Harmonics Chapter 1, Introduction April 2012 Understanding Power System Harmonics Prof. Mack Grady Dept. of Electrical & Computer Engineering University of Texas at Austin
[email protected], www.ece.utexas.edu/~grady Table of Contents Chapter 1. Introduction Chapter 2. Fourier Series Chapter 3. Definitions Chapter 4. Sources Chapter 5. Effects and Symptoms Chapter 6. Conducting an Investigation Chapter 7. Standards and Solutions Chapter 8. System Matrices and Simulation Procedures Chapter 9. Case Studies Chapter 10. Homework Problems Chapter 11. Acknowledgements Appendix A1. Fourier Spectra Data Appendix A2. PCFLO User Manual Appendix A3. Harmonics Analysis for Industrial Power Systems (HAPS) User Manual and Files 1. Introduction Power systems are designed to operate at frequencies of 50 or 60Hz. However, certain types of loads produce currents and voltages with frequencies that are integer multiples of the 50 or 60 Hz fundamental frequency. These higher frequencies are a form of electrical pollution known as power system harmonics. Power system harmonics are not a new phenomenon. In fact, a text published by Steinmetz in 1916 devotes considerable attention to the study of harmonics in three-phase power systems. In Steinmetz’s day, the main concern was third harmonic currents caused by saturated iron in transformers and machines. He was the first to propose delta connections for blocking third harmonic currents. After Steinmetz’s important discovery, and as improvements were made in transformer and machine design, the harmonics problem was largely solved until the 1930s and 40s. Then, with the advent of rural electrification and telephones, power and telephone circuits were placed on common rights-of-way.