View metadata, citation and similar papers at core.ac.uk brought to you by CORE provided by Texas A&M University ESL-HH-00-05-51 CONTROL OF HUMIDITY WITH SINGLE - DUCT, SINGLE - ZONE,CONSTANT AIR VOLUME SYSTEM - A CASE STUDY Hui Chen Song Deng Research Associate Senior RA, Project Manager Energy Systems Laboratory Energy Systems Laboratory Texas A&M University System Texas A&M University System College Station, Texas College Station, Texas Phone: (979) 458-2656 Phone: (979) 845-1234 Fax: (979) 862-2457 Fax: (979) 862-2457 Email:
[email protected] Email:
[email protected] Homer L. Bruner, Jr., CEM David E. Claridge, Ph.D., P.E. Mechanical Systems Specialist Professor, Associate Director Utilities Office of Energy Management Energy Systems Laboratory Physical Plant Department Texas A&M University System Texas A&M University System College Station, Texas College Station, Texas Phone: (409) 845-1280 Phone: (409) 862-7185 Fax: (409) 862-2457 Fax: (409) 845-005 1 Email:
[email protected] Email:
[email protected] ABSTRACT analyses on the single-duct constant air volume The lecture hall of the Richardson Petroleum equipment and its Energy Management Control Building at Texas A&M University is a large lecture System (EMCS) algorithm controls. Several hall, with a total floor area of approximately 2500 f?. problems were observed and most were related to the The lecture hall was served by a constant air volume very high humidity of the local climate (e.g., 98% (CAV) air handling unit (AHU) which had no reheat design conditions are 94/75 DBIWB (OF /OF) for coil.