<<

providing insights for today’s hvac system designer

Engineers Newsletter volume 45–2

waterside Keeping the "Free" In Free-Cooling

This EN revisits the topic of a 2008 Identify the Right What if my preferred system can't use newsletter and provides additional either type of ? discussion about applying and Applications controlling a waterside economizer. Energy standards and model codes do not have blanket exceptions for these systems. The critical first step for a successful However, there are a number of exceptions There are six basic steps to designing waterside economizer cannot be to consider. For small terminals <54,000 overlooked: identifying the right Btu/h, no economizer is required by ASHRAE and operating a waterside economizer: Standard 90.1-2013. applications. Waterside economizers are • Identify the right application usually less effective at saving energy than Systems with condenser recovery may • Select and size airside economizers. There are simply qualify for an exception. Air-cooled more heat exchangers between the source serving central equipment can use the • Determine control points efficiency trade off for equipment (Table 1), of the and the cooling load. condenser heat recovery or desuperheaters, • Protect and tower Each "loses" a few degrees or add a free cooling circuit. of cooling, the approach temperature. Each • Predict value of integrated mode transfer of cooling requires energy- Equipment efficiency trade off method • Deliver energy savings consuming equipment, such as condenser ASHRAE Standard 90.1-2010 and later fans, condenser- pumps and chilled- provides a new exception for the economizer In order to deliver energy savings, the water pumps. requirement. The standard back-calculated system must be designed and an IPLV or IEER improvement by climate controlled properly. Therefore, it’s critical that we select the zone that would provide equivalent energy right applications, and intelligently control savings (Table 1). the system to deliver energy savings. Table 1. ASHRAE Standard 90.1-2013, 6.5.1-3 Climate zone Part load efficiency There are several reasons for designing a improvement system to use a waterside economizer. 2A 17% 2B 21% Sometimes airside economizers are 3A 27% impractical. In most dedicated outdoor air systems, the airflow rate is sized for the 3B 32% minimum, code-required ventilation rate. 3C 65% Therefore, even if the outdoor air is 4A 42% suitable for cooling, the system is not 4B 49% capable of delivering “100% of the design 4C 64% supply air quantity as outdoor air for 5A 49% cooling,” as required for airside economizing by ASHRAE Standard 90.1. 5B 59% 5C 74% Another constraint could be due to central 6A 56% mechanical system architectural issues or 6B 65% preferences. 772% 877%

© 2016 Trane, a business of Ingersoll Rand. All rights reserved. 1

Sometimes airside economizers are making heat recovery systems work. The temperature (WB), the driving force for the undesirable. Airside economizer heat rejected by the cooling system water economizer cycle. Figure 1 illustrates applications that bring in dry air may use offsets the heating required in another the different opportunities for the more energy if humidification is required. system. The best system would be one waterside economizer cycle. The graphs ASHRAE Standard 90.1 requires that if that uses the economizer to offset only compare data plots for a hospital and an spaces are humidified to above 35°F the portion of the cooling load that is not office in climate 4A. The area under the dewpoint, the systems serving them needed for satisfying the heating load, black line to the left of, say, 50°F WB must use a water economizer when an commonly called a load-shedding represents the ton-hours that might be economizer is required. economizer. served or at least partially served by a Designers of process cooling applications waterside economizer cycle. The office is such as data centers may have concerns Does a water economizer make sense unoccupied during many of the hours about the attributes of the air in airside for my application? Carefully consider below 50°F WB, reducing the waterside economizer mode, or about outdoor air the expected load profile. Offices and economizer savings opportunity. On the dampers malfunctioning. hospitals are two applications where other hand, the hospital requires more prototypical load profiles use chilled- ventilation, so its system already brings in water systems and are available across more outdoor air for a partial airside Sometimes condenser heat recovery is multiple climates. These profiles can be economizing effect during these cooler impractical. Systems with condenser found in Trane’s myPLV™ or by exporting hours of operation. heat recovery of sufficient capacity are TRACE hourly load and weather given an exception to economizing. information to a spreadsheet application. The airside economizer opportunity for the Shedding mechanical cooling when the hospital and office load profiles is outdoor temperature is cool reduces the Using this data, it is possible to plot summarized in Table 2. This is the free hours of simultaneous heating and cooling load against the wet-bulb cooling sacrificed when an airside cooling—conditions that are key to economizer is not used.

Figure 1. Hospital and office cooling and operating hour distribution in zone 4A

hospital 4A office 4A 140000 250 ton-hrs 120000 annual hrs 200 operating hrs 100000 150 80000

60000 100 number of hours

central plant ton-hrs 40000 50 20000

0 0 020406080 100 0 20 40 60 80 100 outdoor wet- bulb temperature (ºF)

Table 2. Summary of operation and load displaced by airside economizer

climate building type chiller plant load plant annual cooling load airside economizer plant hours zone without operating offset by airside economizer operating hours displaced with economizer hours economizer ton-hrs (%) airside econ (%) (ton-hrs) (ton-hrs)

1A office 2,681,687 5,806 2,601 0.1 55 0.9

2A office 2,020,071 5,022 9,546 0.5 225 4.5

3A office 1,414,396 4,240 12,386 0.9 358 8.4

4A office 1,123,020 4,033 75,286 6.7 995 24.7

5A office 918,012 3,935 97,335 10.6 1,352 34.4

1A hospital 5,547,962 8,760 20,207 0.4 86 1. 0

2A hospital 4,628,842 8,759 253,285 5.5 1,412 16.1

3A hospital 3,667,161 8,758 516,296 14.1 2,605 29.7

4A hospital 3,109,749 8,729 683,872 22.0 3,769 43.2

5A hospital 2,635,926 8,596 722,553 27.4 4,426 51.5

2 Trane Engineers Newsletter volume 45–2 providing insights for today’s HVAC system designer The summary clearly shows that some the usefulness of the cycle. (More on 45°F WB with 50°F DB or less, with no building types are more conducive than that later in this newsletter.) more than 25 percent load at these others to either style of economizing, conditions. This is the minimum waterside most likely as a function of how the How much capacity does my economizer size for meeting code. ventilation loads and operational hours waterside economizer need? for the building coincide with outdoor Table 3 displays a pivot table for the Integrate with mechanical cooling. conditions that are suitable. hospital in climate 4A. Extracting the Section 6.5.1.3 Integrated Economizer hourly loads and weather into a Control of ASHRAE 90.1 states, spreadsheet is useful for summarizing Select and Size and visualizing how much load can be "Economizer systems shall be expected at a given wet bulb, and for integrated…and be capable of providing partial cooling even when additional Several styles of waterside economizers how many hours. In this example, there mechanical cooling is required to meet the are common. The 2008 EN compared were remainder of the cooling load" and contrasted different technologies, • No hours with loads below system layouts, and control methods for 10 percent at 34°F WB, or There is no definition of how the waterside economizers. Its conclusions below 15 percent at 42°F WB or integration must happen. Blending two may be summarized as: higher temperatures of water (a slightly warmer temperature from the waterside 1 Sidecar position benefits include • No hours with loads above economizer with colder water from the preferential loading of the 25 percent at 37°F WB or lower economizer and downstream mechanical cooling chiller) is acceptable temperature control with chillers, • No hours with loads above though not typically intentionally practiced. plus potentially less disruptive 30 percent at 45°F WB or lower transition into and out of waterside The value of this mode is uncertain. Energy economizer free cooling mode, as These observations will be helpful when simulation software rarely shows a the chiller downstream will unload or evaluating potential control points for the significant difference between integrated load to meet setpoint. system. and non-integrated economizer operation. Regardless of its value, the current model 2 A dedicated free-cooling heat Meet the prescriptive requirements in codes require integration. We'll revisit this exchanger has about a 1.5°F closer the energy code. Unless exempted, topic later in this newsletter. approach to wet bulb than the the minimum capacity of the water integrated chiller. On economizer is determined by the the other hand, the thermosiphon Determine maximum chilled-water expected cooling load at a given outdoor has lower maintenance, lower first temperature. The amount of cooling that dry bulb (DB) and WB condition. For cost and likely lower pressure drop can be accomplished by the waterside comfort cooling applications these due to the shell-and-tube heat economizer is dependent on the desired conditions are 50°F DB/45°WB. exchanger. chilled-water temperature. Is it the normal chilled-water setpoint? Or could the 3 Exiting or terminating free cooling Expected load at 50°F DB/45°F WB. system tolerate warmer water? If so, how waterside economizer mode To meet this requirement, a predicted much warmer? requires decisions to be made about load profile for the year is necessary. The example hospital data gave 39 hours at

Table 3. Number of hours by expected load and wet-bulb temperature

cooling total load outdoor wet bulb temperature hrs (%)

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

5301616141061 93

10 68 93 124 158 138 152 120 58 61 21 16 15 10 4 2 1040

15 9 12 27 60 62 76 103 103 117 114 105 99 54 70 68 35 33 22 6 2 3 1180

20 2 5 20 25 28 40 30 47 45 60 53 58 47 61 45 57 44 48 42 757

25 48712131830293439 21 26 24 27 47 339

30 3 2 2 4 14 31 40 41 44 36 30 26 273

40 2 1 4 7 7 21

total 98 118 152 199 208 222 202 181 189 170 178 157 171 118 152 155 136 145 162 115 130 111 112 122 3703 hrs

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 45–2 3

Some systems that use waterside Figure 2. Effect of load ( ΔT or range) and wet bulb on tower approach economizers also use sensible only equipment such as chilled-beams or radiant 25 cooling. These devices use fairly warm range water for cooling to keep the surface 20 temperature above the space dewpoint to 14 Load and wet bulb have a bigger effect on avoid unintended condensation. 12 approach in the waterside economizer regime Conventional systems can also tolerate 15 10 warmer , especially when (°F) perature 8 m loads are low, and when outdoor air is less 10 6 humid—conditions normally expected 4 when the water economizer mode is active. 5 approach te approach 0 Determine Control Points 3040 5060 70 80 outdoor wet-bulb temperature (ºF) Predicting if the system can meet the current day’s cooling load with the waterside economizer is roughly two parts moisture as well. Unless the load is quite no flow through isolated tower cell(s) experience and one part alchemy. low (and it very well may be), the tower may lead to icing. leaving temperature is, counterintuitively, • Balance condenser-pump energy Most chilled-water systems with an incapable of getting as close to the lower when tower fans are at minimum experienced hand at the helm "know" when wet-bulb temperature (Figure 2). speed. If too many cells run at it will work and when it probably won't. A tower solver spreadsheet tool tuned for a minimum speed, the increased Distilling tribal knowledge into a control given combination of tower and flow condenser pump energy necessary to algorithm can be a difficult task. The goal is turndown capability can be helpful for achieve sufficient cell water flow limits to predict what temperature you can get determining control points. the energy savings from tower fans. out of the cooling tower before driving the tower fans to full speed and overriding your • Know the maximum flow of the heat optimal temperature control algorithm for Number of tower cells to operate. The exchanger(s) and the minimum flow of mechanical cooling. number of tower cells that may operate is a the towers and modify the sequence relevant variable in tower performance accordingly. predictions. One method for preventing Tower performance. To determine if the high tower fan energy in economizer mode towers can make the water cold enough, Example control points. Table 4 is by flowing through more tower cells. The overlays potential control points on the without always driving the tower as cold as tower fans are run to the same (hopefully possible at the expense of fan energy, we load profile from Table 3. The loads cluster low) speed, and the tower is designed for into three regimes based on wet-bulb must predict tower performance. Many lower flow. people erroneously believe that the tower temperature. A tower solver was used to estimate performance and determine the can or will make a constant approach to However: wet bulb. This is simply not true. number of cells to operate at the highest • If water flow rates are too low the tower expected load for a given wet bulb. At lower wet-bulb temperatures, ambient may ice or scale, suggesting it would be air entering the tower doesn't absorb better to turn off a tower cell. However,

Table 4. Hospital expected load at each wet-bulb temperature

cooling total load outdoor wet-bulb temperature (°F) (%) hrs

27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

5 30 16 16 14 10 6 1 93

10 68 93 124 158 138 regime152 1:120 58 61 21 16 15 10 4 regime2 2: regime 3: 1040 all chillers off all chillers off integrated mode 15 9 12 27 60 62 76 103 103 117 114 105 99 54 70 68 35 33 22 6 2 3 1180 1 tower cell 2 tower cells one chiller on 20 45°F tower2 setpoint5 20 25 28 40 30 47 4547°F tower60 53setpoint58 47 61 45 573 tower44 cells48 42 757 47°F tower setpoint 25 4 8 7 12 13 18 30 29 34 39 21 26 24 27 47 339

30 3 2 2 4 14 31 40 41 44 36 30 26 273

40 2 1 4 7 7 21

total 98 118 152 199 208 222 202 181 189 170 178 157 171 118 152 155 136 145 162 115 130 111 112 122 3703 hrs 4 Trane Engineers Newsletter volume 45–2 providing insights for today’s HVAC system designer The number of cells operating was Figure 3. Head pressure control method for integrated waterside economizer considered suitable if, for a given wet bulb and maximum expected load, the tower condenser pressure fan was below 100 percent speed, and signal field- provided the leaving water temperature was below (required factory option) controller chiller the maximum leaving chilled-water (if needed) control temperature setpoint, minus 2-3 degrees panel of heat-exchanger approach. valve actuator Regime 1: All chillers are off, one tower chiller 2 butterfly cell is on and set for 45°F leaving-water to/from condenser temperature, waterside economizer is cooling tower valves enabled condenser Regime 2: All chillers are off, two tower water pump cells are on and set for 47°F leaving-water temperature, waterside economizer is enabled control, ensure that the minimum periods of time (20 minutes is typically tower flow rate is always met to acceptable). Regime 3: Lead mechanical cooling chiller avoid freezing. is on, three tower cells are open and set There are five methods of head pressure for 47°F leaving-water temperature, • Condenser bypass is preferred, see control for water-cooled chillers; some waterside economizer is enabled, chiller next section. are more suitable for systems with head pressure control as necessary. Once waterside economizers. Figure 1 shows you start the lead chiller, it’s possible to Plan for chiller head pressure the preferred method; other methods are add another tower cell. The chiller adds a control. Operating the chiller described and illustrated in several Trane heat exchanger to the system, so while continuing to drive Engineering Bulletins. Some methods condenser flow rises enough to support the cooling tower to a colder have drawbacks when used for head another tower cell's flow. Alternatively, temperature requires a plan for chiller pressure control during integrated consider a dedicated tower for the lead head pressure control. While it's not waterside economizer mode. chiller or an air-cooled lead chiller. unique to this application, applications without waterside economizing may Condenser bypass is the preferred have fewer hours expected for method for waterside economizer mode, Protect Chiller and Tower operation in this condition. as it allows the tower flow rate to remain high, which provides adequate fill Careful coordination between the chiller coverage to prevent icing or deicing, with and the system controls is critical Plan for cold towers. The waterside fast-acting head pressure control at the (watch for scope gap). Many newer economizer requires a winterized cooling chiller (Figure 3). tower in many climates. Since the tower chillers have the ability to directly is expected to operate when it's cold control their own head pressure Tower fan speed, leaving temperature outside, it cannot be seasonally drained. device—this is preferred. Newer chillers setpoint control simply resets the also may selectively ignore the tower leaving-water temperature Use chiller bypass for chiller head condenser flow switch during head setpoint higher when requested by the pressure control so that the tower flow pressure control mode. And, chillers chiller controller. This is slow acting and rate can be higher than the condenser must be capable of performing an will be at odds with the waterside flow rate when needed, for freeze inverted start, defined as having the economizer control points. Use this protection and proper fill coverage. condenser at a lower pressure than the method for entering and exiting . economizer mode, but not for head Carefully consider the outdoor parts of the pressure control. system that are off or isolated from the The controls contractor should be building load: alerted to the time permitted to achieve Tower bypass may be problematic for • Use a dry or indoor sump, or use heat the required differential pressure, as not waterside economizer mode, as its trace and sump heaters all chiller types have the same ability to manage chiller head pressure requirements. For example, achieving will be constrained by the minimum • Install heat trace on the make-up differential pressure in a helical rotary required flow rate of the tower. When water system (screw) chiller must happen in two systems are expected to operate for • If using tower bypass, throttling minutes. In this type of chiller, oil is more than transient periods of time in valves, or variable-speed condenser used for creating the compression seal. head pressure mode, tower bypass is pumps for chiller head pressure Centrifugal chillers are more tolerant of less desirable, though fast acting. low differential pressures for longer Another problem with this method is that

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 45–2 5

it is typical to share a common tower Figure 4. Integrated free cooling in November bypass across all devices, and one or more of the waterside economizer 47 devices may require higher tower flow 25 free cooling pump (kW) than the others. condenser water pump chilled-water pump Throttling valve or variable flow cooling tower 45 20 clg equipment electric (kW) condenser pump, when available per chiller, can have a similar effect as 43 condenser bypass, but may make it 15 difficult to adequately flow the preferred kW outdoor wet bulb number of tower cells while continuing 41 to meet the head pressure 10 requirements. wet-bulb temperature (°F) 39 For all these reasons, condenser bypass 5 and tower speed control are preferred for waterside economizers. 37 0 10 12 14 16 18 Value of Integrated h Economizer Mode tough to pin down as a control point, but integrated mode wins more dramatically our building models offer guidance. with a variable-speed lead chiller. Because tower fans, condenser-water Whether or not to stop waterside pumps and chillers would be at a different In addition, the waterside economizer economizer if it’s not meeting the operating point than they would have "steals" load from the chiller and drives the entire cooling load. One of the biggest been, we can’t just look at the chiller-only chiller into a less efficient operating point. debates that has raged for many years is energy prediction. When load is low, chiller kW/ton is whether integrated economizer mode relatively high—that is, not very efficient— actually provides value. The two Consider a fall day while operating in free- even when using a variable-speed positions can be summarized as: cooling mode (Figure 4). For each hour, compressor. This is because a portion of • Integrate free and mechanical the right column is the series or the chiller energy is constant. The less cooling. Code requires it (so it must integrated free cooling alternative. The left work (tons) that it does, the lower the be the right thing to do), plus it’s easy column is the parallel, all-or-nothing, non- efficiency. Having tower fans operate at enough to initiate and terminate if integrated free cooling alternative. high speed to continue the cycle, while the chiller is in series with the the condenser pump and chilled-water Once the economizer cycle can no longer waterside economizer device. pump speeds are also high, creates the meet the entire load (five out of the nine classic example of chasing your tail. • Energy models and other calculations hours when the plant is operating), suggest the opposite. Integrated free remaining in economizer mode after This is why integrated and non-integrated cooling doesn’t usually save much starting the chiller actually uses more economizer mode comparisons defy the energy, and it complicates the energy than mechanical-only cooling. engineer and energy modeler's controls on the lead chiller. Either it How can this be? expectations and result in very similar meets all of the load or it's system annual energy consumption. discontinued. While chiller energy is reduced in the integrated mode, tower and pump energy Based on the model energy codes, increase more than the chiller energy integrated has won the debate. But decreases, overwhelming any potential Deliver Energy Savings should it have? All rules should be re- savings. The cooling tower fans, evaluated occasionally, and we must not economizer pump and condenser-water This brings us to a few final thoughts for assume that all applications react the pump were higher in the integrated terminating waterside economizer mode. same way. Data center loads are fairly alternative. What amount of free cooling is worth it? constant year-round—office loads are Rather than assume that supressing the not. Even if the need for an economizer pump return water temperature a couple of were designed out of the system, the degrees is sufficient, understand how the The key is to know the likely system integrated mode would still use more entire system performs in economizer efficiency of mechanical (only) cooling energy overall than the non-integrated mode, and identify the alternative system when the waterside economizer can no alternative. This particular example used a performance in mechanical-cooling mode. longer meet the entire load. This can be fixed-speed lead chiller. The non-

6 Trane Engineers Newsletter volume 45–2 providing insights for today’s HVAC system designer Table 5. Chiller plant performance (chiller, tower, all pumps) References with chilled-water reset without chilled-water reset Energy @ 20% plant load CHWSP 49°F, LCWT ~64°F CHWSP 45°F, LCWT ~61°F [1] Hanson, S., "Free Cooling with Waterside Economizers," Engineers Newsletter, 2008, fixed-speed chiller and condenser-water 0.758 kW/ton 0.745 kW/ton Trane. pump, variable-speed tower and chilled- water pumps [2] Hanson, S., "ASHRAE Standard 90.1-2010: variable-speed chiller, tower and chilled- 0.451kW/ton 0.440 kW/ton Updates to Mechanical System Mandatory and water pumps, fixed-speed condenser-water Prescriptive Requirements," Engineers pump Newsletter, 39-3, 2010, Trane.

[3] Hanson, S., "ASHRAE Standard 90.1-2013 HVAC and Power Section Highlights," Engineers A variable-speed lead chiller and its If the goal is to prevent the chiller from Newsletter, 44-1, 2010, Trane. condenser pump and tower fan(s) cycling on low load, instead of hot-gas bypass, add more load to the chiller by [4] Lindahl, P., "Cold Weather Operation of Cooling operating at slow speed might use 0.36 Towers," ASHRAE Journal, March 2014. kW/ton. Determine this number and use reducing the load performed by the it as a yardstick to decide if free cooling waterside economizer. If you're also [5] Schwedler, M., "Effect of Heat Rejection Load is "free" after all. concerned about the low efficiency at low and Wet Bulb on Cooling Tower Performance." chiller loads in the integrated mode, ASHRAE Journal, 2014. consider installing thermal storage instead Chilled-water reset. By encouraging [6] Sullivan, B., "Chiller Selection Made Easier with extending the economizer mode, the as a first stage of supplemental cooling. myPLV™," Engineers Newsletter, 44-4, Trane system effects of chilled-water reset, at 2015. some point, limit the potential energy savings. Chilled-water reset is a waterside economizer’s friend, until it Summary isn't. That point occurs when the chiller Upcoming Trane Engineers is started and operated in head pressure Designers must evaluate the proper Newsletter LIVE Programs! control mode. application of waterside economizers and plan for cold towers, as well as cold start-up and operation of chillers. Fan Efficiency Regulations and Release or reduce chilled-water reset Technology Advances. The Air during head pressure control. When a Warmer climates have fewer hours Movement and Control Association chiller is in head pressure control mode, conducive to waterside economizing. The (AMCA) estimates that fans consume an excessively warm chilled-water load profile should be considered when between 30 and 40 percent of setpoint perpetuates the need for head deciding if enough ton-hours and operating commercial HVAC energy. Improving fan pressure control. Releasing or reducing hours exist at attractive wet-bulb efficiency is an important step towards chilled-water reset may even save temperatures. The equipment efficiency reducing overall building energy use. energy, see Table 5. Delivering colder trade off may be a better option in some This program discusses common fan water allows for a reduced chilled-water cases. efficiency metrics, and explains the flow rate and therefore reduced chilled- requirements of new regulations and water pump energy. Due to coil Series arrangement is easier to control industry energy standards. Presenters dynamics, variable flow systems with without disrupting cooling, but beware of also discuss recent fan technology two-way valves (that are operating extending the economizer cycle too long. advances, including motorized properly) should return the same or impellers, direct-drive plenum fans, fan warmer water to the free-cooling heat Once the chiller starts, integrated free and arrays, optimized motor selection, exchanger, not the other way around. mechanical cooling may have marginal variable aspect ratio, and vibration value when mechanical cooling is isolation. Consider putting a variable-frequency controlled optimally. Release chilled-water drive on the lead mechanical chiller reset in integrated mode. If the lead Acoustics in HVAC Outdoor but do not let low chiller loading in mechanical cooling chiller is variable-speed Applications. This program reviews integrated economizer mode trigger hot- and/or high efficiency, terminate the analysis steps required to avoid gas bypass installation or operation. This economizer mode sooner. is false loading and absolutely not the noise complaints caused by outdoor HVAC equipment. Topics include way to go when trying to save energy. By Susanna Hanson, applications engineer, and Jeanne Harshaw, program manager,Trane. You can find this and equipment and sound attenuation previous issues of the Engineers Newsletter at selection, equipment location, sound www.trane.com/EN. To comment, send e-mail to ordinances, barrier walls, reflective [email protected]. surfaces and sound power to sound pressure conversion calculations.

Contact your local Trane office for event details.

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 45–2 7

www.Trane.com/bookstore TRACE 700 v6.3.3 Learn HVAC design strategies and earn credit Now Available

The latest release of TRACE™ 700 focuses on updating and adding to the standard libraries included in the program.

ASHRAE Standard 90.1-2013 libraries. Previously the TRACE library included equipment and constructions for 90.1–2004, 2007, and 2010. This has now been expanded to include 90.1- 2013 equipment and constructions to Earn continuing education credit on- Application manuals. Comprehensive support the LEED v5. demand for LEED® . 60 or 90-minute on- reference guides that can increase your demand programs are available free of working knowledge of commercial HVAC CVHS Library Trane Series S charge. New courses include: systems. Topics range from component combinations and innovative design CenTraVac™ chiller is now available as • HVAC Systems and Airside concepts to system control strategies, cooling equipment library in the Economizers industry issues, and fundamentals. The program. This can be found in the water- • Variable-Speed on following are just a few examples: cooled chiller category. Remember, you Chillers can still import Trane equipment • Chilled-Water VAV Systems selections from TOPSS® into TRACE. All courses are available at • Water-Source and Ground-Source www.trane.com/continuingeducation. Systems Visit www.Trane.com/TRACE to view version details or download a free 30- • Fans clinics. A series of day trial. educational presentations that teach • Dehumidification in HVAC Systems HVAC fundamentals, equipment, and • Ice Storage Systems systems. The series includes full-color student workbooks, which can be • Acoustics in Air-Conditioning purchased individually. Approved by the American Institute of Architects for 1.5 Visit www.trane.com/bookstore for a (Health, Safety and Welfare) learning units complete list of manuals and to place per clinic. Contact your local Trane office your order. to sign up for training in your area.

Engineers Newsletter LIVE. Educational programs covering specific aspects of HVAC design and control. Topics range from water- and airside system strategies to ASHRAE standards and industry codes. Contact your local Trane office for a schedule and to register for upcoming events. Review past programs by visiting www.trane.com/ENL.

Trane, Trane believes the facts and suggestions presented here to be accurate. However, final design and A business of Ingersoll Rand application decisions are your responsibility. Trane disclaims any responsibility for actions taken on the material presented. For more information, contact your local Trane office or e-mail us at [email protected] TM ® The following are registered trademarks of United States Green Building Council: LEED TM ® The following are registered trademarks of Trane: TRACE and CenTraVac

8 Trane Engineers Newsletter volume 45–2 ADM-APN058-EN (June 2016)