"Free" Cooling Using Water Economizers

Total Page:16

File Type:pdf, Size:1020Kb

engineers newsletter volume 37–3 • providing insights for today’s hvac system designer "free" cooling using Standard 90.1 requirements Water Economizers The following sections of the Standard 90.1 prescriptive path are relevant for water economizers.[4] from the editor … Why economize? In past newsletters, we addressed the ability to accomplish "free" cooling by There are times of the year when a Section 6.5.1 Economizers. "Each artfully rearranging traditional cooling cooling system…" over the size equipment [1] and other ways to achieve system can use outdoor conditions to byproduct cooling virtually for free.[2] cool the building or process using the thresholds shown below "that has a fan We’ve also provided newsletters that standard cooling components to shall include either an air or water discussed air economizers and energy distribute its cooling effect. economizer." There are nine exceptions: code requirements.[3] small individual fan cooling units, In this EN, Susanna Hanson (Trane The most prevalent technique is an air spaces humidified above 35°F (2ºC) applications engineer) focuses on the economizer. When the temperature, or dew point for processes, systems with traditional methods of water-side enthalpy, of the outdoor air is low, condenser heat recovery, some economizing and associated energy code requirements. cooler outdoor air is used to reduce the residential applications, and systems temperature (or enthalpy) of air entering with minimal hours or cooling loads. the cooling coil. This can reduce or There is also an option to use higher eliminate mechanical cooling for much Let’s start with some definitions. efficiency equipment in lieu of an of the year in many climates. economizer for unitary system sizes Economize: V. Tr. To use or manage below 760 kBtu/h (63 tons). There is no with thrift: the need to economize Why water economize? Some high efficiency trade-off option for scarce energy resources. applications reduce or negate the applied systems. - economizer n. benefits of air economizers or simply The requirements vary by system size make them impractical. In these cases, and climate zone (Table 6.5.1 and The variety of ways to be thrifty with a water economizer can reduce Figure 1). HVAC energy explains why there are so compressor run hours and energy use. many components of equipment and Some examples include: systems called "economizers". For the Table 6.5.1 Minimum system size for which an economizer is required purposes of this discussion, we will • Minimum humidity requirements - focus on the water economizer as bringing in additional cold, dry Cooling capacity for outdoor air can increase which an economizer is defined by ASHRAE Standard 90.1- Climate zones required 2007 (Standard 90.1) section 3.2. humidification loads. 1a, 1b, 2a, 3a, 4a No economizer required • System limitations - some air Economizer, water: A system by handling units are easily equipped 2b, 5a, 6a, 7, 8 >135,000 Btu/h which the supply air of a cooling with economizers while others are 3b, 3c, 4b, 4c, 5b, 5c, 6b >65,000 Btu/h system is cooled indirectly with water not. This can be related to space, that is itself cooled by heat or mass distance to the outside air intake, transfer to the environment without increased return or exhaust fan Section 6.5.1.2.1 Design Capacity. the use of mechanical cooling. sizing, duct routing, or duct space. The section states that "water economizer systems shall be capable of • Dedicated outdoor air systems - a cooling supply air by indirect separate outdoor air unit is typically evaporation and providing up to 100% sized to serve only the ventilation of the expected system cooling load at loads. Another system to handle outdoor air temperatures of 50°F (10ºC) other building loads may be served dry bulb/45°F (7ºC) wet bulb and below." by chilled water. unless dehumidification loads cannot be met in which case, the water economizer system "must satisfy 100% of the expected system cooling load at 45°F dry bulb/40°F (4ºC) wet bulb." © 2008 Trane All rights reserved ● 1 Figure 1. Standard 90.1 regional economizer requirements based on cooling system capacity growth and corrosion. Maintaining this circuit involves frequently providing the same proper water treatment as the cooling tower. Economizer required if system > 135,000 Btu/h Evaporative cooler with air-cooled chiller. A variation on the water economizer for air-cooled chillers is to Economizer use an evaporative cooler in series with required if system the air-cooled chiller. The air-cooled > 65,000 Btu/h chiller will come on once the evaporative cooler can no longer handle the load by itself. Dry cooler with air-cooled chiller. Another variation for air-cooled chillers is a dry cooler, or closed-circuit cooling tower, in series with the air-cooled Expected building loads can vary chiller. widely for a given dry-bulb and wet- Types of water bulb combination (e.g. night versus economizers Because of their high approach day, occupied versus unoccupied), so temperature, dry coolers may not be this requirement is somewhat unclear. Strainer cycle. In this system, the able to meet the requirement of 100% A reasonable assumption is that the condenser and chilled-water systems of the cooling load at either 50ºF/45ºF intent of the Standard is 100% of the are connected. When the outdoor wet- or 45ºF/40ºF (see previous discussion normal daytime operation cooling load. bulb temperature is low enough, cold of Section 6.5.1.2.1). water from the cooling tower is routed Section 6.5.1.2.2 Maximum Pressure directly into the chilled-water loop. Plate-and-frame heat exchanger. In Drop. "Precooling coils and water-to- this type of water economizer, the water heat exchangers used as part of Although the strainer cycle is the most water from the cooling tower is kept a water economizer system shall either efficient water economizer option, it separate from the chilled-water loop by have a water-side pressure drop of less greatly increases the risk of fouling in a plate-and-frame heat exchanger. This than 15 ft of water or a secondary loop the chilled-water system and cooling is a popular configuration because it shall be created so that the coil or heat coils with the same type of can achieve high heat-transfer exchanger pressure drop is not seen by contamination that is common in open- efficiency without cross- the circulating pumps when the cooling-tower systems. A strainer or contamination. With the addition of a system is in the normal cooling filter can be used to minimize this second condenser-water pump and (noneconomizer) mode." contamination, but the potential for proper piping modifications, this heat fouling prevents widespread use of the exchanger can operate simultaneously A sidestream application (see Figure 3) strainer-cycle system. with the chiller. As much heat as has no maximum pressure drop, since possible is rejected through the heat it is not seen by the circulating pumps Indirect evaporative precooling exchanger while the chiller handles the when in normal cooling mode. coil. For water-cooled, self-contained rest of the cooling load. direct-expansion (DX) systems (like Section 6.5.1.3 Integrated floor-by-floor systems), a precooling Plate-and-frame heat exchangers Economizer Control. "Economizer coil upstream of the refrigerant coil is isolate the building loop from the water systems shall be integrated with the supplied with cold water from the in the open cooling tower loop, but mechanical cooling system and be cooling tower. This indirect evaporative they must be cleaned, typically capable of providing partial cooling precooling-coil circuit is similar to the annually. The labor and parts for even when additional mechanical strainer cycle because it interfaces an cleaning and reassemby (e.g. cooling is required to meet the open circuit directly with the air gasketing) is an expense that should be remainder of the cooling load." delivered to the zones. factored into the life-cycle cost of this option. This is only required in climate zones Indirect evaporative cooling-coil 3b, 3c, 4b, 4c, and 5c. However, circuits, connected directly to an open integrated control is worth considering cooling tower, must be maintained even in cases where it is not required. properly to minimize fouling, microbial 2 ● Trane Engineers Newsletter volume 37–3 providing insights for today’s HVAC system designer Free-cooling chiller. Another method fewer pipes, pumps and fittings and no The water economizer must either of "free" cooling is to transfer heat heat exchanger are required. create the leaving chilled-water between the cooling tower water and setpoint, or the plant must mix colder- the chilled water inside a centrifugal If the free-cooling chiller is part of a than-required water from the operating chiller through the use of refrigerant traditional parallel chiller lineup, chiller with warmer water from the migration, also known as a simultaneous operation is not possible economizer to satisfy the chilled-water thermosiphon. When the temperature without blending leaving chilled-water setpoint. This is seen as undesirable as of the water from the cooling tower is temperatures. It is common for it may use as much energy as it saves. colder than the desired chilled-water designers to embrace a heat exchanger The chiller uses 1.0 to 2.5% more temperature, the compressor is turned in series with a chiller but less energy per degree of colder water off and automatic shutoff valves inside common to embrace chillers in series. created. In this case, since the the chiller refrigerant circuit are If simultaneous operation is desired, temperature is then raised by the opened. Because refrigerant vapor the free-cooling chiller should be warmer water from the economizer, no migrates to the area with the lowest installed in the same location as the pump energy savings are available to temperature, refrigerant boils in the heat exchanger in Figure 3.
Recommended publications
  • Consider Installing a Condensing Economizer, Energy Tips
    ADVANCED MANUFACTURING OFFICE Energy Tips: STEAM Steam Tip Sheet #26A Consider Installing a Condensing Economizer Suggested Actions The key to a successful waste heat recovery project is optimizing the use of the recovered energy. By installing a condensing economizer, companies can im- ■■ Determine your boiler capacity, prove overall heat recovery and steam system efficiency by up to 10%. Many average steam production, boiler applications can benefit from this additional heat recovery, such as district combustion efficiency, stack gas heating systems, wallboard production facilities, greenhouses, food processing temperature, annual hours of plants, pulp and paper mills, textile plants, and hospitals. Condensing economiz- operation, and annual fuel ers require site-specific engineering and design, and a thorough understanding of consumption. the effect they will have on the existing steam system and water chemistry. ■■ Identify in-plant uses for heated Use this tip sheet and its companion, Considerations When Selecting a water, such as boiler makeup Condensing Economizer, to learn about these efficiency improvements. water heating, preheating, or A conventional feedwater economizer reduces steam boiler fuel requirements domestic hot water or process by transferring heat from the flue gas to the boiler feedwater. For natural gas-fired water heating requirements. boilers, the lowest temperature to which flue gas can be cooled is about 250°F ■■ Determine the thermal to prevent condensation and possible stack or stack liner corrosion. requirements that can be met The condensing economizer improves waste heat recovery by cooling the flue through installation of a gas below its dew point, which is about 135°F for products of combustion of condensing economizer.
    [Show full text]
  • Page 1 OPTIMAL ENERGY MANAGEMENT of HVAC
    Page 1 OPTIMAL ENERGY MANAGEMENT OF HVAC SYSTEMS BY USING EVOLUTIONARY ALGORITHM Session Number: CIB T2S5 Authors Fong K F, BEng, MSc, CEng, MCIBSE, MHKIE, MASHRAE Hanby V I, BSc, PhD, CEng, MInstE, MCIBSE Chow T T, PhD, CEng, MIMechE, MCIBSE, FHKIE, MASHRAE Abstract The available plant and energy simulation packages become robust and user-friendly, and this is the major reason that they are so popular even in the consultancy fields in these few years. In fact, these plant and energy simulation packages can be widely adopted in studying different alternatives of the operation of HVAC and building services systems. Since there are many parameters involved in different equipment and systems, one of the useful areas of studies is to optimize the essential parameters in order to provide a satisfactory solution for design or operation in terms of efficient and effective facilities management. Therefore in this paper, the simulation-optimization approach is proposed for effective energy management of HVAC systems. Due to the complexity of the HVAC systems, which commonly include the refrigeration, water and air side systems, it is necessary to suggest optimal conditions for different operation according to the dynamic cooling load requirements throughout a year. A simulation-EA coupling suite has been developed by using the metaheuristic skill, and the evolutionary algorithm can be effectively used to handle the discrete, non-linear and highly constrained characteristics of the typical HVAC and building services optimization problems. The effectiveness of this simulation-EA coupling suite has been demonstrated through the establishment of the monthly optimal reset scheme of the chilled water supply temperature of a local central chiller plant.
    [Show full text]
  • Boiler & Cooling Tower Control Basics
    Boiler & Cooling Tower Control Basics By James McDonald, PE, CWT Originally Published: CSTR – May 2006 For those of us who have been around boilers and cooling towers for years now, it can be easy to forget how we may have struggled when we first learned about controlling the chemistry of boilers and cooling towers. After running all the chemical tests, where do you start when the phosphate is too high, conductivity too low, sulfite nonexistent, and molybdate off the charts? Even better, how would you explain this decision process to a new operator? Cycles of Concentration The first place you always start is cycles of concentration (cycles). You may measure cycles by measuring conductivity or chlorides. If everything else is running normally, when the cycles are too high, everything else should be proportionally too high. When the cycles are too low, everything else should be proportionally too low. When the cycles are brought back under control, the other parameters should come back within range too. Example We wish to run a boiler at 2,000 µmhos, 45 ppm phosphate, and 40 ppm sulfite; however, the latest tests show 1,300 µmhos, 29 ppm phosphate, and 26 ppm sulfite. The conductivity is 35% lower than what it should be. Doing the math ((45- 29)/45=35%), we see that the phosphate and sulfite are also 35% too low. By reducing boiler blowdown and bringing the conductivity back within control, the phosphate and sulfite should be within their control range too. Boilers 100 Beyond Cycles Whether we’re talking about boilers or cooling towers, we know if we reduce blowdown, cycles will increase, and if we increase blowdown, cycles will decrease.
    [Show full text]
  • Ene04 Low Carbon Design Low and Zero Carbon Technologies
    Ene04 Low carbon design Low and zero carbon technologies Actions: i. Implement LZC (low and zero carbon) technologies in-line with the LZC feasibility study ii. Implement passive design measures and free cooling technologies in line with the previous analysis undertaken Recognised local LZC technologies Technologies eligible to contribute to achieving the criteria must produce energy from renewable sources and meet all other ancillary requirements as defined by Directive 2009/28/EC. Local does not have to mean on site – community schemes near to the site can be used as a way of demonstrating compliance. The following requirements must also be met: 1. There must be a direct supply of energy produced to the building under assessment. 2. Technologies under 50 kWe or 45 kWth must be certified by a Microgeneration Certification Scheme (MCS), or equivalent, and installed by MCS (or equivalent) certified installers. 3. Combined heat and power (CHP) schemes above 50 kWe must be certified under the CHPQA standard. CHP schemes fuelled by mains gas are eligible to contribute to performance against this issue. 4. Heat pumps can only be considered as a renewable technology when used in heating mode. Refer to Annex VI of Directive 2009/28/EC for more detail on accounting for energy from heat pumps. 5. Where MCS or CHPQA certification is not available, the design team must investigate the availability of alternative accreditation schemes in line with the Directives listed above, or an equivalent country or regional directive or standard. Where an accreditation scheme exists, it should be used for the purpose of verifying compliance of the specified LZC technology.
    [Show full text]
  • Use Feedwater Economizers for Waste Heat Recovery, Energy Tips
    ADVANCED MANUFACTURING PROGRAM Energy Tips: STEAM Steam Tip Sheet #3 Use Feedwater Economizers for Waste Heat Recovery Suggested Actions ■■ Determine the stack temperature A feedwater economizer reduces steam boiler fuel requirements by transferring after the boiler has been tuned heat from the flue gas to incoming feedwater. Boiler flue gases are often to manufacturer’s specifications. rejected to the stack at temperatures more than 100°F to 150°F higher than The boiler should be operating the temperature of the generated steam. Generally, boiler efficiency can at close-to-optimum excess be increased by 1% for every 40°F reduction in flue gas temperature. By air levels with all heat transfer recovering waste heat, an economizer can often reduce fuel requirements by 5% surfaces clean. to 10% and pay for itself in less than 2 years. The table provides examples of ■■ Determine the minimum the potential for heat recovery. temperature to which stack gases Recoverable Heat from Boiler Flue Gases can be cooled subject to criteria such as dew point, cold-end Recoverable Heat, MMBtu/hr corrosion, and economic heat Initial Stack Gas transfer surface. (See Exhaust Temperature, °F Boiler Thermal Output, MMBtu/hr Gas Temperature Limits.) 25 50 100 200 ■■ Study the cost-effectiveness of installing a feedwater economizer 400 1.3 2.6 5.3 10.6 or air preheater in your boiler. 500 2.3 4.6 9.2 18.4 600 3.3 6.5 13.0 26.1 Based on natural gas fuel, 15% excess air, and a final stack temperature of 250˚F. Example An 80% efficient boiler generates 45,000 pounds per hour (lb/hr) of 150-pounds-per-square-inch-gauge (psig) steam by burning natural gas.
    [Show full text]
  • Demand-Response Management of a District Cooling Plant of a Mixed Use City Development
    Demand-Response Management of a District Cooling Plant of a Mixed Use City Development Segu Madar Mohamed Rifai Master of Science Thesis KTH - Royal Institute of Technology School of Industrial Engineering and Management Department of Energy Technology SE-100 44 STOCKHOLM Thesis Registration No.: EGI- 2012-011MSC Title: Demand-Response Management of a District Cooling Plant of a Mixed Use City Development. SEGU MADAR MOHAMED RIFAI Student Number: 731222 A-315 Approved Examiner Supervisor at KTH Date: 05/06/2012 Prof. Björn Palm Dr. Samer Sawalha Local Supervisor Dr. Hari Gunasingam Commissioner Contact person i | P a g e Abstract Demand for cooling has been increasing around the world for the last couple of decades due to various reasons, and it will continue to increase in the future particularly in developing countries. Traditionally, cooling demand is met by decentralised electrically driven appliances which affect energy, economy and environment as well. District Cooling Plant (DCP) is an innovative alternative means of providing comfort cooling. DCP is becoming an essential infrastructure in modern city development owning to many benefits compared to decentralized cooling technology. Demand Response Management (DRM) is largely applied for Demand Side management of electrical grid. Demand of electrical energy is closely connected with the demand of alternative form of energy such as heating, cooling and mechanical energy. Therefore, application of DR concept should be applied beyond the electrical grid; in particular, it could be applied to any interconnected district energy systems. District Cooling Plant is one of a potential candidate and Demand Response management solutions can be applied to DCP for sustainable operation.
    [Show full text]
  • Free Cooling – Outside Air Economizer White Paper #11
    FREE COOLING – OUTSIDE AIR ECONOMIZER WHITE PAPER #11 It’s like opening a window when it’s hot inside and cool outside. How much does it save? The easy answer is ‘it depends.’ To really find out, read further. You’ll see there are a lot of factors. Like all heat recovery concepts, a pre-requisite for success is to have the free heat (or free cooling) available at the same location and time as there is a need for it. The free heat in Atlanta has no practical use in Alaska because they are too far apart. Likewise, free cooling from outdoors doesn’t provide any value unless it is warm indoors at that time. Balance Temperature Buildings are like boxes. They have thermal losses and gains through the shell (envelope), and they also have appliances and activities inside that generate heat. See Figure 1. There will be a point where the envelope loss just matches the internal heat gains and neither heating nor cooling is required; above this ‘balance temperature’, cooling will be required. Source: Commercial Energy Auditing Reference Handbook, 3e Doty,S., Fairmont Press. Figure 1. Thermal Balance Temperature FREE COOLING – OUTSIDE AIR ECONOMIZER White Paper What is your building’s balance temperature? A building’s thermal balance temperature can be estimated with a method called regression, but there are also clues. See Table 1. If there is a lot of heat-producing equipment inside, the building becomes self- heating and will include hours in cooling mode when it is cold outside. Opportunity! If the heating and cooling load is mostly from envelope (not a lot of equipment), the balance point will be higher which means it probably won’t be hot inside while it is cold outside.
    [Show full text]
  • Mechanical Systems Water Efficiency Management Guide
    Water Efficiency Management Guide Mechanical Systems EPA 832-F-17-016c November 2017 Mechanical Systems The U.S. Environmental Protection Agency (EPA) WaterSense® program encourages property managers and owners to regularly input their buildings’ water use data in ENERGY STAR® Portfolio Manager®, an online tool for tracking energy and water consumption. Tracking water use is an important first step in managing and reducing property water use. WaterSense has worked with ENERGY STAR to develop the EPA Water Score for multifamily housing. This 0-100 score, based on an entire property’s water use relative to the average national water use of similar properties, will allow owners and managers to assess their properties’ water performance and complements the ENERGY STAR score for multifamily housing energy use. This series of Water Efficiency Management Guides was developed to help multifamily housing property owners and managers improve their water management, reduce property water use, and subsequently improve their EPA Water Score. However, many of the best practices in this guide can be used by facility managers for non-residential properties. More information about the Water Score and additional Water Efficiency Management Guides are available at www.epa.gov/watersense/commercial-buildings. Mechanical Systems Table of Contents Background.................................................................................................................................. 1 Single-Pass Cooling ..........................................................................................................................
    [Show full text]
  • Specific Appliances, Fireplaces and Solid Fuel Burning Equipment
    CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT SECTION 901 SECTION 905 GENERAL FIREPLACE STOVES AND ROOM HEATERS 901.1 Scope. This chapter shall govern the approval, design, 905.1 General. Fireplace stoves and solid-fuel-type room installation, construction, maintenance, alteration and repair heaters shall be listed and labeled and shall be installed in of the appliances and equipment specifically identified here­ accordance with the conditions of the listing. Fireplace stoves in and factory-built fireplaces. The approval, design, installa­ shall be tested in accordance with UL 737. Solid-fuel-type tion, construction, maintenance, alteration and repair of gas- room heaters shall be tested in accordance with UL 1482. fired appliances shall be regulated by the Florida Building Fireplace inserts intended for installation in fireplaces shall Code, Fuel Gas. be listed and labeled in accordance with the requirements of UL 1482 and shall be installed in accordance with the manu­ 901.2 General. The requirements of this chapter shall apply facturer's installation instructions. to the mechanical equipment and appliances regulated by this chapter, in addition to the other requirements of this code. 905.2 Connection to fireplace. The connection of solid fuel appliances to chimney flues serving fireplaces shall comply 901.3 Hazardous locations. Fireplaces and solid fuel-burn­ with Sections 801.7 and 801.10. ing appliances shall not be installed in hazardous locations. SECTION 906 901.4 Fireplace accessories. Listed fireplace accessories FACTORY-BUILT BARBECUE APPLIANCES shall be installed in accordance with the conditions of the listing and the manufacturer's installation instructions. 906.1 General.
    [Show full text]
  • Modeling and Optimization of a Thermosiphon for Passive Thermal Management Systems
    MODELING AND OPTIMIZATION OF A THERMOSIPHON FOR PASSIVE THERMAL MANAGEMENT SYSTEMS A Thesis Presented to The Academic Faculty by Benjamin Haile Loeffler In Partial Fulfillment of the Requirements for the Degree Master of Science in the G. W. Woodruff School of Mechanical Engineering Georgia Institute of Technology December 2012 MODELING AND OPTIMIZATION OF A THERMOSIPHON FOR PASSIVE THERMAL MANAGEMENT SYSTEMS Approved by: Dr. J. Rhett Mayor, Advisor Dr. Sheldon Jeter G. W. Woodruff School of Mechanical G. W. Woodruff School of Mechanical Engineering Engineering Georgia Institute of Technology Georgia Institute of Technology Dr. Srinivas Garimella G. W. Woodruff School of Mechanical Engineering Georgia Institute of Technology Date Approved: 11/12/2012 ACKNOWLEDGEMENTS I would like to first thank my committee members, Dr. Jeter and Dr. Garimella, for their time and consideration in evaluating this work. Their edits and feedback are much appreciated. I would also like to acknowledge my lab mates for the free exchange and discussion of ideas that has challenged all of us to solve problems in new and better ways. In particular, I am grateful to Sam Glauber, Chad Bednar, and David Judah for their hard work on the pragmatic tasks essential to this project. Andrew Semidey has been a patient and insightful mentor since my final terms as an undergrad. I thank him for his tutelage and advice over the years. Without him I would have remained a mediocre heat transfer student at best. Andrew was truly indispensable to my graduate education. I must also thank Dr. Mayor for his guidance, insight, and enthusiasm over the course of this work.
    [Show full text]
  • Energy and Exergy Analysis of Data Center Economizer Systems
    San Jose State University SJSU ScholarWorks Master's Theses Master's Theses and Graduate Research Spring 2011 Energy and Exergy Analysis of Data Center Economizer Systems Michael Elery Meakins San Jose State University Follow this and additional works at: https://scholarworks.sjsu.edu/etd_theses Recommended Citation Meakins, Michael Elery, "Energy and Exergy Analysis of Data Center Economizer Systems" (2011). Master's Theses. 3944. DOI: https://doi.org/10.31979/etd.bf7d-khxd https://scholarworks.sjsu.edu/etd_theses/3944 This Thesis is brought to you for free and open access by the Master's Theses and Graduate Research at SJSU ScholarWorks. It has been accepted for inclusion in Master's Theses by an authorized administrator of SJSU ScholarWorks. For more information, please contact [email protected]. ENERGY AND EXERGY ANALYSIS OF DATA CENTER ECONOMIZER SYSTEMS A Thesis Presented to The Faculty of the Department of Mechanical and Aerospace Engineering San José State University In Partial Fulfillment of the Requirements for the Degree Master of Science By Michael E. Meakins May 2011 © 2011 Michael E. Meakins ALL RIGHTS RESERVED The Designated Thesis Committee Approves the Thesis Titled ENERGY AND EXERGY ANALYSIS OF DATA CENTER ECONOMIZER SYSTEMS by Michael E. Meakins APPROVED FOR THE DEPARTMENT OF MECHANICAL AND AEROSPACE ENGINEERING SAN JOSÉ STATE UNIVERSITY May 2011 Dr. Nicole Okamoto Department of Mechanical and Aerospace Engineering Dr. Jinny Rhee Department of Mechanical and Aerospace Engineering Mr. Cullen Bash Hewlett Packard Labs ABSTRACT ENERGY AND EXERGY ANALYSIS OF DATA CENTER ECONOMIZER SYSTEMS By Michael E. Meakins Electrical consumption for data centers is on the rise as more and more of them are being built.
    [Show full text]
  • A Comprehensive Review of Thermal Energy Storage
    sustainability Review A Comprehensive Review of Thermal Energy Storage Ioan Sarbu * ID and Calin Sebarchievici Department of Building Services Engineering, Polytechnic University of Timisoara, Piata Victoriei, No. 2A, 300006 Timisoara, Romania; [email protected] * Correspondence: [email protected]; Tel.: +40-256-403-991; Fax: +40-256-403-987 Received: 7 December 2017; Accepted: 10 January 2018; Published: 14 January 2018 Abstract: Thermal energy storage (TES) is a technology that stocks thermal energy by heating or cooling a storage medium so that the stored energy can be used at a later time for heating and cooling applications and power generation. TES systems are used particularly in buildings and in industrial processes. This paper is focused on TES technologies that provide a way of valorizing solar heat and reducing the energy demand of buildings. The principles of several energy storage methods and calculation of storage capacities are described. Sensible heat storage technologies, including water tank, underground, and packed-bed storage methods, are briefly reviewed. Additionally, latent-heat storage systems associated with phase-change materials for use in solar heating/cooling of buildings, solar water heating, heat-pump systems, and concentrating solar power plants as well as thermo-chemical storage are discussed. Finally, cool thermal energy storage is also briefly reviewed and outstanding information on the performance and costs of TES systems are included. Keywords: storage system; phase-change materials; chemical storage; cold storage; performance 1. Introduction Recent projections predict that the primary energy consumption will rise by 48% in 2040 [1]. On the other hand, the depletion of fossil resources in addition to their negative impact on the environment has accelerated the shift toward sustainable energy sources.
    [Show full text]