OFFICE OF STRUCTURES STRUCTURAL DETAIL MANUAL

Chapter 07 REINFORCING (REBAR)

OFFICE OF STRUCTURES STRUCTURAL DETAIL MANUAL

Chapter 07 – Reinforcing Details

SECTION 01 LAPS (REBAR-BL)

LOCATION CATEGORY A

BAR CENTER TO CENTER SPACING

SIZE 3'' 4'' 5'' > 6''

#4 2'-5'' 3'-1'' 2'-5'' 2'-10'' 2'-5'' 2'-10'' 2'-5'' 2'-10''

#5 3'-1'' 4'-0'' 3'-0'' 3'-10'' 3'-0'' 3'-7'' 3'-0'' 3'-7''

#6 4'-5'' 5'-9'' 3'-7'' 4'-8'' 3'-7'' 4'-8'' 3'-7'' 4'-8''

#7 6'-0'' 7'-10'' 4'-6'' 5'-11'' 4'-2'' 5'-5'' 4'-2'' 5'-5''

#8 7'-10'' 10'-3'' 5'-11'' 7'-8'' 4'-9'' 6'-2'' 4'-9'' 6'-2''

#9 10'-0'' 13'-0'' 7'-6'' 9'-9'' 6'-0'' 7'-10'' 5'-10'' 7'-8''

#10 - - 9'-6'' 12'-5'' 7'-7'' 9'-11'' 7'-2'' 9'-5''

#11 - - 11'-8'' 15'-3'' 9'-4'' 12'-3'' 8'-8'' 11'-4''

Location Category A - Bars in horizontal layers in top of pour with 12'' or more of below them such as in: footings, pier caps, etc.

LOCATION CATEGORY

BAR CENTER TO CENTER SPACING

SIZE 3'' 4'' 5'' > 6''

#4 1'-10'' 2'-9'' 1'-10'' 2'-2'' 1'-10'' 2'-2'' 1'-10'' 2'-2''

#5 2'-5'' 3'-7'' 2'-4'' 3'-5'' 2'-4'' 2'-9'' 2'-4'' 2'-9''

#6 3'-5'' 5'-1'' 2'-9'' 4'-1'' 2'-9'' 4'-1'' 2'-9'' 4'-1''

#7 4'-8'' 6'-11'' 3'-6'' 5'-3'' 3'-2'' 4'-9'' 3'-2'' 4'-9''

#8 6'-1'' 9'-1'' 4'-7'' 6'-10'' 3'-8'' 5'-5'' 3'-8'' 5'-5''

#9 7'-8'' 11'-6'' 5'-9'' 8'-8'' 4'-8'' 6'-11'' 4'-6'' 6'-9''

#10 - - 7'-4'' 10'-11'' 5'-10'' 8'-9'' 5'-7'' 8'-4''

#11 - - 9'-0'' 13'-6'' 7'-2'' 10'-9'' 6'-8'' 10'-0''

Location Category B - All bars not in Location Category A.

= Non-epoxy coated = Epoxy coated

Note: 1. When bar lap is not specified on 5. These bar laps are Class B splices required by analysis over the the Plans, the above dimensions based on the development lengths entire length of the lap splice shall be used. in Det. No. REBAR-DL-101. Class B and (b) one-half or less of the 2. These bar laps do not apply when splices are 1.3 times the total reinforcement is spliced bar is in lightweight concrete. development length. within the required lap splice Greater lengths are required for 6. Class A splices may be used when length. Class A splices are 1.0 this material. (a) the area of reinforcement times the development length. 3. These bar laps only apply where provided is at least twice that

the General Notes indicate APPROVAL Reinforcing Steel Design, fy = 60 STATE OF MARYLAND

DIRECTOR DEPARTMENT OF TRANSPORTATION

ksi, and Concrete Design, ' = OFFICE OF STRUCTURES

STATE HIGHWAY ADMINISTRATION B

3000 psi. A DATE: OFFICE OF STRUCTURES

03/21/2017 R

4. These bar laps assume cover of

VERSION BAR LAP DIMENSIONS FOR - 2''. Greater lap lengths will be GRADE 60 REINFORCING STEEL B required for cover less than 2''. A IN MIX NO.3 (3500 P..I.) CONCRETE R 1.0 1 1 A DETAIL NO. REBAR-BL-101 SHEET OF P LOCATION CATEGORY A

BAR CENTER TO CENTER SPACING

SIZE 3'' 4'' 5'' > 6''

#4 2'-4'' 3'-0'' 2'-4'' 2'-9'' 2'-4'' 2'-9'' 2'-4'' 2'-9''

#5 3'-0'' 3'-11'' 2'-11'' 3'-9'' 2'-11'' 3'-6'' 2'-11'' 3'-6''

#6 4'-4'' 5'-8'' 3'-6'' 4'-6'' 3'-6'' 4'-6'' 3'-6'' 4'-6''

#7 5'-11'' 7'-8'' 4'-5'' 5'-9'' 4'-1'' 5'-3'' 4'-1'' 5'-3''

#8 7'-8'' 10'-0'' 5'-9'' 7'-6'' 4'-7'' 6'-0'' 4'-7'' 6'-0''

#9 9'-9'' 12'-9'' 7'-4'' 9'-7'' 5'-10'' 7'-8'' 5'-9'' 7'-6''

#10 - - 9'-3'' 12'-1'' 7'-5'' 9'-8'' 7'-1'' 9'-3''

#11 - - 11'-5'' 14'-11'' 9'-2'' 11'-11'' 8'-6'' 11'-1''

Location Category A - Bars in horizontal layers in top of pour with 12'' or more of concrete below them such as in: footings, pier caps, etc.

LOCATION CATEGORY B

BAR CENTER TO CENTER SPACING

SIZE 3'' 4'' 5'' > 6''

#4 1'-10'' 2'-8'' 1'-10'' 2'-2'' 1'-10'' 2'-2'' 1'-10'' 2'-2''

#5 2'-4'' 3'-6'' 2'-3'' 3'-4'' 2'-3'' 2'-8'' 2'-3'' 2'-8''

#6 3'-4'' 5'-0'' 2'-8'' 4'-0'' 2'-8'' 4'-0'' 2'-8'' 4'-0''

#7 4'-6'' 6'-9'' 3'-5'' 5'-1'' 3'-2'' 4'-8'' 3'-2'' 4'-8''

#8 5'-11'' 8'-10'' 4'-5'' 6'-8'' 3'-7'' 5'-4'' 3'-7'' 5'-4''

#9 7'-6'' 11'-3'' 5'-8'' 8'-5'' 4'-6'' 6'-9'' 4'-5'' 6'-7''

#10 - - 7'-2'' 10'-8'' 5'-9'' 8'-7'' 5'-5'' 8'-2''

#11 - - 8'-10'' 13'-2'' 7'-1'' 10'-7'' 6'-6'' 9'-9''

Location Category B - All bars not in Location Category A.

= Non-epoxy coated = Epoxy coated

Note: 1. When bar lap is not specified on 6. These bar laps are Class B splices required by analysis over the the Plans, the above dimensions based on the development lengths entire length of the lap splice shall be used. in Det. No. REBAR-DL-102. Class B and (b) one-half or less of the 2. These bar laps only apply to 4500 splices are 1.3 times the total reinforcement is spliced psi lightweight concrete. development length. within the required lap splice 3. These bar laps only apply where 7. Class A splices may be used when length. Class A splices are 1.0 the General Notes indicate (a) the area of reinforcement times the development length. Reinforcing Steel Design, fy = 60 ksi, provided is at least twice that

and Concrete Design, f'c = 4000 psi. APPROVAL 4. The unit weight of the lightweight STATE OF MARYLAND

DIRECTOR DEPARTMENT OF TRANSPORTATION R

concrete was assumed to be 118 pcf OFFICE OF STRUCTURES E

STATE HIGHWAY ADMINISTRATION B

when calculating the Concrete A DATE: OFFICE OF STRUCTURES

03/21/2017 R

Density Modification Factor.

VERSION BAR LAP DIMENSIONS FOR GRADE 60 - 5. These bar laps assume cover of 2''. REINFORCING STEEL IN MIX NO.10 (4500 P.S.I.) B Greater lap lengths will be required A LIGHTWEIGHT CONCRETE R for cover less than 2''. 1.0 L 1 1 A DETAIL NO. REBAR-BL-102 SHEET OF P LOCATION CATEGORY A

BAR CENTER TO CENTER SPACING

SIZE 3'' 4'' 5'' > 6''

#4 2'-1'' 2'-8'' 2'-1'' 2'-6'' 2'-1'' 2'-6'' 2'-1'' 2'-6''

#5 2'-8'' 3'-6'' 2'-7'' 3'-4'' 2'-7'' 3'-1'' 2'-7'' 3'-1''

#6 3'-10'' 5'-0'' 3'-1'' 4'-0'' 3'-1'' 4'-0'' 3'-1'' 4'-0''

#7 5'-3'' 6'-10'' 3'-11'' 5'-1'' 3'-7'' 4'-8'' 3'-7'' 4'-8''

#8 6'-10'' 8'-11'' 5'-1'' 6'-8'' 4'-1'' 5'-4'' 4'-1'' 5'-4''

#9 8'-8'' 11'-3'' 6'-6'' 8'-6'' 5'-2'' 6'-9'' 5'-1'' 6'-7''

#10 - - 8'-3'' 10'-9'' 6'-7'' 8'-7'' 6'-3'' 8'-2''

#11 - - 10'-1'' 13'-3'' 8'-1'' 10'-7'' 7'-6'' 9'-9''

Location Category A - Bars in horizontal layers in top of pour with 12'' or more of concrete below them such as in: footings, pier caps, etc.

LOCATION CATEGORY B

BAR CENTER TO CENTER SPACING

SIZE 3'' 4'' 5'' > 6''

#4 1'-7'' 2'-5'' 1'-7'' 1'-11'' 1'-7'' 1'-11'' 1'-7'' 1'-11''

#5 2'-1'' 3'-1'' 2'-0'' 3'-0'' 2'-0'' 2'-5'' 2'-0'' 2'-5''

#6 3'-0'' 4'-5'' 2'-5'' 3'-7'' 2'-5'' 3'-7'' 2'-5'' 3'-7''

#7 4'-0'' 6'-0'' 3'-0'' 4'-6'' 2'-9'' 4'-2'' 2'-9'' 4'-2''

#8 5'-3'' 7'-10'' 3'-11'' 5'-11'' 3'-2'' 4'-9'' 3'-2'' 4'-9''

#9 6'-8'' 10'-0'' 5'-0'' 7'-6'' 4'-0'' 6'-0'' 3'-11'' 5'-10''

#10 - - 6'-4'' 9'-6'' 5'-1'' 7'-7'' 4'-10'' 7'-2''

#11 - - 7'-10'' 11'-8'' 6'-3'' 9'-4'' 5'-9'' 8'-8''

Location Category B - All bars not in Location Category A.

= Non-epoxy coated = Epoxy coated

Note: 1. When bar lap is not specified on 5. These bar laps are Class B splices required by analysis over the the Plans, the above dimensions based on the development lengths entire length of the lap splice shall be used. in Det. No. REBAR-DL-103. Class B and (b) one-half or less of the 2. These bar laps do not apply when splices are 1.3 times the total reinforcement is spliced bar is in lightweight concrete. development length. within the required lap splice Greater lengths are required for 6. Class A splices may be used when length. Class A splices are 1.0 this material. (a) the area of reinforcement times the development length. 3. These bar laps only apply where provided is at least twice that

the General Notes indicate APPROVAL Reinforcing Steel Design, fy = 60 STATE OF MARYLAND DIRECTOR DEPARTMENT OF TRANSPORTATION R ksi, and Concrete Design, f'c = OFFICE OF STRUCTURES E STATE HIGHWAY ADMINISTRATION B A 4000 psi. DATE: OFFICE OF STRUCTURES

03/21/2017 R

4. These bar laps assume cover of VERSION BAR LAP DIMENSIONS FOR - 2''. Greater lap lengths will be GRADE 60 REINFORCING STEEL B required for cover less than 2''. A IN MIX NO.6 (4500 P.S.I.) CONCRETE R 1.0 L 1 1 A DETAIL NO. REBAR-BL-103 SHEET OF P OFFICE OF STRUCTURES STRUCTURAL DETAIL MANUAL

Chapter 07 – Reinforcing Details

SECTION 02 DEVELOPMENT LENGTH (REBAR-DL)

LOCATION CATEGORY A

BAR CENTER TO CENTER SPACING

SIZE 3'' 4'' 5'' > 6''

#4 1'-10'' 2'-5'' 1'-10'' 2'-2'' 1'-10'' 2'-2'' 1'-10'' 2'-2''

#5 2'-5'' 3'-1'' 2'-4'' 3'-0'' 2'-4'' 2'-9'' 2'-4'' 2'-9''

#6 3'-5'' 4'-5'' 2'-9'' 3'-7'' 2'-9'' 3'-7'' 2'-9'' 3'-7''

#7 4'-8'' 6'-1'' 3'-6'' 4'-7'' 3'-2'' 4'-2'' 3'-2'' 4'-2''

#8 6'-1'' 7'-11'' 4'-7'' 5'-11'' 3'-8'' 4'-9'' 3'-8'' 4'-9''

#9 7'-8'' 10'-0'' 5'-9'' 7'-6'' 4'-8'' 6'-0'' 4'-6'' 5'-11''

#10 - - 7'-4'' 9'-6'' 5'-10'' 7'-8'' 5'-7'' 7'-3''

#11 - - 9'-0'' 11'-9'' 7'-2'' 9'-5'' 6'-8'' 8'-8''

Location Category A - Bars in horizontal layers in top of pour with 12'' or more of concrete below them such as in: footings, pier caps, etc.

LOCATION CATEGORY B

BAR CENTER TO CENTER SPACING

SIZE 3'' 4'' 5'' > 6''

#4 1'-5'' 2'-1'' 1'-5'' 1'-8'' 1'-5'' 1'-8'' 1'-5'' 1'-8''

#5 1'-10'' 2'-9'' 1'-9'' 2'-8'' 1'-9'' 2'-1'' 1'-9'' 2'-1''

#6 2'-8'' 3'-11'' 2'-1'' 3'-2'' 2'-1'' 3'-2'' 2'-1'' 3'-2''

#7 3'-7'' 5'-4'' 2'-8'' 4'-0'' 2'-6'' 3'-8'' 2'-6'' 3'-8''

#8 4'-8'' 7'-0'' 3'-6'' 5'-3'' 2'-10'' 4'-2'' 2'-10'' 4'-2''

#9 5'-11'' 8'-10'' 4'-5'' 6'-8'' 3'-7'' 5'-4'' 3'-6'' 5'-2''

#10 - - 5'-8'' 8'-5'' 4'-6'' 6'-9'' 4'-3'' 6'-5''

#11 - - 6'-11'' 10'-4'' 5'-7'' 8'-4'' 5'-2'' 7'-8''

Location Category B - All bars not in Location Category A.

= Non-epoxy coated = Epoxy coated

Note: 1. When development length is not 5. The Excess Reinforcement Factor 7. If depth of member does not specified on the Plans, the above was assumed to be 1.0 when allow bar development length dimensions shall be used. calculating these dimensions. indicated in Location Categories 2. These development lengths do not 6. Atr was assumed to be 0 when A and B; then hooks shall be R

apply when bar is in lightweight calculating the Reinforcement added to all bars not conforming, E B

concrete. Greater lengths are Confinement Factor. as per , E, and F per Det. No. A R

required for this material. REBAR-DL-201. -

3. These development lengths only D

apply where the General Notes APPROVAL E STATE OF MARYLAND indicate Reinforcing Steel Design, fy DIRECTOR DEPARTMENT OF TRANSPORTATION E OFFICE OF STRUCTURES L = 60 ksi, and Concrete Design, f'c = STATE HIGHWAY ADMINISTRATION P OFFICE OF STRUCTURES 3000 psi. DATE:03/21/2017 E

4. These development lengths assume VERSION DEVELOPMENT LENGTH DIMENSIONS FOR

cover of 2''. Greater development GRADE 60 REINFORCING STEEL L

lengths will be required for cover IN MIX NO.3 (3500 P.S.I.) CONCRETE E 1.0 N less than 2''. 1 T DETAIL NO. REBAR-DL-101 SHEET OF LOCATION CATEGORY A

BAR CENTER TO CENTER SPACING

SIZE 3'' 4'' 5'' > 6''

#4 1'-10'' 2'-4'' 1'-10'' 2'-2'' 1'-10'' 2'-2'' 1'-10'' 2'-2''

#5 2'-4'' 3'-1'' 2'-3'' 2'-11'' 2'-3'' 2'-8'' 2'-3'' 2'-8''

#6 3'-4'' 4'-4'' 2'-8'' 3'-6'' 2'-8'' 3'-6'' 2'-8'' 3'-6''

#7 4'-6'' 5'-11'' 3'-5'' 4'-5'' 3'-2'' 4'-1'' 3'-2'' 4'-1''

#8 5'-11'' 7'-9'' 4'-5'' 5'-10'' 3'-7'' 4'-8'' 3'-7'' 4'-8''

#9 7'-6'' 9'-10'' 5'-8'' 7'-4'' 4'-6'' 5'-11'' 4'-5'' 5'-9''

#10 - - 7'-2'' 9'-4'' 5'-9'' 7'-6'' 5'-5'' 7'-1''

#11 - - 8'-10'' 11'-6'' 7'-1'' 9'-2'' 6'-6'' 8'-6''

Location Category A - Bars in horizontal layers in top of pour with 12'' or more of concrete below them such as in: footings, pier caps, etc.

LOCATION CATEGORY B

BAR CENTER TO CENTER SPACING

SIZE 3'' 4'' 5'' > 6''

#4 1'-5'' 2'-1'' 1'-5'' 1'-8'' 1'-5'' 1'-8'' 1'-5'' 1'-8''

#5 1'-10'' 2'-8'' 1'-9'' 2'-7'' 1'-9'' 2'-1'' 1'-9'' 2'-1''

#6 2'-7'' 3'-10'' 2'-1'' 3'-1'' 2'-1'' 3'-1'' 2'-1'' 3'-1''

#7 3'-6'' 5'-3'' 2'-8'' 3'-11'' 2'-5'' 3'-7'' 2'-5'' 3'-7''

#8 4'-7'' 6'-10'' 3'-5'' 5'-2'' 2'-9'' 4'-1'' 2'-9'' 4'-1''

#9 5'-10'' 8'-8'' 4'-4'' 6'-6'' 3'-6'' 5'-3'' 3'-5'' 5'-1''

#10 - - 5'-6'' 8'-3'' 4'-5'' 6'-7'' 4'-2'' 6'-3''

#11 - - 6'-9'' 10'-2'' 5'-5'' 8'-2'' 5'-0'' 7'-6''

Location Category B - All bars not in Location Category A.

= Non-epoxy coated = Epoxy coated

Note: 1. When development length is not 6. These development lengths 9. If depth of member does not specified on the Plans, the above assume cover of 2''. Greater allow bar development length dimensions shall be used. development lengths will be indicated in Location Categories 2. These development lengths only required for cover less than 2''. A and B; then hooks shall be apply to 4500 psi lightweight 7. The Excess Reinforcement Factor added to all bars not conforming, concrete. was assumed to be 1.0 when as per D, E, and F per Det. No. 3. These development lengths only calculating these dimensions. REBAR-DL-202.

apply where the General Notes 8. Atr was assumed to be 0 when R E

indicate Reinforcing Steel Design, calculating the Reinforcement B A

fy = 60 ksi, and Concrete Design, Confinement Factor. R

f'c = 4000 psi. -

4. The unit weight of the lightweight D APPROVAL E concrete was assumed to be 118 STATE OF MARYLAND V DIRECTOR DEPARTMENT OF TRANSPORTATION E pcf when calculating the Concrete OFFICE OF STRUCTURES L STATE HIGHWAY ADMINISTRATION O P Density Modification Factor. OFFICE OF STRUCTURES DATE:03/21/2017 M

5. The splitting tensile strength of E VERSION DEVELOPMENT LENGTH DIMENSIONS FOR N the lightweight concrete was T GRADE 60 REINFORCING STEEL IN MIX NO.10 assumed to be not specified when L (4500 P.S.I.) LIGHTWEIGHT CONCRETE E calculating the Concrete Density 1.0 N G

Modification Factor. 1 1 T DETAIL NO. REBAR-DL-102 SHEET OF H LOCATION CATEGORY A

BAR CENTER TO CENTER SPACING

SIZE 3'' 4'' 5'' > 6''

#4 1'-7'' 2'-1'' 1'-7'' 1'-11'' 1'-7'' 1'-11'' 1'-7'' 1'-11''

#5 2'-1'' 2'-8'' 2'-0'' 2'-7'' 2'-0'' 2'-5'' 2'-0'' 2'-5''

#6 3'-0'' 3'-10'' 2'-5'' 3'-1'' 2'-5'' 3'-1'' 2'-5'' 3'-1''

#7 4'-0'' 5'-3'' 3'-0'' 3'-11'' 2'-9'' 3'-7'' 2'-9'' 3'-7''

#8 5'-3'' 6'-10'' 3'-11'' 5'-2'' 3'-2'' 4'-1'' 3'-2'' 4'-1''

#9 6'-8'' 8'-8'' 5'-0'' 6'-6'' 4'-0'' 5'-3'' 3'-11'' 5'-1''

#10 - - 6'-4'' 8'-3'' 5'-1'' 6'-7'' 4'-10'' 6'-3''

#11 - - 7'-10'' 10'-2'' 6'-3'' 8'-2'' 5'-9'' 7'-6''

Location Category A - Bars in horizontal layers in top of pour with 12'' or more of concrete below them such as in: footings, pier caps, etc.

LOCATION CATEGORY B

BAR CENTER TO CENTER SPACING

SIZE 3'' 4'' 5'' > 6''

#4 1'-3'' 1'-10'' 1'-3'' 1'-6'' 1'-3'' 1'-6'' 1'-3'' 1'-6''

#5 1'-7'' 2'-5'' 1'-6'' 2'-3'' 1'-6'' 1'-10'' 1'-6'' 1'-10''

#6 2'-3'' 3'-5'' 1'-10'' 2'-9'' 1'-10'' 2'-9'' 1'-10'' 2'-9''

#7 3'-1'' 4'-8'' 2'-4'' 3'-6'' 2'-2'' 3'-2'' 2'-2'' 3'-2''

#8 4'-0'' 6'-0'' 3'-0'' 4'-6'' 2'-5'' 3'-8'' 2'-5'' 3'-8''

#9 5'-2'' 7'-8'' 3'-10'' 5'-9'' 3'-1'' 4'-7'' 3'-0'' 4'-6''

#10 - - 4'-11'' 7'-4'' 3'-11'' 5'-10'' 3'-9'' 5'-7''

#11 - - 6'-0'' 9'-0'' 4'-10'' 7'-2'' 4'-5'' 6'-8''

Location Category B - All bars not in Location Category A.

= Non-epoxy coated = Epoxy coated

Note: 1. When development length is not 5. The Excess Reinforcement Factor 7. If depth of member does not specified on the Plans, the above was assumed to be 1.0 when allow bar development length dimensions shall be used. calculating these dimensions. indicated in Location Categories

2. These development lengths do not 6. Atr was assumed to be 0 when A and B; then hooks shall be R E

apply when bar is in lightweight calculating the Reinforcement added to all bars not conforming, B A

concrete. Greater lengths are Confinement Factor. as per D, E, and F per Det. No. R

required for this material. REBAR-DL-203. -

3. These development lengths only D

APPROVAL E

apply where the General Notes STATE OF MARYLAND V DIRECTOR DEPARTMENT OF TRANSPORTATION E indicate Reinforcing Steel Design, fy OFFICE OF STRUCTURES L STATE HIGHWAY ADMINISTRATION O = 60 ksi, and Concrete Design, f'c = P OFFICE OF STRUCTURES DATE:03/21/2017 M

4000 psi. E VERSION DEVELOPMENT LENGTH DIMENSIONS FOR N 4. These development lengths assume T GRADE 60 REINFORCING STEEL

cover of 2''. Greater development L

IN MIX NO.6 (4500 P.S.I.) CONCRETE E lengths will be required for cover 1.0 N G

less than 2''. T 1 1 DETAIL NO. REBAR-DL-103 SHEET OF H t t n n e e m m p p ' ' ' ' o o l l h h e e t t v v g g e e n n D D e e ' ' ' L ' L

G G

Hook 2'' min. cover 2•'' min. cover 3'' min. cover for footings 3'' min. cover for footings (See plans for exceptions) (See plans for exceptions)

STANDARD 90 STANDARD 180 HOOK

* BAR LOCATION CATEGORY Note: SIZE D E F For Hook Dimensions and Bends, #4 8'' 11'' 9'' see Detail No. REBAR-BB-102.

#5 10'' 1'-2'' 11'' #6 1'-0'' 1'-5'' 1'-2'' #7 1'-2'' 1'-8'' 1'-4''

#8 1'-4'' 1'-10'' 1'-6'' #9 1'-6'' 2'-1'' 1'-8'' #10 1'-8'' 2'-4'' 1'-11''

#11 1'-10'' 2'-7'' 2'-1''

* LOCATION CATEGORY:

D- All bars terminating with a standard 180 hook with side cover (normal to plane of hook) not less than 2•'',and for 90°deg. hook,cover on bar extension beyond hook not less than 2''. E- All bars not in Category D. F- All bars with hook enclosed vertically or horizontally within ties or stirrup-ties spaced along the full development length not greater than 3d where d is the diameter of the hooked bar.

Note: 1.When development length is not specified on the Plans, the above dimensions shall be used.

2.These development lengths do not apply when bar is R E

in lightweight concrete or any other B A

strength of concrete. R

3.These development lengths only apply where the -

General Notes indicate Reinforcing D

APPROVAL E

Steel Design, fy = 60 ksi. and STATE OF MARYLAND V Concrete Design, f'c = 3000 psi. DIRECTOR DEPARTMENT OF TRANSPORTATION E OFFICE OF STRUCTURES L 4.If depth of member does not allow STATE HIGHWAY ADMINISTRATION O P OFFICE OF STRUCTURES bar development length indicated in DATE: 05/10/2011 M DEVELOPMENT LENGTH DIMENSIONS OF HOOKED E Categories A, B, and C: Detail No. VERSION N REBAR-DL-101; then hook shall be BARS FOR GRADE 60 REINFORCING STEEL T

added to all bars not conforming, IN MIX NO.3 (3500 P.S.I.) CONCRETE L E

as per D,E & F. 1.0 NON-EPOXY COATED REINFORCING N G

1 1 T DETAIL NO. REBAR-DL-201 SHEET OF H t t n n e e m m p p ' ' ' ' o o l l h h e e t t v v g g e e n n D D e e ' ' ' L ' L

G G

Hook 2'' min. cover 2•'' min. cover 3'' min. cover for footings 3'' min. cover for footings (See plans for exceptions) (See plans for exceptions)

STANDARD 90 HOOK STANDARD 180 HOOK

* BAR LOCATION CATEGORY SIZE D E F Note: #4 9'' 1'-1'' 10'' For Hook Dimensions and Bends, see Detail No. REBAR-BB-102. #5 11'' 1'-4'' 1'-1''

#6 1'-1'' 1'-7'' 1'-3''

#7 1'-4'' 1'-10'' 1'-6''

#8 1'-6'' 2'-1'' 1'-8''

#9 1'-8'' 2'-4'' 1'-11''

#10 1'-10'' 2'-8'' 2'-2''

#11 2'-1'' 2'-11'' 2'-4''

* LOCATION CATEGORY:

D- All bars terminating with a standard 180 hook with side cover (normal to plane of hook) not less than 2•'',and for 90°deg. hook,cover on bar extension beyond hook not less than 2''. E- All bars not in Category D. F- All bars with hook enclosed vertically or horizontally within ties or stirrup-ties spaced along the full development length not greater than 3d where d is the diameter of the hooked bar.

Note: 1.When development length is not specified on the

Plans, the above dimensions shall be used. R E

2.These development lengths only apply B A

to 4500 P.S.I. lightweight concrete. R

3.These development lengths only apply where the -

General Notes indicate Reinforcing D

APPROVAL E

Steel Design, fy = 60 ksi. and STATE OF MARYLAND V Concrete Design, f'c = 4000 psi. DIRECTOR DEPARTMENT OF TRANSPORTATION E OFFICE OF STRUCTURES L 4.If depth of member does not allow STATE HIGHWAY ADMINISTRATION O P OFFICE OF STRUCTURES bar development length indicated in DATE: 05/10/2011 M DEVELOPMENT LENGTH DIMENSIONS OF HOOKED E Categories A, B, and C: Detail No. VERSION N BARS FOR GRADE 60 REINFORCING STEEL T

REBAR-DL-102; then hook shall be

added to all bars not conforming, IN LIGHTWEIGHT (4500 P.S.I.) CONCRETE L E

as per D,E & F. 1.0 NON-EPOXY COATED REINFORCING N G

1 1 T DETAIL NO. REBAR-DL-202 SHEET OF H t t n n e e m m p p ' ' ' ' o o l l h h e e t t v v g g e e n n D D e e ' ' ' L ' L

G G

Hook 2'' min. cover 2•'' min. cover 3'' min. cover for footings 3'' min. cover for footings (See plans for exceptions) (See plans for exceptions)

STANDARD 90 HOOK STANDARD 180 HOOK

* BAR LOCATION CATEGORY SIZE D E F Note: #4 7'' 10'' 8'' For Hook Dimensions and Bends, #5 9'' 1'-0'' 10'' see Detail No. REBAR-BB-102. #6 10'' 1'-3'' 1'-0''

#7 1'-0'' 1'-5'' 1'-2''

#8 1'-2'' 1'-7'' 1'-4''

#9 1'-4'' 1'-10'' 1'-6''

#10 1'-5'' 2'-1'' 1'-8''

#11 1'-7'' 2'-3'' 1'-10''

* LOCATION CATEGORY:

D- All bars terminating with a standard 180 hook with side cover (normal to plane of hook) not less than 2•'',and for 90°deg. hook,cover on bar extension beyond hook not less than 2''. E- All bars not in Category D. F- All bars with hook enclosed vertically or horizontally within ties or stirrup-ties spaced along the full development length not greater than 3d where d is the diameter of the hooked bar.

Note: 1.When development length is not specified on the Plans, the above dimensions shall be used.

2.These development lengths do not apply when bar is R E

in lightweight concrete or any other B A

strength of concrete. R

3.These development lengths only apply where the -

General Notes indicate Reinforcing D

APPROVAL E

Steel Design, fy = 60 ksi. and STATE OF MARYLAND V Concrete Design, f'c = 4000 psi. DIRECTOR DEPARTMENT OF TRANSPORTATION E OFFICE OF STRUCTURES L 4.If depth of member does not allow STATE HIGHWAY ADMINISTRATION O P OFFICE OF STRUCTURES bar development length indicated in DATE: 05/10/2011 M DEVELOPMENT LENGTH DIMENSIONS OF HOOKED E Categories A, B, and C: Detail No. VERSION N BARS FOR GRADE 60 REINFORCING STEEL T

REBAR-DL-103; then hook shall be

added to all bars not conforming, IN MIX NO.6 (4500 P.S.I.) CONCRETE L E

as per D,E & F. 1.0 NON-EPOXY COATED REINFORCING N G

1 1 T DETAIL NO. REBAR-DL-203 SHEET OF H OFFICE OF STRUCTURES STRUCTURAL DETAIL MANUAL

Chapter 07 – Reinforcing Details

SECTION 03 BAR BENDS (REBAR-BB)

TYPICAL BAR BENDS DETAILS AND NOTES

SPIRAL ''E'' PITCH

TYPES SP1, SP2, SP3 ''O'' SP1 - 1 1/2 EXTRA TURNS T & B OUTSIDE DIA. SP2 - 2 EXTRA TURNS T & B SP3 - 3 EXTRA TURNS T & B B HEIGHT LENGTH = LIN. FT. WIRE

Unless otherwise noted diameter D is the same for all bends and hooks on a bar

B

C

J D D D H Where slope differs from 45 dimensions D 'H' and 'K' must be shown

ENLARGED VIEW SHOWING BAR BENDING DETAILS

Notes: 1. All dimensions are out-to-out of bar or to tangent points for 135 and 180 hooks. 2. '' dimensions on 180 hooks to be shown only where necessary to restrict hook size. Otherwise standard hooks are to be used. 3. Where 'J' is not shown. ''J' will be kept equal to or less than 'H' on truss bars. Where 'J' can exceed 'H' it should be shown. 4. 'H' dimension on stirrups to be shown where necessary to fit within concrete. 5. Where bars are to be bent more accurately than standard bending toler- ances, bending dimensions which require closer fabrication should have limits indicated.

NOTE TO FABRICATOR

BENDING TOLERANCE NOTE APPROVAL TIES AND STIRRUPS SHALL BE STATE OF MARYLAND BENT WITH A PLUS ZERO INCH DIRECTOR DEPARTMENT OF TRANSPORTATION OFFICE OF STRUCTURES (+0'') MINUS (-) NORMAL ACI STATE HIGHWAY ADMINISTRATION REBAR BARBENDS BENDING TOLERANCES DATE: 02/10/1994 OFFICE OF STRUCTURES

VERSION BAR BEND TYPES GENERAL NOTES 1.0

DETAIL NO. REBAR-BB-101 SHEET 1 OF 8 ACI TYPICAL BAR BENDS STANDARD PIN BENDING

J A C B 20 B A G J 1 11 D B R D C O O B 2 A G B 22 A C F O H E K G C J O D B H K B F 12 J D H 3 A C E H G K O J D A K K B F O 23 A C K H E K G B F D 4 A C E H G B H K 13 D H K K C J J R D B O G 24 A G B O A H C 5 G K/2 J D O K Standee D O 14 A E E B B D H C H A C 6 H G C K K 25 D K B O F O C K

D A G 16 B 7 C H E H D J Standee D A K K K 26 C E

B B F 8 A 17 B D G C B J H R 9 B O 18 A C

B

R O 10 19 K B A C H C D H O K

NOTE TO FABRICATOR

BENDING TOLERANCE NOTE APPROVAL TIES AND STIRRUPS SHALL BE STATE OF MARYLAND BENT WITH A PLUS ZERO INCH DIRECTOR DEPARTMENT OF TRANSPORTATION OFFICE OF STRUCTURES (+0'') MINUS (-) NORMAL ACI STATE HIGHWAY ADMINISTRATION REBAR BARBENDS BENDING TOLERANCES DATE: 02/10/1994 OFFICE OF STRUCTURES

VERSION BAR BEND TYPES ACI - STANDARD PIN BENDING 1.0

DETAIL NO. REBAR-BB-101 SHEET 2 OF 8 ACI TYPICAL BAR BENDS TIES AND STIRRUPS

LAP = K A G A G J H O B D B D

C C

S1 S7 T3 K A G A G J B C G H A H B D B D E D C C

S2 S8 T4

A G A G J J H B D B D B A G

C C

S3 S9 T5

A G B G A O B D H C E

C D

S4 S11 T6

A G K B E G G A A D B D C E B

C D C

S5 T1 T7

A G K B G E A A D B D C E G B C D C

S6 T2 T8

A B G

T9 NOTE TO FABRICATOR

BENDING TOLERANCE NOTE APPROVAL TIES AND STIRRUPS SHALL BE STATE OF MARYLAND BENT WITH A PLUS ZERO INCH DIRECTOR DEPARTMENT OF TRANSPORTATION OFFICE OF STRUCTURES (+0'') MINUS (-) NORMAL ACI STATE HIGHWAY ADMINISTRATION REBAR BARBENDS BENDING TOLERANCES DATE: 02/10/1994 OFFICE OF STRUCTURES

VERSION BAR BEND TYPES ACI - TIES A 1.0 DETAIL NO. REBAR-BB-101 SHEET 3 OF 8 SHA TYPICAL BAR BENDS TIES AND STIRRUPS

J A G A G O G O A J J A G B H H A G B D B D H B D B E B D D D C C C K K K C C

C1 C7 C14 C22 C38 O A G A G K E C D A G B B H G H A G B D D H A B B B D C D J O C C K K C K

C2 C8 C15 C23 C39 A G O A G F A B C J G G J E D E H F A H B D B H D A G B D C B D H D O C C J C K K K K

C3 C9 C16 C27 C40 LAP B A G O B K A E C C B G H D D J D B D H B H B D H C B D C H C C C E K C K K O K K K

C4 C11 C17 C32 C41

J O A G A G A G K E A G J A H H D D H D B B B D B D B C C C C K K K K C

C5 C12 C18 C33 C42

O K K D A G K A E G E A E D H H C H C B D H B D O B D E B C B C G K K C F A C6 C13 C20 C36 C43

NOTE TO FABRICATOR APPROVAL STATE OF MARYLAND BENDING TOLERANCE NOTE DIRECTOR DEPARTMENT OF TRANSPORTATION OFFICE OF STRUCTURES TIES AND STIRRUPS SHALL BE STATE HIGHWAY ADMINISTRATION REBAR BARBENDS BENT WITH A PLUS ZERO INCH DATE: 02/10/1994 OFFICE OF STRUCTURES (+0'') MINUS (-) NORMAL ACI VERSION BENDING TOLERANCES BAR BEND TYPES SHA - TIES AND STIRRUPS 1.0 DETAIL NO. REBAR-BB-101 SHEET 4 OF 8 SHA TYPICAL BAR BENDS TIES AND STIRRUPS

O K J O H C D A G E C J R B H E R

A H B D K O D LAP=K D R B R B B G

C VARIES C C A C42 C47 C51 C56 6 1/2 '' K E A

A B E H C A A G G B K D H C R B D R D F J D B H E O C C A C43 C48 C52 C58 O K C OVERBEND K E A HOOK D A H B D C J H A K D E R K B E J C K B J D B H C O R E A A G C44 C49 C53 O K C O C59 B A B D A G H F 3'' A C E E R J D O K C45 C50 C54 C * C A G K * E H B D * B * C B * * D H * D C46

A A Overbend

C78 C82 For Wing Wall Parapet * Measured to Tangents NOTE TO FABRICATOR of Curves.

BENDING TOLERANCE NOTE APPROVAL TIES AND STIRRUPS SHALL BE STATE OF MARYLAND BENT WITH A PLUS ZERO INCH DIRECTOR DEPARTMENT OF TRANSPORTATION OFFICE OF STRUCTURES (+0'') MINUS (-) NORMAL ACI STATE HIGHWAY ADMINISTRATION REBAR BARBENDS BENDING TOLERANCES DATE: 02/10/1994 OFFICE OF STRUCTURES

VERSION BAR BEND TYPES SHA - TIES AND STIRRUPS 1.0 DETAIL NO. REBAR-BB-101 SHEET 5 OF 8 SHA TYPICAL BAR BENDS STANDARD PIN BENDING

O O

O A G B F A G B J A C H B F B D C E D G C E K H C D D K

C57 C65 C71 C76

O K O A E B A J J H B C H B J B D D G H C G K C G C K O

C60 C66 C72 C77 K K O O O J

C B D H H B J D A B R 2 H 1 B D C C H H C D G A E O K K K

C61 C67 C73 C79

K O B O C A F D A J B H B C B E H C H G D D E K A K D C K C63 C69 C74 C80 O J O A E A G G B F O J B B R J C C H B B F H C C E D K C E R D H O K 2 D D K H 1 C64 C70 C75

NOTE TO FABRICATOR

BENDING TOLERANCE NOTE APPROVAL TIES AND STIRRUPS SHALL BE STATE OF MARYLAND BENT WITH A PLUS ZERO INCH DIRECTOR DEPARTMENT OF TRANSPORTATION OFFICE OF STRUCTURES (+0'') MINUS (-) NORMAL ACI STATE HIGHWAY ADMINISTRATION REBAR BARBENDS BENDING TOLERANCES DATE: 02/10/1994 OFFICE OF STRUCTURES

VERSION BAR BEND TYPES SHA - STANDARD PIN BENDING 1.0 DETAIL NO. REBAR-BB-101 SHEET 6 OF 8 SHA TYPICAL BAR BENDS RADIUS BENDING

O A J

H B R

C D G

C81 O B A G J R H H B E K R R C D C K

C85 C87 O

C R H B D J

K

C91

O

J C

R H B

K C92

Two Plane Bending C D B PLAN

C B C B D D ELEVATION END VIEW

C55

NOTE TO FABRICATOR

BENDING TOLERANCE NOTE APPROVAL TIES AND STIRRUPS SHALL BE STATE OF MARYLAND BENT WITH A PLUS ZERO INCH DIRECTOR DEPARTMENT OF TRANSPORTATION OFFICE OF STRUCTURES (+0'') MINUS (-) NORMAL ACI STATE HIGHWAY ADMINISTRATION REBAR BARBENDS BENDING TOLERANCES DATE: 02/10/1994 OFFICE OF STRUCTURES

VERSION BAR BEND TYPES SHA - RADIUS BENDING 1.0

DETAIL NO. REBAR-BB-101 SHEET 7 OF 8 SHA TYPICAL BAR BENDS TRUSS BAR CONFIGURATIONS

O

B E E E F TR 1 A J C H C C C C C C C D K D D D

O

B E E E

TR 2 A J C H C C C C C C D K D D F

O

B E E F TR 3 A J C H C C C C C J G D K D D

O

B E E

TR 4 A J C H C C C C D K D F

O

B E F TR 5 A J C H C C C J G D K D

O

B E

TR 6 A J C H C C D K F

O

B F ACI Type A J C H E J G 3 D K Note: TR 1 and TR 2 are to be used only when there are more ACI than three bays and it is Type J necessary to splice truss bars. 3 Straight T. & B. Bars * .N.O. Can be substituted for bars in STR. these configuration patterns T & B ( * T. Bars with or without hooks) Hooks for truss bars optional.

NOTE TO FABRICATOR APPROVAL STATE OF MARYLAND DIRECTOR DEPARTMENT OF TRANSPORTATION BENDING TOLERANCE NOTE OFFICE OF STRUCTURES STATE HIGHWAY ADMINISTRATION REBAR BARBENDS TIES AND STIRRUPS SHALL BE DATE: 02/10/1994 OFFICE OF STRUCTURES BENT WITH A PLUS ZERO INCH (+0'') MINUS (-) NORMAL ACI VERSION BENDING TOLERANCES BAR BEND TYPES TRUSS BAR CONFIGURATIONS 1.0

DETAIL NO. REBAR-BB-101 SHEET 8 OF 8 HOOKS TABLE 1 REFERENCES

1. ACI Types 1 thru 26 2. SHA Standard Pin Bending 3. SHA Radius Bending

Detailing Hook Detailing Dimension A or G Dimension

J D D b b d d b 4 d or b A or G 12 d 2 1/2 '' min.

180^ 90^

RECOMMENDED END HOOKS, ALL GRADES Finished BAR bend diameter 180 - deg hook 90 - deg hook SIZE D, in. A or G in J, in. A or G in #3 2 1/4 5 3 6 #4 3 6 4 8 #5 3 3/4 7 5 10 #6 4 1/2 8 6 1-0 #7 5 1/4 10 7 1-2 #8 6 11 8 1-4 #9 9 1/2 1-3 11 3/4 1-7 #10 10 3/4 1-5 1-1 1/4 1-10 #11 12 1-7 1-2 3/4 2-0 #14 18 1/4 2-3 1-9 3/4 2-7 #18 24 3-0 2-4 1/2 3-5

APPROVAL STATE OF MARYLAND DIRECTOR DEPARTMENT OF TRANSPORTATION OFFICE OF STRUCTURES STATE HIGHWAY ADMINISTRATION REBAR BARBENDS DATE: 11/17/1997 OFFICE OF STRUCTURES

VERSION REINFORCING STEEL HOOK TABLES AND DIAGRAMS 1.0

DETAIL NO. REBAR-BB-102 SHEET 1 OF 2 HOOKS TABLE 11 REFERENCES

1. ACI Types S1 thru S11 2. ACI Types T1 thru T8 3. SHA Ties and Stirrups (Note: Tie and stirrup types supplied in sizes #3-#8)

STIRRUP AND TIE HOOKS 12 d forb #6, #7, #8 6 d for #3, #4, #5 b 6d or 2 1/2 '' or 2 1/2 in. minimum b Hook min. A or G

D H A or G Detailing Hook d b d b D Dimension A or G Detailing Detailing Dimension Dimension

J D b d D D 4 d orb 2 1/2 '' min.

90^ 135^ 180^

STIRRUP AND TIE HOOK DIMENSIONS, in.

BAR D, in. 90 - deg hook 135 - deg hook SIZE A or G A or G H, approx #3 1 1/2 4 4 2 1/2 #4 2 4 1/2 4 1/2 3 #5 2 1/2 6 5 1/2 3 3/4 #6 4 1/2 1-0 7 3/4 4 1/2 #7 5 1/4 1-2 9 5 1/4 #8 6 1-4 10 1/4 6

RECOMMENDED END HOOKS, ALL GRADES Finished BAR bend diameter 180 - deg hook SIZE D, in. A or G in J, in. #3 2 1/4 5 3 #4 3 6 4 #5 3 3/4 7 5 #6 4 1/2 8 6 #7 5 1/4 10 7 #8 6 11 8

APPROVAL STATE OF MARYLAND DIRECTOR DEPARTMENT OF TRANSPORTATION OFFICE OF STRUCTURES STATE HIGHWAY ADMINISTRATION REBAR BARBENDS DATE: 11/17/1997 OFFICE OF STRUCTURES

VERSION REINFORCING STEEL HOOK TABLES AND DIAGRAMS 1.0 DETAIL NO. REBAR-BB-102 SHEET 2 OF 2 OFFICE OF STRUCTURES STRUCTURAL DETAIL MANUAL

Chapter 07 – Reinforcing Details

SECTION 04 EXISTING REINFORCING (REBAR-ER)

4'' Low hydrogen electrodes with Existing #8, #9, preheat and interpass 2'' 2'' temperature between #10, or #11 bar. 1/8 2@ 1/16 ''= 1/8 '' 400 F and 1100 F. 60

2'' x 2'' x 1/4 '' x 0'-4'' New #8, #9, #10 or #11 bar. #8 and #9 bars. 2'' x 2'' x 3/8 '' x 0'-4'' Tack weld #10 and #11 bars.

DETAIL FOR WELD SPLICE FOR #8,#9,#10 OR #11 BARS Scale: 3/8 '' = 1''

1/4 '' 5'' 1/2 '' 5'' 1/4 '' Flare bevel groove weld Low hydrogen electrodes preheat and interpass temperature between 400^ and 1100^ F

S

E

1 3/4 '' x 1 3/4 '' x 1/4 '' x 0'-11''.

Existing #4, #5, #6 or #7 bar. New #4, #5, #6 or #7 bar.

E = Effective throat weld DETAIL FOR WELD SPLICE E = .4S Notes: FOR #4,#5,#6 OR #7 BARS 1. All welding to be in conformance with Scale: 3/8 '' = 1'' S = Radius rebar ANSI/AWS-latest addition. 2. Prequalification required in conformance with ANSI/AWS-latest addition. 3. Angles shall be made of ASTM A 709 Grade 36 or AISI 1010, 1015 or 1020 steel. 4. E7018 electrodes shall be used in making the above welded splices. 5. If sufficient bar lap is not available APPROVAL STATE OF MARYLAND DIRECTOR when existing reinforcing steel is DEPARTMENT OF TRANSPORTATION REBAR -EXISTING exposed, this detail to extend bars OFFICE OF STRUCTURES STATE HIGHWAY ADMINISTRATION shall be used. Cost of these DATE: 11/26/2007 OFFICE OF STRUCTURES connections shall be included in VERSION contract prices bid on pertinent SPLICING TO EXISTING REINFORCING STEEL concrete items. WELDED SPLICE 1.0 6. Welded splices shall not be used in decks. DETAIL NO. REBAR-ER-101 SHEET 1 OF 2 Construction gap less than required lap splice dimension See Detail A below

Sleeve coupler with locking bolts

PROPOSED DECK WIDENING EXISTING DECK

SECTION THROUGH SLAB Scale: 1'' = 1'-0''

Surface of Rotate position of sleeve so that concrete maximum cover can be maintained

Spacing and quantity of locking bolts as per manufacturer.

DETAIL A Scale: 3'' = 1'-0'' Notes: 1. The coupler must develop a minimum of 125% of the specified strength of the reinforcing bar being spliced. 2. Couplers used to connect epoxy coated reinforcing bars must be epoxy coated. 3. The uncoated surface of the sheared off indicator bolt must be covered with epoxy prepared from an approved epoxy

touchup kit. APPROVAL 4. Longitudinal deck reinforcing steel STATE OF MARYLAND DIRECTOR DEPARTMENT OF TRANSPORTATION REBAR -EXISTING is not shown. OFFICE OF STRUCTURES STATE HIGHWAY ADMINISTRATION 5. Existing slab shown dashed. DATE: 11/26/2007 OFFICE OF STRUCTURES 6. These couplers will not be measured for payment, but all costs thereof VERSION SPLICING TO EXISTING REINFORCING STEEL shall be included in the Contract MECHANICAL SPLICE lump sum price for the pertinent 1.0 Reinforcing Steel items. DETAIL NO. REBAR-ER-101 SHEET 2 OF 2