ZASF-A Secondary VAV Damper Terminal Box Accessory Controller

The Automated Logic® ZASF-A secondary VAV damper is an integral component of the WebCTRL® system.

The ZASF-A is intended specifically for VAV terminal box applications and is designed to be used with the ZN341A and ZN141A. It mounts directly on the secondary VAV damper shaft and provides an integral actuator and a second integrated flow sensor for damper positioning and air-flow sensing in dual or tracking systems. Key Features and Benefits

Application Features • Quick & easy test and balancing process

Hardware Features • Separable actuator with a 45 inch-pound (5 Nm) torque rating that can be mounted up to a maximum distance of 300 feet from the controller • Precision differential pressure sensor and advanced VAV algorithm increase occupant comfort at both minimum and maximum design air flows, while also extending actuator life

System Benefits • Connects seamlessly to the WebCTRL building automation system

The WebCTRL® building automation system gives you the ability to understand your building operations and analyze the results. The WebCTRL system integrates environmental, energy, security and safety systems into one powerful management tool that allows you to reduce energy consumption, increase occupant comfort, and achieve sustainable building operations. Our web-based platform allows building managers to control and access information about their HVAC, lighting, central plant and critical processes on premises or remotely at any time of day.

​Automated Logic Corporation 1150 Roberts Boulevard, Kennesaw, Georgia 30144 WE MAKE BUILDINGS BETTER. 770-429-3000 Fax 770-429-3001 | www.automatedlogic.com Next level building automation engineered to help you make smart decisions. © Automated Logic 2019 ZASF-A Secondary VAV Damper Specifications

Power The ZASF-A receives power from the ZN341A or ZN141A. Increases the controller’s power supply by 3 VA when connecting a ZASF-A

Actuator Belimo brushless DC motor, torque 45 inch-pounds (5 Nm), runtime 154 seconds

Act Net port To connect the actuator to the ZASF-A controller and to the ZN341A or ZN141A

Integral sensor Precision differential pressure sensor 0–2 in. H2O, sensitive down to ±0.001 in. H2O. Barbed tapered airflow connections accept 3/16 in. (4.75 mm) I.D. tubing. Allows for readings across the 0–2in. H2O range, accurate to ±5% of full flow at 2 in. H2O

Status indicators LED’s indicate status of communications, running, power, and motor direction

Environmental op.range 32 to 130°F (0 to 54.4°C), 10–90% relative , non-condensing

Physical UL94-5VA plenum rated enclosure for installation in plenum (or other space for environmental air) in accordance with NEC Section 300.22 (c) and (d)

Controller and actuator 7.1 in. (18.0 cm) from left side controller mounting hole centerline to actuator mounting hole centerline mounting dimensions

Controller mounting 5.3 in. (13.4 cm) from left side controller mounting hole centerline to right side controller mounting hole centerline dimensions

Actuator mounting 4.4 in. (11.2 cm) from shaft centerline to mounting hole centerline dimensions

8 7 6 5 4 3 2 1

REV ECO DESCRIPTION BY/DATE CHKD/DATE

Controller overall dimensions Actuator overall dimensions 3 DIMENSIONAL CHANGES RE 10/17/17 RE 10/17/17 Width: 6.4 in. (16.3 cm) Width: 3.0 in. (7.6 cm) Height: 5.7 in. (14.5 cm) Height: 5.9 in. (15.0 cm) Depth: 2.1 in. (5.3 cm) Depth: 2.5 in. (6.4 cm) D D

1.67 1.93

.60 .58

.33

6.41 5.10 C 5.87 C 4.89

2.55

1.04

7.08 1.46

8.93

B B

2.50 2.07

.75 5.22 2.96 DWG. NO.

Listed by UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B, Class B, CE VAV MODULES

A

Weight 1.8 lbs (0.82 kg) THIRD ANGLE PROJECTION UNITS MAT'L IN [MM] MM (IN)

DO NOT SCALE DRAWING ALL MATERIALS DESCRIPTION UNLESS OTHERWISE SPECIFIED AND FINISHES VAV MODULE DRAWING DIMENSIONS IN INCHES MUST BE RoHS A TOLERANCES: DWG. NO. REV. DECIMAL COMPLIANT FRACTIONS ± 1/32 VAV MODULES .XXX = ±.005 CAD FILE NAME 3 ±0°30' .XX = ±.010 CUST. PART NO. THIS DOCUMENT IS THE PROPERTY OF AUTOMATED LOGIC CORP. / CCS CORP. AND IS 125 .SLDDRW DELIVERED ON THE EXPRESS CONDITION THAT IT IS NOT TO BE DISCLOSED, REPRODUCED ±.005 .X = ±.015 IN WHOLE OR IN PART, OR USED FOR MANUFACTURE BY ANYONE OTHER THAN AUTOMATED DRAWN DATE CHECKED DATE APPROVED DATE SCALE SHT SHT All trademarks used herein are the property of their respective owners. LOGIC CORP. / CCS CORP. WITHOUT ITS WRITTEN CONSENT, AND THAT NO RIGHT IS GRANTED TO DISCLOSE OR USE ANY INFORMATION CONTAINED IN SAID DOCUMENT. RA ELLETT 04/10/17 04/10/17 04/10/17 DO NOT SCALE 1 OF 1 8 7 6 5 4 3 2 1 1150 Roberts Boulevard, Kennesaw, Georgia 30144 770-429-3000 Fax 770-429-3001 | www.automatedlogic.com

WE MAKE BUILDINGS BETTER. Next level building automation engineered 01292019 to help you make smart decisions.