: 200mA Shared Between UI's, SN, and UL924 RO 63 +24VAC RO 64

LOAD N 2 -24VAC GRN GROUND 3 Auxiliary Out WHT NEUTRAL - + BLK LINE ~ ~ TRANSFORMER LED1 (NORMAL) 24VAC IN 24VDC OUT CIRCUIT BREAKER UL924 RELAY CONTROL 20A MAX RP16: UL924 Controls RO 1-16

LEXP LEXP LEXP RP32: UL924 Controls RO 17-32 (Optional) (Optional) (Optional) R R R O O K T T

L RP48: UL924 Controls RO 33-48 W B A A O C C I I P

D D L RP64: UL924 Controls RO 49-64 N A N I I

M P P R K M M L O B A A N L L

NEUTRAL WHT LOW VOLTAGE ENTRY (EMERGENCY) R R CIRCUIT BREAKER R E E O F

BALLAST 20A MAX W W D O O

BLK EMERGENCY GENERATOR E P P

R I L GRN GROUND L A EMERGENCY A W

M M TRANSFER WHT NEUTRAL Y R R R O O SWITCH O T N N

C ) ) - + EMERGENCY LIGHT FIXTURE A ( ( F C C D D V V 4 4 2 2

Engineering Standards RPDTL_01.20

Relay Panel, UL924 Detail

Rev: 4 Type: Date: 01-20-15 Job #:

Engineered: NB

Drawn: NB

Checked:

1 of 1 13.00" 5.75" 18.00" 5.75" 18.00" 5.75" 18.00" 5.75" 18.00" 5.75" 0.00" 0.00" 0.00" 0.00" 0.00" 1.00" 1.25" 1.25" 1.25" 1.25"

RP 08 RP 16 RP 32 RP 48 RP 64 14.75" 16.20" 10.80" 25.00" 13.76"

0 1 1 14.70" . . 2 0 0 . Ø0.25" 0 1 1 0 0 0 33.80" . . 7 " " 0 0 0 . " 0 0 0 19.60" " " 0 " 42.60" 23.50" 0 1 1 . . 7 0 0 . 0 LINE VOLTAGE ENTRY LINE VOLTAGE ENTRY 0 0 " " 0 "

RELAY PANEL 32.30" 0 1 1 . . 7 0 0 . 0 Off On On Off 0 0 0 RELAY PANEL CONTROL BOARD (RPCB) " " RO 01 RO 02 " ON RO 04 9 0 1 9 0 1 RO 03 2 2

8 8 41.10" 3 3

7 7

4

J1 4 6 6

5 RO 05 RO 06 1 2 3 4 5 6 7 8 5 0 1 1 . . 7 0 0

RO 08 SW3 . 0 RO 07 Wire Strip 10's 1's 0 0 " " Baud Rate BAUD RATE SELECTION-BN 0 BN-Address "

RO 09 Length Indicator RO 10 - + 485-TX

D

N

L N 485-RX

B

H RO 11 RO 12 J3 B Line S 9600 19200 38400 RO 13 Relay 01 RO 14 CAN-TX TEST ON ON ON RO 15 Load RO 16 CAN-RX BUSY RO 17 Status Indicator & RO 18 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 SN+ JP2 DI EXPANDER (LEXP) Manual Override RO 20 SN Terminator SW3 SW3 SW3 RO 19 SN-

RO 21 RO 22 +24V

2 0 9 7 6 4 2 1 9 8

1 8 5 3 0 7 D

GND D

3 3 2 2 2 2 2 2 1 1

3 2 2 2 1

RO 23 RO 24 2

N N

------

76800 115200 -

------

I I I I I I I I I I

I I I I I I

G G

D D D D D D D D D D

D D D D D RO 25 RO 26 ON ON D RO 27 RO 28 Bluetooth LEXP R T

RO 29 RO 30 BTOC 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 O N

BT-TX J SW3 SW3 2 J J 6

RO 31 RO 32 BT-RX 9 1

O

UI-1 3 RO 34 F

RO 33

UI-2 C o

RO 35 RO 36 +24V n t r

GND o

RO 37 RO 38 l

l POWER e

UI-3 r RO 39 RO 40 BACnet MS/TP NETWORK-BN UI-4 RO 42 RO 41 +24V TOPOLOGY: RS-485, (Half Duplex) Daisy Chain RO 43 RO 44 GND J J A A B 5 4 UI-5 D J18

RO 45 RO 46 WIRE: CL3P 22/2 Shielded, Low Cap, 4000' Max D

RPCB N UI-6 RELAYS 1-32 R RO 47 RO 48 E S

J19 R

+24V S RO 49 RO 50 GND C D

RO 51 RO 52 UI-7

0 2 3 5 6

1 4

D D

1 2 4 5 7 8 9 1 1 1 1 1

3 1 1

UI-8 6

------

- - -

RO 54 - N

RO 53 N

I I I I I I I I I I I I

I I I I

D D D D D D D D D D D D

D D D D G +24V STATION/SATELLITE NETWORK-SN G RO 56 RO 55 GND RO 57 RO 58 UI-9 RELAYS 33-64 TOPOLOGY: Daisy Chain Only RO 59 RO 60 UI-10 WIRE: CL3P 22/4 Unshielded Low Cap, 500' Max DIGITAL INPUTS (DI) RO 61 RO 62 +24V GND RO 63 RO 64 POWER: 24 VDC Externally Powered or Dry Contact WIRE: 18 AWG Solid or Stranded, 500' Max UI-11 UI-12 +24V POWER TERMINATION-BN TERMINATION-SN GND SWITCH UI-13 (Un-terminated) (Terminated)

T Plug EOL Resistor into J3 UI-14 +24VAC

U

+24V O -24VAC to Terminate BACnet PWR RUN JP2 JP2 GND +24VAC

N LEXP LEXP LEXP UI-15 I -24VAC

UI-16

8 9 0 1 2 3 4

(Optional) (Optional) (Optional) 7

V V V

+24V V

D D D D D

1 1 1 2 2 2 2 2

4 4 4 4

V

------

I I I I I I I I

N N N N N

2 2 2 5

GND 2

U U + G U U + G U U + G U U + G + G

UNIVERSAL INPUTS (UI) POWER: 24 VDC, 200 Total All Inputs Engineering Standards WIRE: 18 AWG Solid or Stranded, 500' Max LINE VOLTAGE ENTRY LOW VOLTAGE ENTRY LINE VOLTAGE ENTRY RPDTL_01.00

Relay Panel Details, Standard RELAY OUTPUTS (RO) TORQUE SPECIFICATIONS LOAD RATINGS: Short Circuit Current Rating 30,000A at 277 VAC RO SCREW TERMINALS: 36in-lbs Rev: 4 Type: Date: 01-09-14 Job #: 20A Tungst e n a t 3 4 7 V A C 30A Ballast at 347 VAC GROUND LUG: 20in-lbs Engineered: NB 20A Resisti v e a t 3 4 7 V A C 1.5 HP at 120 VAC 4-40 FASTENERS: 5in-lbs (Max) for RO and Relay Voltage Divider Fasteners Drawn: NB WIRE: (2) 14-10 AWG or (1) 8AWG (Solid or Stranded Copper Wire) 6-32 FASTENERS: 10in-lbs (Max) for RPCB and LEXP Fasteners Checked: WCD

1 of 1 LINE BLK CIRCUIT-XX Relay 01 Relay 02 CIRCUIT BREAKER LOW 20A MAX Relay 03 Relay 04 HIGH Relay 05 Relay 06

Relay 07 Relay 08

Relay 09 Relay 10

Relay 11 Relay 12

Relay 13 Relay 14 SHIELD SHIELD RED-24VDC K K

L L Relay 15 BLK BLK Relay 16 BLK-GND B B RED RED OCCUPANCY Relay 17 Relay 18 SENSOR (IN) - + Relay 19 D WHT-N.O.

L Relay 20 N N B H B K K

SN+ S L L B B Relay 21 SN- (OUT) Relay 22 BOS-315 NEUTRAL WHT WHT +24V (SET TIMER TO MINIMUM) GND BALLAST-1 BALLAST-2 Relay 23 Relay 24 UI-1 Relay 25 Relay 26 UI-2 RED RED-24VDC +24V LIGHT Relay 27 BLK BLK-GND GND Relay 28 SENSOR UI-3 YEL YEL-SIGNAL Relay 29 UI-4 Relay 30 LIGHT FIXTURE +24V Relay 31 Relay 32 GND LS24-I UI-5 UI-6 +24V GND UI-7 UI-8 RPCB +24V GND UI-9 UI-10 T D K H L +24V E B R GND W UI-11 UI-12 +24V GND T1 UI-13 UI-14 +24V GRN GROUND GND P1 BLK LINE UI-15 P2 277V CIRCUIT BREAKER T3 P1 BLU BRN UI-16 BLK 20A MAX P2 YEL 120V 4 3 2 1 0 9 8 +24V 7 V V V

V WHT D D D D D 2 2 2 2 2 1 1 1 4 4 V 4 4 ------N I I I N I N T2 N I N I I I

GND 2 2 5 2 2 WHT NEUTRAL G + U U G U + + G U G + G U + U U U T T L K K D K D D

H LV-SW2 H L L L E E E E Y B B B R R R W W

FROM MSTP NETWORK CL3P 22/2 SHIELDED LOW CAP MAX 4,000' CL3P 22/2 SHIELDED LOW CAP MAX 4,000' TO MSTP NETWORK

CL3P 18/3 MAX 500' Engineering Standards CL3P 18/3 MAX 500' CL3P 18/3 MAX 500' RPSB32_01.00

Relay Panel 32 Relay, Low Voltage 2-Button Switch

Rev: 4 Type: Date: 01-20-15 Job #:

Engineered: NB

Drawn: NB

Checked:

1 of 1 Master BACnet Points List

Description Name Object Type ID Analog Input ANALOG_INPUT_100ssxx ANALOG_VALUE 100ssxx Digital Input DIGITAL_INPUT_100ssxx BINARY_VALUE 100ssxx Load Status LOAD_STATUS_110ssxx BINARY_VALUE 110ssxx Line Voltage Input LINE_VOLTAGE_INPUT_120ssxx BINARY_VALUE 120ssxx Device nnnn_DEVICE_OBJECT_132aaa DEVICE 132aaa Channel Status CHANNEL_STATUS_200zzcc BINARY_VALUE 200zzcc Channel Level CHANNEL_LEVEL_201zzcc ANALOG_VALUE 201zzcc Occupancy Timer Occupied Mode OCC_TIMER_OCC_MODE_210zzcc ANALOG_VALUE 210zzcc Occupancy Timer Unoccupied Mode OCC_TIMER_UNOCC_MODE_211zzcc ANALOG_VALUE 211zzcc Timer Unoccupied Mode TIMER_UNOCC_212zzcc ANALOG_VALUE 212zzcc Timer Occupied Mode TIMER_OCC_213zzcc ANALOG_VALUE 213zzcc Daylight Harvesting Setpoint DAY_HARVEST_SETPT_220zzcc ANALOG_VALUE 220zzcc Run Command RUN_COMMAND_300zz00 BINARY_VALUE 300zz00 Schedule SCHEDULE_310zz00 SCHEDULE 310zz00 Occupied/Unoccupied Mode Source OCCUNOCC_MODE_SOURCE_330zzcc MULTISTATE_VALUE 330zzcc Virtual Station On Off VS_ON_OFF_340tttb MULTISTATE_VALUE 340tttb Virtual Station Indicator LED VS_BUTTON_INDICATOR_341tttb MULTISTATE_VALUE 341tttb Virtual Station Level Set VS_LEVEL_SET_342tttb MULTISTATE_VALUE 342tttb

Note - BACnet Object ID and Object Name must be turned on with BRT Essentials

1 of 10 Master BACnet Points List

Digital Line Voltage Analog b - Button or Station Device Device Name Input Load Status Input Input Product Button Set zz -Zone cc - Channel ss - Slot ttt - Address aaa - Address nnnn - Name xx - Instance xx - Instance xx - Instance xx - Instance ZCSB 01 01 - 08 00 000 000 - 099 ZCSB 01 - 06 01 - 02 01 - 02 01 - 06 ZCSS NA 01 - 02 01 - 08 00 - 03 000 - 006 000 - 099 ZCSS 01 - 06 01 - 02 01 - 02 01 - 06 ZCDS NA 01 - 02 01 - 08 00 - 03 000 - 006 000 - 099 ZCDS 01 - 06 01 - 02 01 - 02 01 - 06 ZCDE NA 01 - 04 01 - 08 00 - 07 000 - 012 000 - 099 ZCDE 01 - 06 01 - 02 01 - 02 01 - 06 RPSB NA 01 - 64 01 - 08 00 000 000 - 099 RPSB 01 - 24 NA NA 01 - 24 RPSS NA 01 - 64 01 - 08 00 - 16 000 - 064 000 - 099 RPSS 01 - 24 NA NA 01 - 24 RPDS NA 01 - 64 01 - 08 00 - 16 000 - 064 000 - 099 RPDS 01 - 24 NA NA 01 - 24 RKUN NA 01 - 64 01 - 08 00 - 04 000 - 064 000 - 099 RKUN 01 - 24 NA NA 01 - 24 RKUS NA 01 - 64 01 - 08 00 - 04 000 - 064 000 - 099 RKUS 01 - 24 01 - 64 NA 01 - 24

SCSS NA NA NA NA NA NA NA 01 - 06 01 - 02 01 - 02 01 - 06 SCDS NA NA NA NA NA NA NA 01 - 06 01 - 02 01 - 02 01 - 06 MIO-AO08 NA NA NA NA NA NA NA NA NA NA NA MIO-UI16 NA NA NA NA NA NA NA 01 - 16 NA NA 01 - 16 RP-FI1-C NA NA NA NA NA NA NA NA NA NA NA RK-FI1-A NA NA NA NA NA NA NA 01 - 64 NA NA NA LEXP32 NA NA NA NA NA NA NA 01 - 32 NA NA NA

CTS1CH 1 NA NA NA NA NA NA NA NA NA NA CTS2CH 1 - 2 NA NA NA NA NA NA NA NA NA NA CTS3CH 1 - 3 NA NA NA NA NA NA NA NA NA NA CTS4CH 1 - 4 NA NA NA NA NA NA NA NA NA NA CTS6CH 1 - 6 NA NA NA NA NA NA NA NA NA NA CTS1RL 1 NA NA NA NA NA NA NA NA NA NA CTS2RL 1 - 2 NA NA NA NA NA NA NA NA NA NA CTS3PR 1 - 4 NA NA NA NA NA NA NA NA NA NA CTS6PR 1 - 6 NA NA NA NA NA NA NA NA NA NA

2 of 10 Master BACnet Points List

Device Description Type Default Access Object_Identifier BACnet device object for the controller. BACnetObjectIdentifier 132aaa Read Object_Name CharacterString nnnn_DEVICE_OBJECT_132aaa Read Object_Type BACnetObjectType DEVICE Read System_Status BACnetDeviceStatus Read Blue Ridge Technologies International, Vendor_Name CharacterString Read LLC Vendor_Identifier Unsigned16 132 Read Model_Name CharacterString Read Firmware_Revision CharacterString Read Application_Software_Version CharacterString Read Protocol_Version Unsigned Read Protocol_Revision Unsigned Read Protocol_Services_Supported BACnetServicesSupported Read Protocol_Object_Types_Supported BACnetObjectTypesSupported Read Object_List BACnetARRAY[N] of BACnetObjectIdentifier Read Max_APDU_Length_Accepted Unsigned ? Segmentation_Supported BACnetSegmentation NO_SEGMENTATION Read Local_Time Time Read/Write Local_Date Date Read/Write UTC_Offset INTEGER Read/Write Daylight_Savings_Status BOOLEAN Read/Write APDU_Timeout Unsigned 6000 Read/Write Number_Of_APDU_Retries Unsigned 3 Read/Write Max_Master Unsigned (1..127) 99 Read/Write Max_Info_Frames Unsigned 10 Read/Write Device_Address_Binding BACnetList of BACnetAddressBinding Read Database_Revision Unsigned Read Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

Digital Input Description Type Default Access Object_Identifier Indicates the status of a binary input, BACnetObjectIdentifier 100ssxx Read Object_Name either on or off. CharacterString DIGITAL_INPUT_100ssxx Read Object_Type BACnetObjectType BINARY_VALUE Read Present_Value Any 0 Read Status_Flags BACnetStatusFlags 0 Read Event_State BACnetEventState NORMAL Read Out_Of_Service BOOLEAN TRUE Read Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

3 of 10 Master BACnet Points List

Load Status Description Type Default Access Object_Identifier Indicates whether a given load relay is BACnetObjectIdentifier 110ssxx Read Object_Name open or closed. On indicates the relay CharacterString LOAD_STATUS_110ssxx Read Object_Type is closed. Off indicates the relay is BACnetObjectType BINARY_VALUE Read Present_Value open. Any 0 Read Status_Flags BACnetStatusFlags 0 Read Event_State BACnetEventState NORMAL Read Out_Of_Service BOOLEAN TRUE Read Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

Line Voltage Input Description Type Default Access Object_Identifier Indicates the status of a line voltage BACnetObjectIdentifier 120ssxx Read Object_Name input, either on or off. CharacterString LINE_VOLTAGE_INPUT_120ssxx Read Object_Type BACnetObjectType BINARY_VALUE Read Present_Value Any 0 Read Status_Flags BACnetStatusFlags 0 Read Event_State BACnetEventState NORMAL Read Out_Of_Service BOOLEAN TRUE Read Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

Channel Status Description Type Default Access Object_Identifier Indicates the status of a Channel, either BACnetObjectIdentifier 200zzcc Read Object_Name lights on or lights off. CharacterString CHANNEL_STATUS_200zzcc Read Object_Type BACnetObjectType BINARY_VALUE Read Present_Value Any 0 Read Status_Flags BACnetStatusFlags 0 Read Event_State BACnetEventState NORMAL Read Out_Of_Service BOOLEAN TRUE Read Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

Run Command Description Type Default Access Object_Identifier Controls mode of operation. On is BACnetObjectIdentifier 300zz00 Read Object_Name when occupants are expected present. CharacterString RUN_COMMAND_300zz00 Read Object_Type Off when occupants are expected not BACnetObjectType BINARY_VALUE Read Present_Value present. Any 1 Read/Write Status_Flags BACnetStatusFlags 0 Read Event_State BACnetEventState NORMAL Read Out_Of_Service BOOLEAN TRUE Read Priority_Array BACnetPriorityArray Read Relinquish_Default BACnetBinaryPV 1 Read/Write Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

4 of 10 Master BACnet Points List

Analog Input Description Type Default Access Object_Identifier Indicates the status value of an analog BACnetObjectIdentifier 100ssxx Read Object_Name input. Units and range are configured CharacterString ANALOG_INPUT_100ssxx Read Object_Type within BRT Essentials. BACnetObjectType ANALOG_VALUE Read Present_Value Any 0 Read Status_Flags BACnetStatusFlags 0 Read Event_State BACnetEventState NORMAL Read Out_Of_Service BOOLEAN TRUE Read Units BACnetEngineeringUnits Read Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

Channel Level Description Type Default Access Object_Identifier Indicates the lighting output level in % BACnetObjectIdentifier 201zzcc Read Object_Name for a channel. CharacterString CHANNEL_LEVEL_201zzcc Read Object_Type BACnetObjectType ANALOG_VALUE Read Present_Value Any 0 Read Status_Flags BACnetStatusFlags 0 Read Event_State BACnetEventState NORMAL Read Out_Of_Service BOOLEAN TRUE Read Units BACnetEngineeringUnits percent Read Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

Occupancy Timer Occupied Mode Description Type Default Access Object_Identifier Timer value in minutes used to count BACnetObjectIdentifier 210zzcc Read Object_Name down time during occupied mode as CharacterString OCC_TIMER_OCC_MODE_210zzcc Read Object_Type occupancy timer times out. BACnetObjectType ANALOG_VALUE Read Present_Value Any 30 Read/Write Status_Flags BACnetStatusFlags 0 Read Event_State BACnetEventState NORMAL Read Out_Of_Service BOOLEAN TRUE Read Units BACnetEngineeringUnits minutes Read Priority_Array BACnetPriorityArray Read Relinquish_Default BACnetBinaryPV 0 Read/Write Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

5 of 10 Master BACnet Points List

Occupancy Timer Unoccupied Mode Description Type Default Access Object_Identifier Timer value in minutes used to count BACnetObjectIdentifier 211zzcc Read Object_Name down time during unoccupied mode as CharacterString OCC_TIMER_UNOCC_MODE_211zzcc Read Object_Type occupancy timer times out. BACnetObjectType ANALOG_VALUE Read Present_Value Any 30 Read/Write Status_Flags BACnetStatusFlags 0 Read Event_State BACnetEventState NORMAL Read Out_Of_Service BOOLEAN TRUE Read Units BACnetEngineeringUnits minutes Read Priority_Array BACnetPriorityArray Read Relinquish_Default BACnetBinaryPV 0 Read/Write Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

Timer Unoccupied Mode Description Type Default Access Object_Indentifier Timer value in minutes used to count BACnetObjectIdentifier 212zzcc Read Object_Name down time when override is initiated by CharacterString TIMER_UNOCC_212zzcc Read Object_Type the space occupant during Unoccupied BACnetObjectType ANALOG_VALUE Read Present_Value Mode. Any 120 Read/Write Status_Flags BACnetStatusFlags 0 Read Event_State BACnetEventState NORMAL Read Out_Of_Service BOOLEAN TRUE Read Units BACnetEngineeringUnits minutes Read Priority_Array BACnetPriorityArray Read Relingquish_Default BACnetBinaryPV 0 Read/Write Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

Timer Occupied Mode Description Type Default Access Object_Indentifier Timer value in minutes used to count BACnetObjectIdentifier 213zzcc Read Object_Name down time when override is initiated by CharacterString TIMER_OCC_213zzcc Read Object_Type the space occupant during Occupied BACnetObjectType ANALOG_VALUE Read Present_Value Mode. Any 120 Read/Write Status_Flags BACnetStatusFlags 0 Read Event_State BACnetEventState NORMAL Read Out_Of_Service BOOLEAN TRUE Read Units BACnetEngineeringUnits minutes Read Priority_Array BACnetPriorityArray Read Relinquish_Default BACnetBinaryPV 0 Read/Write Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

Daylight Harvesting Setpoint Description Type Default Access Object_Identifier Daylight harvesting setpoint in foot BACnetObjectIdentifier 220zzcc Read Object_Name candles. CharacterString DAY_HARVEST_SETPT_220zzcc Read Object_Type BACnetObjectType ANALOG_VALUE Read Present_Value Any 0 Read/Write Status_Flags BACnetStatusFlags 0 Read

6 of 10 Daylight harvesting setpoint in foot candles. Master BACnet Points List

Event_State BACnetEventState NORMAL Read Out_Of_Service BOOLEAN TRUE Read Units BACnetEngineeringUnits foot candles Read Priority_Array BACnetPriorityArray Read Relinquish_Default BACnetBinaryPV 0 Read/Write Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

7 of 10 Master BACnet Points List

Schedule Description Type Default Access Object_Identifier Controls mode of operation based on BACnetObjectIdentifier 310zz00 Read Object_Name schedule. On is when occupants are CharacterString SCHEDULE_310zz00 Read Object_Type expected present. Off when occupants BACnetObjectType SCHEDULE Read Present_Value are expected not present. Any 0 Read Effective_Period BACnetDateRange Read/Write Weekly_Schedule BACnetARRAY[7] of BACnetDailySchedule Read/Write Exception_Schedule BACnetARRAY[N] of BACnetSpecialEvent Read/Write Schedule_Default Any 0 Read List_Of_Object_Property_References BACnetLIST of BACnetDeviceObjectPropertyReference Read Priority_For_Writing Unsigned (1..16) 16 Read Status_Flags BACnetStatusFlags Read Reliability BACnetReliability Read Out_Of_Service BOOLEAN FALSE Read Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

Occupied/Unoccupied Mode Source Description Type Default Access Object_Identifier Determines whether the Channel's BACnetObjectIdentifier 330zzcc Read Object_Name mode is determined by Remote CharacterString OCCUNOCC_MODE_SOURCE_330zzcc Read Object_Type Command, Schedule or Remote BACnetObjectType MULTISTATE_VALUE Read Present_Value Command with Schedule Fallback. In Unsigned 1 Read/Write Status_Flags the later instance, Fallback is initiated BACnetStatusFlags 0 Read Event_State when the Remote Command is not BACnetEventState NORMAL Read Out_Of_Service refreshed within 2 minutes. BOOLEAN FALSE Read Number_Of_States Unsigned 3 Read [1]Remote Command State_Text BACnetARRAY[N] of CharacterString [2]Local Schedule Read [3]Remote with Local Schedule Fallback Priority_Array BACnetPriorityArray Read Relinquish_Default Unsigned 0 Read/Write Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

8 of 10 Master BACnet Points List

Virtual Station On Off Description Type Default Access Object_Identifier This commandable object is used to BACnetObjectIdentifier 340tttb Read Object_Name either toggle the on/off state of the CharacterString VS_ON_OFF_340tttb Read Object_Type channel, or to directly set the state to BACnetObjectType MULTISTATE_VALUE Read Present_Value either on or off. The purpose is to Unsigned 1 Read/Write Status_Flags allow the system designer to provide a BACnetStatusFlags 0 Read Event_State virtual on/off button from a BACnet BACnetEventState NORMAL Read Out_Of_Service source other than a physical station. BOOLEAN FALSE Read Number_Of_States Unsigned 3 Read [1]Toggle State_Text BACnetARRAY[N] of CharacterString [2]On Read [3]Off Priority_Array BACnetPriorityArray Read Relinquish_Default Unsigned 0 Read/Write Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

Virtual Station Indicator LED Description Type Default Access Object_Identifier This object provides indication as to BACnetObjectIdentifier 341tttb Read Object_Name whether the Station Button should light CharacterString VS_BUTTON_INDICATOR_341tttb Read Object_Type or unlight its indicator LED. BACnetObjectType MULTISTATE_VALUE Read Present_Value Unsigned 1 Read Status_Flags BACnetStatusFlags 0 Read Event_State BACnetEventState NORMAL Read Out_Of_Service BOOLEAN FALSE Read Number_Of_States Unsigned 3 Read [1]Off [2]On State_Text BACnetARRAY[N] of CharacterString Read [3]Flash [4]Dim Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

9 of 10 Master BACnet Points List

Virtual Station Level Set Description Type Default Access Object_Identifier This commandable object is used to BACnetObjectIdentifier 342tttb Read Object_Name either set the channel light level CharacterString VS_LEVEL_SET_342tttb Read Object_Type percentage directly, or to increment BACnetObjectType MULTISTATE_VALUE Read Present_Value the level up or down by a fixed Unsigned 0 Read/Write Status_Flags percentage. The purpose is to allow BACnetStatusFlags 0 Read Event_State the sytsem designer to provide BACnetEventState NORMAL Read Out_Of_Service raise/lower functionality from a BACnet BOOLEAN FALSE Read Number_Of_States source other than a physical station. Unsigned 110 Read [1]1 percent [2]2 percent … [100]100 percent [101]-5 percent change [102]-4 percent change [103]-3 percent change State_Text BACnetARRAY[N] of CharacterString Read [104]-2 percent change [105]-1 percent change [106}+1 percent change [107]+2 percent change [108]+3 percent change [109]+4 percent change [110]+5 percent change Priority_Array BACnetPriorityArray Read Relinquish_Default Unsigned 0 Read/Write Property_List BACnetARRAY[N] of BACnetPropertyIdentifier Read

Note - Whether a given input is exposed as a BV or an AV is based on input configuration.

10 of 10 BACnet Protocol Implementation Conformance Statement

Date: March 30, 2015 Vendor Name: Blue Ridge Technologies International Product Name: Aperio Product Model Number: ZC, RP, RK, RI Application Software Version: NA Firmware Revision: 1.3.x BACnet Protocol Revision: 135-2010 rev. 12

Product Description:

The Aperio Controller Board is a general purpose lighting controller used across the Blue Ridge Technologies product line. This product supports native BACnet connecting directly to the MS/TP LAN. All standard MS/TP baud rates are supported. All B-AAC required objects are supported. The quantities of each object available are dependent upon factory configuration since this Aperio Controller Board can be provided in products with differing lighting zone and channel capacities.

BACnet Standardized Device Profile (Annex L):

 BACnet Operator Workstation (B-OWS)  BACnet Advanced Operator Workstation (B-AWS)  BACnet Operator Display (B-OD)  BACnet Building Controller (B-BC) X BACnet Advanced Application Controller (B-AAC)  BACnet Application Specific Controller (B-ASC)  BACnet Smart Sensor (B-SS)  BACnet Smart Actuator (B-)

List all BACnet Interoperability Building Blocks Supported (Annex K): DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM-B, DS-COV-B, DS-COVU-B, AE-N-I-B, AE-ACK-B, AE-INFO-B, SCHED-I-B, DM-DDB-B, DM-DOB-B, DM-DCC-B, DM-TS-B, DM-UTC-B

Segmentation Capability:

 Able to transmit segmented messages Window Size  Able to receive segmented messages Window Size

Standard Object Types Supported:

Objects are not creatable nor deletable using the CreateObject or the DeleteObject services.

Object/Property Support Matrix

The following table summarizes the Object Types/Properties supported:

Object Type Multi Property Binary Analog Device State Schedule Value Value Value Object_Identifier X X X X X Object_Name X X X X X

Page 1 of 7

BACnet Protocol Implementation Conformance Statement

Object_Type X X X X X System_Status X Vendor_Identifier X Model_Name X Firmware_Revision X Application_Software_Version X Protocol_Version X Protocol_Revision X Protocol_Services_Supported X Object_Types_Supported X Object_List X Max_APDU_Length_Accepted X Segmentation_Supported X Local_Time X Local_Date X UTC_Offset X Daylight_Savings_Status X APDU_Timeout X Number_Of_APDU_Retries X Max_Master X Max_Info_Frames X Device_Address_Binding X Database_Revision X Configuration_Files X Last_Restore_Time X Backup_Failure_Timeout X Present_Value X X X X Status_Flags X X X X Event_State X X X Out_Of_Service X X X Number_Of_States X Priority_Array X* X* X* Relinquish_Default X* X* X* Units X Date_List Effective_Period X Weekly_Schedule X Execption_Schedule X Schedule_Default X List_Of_Object_Property_Ref X Priority_For_Writing X Reliability X Out_Of_Service X Notification_Class X X Event_Enable X X Acked_Transitions X X Notify_Type X X Event_Time_Stamps X X Time_Delay X X Alarm_Value X High_Limit X Low_Limit X Deadband X

Page 2 of 7

BACnet Protocol Implementation Conformance Statement

Limit_Enabled X Property_List X X X X X

* For commandable values only.

Device Object Summary

The following table summarizes the Device Object supported (see Instance Key for values of nnnn and aaa):

Instance ID Object Name 132aaa nnnn_DEVICE_OBJECT_132aaa

Binary Value Instance Summary

The following table summarizes the Binary Value Objects supported (see Instance Key for values of ss, xx, zz and cc):

Present Value Instance ID Object Name Description Access Type Indicates the status of a binary input, either 100ssxx DIGITAL_INPUT_100ssxx R on or off. Indicates whether a given load relay is open or closed. On indicates the relay 110ssxx LOAD_STATUS_110ssxx R is closed. Off indicates the relay is open. Indicates the status of a line voltage 120ssxx LINE_VOLTAGE_INPUT_120ssxx R input, either on or off. Indicates the status of a Channel, either 200zzcc CHANNEL_STATUS_200zzcc R lights on or lights off. Controls mode of operation. On is when occupants are expected present. 300zz00 RUN_COMMAND_300zz00 C Off when occupants are expected not present. NOTE: For Present Value Access Types, R = Read-only, W = Writeable, C = Commandable. Commandable values support priority arrays and relinquish defaults.

Analog Value Instance Summary

The following table summarizes the Analog Value Objects supported (see Instance Key for values of ss, xx, zz and cc):

Present Value Instance ID Object Name Description Units Access Type Indicates the status value of 100ssxx ANALOG_INPUT_100ssxx R an analog input. Indicates the lighting output 201zzcc CHANNEL_LEVEL_201zzcc Percent level for a channel. Timer value used to count 210zzcc OCC_TIMER_OCC_MODE_210zzcc down time during occupied Minutes C mode as occupancy timer

Page 3 of 7

BACnet Protocol Implementation Conformance Statement

times out. Timer value used to count down time during 211zzcc OCC_TIMER_UNOCC_MODE_211zzcc Minutes C unoccupied mode as occupancy timer times out. Timer value in minutes used to count down time 212zzcc TIMER_UNOCC_212zzcc when override is initiated Minutes C by the space occupant during Unoccupied Mode. Timer value in minutes used to count down time 213zzcc TIMER_OCC_213zzcc when override is initiated Minutes C by the space occupant during Occupied Mode. Daylight harvesting Foot 220zzcc DAY_HARVEST_SETPT_220zzcc C setpoint. Candles NOTE: For Present Value Access Types, R = Read-only, W = Writeable, C = Commandable. Commandable values support priority arrays and relinquish defaults.

Schedule Instance Summary

The following table summarizes the Schedule Objects supported (see Instance Key for values of zz):

Date_List Instance ID Object Name Description Access Type Schedules to be assigned to 310zz00 SCHEDULE_310zz00 W lighting zones. NOTE: For Present Value Access Types, R = Read-only, W = Writeable, C = Commandable. Commandable values support priority arrays and relinquish defaults.

Occupied/Unoccupied Mode Source Instance Summary

The following table summarizes the Occupied/Unoccupied Mode Sources supported (see Instance Key for values of zz and cc):

Date_List Instance ID Object Name Description Access Type 330zzcc OCCUNOCC_MODE_SOURCE_330zzcc Occupied/Unoccupied mode C NOTE: For Present Value Access Types, R = Read-only, W = Writeable, C = Commandable. Commandable values support priority arrays and relinquish defaults.

Virtual Station Instance Summary

The following table summarizes the Virtual Stations supported (see Instance Key for values of ttt and b):

Date_List Instance ID Object Name Description Access

Page 4 of 7

BACnet Protocol Implementation Conformance Statement

Type 340tttb VS_ON_OFF_340tttb Virtual Station On/Off C 341tttb VS_BUTTON_INDICATOR_341tttb Virtual Station Indicator LED R 342tttb VS_LEVEL_EST_342tttb Virtual Station Level Set C NOTE: For Present Value Access Types, R = Read-only, W = Writeable, C = Commandable. Commandable values support priority arrays and relinquish defaults.

Instance Key

The following tables provide range of values exposed in BACnet Object IDs and Object Names by Product:

Device Device Name cc - aaa - nnnn - Product zz -Zone Channel ss - Slot Address Name ZCSB 01 01 - 08 00 000 - 099 ZCSB ZCSS 01 - 02 01 - 08 00 - 03 000 - 099 ZCSS ZCDS 01 - 02 01 - 08 00 - 03 000 - 099 ZCDS ZCDE 01 - 04 01 - 08 00 - 07 000 - 099 ZCDE RPSB 01 - 64 01 - 08 00 000 - 099 RPSB RPSS 01 - 64 01 - 08 00 - 16 000 - 099 RPSS RPDS 01 - 64 01 - 08 00 - 16 000 - 099 RPDS RKUN 01 - 64 01 - 08 00 - 16 000 - 099 RKUN RKUS 01 - 64 01 - 08 00 - 16 000 - 099 RKUS

Line Digital Load Voltage Analog Input Status Input Input xx - xx - xx - xx - Product Instance Instance Instance Instance ZCSB 01 - 06 01 - 02 01 - 02 01 - 06 ZCSS 01 - 06 01 - 02 01 - 02 01 - 06 ZCDS 01 - 06 01 - 02 01 - 02 01 - 06 ZCDE 01 - 06 01 - 02 01 - 02 01 - 06 RPSB 01 - 24 NA NA 01 - 24 RPSS 01 - 24 NA NA 01 - 24 RPDS 01 - 24 NA NA 01 - 24 RKUN 01 - 24 NA NA 01 - 24 RKUS 01 - 24 NA NA 01 - 24

SCSS 01 - 06 01 - 02 01 - 02 01 - 06 SCDS 01 - 06 01 - 02 01 - 02 01 - 06 LEXP32 01 - 32 NA NA NA

b – Button or Button Product Set CTS1CH 1 CTS2CH 1 - 2 CTS3CH 1 - 3 CTS4CH 1 - 4

Page 5 of 7

BACnet Protocol Implementation Conformance Statement

CTS6CH 1 - 6 CTS1RL 1 CTS2RL 1 - 2 CTS3PR 1 - 4 CTS6PR 1 - 6

Data Link Layer Options:

 BACnet IP, (Annex J)  BACnet IP, (Annex J), Foreign Device  ISO 8802-3, Ethernet (Clause 7)  ATA 878.1, 2.5 Mb. ARCNET (Clause 8)  ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s) ______X MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 57600, 76800, 115200  MS/TP slave (Clause 9), baud rate(s):  Point-To-Point, EIA 232 (Clause 10), baud rate(s):  Point-To-Point, modem, (Clause 10), baud rate(s):  LonTalk, (Clause 11), medium: ______ BACnet/ZigBee (ANNEX O)  Other:

Device Address Binding:

Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.)  Yes X No

Networking Options:

 Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.  Annex H, BACnet Tunneling Router over IP  BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices?  Yes  No Does the BBMD support network address translation?  Yes  No

Network Security Options:

X Non-secure Device - is capable of operating without BACnet Network Security  Secure Device - is capable of using BACnet Network Security (NS-SD BIBB)  Multiple Application-Specific Keys:  Supports encryption (NS-ED BIBB)  Key Server (NS-KS BIBB)

Character Sets Supported:

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

X ISO 10646 (UTF-8)  IBM/Microsoft DBCS  ISO 8859-1

Page 6 of 7

BACnet Protocol Implementation Conformance Statement

 ISO 10646 (UCS-2)  ISO 10646 (UCS-4)  JIS X 0208

If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports: ______

Page 7 of 7