Low Voltage Switchboards and Switchgear

1.0 CMP Switchboards...... 1-3 1 Standards and Certifications...... 1-4 Product Selection...... 1-4 Technical Data and Specifications...... 1-5 Layouts and Dimensions...... 1-6 2.0 Pow-R-Line CS Switchboards...... 2-9 2 Standards and Certifications...... 2-10 Product Selection and Specifications...... 2-10 Layouts and Dimensions...... 2-14 3.0 Pow-R-Line C Switchboards...... 3-19 3 Standards and Certifications...... 3-21 Product Selection...... 3-22 Technical Data and Specifications...... 3-25 4.0 Commercial Metering Switchboards...... 4-29 4 Standards and Certifications...... 4-30 Product Selection...... 4-30 Dimensions...... 4-30 5.0 Integrated Facility Switchboards...... 5-31 5 Features, Benefits and Functions...... 5-32 Options...... 5-32 Standards and Certifications...... 5-32 Product Selection...... 5-33 Technical Data and Specifications...... 5-41 6.0 Pow-R-Line C Switchboards with 6 Drawout Moulded-Case ...... 6-43 Standards and Certifications...... 6-44 Product Selection...... 6-45 Technical Data and Specifications...... 6-45 Dimensions...... 6-45 7.0 Generator Connection Assemblies 7 Generator Quick Connect Switchboards...... 7-48 Standards and Certifications...... 7-49 Product Selection...... 7-49 Technical Data and Specifications...... 7-49 Dimensions...... 7-49 Customer Service Termination Enclosure...... 7-50 Roll-Up Generator Quick Connect Assembly...... 7-52 8.0 Pow-R-Line C Switchgear...... 8-55 8 Standards and Certifications...... 8-58 Optional Breaker Accessories...... 8-58 Dimensions...... 8-60 9.0 Switchboard Accessories and Modifications...... 9-61 9 Moulded-Case Circuit Breakers Magnum Power Circuit Breakers...... 9-64 Trip Units...... 9-65 Fusible ...... 9-71 Surge Protection Devices...... 9-75 Metering...... 9-76

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 1-1

Low Voltage Switchboards and Switchgear CMP Switchboards

CMP-A1 Switchboard CMP-A2 Switchboard Contents 1 Description Page Standards and Certifications...... 1-4 2 Product Selection...... 1-4 Technical Data and Specifications...... 1-5 3 Layouts and Dimensions...... 1-6 4 5 6 7 8 9 1

CMP Switchboards 1

Product Description Features, Benefits sprinklerproof, & components totally front 1 Eaton’s CMP switchboard and Functions NEMA 3R optional accessible to enable the combines all three The service entrance • Sealing screws, knurled panel to be installed against 1 components of a service panel is CSA® approved thumb screws and the wall. Freestanding option entrance application into a and completely factory padlock hasp is available for 18" deep enclosure. 1 single cell, including a main assembled. Barriers are • Utility ground stud service compartment, a provided to isolate the • Hydro stubs are available All covers are painted 1 utility metering section and main disconnect, the utility • Distribution cell ANSI 61 grey. the distribution feeders, metering compartment accommodates Eaton’s providing the most flexible System 1 and the distribution Series C and Series G and compact footprint for section into three separate breakers, fusible switches • Tin-plated aluminum the entire service entrance compartments. The design (FDPW), metered switches 1 switchboard. • allows for the assembly up to 200A (FSMC) Silver-flashed copper to be reversed in the field and chassis-mounted • Tin-plated copper 1 Application Description without modification and panelboards to accommodate either top Eaton's CMP switchboard is or bottom entry of service • User metering (refer to Tab Main Breaker 1 ideally suited to commercial entrance cables. 9-Components, or contact Eaton type main breaker, and industrial applications Eaton for more information) maximum 800A (CMP-A1) 1 such as: • Freestanding (18"D Only) • Surge protection devices or 1200A (CMP-A2) with • Light Commercial • Compact and (refer to Tab 9-Components, standard thermal-magnetic or 1 space-efficient or contact Eaton for more solid-state trip units available. • Retail • Top or bottom entry information) The trip unit on the standard 1 • Shopping Plaza • Meets the provincial • Door-Over-Distribution thermal-magnetic breaker and municipal metering • Special Colours may be changed; however, 1 • Shopping Centers requirements all power to the switchboard must be disconnected prior to • Accommodates a variety • Institutions / Schools Enclosure removal of the breaker cover. 1 of utility CTs and PTs • Agricultural The service entrance • CSA approved up to switchboard is standard CSA The main breaker section 1 • Small buildings 800A (CMP-A1) and Type 1 & sprinklerproof, and comes complete with 1200A (CMP-A2) at NEMA 3R is optional. The provisions for padlocking • Sports and entertainment 1 600 Vac CSA Type 1 & sprinkerproof the main breaker and the facilities • Main breaker maximum options are fabricated sealing screws on the front 800A (CMP-A1) and from code gauge formed cover. Grounding is supplied 1 1200A (CMP-A2) galvanized steel, complete with a removable disconnect link to ground the neutral, • Breakers are padlockable with flat covers to form a rigid 1 the service conduit and the to ensure maximum deadfront totally enclosed system ground. security structure. 1 • Standard enclosure All compartments are ratings of CSA Type 1 & designed to make 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 1-3 Low Voltage Switchboards and Switchgear CMP Switchboards

1 Utility Metering Compartment Distribution Section Standards and Certifications Product Selection The utility metering The distribution section • CSA C22.2 No. 31 Description Type compartment is designed accepts the installation • CSA C22.2 No. 244 2 to meet the provincial of circuit breakers on a 800A maximum at 600 Vac CMP-A1 • CSA C22.2 No. 229 and municipal utility Pow-R-Line 4 type interior. 1200A maximum at 600 Vac CMP-A2 3 requirements. It is bussed A flat cover is supplied and and pre-drilled to accept any space not occupied by Breaker Accessories standard bus type current a feeder breaker has a filler 4 • Padlock hasp . Utility CTs plate, allowing no access to and PTs can be easily parts when energized. • Visible windows 5 factory or field installed. The • Electronic trip units The distribution section compartment has provisions • Shunt trip accommodates 14 three-pole 6 for sealing the front cover, • Auxiliary and the cover has a hinged breakers (“21X” of circuit • Bell alarm 7 door for easy access. breaker distribution space; 1X = 1-3/8 inch). • Undervoltage release 8 Metering options include: • CTs—window type and 9 bar type • External clamp-on CTs to 1 verify meter • Up to four PTs in utility 1 compartment • Neutral and ground 1 studs available Utility specific options:

1 • Standard • BC Hydro 1 • Hydro Quebec 1 • Alectra utilities 1 1 1 1 CMP-A1 CMP-A2 1 1 1 1 1 1 1 1 1 1 1

1-4 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear CMP Switchboards

Technical Data and Specifications 1 Rating Breaker Options CMP-A2 2 The service entrance panel bus is rated to 800A (CMP-A1), Device Ampere kA Value Mounting 1200A (CMP-A2), 600V, three-phase, four-wire, 60 Hz. Type Rating 240V 600V Height a 3 Main Breakers Interrupting Rating KD Frame 70–400 b 65–200 25–65 4X 4 • Maximum 65 kA at 600V LD Frame 300–600 65–200 25–50 6X • Maximum 200 kA at 240V LG Frame 250–600 65–200 18–65 4X 5 MDL Frame 300–800 c 65–100 25–35 6X Breaker Options CMP-A1 NG Frame 500–1200 65–200 25–65 6X 6 Branch Breakers Device Ampere kA Value Mounting Type Rating 240V 600V Height FD Frame 15–225 18–200 14–35 3X 7 Main Breakers JD Frame 70–250 65–200 18–35 3X b KD Frame 70–400 b 65–200 25–65 4X KD Frame 70–400 65–200 25–65 4X 8 LD Frame 300–600 65–200 25–50 6X LD Frame 300–600 65–200 25–50 6X LG Frame 250–600 65–200 18–65 4X LG Frame 250–600 65–200 18–65 4X 9 c MDL Frame 300–800 c 65–100 25–35 6X MDL Frame 300–800 65–100 25–35 6X NG Frame 320–800 65–200 25–65 6X NG Frame 500–1200 65–200 25–65 6X 1 Branch Breakers Branch Fusible Switches-CMP A2 1 FD Frame 15–225 18–200 14–35 3X JD Frame 70–250 65–200 18–35 3X Device Cell Width Mounting Type 38-Inch 44-Inch Height a 1 KD Frame 70–400 b 65–200 25–65 4X LD Frame 300–600 65–200 25–50 6X 30/30A twin Y Y 4X 1 LG Frame 250–600 65–200 18–65 4X 30/60A twin Y Y 4X 60/60A twin Y Y 4X 100/100A twin Y Y 5X 1 200A (single or twin) Y Y 6X 1 FSMC Device Options CMP-A2 400A Y Y 9X Ampere Single 600A Y Y 11X Rating or Twin X Space a 1 800A N Y 11X 30/30 Twin 7X 1200A N Y 15X 1 30/60 Twin 7X NNote 60/30 Twin 7X a 1X = 1-3/8 inch. 1 60/60 Twin 7X b Ampere ratings below 100A available with electronic trip unit only. 100/100 Twin 7X c Ampere ratings below 400A available with thermal-magnetic only. 1 200 Single 7X 1 1 1 1 Twin 30A, 60A or 100A FSMC Switch 1 1 1 1

Single 200A FSMC Switch 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 1-5 Low Voltage Switchboards and Switchgear CMP Switchboards

Dimensions (CSA Type 1 & Sprinklerproof) 1 Approximate Dimensions in Inches (mm)

2 Layout A: Top-Fed CMP-A1 Main/PUC/21X Layout B: Bottom-Fed CMP-A1 Main/PUC/21X Distribution (800A Maximum at 600 Vac) Distribution (800A Maximum at 600 Vac) 3 4 5 6 7 8 9 1 1 1 1 1 Layout C: Top-Fed CMP-A2 Main/PUC/21X Layout D: Bottom-Fed CMP-A2 Main/PUC/21X 1 Distribution (1200A Maximum at 600 Vac) Distribution (1200A Maximum at 600 Vac) 1 1 1 1 1 1 1 1 1

b 1 b

1 NNote a 1X = 1-3/8 inch 1 b Bottom-fed: Only 2 rows of twin 100A or single 200A FSMC. Top fed: Only 1 row of single 200A or twin 100A FSMC 1 c For NEMA 3R dimensions consult your local Eaton sales representative 1 1

1-6 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear CMP Switchboards

Dimensions (CSA Type 1 & Sprinklerproof) Approximate Dimensions in Inches (mm) 1

Layout E: Top-Fed CMP-A2 Main/40X Layout F: Bottom-Fed CMP-A2 Main/40X 2 Distribution (1200A Maximum at 600 Vac) Distribution (1200A Maximum at 600 Vac) 3 4 5 6 7 8 9 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 1-7 Low Voltage Switchboards and Switchgear CMP Switchboards

1 This page intentionally left blank. 2 3 4 5 6 7 8 9 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

1-8 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Pow-R-Line CS Switchboards

Pow-R-Line CS Switchboards Contents 1 Description Page Standards and Certifications...... 2-10 2 Product Selection and Specifications...... 2-10 Layouts and Dimensions...... 2-14 3 4 5 6 7 8 9 1

Pow-R-Line CS Switchboards 1

Product Description Application Description Features, Benefits • Breakers are padlockable 1 Eaton’s Pow-R-Line CS The Pow-R-Line CS and Functions to ensure maximum security switchboard is the most switchboard is ideally suited • Compact and space- 1 compact expandable service to commercial and industrial efficient • Distribution cell entrance and distribution applications such as: • Top or bottom entry accommodates Eaton’s 1 solution in Canada. Eaton’s • Light Commercial Series C and Series G Pow-R-Line CS switchboard • Meets the provincial breakers, fusible switches 1 is a compact solution that • Retail and municipal metering (FDPW), metered switches offers main device, utility requirements up to 200A (FSMC) • 1 metering, and distribution in Shopping Plaza and chassis-mounted a single cell. Additionally, the • Utility ground stud • Shopping Centers panelboards switchboard is expandable • 75°C or 90°C wireway 1 to include a 75°C or • Institutions / Schools • User metering (refer to 90°C wireway, sub-main, • Main breaker maximum Tab 9-Components, or 1 distribution, and fusible • Agricultural 400, 600, 800, or 1200A contact Eaton for more switch metercenter cells for information) • Small buildings • Optional distribution cell, a complete offering. Eaton’s 1 sub-main cell with utility • Surge protection Pow-R-Line CS Switchboard • Sports and entertainment compartment, wire way, uses a space-saving design devices (refer to Tab 1 facilities pull boxes, fusible switch to provide a smaller footprint 9-Components, or meter center (FSMC) than any other comparable contact Eaton for more information) 1 switchboards in the market. • Convenient space for utility CTs and PTs • Door-Over-Distribution 1 • Sealing screws, knurled • Special Colours thumb screws and padlock 1 hasp • Cross-bus for future expansion • Standard enclosure 1 ratings of CSA Type 1; • Freestanding (18”D Only) sprinklerproof optional • Fire pump breaker in 1 • Nema 3R (Available only wireway (up to 400A) for single cell or incoming 1 through wireway) 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 2-9 Low Voltage Switchboards and Switchgear Pow-R-Line CS Switchboards

Enclosure Utility Metering Provisions: Special Dimensions and • Ability to add surge 1 Standard enclosure is CSA® • Meets all provincial and Configurations: protection and user Type 1; sprinklerproof. municipal utility metering metering in the distribution Eaton has the ability to offer 2 Nema Type 3R is optional, requirements section custom dimensions to suit and available only for single • Optional door-over- • Utility ground studs limited space requirements. cell or incoming through distribution 3 available Special heights, special wireway. Freestanding option • • Utility CTs and PTs can depths, widths, and corner Optional cross-bus for is available for 18” deep 4 be easily factory or field sections. future expansion enclosure. installed • 12” or 18” depth 5 • PUC Utility metering Standards and Certifications: • 48” width Finish options include: • CSA C22.2 No. 31 • CTs-window type and 6 Standard: • CSA C22.2 No. 244 Pow-R-Line CS – 50X bar type Distribution Cell: Galvanized steel tub. • CSA C22.2 No. 229 • External clamp-on CTs • Pow-R-Line 1A / 2A 7 All doors and covers have to verify meter chassis a grey paint finish (ANSI 61) 8 • Up to four PTs in utility • 50X distribution section using a modern, completely compartment automated and continuously configurable for metered 9 monitored electrostatic • Neutral and ground fusible switches (FSMC), powdered coating. studs available non-metered fusible 1 This continually monitored switches (FDPW) or circuit system includes spray Breaker Accessories: breakers (not mixed) de-grease and clean, spray • Padlock hasp • Ability to add surge 1 Additional Sections: rinse, iron phosphate spray • Visible windows protection and user metering in the distribution coating rinse, nonchemical • Electronic trip units 1 seal, oven drying, Pow-R-Line CS - Wireway: section • Shunt trip electrostatic powder spray • Direct cable connection or • Optional door-over- 1 paint coating and oven curing. • Auxiliary switch wireway distribution • Bell alarm • 75°C rated (standard) or • Optional cross-bus for 1 Optional: • Undervoltage release 90°C rated (optional) future expansion Assembly can be painted • Factory bussing to • 12” or 18” depth 1 any colour required by the Considerations: disconnect / circuit breaker • 30”W, 38”W, or 48”W customer. Arc flash is an ongoing in main assembly depending on the feeder 1 concern in the electrical • 30”D X 30”W design device configuration and industry. Eaton offers a available for specific utility amperage Busbar System 1 variety of solutions to reduce requirements • Tin-plated aluminum the risk of arc flash such • 12”, 18”, or 30” depth Pow-R-Line CS – Sub-main cell • Silver-flashed copper as the Arcflash Reduction (30”D available only at with 600A max. breaker: 1 • Tin-plated copper Maintenance System™ 30”W) • 80% Rated sub-main in Eaton’s moulded-case • Width options: 1 Main Breaker: breakers. disconnect, up to 600A • 800A: 12”W, circuit breaker Main breaker up to 1200A, 18”W, 24”W, • Includes reverse fed 1 80% or 100% rated. Advanced Metering and 30”W × 30”D breaker, utility metering Communications: NNote: For 100% rating, • 1200A: 24”W, or compartment and 1 incoming wireway required. Eaton has an extensive line of 30”W × 30”D outgoing lugs powerful metering products, • PUC Utility metering 1 trip units, controllers and Customer Metering: Pow-R-Line CS – 1200A • Field wiring connection gateways, that can be wired Main/40X Distribution Cell: Full line of Eaton together in switchboards to compartment 1 microprocessor-based create an intelligent system • Service entrance rated • Optional door-over- customer metering and and interface with building main compartment distribution 1 monitoring devices. management and SCADA • Main circuit breaker • Optional cross-bus for Please refer to Tab 9— systems. (400, 600, 800 or 1200A) future expansion 1 Components, or contact • Top or bottom, left or • 12” or 18” depth Eaton for more information. Provision for Future Devices right cable entry Chassis/Group Mounted: • 30” width 1 • 1200A, 100% rated main Surge Protection Device Where a provision for future available when a wireway 1 (SPD): circuit protective devices is selected. Standard integrated surge is required, the space and • 40X distribution section 1 protection device with a blank filler plate will be configurable for metered integral disconnect is supplied. Connections and fusible switches (FSMC), available if required. mounting hardware are not non-metered fusible 1 Tab 9—Components, included. switches (FDPW) or circuit or contact Eaton for more breakers (not mixed) 1 information.

2-10 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Pow-R-Line CS Switchboards

Technical Data and Specifications 1 Rating Breaker Options Pow-R-Line CS 2 The service entrance panel bus is rated to 800A, 1200A, Device Ampere kA Value Mounting 600V, three-phase, four-wire, 60Hz. Type Rating 240V 600V Height a 3 Main Breakers Interrupting Rating KD Frame 70–400 b 65–200 25–65 4X 4 • Maximum 65 kA at 600V LD Frame 300–600 65–200 25–50 6X • Maximum 200 kA at 240V LG Frame 250–600 65–200 18–65 4X 5 MDL Frame 300–800 c 65–100 25–35 6X FSMC Device Options Pow-R-Line CS NG Frame 320–800 65–200 25–65 6X 6 Ampere Single NG Frame 500–1200 65–200 25–65 6X d Rating or Twin X Space a Branch Breakers 7 30/30 Twin 7X FD Frame 15–225 18–200 14–35 3X 30/60 Twin 7X JD Frame 70–250 65–200 18–35 3X 8 60/30 Twin 7X KD Frame 70–400 b 65–200 25–65 4X 60/60 Twin 7X LD Frame 300–600 65–200 25–50 6X 9 100/100 Twin 7X LG Frame 250–600 65–200 18–65 4X 200 Single 7X MDL Frame 300–800 c 65–100 25–35 6X 1 NG Frame 320–800 65–200 25–65 6X NG Frame 500–1200 65–200 25–65 6X d 1

Branch Fusible Switches-Pow-R-Line CS 1

Device Cell Width Mounting Type 38-Inch 48-Inch Height a 1 30/30A twin Y Y 4X 30/60A twin Y Y 4X 1 Twin 30A, 60A or 100A FSMC Switch 60/60A twin Y Y 4X 1 100/100A twin Y Y 5X 200A (single or twin) Y Y 6X 1 400A Y Y 9X 600A Y Y 11X 1 800A N Y 11X 1200A N Y 15X 1 NNote Single 200A FSMC Switch a 1X = 1-3/8 inch. 1 b Ampere ratings below 100A available with electronic trip unit only. c Ampere ratings below 400A available with thermal-magnetic only. 1 d Only available for 1200A Cell 1 1 1 1 1 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 2-11 Low Voltage Switchboards and Switchgear Pow-R-Line CS Switchboards

Dimensions (CSA Type 1 & Sprinklerproof) 1 Approximate Dimensions in Inches (mm)

2 Layout Ae: Top-Fed Pow-R-Line CS Main/PUC/21X Layout Be: Bottom-Fed Pow-R-Line CS Main/PUC/21X Distribution (800A Maximum at 600 Vac) Distribution (800A Maximum at 600 Vac) 3 4 5 6 7 8 9 1 1 1 1 1 Layout Ce: Top-Fed Pow-R-Line CS Main/PUC/21X Layout De: Bottom-Fed Pow-R-Line CS Main/PUC/21X 1 Distribution (1200A Maximum at 600 Vac) Distribution (1200A Maximum at 600 Vac) 1 1 1 1 1 1 1 1 1

b 1 b

1 NNote a 1X = 1-3/8 inch 1 b Bottom-fed: Only 2 rows of FSMC metered switches. Top-fed: Only 1 row of FSMC metered switches 1 c For NEMA 3R dimensions consult your local Eaton sales representative 1 1

2-12 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Pow-R-Line CS Switchboards

Dimensions (CSA Type 1 & Sprinklerproof) Approximate Dimensions in Inches (mm) 1

Layout Ee: Top-Fed Pow-R-Line CS Main/40X Layout Fe: Bottom-Fed Pow-R-Line CS Main/40X 2 Distribution (1200A Maximum at 600 Vac) Distribution (1200A Maximum at 600 Vac) 3 4 5 6 7 8 9 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 2-13 Low Voltage Switchboards and Switchgear Pow-R-Line CS Switchboards

Dimensions 1 Approximate Dimensions in Inches (mm)

2 Layout Ae: Bottom-Fed Pow-R-Line CS with Incoming Wire Way Layout Be: Top-Fed Pow-R-Line CS with Incoming Wire Way and Main/PUC/21X Distribution (800A Maximum at 600 Vac) and Main/PUC/21X Distribution (800A Maximum at 600 Vac) 3 4 5 6 7 8 9 1 a 1

1 c c 1

1 Layout Ce: Bottom-Fed Pow-R-Line CS with Incoming Wire Way Layout De: Top-Fed Pow-R-Line CS with Incoming Wire Way and 1 and Main/PUC/21X Distribution (1200A Maximum at 600 Vac) Main/PUC/21X Distribution (1200A Maximum at 600 Vac) 1 1 1 1 1 1

1 a a

1 c c 1 1 NNote 1 a 1X = 1-3/8 inch. b Width of cell is determined by breaker size and trip unit type. For fusible switches 800A and above, 48-inch-wide (1219.2 mm) cell is required. Contact Eaton for more information. 1 c 30”W X 30”D, rear aligned wireway available as an option. 1 1 1

2-14 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Pow-R-Line CS Switchboards

Dimensions (CSA Type 1 & Sprinklerproof) Approximate Dimensions in Inches (mm) 1

Layout Ee: Bottom-Fed Pow-R-Line CS Main/40X Layout Fe: Top-Fed Pow-R-Line CS Main/40X 2 Distribution (1200A Maximum at 600 Vac) Distribution (1200A Maximum at 600 Vac) 3 4 5 6 7 8 9 1 a 1 c c 1 1

Additional Cells 1 50X Distribution Cell Top exit Sub-main cell Bottom exit Sub-main cell 1 (1200 Maximum at 600 Vac) with 600A maximum breaker with 600A maximum breaker 1 1 1 1 1 1

a 1 1

d e b 1 NNote 1 a 1X = 1-3/8 inch. b Width of cell is determined by breaker size and trip unit type. For fusible switches 800A and above, 44-inch-wide (1117.6 mm) cell is required. Contact Eaton for more information. 1 c 30”D X 30”W wireway available as an option. d TBD 1 e TBD 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 2-15 Low Voltage Switchboards and Switchgear Pow-R-Line CS Switchboards

1 Filler 1X Breaker To Fusible Transition, All Widths Sub Panel 2 18 12X Poles BAB 100 Amp QBHW 3 42 Max. GHB, GBH 20X Poles 4 400 Amp. Maximum Bus Rating 1P 1P 1X 5 2P 2P 2X EHD, 6 225 Amp FDB, FD, x Max. HFD, FDC 7 3P 3P 3X FDE, HFDE(3P) Wide B o 8 2P 2P 2X 225 Amp

9 h (609.6 mm) Max. ED, EDH, EDC

1 3P 3P 24-In c 3X

1 250 Amp 2 or 3P 3X JD, HJD, JDC Max. 1 400 Amp Max. DK, KD, HKD, KDC, CKD, CHKD 2 or 3P 4X 1 600 Amp Max. LGE, LGH, LGU 600 Amp LD, HLD, CLD, CHLD, LDC 2 or 3P 6X 1 oad Max. L

1 100 Amp 2 or 3P 2 or 3P 3X

x FCL, FB-P Max. 1 3X 250 Amp

Wide B o JD, HJD, JDC 1 2 or 3P 2 or 3P Max. 4X 400 Amp DK, KD, HKD, KDC, 1 2 or 3P 2 or 3P Max. CKD, CHKD

h (965.2 mm) 400 Amp 6X Max. LCL, LA-P

2 or 3P 38-In c 1 800 Amp MDL, HMDL,

1 Max. CMDL, CHMDL 1200 Amp 2 or 3P 6X NGS, NGH, NGC 1 Max. 1 1 2 or 3P 800 Amp 6X NB-P 1 Max. 1200 Amp NGSC, NGHC, NGCC Max.

1 48-Inch (1219.2 mm) Wide Box 1 Breaker may be used as main.

1 Figure 2-4. Layout for Branch and Horizontally Mounted Main Devices — PRLCS a BAB and QBHW breakers with shunt trips require one additional pole space, i.e., 1-pole is 2-pole size, 2-pole is 3-pole size, and 3-pole is 4-pole size. 1 b If panel contains only BAB or QBHW branch breakers, use a PRL1a panelboard. c GHB and GBH breakers cannot be mixed on same subchassis as BAB, QBHW. 1 d If panel contains only GHB and GBH branch breakers, use a PRL2a panelboard. e When only one single-pole breaker of the group is required on either side of chassis, the single-pole breaker space required changes from 1X to 2X. 1 f Minimum 38-inch (965.2 mm) wide box is required if optional #6 – 300 kcmil lug is required.

2-16 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Pow-R-Line CS Switchboards

Fusible to Breaker Transition 1 1X Requires 1X Filler 2

30A 30A 4X 3 4

60A 60A 4X 5 6 7 200A 6X Main or Branch Switch 8 9

100A 100A 5X 1 1

400A 9X 1

Branch Switch 38-inch (965.2 mm) Wide Box 1

600A 11X 1 Branch Switch 1 1 200A 200A 6X 1 1 400A 9X Main or Branch 1 1 600A 11X Main or Branch 1 1 800A 11X Branch 1 1

1200A 15X Branch 48 Inch (1219.2 mm) Wide Box 1 1

Figure 2-7. Branch and Horizontally Mounted Main Device Layout — PRLCS 1 ● 400 and 600 ampere horizontally mounted feeder switches in 38-inch (965 mm) or 48-Inch (1219.2 mm) wide box. 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 2-17 Low Voltage Switchboards and Switchgear Pow-R-Line CS Switchboards

1 This page intentionally left blank. 2 3 4 5 6 7 8 9 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

2-18 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Pow-R-Line C Switchboards

Pow-R-Line C Switchboard Contents 1 Description Page Standards and Certifications...... 3-21 2 Product Selection...... 3-22 Technical Data and Specifications...... 3-25 3 4 5 6 7 8 9 1

Pow-R-Line C Switchboards 1

Product Description Application Description Features, Benefits • A main moulded-case 1 Eaton Pow-R-Line C™ The Pow-R-Line C and Functions circuit breaker or a main switchboards combine a switchboard is ideally suited fusible switch, within the 1 space-saving design with to commercial and industrial Main Devices sizes listed for panelboard a modular construction and applications such as: design, can be included • Magnum DS power circuit in the panel-mounted 1 increased system ratings breakers, fixed-mounted • Institutions and assembly in lieu of a to provide economical and or drawout, 800A to dependable electrical system school boards separate, individually 1 6000A at 600 Vac mounted unit distribution and protection. • Office towers maximum—100% rated • Health care facilities • Ground fault protection on 1 • Eaton fixed-mounted feeders if required • Retail facilities moulded-case circuit • • Utility breakers up to 2500A, Optional 10X 1 600 Vac maximum (1X = 1-3/8 inch) box • Solar applications available for meters, 1 • Residential • Eaton fusible switches protection and control up to 1200A, 600 Vac • Commercial devices maximum 1 • Industrial • Bolted pressure switches Pow-R-Line C designates up to 4000A a family of distribution 1 • Ground fault protection on switchboards, incorporating main device if required design concepts that fit 1 the ever-increasing need for applications on high Distribution Devices short-circuit systems, while 1 • Moulded-case circuit retaining maximum safety breakers fixed-mounted and convenience throughout 1 up to 2000A, 600 Vac the line. maximum Feeder circuit protective 1 • Moulded-case circuit devices are an assembly breakers drawout up to of units mounted on a 1 600A, 600 Vac maximum panelboard-type base • Fusible switches up to (panelboard construction). 1 1200A, 600 Vac maximum Circuit protective devices • Fusible switched meter are front accessible. 1 sockets (FSMC) up to 200A (48.00-inch-wide cell only) 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 3-19 Low Voltage Switchboards and Switchgear Pow-R-Line C Switchboards

Enclosure Standard Switchboard Height Provision for Busway Surge Protection Device (SPD) 1 Standard enclosure is CSA® The standard Pow-R-Line C Entrance and Exit Standard integrated surge Type 1; sprinklerproof, Type 2, switchboard height is Busway connections to protection device with 2 3R are optional. Structures 90.00 inches (2286.0 mm). switchboard sections include integral disconnect is and formed doors are made Custom height is cutout and drilling in the available if required. Please 3 of code gauge steel. available at 78.00 inches top of the switchboard with refer to Tab 9—Components (1981.0 mm) high. riser connections from the or contact Eaton for more switchboard device or the information. 4 Standard Finish Optional base channels bus, up to the point where Grey paint finish (ANSI 61) 1.00 inch (25.4 mm), the bus duct enters the 5 using a modern, completely 1.50 inches (38.1 mm) switchboard. No connections Transition Cells automated and continuously (standard option) or are furnished external to Transition structures are 6 monitored electrostatic 2.00 inches (50.8 mm) high the switchboard. required for connecting powder coating. This available. Consult Eaton for switchboards to the 7 continually monitored system other options. In all transactions involving secondary of power centre includes spray de-grease busway attached to switch- (dry or fluid and clean, spray rinse, iron boards, it is essential that filled), motor control Provision for Future Devices information regarding 8 phosphate spray coating Chassis/Group Mounted centres, and for other special rinse, nonchemical seal, orientation of the busway switchboard configurations Where a provision for future 9 oven drying, electrostatic with respect to the front such as “L” or “U” shaped circuit protective devices powder spray paint coating of the switchboard be lineups. In some applications, is required, the space and and oven curing. supplied to the coordinating an extra structure complete 1 a blank filler plate will be assembly plant. with connections is required; supplied. Connections and in others, where switchboard Integral Base mounting hardware are NNote: Additional depth to the 1 depth and space permit, only not included. Optional switchboard may be required. The ruggedly formed base the connection conductors insulated main bus is 1 greatly increases the rigidity are required. Refer to factory available if required. On Pow-R-Line C of the structure, reduces switchboards, a bus system for these applications. 1 the possibility of damage is used to connect the bus during the installation of the Busbar System duct to the individually equipment, and is suitable for PLC Transfer Schemes Standard tin-plated aluminum mounted device, the main or 1 rolling, jacking and handling. Advanced PLC-based transfer or copper up to 3000A. sub-main switchboard bus, A lifting angle is bolted and load shedding schemes Standard silver-plated copper or the vertical main bus of 1 onto the top of the bus can be designed for various for 4000A to 6000A. Tin- the panel-mounted circuit compartment structure for applications such as data plated copper also available. protective device panels. increased strength. centres, health care facilities 1 Optional insulated main bus Side or rear hydro stub, and wastewater treatment is available. collector bus, utility wireway plants. HMI is optional for 1 Front Accessible Standard bus and connectors and transformer coordination touch screen monitoring Front accessible switchboards on all switchboards are to Eaton standard cross bus and control of incoming, 1 align at the rear, enabling rated for use on systems are available; consult Eaton tie and feeder power them to be placed against capable of producing up to factory for more information. circuit breakers. Contact 1 a wall (Pow-R-Line C front 50,000A rms symmetrical an Eaton sales engineer accessible). If the main short-circuit current at the Utility Metering Provisions for more information. 1 section is deeper than others, incoming terminals. due to physical size of the • Meets all provincial and main device, the necessary Increased bus short-circuit municipal utility metering Bus Duct Integration 1 off-set in lineup will occur in ratings equal to that of requirements Custom bus duct can be front, and the main section connected switchboard • Utility ground studs integrated into switchboard 1 will be accessible from the devices, up to 200,000A rms available assemblies. Eaton can design side as well as from the front. symmetrical, are available • Utility CTs and PTs and manufacture custom bus 1 Standard front accessible in most Pow-R-Line C can be easily factory or duct flanges to coordinate switchboards will align at switchboards when approved field installed with the bus duct risers of the front and the rear. main devices are installed. a wide range of amperage. 1 Contact Eaton for more information. CSA labeled Customer Metering Rear Accessible 1 switchboard sections are Full line of Eaton Eaton offers rear accessible marked with their applicable microprocessor-based 1 switchboards that align at the short-circuit rating. customer metering and front and the rear. NNote: The short-circuit rating monitoring devices. Please 1 of the switchboard assembly refer to Tab 9—Components, is limited to the interrupting or contact Eaton for more capacity of the lowest rated information. 1 branch device. 1 1

3-20 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Pow-R-Line C Switchboards

Transformer and MCC Advanced Metering Standards and Certifications Close-Coupling and Communications • CSA C22.2 No. 31 1 Close-couple dry-type, Eaton has an extensive line of • CSA C22.2 No. 244 liquid-filled transformers powerful metering products, 2 • Seismic qualified to and motor control centres trip units, controllers and Zone 4 per IBC/CBC (MCC) with standard gateways, that can be wired 3 switchboard configurations together in switchboards to can be supplied. Transformer create an intelligent system 4 unit substations and MCC and interface with building bus coordination would management and SCADA create a compact lineup and systems. 5 minimization of installation time by eliminating cable Special Dimensions 6 installations. and Configurations Eaton has the ability to offer 7 Integrated Transfer Switches custom dimensions to suit Eaton automatic transfer limited space requirements. 8 switches (contactor, Special heights, special moulded-case circuit breaker depths and widths, corner 9 or power circuit breaker sections, back-to-back, front type, including optional access only (on deeper 1 bypass-isolation type) switchboards that normally can be integrated into a require rear access), rear switchboard lineup. Electrical access and side access 1 and mechanical coordination configurations are available. is ensured when transfer 1 switches are integrated into Arc Flash Considerations the switchboard. 1 Arc flash is an ongoing concern in the electrical industry. Eaton offers a 1 variety of solutions to reduce the risk of arc flash such 1 as the Arcflash Reduction Maintenance System™ in 1 moulded-case or power circuit breakers, safety shutters in Magnum drawout 1 power circuit breakers, infra- red viewing windows and 1 remote racking accessories. 1 1 1 1 1 1 1 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 3-21 Low Voltage Switchboards and Switchgear Pow-R-Line C Switchboards

Product Selection 1 For complete application and pricing information, contact your local Eaton sales office. 2 Wireway Cell Layouts 3 Approximate Dimensions in Inches (mm) Wireways are front access with rear and side access option, top or bottom incoming, 4 three- or four-wire, aluminum or copper, with bolted cover standard and front door optional.

5 Pow-R-Line C Switchboards Wireway Section Layout a 6 7 8 9 90.00 Wireway (2286.0) 1 1 1

D 1 W 1 Wireway 1 1 Pow-R-Line C Wireway Cells Cell Depth Cell Width (W) Ampere 18.00 24.00 30.00 36.00 60.00 to 90.00 18.00 24.00 1 Rating (457.2) (609.6) (762.0) (914.4) (1524.0 to 2286.0) (457.2) (609.6) 1 800        1200        1 2000        2500       1 3000      3200      1 4000    NNote 1 a 91.50 inches (2324.1 mm) high with 1.50 inch (38.1 mm) optional base channel. Specific municipality code designs available. Consult Eaton for more information. Consult Eaton for CSA enclosure rating. 1 Custom 78.00 inches (1981.2 mm) high wireways available. Consult Eaton for custom height information. Custom lug sizing and spacing available. Consult Eaton for more information. 1 1 1 1 1 1 1

3-22 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Pow-R-Line C Switchboards

Main and Utility Cell Layouts Approximate Dimensions in Inches (mm) 1 With copper or aluminum main bus; system incoming by cable or bus duct; 2 available for indoor or outdoor structures. 3 Pow-R-Line C Switchboards Main and Utility Section Layouts a 4 5 GFR Metering Compartment 6

Main/ Main/ Main/ Sub-Main Sub-Main Sub-Main 7 Breaker Device Device 8 90.00 90.00 90.00 90.00 (2286.0) (2286.0) (2286.0) (2286.0) 9

Utility CT/PT Utility CT/PT Utility CT/PT Utility CT/PT Compartment 1 Compartment Compartment Compartment 1

38.00/48.00 b 38.00/48.00 b 38.00/48.00 b 38.00/48.00 b 1 (965.2/1219.2) (965.2/1219.2) (965.2/1219.2) (965.2/1219.2) 18.00/24.00 18.00/24.00 18.00/24.00 18.00/24.00 1 (457.2/609.6) (457.2/609.6) (457.2/609.6) (457.2/609.6) 1 Layout A Layout B Layout C Layout D Top-mounted main/sub-main Top-mounted main/sub-main Top-mounted main/sub-main Top-mounted main/sub-main bolted pressure switch with breaker with utility metering device with utility device with horizontal 1 utility metering compartment compartment and vertical metering compartment. metering compartment and and ground fault relay. metering compartment. utility metering compartment. 1 1 Standard Pow-R-Line C Main and Utility Cells—Main Devices Ampere Rating Main Device Frame Layout A Layout B Layout C Layout D 1 100–2500 Moulded-case circuit breaker F, J, K, L, M, N, R    400–1200 Fusible switch FDP   1 1200–2000 Fusible switch Pringle switch   2500–3000 c Fusible switch Pringle switch   1 3000 c Fusible switch Pringle switch   800–1200 c Power circuit breaker Fixed mounted    1 1200–3200 c Power circuit breaker Fixed mounted    4000–6000 d Power circuit breaker Fixed mounted   1 800–1200 d Power circuit breaker Drawout   1200–3200 d Power circuit breaker Drawout   1 4000–6000 d Power circuit breaker Drawout   NNote 1 a 91.50 inches (2324.1 mm) high with 1.50 inch (38.1 mm) optional base channel. b Main devices up to and including 3200A require 38.00-inch-wide (965.2 mm) cells; main devices 4000–6000A require 48.00-inch-wide (1219.2 mm) cells. 1 c 24.00 inch (609.6 mm) depth required. d Additional depth required. Consult Eaton for more information. 1 All layouts shown are top fed. Consult Eaton for top and bottom incoming. Custom 78.00 inches (1981.2 mm) high main utility available. Consult Eaton for custom heights. Consult Eaton for copper or aluminum bussing, CSA enclosure rating, and horizontal and vertical metering. 1 ® Power Xpert Metering is not compatible with vertical metering layout (Layout B). 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 3-23 Low Voltage Switchboards and Switchgear Pow-R-Line C Switchboards

Main and Half-High Distribution Cell Layouts 1 Approximate Dimensions in Inches (mm) 2 With copper or aluminum main bus; system incoming by cable or bus duct; available for indoor or outdoor structures. 3 Pow-R-Line C Switchboards Main and Half-High Distribution Section Layout a 4 5 6 b Main/ 18X/22X Sub-Main Chassis 7 Device 8 90.00 90.00 9 (2286.0) (2286.0)

b 1 Main/ 18X/22X Sub-Main Chassis Device 1 1 38.00 38.00 (965.2) (965.2) 1 24.00 24.00 (609.6) (609.6) 1 Bottom-mounted main/ Top-mounted main/ sub-main breaker with sub-main breaker with 1 distribution chassis. distribution chassis. 1 Pow-R-Line C Main and Half-High Cells— 1 Main Devices Ampere Main Main/ Distribution 1 Rating Device Frame Utility Chassis 400–2500 Moulded-case K, L, M, N, R Main 18X 1 circuit breakers 400–2500 Moulded-case K, L, M, N, R Main 22X 1 circuit breakers 400–1200 Fusible switch FDP Main 18X 1 400–1200 Fusible switch FDP Main 22X NNote 1 a 91.50 inches (2324.1 mm) high with 1.50 inch (38.1 mm) optional base channel. b 1X = 1-3/8 inch. Consult Eaton for CSA enclosure rating. 1 Consult Eaton for horizontal and vertical metering. Consult Eaton for top or bottom incoming and additional layouts. 1 1 1 1 1 1 1

3-24 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Pow-R-Line C Switchboards

Distribution Cell Layouts Approximate Dimensions in Inches (mm) 1 Distribution boards are offered in copper or aluminum, three- or four-wire, 2 with cable in option available. Pow-R-Line C Switchboards Distribution Section Layout a 3 4 5 6

b 50X 7 Vertical 90.00 Panel (2286.0) Space 8 for Devices 9 1 1 38.00/48.00 c (965.2/1219.2) 1 18.00/24.00 (457.2/609.6) 1 50X Distribution Chassis 1

Standard Pow-R-Line C Distribution Cells—Branch Devices 1 Ampere Rating Frame Feeder Device Distribution Size 1 100–1600 F, J, K, L, M, N d, R e Moulded-case circuit breaker 18X / 22X / 50X 20–600 JG, LG Drawout MCCB f 18X / 22X / 50X 1 30/60 Single Fusible switch 18X / 22X / 50X 100 Single/twin Fusible switch 18X / 22X / 50X 1 200 Single/twin Fusible switch 18X / 22X / 50X 400 Single Fusible switch 18X / 22X / 50X 1 600 Single Fusible switch 18X / 22X / 50X 800 Single Fusible switch 18X / 22X / 50X 1 1200 Single Fusible switch 18X / 22X / 50X 1

Commercial Metering Switchboard 1 Eaton offers Fusible Switch Metering Centres (FSMC) for commercial metering applications. Please refer to Tab 3—Commercial Metering for more information. 1

NNote 1 a 91.50 inches (2324.1 mm) high with optional base channel. b 1X = 1-3/8 inch. 1 c Width of cell may require 48.00 inches (1219.2 mm) due to cable sizing or other features; consult Eaton for more information. d For cable sizing 750 kcmil and greater, 48.00-inch-wide (1219.2 mm) cell required. 1 e Copper bussing and 50 kAIC only. f Refer to Tab 5—Pow-R-Line C Switchboards with Drawout Moulded-Case Circuit Breaker, for more information. 1 Consult Eaton for CSA enclosure rating. 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 3-25 Low Voltage Switchboards and Switchgear Pow-R-Line C Switchboards

1 Filler 1X Breaker To Fusible Transition, All Widths Sub Panel 2 18 12X Poles BAB 100 Amp QBHW 3 42 Max. GHB, GBH 20X Poles 4 400 Amp. Maximum Bus Rating 1P 1P 1X 5 2P 2P 2X EHD, 6 225 Amp FDB, FD, Max. HFD, FDC 7 3P 3P 3X FDE, HFDE(3P) 8 2P 2P 2X 9 225 Amp Max. ED, EDH, EDC 1 3P 3P 3X

1 x 250 Amp 2 or 3P 3X JD, HJD, JDC Max. 1 Wide B o 400 Amp Max. DK, KD, HKD, KDC, CKD, CHKD 2 or 3P 4X 1 600 Amp Max. LGE, LGH, LGU 600 Amp LD, HLD, CLD, CHLD, LDC 6X

2 or 3P h (965.2 mm) 1 oad Max. L 38-In c 1 100 Amp 2 or 3P 2 or 3P 3X FCL, FB-P Max. 1 250 Amp 3X JD, HJD, JDC 1 2 or 3P 2 or 3P Max. 4X 400 Amp DK, KD, HKD, KDC, 1 2 or 3P 2 or 3P Max. CKD, CHKD 400 Amp 6X Max. LCL, LA-P 1 2 or 3P 800 Amp MDL, HMDL,

1 Max. CMDL, CHMDL 1200 Amp 2 or 3P 6X NGS, NGH, NGC 1 Max. 1 1 2 or 3P 800 Amp 6X NB-P 1 Max. 1200 Amp NGSC, NGHC, NGCC Max.

1 48-Inch (1219.2 mm) Wide Box 1 Breaker may be used as main.

1 Figure 2-4. Layout for Branch and Horizontally Mounted Main Devices — PRLC a BAB and QBHW breakers with shunt trips require one additional pole space, i.e., 1-pole is 2-pole size, 2-pole is 3-pole size, and 3-pole is 4-pole size. 1 b If panel contains only BAB or QBHW branch breakers, use a PRL1a panelboard. c GHB and GBH breakers cannot be mixed on same subchassis as BAB, QBHW. 1 d If panel contains only GHB and GBH branch breakers, use a PRL2a panelboard. e When only one single-pole breaker of the group is required on either side of chassis, the single-pole breaker space required changes from 1X to 2X. 1 f Minimum 38-inch (965.2 mm) wide box is required if optional #6 – 300 kcmil lug is required.

3-26 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Pow-R-Line C Switchboards

Fusible to Breaker Transition 1 1X Requires 1X Filler 2

30A 30A 4X 3 4

60A 60A 4X 5 6 7 200A 6X Main or Branch Switch 8 9

100A 100A 5X 1 1

400A 9X 1

Branch Switch 38-inch (965.2 mm) Wide Box 1

600A 11X 1 Branch Switch 1 1 200A 200A 6X 1 1 400A 9X Main or Branch 1 1 600A 11X Main or Branch 1 1 800A 11X Branch 1 1

1200A 15X Branch 48 Inch (1219.2 mm) Wide Box 1 1 1 Figure 2-7. Branch and Horizontally Mounted Main Device Layout — PRLC ▲ Fusible switch may be used as horizontal main. 1 ● 400 and 600 ampere horizontally mounted feeder switches in 38-inch (965 mm) or 48-Inch (1219.2 mm) wide box. 400 and 600 ampere horizontally mounted main switches only in 44-inch (1117.6 mm) wide box. For vertically mounted main see Page 2-19 for sizing. 1 Note: See Page 2-19 for MLO or Neutral and Vertically Mounted Main space requirements. 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 3-27 Low Voltage Switchboards and Switchgear Pow-R-Line C Switchboards

1 This page intentionally left blank. 2 3 4 5 6 7 8 9 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

3-28 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Commercial Metering Switchboards

Commercial Metering Switchboard Contents 1 Description Page Standards and Certifications...... 4-30 2 Product Selection...... 4-30 Dimensions...... 4-30 3 4 5 6 7 8 9 1

Commercial Metering Switchboards 1

Product Description Features, Benefits Main Bus Enclosure 1 Eaton commercial metering and Functions • Single-bolt bus joints • Freestanding, front switchboards use space- The commercial metering up to 3000A for ease accessible design (rear 1 saving design with modular switchboard has a free- of installation at accessible where required) construction, incorporating standing switchboard shipping splits • Structures are ANSI 61 1 metering sections with construction; it is factory • 50 kA bracing standard; light grey baked enamel, tenant feeder circuits using assembled and fully 65, 85, 100 kA optional code gauge steel with 1 meter sockets to meet integrated. • Tin-plated aluminum bus formed doors / removable local utility or customer is standard with optional back sheets; other colours requirements. All meter optional 1 Metering Unit / Metering Cell silver-plated copper sockets and associated available • Standard enclosures feeder devices are • Twin-mounted 30A, ® 1 • Provision for future are CSA Type 1; completely factory prewired 60A and 100A metering extension is provided sprinklerproof optional and shipped ready for the switches available as standard • Split back sheets for 1 installation of the meters. • Single-mounted 200A ease of handling metering switches available • Available with a bus Eaton offers a number of connected, incoming • Single-cell shipping splits 1 options for commercial • Metering switches are Pow-R-Line C™ main cell available as standard for metering switchboards. type FSMC (fusible switch or a separate, standalone ease of handling 1 These include assemblies meter sockets), suitable to main lugs only structure accept revenue grade, self- that meet utility requirements • Channel sills optional for globe type watthour contained meters 1 meters and electronic tenant • Various meter base jaw metering switchboards. options available to meet 1 all requirements—most Application Description common is Star (Y) type, 1 seven jaw, suitable for Commercial multi-metering four-wire systems up to 1 applications such as: 347/600V • Shopping centres • Switch jaws are spring 1 • Office buildings reinforced to firmly grip blades • Condominium complexes • Maximum quantity of 1 • Apartment buildings six FSMC twin or single units can be installed 1 in each 90.00 inch (2286.0 mm) high 1 x 48.00-inch-wide (1219.2 mm) enclosure 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 4-29 Low Voltage Switchboards and Switchgear Commercial Metering Switchboards

Standards and Certifications Product Selection Dimensions 1 • CSA C22.2 No. 229 Approximate Dimensions in Inches (mm) • CSA C22.2 No. 31 FSMC Device Options 2 FSMC Layout • CSA C22.2 No. 244 Ampere Single 3 Rating or Twin X Space a 30/30 Twin 7X 4 30/60 Twin 7X 60/30 Twin 7X 5 60/60 Twin 7X 100/100 Twin 7X 6 200 Single 7X NNot 7 a 1X = 1-3/8 inch.

90.00 8 (2286.0) 9 1 1

1 18.00/24.00 48.00 (457.2/609.6) 1 (1219.2) 1 1

FSMC Units Installed in 1 Pow-R-Line C Switchboard 1 Twin 30A, 60A or 100A FSMC Switch 1 1 1 1 Single 200A FSMC Switch 1 1 1 1 1 1 1 1 1

4-30 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Integrated Facility Switchboards

Integrated Facility Switchboards Contents 1 Description Page Features, Benefits 2 and Functions...... 5-32 Options...... 5-32 3 Standards and Certifications...... 5-32 Product Selection...... 5-33 4 Technical Data and Specifications...... 5-41 5 6 7 8 9 1

Integrated Facility Switchboards 1

Product Description The service entrance Other associated equipment Application Description 1 Eaton Integrated Facility equipment can be integrated can also be integrated into Eaton Integrated Facility Switchboards™ (IFS™) utilizes with multiple lighting the assembly, including Switchboards are designed 1 the modular Pow-R-Line C™ and appliance branch dry-type distribution to meet specific needs for: switchboard design to panelboards into a compact transformers, time clock 1 integrate traditionally front accessible group- space, lighting control, • Retail stores separate electrical distribution mounted switchboard. electronic controls, surge • Commercial offices 1 and control equipment Where multiple switchboards protection devices, metering, • High rise buildings or panelboards are used automatic transfer switches into a single space-saving • Correctional facilities factory assembled and in the same electrical and energy monitoring 1 • Agricultural facilities connected package. room as a conventional devices. Depending upon distribution system, the the application, other user- • Industrial facilities 1 integrated design significantly defined equipment such as a • Hospitals / health reduces equipment space subsystem control package care facilities requirements, as well as may also be incorporated. 1 • Educational facilities minimizes installation time and costs. Whether the application is 1 a multi-site prototype or a single application, integrated 1 switchboards offer time and space-saving features. 1 1 1 1 1 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 5-31 Low Voltage Switchboards and Switchgear Integrated Facility Switchboards

Features, Benefits Space Savings Busbar System Options 1 and Functions The space-saving Standard bus in the • Automatic transfer switchboard installation switchboards is tin-plated switches 2 Front Accessible provides additional usable aluminum or silver-plated • Breakers Integrated facility floor space. For example: copper; optional tin-plated • Metering 3 switchboards are front copper available. • Retail stores—floor space • Dry-type transformers accessible and align at the for sales rear, enabling them to be • Enclosed control 4 • Offices—additional Short-Circuit Rating placed against a wall. Most • Seismic construction storage, cubicle Standard bus and connectors 5 switchboards align at the • Surge protection devices front and the rear. If the main • Health care—additional on all switchboards are rated • UPS section is deeper than others work area for use on systems capable 6 due to physical size of the • Retrofits—ability to fit of producing up to 65 kA • HVAC control main device, the necessary existing rooms rms symmetrical short-circuit • Harmonic blocking filter 7 off-set in line-up will occur current at the incoming • correction terminals. in the front, and the main Site Construction Savings • Generator Quick Connect section will be accessible 8 Timely installation of the Short-circuit ratings up to from both the front and electrical system typically is 200 kA symmetrical are the side. Standards and Certifications a key element on the critical available when used with 9 • CSA® C22.2 No. 31 path for any project. approved devices. Contact 1 Standard Switchboard Height Eaton for more information. • CSA C22.2 No. 244 Along with the time to • Factory wired panelboards Switchboard height is install the equipment, other 90.00 inches (2286.0 mm). and dry-type distribution 1 expenses include the time to Bus Duct Integration transformers meet CSA handle all of the loose pieces Applications such as condo, C22.2 No. 31 and the 1 Switchboard Shipping Splits of equipment arriving on a job commercial office towers Canadian Electrical Code site and ensuring it reaches The sections can be and health care facilities may • Zone 4 Construction (IBC/ the proper trades person. shipped as specified by require bus duct. Custom CBC Seismic Qualified) 1 With Eaton Integrated Facility the customer to meet bus duct flanges can be Switchboards, one piece specific requirements. designed and manufactured 1 of equipment is typically to coordinate with bus duct For retrofit applications, shipped to a job site virtually risers of a wide range of 1 single-piece switchboard eliminating these issues. amperages. The bus duct can structures can be shipped to The equipment may also even be directly integrated facilitate movement through 1 be used for temporary into the switchboard, limited access doorways, etc. power on job sites, further eliminating the need for bus 1 reducing construction plugs and therefore creating Factory Interconnections expenses and times. a more compact footprint. 1 Where interconnections are required within the IFS, Lighting Control power cabling is factory 1 Eaton lighting control installed and sized per the panelboards with remote Canadian Electrical Code. 1 control breakers can be installed in IFS assemblies. 1 1 1 1 1 1 1 1 1 Traditionally Mounted Equipment

1 Integrated Facility Switchboard

5-32 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Integrated Facility Switchboards

Product Selection 1 Integrated Facility Switchboard Applications 2 Electrical Room With and Without IFS—Plan View 3 Panel L1 Panel L2 4 Main IFS Switchboard 5 Transformer Integrated Facility Switchboard Solution 6 7 8 Telephone Panel P3 Panel P2 Panel P1 Telephone 9 Traditional Electrical Room IFS Electrical Room 1

Optimized IFS Layout—Front View 1

Main RD 1 Breaker Customer P1 P3 L1 1 Metering Feeder Breaker Section 1 Utility SPD Dry-Type Metering P2 L2 Distribution Section 1 Transformer 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 5-33 Low Voltage Switchboards and Switchgear Integrated Facility Switchboards

1 Approximate Dimensions in Inches (mm) Integrated Facility Switchboards Distribution Section Layout 2 Eaton Pow-R-Line panelboard integration—factory wired from feeder device in adjacent section(s) to panelboards. Standard features include lockable trim doors and factory-mounted overcurrent devices. 3 Style 1 and 2 Integrated Facility Switchboards Distribution Section Layout 4 W 5 3.00 3.00 (76.2) (76.2) 6 3.00 7 D (76.2) 12.00 Conduit Area (304.8) 8 Cell “A”

Floor Plan 9 90.00 90.00 Style 1 and 2 Sections (2286.0) (2286.0) Cell “C” 1 W 3.00 3.00 1 Cell “B” (76.2) (76.2)

1 3.00 D (76.2) Conduit Area 3.00 (76.2) 1 D D W W 1 IFS Style 1 Section IFS Style 2 Section Floor Plan 1 Style 2 Section with Blank Steel Backpan Only 1 IFS Style 1 Allowable Configurations (Select One “Panelboard Type” per Panelboard “Cell”) Main Maximum Branch Allowable Width (W) Depth (D) Panel Panelboard Maximum Device Main Rating Circuit Panelboard Section 1 Cell Type Vac Rating Type Amperes Ampere Range Modifications Standard Optional Standard Optional Height 1 IFS Style 1 Section A Pow-R-Line 1a 240 MLO 600 15–100 ab 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) Breaker 225 20.00 (508.0) 26.00 (660.4) 1 30.00 (762.0) Pow-R-Line 2a 600Y/347 MLO 600 15–100 ab 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) 1 Breaker 225 20.00 (508.0) 26.00 (660.4) 30.00 (762.0) 1 Pow-R-Command™ 240 MLO 225 15–100 ab 20.00 (508.0) 26.00 (660.4) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) 480Y/277 30.00 (762.0) 1 Blank steel — None — — d 20.00 (508.0) 26.00 (660.4) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) backpan c 30.00 (762.0) 1 B Pow-R-Line 1a 240 MLO 600 15–100 ab 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) Breaker 225 20.00 (508.0) 26.00 (660.4) 30.00 (762.0) 1 Pow-R-Line 2a 600Y/347 MLO 600 15–100 ab 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) Breaker 225 20.00 (508.0) 26.00 (660.4) 1 30.00 (762.0) Pow-R-Command 240 MLO 225 15–100 ab 20.00 (508.0) 26.00 (660.4) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) 1 480Y/277 30.00 (762.0) Blank steel — None — — d 20.00 (508.0) 26.00 (660.4) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) 1 backpan c 30.00 (762.0) NNote 1 a Copper main lugs, ground bar circuit breaker handle lockoff devices, nameplates, 200% rated neutral through 400A, permanent circuit numbers, directory frames, shunt trip breakers, through-feed lugs to panel immediately above or below. b If panel sizing with non-interchange main is 48.00 inches (1219.2 mm) high or less, the panel will fit in a half section. If it is 72.00 inches (1828.8 mm) high, you must use a full section. 1 If it is 60.00 inches (1524.0 mm) high, contact Eaton for structure dimensions. (One exception is PRL 1a/2a with 400A MLO and 42 circuits, which will fit in half section.) c Possible uses: HVAC, dimming, contactors, A/V equipment and data rack equipment. Contact Eaton for details. 1 d Galvanized steel backpan provided for customer specified equipment. Contact Eaton for details.

5-34 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Integrated Facility Switchboards

Approximate Dimensions in Inches (mm) 1 Style 1 and 2 Integrated Facility Switchboards Distribution Section Layout 2 W 3.00 3.00 (76.2) (76.2) 3 4 3.00 D (76.2) 12.00 Conduit Area 5 (304.8) Cell “A” 6

Floor Plan 90.00 90.00 Style 1 and 2 Sections 7 (2286.0) (2286.0) Cell “C”

W 8 3.00 3.00 Cell “B” (76.2) (76.2) 9

3.00 1 D (76.2) Conduit Area 3.00 (76.2) D D 1 W W 1 IFS Style 1 Section IFS Style 2 Section Floor Plan Style 2 Section with Blank Steel Backpan Only 1 IFS Style 2 Allowable Configurations (Select One “Panelboard Type” per Panelboard “Cell”) 1 Main Maximum Branch Allowable Width (W) Depth (D) Panel Panelboard Maximum Device Main Rating Circuit Panelboard Section Cell Type Vac Rating Type Amperes Ampere Range Modifications Standard Optional Standard Optional Height 1 IFS Style 2 Section 1 C Pow-R-Line 1a 240 MLO 600 15–100 ab 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) Breaker 400 1 Pow-R-Line 2a 600Y/347 MLO 600 15–100 ab 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) Breaker 400 1 Pow-R-Line 3a 600 MLO 600 15–125 ab 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) Breaker 400 1 Pow-R-Command 480Y/277 MLO 400 15–100 ab 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) Breaker 225 1 Blank steel — None — — d 20.00 (508.0) 26.00 (660.4) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) backpan c 30.00 (762.0) 1 NNote a Copper main lugs, ground bar circuit breaker handle lockoff devices, nameplates, 200% rated neutral through 400A, permanent circuit numbers, directory frames, shunt trip breakers, through-feed lugs to panel immediately above or below. 1 b If panel sizing with non-interchange main is 48.00 inches (1219.2 mm) high or less, the panel will fit in a half section. If it is 72.00 inches (1828.8 mm) high, you must use a full section. If it is 60.00 inches (1524.0 mm) high, contact Eaton for structure dimensions. (One exception is PRL 1a/2a with 400A MLO and 42 circuits, which will fit in half section.) 1 c Possible uses: HVAC, dimming, contactors, A/V equipment and data rack equipment. Contact Eaton for details. d Galvanized steel backpan provided for customer specified equipment. Contact Eaton for details. 1 1 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 5-35 Low Voltage Switchboards and Switchgear Integrated Facility Switchboards

1 Approximate Dimensions in Inches (mm) Style 3 and 4 Integrated Facility Switchboards Distribution Section Layout 2 3 4 Cell “F” W Cell “D” 3.00 3.00 5 (76.2) (76.2) 6 90.00 90.00 3.00 (2286.0) (2286.0) D (76.2) Conduit Area 3.00 7 (76.2) 8 Cell “E” 9 Floor Plan Style 3 Section with Blank Space in Cell “E” Bottom Entry Conduit Space not 1 Recommended with Transformer D D in Cell “E” or “F” (Style 3 or 4) 1 W W 1 IFS Style 3 Section IFS Style 4 Section

1 IFS Style 3 Allowable Configurations (Select One “Panelboard Type” per Panelboard “Cell”) Main Maximum Branch Allowable Width (W) Depth (D) 1 Panel Panelboard Maximum Device Main Rating Circuit Panelboard Section Cell Type Vac Rating Type Amperes Ampere Range Modifications Standard Optional Standard Optional Height 1 IFS Style 3 Section D Pow-R-Line 1a 240 MLO 600 15–100 a 26.00 (660.4) 30.00 (762.0) 24.00 (609.6) — 90.00 (2286.0) 1 Breaker 225 Pow-R-Line 2a 600Y/347 MLO 600 15–100 a 26.00 (660.4) 30.00 (762.0) 24.00 (609.6) — 90.00 (2286.0) 1 Breaker 225 Pow-R-Line 3a 600 MLO 600 15–125 ab 26.00 (660.4) 30.00 (762.0) 24.00 (609.6) — 90.00 (2286.0) 1 Breaker 400 Pow-R-Line C 600 MLO 800 15–600 a 26.00 (660.4) 36.00 (914.4) 24.00 (609.6) — 90.00 (2286.0) 1 switchboard Breaker 600 30.00 (762.0) chassis MLO or 800 15–600 a 36.00 (914.4) — 24.00 (609.6) — 90.00 (2286.0) 1 Breaker Pow-R-Command 240 MLO 225 15–100 a 26.00 (660.4) 30.00 (762.0) 24.00 (609.6) — 90.00 (2286.0) 1 480Y/277 Blank steel — None — — c 26.00 (660.4) 30.00 (762.0) 24.00 (609.6) — 90.00 (2286.0) 1 backpan NNote a Copper main lugs, ground bar circuit breaker handle lockoff devices, nameplates, 200% rated neutral through 400A, permanent circuit numbers, directory frames, shunt trip breakers, through-feed 1 lugs to panel immediately above or below. b If panel sizing with non-interchange main is 48.00 inches (1219.2 mm) high or less, the panel will fit in a half section. If it is 72.00 inches (1828.8 mm) high, you must use a full section. 1 If it is 60.00 inches (1524.0 mm) high, contact Eaton for structure dimensions. (One exception is PRL 1a/2a with 400A MLO and 42 circuits, which will fit in half section.) c Galvanized steel backpan provided for customer specified equipment. Contact Eaton for details. 1 Select one “Panelboard Type” or one “Blank Steel Backpan” and either one “Transformer” or one “Blank Space” per “Cell.“ 1 1 1 1 1

5-36 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Integrated Facility Switchboards

Approximate Dimensions in Inches (mm) 1 Style 3 and 4 Integrated Facility Switchboards Distribution Section Layout 2 3 4 Cell “F” W Cell “D” 3.00 3.00 (76.2) (76.2) 5 6 90.00 90.00 3.00 (2286.0) (2286.0) D (76.2) Conduit Area 3.00 (76.2) 7 8 Cell “E” Floor Plan Style 3 Section 9 with Blank Space in Cell “E” Bottom Entry Conduit Space not Recommended with Transformer 1 D D in Cell “E” or “F” (Style 3 or 4) W W 1 IFS Style 3 Section IFS Style 4 Section 1

IFS Style 3 and 4 General Purpose Dry-Type Distribution Transformers 1 Panel Panelboard Temperature kVA Full Cap Taps Allowable Width (W) Depth (D) Section Cell Type Rise Windings Range FCAN FCBN Modifications Standard Optional Standard Optional Height 1 IFS Style 3 Section E ab Transformer c 150°C only d Aluminum 15–45 4–2.5% 2–2.5% a 26.00 (660.4) — 24.00 (609.6) — 90.00 (2286.0) 1 150°C only d Aluminum 75 4–2.5% 2–2.5% a 30.00 (762.0) — 24.00 (609.6) — 90.00 (2286.0) 115°C Aluminum 112.5 4–2.5% 2–2.5% a 36.00 (914.4) — 24.00 (609.6) — 90.00 (2286.0) 1 IFS Style 4 Section F a Transformer c 150°C Aluminum 150 4–2.5% 2–2.5% a 36.00 (914.4) — 30.00 (762.0) — 90.00 (2286.0) 1 225 4–2.5% 2–2.5% a 44.00 (1117.6) — 36.00 (914.4) — 90.00 (2286.0) 1 NNote a Copper windings, 115°C, 80°C, K-Factor, low sound are available options but may change dimensions. 1 b Either one F Frame or K Frame circuit breaker can be included in any transformer section to be used as a disconnect. c General purpose CSA C802.2 Energy Efficient. 1 d Contact Eaton for other temperature rise transformers and special requirements. 1 1 1 1 1 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 5-37 Low Voltage Switchboards and Switchgear Integrated Facility Switchboards

1 Approximate Dimensions in Inches (mm) Style 5 and 6 Integrated Facility Switchboards Distribution Section Layout 2 W 3.00 3.00 3 (76.2) (76.2)

4 a 22X 3.00 Distribution D (76.2) 12.00 Cell “G” Conduit Area 5 Chassis (304.8) Cell “H” 6 90.00 90.00 (2286.0) (2286.0) Floor Plan 7 Style 5 and 6 Sections

a 8 22X Distribution Cell “G” 9 Chassis Cell “H” 1 D D 1 W W 1 IFS Style 5 Section IFS Style 6 Section 1 IFS Style 5 and 6 Allowable Configurations (Select One “Panelboard Type” per Panelboard “Cell”) Main Maximum Branch Allowable Width (W) Depth (D) Panel Panelboard Maximum Device Main Rating Circuit Panelboard Section 1 Cell Type Vac Rating Type Amperes Ampere Range Modifications Standard Optional Standard Optional Height 1 IFS Style 5 and 6 Sections G Pow-R-Line 1a 240 MLO 600 15–100 bc 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) 1 Breaker 225 Pow-R-Line 2a 600Y/347 MLO 600 15–100 bc 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) 1 Breaker 225 Pow-R-Line 3a 600 MLO 600 15–125 bc 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) 1 Breaker 400 Pow-R-Command b 240 MLO 225 15–100 b 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) 1 480Y/277 H Pow-R-Line C 600 MLO 800 15–600 b 26.00 (660.4) 30.00 (762.0) 18.00 (457.2) 24.00 (609.6) 90.00 (2286.0) switchboard Breaker 600 36.00 (914.4) 1 chassis Breaker 800 15–600 b 36.00 (914.4) — 24.00 (609.6) — 90.00 (2286.0) 1 NNote a 1X = 1-3/8 inch. b Copper main lugs, ground bar circuit breaker handle lockoff devices, nameplates, 200% rated neutral through 400A, permanent circuit numbers, directory frames, shunt trip breakers, 1 through-feed lugs to panel immediately above or below. c If panel sizing with non-interchange main is 48.00 inches (1219.2 mm) high or less, the panel will fit in a half section. If it is 72.00 inches (1828.8 mm) high, you must use a full section. 1 If it is 60.00 inches (1524.0 mm) high, contact Eaton for structure dimensions. (One exception is PRL 1a/2a with 400A MLO and 42 circuits, which will fit in half section.) 1 1 1 1 1 1 1

5-38 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Integrated Facility Switchboards

Approximate Dimensions in Inches (mm) 1 Style 7 Integrated Facility Switchboards Distribution Section Layout 2 W 3

Cell Cell 4 “I” “J” D 5

Floor Plan Style 7 Section 6 There is no Bottom Entry Conduit Space with 7 Transformer in Cell “J”

Cell “K” 8 9

IFS Style 7 Section 1 1 IFS Style 7 Panelboard Over Dry-Type Transformer (Select One “Panelboard Type” per Panelboard “Cell”) Main Maximum Branch Allowable Width (W) Depth (D) 1 Panel Panelboard Maximum Device Main Rating Circuit Panelboard Section Cell Type Vac Rating Type Amperes Ampere Range Modifications Standard Optional Standard Optional Height 1 IFS Style 7 Section I Pow-R-Line 1a 240 MLO 400 15–100 a 36.00 (914.4) — 24.00 (609.6) — 90.00 (2286.0) 1 Breaker Pow-R-Line 2a 600Y/347 MLO 400 15–100 a 36.00 (914.4) — 24.00 (609.6) — 90.00 (2286.0) 1 Breaker J Pow-R-Line 1a 240 MLO 400 15–100 a 36.00 (914.4) — 24.00 (609.6) — 90.00 (2286.0) 1 Breaker Pow-R-Line 2a 600Y/347 MLO 400 15–100 a 36.00 (914.4) — 24.00 (609.6) — 90.00 (2286.0) 1 Breaker Pow-R-Line 3a 600 MLO 400 15–225 ab 36.00 (914.4) — 24.00 (609.6) — 90.00 (2286.0) 1 Breaker 1 IFS Style 7 General Purpose Dry-Type Distribution Transformers Full Cap Taps Width (W) Depth (D) Panel Panelboard Temperature kVA Allowable Section 1 Cell Type Rise Windings Range FCAN FCBN Modifications Standard Optional Standard Optional Height IFS Style 7 Section 1 K Transformer cd 150°C only e Aluminum 15–75 4–2.5% 2–2.5% f 36.00 (914.4) — 24.00 (609.6) — 90.00 (2286.0) 115°C Aluminum 112.5 4–2.5% 2–2.5% f 36.00 (914.4) — 24.00 (609.6) — 90.00 (2286.0) 1 NNote a Copper main lugs, ground bar circuit breaker handle lockoff devices, nameplates, 200% rated neutral through 400A, permanent circuit numbers, directory frames, shunt trip breakers, 1 through-feed lugs to panel immediately above or below. b If panel sizing with non-interchange main is 48.00 inches (1219.2 mm) high or less, the panel will fit in a half section. If it is 72.00 inches (1828.8 mm) high, you must use a full section. 1 If it is 60.00 inches (1524.0 mm) high, contact Eaton for structure dimensions. (One exception is PRL 1a/2a with 400A MLO and 42 circuits, which will fit in half section.) c Either one F Frame or K Frame circuit breaker can be included in any transformer section to be used as a disconnect. 1 d General purpose CSA C802.2 Energy Efficient. e Contact Eaton for other temperature rise transformers and special requirements. 1 f Copper windings, 115°C, 80°C, K-Factor, and harmonic mitigating transformers are available options but may change dimensions. 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 5-39 Low Voltage Switchboards and Switchgear Integrated Facility Switchboards

1 Approximate Dimensions in Inches (mm) 2 Integrated Facility Switchboards ATS Section Layout Eaton Pow-R-Line panelboard and integrated wall-mounted ATS (non-bypass)—factory wired from feeder devices in adjacent sections. 3 Standard features include lockable trim doors and factory-mounted overcurrent devices. 4 Style 8, 9, 10 and 11 Integrated Facility Switchboards ATS Section Layout 5 6 a 22X 7 Distribution Cell “L” Cell “O” Chassis 8 90.00 90.00 90.00 90.00 9 (2286.0) (2286.0) Cell “N” (2286.0) (2286.0) 1 22X a Cell “M” Distribution Cell “P” 1 Chassis 1 D D D D 1 W W W W

1 IFS Style 8 Section IFS Style 9 Section IFS Style 10 Section IFS Style 11 Section

1 IFS Style 8, 9, 10 and 11 Contactor-Based, Non-Bypass Transfer Switches (Select One “ATS Type” per ATS “Cell”) 1 Width Depth Standard Terminals Maximum Main Rating 20.00 26.00 30.00 36.00 18.00 24.00 Load Side, Normal Neutral 1 ATS Cell Vac Rating Amperes (508.0) (660.4) (762.0) (914.4) (457.2) (609.6) and Standby Source Connection IFS Style 8, 9, 10 and 11 Sections 1 L/M/O/P 480 40–100       (1) #14–2/0 (3) #14–1/0 600 40–100       (1) #6–250 kcmil (3) #14–1/0 1 480 150–200       (1) #6–250 kcmil (3) 1/0–250 kcmil 600 150–200       (1) #6–250 kcmil (3) 1/0–250 kcmil 1 480 225–400       (2) 3/0–250 kcmil (6) 250–500 kcmil (1) 3/0–600 kcmil 1 N 480 40–100       (1) #14–2/0 (3) #14–1/0 600 40–100       (1) #6–250 kcmil (3) #14–1/0 1 480 150–200       (1) #6–250 kcmil (3) 1/0–250 kcmil 600 150–200       (1) #6–250 kcmil (3) 1/0–250 kcmil 1 480 225–400       (2) 3/0–250 kcmil (6) 250–500 kcmil (1) 3/0–600 kcmil 1 600 225–400    (2) 3/0–250 kcmil (6) 250–500 kcmil (1) 3/0–600 kcmil 1 600–1200    (4) 1/0–750 kcmil (12) 1/0–750 kcmil 480 600–1200    (4) 1/0–750 kcmil (12) 1/0–750 kcmil 1 NNote a 1X = 1-3/8 inch. 1 All amperages available in three- and four-pole. 1 1 1

5-40 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Integrated Facility Switchboards

Approximate Dimensions in Inches (mm) 1 IFS Style 8, 9, 10 and 11 Breaker-Based, Non-Bypass Transfer Switches (Select One “ATS Type” per ATS “Cell”) 2 Width Depth Frame Maximum Main Rating 26.00 30.00 36.00 18.00 24.00 3 ATS Cell Size Vac Rating Amperes (660.4) (762.0) (914.4) (457.2) (609.6) IFS Style 8, 9, 10 and 11 Sections 4 L/M/O/P F 600 30–150      240 30–200 5 N F 600 30–150      240 30–200 6 K, L, M 600/240 225–600    N a 600/240 800–1200    7 NNote a Please consult Eaton for N size breaker frame. 8 All amperages available in two-, three- and four-pole. 9 Technical Data and Specifications 1 Contactors / Motor Control 1 Consult Eaton for complete application. 1 Seismic Construction Zone 4 seismic is optional. 1

Metering 1 Metering can be installed in the following standard cells: 1 • Blank steel backpan (20, 26, 30, 36 inches wide) • Pow-R-Line 4 chassis (minimum 36 inches wide, 1 22X spacing) Metering products: 1 • IQ 100 (130, 140, 150) 1 • IQ 200 (250, 260) • PXM (2250, 2260, 2270, 4000, 6000, 8000) 1 • PXG (400e, 600e, 800e) • IQ 35M 1 • Non-Eaton products Consult Eaton for more information. 1 1 1 1 1 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 5-41 Low Voltage Switchboards and Switchgear Integrated Facility Switchboards

1 This page intentionally left blank. 2 3 4 5 6 7 8 9 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

5-42 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Pow-R-Line C Switchboards with Drawout Moulded-Case Circuit Breaker

Pow-R-Line C Switchboard with Drawout Moulded-Case Circuit Breakers Contents 1 Description Page Standards and Certifications...... 6-44 2 Product Selection...... 6-45 Technical Data and Specifications...... 6-45 3 Dimensions...... 6-45 4 5 6 7 8 9 1

Pow-R-Line C™ Switchboards with Drawout Moulded-Case Circuit Breaker 1

Product Description Application Description The base cassette is Drawout Cassette 1 Eaton drawout moulded- Drawout moulded-case circuit designed to accept the The drawout cassette case circuit breakers are breaker switchboards are drawout cassette that contains the breaker and is 1 installed in switchboards in ideal for applications such as: contains the breaker. The group-mounted. The cassette a group-mounted manner. loadside feeder conductors incorporates a viewing 1 Breakers use drawout • Data centres are also part of the base window and an external cassettes and are three- • Health care facilities cassette, allowing the racking port. The viewing 1 pole with ratings from 20A • Process industry loadside feeder conductors window allows personnel to to remain with the base to 600A. The breakers are • Institutions visually inspect the breaker inserted and removed via a cassette when the breaker is status and to see whether 1 • Laboratories mechanical system similar removed without removing the breaker is connected to to other drawout designs • Critical load applications the loadside conductors. or disconnected from the 1 associated with switchgear; The base cassette contains a bus. The window exposes however, these breakers Features, Benefits drawout racking mechanism, the Connected/Disconnected 1 are horizontally mounted in and Functions a Connected/Disconnected position indicator on the base a traditional switchboard. position indicator and a pull- cassette. The external racking 1 Feeder devices are also Enclosures apart terminal block base port allows access to the front accessible and front racking mechanism to draw CSA® Type 1, sprinklerproof (used for connections to the connected. out the breaker. 1 optional. Please consult Eaton breaker accessories). Group-mounted drawout for other enclosure types. NNote: Per industry practice, The drawout cassette 1 moulded-case circuit breakers all power to the board section contains handles attached to the deadfront to help include Eaton JG and LG Base Cassette must be disconnected at its breaker families and include source before working on any easily remove the breaker. 1 standard thermal-magnetic The base cassette is electrical equipment. The cassette also contains trip units or optional Eaton permanently factory mounted a pigtail wiring harness, 1 310+ electronic trip units. to the switchboard’s chassis. Safety features include which is factory-wired from The lineside connections finger-safe connections to the breaker accessory ports 1 use bus connectors and are the moulded-case circuit and contains a pull-apart factory connected to the breaker drawout cassette and terminal block that attaches switchboard’s vertical bus. a mechanism system that the permanently mounted 1 will not allow the breaker to female terminal block located be connected or removed on the base cassette. 1 while the breaker is in the External connections on energized, ON, position. the secondary side of the 1 terminal block are provided by the installer. 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 6-43 Low Voltage Switchboards and Switchgear Pow-R-Line C Switchboards with Drawout Moulded-Case Circuit Breaker

The drawout cassette Surge Protection Devices (SPDs) When the Eaton Arcflash Zone selective interlocking 1 employs two breaker Eaton SPDs are available. Reduction Maintenance provides increased system families—the JG and the A moulded-case circuit System is enabled, the protection and can reduce 2 LG with standard thermal- breaker is provided as a resulting reduced arc-flash arc-flash risk by allowing the magnetic trip unit. Optional lineside disconnect for energy allows for reduced breaker closest to the fault 3 310+ electronic trip units the SPD. Refer to Tab 9— PPE, which improves worker to trip without any preset offer ampere ratings from Components—or contact comfort and mobility. With time delays. This is achieved 20A to 250A on the JG and Eaton for more information. the Arcflash Reduction by selecting and setting the 4 100A to 600A on the LG. Maintenance System set trip unit equipped with the at 2.5X or 4.0X, it reduces zone selective interlocking Optional Infrared (IR) incident energy levels to allow option. The hardwired 5 Breaker Options Viewing Windows PPE Category 0 for currents connection between the 6 • Electronic trip units Infrared windows are an of 2.5X or 4.0X the breaker trip units sends a restraining • Infrared viewing windows available option on both ampere rating or greater. The signal upstream, allowing the for the lineside and the JG and LG families of initial setting of each Arcflash breaker closest to the fault 7 loadside connections single-mounted drawout Reduction Maintenance to act instantaneously. Zone • Shunt trips moulded-case circuit breaker System trip unit is determined selective interlocking reduces 8 cassettes. Infrared windows by completing a power stress on the distribution • Auxiliary contacts can be located to view the system analysis to assess system and can reduce arc- 9 • Bell alarm lineside and/or loadside available fault current at the flash risk by isolating faults • Zone selective interlocking connections. circuit breaker. Based on that without time delays. 1 • Arcflash Reduction analysis, the Maintenance mode protection settings are Maintenance System™ Arcflash Reduction Standards and Certifications Maintenance System defined, achieving a reduced 1 The JG and LG families level of arc-flash energy. The • CSA C22.2 No. 31 of drawout breakers are The Eaton Arcflash Reduction Maintenance mode is then • CSA C22.2 No. 244 1 available in either a single Maintenance System provides activated by adjusting the trip group-mounted design or reduced levels of incident unit’s instantaneous setting to 1 a high-density, twin group- arc-flash energy when put desired Maintenance mode mounted design where two in the Maintenance mode. levels that are determined by breakers occupy the same The Arcflash Reduction the power analysis. 1 vertical space. Maintenance System is available on the LG family of drawout MCCBs, combining Electronic Trip Units With Zone 1 Short-Circuit Rating the Arcflash Reduction Selective Interlocking (ZSI) 1 The short-circuit current Maintenance System with Unlike power air circuit rating of the switchboard is the Digitrip 310+ electronic breakers, moulded-case determined by the short- trip unit and allowing for the circuit breakers do not offer 1 circuit current rating of the ability to place the trip unit in the ability to turn off the lowest rated overcurrent Maintenance mode to reduce instantaneous trip settings. 1 device in the switchboard. potential arc-flash energy. As a result, the coordination This is done by a dedicated between one breaker and 1 Busbar System instantaneous sensing circuit another could compromise with settings of 2.5 and 4.0 selectivity (breaker closest 1 Standard tin-plated copper times the current rating of to the fault opening first). bus and silver-plated copper. the trip unit. This dedicated Zone selective interlocking analog sensing circuit delivers is designed to mitigate 1 Metering breaker clearing times that are selectivity issues with A full line of Eaton customer faster than instantaneous by moulded-case circuit breakers. 1 metering is available. All eliminating microprocessor processing latencies. This Both the JG and LG families options offered in Eaton’s of moulded-case circuit 1 standard bolt-on switchboard provides superior arc flash reduction to competing breakers offer zone selective product are also available interlocking as an option. 1 with the Pow-R-Line drawout systems that simply lower moulded-case circuit breaker the standard instantaneous switchboard. Refer to Tab 9— pickup set point. 1 Components—or contact 1 Eaton for more information. 1 1 1 1

6-44 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Pow-R-Line C Switchboards with Drawout Moulded-Case Circuit Breaker

Product Selection Technical Data and Specifications Eaton Pow-R-Line C switchboard: 1 Standard Adjustable Thermal-Magnetic Single Group-Mounted • Maximum 4000A rating Feeder Trip Units 2 • Rated at 240, 480 and 600 Vac 250A JG Frame 600A LG Frame • Maximum interrupting ratings: 3 70A 250A • 200 kAIC at 240 Vac 90A 300A • 100 kAIC at 480 Vac 4 100A 350A • 65 kAIC at 600 Vac 125A 400A 5 150A 500A 175A 600A Short-Circuit Current Ratings 6 200A — Short-Circuit Rating kA 225A — Maximum Breaker Breaker Symmetrical by Vac 7 Ampere Rating Frame 240V 480V 600V 250A — 250 JGS 85 35 18 8 JGH 100 65 25 Optional 310+ Electronic Trip Units Twin Group-Mounted JGC 200 100 35 Feeder 9 250A JG Frame 600A LG Frame JGU 200 150 50 20A 100A 600 LGS 85 35 25 1 25A 125A LGH 100 65 35 30A 150A LGC 200 100 50 1 40A 175A LGU 200 150 65 45A 200A 1 50A 225A Optional Accessories 70A 250A 1 Position a 80A 300A Accessory Left Right 90A 350A 1 100A 400A Alarm contact (Make/Break) —  110A 450A Auxiliary switch (1A/1B) —  1 125A 500A Auxiliary switch (2A/2B) —  150A 600A Auxiliary switch and alarm contact —  1 175A — Shunt trip (specify voltage)  — 200A — Undervoltage release mechanism  — 1 225A — 250A — 1 Dimensions Approximate Dimensions in Inches (mm) 1 1 Drawout Group-Mounted “X” Space Factors b Group-Mounted Width 1 Breaker Family Type Chassis “X” Space and Configuration Required 38.00 (965.2) 48.00 (1219.2) JG family, single mount 7X   1 JG family, dual/twin mount 7X —  1 LG family, single mount 9X   LG family, dual/twin mount 9X —  1 NNote a Only one accessory per position. 1 b 1X = 1-3/8 inch. 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 6-45 Low Voltage Switchboards and Switchgear Pow-R-Line C Switchboards with Drawout Moulded-Case Circuit Breaker

1 Layout for Branch and Horizontally Mounted Main Devices—PRLC Instructions 2 Determine box size by locating all main and feeder devices in your panel. The width of box is determined by the maximum box size shown for each device. 3 4 5

Feeder Only 250A 6 7X JGS, JGH, JGC Single Drawout Max. 7 8

Main or Feeder 600A 9 9X LGS, LGH, LGC Single Drawout Max. 1 1

Main Only 1200A 1 6X a a a Fixed Mount Max. NGS , NGH , NGC

1 38 Inch (965.2 mm) Wide Box 1 Feeder Only Feeder Only 250A 7X JGS, JGH, JGC 1 Dual Drawout Dual Drawout Max. 1 1 Main or Feeder Main or Feeder 600A LGS, LGH, LGC 1 Dual Drawout Dual Drawout 9X Max. 1 48 Inch (1219.2 mm) Wide Box 1

1 a 100% rated breaker. b Optional 750 kcmil terminal requires 44-inch (1117.6 mm) wide box. 1 c Contact Eaton for availability. 1 1 1 1 1 1 1 1

6-46 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Pow-R-Line C Switchboards with Drawout Moulded-Case Circuit Breaker

This page intentionally left blank. 1 2 3 4 5 6 7 8 9 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 6-47 Low Voltage Switchboards and Switchgear Generator Connection Assemblies

1 Typical Generator Quick Connect Assembly Contents Description Page 2 Generator Quick Connect Switchboards...... Standards and Certifications...... 7-49 3 Product Selection...... 7-49 Technical Data and Specifications...... 7-49 4 Dimensions...... 7-49 5 Customer Service Termination Enclosure...... 7-50 Roll-Up Generator Quick Connect Assembly...... 7-52 6 7 8 External View Internal View 9 1

1 Generator Quick Connect Switchboards

1 Product Description Application Description Features, Benefits Safer and More Reliable The Eaton Generator Quick The Generator Quick Connect and Functions • Reduces the potential 1 Connect Switchboard is Switchboard can be applied safety hazards associated an engineered assembly in both new and retrofit Reduced Downtime with connecting the 1 designed to allow safe applications. (Speed of Connection) mobile generator to and reliable connection of The Generator Quick Connect the facility’s electrical The switchboard supports a mobile generator to the Switchboard is ready for system under lost power 1 all market segments and facility’s electrical system. immediate connection. conditions applications, such as: Once the Quick Connect • Eliminates the safety The Eaton Quick Connect 1 • Switchboard is installed: hazards of generator includes Cam-type Commercial facilities cables lying in the path of receptacles, standard • Institutions and 1 • A permanent connection customers or employees mechanical lugs, a dedicated school boards point for temporary mobile generator-service disconnect, • Retail buildings power is established 1 Reduced Emergency Costs and a manual key-interlock • Industrial facilities • No additional field transfer scheme. The • Residential facilities modifications to the The costs associated with 1 switchboard provides a temporarily connecting • Health care facilities internal switchboard are quick and safe supply of required to connect the mobile generators, such as • Wastewater treatment 1 emergency power to parts of generator cables modifying switchboards, the electrical power system facilities • Modifications to the making physical modifications that are not covered by the • Data centres to buildings, and routing 1 emergency power system; facility’s physical structure to accommodate generator cables to connect the mobile it can also back up existing generator, are eliminated or 1 generators. cables (e.g., drilling holes in walls) is not required greatly reduced. 1 Loads connected to the • No routing of cables Generator Quick Connect through doorways, Switchboard can be safely windows, hallways or 1 transferred to an alternative staircases is required power source. 1 1 1 1 1 1

7-48 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Generator Connection Assemblies

Decreased Utility Dependency Standards and Certifications Technical Data and Specifications The Quick Connect • CSA® C22.2 No. 31 1 Switchboard allows the Generator Quick Connect kW Ratings (Rated up to 600V) a facility to switch between 2 kW (Maximum) Rating c utility feed and generator feed, without relying on utility 80% Rated Generator 100% Rated Generator 3 Ampere Disconnect Breaker Disconnect Breaker for disconnect service. b Rating 600V 208V 600V 208V 4 Product Selection 400 266 92 332 115 600 399 138 498 173 Standard Generator Quick 5 Connect Assembly 800 531 184 664 230 1200 797 276 996 345 • Standard ratings available 6 up to 2000A (80% rated) 1600 1063 368 1329 461 or 1600A (100% rated) Generator Quick Connect Main Breaker Ratings 7 • Detailed operating instructions mounted Breaker Maximum Interrupting Rating (kA) 8 Cam Lock Receptacles with on front cover Frame Ampere Rating 240V 600V Colour-Coded Generator Connections • The Generator Service N-Frame 1200 65, 100 25, 35, 65 9 Disconnect is a CSA R-Frame 1600 125, 200 50, 65 approved circuit breaker key interlocked with the R-Frame 2000 (80% rated) 125, 200 50, 65 1 service disconnect • Accessories include Generator Quick Connect Schematic 1 ground fault, shunt trip, auxiliary contacts and 1 alarms Building Wall • Colour-coded Cam-type Inside Generator Quick Connnect Switchboard 1 Bottom Flip-Up Cover for plug receptacles for easy Easy Access to Incoming Lugs connection to generator or Cam Lock Receptacles 1 • Mechanical lugs are Generator Cable Portable provided for alternate Generator Power 1 method of connecting generator cables Underground Conduit 1 • Standard enclosure is CSA Type 1; sprinklerproof, Type 2, 3R are optional 1 • Pow-R-Line C™ Dimensions 1 construction similar Approximate Dimensions in Inches (mm) to Eaton’s standard switchboard Standard structures are 24.00 inches (762.0 mm) deep, by 1 30.00 inches (762.0 mm) wide by 90.00 inches (2286.0 mm) high. Custom Generator Quick 1 Connect Assembly CSA Type 3R enclosures are equipped with a 13.00-inch (330.0 mm) front structure extension. • Accommodates ratings 1 greater than 1600A NNote (100% rated) or 2000A a (80% rated); consult Eaton 50 kAIC standard bus bracing. 1 for more information b Standard ratings up to 1600A; for higher amperages, consult Eaton. c • Custom integration into Calculated using the following: kW (max.) = [(V*A*1.73*PF)/1000]*(breaker rating) 1 with PF (power factor) equaling 0.8. switchboard lineups are available; consult Eaton 1 for more information 1 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 7-49 Low Voltage Switchboards and Switchgear Generator Connection Assemblies

1 Customer Service Termination Enclosure Contents Description Page 2 Generator Quick Connect Switchboards...... 7-48 Customer Service Termination Enclosure...... 3 Catalogue Number Selection...... 7-51 Product Selection...... 7-51 4 Technical Data and Specifications...... 7-51 5 Roll-Up Generator Quick Connect Assembly...... 7-52 6 7 8 9 1

1 Customer Service Termination Enclosure

1 Product Description Features, Benefits Busbar System Standards and Certifications Eaton Customer Service and Functions • Standard aluminum • CSA C22.2 No. 31 1 Termination Enclosures bussing (CSTEs) are the splitter Enclosure • Optional copper bussing; 1 connection assemblies Eaton CSTEs are made please consult Eaton for between utility transformers with code gauge steel more information and the customer’s main construction. Standard 1 distribution for specific enclosures are CSA Type 3R, Utility Metering utility applications. complete with ventilation 1 and a padlocking handle. Utility CTs and PTs are installed by others. Optional 1 Both pad-mounted and remote meter assemblies wall-mounted designs available—EATON #M501. 1 are available. Terminations 1 • Load mechanical lugs to suit #2–500 kcmil 1 • Provisions for utility two- hole compression lugs— 1 on line side 1 1 1 1 1 1 1 1 1

7-50 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Generator Connection Assemblies

Catalogue Number Selection 1 CSTE 4 1 M W 2 3 Ampere Rating Design 4 = 400A Volts Connection P = Pad-mount 6 = 600A 1 = 120/240 M = Utility W = Wall-mount 4 8 = 800A 2 = 120/208 metering 10 = 1000A 6 = 347/600 S = Splitter 5 12 = 1200A 16 = 1600A 20 = 2000A 6 25 = 2500A 30 = 3000A 7 NNot Please use catalogue number selection for purchasing. 8 9 Product Selection Approximate Dimensions in Inches (mm) 1

Wall-Mounted CSTE Available as Splitter Only 1 Ampere Rating Width Depth Height 1 400 30.00 (762.0) 10.00 (254.0) 30.00 (762.0) 600–1000 36.00 (914.4) 16.00 (406.4) 46.00 (1168.4) 1 1200–2000 46.00 (1168.4) 23.00 (584.2) 48.00 (1219.2) 2500–4000 60.00 (1524.0) 30.00 (762.0) 60.00 (1524.0) 1 Wall-Mounted CSTE Available as Splitter with Utility Metering Provisions 1 Ampere Rating Width Depth Height 400 30.00 (762.0) 10.00 (254.0) 30.00 (762.0) 1 600–1000 36.00 (914.4) 16.00 (406.4) 46.00 (1168.4) 1200–1600 46.00 (1168.4) 23.00 (584.2) 48.00 (1219.2) 1 2000–4000 60.00 (1524.0) 30.00 (762.0) 60.00 (1524.0) 1 Pad-Mounted CSTE Available as Splitter Only or Splitter with Utility Metering Provisions 1 Ampere Rating Width Depth Height 1 400–1000 36.00 (914.4) 16.00 (406.4) 52.00 (1320.8) 1200–1600 46.00 (1168.4) 23.00 (584.2) 48.00 (1219.2) 1 2000–4000 60.00 (1524.0) 30.00 (762.0) 60.00 (1524.0) 1 Technical Data and Specifications 1 Ratings • 120/240 Vac 1 • 208Y/120V • 600Y/347V 1 • Ampere ratings of 400, 600, 800, 1000, 1200, 1600, 2000, 2500, 3000A (for ratings above 3000A, consult Eaton) 1 • Assembly short-circuit rating: 50,000A rms symmetrical 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 7-51 Low Voltage Switchboards and Switchgear Generator Connection Assemblies

1 Roll-Up Generator Quick Connect Assembly Contents Description Page 2 Generator Quick Connect Switchboards...... 7-48 Customer Service Termination Enclosure...... 7-50 3 Roll-Up Generator Quick Connect Assembly...... Catalogue Number Selection...... 7-53 4 Product Selection...... 7-53 5 Technical Data and Specifications...... 7-53 6 7 8 9 1

1 Roll-Up Generator Quick Connect Assembly

1 Product Description Features, Benefits Busbar System Standards and Certifications Eaton’s Roll-Up Generator and Functions • Standard aluminum • CSA C22.2 No. 31 1 Quick Connect Assembly bussing is the connection assembly Enclosure • Optional copper bussing, 1 between the temporary Eaton Roll-Up Generator please consult Eaton for generator and the customer’s Quick Connect Assemblies more information main distribution or transfer are made with code gauge 1 switch. steel construction. Standard Terminations enclosure is CSA Type 3R 1 Roll-Up Generator Quick • Accommodates Connect Assemblies are with a padlocking handle; Type 4X is optional. mechanical and 1 splitter connection points compression lugs housing generator connection Both pad-mounted and • Provisions for two-hole points and load connection wall-mounted designs compression lugs or 1 points. are available. cam lock receptacles 1 1 1 1 1 1 1 1 1 1 1 1

7-52 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Generator Connection Assemblies

Catalogue Number Selection 1 RUG 4 1 PC 2 3 Ampere Rating Design 4 = 400A Volts P = Pad-mount 6 = 600A 1 = 120/240 W = Wall-mount 4 8 = 800A 2 = 120/208 PC = Pad-mount (cam lock) 10 = 1000A 6 = 347/600 WC = Wall-mount (cam lock) 5 12 = 1200A 16 = 1600A 20 = 2000A 6 25 = 2500A 30 = 3000A 7 NNot Please use catalogue number selection for purchasing. Catalogue number selection is for 8 standard CSA Type 3R enclosure. Consult Eaton for CSA Type 4X enclosures. 9 Product Selection Approximate Dimensions in Inches (mm) 1 1 Wall-Mounted Roll-Up Generator Quick Connect Assembly Available as Splitter Connection with or without Cam Locks 1 Ampere Rating Width Depth Height 600–1000 36.00 (914.4) 16.00 (406.4) 46.00 (1168.4) 1 1200–1600 46.00 (1168.4) 23.00 (584.2) 48.00 (1219.2) 2000–4000 60.00 (1524.0) 30.00 (762.0) 60.00 (1524.0) 1

Pad-Mounted Roll-Up Generator Quick Connect Assembly Available as 1 Splitter Connection without Cam Locks Ampere Rating Width Depth Height 1 600–1000 36.00 (914.4) 16.00 (406.4) 58.00 (1473.2) 1200–1600 46.00 (1168.4) 23.00 (584.2) 60.00 (1524.0) 1 2000–4000 60.00 (1524.0) 30.00 (762.0) 72.00 (1828.8) 1 Pad-Mounted Roll-Up Generator Quick Connect Assembly Available as Splitter Connection with Cam Locks 1 Ampere Rating Width Depth Height 1 600–1600 46.00 (1168.4) 23.00 (584.2) 72.00 (1828.8) 2000–4000 60.00 (1524.0) 30.00 (762.0) 72.00 (1828.8) 1

Technical Data and Specifications 1

Ratings 1 • 120/240 Vac • 208Y/120V 1 • 600Y/347V • Ampere ratings of 600, 800, 1000, 1200, 1600, 2000, 2500, 1 3000A (for ratings above 3000A, consult Eaton) • Assembly short-circuit rating: 50,000A rms symmetrical 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 7-53 Low Voltage Switchboards and Switchgear Generator Connection Assemblies

1 This page intentionally left blank. 2 3 4 5 6 7 8 9 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

7-54 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Pow-R-Line C Switchgear

Pow-R-Line C Switchgear Contents 1 Description Page Standards and Certifications...... 8-58 2 Optional Breaker Accessories...... 8-58 Dimensions...... 8-60 3 4 5 6 7 8 9 1

Pow-R-Line C Switchgear 1

Product Description Features, Benefits • Standard 100 kA short- Structure Features 1 Eaton’s Pow-R-Line C™ and Functions circuit bus bracing Standard finish: Grey switchgear is an assembly • Lower installation and • Optional 150 and 200 kA paint finish (ANSI 61) using 1 of metal enclosures, each maintenance costs short-circuit bus bracing a modern, completely automated and continuously housing drawout or fixed • Higher interrupting ratings • Optional insulating barriers 1 mounted low voltage power and withstand ratings to isolate the cable monitored electrostatic circuit breakers. compartment from the powder coating. This • Better coordination 1 bus compartment continually monitored The Canadian switchgear is capability system includes spray • Both indoor and outdoor particularly designed for the • Increased tripping de-grease and clean, spray 1 construction market such sensitivity walk-in and non-walk-in enclosures; standard rinse, iron phosphate spray as data centres, hospitals, • Enhanced safety measures coating spray rinse, non- 1 retail, office buildings and enclosure is CSA Type • Higher quality, reliability chemical seal, oven drying, commercial applications. In 1; optional enclosures and maintainability are CSA Type 2, 3R; electrostatic powder spray 1 addition to power breakers, paint coating and oven curing. the switchgear includes • Communications and sprinklerproof optional control and measuring power quality monitoring • Full range of safety Integral base: The ruggedly 1 devices such as relays, and measuring capabilities solutions dealing with formed base greatly increases arc flash hazards by using the rigidity of the structure, instruments, meters, Pow-R-Line C switchgear 1 Eaton Arcflash Reduction reduces the possibility of instrument transformers and provides: control power transformers. Maintenance System damage during the installation 1 • 100% rated, fully features of the equipment, and is selective protection suitable for rolling, jacking Application Description Maximum ratings for • Integral microprocessor- and handling. A lifting angle 1 Switchgear is used to Pow-R-Line C switchgear are is bolted onto the top of the protect, control and monitor based breaker tripping 600 Vac, 12,000A continuous systems bus compartment structure 1 low voltage distribution cross bus and 200,000A for increased strength. systems. Primarily used as • Two-step stored-energy short-circuit capacity. “standalone” distribution breaker closing Heavy-duty door hinges: 1 assemblies, they can Each breaker door is also be incorporated into mounted with hinge pins. 1 secondary unit substations: Removal of the door is easily UPS systems and generator accomplished by just lifting 1 systems. Switchgear is ideally the hinge pin. This allows suited to applications such easy access to the breaker as construction, commercial internal compartment for 1 and utility with distribution inspection and maintenance. systems rated 600V or 1 below, 200 kAIC or below bus bracing, and 12,000A 1 or below continuous loads (cross bus). 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 8-55 Low Voltage Switchboards and Switchgear Pow-R-Line C Switchgear

Rear cover/doors: In Closing spring automatic Single-cylinder key interlock Ground: A ground bus is 1 Pow-R-Line C switchgear, discharge: Mechanical can be installed on the furnished the full length of standard rear bolted covers interlocking automatically breaker. Accessible on the the switchgear assembly and 2 are provided. 48.00-inch-wide discharges the closing faceplate of the breaker, the is fitted with terminals for (1219.2 mm) cells are split springs when the breaker device can be ordered to lock purchaser’s connections. 3 into two sections to facilitate is removed from its the breaker in the open or handling during removal and compartment. closed position. Glass reinforced polyester installation. Optional rear and bus bracing and 4 doors are also available. Optional safety shutters: support insulation system: Positive acting safety Bus Features Glass reinforced polyester 5 Through-the-door design: shutters that isolate the Buses and connections: is a total system providing The following functions may breaker connections to the Vertical and cross bus exceptional mechanical be performed without the main bus when the breaker ratings in Pow-R-Line C and dielectric withstand 6 need to open the circuit is withdrawn from the cell switchgear are based on a strength, as well as high breaker door—lever the is an option offered for CSA® and ANSI standard resistance to heat, flame and 7 breaker between positions additional safety beyond our temperature rise of 65°C moisture. Substantial testing (drawout), operate manual standard design. They reduce above a maximum ambient to demonstrate accelerated 8 charging system and view the potential of accidental air temperature of 40°C. effects of heating and cooling the spring charge status flag, contact with live bus. on the mechanical and 9 close and open breaker, view Optional insulating covers Bus ampacities: Vertical dielectric properties of this and adjust trip unit and read (“boots”) are furnished and cross bus ratings in system prove it to provide the breaker rating nameplate. on live main stationary Pow-R-Line C switchgear are superior performance for 1 disconnecting contacts in 2000, 3000, 4000, 5000 and decades of trouble-free Cassette design: The breaker compartments equipped for 6000A. In addition, an 8000, operation. 1 cassette supports the future breakers. 10,000 and 12,000A cross breaker in the cell, as well bus rating is available. Optional bus insulation: as on the movable extension Breaker inspection: Insulated bus systems with 1 rails when the breaker is When withdrawn on the Bus bracing: Vertical bus removable PVC boots for placed into or removed rails, breaker is completely configuration provides an inspection and maintenance. 1 from the cell. The extension accessible for visual optional industry-leading rails allow the breaker to be inspection; tilting is not short-circuit withstand rating Barriers: Optional vented 1 drawn out without having necessary. The rails are of 200,000A. Standard polypropylene barriers to de-energize the entire permanent parts of every bracing is 100,000A. It has isolate the main bus and switchgear lineup. breaker cassette. been verified through testing connections from the cable 1 to maximum withstand compartment providing Accessibility: When the rear Interference interlocks: 200,000A short-circuit for added safety to the workers 1 door is open or removed, Supplied on breakers and a full 30 cycles. while reducing the potential each breaker compartment in compartments where of objects falling into the bus 1 provides front access to the compartments are of NNote Short-circuit rating of compartment. In addition, isolated, vertical wireways, the same physical size. switchgear assembly is limited to vertical barriers between the interrupting capacity of the primary disconnects and Interference interlocks ensure lowest rated branch device. cable sections can be added 1 other breaker compartment an incorrect breaker cannot to reduce potential hazards. accessories for ease of field be inserted. Plating: Bolted, silver-plated Barriers are removable 1 wiring and troubleshooting to give access to the bus Optional key interlock copper main buses are field connections. standard. The plating is compartment for inspection (cassette mounted): This and maintenance. 1 Four-position drawout: mechanism holds the breaker over the entire length of the Breakers can be in connected, cell mechanically trip-free to bar, not just at the joints. 1 test, disconnected or prevent electrical or manual Optional tin-plated copper removed position. The closing. Breaker can be buses are available. 1 breaker can be moved stored in compartment, and Full neutral: For four-wire between the connected, test completely removed for applications, the neutral 1 and disconnected positions maintenance or for use as bus is rated 100% of main while the compartment door a spare without disturbing bus rating as standard. 1 is closed. the interlock. Modification of Neutral cross bus ratings up the breaker is not required. to a maximum of 12,000A Single- or double-cylinder are available as an option. 1 cassette-mounted key Additionally, four-pole interlock is available as breakers can be used in 1 an option. conjunction with four-wire systems. 1 1 1 1

8-56 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Pow-R-Line C Switchgear

Wiring Features Control wire: Standard wire Surge Protection Device (SPD) Integrated Transfer Switches Cable compartment: is Type SIS insulated stranded Standard integrated surge Eaton automatic transfer 1 The cable compartment gives copper, extra flexible No. 14 protection device with switches (using power ample room for terminating AWG minimum. integral disconnect is circuit breakers, including 2 the power cables. Removable Control wire marking: available if required. The SPD optional bypass-isolation top roof sheets allow for Control wire marking is is mounted on the back pan, type) can be integrated 3 easy conduit hub installation. provided as a standard at and the removable display into a switchgear lineup. The floor of the cable each end of the wire. As an is mounted on the door; the Electrical and mechanical 4 compartment is open to allow option, wire marking can be SPD is protected by a small coordination is ensured when cable entry from underground added to the control wiring 30A fusible rotary switch. power circuit breaker transfer 5 duct banks. Optional bottom by using heat shrink sleeve Please refer to Tab 9— switches are integrated into plates are available. type marking. This marking is Components or contact the switchgear. Maximum designed to be a permanent, Eaton for more information. selectivity is achieved due 6 In addition to cable, custom to the high withstand rating busway and nonsegregated one-piece, heat-shrink sleeve designed to provide clear, of the power circuit breaker 7 bus duct can be terminated PLC Transfer Schemes transfer switch. in the compartment. durable identification of wires and cables. Advanced PLC-based transfer 8 Lug pad: The lugs are and load shedding schemes can be designed for various Advanced Metering located on the breaker run- Secondary terminal and Communications compartment: There are applications such as data 9 backs to accommodate lug Eaton has an extensive line of orientations at an optional 72 finger-safe secondary centres, health care facilities connections for a standard and waste water treatment powerful metering products, 1 45-degree angle. This reduces trip units, controllers and the bending radius of the frame Pow-R-Line C breaker. plants. HMI is optional for The customer’s secondary touch screen monitoring and gateways that can be wired cable needed for making the together in switchgears to 1 connections, thus reducing terminal connections are control of incoming, tie located at the front of the and feeder power circuit create an intelligent system installation and maintenance and interface with Building 1 time. Mechanical setscrew structure behind an optional breakers. Contact Eaton for separate door, providing more information. Management and SCADA type lugs are standard. Systems. Optional NEMA two-hole access to these connections 1 compression lugs are without the need to open the Bus Duct Integration available. breaker compartment door. Special Dimensions 1 Custom bus duct can be and Configurations Control raceway: A vertical Short-circuiting terminal integrated into switchgear Eaton has the ability to offer wireway is provided for blocks: Based on customer assemblies. Eaton can design 1 custom dimensions to suit routing of factory wiring in specific requirement. Consult and manufacture custom bus limited space requirements. each switchgear section. Eaton for more information. duct flanges to coordinate 1 Special heights, special Breaker secondary terminal with the bus duct risers of a Shipping split connection: depths and widths, corner blocks are mounted as wide range of amperage. As an option, at each sections, back-to-back 1 standard above each circuit shipping split, the control and front-access-only breaker. The terminal blocks connections are made with Transformer and configurations are available. 1 are rated 30A, and will plug-in terminal blocks rated MCC Close-Coupling accept bare wire, ring or 300V, 10A. The terminal Close-couple dry type, spade terminals for wire size Arc Flash Considerations 1 blocks mechanically interlock liquid-filled transformers or maximum of No. 10. without removing the motor control centres (MCC) Arc flash is an ongoing 1 Control circuits may be wired line or load connections. with standard switchgear concern in the electrical in all cells without removing This method of making configurations can be industry. Eaton can offer the circuit breaker. In the shipping split control supplied. Transformer unit- a variety of solutions to 1 addition, power circuits may connections increases the substations and MCC bus- reduce the risk of arc flash be connected in the rear of speed of installation and coordination would create such as Arcflash Reduction 1 the switchgear at the same reduces the potential of a most compact lineup and Maintenance System in time control circuits are being incorrect connections. minimization of installation power circuit breakers, safety 1 wired in the front of the time by eliminating cable shutters in Magnum drawout switchgear. installations. power circuit breakers, infra- red viewing windows and 1 For applications involving remote racking accessories. excessive wiring, or 1 nonstandard terminal blocks, terminal blocks are optionally 1 mounted on the rear frame with the power cables where they are readily accessible 1 for customer’s connections and inspection. 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 8-57 Low Voltage Switchboards and Switchgear Pow-R-Line C Switchgear

Standards and Certifications Optional Breaker Lifting Device Options Padlockable Pushbutton Cover 1 • CSA® C22.2 No. 31 Accessories Eaton provides a variety of A padlockable cover is • ANSI C37.20.1 lifting options such as breaker available to limit access to the 2 Shunt Trip Device lifting yokes and portable lift ON and OFF pushbuttons. • Built in an ISO® certified facility The shunt trip opens trucks. Please refer to Eaton catalogue PG01301002E 3 the circuit breaker Mechanical Operations Counter instantaneously when its (Miscellaneous Accessories) 4 coil is energized by a voltage for more information. The operations counter is input. A total of two shunt a mechanical device used to provide a record of the trips can be mounted on an Auxiliary Switch 5 Eaton power circuit breaker. number of circuit operations. Eaton’s Magnum DS Power An auxiliary switch provides It is mounted in the lower 6 Circuit Breakers comply with: remote electrical indication if right portion of the circuit Electrical Motor Operator the circuit breaker is open or breaker and can be viewed • ANSI C37.13 7 A motor operator is an closed. Up to three auxiliary through the front cover. • ANSI C37.16 assembly switches can be mounted • in the circuit breaker. Each 8 ANSI C37.17 internally mounted in the Key Off Lock Provisions • ANSI C37.50 circuit breaker. It charges the switch has two normally open closing springs electrically for (“a”) and two normally closed The key off lock secures 9 NNote Consult Eaton for remote or local operation. The (“b”) contacts for a total of the circuit breaker in the Seismically Qualified designs 12 available contacts. OFF position. It is mounted and for ANSI certified designs. motor operator can be factory or site installed. in the lower right portion of 1 the circuit breaker and can Mechanical Trip Indicator Flag be viewed through the front 1 Spring Release Device A red, pop-out mechanical cover. The customer supplies The spring release remotely trip flag is located just above the key lock. The provisions 1 closes the circuit breaker the trip unit in the circuit available are for Kirk. when the coil is energized by breaker’s front cover. It operates by popping out 1 a voltage input. The closing Latch Check Switch spring must already be to indicate that the circuit 1 charged for the device breaker opened in response A latch check switch (LCS) to work. to an overcurrent condition. indicates when the circuit The flag is manually reset by breaker is “ready to close”. 1 pushing it back into position. The internal version of the Bubble Cover The circuit breaker can be re- LCS is wired to the spring 1 Plexiglass breaker covers closed, even if the flag is not release. It will not permit for security and dust ingress reset. An optional overcurrent activation of the spring protection. trip switch, however, can be release until the circuit 1 used as an electrical lockout. breaker is fully charged and the trip latch is reset. 1 Undervoltage Release The undervoltage release Bell Alarm / Overcurrent Cassettes 1 opens the circuit breaker Trip Switch when its supply voltage falls An overcurrent trip switch For information on breaker below 70%. If the release is (bell alarm) provides an cassettes, refer to Eaton 1 not energized to 85% of its electrical indication when catalogue RP01301001E. supply voltage, the circuit a circuit breaker trips as 1 breaker cannot be reclosed a result of an overcurrent electrically or manually. condition. Opening as a result 1 of a circuit breaker’s manual open button, shunt trip or 1 undervoltage release does not cause the overcurrent trip 1 switch to operate. 1 1 1 1 1 1

8-58 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Pow-R-Line C Switchgear

Pow-R-Line C Switchgear—Typical Cell Configurations 1 Maximum 3000A Cross Bus a 2 3 Instrument Inst. Inst. Inst. Compartment Comp. Comp. Comp. or SPD or SPD or SPD 4 Main c Main Tie Feeder 800–12000–1600 5 800–1200 800–1200 800–1200 2000–2500–3000 1600–2000 1600–2000 1600–2000 90.00 90.00 3000 90.00 3000 90.00 6 (2286.0) (2286.0) (2286.0) c (2286.0) Feeder b b Blank or b Blank or b 800–1200 Feeder Tie or 1600–2000 7 Utility Feeder CT/PT Compartment Feeder 8 Blank or Blank or 800–1200 Feeder Feeder 1600–2000 9 d d d 38.00 24.00 24.00 24.00 (965.2) (609.6) (609.6) (609.6) 1

72.00/78.00/84.00/90.00 72.00/78.00/84.00/90.00 72.00/78.00/84.00/90.00 72.00/78.00/84.00/90.00 (1828.8/1981.2/2133.6/2286.0) (1828.8/1981.2/2133.6/2286.0) (1828.8/1981.2/2133.6/2286.0) (1828.8/1981.2/2133.6/2286.0) 1 1 1 3000A Maximum, 3200A, 4000A, 5000A, 6000A, 8000A Cross Bus a 4000A, 5000A, 6000A Cross Bus a 1 1 Feeder Inst. Inst. Instrument 800–1200 Comp. Comp. Compartment or SPD 1 1600–2000 or SPD or SPD

Feeder Feeder Feeder Main 1 800–1200 800–1200 800–1200 4000–5000–6000 1600–2000 1600–2000 1600–2000 90.00 Transition 90.00 90.00 2500 90.00 90.00 1 (2286.0) Cell (2286.0) (2286.0) (2286.0) Feederf (2286.0) Feeder e e e Blank or c 800–1200 e 800–1200 Feeder 1600–2000 1 1600–2000 Utility e 2500–3000 CT/PT Feeder Feeder Feederf Compartment 1 800–1200 800–1200 800–1200 1600–2000 1600–2000 1600–2000 2500 2500–3000 1 d d d d 24.00 24.00 24.00 24.00 48.00 1 (609.6) (609.6) (609.6) (609.6) (1219.2) 78.00/84.00/90.00 78.00/84.00/90.00 78.00/84.00/90.00 78.00/84.00/90.00 78.00/84.00/90.00 1 (1981.2/2133.6/2286.0) (1981.2/2133.6/2286.0) (1981.2/2133.6/2286.0) (1981.2/2133.6/2286.0) (1981.2/2133.6/2286.0) 1 NNote a Higher bus ampacities available; please contact Eaton for more information. 1 b 90.00-inch (2286.0 mm) height does not include optional base channel. Standard height is 1.50 inches (38.1 mm), custom height of 2.00 inches (50.8 mm) or 4.00 inches (101.6 mm) available. c Maximum one tie breaker per cell. 1 d 30.00-inch-wide (762.0 mm) cells are available for certain applications. Contact Eaton for more information. 1 e Feeder can be 800, 1200, 1600, 2000A; blank if there are two 2500A feeders in the same distribution section. f Maximum one 3000A feeder per cell. 1 Consult Eaton for custom layouts. 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 8-59 Low Voltage Switchboards and Switchgear Pow-R-Line C Switchgear

4000A, 5000A, 6000A Cross Bus a 1 2 Instrument Instrument Instrument Instrument Compartment or SPD Compartment or SPD Compartment or SPD 3 Compartment or SPD 4 Main Main Main 4000–5000 4000–5000 4000 Feeder 5 90.00 90.00 90.00 90.00 4000–5000 (2286.0) (2286.0) (2286.0) (2286.0) 6 b b b b

Tie 7 Blank Blank 4000 8 Blank

9 48.00 48.00 48.00 48.00 (1219.2) (1219.2) (1219.2) (1219.2) 78.00/84.00/90.00 78.00/84.00/90.00 78.00/84.00/90.00 78.00/84.00/90.00 1 (1981.2/2133.6/2286.0) (1981.2/2133.6/2286.0) (1981.2/2133.6/2286.0) (1981.2/2133.6/2286.0) 1 1 NNote a Higher bus ampacities available; please contact Eaton for more information. b 90.00 inch (2286.0 mm) height does not include optional base channel. Standard height is 1.50 inches (38.1 mm), custom height of 2.00 inches (50.8 mm) or 4.00 inches (101.6 ) available. 1 Main breaker can be in cell B, C or D. 1 Consult Eaton for custom layouts.

1 Dimensions 1 Approximate Dimensions in Inches (mm) 1 Switchgear Dimensions Pow-R-Line C Interrupting Short-Time 1 Cell Width Breaker Frame Rating Rating 24.00 (609.6) or 800A, 1600A, 2000A, Maximum 100 kA 85 kA for 60 cycles 1 30.00 (762.0) 3000A, 3200A 48.00 (1219.2) 4000A, 5000A, 6000A Maximum 100 kA 100 kA for 60 cycles 1 1 Breaker Frame Size Ampere 1 Rating Height Depth Width 800–3200 16.40 (416.6) 15.40 (391.2) 16.30 (414.0) 1 4000–6000 16.40 (416.6) 15.40 (391.2) 34.20 (868.7) 1 1 1 1 1 1 1

8-60 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

Switchboard Accessories and Modifications Contents 1 Description Page Moulded-Case Circuit Breakers 2 Magnum Power Circuit Breakers...... 9-64 Trip Units...... 9-65 3 Fusible Switches...... 9-71 Surge Protection Devices...... 9-75 4 Metering...... 9-76 5 6 7 8 Series C Moulded-Case Circuit Breaker Product Family 9 1

Moulded-Case Circuit Breakers 1 1 Quick Reference—Series C® Circuit Breakers a CSA® Listed Interrupting Ratings rms Symmetrical Amperes (kA) Circuit Cont. Amp. 1 Breaker Rating No. of Volts Trip Vac Ratings Vdc Ratings c Type @ 40°C Poles AC DC Type b 120 120/240 240 277 347 480Y/277 480 600Y/347 600 125 250 125/250 1 F-Frame ED 100–225 2, 3 240 125 N.I.T. — — 65 — — — — — — 10 — — 1 EDH 100–225 2, 3 240 125 N.I.T. — — 100 — — — — — — 10 — — EDC 100–225 2, 3 240 125 N.I.T. — — 200 — — — — — — 10 — — 1 EHD 15–100 1 277 125 N.I.T. — — — 14 — — — — — 10 — — EHD 15–100 2, 3 480 250 N.I.T. — — 18 — — — 14 — — — 10 — 1 FDB 15–150 1 347 125 N.I.T. — — — — 14 — — — — 10 — — FDB 15–225 2, 3 600 250 N.I.T. — — 18 — — — 14 — 14 — 10 — 1 FDB 15–225 4 600 250 N.I.T. — — 18 — — — 14 — 14 — 10 — FD 15–150 1 347 125 N.I.T. — — — 35 18 — — — — 10 — — 1 FD 15–225 2, 3 600 250 N.I.T. — — 65 — — — 35 — 18 — 10 — FD 15–225 4 600 250 N.I.T. — — 65 — — — 35 — 18 — 10 — 1 FDE 15–225 3 600 — N.I.T. — — 65 — — — 35 — 18 — — — HFD 15–30 1 347 125 N.I.T. — — — 65 25 — — — — 10 — — 1 HFD 15–225 2,3 600 250 N.I.T. — — 100 — — — 65 — 25 — 22 — HFD 15–225 4 600 250 N.I.T. — — 100 — — — 65 — 25 — 22 — 1 HFDE 15–225 3 600 — N.I.T. — — 100 — — — 65 — 25 — — — FDC d 15–30 1 347 125 N.I.T. — — — — 30 — — — — 10 — — 1 FDC d 15–225 2, 3 600 250 N.I.T. — — 200 — — — 100 — 35 — 22 — FDC d 15–225 4 600 250 N.I.T. — — 200 — — — 100 — 35 — 22 — 1 FDCE d 15–225 3 600 — N.I.T. — — 200 — — — 100 — 25 — — — FD-LFD 15–150 3 600 — N.I.T. — — 200 — — 200 — — 200 — — — 1 NNote 1 a Refer to catalogue no. PG01200001K for complete Series C Moulded-Case Circuit Breaker information. b N.I.T. is non-interchangeable trip unit and I.T. is interchangeable trip unit. 1 c Two-pole circuit breaker, or two poles of three-pole circuit breaker at 250 Vdc. d Current limiting. 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 9-61 Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

1 Quick Reference—Series C Circuit Breakers a, continued CSA Listed Interrupting Ratings rms Symmetrical Amperes (kA) Circuit Cont. Amp. Volts Vac Ratings Vdc Ratings c 2 Breaker Rating No. of Trip Type @ 40°C Poles AC DC Type b 120 120/240 240 277 480 600 125 250 125/250 3 J-Frame JD 70–250 2, 3, 4 600 250 I.T. — — 65 — 35 18 — 10 — 4 HJD 70–250 2, 3, 4 600 250 I.T. — — 100 — 65 25 — 22 — JDC d 70–250 2, 3, 4 600 250 I.T. — — 200 — 100 35 — 22 — 5 K-Frame DK 250–400 2, 3 240 250 I.T. — — 65 — — — — 10 — 6 KD 100–400 2, 3, 4 600 250 I.T. — — 65 — 35 25 — 10 — CKD 100–400 2, 3, 4 600 250 I.T. — — 65 — 35 25 — 10 — 7 HKD 100–400 2, 3, 4 600 250 I.T. — — 100 — 65 35 — 22 — CHKD 100–400 2, 3, 4 600 250 I.T. — — 100 — 65 35 — 22 — 8 KDC d 100–400 2, 3, 4 600 250 I.T. — — 200 — 100 65 — 22 — 9 L-Frame LD 300–600 2, 3, 4 600 250 I.T. — — 65 — 35 25 — 22 — 1 CLD 300–600 2, 3, 4 600 250 I.T. — — 65 — 35 25 — 22 — HLD 300–600 2, 3, 4 600 250 I.T. — — 100 — 65 35 — 25 — 1 CHLD 300–600 2, 3, 4 600 250 I.T. — — 100 — 65 35 — 25 — LDC d 300–600 2, 3, 4 600 250 I.T. — — 200 — 100 50 — 25 — 1 CLDC d 300–600 2, 3, 4 600 250 I.T. — — 200 — 100 50 — 25 — MDL-Frame 1 MDL 300–800 2, 3 600 250 I.T. — — 65 — 50 25 — 22 — CMDL 300–800 2, 3 600 250 I.T. — — 65 — 50 25 — 22 — 1 HMDL 300–800 2, 3 600 250 I.T. — — 100 — 65 35 — 25 — CHMDL 300–800 2, 3 600 250 I.T. — — 100 — 65 35 — 25 — 1 N-Frame ND 400–1200 3, 4 600 — N.I.T. — — 65 — 50 25 — — — 1 CND 400–1200 3, 4 600 — N.I.T. — — 65 — 50 25 — — — HND 400–1200 3, 4 600 — N.I.T. — — 100 — 65 35 — — — 1 CHND 400–1200 3, 4 600 — N.I.T. — — 100 — 65 35 — — — NDC 400–1200 3, 4 600 — N.I.T. — — 200 — 100 65 — — — 1 CNDC 400–1200 3, 4 600 — N.I.T. — — 200 — 100 65 — — — R-Frame 1 RD 1600 800–1600 3, 4 600 — N.I.T. — — 125 — 65 50 — — — CRD 1600 800–1600 3, 4 600 — N.I.T. — — 125 — 65 50 — — — 1 RD 2000 1000–2000 3, 4 600 — N.I.T. — — 125 — 65 50 — — — CRD 2000 1000–2000 3, 4 600 — N.I.T. — — 125 — 65 50 — — — 1 RD 2500 1200–2500 3, 4 600 — N.I.T. — — 125 — 65 50 — — — RDC 1600 800–1600 3, 4 600 — N.I.T. — — 200 — 100 65 — — — 1 CRDC 1600 800–1600 3, 4 600 — N.I.T. — — 200 — 100 65 — — — 1 RDC 2000 1200–2500 3, 4 600 — N.I.T. — — 200 — 100 65 — — — CRDC 2000 1000–2000 3, 4 600 — N.I.T. — — 200 — 100 65 — — — 1 RDC 2500 1200–2500 3, 4 600 — N.I.T. — — 200 — 100 65 — — — HMCP Motor Circuit Protectors 1 Current Limit-R® Current Limiting Circuit Breakers—Non-Fused Type LCL 125–400 2, 3 600 — N.I.T. — — 200 — 200 100 — — — 1 TRI-PAC® Current Limiting Circuit Breakers—Fused Type FB 15–100 2, 3 600 250 N.I.T. — — 200 — 200 200 — — — 1 LA 70–400 2, 3 600 250 I.T. — — 200 — 200 200 — — — NB 300–800 2, 3 600 250 I.T. — — 200 — 200 200 — — — 1 NNote a Refer to catalogue no. PG01200001K for complete Series C Moulded-Case Circuit Breaker information. 1 b N.I.T. is non-interchangeable trip unit and I.T. is interchangeable trip unit. c Two-pole circuit breaker, or two poles of three-pole circuit breaker at 250 Vdc. 1 d Current limiting.

9-62 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

® Quick Reference—Series G Circuit Breakers a 1 Breaker Capacity (kA rms) Vac 50–60 Hz CSA Trip Units c 2 Max. Vac Vdc FT-AM /AT-AM Circuit Rated Ratings Ratings Electronic (Digitrip™ RMS 310) Thermal-Magnetic Electronic RMS d Breaker Current No. of Ampere Fixed Adjustable 3 Type (Amperes) Poles 240 480 600 125/250 b Range Interchangeable Built-In Thermal Thermal Magnetic LS LSI LSG LSIG JG-Frame 4 E 250 2, 3, 4 65 25 18 10 20–250     Adjustable     S 250 2, 3, 4 85 35 18 22 20–250     Adjustable     5 H 250 2, 3, 4 100 65 25 22 20–250     Adjustable     C 250 3, 4 200 100 35 42 20–250     Adjustable     6 U 250 3, 4 200 150 50 50 20–250     Adjustable     LG-Frame 7 E 600 3, 4 65 35 18 22 100–600     Adjustable  b  b  b  b 8 S 600 3, 4 85 50 25 22 100–600     Adjustable  b  b  b  b H 600 3, 4 100 65 35 42 100–600     Adjustable  b  b  b  b 9 C 600 3, 4 200 100 50 42 100–600     Adjustable  b  b  b  b U 600 3, 4 200 150 65 50 100–600     Adjustable  b  b  b  b 1

Quick Reference—Series G Circuit Breakers, continued 1 Breaker Capacity (kA rms) Vac 50–60 Hz Trip Units 1 Electronic Max. CSA Electronic (Digitrip RMS 310+, 1 Circuit Rated Vac Ratings (Digitrip RMS 310+) 610 and 910) Electronic d Breaker Current No. of Ampere Type (Amperes) Poles 240 480 600 Range Built-In Built-In LI LS LSI LIG LSG LSIG ALSI ALSIG 1 NG-Frame S 800, 1200 2, 3, 4 85 50 25 320–1200  — —   —     1 H 800, 1200 2, 3, 4 100 65 35 320–1200  — —   —     C 800, 1200 2, 3, 4 200 100 65 320–1200  — —   —     1 RG-Frame H 1600, 2000, 2500 3, 4 125 65 50 800–2500 —   e    e     1 C 1600, 2000, 2500 3, 4 200 100 65 800–2500 —   e    e     NNote 1 a Refer to catalogue no. CA08100005E for complete Series G Moulded-Case Circuit Breaker information. 1 b Two poles in series. c F = Fixed, A = Adjustable, T = Thermal, M = Magnetic. 1 d Not suitable for DC application. Four-pole ground fault not available. e Available only on Digitrip 610 and 910 trip units. 1 1 1 1 1 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 9-63 Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

1 Magnum Power Circuit Breakers Magnum DS® Low Voltage Power Circuit Breaker Family ANSI Rated for Switchgear Applications 2 3 4 5 6 7 8 9 1 Magnum DS Switchgear Low Voltage Power Circuit Breakers rms Symmetrical Current Ratings kA 50/60 Hz a Fixed Internal Available Current Sensor and Rating 1 Frame Breaker Type Frame Interrupting Interrupting Interrupting Short-Time Instantaneous Plugs for Digitrip RMS Trip Unit

Amperes Catalogue Number Type at 254 Vac at 508 Vac at 635 Vac Withstand Trip (Establishes Breaker In Rating) 1 800 MDS-408 Standard 42 42 42 42 — 200, 250, 300, 400, 600, 800 MDS-608 Standard 65 65 65 65 — 1 MDS-808 Standard 85 85 85 85 — MDS-C08 Standard 100 100 100 85 85 1 MDS-L08 b Standard 200 200 200 — — 1200 MDS-412 Standard 42 42 42 42 — 200, 250, 300, 400, 600, 800, 1000, 1200 1 MDS-512 Standard 50 50 50 50 — MDS-612 Standard 65 65 65 65 — 1 MDS-812 Standard 85 85 85 85 — 1 MDS-C12 Standard 100 100 100 85 — 1600 MDS-616 Standard 65 65 65 65 — 200, 250, 300, 400, 600, 800, 1000, 1 MDS-816 Standard 85 85 85 85 — 1200, 1600 MDS-C16 Standard 100 100 100 85 85 1 MDS-L16 b Standard 200 200 200 — — 2000 MDS-620 Standard 65 65 65 65 — 200, 250, 300, 400, 600, 800, 1000, 1200, 1 MDS-820 Standard 85 85 85 85 — 1600, 2000 MDS-C20 Standard 100 100 100 85 85 1 MDS-L20 b Standard 200 200 200 — — 3200 MDS-632 Standard 65 65 65 65 — 200, 250, 300, 400, 600, 800, 1000, 1200, 1 MDS-832 Standard 85 85 85 85 — 1600, 2000, 2500, 3000, 3200 MDS-C32 Standard 100 100 100 85 85 1 4000 MDS-840 Double 85 85 85 85 — 2000, 2500, 3200, 4000 MDS-C40 Double 100 100 100 100 — 1 5000 MDS-850 Double 85 85 85 85 — 2500, 3200, 4000, 5000 MDS-C50 Double 100 100 100 100 — 1 NNote a Interrupting ratings shown based on breaker equipped with integral Digitrip RMS trip unit. Interruption ratings for non-automatic breakers are equal to the published short-time withstand rating. These interruption ratings are based on the standard duty cycle consisting of an open operation, a 15-second interval and a close-open operation, in succession, with delayed tripping in case 1 of short-delay devices. The standard duty cycle for short-time ratings consists of maintaining the rated current for two periods of 1/2 seconds each, with a 15-second interval of zero current between the two periods. 1 b Magnum MDSL current limiting power circuit breaker with integral current limiters. Current limiter selected determines short-time and fixed instantaneous trip rating. Maximum voltage rating is 600 Vac. 1 1 1

9-64 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

Trip Units 1 Moulded-Case Digitrip Selection Guide 2 Trip Unit Digitrip Digitrip Digitrip Digitrip Digitrip Digitrip Digitrip Digitrip Type RMS 310+ RMS 310 RMS 510 RMS 610 RMS 810 RMS 910 OPTIM 550 OPTIM 1050 3 rms sensing Yes Yes Yes Yes Yes Yes Yes Yes Breaker Type 4 Frame FDE, JG, K, LG, NG, RG a K, L, M, N, R R R, RG R R, RG K, L, N K, L, N, R Ampere range 15–2500 15–2500 800–5000 800–5000 800–5000 800–5000 70–1200 70–5000 5 Interrupting rating at 480V 35, 65, 100, 150 kA 35, 65, 100 kA 65, 100 kA 65, 100 kA 65, 100 kA 65, 100 kA 35, 65, 100 kA 35, 65, 100 kA Protection 6 Ordering options LS, LSG LSI, LSIG LS, LSG LSI, LSIG LI, LS, LSI, LIG, LI, LS, LSI, LIG, LI, LS, LSI, LIG, LI, LS, LSI, LIG, LSI, LSI (A), LSI (A), LISG LSG, LSIG LSG, LSIG LSG, LSIG LSG, LSIG LSIG 7 Arcflash Reduction No ALSI, ALSIG b No No No No No No No No Maintenance System™ 8 Fixed rated plug (In) No Yes Yes Yes Yes Yes Yes Yes Yes Yes Overtemperature trip Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 9 Long Delay Protection (L)

Adjustable rating plug (In) No Yes No No No No No No 1 c Long delay pickup 40–100% frame 0.5–1.0 (In) 0.5–1.0 x (In) 0.5–1.0 x (In) 0.5–1.0 x (In) 0.5–1.0 x (In) 0.4–1.0 x (In) 0.4–1.0 x (In) Long delay time I2t 2–24 seconds 10 seconds 2–24 seconds 2–24 seconds 2–24 seconds 2–24 seconds 2–24 seconds 2–24 seconds 1 Long delay time I4t No No No No No No 1–5 seconds 1–5 seconds Long delay thermal memory Yes Yes Yes Yes Yes Yes Yes Yes 1

High load alarm Yes No No 0.85 x Ir 0.85 x Ir 0.85 x Ir 0.5–1.0 x Ir 0.5–1.0 x Ir Short Delay Protection (S) 1 d Short delay pickup Varies by frame 200–800% x (In) 200–600% 200–600% 200–600% 200–600% 150–800% 150–800% S1 and S2 x (I ) S1 and S2 x (I ) S1 and S2 x (I ) S1 and S2 x (I ) x (I ) x (I ) r r r r r r 1 Short delay time I2t Yes No 100 ms No 100–500 ms 100–500 ms 100–500 ms 100–500 ms 100–500 ms 100–500 ms Short delay time flat No Inst–300 ms No Inst–300 ms 100–500 ms 100–500 ms 100–500 ms 100–500 ms 100–500 ms 100–500 ms 1 Short delay time ZSI Yes No Yes Yes Yes Yes Optional Yes Instantaneous Protection (I) 1

Instantaneous pickup No Varies by No 200–800% 200–600% 200–600% 200–600% 200–600% 200–800% x (In) 200–800% x (In) frame d x (I ) M1 and M2 x (I ) M1 and M2 x (I ) M1 and M2 x (I ) M1 and M2 x (I ) n n n n n 1 Discriminator No No Yes e Yes e Yes e Yes e Yes Yes Instantaneous override Yes Yes Yes Yes Yes Yes Yes Yes 1 Ground Fault Protection (G) Ground fault alarm Yes Yes No No No No 20/25–100% f 20/25–100% gh 1 f f f f f f f gh Ground fault pickup 20–100% frame Var/frame 25–100% x In 25–100% x In 25–100% x In 25–100% x In 20/25–100% 20/25–100% Ground fault delay I2t No No 100–500 ms 100–500 ms 100–500 ms 100–500 ms 100–500 ms 100–500 ms 1 Ground fault delay flat Inst–300 ms Inst–500 ms 100–500 ms 100–500 ms 100–500 ms 100–500 ms 100–500 ms 100–500 ms Ground fault ZSI Yes No Yes Yes Yes Yes Optional Yes 1 Ground fault Yes Yes Yes Yes Yes Yes Yes Yes thermal memory 1 System Diagnostics Cause of trip LEDs No No Yes Yes Yes Yes Yes Yes 1 Magnitude of No No No Yes Yes Yes Yes Yes trip information 1 Remote signal contacts No No No Yes Yes Yes No Yes Legend NNote 1 BIM = Breaker Interface Module a No rating plugs necessary. e LS/LSG only. I = Sensor Rating s b Only available on LG, NG and f Not to exceed 1200A. 1 In = Rating Plug RG breaker. g L- and N-Frames *20–100% x I . Ir = LDPU Setting x In s c Adjust by rating plug. R-Frame *25–100% x I . n 1 d FDE and JG 200–1200% x In h By OPTIMizer/BIM. LG 200–1200% x I n 1 NG 200–900% x In RG 200–800% x In 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 9-65 Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

Moulded-Case Digitrip Selection Guide, continued 1 Trip Unit Digitrip Digitrip Digitrip Digitrip Digitrip Digitrip Digitrip Digitrip Type RMS 310+ RMS 310 RMS 510 RMS 610 RMS 810 RMS 910 OPTIM 550 OPTIM 1050 2 System Monitoring 3 Digital display No No No Yes Yes Yes Yes a Yes a Current No No No Yes Yes Yes Yes Yes 4 Voltage No No No No No Yes No No Power and energy No b No c No No Yes Yes No Yes 5 Power quality harmonics No No No No No Yes No Yes Power factor No No No No Yes (over Yes No Yes PowerNet only) 6 Communications 7 PowerNet™ No No No No Yes Yes Optional Yes Testing Testing method Test kit Test set Integral Integral Integral Integral OPTIMizer, OPTIMizer, BIM, 8 BIM, PowerNet PowerNet (optional) 9 Legend NNote BIM = Breaker Interface Module a By OPTIMizer/BIM. 1 Is = Sensor Rating b Yes, with addition of Power Monitoring/ In = Rating Plug Metering Module (PM3). I = LDPU Setting x I 1 r n c Yes, with addition of Energy Sentinel. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

9-66 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

Digitrip Trip Units for Magnum DS Power Circuit Breakers 1 Digitrip 520 Digitrip 520M Digitrip 520MC Digitrip 1150+ a 2 3

Trip Unit Type 4 Ampere range 200–6000A 200–6000A 200–6000A 200–6000A Interrupting rating at 480V 42–200 kA 42–200 kA 42–200 kA 42–200 kA 5 rms sensing Yes Yes Yes Yes Protection and Coordination 6 Protection Ordering options LI, LSI, LSIG LSI, LSIG, LSIA LSI, LSIG, LSIA LSI, LSIG, LSIA 7 Fixed rating plug (In) Yes Yes Yes Yes Overtemperature trip Yes Yes Yes Yes 8 Long delay protection (L) Long delay pickup 0.4–1.0 x (In) 0.4–1.0 x (In) 0.4–1.0 x (In) 0.4–1.0 x (In) Long delay time I2t at 6 x I 2–24 seconds 2–24 seconds 2–24 seconds 2–24 seconds r 9 Long delay time I4t No No No 1–5 seconds IEEE curves No No No Yes 1 Long delay thermal memory Yes Yes Yes Yes High load alarm No No No 0.5–1.0 x (I ) r 1 Short delay protection (S) Short delay pickup 200–1000% x (Ir) and M1 200–1000% x (Ir) and M1 200–1000% x (Ir) and M1 200–1000% x (Ir) and M1 Short delay time I2t at 8 x I 100–500 ms 100–500 ms 100–500 ms 100–500 ms r 1 Short delay time flat 100–500 ms 100–500 ms 100–500 ms 100–500 ms Short delay time ZSI Yes Yes Yes Yes 1 Instantaneous protection (I) Instantaneous pickup 200–1000% x (In) and M1 200–1000% x (In) and M1 200–1000% x (In) and M1 200–1000% x (In) and M1 Making current release Yes Yes Yes Yes 1 Off position LSI and LSIG Yes Yes Yes Ground fault protection (G) b Ground fault alarm No Yes Yes Yes 1 Ground fault pickup 25–100% x (In) 25–100% x (In) 25–100% x (In) 24–100% x (In) Ground fault delay I2t at 0.625 x I 100–500 ms 100–500 ms 100–500 ms 100–500 ms n 1 Ground fault delay flat 100–500 ms 100–500 ms 100–500 ms 100–500 ms Ground fault ZSI Yes Yes Yes Yes 1 Ground fault thermal memory Yes Yes Yes Yes Disable ground fault protection No No No No 1 Neutral protection (N) Model LSI Model LSI Model LSI Model LSI Legend NNote 1 a b In = Rating Plug and Sensor Rating Over and undervoltage alarm or trip, 1200A maximum ground fault setting over and underfrequency alarm or trip, ® Ir = Long Delay Pickup Setting per UL/NEC. 1 voltage unbalance alarm or trip, reverse power trip, and phase rotation alarm are included. 1 1 1 1 1 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 9-67 Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

1 Digitrip Trip Units for Magnum DS Power Circuit Breakers, continued Digitrip 520 Digitrip 520M Digitrip 520MC Digitrip 1150+ a 2 3

4 Trip Unit Type System Diagnostics 5 Cause-of-trip LEDs Yes Yes Yes Yes Magnitude of trip information No Yes Yes Yes 6 Remote signal contacts No Yes Yes Yes Programmable contacts No No No Yes 7 System Monitoring 8 Digital display No 4-character LCD 4-character LCD 24-character LED Current (% ) full scale sensor No Yes ±2% Yes ±2% Yes ±1% 9 Voltage (%) L to L No No No Yes ±1% Power and energy (%) No No No Yes ±2% 1 Apparent power kVA and demand No No No Yes Reactive power kVAR No No No Yes 1 Power factor No No No Yes Crest factor No No No Yes 1 Power quality—harmonics No No No Yes % THD, waveform capture No No No Yes 1 System Communications Type No No INCOM™ INCOM/TripLink 1 Power supply in breaker — Optional Standard Standard Additional Features 1 Trip log (three events) No No No Yes Electronic operations counter No No No Yes 1 Testing method b Test set Test set Test set Integral and test set Waveform capture No No No Yes 1 Arcflash Reduction Maintenance System No No Yes Yes Breaker health monitor No No No Yes 1 functions No No No Yes a Legend NNote 1 a b In = Rating Plug and Sensor Rating Over and undervoltage alarm or trip, Test set for secondary injection. Ir = Long Delay Pickup Setting over and underfrequency alarm or trip, 1 voltage unbalance alarm or trip, reverse power trip, and phase rotation alarm 1 are included. 1 1 1 1 1 1 1 1 1

9-68 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

Digitrip Trip Units for Magnum DS Power Circuit Breakers, continued 1 Digitrip 520i Digitrip 520Mi Digitrip 520MCi Digitrip 1150i+ a 2 3

Trip Unit Type 4 Ampere range 200–6300A 200–6300A 200–6300A 200–6300A Interrupting rating at 690V 40–100 kA 40–100 kA 40–100 kA 40–100 kA 5 rms sensing Yes Yes Yes Yes Protection and Coordination 6 Protection Ordering options LI, LSI, LSIG LSI, LSIG, LSIA LSI, LSIG, LSIA LSI, LSIG, LSIA 7 Fixed rating plug (In) Yes Yes Yes Yes Overtemperature trip Yes Yes Yes Yes 8 Long delay protection (L) Long delay setting 0.4–1.0 x (In) 0.4–1.0 x (In) 0.4–1.0 x (In) 0.4–1.0 x (In) Long delay time I2t at 6 x I 2–24 sec 2–24 sec 2–24 sec 2–24 sec r 9 Long delay time I4t No No No 1–5 sec IEC Type A, B, C curves No No No Yes 1 Long delay thermal memory Yes Yes Yes Yes High load alarm No No No 0.7–1.0 x I r 1 Short delay protection (S) Short delay pickup 200–1000% x (Ir) and M1 200–1000% x (Ir) and M1 200–1000% x (Ir) and M1 150–1000% x (Ir) and M1 Short delay time I2t at 8 x I 100–500 ms 100–500 ms 100–500 ms 100–500 ms r 1 Short delay time flat 100–500 ms 100–500 ms 100–500 ms 100–500 ms Short delay time ZSI Yes Yes Yes Yes 1 Instantaneous protection (I) Instantaneous pickup 200–1000% x (In) and M1 200–1000% x (In) and M1 200–1000% x (In) and M1 200–1000% x (In) and M1 Making current release Yes Yes Yes Yes 1 Off position Yes Yes Yes Yes Earth fault protection (G) Earth fault alarm No Yes Yes Yes 1 Earth fault pickup 25–100% x (In) 25–100% x (In) 25–100% x (In) 24–100% x (In) Earth fault delay I2t at 0.625 x I 100–500 ms 100–500 ms 100–500 ms 100–500 ms n 1 Earth fault delay flat 100–500 ms 100–500 ms 100–500 ms 100–500 ms Earth fault ZSI Yes Yes Yes Yes 1 Earth fault memory Yes Yes Yes Yes Disable ground fault protection No No No Yes 1 Neutral protection (N) Model LSI Model LSI Model LSI Model LSI Legend NNot 1 a In = Rating Plug and Sensor Rating Over and undervoltage alarm or trip, over and underfrequency alarm or trip, Ir = Long Delay Pickup Setting 1 i = Trip units are only used on voltage unbalance alarm or trip, reverse IEC breakers with earth fault power trip, and phase rotation alarm are included. 1 1 1 1 1 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 9-69 Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

1 Digitrip Trip Units for Magnum DS Power Circuit Breakers, continued Digitrip 520i Digitrip 520Mi Digitrip 520MCi Digitrip 1150i+ a 2 3

4 Trip Unit Type System Diagnostics 5 Cause of trip LEDs Yes Yes Yes Yes Magnitude of trip information No No No Yes 6 Remote signal contacts No Yes Yes Yes Programmable contacts No No No 2 7 System Monitoring 8 Digital display No 4-Character LCD 4-Character LCD 24-Character LED Current (%) full scale sensor No Yes ± 2% Yes ± 2% Yes ± 1% 9 Voltage (%) L to L No No No Yes ± 1% Power and energy (%) No No No Yes ± 2% 1 Apparent power kVA and demand No No No Yes Reactive power kVAR No No No Yes 1 Power factor No No No Yes Crest factor No No No Yes 1 Power quality—harmonics No No No Yes % THD No No No Yes 1 System Communications Type — — INCOM/PowerNet/Modbus b/ INCOM/PowerNet/TripLink/ 1 PROFIBUS b Modbus b/PROFIBUS b Power supply in breaker N/A Optional Standard Standard 1 Additional Features Trip log (three events) No No No Yes 1 Electronic operations counter No No No Yes Testing method c Test set Test set Test set Integral and test set 1 Waveform capture No No No Yes ARMs (Arcflash Reduction Maintenance System Mode) No No Yes Yes d 1 Breaker health monitor No No No Yes Programmable relay functions No No No Yes a 1 Legend NNot a In = Rating Plug and Sensor Rating Over and undervoltage alarm or trip, over and underfrequency alarm or trip, 1 Ir = Long Delay Pickup Setting i = Trip units are only used on voltage unbalance alarm or trip, reverse IEC breakers with earth fault power trip, and phase rotation alarm 1 are included b Requires externally mounted MMINT 1 or PMINT module. c Test set for secondary injection. 1 d Contact Eaton for availability. 1 1 1 1 1 1 1

9-70 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

Fusible Switches 1 Horizontally Mounted Fusible Switches Fusible Switch Ratings Rating Horizontally 2 (Amperes/Voltage) Type Unit Size a Mounted 30 250 AC or DC R 4X Twin 3 30/60/100A 600 AC R, J 4X Twin 60 250 AC or DC R 4X Twin 4 30/60/100A 600 AC R, J 4X Twin 5 200A 100 250 AC or DC R 4X Twin 600 AC R, J 5X Twin 6 400A 200 250 AC or DC R, T 6X Single or twin 600 AC R, J, T 6X Single or twin 7 400 250 AC or DC R, T 9X Single 600/800A 600 AC R, J, T 9X Single 8 600 250 AC R, T 11X Single 600 AC R, J, T 11X Single 9 800 250 AC T 11X Single 1200A 600 AC L, T 11X Single 1 1200 250 AC T 15X Single 600 AC L 15X Single 1 NNot a 1X = 1-3/8 inch. 1 1 1 Horizontally Mounted Fusible Switches—X Spacing a 1 30–60 30–60 100A 100A 4X 38.00 1 (965.2) Wide 200A 6X 1

30–60 30–60 5X 1 100A 100A

200A 200A 6X 1 1 400A 9X 1 48.00 (1219.2) Wide 600/800A 11 X 1 Structure 1 1 1200A 15X 1 1 NNote: 200A, 600V with Class R fuses available as a single unit only. 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 9-71 Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

Fusible Switch Selection Guide 1 Dimensions in Inches (mm)

2 30/60/100A 400A

3 18.00 (457.2) Wide, 4X High, Twin Fusible Switch 22.00 (558.8) Wide, 9X High, Single Fusible Switch a 4 Ampere Rating Ampere Rating Fuse Type Catalogue Number Unit 1 Unit 2 Fuse Type Catalogue Number 240 Vac or 250 Vac 5 240 Vac or 250 Vdc 400 R FDPW325R 30 30 R FDPWT3211R 400 (Main) R FDPW325MR 6 30 60 R FDPWT3212R 600 Vac 30 100 R FDPWT3213R 400 R FDPW365R 7 60 60 R FDPWT3222R 400 (Main) R FDPW365MR 60 100 R FDPWT3223R 400 J FDPW365J 8 100 100 R FDPWT3233R 400 (Main) J FDPW365MJ 600 Vac 9 30 30 R FDPWT3611R 18.00 (457.2) Wide, 16X High—Top Feed Main a 30 30 J FDPWT3611J Ampere Rating Fuse Type Catalogue Number 30 60 R FDPWT3612R 1 240 Vac or 250 Vac 30 60 J FDPWT3612J 400 R FDPW325TR 60 60 R FDPWT3622R 1 600 Vac 60 60 J FDPWT3622J 1 400 R FDPW365TR 22.00 (558.8) Wide, 5X High, Twin Fusible Switch 400 J FDPW365TJ

1 Ampere Rating 18.00 (457.2) Wide, 16X High—Bottom Feed Main a Unit 1 Unit 2 Fuse Type Catalogue Number Ampere Rating Fuse Type Catalogue Number 1 600 Vac 240 Vac or 250 Vac 30 100 R FDPWT3613R 400 R FDPW325BR 1 60 100 R FDPWT3623R 600 Vac 100 100 R FDPWT3633R 1 400 R FDPW365BR 400 J FDPW365BJ 1 200A NNot a For cable-in/cable-out application of a branch switch, additional terminals are required. 1 22.00 (558.8) Wide, 6X High, Twin Fusible Switch Order the terminal kit TA750FDPW. The kit contains three terminals and hardware. Ampere Rating 1 Unit 1 Unit 2 Fuse Type Catalogue Number 1 240 Vac or 250 Vdc 200 200 R FDPBT3244R 1 200 200 R FDPBT3244RDS 600 Vac 1 200 200 J FDPBT3644J 200 200 J FDPBT3644JDS 1 18.00 (457.2) Wide, 6X High, Single Fusible Switch 1 Ampere Rating Fuse Type Catalogue Number 240 Vac or 250 Vac 1 200 T FDPBS324F 200 R FDPBS324R 1 600 Vac 200 R FDPBS364R 1 200 J FDPBS364J 1 200 T FDPBS364F 1 1

9-72 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

600A 1200A 1 22.00 (558.8) Wide, 11X High, Single Fusible Switch a 22.00 (558.8) Wide, 15X High, Single Fusible Switch c Ampere Rating Fuse Type Catalogue Number Ampere Rating Fuse Type Catalogue Number 2 240 Vac or 250 Vac 240 Vac 3 600 R FDPW326R 1200 T FDPW328F 600 (Main) R FDPW326MR 1200 (Main) T FDPW328MF 4 600 Vac 600 Vac 600 R FDPW366R 1200 L FDPW368 5 600 (Main) R FDPW366MR 1200 (Main) L FDPW368M 600 J FDPW366J 6 600 (Main) J FDPW366MJ 22.00 (558.8) Wide, 16X High—Top Feed Main c Ampere Rating Fuse Type Catalogue Number 7 18.00 (457.2) Wide, 16X High—Top Feed Main a 240 Vac Ampere Rating Fuse Type Catalogue Number 1200 T FDPW328TF 8 240 Vac or 250 Vac 600 Vac 600 R FDPW326TR 1200 L FDPW368T 9 600 Vac 600 R FDPW366TR 22.00 (558.8) Wide, 16X High—Bottom Feed Main c 1 600 J FDPW366TJ Ampere Rating Fuse Type Catalogue Number 1 240 Vac 18.00 (457.2) Wide, 16X High—Bottom Feed Main a 1200 T FDPW328BF 1 Ampere Rating Fuse Type Catalogue Number 600 Vac 240 Vac or 250 Vac 1200 L FDPW368B 1 600 R FDPW326BR NNote 600 Vac a For cable-in/cable-out application of a branch switch, additional terminals are required. 1 600 R FDPW366BR Order two of the terminal kit TA750FDPW. Each kit contains three terminals and hardware. 600 J FDPW366BJ b For cable-in/cable-out application of a branch switch, additional terminals are required. 1 Order three of the terminal kit TA750FDPW. Each kit contains three terminals and hardware. c For cable-in/cable-out application of a branch switch, additional terminals are required. Order four of the terminal kit TA750FDPW. Each kit contains three terminals and hardware. 1 800A 1 22.00 (558.8) Wide, 11X High, Single Fusible Switch b Ampere Rating Fuse Type Catalogue Number 1 240 Vac 800 T FDPW327F 1 800 (Main) T FDPW327MF 600 Vac 1 800 L FDPW367 800 (Main) L FDPW367M 1

18.00 (457.2) Wide, 16X High—Top Feed Main b 1 Ampere Rating Fuse Type Catalogue Number 1 240 Vac 800 T FDPW327TF 1 600 Vac 800 L FDPW367T 1 18.00 (457.2) Wide, 16X High—Bottom Feed Main b 1 Ampere Rating Fuse Type Catalogue Number 240 Vac 1 800 T FDPW327BF 600 Vac 1 800 L FDPW367B 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 9-73 Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

1 FDPW Switch Ratings Short-Circuit Horsepower Rating Size and Type of Cu/Al 2 Ampere Rating Voltage Rating kAIC Standard Maximum Fuse Type Conductor per Phase 30A switch 240 Vac 200 3 7.5 R #14 to 1/0 3 480 Vac 200 5 15 R, J #14 to 1/0 600 Vac 200 7.5 20 R, J #14 to 1/0 4 250 Vdc 10 5 5 a #14 to 1/0 60A switch 240 Vac 200 7.5 15 R #14 to 1/0 5 480 Vac 200 15 30 R, J #14 to 1/0 600 Vac 200 15 50 R, J #14 to 1/0 6 250 Vdc 10 10 10 a #14 to 1/0 100A switch 240 Vac 200 15 30 R #14 to 1/0 7 480 Vac 200 25 60 R, J #14 to 1/0 600 Vac 200 30 75 R, J #14 to 1/0 8 250 Vdc 10 20 20 a #14 to 1/0 200A switch b 240 Vac 200 25 60 R, T #4 to 300 kcmil 9 480 Vac 200 50 125 R, J, T #4 to 300 kcmil 600 Vac 200 60 150 R, J, T #4 to 300 kcmil 1 250 Vdc 10 40 40 a #4 to 300 kcmil 400A switch 240 Vac 200 50 125 R, T 250 to 750 kcmil or (2) 3/0 to 250 kcmil c 1 480 Vac 200 100 250 R, J, T 250 to 750 kcmil or (2) 3/0 to 250 kcmil c 600 Vac 200 125 350 R, J, T 250 to 750 kcmil or (2) 3/0 to 250 kcmil c 1 250 Vdc 10 50 50 a 250 to 750 kcmil or (2) 3/0 to 250 kcmil c 600A switch 240 Vac 200 75 200 R, T (2) #4 to 600 kcmil or (4) 3/0 to 250 kcmil 1 480 Vac 200 150 400 R, J, T (2) #4 to 600 kcmil or (4) 3/0 to 250 kcmil 600 Vac 200 200 500 R, J, T (2) #4 to 600 kcmil or (4) 3/0 to 250 kcmil 1 800A switch 240 Vac 200 N/A N/A T (3) 250 to 750 kcmil or (6) 3/0 to 250 kcmil 480 Vac 200 N/A N/A L, T (3) 250 to 750 kcmil or (6) 3/0 to 250 kcmil 1 600 Vac 200 N/A N/A L, T (3) 250 to 750 kcmil or (6) 3/0 to 250 kcmil 1200A switch 240 Vac 200 N/A N/A T (4) 250 to 750 kcmil or (8) 3/0 to 250 kcmil 1 480 Vac 200 N/A N/A L (4) 250 to 750 kcmil or (8) 3/0 to 250 kcmil 600 Vac 200 N/A N/A L (4) 250 to 750 kcmil or (8) 3/0 to 250 kcmil 1 NNote 1 a Contact fuse manufacturer for UL listed DC fuses. b Switch type FDPB (breaker based). 1 c Lug size conversion kit available for: 1 x 750 kcmil (600A FDP), 2 x 750 kcmil (600A FDPW), 3 x 350 kcmil (600A CFDOW SW). N/A = Not Applicable 1 1 1 1 1 1 1 1 1 1 1

9-74 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

Surge Protection Devices 1 SPD Series Specifications 2 Description Specification Surge capacity ratings available 50, 80, 100, 120, 160, 200, 250, 300, 400 kA per phase 3

Nominal discharge current (In) 20 kA Short-circuit current rating (SCCR) 200 kA 4 SPD type Basic feature package = Type 1 (can also be used in Type 2 applications) Standard and Standard with Surge Counter feature packages = Type 2 5 Single split-phase voltages available 120/240 Three-phase wye system voltages available 120/208, 127/220, 230/400, 277/480, 347/600 6 Three-phase delta system voltages available 240, 480, 600 Input power frequency 50/60 Hz 7 Power consumption (basic units): 208Y, 220Y, 240S, 240D and 240H voltage codes 0.5W 8 400Y, 480Y and 480D voltage codes 1.1W 600Y and 600D voltage codes 1.3W 9 Power consumption (standard and standard with surge counter units): 208Y, 220Y, 240S, 240D and 240H voltage codes 0.6W 1 400Y, 480Y and 480D basic voltage codes 1.7W 600Y and 600D voltage codes 2.1W 1 Protection modes Single split phase...... L-N, L-G, N-G, L-L Three-phase wye...... L-N, L-G, N-G, L-L 1 Three-phase delta...... L-G, L-L Three-phase high-leg delta...... L-N, L-G, N-G, L-L Maximum continuous operating voltage (MCOV): 1 240S, 208Y, 220Y and 240H MCOV 150 L-N, 150 L-G, 150 N-G, 300 L-L 1 400Y and 480Y MCOV 320 L-N, 320 L-G, 320 N-G, 640 L-L 600Y MCOV 420 L-N, 420 L-G, 420 N-G, 840 L-L 1 240D MCOV 320 L-G, 320 L-L 480D MCOV 640 L-G, 640 L-L 1 600D MCOV 840 L-G, 840 L-L Ports 1 1 Operating temperature –4°F through 122°F (–20°C through 50°C) Operating humidity 5% through 95%, noncondensing 1 Operating altitude Up to 16,000 ft (5000m) Seismic withstand capability Meets or exceeds the requirements specified in IBC 2006, CBC 2007 1 Weight 50–200 kA units approximately 3.5 lbs (1.6 kg) 250–400 kA units approximately 7.0 lbs (3.2 kg) 1 Form C relay contact ratings 150 Vdc or 125 Vac, 1A maximum Form C relay contact logic Power ON, normal state—NO contact = open, NC contact = closed Power OFF or fault state—NO contact = closed, NC contact = open 1 EMI/RFI filtering attenuation Up to 50 dB from 10 kHz to 100 MHz Agency certifications and approvals UL 1449 3rd Edition recognized component for the U.S. and Canada 1 UL 1283 (Type 2 SPDs only) Warranty 10 years 1 1 Feature Package Comparison Standard with 1 Feature Basic Standard Surge Counter Surge protection using thermally protected MOV technology    1 Dual-coloured protection status indicators for each phase    Dual-coloured protection status indicators for the neutral-ground protection mode    1 Audible alarm with silence button   Form C relay contact   1 EMI/RFI filtering, providing up to 50 dB of noise attenuation from 10 kHz to 100 MHz   Surge counter with reset button  1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 9-75 Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

1 Metering 2 Metering Selection Chart Power Xpert® Meter Power Xpert Meter 2000 Series Power Xpert Meter 1000 Series IQ 250/260 Series 3 4000/6000/8000 Series 4

5 Device Name 6 Electrical Parameters Volts 0.1% of reading + 0.02% FS 0.1% of reading 0.2% of reading 0.1% of reading 7 Amperes 0.05% of reading + 0.01% FS 0.1% of reading 0.2% of reading 0.1% of reading Current range (% of nominal) 0.005–20A (400%) 0.1–200% 5 mA-50000 A (120-200%) 0.1–200% 8 Watts 0.1% of reading + 0.0025% FS 0.2% of reading 0.2% of reading 0.2% of reading VARs 0.1% of reading + 0.0025% FS 0.2% of reading 0.2% of reading 0.2% of reading 9 VA 0.1% of reading + 0.0025% FS 0.2% of reading 0.2% of reading 0.2% of reading PF-apparent 0.1% 0.2% of reading 0.2% of reading 0.2% of reading 1 PF-displacement 0.1% — — — Frequency ±0.01 Hz ±0.03 Hz 0.2% Hz ±0.03 Hz 1 THD-voltage 127th 40th bcde 31st, 63rd lmn 40th f THD-current 127th 40th bcde 31st (PXM 1000), 63rd 40th f 1 Watthours ±0.2% per ANSI C12.20 0.2 Class a ±0.2% per ANSI C12.20 0.2 Class ±0.2% per ANSI C12.20 0.2 Class ±0.2% per ANSI C12.20 0.2 Class VAR-hours ±0.2% per ANSI C12.20 0.2 Class a ±0.2% per ANSI C12.20 0.2 Class ±0.2% per ANSI C12.20 0.2 Class ±0.2% per ANSI C12.20 0.2 Class 1 VA-hours ±0.2% per ANSI C12.20 0.2 Class a ±0.2% per ANSI C12.20 0.2 Class ±0.2% per ANSI C12.20 0.2 Class ±0.2% per ANSI C12.20 0.2 Class Ampere-demand 0.05% of reading + 0.01% FS ±0.1% per ANSI C12.20 0.2 Class ±0.1% per ANSI C12.20 0.2 Class ±0.1% per ANSI C12.20 0.2 Class 1 Watt-demand ±0.2% per ANSI C12.20 0.2 Class a ±0.2% per ANSI C12.20 0.2 Class ±0.2% per ANSI C12.20 0.2 Class ±0.2% per ANSI C12.20 0.2 Class VAR-demand ±0.2% per ANSI C12.20 0.2 Class a ±0.2% per ANSI C12.20 0.2 Class ±0.2% per ANSI C12.20 0.2 Class ±0.2% per ANSI C12.20 0.2 Class 1 VA-demand ±0.2% per ANSI C12.20 0.2 Class a ±0.2% per ANSI C12.20 0.2 Class ±0.2% per ANSI C12.20 0.2 Class ±0.2% per ANSI C12.20 0.2 Class Revenue accuracy ±0.2% per ANSI C12.20 0.2 Class a ANSI C12.20 (0.2%) ±0.2% per ANSI C12.20 0.2 Class ANSI C12.20 (0.2%) 1 Individual ampere harmonics 85th g 40th cde 31st (PXM 1000), 63rd — Individual voltage harmonics 85th g 40th cde 31st (PXM 1000), 63rd — 1 Interharmonics Yes hi — — — Minimum and/or Maximum Values 1 Volts L-L, L-N, N-G, VAUX L-L L-L, L-N L-L, L-N L-L, L-N Current A, B, C, N, G A, B, C, N A, B, C A, B, C 1 Power Watt, VAR, VA Watt, VAR, VA Watt, VAR, VA Watt, VAR, VA Power Factor Apparent/displacement Apparent Apparent Apparent 1 Frequency Hz Hz Hz Hz THD Amperes/volts (L-L, L-N, AUX L-L) Amperes/volts bcde Amperes/volts Amperes/volts f 1 Demand values kW, kVAR, kVA, amperes kW, kVAR, kVA, amperes kW, kVAR, kVA, amperes kW, kVAR, kVA, amperes Trend analysis 2 / 4 h / 8 i GB 256 / 512 b / 768 cde MB 8 l m / 16 n MB j 1 Event logging 2 / 4 h / 8 i GB 100,000 alarms/events with timestamp 8 MB n 128 KB k 1 Disturbance recording 2 / 4 h / 8 i GB, 60 cycles per event 768 MB up to 64 cycles per event de — — Legend NNote PG = Programmable a Under typical operating f IQ 260 only. h PXM 6000 only. l PXM 1100 only 1 conditions. FS = Full scale g Individual values reported i PXM 8000 only. m PXM 1200 only RV = Read value b PXM 2260 only. to 85th harmonic; anti-alias Auxiliary Voltage j At computer only. n PXM 1300 only 1 c PXM 2270 only. filtering prevents higher (Optional) = Provides three frequencies from distorting k Optional. d additional voltage PXM 2280 only. readings (see IEC 61000-4-7). 1 inputs to the meter: e PXM 2290 only. Va2, Vb2, Vc2 Interharmonics = Power Xpert Meter 1 6000/8000 supported 1 1 1

9-76 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

Metering Selection Chart, continued 1 Power Xpert® Meter Power Xpert Meter 2000 Series Power Xpert Meter 1000 Series IQ 250/260 Series 4000/6000/8000 Series 2 3

Device Name 4 Other Features Storage 2 / 4 a / 8 b GB 256 / 512 c / 768 def MB Standard8 MB j k / 16 MB l 128 KB for logging, up to 8 parameters 5 every 15 minutes for 30 days g PG output relays 5 maximum Optional (2) Form C, 5 A or (4) Form A, KYZ Pulse and I/O Option Cards Optional (2) Form C, 5 A or (4) Form A, 6 120 mA 120 mA PG analogue outputs — Optional (4) 4–20 mA or (4) 0–1 mA Via I/O Option Card Output range: Optional (4) 4–20 mA or (4) 0–1 mA 0-5 V / 1-5 V, 0-20 mA / 4-20 mA 7 (optional) Accuracy: 0.5% Temperature drift: 50ppm / °C typical 8 Isolation voltage: 500 Vdc Open circuit voltage: 15 V 9 Discrete contact inputs 8 Optional (2) or (4) Via I/O Option Card Optional (2) or (4) Input voltage range: 20–160 Vac/Vdc Input current (max.): 2 mA 1 Start voltage: 15 V Stop voltage: 5 V Pulse frequency (max.): 100 Hz, 50% 1 duty ratio (5 ms ON and 5 ms OFF) SOE resolution: 2 ms 1 Analogue inputs — — Input range: 0-5 V / 1-5 V, 0-20 mA / — 4-20 mA (optional) Accuracy: 0.2% 1 Temperature drift: 50 ppm / °C typical Isolation voltage: 500 Vdc 1 Synch-input kW utility Via status input Via end of interval pulse with — Via end of interval pulse with optional digital inputs optional digital inputs Auxiliary voltage Yes — Yes — 1 kWh pulse initiator Yes Yes — Yes Waveform display Local/computer h At computer — 1 Waveform capture, samples/cycle Yes, 512 (4096 oversampling) Yes, up to 64 e, up to 512 f Yes, up to 32 l — Frequency distribution display — — — — 1 Display type LCD Red LED Backlit LCD Red LED Display lines/character Graphic (320 x 240 pixels) 3 lines, 4 characters Main Display Area: 4 lines, 3 lines, 4 characters 1 4 characters Bottom Display Area: 1 line, 9 characters 1 Display character height 5.5 mm H x 4 mm W 0.56 (14.2) H 1 line 0.56 (14.2) H Communications Serial: Modbus® RTU, Modbus ASCII Serial: Modbus RTU, Modbus ASCII, Modbus® RTU, Modbus TCP Option, Serial: Modbus RTU, Modbus ASCII, 1 Network: Modbus TCP, Ethernet TCP/IP, DNP 3.0 BACnet/IP Option, Web/HTTP Push DNP 3.0 HTTP, SNMP, SMTP, FTP Network: Modbus TCP, BACnet/IP, Option, Ability to connect to Network: Modbus TCP via Power Xpert Ethernet Eaton’s Power Xpert Gateway 900 Gateway 1 TCP/IP, HTTP, HTTPS, SNMP, SMTP, Waveform FTP ef 1 Setup configuration Via Web browser/display Via Web browser/display Via configuration software/ Via configuration software/display display/ Web Page Dimensions in inches (mm) Meter: 8.82 (224.0) H x 8.22 (208.8) W x 4.85 (123.2) H x 4.85 (123.2) W x 3.78 (96.0) H × 3.78 (96.0) W 4.85 (123.2) H x 4.85 (123.2) W x 1 6.72 (170.7) D 4.97 (126.2) D × 1.99 (50.7) D 4.97 (126.2) D Display: 9.02 (229.1) H x 7.80 (198.1) W x 1 2.49 (63.2) D Operating temperature range –20° to 60°C display unit –20° to 70°C -25° to 70°C –20° to 70°C –20° to 70°C meter base unit i 1 Reference literature TD02601007E TD02601017E TD026079EN TD02601016E Legend NNote 1 PG = Programmable a PXM 6000 only. d PXM 2270 only. g Optional. j PXM 1100 only FS = Full scale b PXM 8000 only. e PXM 2280 only. h At computer only. k PXM 1200 only 1 RV = Read value c Auxiliary Voltage PXM 2260 only. f PXM 2290 only. i Using <10 VA meter sourced l PXM 1300 only (Optional) = Provides three 24V power. 1 additional voltage inputs to the meter: 1 Va2, Vb2, Vc2 Interharmonics = Power Xpert Meter 6000/8000 1 supported

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 9-77 Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

1 Metering Selection Chart, continued IQ Analyzer 6000 Series IQ DP-4000 Series IQ 230 Series 2 3

4 Device Name Electrical Parameters 5 Volts ±0.2% FS a ±0.3% FS ±0.5% FS Amperes ±0.2% FS a ±0.3% FS ±0.5% FS 6 Current range (% of nominal) 3–800% 10–250% 1–200% Watts 0.4% FS, 6 Reading b ±0.6% FS ±1.0% FS 7 VARs 0.4% FS, 6 Reading c ±0.6% FS ±1.0% FS VA 0.4% FS, 6 Reading b ±0.6% FS ±1.0% FS 8 PF-apparent 0.8% FS a ±1.0% FS ±2.0% FS PF-displacement 0.8% FS a ±1.0% FS ±2.0% FS 9 Frequency 0.04% a or 0.01 Hz ±0.17% FS ±0.1% Hz 1 THD-voltage 50th 31st — THD-current 50th 31st — 1 Watthours 0.5% reading b ±0.6% FS ±1.0% per ANSI C12 VAR-hours 1% reading c ±0.6% FS ±1.0% per ANSI C12 1 VA-hours 0.5% reading b ±0.6% FS ±1.0% per ANSI C12 Ampere-demand ±0.2% FS a ±0.3% ±0.5% per ANSI C12 1 Watt-demand ±0.4% FS a ±0.6% ±1.0% per ANSI C12 VAR-demand ±0.4% FS a ±0.6% ±1.0% per ANSI C12 1 VA-demand ±0.4% FS a ±0.6% ±1.0% per ANSI C12 Revenue accuracy ANSI C12.20 (0.5%) — ANSI C12.1 (1%) 1 Individual ampere harmonics 50th — — Individual voltage harmonics 50th — — 1 Interharmonics — — — Minimum and/or Maximum Values 1 Volts L-L, L-N L-L, L-N L-L, L-N Current A, B, C, N, G A, B, C A, B, C 1 Power Watt, VAR, VA Watt, VAR, VA Watt, VAR, VA Power factor Apparent/displacement Apparent/displacement Apparent/displacement 1 Frequency Hz Hz Hz THD Amperes/volts Amperes/volts — 1 Demand values All All All Trend analysis Time/date 2 alarms d 1 Event logging 504 events w/timestamp d d Disturbance recording 10 waveform events — — 1 Legend NNote PG = Programmable a From 3 to 300% of FS. 1 FS = Full scale b At unity power factory and RV = Read value 5–300% of FS. Auxiliary Voltage c 1 (Optional) = Provides three At a power factor <±0.5 and additional voltage 5–300% of FS. 1 inputs to the meter: d At computer only. Va2, Vb2, Vc2 Interharmonics = Power Xpert Meter 1 6000/8000 supported 1 1 1 1

9-78 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

Metering Selection Chart, continued 1 IQ Analyzer 6000 Series IQ DP-4000 Series IQ 230 Series 2 3

Device Name 4 Other Features Storage 90 KB 15 parameters — 5 PG output relays (4) 10 A Form C a (3) 10 A Form C b (2) 100 mA Form A PG analogue outputs (4) 0–10/4–20 mA — — 6 Discrete contact inputs (3) +30 Vdc differential (1) kW demand b (2) +30 Vdc differential Analogue inputs (1) 0–20/4–20 mA — (1) 4–20 mA 7 Synch-input kW Utility At device or via communications At device or via communications b Via communications only Auxiliary voltage c — — — 8 kWh pulse initiator Yes Yes b Yes 9 Waveform display Local b/computer — — Waveform capture, samples/cycle Yes, 128 — — 1 Frequency distribution display Local b/computer — — Display type Graphic LCD with LED backlight 7 Segment LED Backlit LCD 1 Display lines/character 7 lines, 147 characters 1 line, 7 characters 4 lines, 20 characters Display character height Up to 7 lines 1 line 1.60 (40.6) H x.09 (2.3) W 1 Communications Serial: INCOM d Serial: INCOM d Serial: INCOM, Modbus RTU e Network: via Power Xpert Gateway d Network: via Power Xpert Gateway d Network: via Power Xpert Gateway Setup configuration Via configuration software/display Via configuration software/display Via configuration software/display 1 Dimensions in inches (mm) 6.70 (170.2) W x 10.30 (261.6) H x 5.40 (137.2) D f 6.70 (170.2) W x 10.30 (261.6) H x 5.40 (137.2) D f Refer to TD.17.06.T.E Operating temperature range –20° to 70°C –20° to 70°C 0° to 50°C 1 Reference literature — — — 1 Legend NNote PG = Programmable a Relays programmable to operate on any d An IPONI is required. measured function. 1 FS = Full scale e IQ 230M only. RV = Read value b Optional. Auxiliary Voltage f Dimensions in mm = c 1 (Optional) = Provides three The auxiliary voltage option adds three 170.2 W x 261.6 H x 137.2 D. additional voltage additional voltage input channels to inputs to the meter: Power Xpert Meters. 1 Va2, Vb2, Vc2 Interharmonics = Power Xpert Meter 6000/8000 supported 1 1 1 1 1 1 1 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 9-79 Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

1 Metering Selection Chart, continued Power Monitoring / 2 IQ 130/140/150 Series Power Xpert Meter 350 Series IQ 150S/250S Series Metering Module (PM3) 3 4 Device Name 5 Electrical Parameters Volts 0.25% of reading 0.5% of reading 0.1% of reading ±0.5% of reading 6 Amperes 0.25% of reading 0.5% of reading 0.1% of reading ±0.5% of reading Current range (% of nominal) 0.1–200% 10 mA-500000 A (200 %) 0.1–200% — 7 Watts 0.5% of reading a 0.5% of reading 0.2% of reading ±1.0% of reading VARs 0.5% of reading a 0.5% of reading 0.2% of reading ±1.0% of reading 8 VA 0.5% of reading a 0.5% of reading 0.2% of reading ±1.0% of reading 9 PF-apparent 0.5% of reading a 0.5% of reading 0.2% of reading ±2.0% of reading PF-displacement — — — — 1 Frequency ±0.03 Hz a 0.2% of reading ±0.03 Hz ±0.1 Hz THD-voltage — — — — 1 THD-current — — — — Watthours ±0.5% per ANSI C12.20 0.5 Class b ±0.5% per ANSI C12.20 0.5 Class ±0.2% per ANSI C12.20 0.2 Class ±1.0% per ANSI C12.1 1 VAR-hours ±0.5% per ANSI C12.20 0.5 Class b ±0.5% per ANSI C12.20 0.5 Class ±0.2% per ANSI C12.20 0.2 Class ±1.0% of reading VA-hours ±0.5% per ANSI C12.20 0.5 Class b ±0.5% per ANSI C12.20 0.5 Class ±0.2% per ANSI C12.20 0.2 Class ±1.0% of reading 1 Ampere-demand ±0.25% per ANSI C12.20 0.5 Class a ±0.25% per ANSI C12.20 0.5 Class ±0.1% per ANSI C12.20 0.2 Class — Watt-demand ±0.5% per ANSI C12.20 0.5 Class a ±0.5% per ANSI C12.20 0.5 Class ±0.2% per ANSI C12.20 0.2 Class — 1 VAR-demand ±0.5% per ANSI C12.20 0.5 Class a ±0.5% per ANSI C12.20 0.5 Class ±0.2% per ANSI C12.20 0.2 Class — VA-demand ±0.5% per ANSI C12.20 0.5 Class a ±0.5% per ANSI C12.20 0.5 Class ±0.2% per ANSI C12.20 0.2 Class — 1 Revenue accuracy ANSI C12.20 (0.5%) ±0.5% per ANSI C12.20 0.5 Class ANSI C12.20 (0.2%) ±1.0% per ANSI C12.1 Individual ampere harmonics — — — — 1 Individual voltage harmonics — — — — Interharmonics — — — — 1 Minimum and/or Maximum Values Volts L-L, L-N L-L, L-N L-L, L-N — 1 Current A, B, C A, B, C, N, (on Bi-Directional Energy Models) A, B, C, — Power Watt, VAR, VA a Watt, VAR, VA Watt, VAR, VA — 1 Power factor Apparent a Apparent Apparent — Frequency Hz a Hz Hz — 1 THD — — — — Demand values kW, kVAR, kVA, amperes a kW, kVAR, kVA, amperes kW, kVAR, kVA, amperes — 1 Trend analysis c — 2 MB e — Event logging c c 2 MB e — 1 Disturbance recording — — — — Legend NNote 1 PG = Programmable a IQ 140/150. FS = Full scale b IQ 150 only. RV = Read value 1 c Auxiliary Voltage At computer only. (Optional) = Provides three d Optional. 1 additional voltage e IQ 250S only. inputs to the meter: Va2, Vb2, Vc2 1 Interharmonics = Power Xpert Meter 6000/8000 supported 1 1 1 1

9-80 Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

Metering Selection Chart, continued 1 Power Monitoring / Metering IQ 130/140/150 Series Power Xpert Meter 350 Series IQ 150S/250S Series Module (PM3) 2 3 4 Device Name Other Features 5 Storage — — 2 MB b — PG output relays — KYZ Pulse output, Relay Output — — 6 PG analogue outputs — — — — Discrete contact inputs — — — Circuit breaker status 7 Analogue inputs — — — — Synch-input kW utility — — — — 8 Auxiliary voltage c — — — — kWh pulse initiator a — Yes — 9 Waveform display — — — — Waveform capture — — — — 1 Frequency distribution display — — — — Display type Red LED Backlit LCD Red LED — 1 Display lines/character 3 lines, 4 characters 1 line, 6 characters 3 lines, 4 characters — Display character height 0.56 (14.2) H 1 line 0.56 (14.2) H — 1 Communications Serial: Modbus RTU, Modbus®-RTU, BACnet MS/ TP, Serial: Modbus RTU, Modbus ASCII, Serial: INCOM, Modbus RTU d Modbus ASCII a Ability to connect to Eaton’s Power DNP 3.0 Network: via Power Xpert Gateway 1 Network: Modbus TCP a 4 Xpert Gateway 900 Network: Modbus TCP, wired or wireless 1 Setup configuration Via configuration software/display Via configuration software/display Via configuration software/display — Dimensions in inches (mm) 4.85 (123.2) H x 4.85 (123.2) W 2.92 (74.0) D × 3.54 (90.0) H 7.90 (200.7) H x 7.50 (190.5) W Refer to IL01219085E x 4.97 (126.2) D × 4.25 (108.0) W x 3.10 (78.7) D –25° to 70°C 1 Operating temperature range –20° to 70°C -25° to 70°C –20° to 70°C — 1 Reference literature TD02601016E TD150024EN TD02601019E — Legend NNote 1 PG = Programmable a Optional. FS = Full scale b IQ 250S only. RV = Read value 1 c Auxiliary Voltage The auxiliary voltage option adds three (Optional) = Provides three additional voltage input channels to additional voltage Power Xpert Meters. 1 inputs to the meter: d Contact Eaton for availability. Va2, Vb2, Vc2 1 Interharmonics = Power Xpert Meter 6000/8000 supported 1 1 1 1 1 1 1 1 1 1

Low Voltage Switchboards and Switchgear CA015002EN—August 2019 www.eatoncanada.ca 9-81 Low Voltage Switchboards and Switchgear Switchboard Accessories and Modifications

1 This page intentionally left blank. 2 3 4 5 6 7 8 9 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1