Latent And Sensible Energy Reduction For Outside Air

Innovent Packaged Fresh Air Conditioning Units

Innovent LASER units provide both sensible and latent control of outside air at greatly reduced energy costs compared to conventional systems.

Benefits of LASER Technology Innovent offers a ■ Energy costs are reduced using the Innovent heat exchanger to provide “free” precooling and reheat. simple, economical ■ Tempered outside air is provided at low relative humidity. solution to the challenge of meeting ■ Outside air volume is constant and verifiable. the ASHRAE design standard for more ■ Heating/Cooling equipment is selected based on the room load only, reducing the size of the equipment fresh air. and associated duct systems.

■ Humidity in duct work is lower than that for typical cooling equipment. This helps prevent bacteria growth in duct insulation.

LASER-1 units are designed to condition and deliver fresh air to either the space or the intake of a conventional air handler. LASER-2 units have an exhaust air blower and additional heat exchanger for energy recovery from the exhaust airstream.

Both LASER-1 and LASER-2 designs have been pre-engineered over a wide range of airflows. Each unit is designed to incorporate DX or chilled water cooling and a wide variety of heating and filtration options. DX units are available with integral packaged air cooled and water cooled condensing units.

Heating Options Cooling Options Hot Water Coil Chilled Water Coil Steam Coil DX Coil, Split System Indirect Fired Gas Air Cooled DX Coil Electric Heater Water Cooled DX Coil Direct Fired Gas Water Source Heat Pump

All units are fully wired for single point connection and are ETL listed. 24393_4.qx5 8/10/05 9:24 AM Page 3

Designed For High Performance And Low Maintenance

Innovent LASER — Engineered Simplicity in Operation and Maintenance

Innovent products are designed to give long term high performance and low maintenance. The LASER product line continues that tradition.

Over half a decade ago, Innovent realized the necessity for double wall construction in our energy recovery air handlers. Although the market at that time was predominantly single wall, Innovent made the commitment to double wall construction. It is now the industry standard.

Double Wall Construction Provides: ■ Protection for insulation

■ Long unit life

■ Cleanable interior

Innovent Double Wall with Full Independent Frame provides: ■ Total maintenance access

■ Modular design flexibility for retrofit

■ Superior structural design

■ Quiet operation

■ Longer unit life

Many double wall units offered today are modified single wall units with a “liner” covering the insulation. These designs sacrifice maintenance access and structural integrity. Innovent LASER units are built with a full independent frame, flush mounted double wall casing, and fully hinged access doors.

Engineered Simplicity in Heat Exchanger Design. Innovent’s exchanger is the least likely to foul, and the easiest to inspect and clean in the industry.

■ Innovent’s LASER heat exchanger design HAS: - Lower pressure drops

- Simple airflow pattern, 100% accessible surface

■ Innovent’s LASER heat exchanger design does NOT have: - Speed controls, motor/drive sets

- Refrigerants, secondary surface, high fin density

- Dimples, corrugations, baffles 24393_4.qx5 8/10/05 9:24 AM Page 4

LASER 1 Process/Description

3 Dehumidification coil Outside air 1 Heat Exchanger

Free precooling

Tempered supply air 4 Free reheat 2

Process Description 1 – 2 Precooling in heat exchanger 2 – 3 Dehumidification in cooling coil 3 – 4 Free reheat in heat exchanger

Example Conditions

1 96F/77F 2 75F/71F

3 55F/55F 4 72/55% RH 24393_4.qx5 8/10/05 9:24 AM Page 5

LASER 2 Process/Description

Energy Recovery Precool/Reheat 2 4 Dehumidification coil Exhaust Air Heat Exchanger Heat Exchanger

Outside Air 1 3

5 Return Air Tempered supply air

Process Description 1 – 2 Additional reheat (energy recovery) 1 – 2 Winter energy recovery 2 – 3 Precooling in heat exchanger 3 – 4 Dehumidification in cooling coil 4 – 5 Free reheat in heat exchanger

Example Conditions 1 96F/77F 3 68F/68F

2 83F/73F

5 75F/52%RH 4 55F/55F

1 0F 2 50F 24393_4.qx5 8/10/05 9:24 AM Page 6

LASER 1 Plan View

1 2 3 4

Outside Air In

Supply Air Out

5 6

1 Outside air damper 3 Hot Water Coil 5 Supply Fan 2 Filter 4 Heat Exchanger 6 Dehumidification coil

Unit Physical Dimensions* (in inches and pounds)

CFM Model Length Height Width Weight

2000-3500 Laser-1 125 3/16 53 1/4 73 3/4 2500 lb.

4000-5500 Laser-1 134 1/8 64 1/4 83 5/8 3200 lb. 5500-6500 Laser-1 143 3/16 64 1/4 97 5/8 4400 lb. 6500-7500 Laser-1 148 1/8 78 97 5/8 5300 lb. 7500-10000 Laser-1 170 1/16 89 7/8 109 7/16 6600 lb. 10000-15000 Laser-1 193 7/8 101 5/8 131 3/8 9100 lb. 15000+ Contact Innovent Representative

*Dimensions given are for the layout shown above, which is one of several possible arrangements. The optimal arrangement will depend on the outlet condition desired, mounting location, and accessories required. Please fill out the design information sheet on the back cover and contact your Innovent representative for the layout that best meets your requirements. 24393_4.qx5 8/10/05 9:24 AM Page 7

LASER 2 Plan View

Exhaust Air Out 3 4 5

2 1

Outside Air In

6 7 8 9 10

1 Exhaust fan 6 Filter 2 Exhaust damper 7 Outside air face damper 3 Energy recovery heat exchanger 8 Outside air bypass damper 4 Supply fan 9 Precool/Reheat heat exchanger 5 Hot water coil 10 Dehumidification coil

Unit Physical Dimensions* (in inches and pounds)

S/A CFM Length Height Width Weight S/A CFM Length Height Width Weight

1000-1500 225 47 1/4 49 3000 5500-6500 257 64 1/4 97 5/8 7100

1500-2000 235 47 1/4 60 3900 6500-7500 257 78 97 5/8 8300

2000-3500 235 53 1/4 73 3/4 4800 7500-11000 298 89 7/8 109 7/16 10900

3500-4500 235 64 1/4 73 3/4 5200 11000-15000 298 101 7/8 124 1/4 12200

4500-5500 235 64 1/4 83 5/8 6000 15000-20000 351 123 7/8 136 7/8 13900

20000+ Contact Innovent Representative

*Dimensions given are for the layout shown above, which is one of several possible arrangements. The optimal arrangement will depend on the outlet condition desired, mounting location, and accessories required. Please fill out the design information sheet on the back cover and contact your Innovent representative for the layout that best meets your requirements. 24393_4.qx5 8/10/05 9:24 AM Page 8

LASER 1 & LASER 2 Design Parameters

Project Information Project name Tag number Project location Altitude (if above 2,000 ft)

Design Information Outside air flow (cfm) Outside air temperature Summer (DB/WB): Winter (DB/%RH): Return air flow (cfm) – LASER 2 Only Return air temperature – LASER 2 Summer (DB/%RH): Winter (DB/%RH): Only External static pressure (inches Supply: Exhaust (LASER 2 only): wc) Equipment Information Location of unit ■ Indoor ■ Outdoor Mounting ■ Roof curb ■ Structural Steel ■ Concrete Slab ■ Other (please describe): Electrical Service ■ 208/3 ■ 230/3 ■ 480/3 Connections ■ Floor ■ End Cooling coil type ■ DX air cooled ■ DX water cooled ■ DX split system ■ Chilled water (indicate water temp): Heating type ■ Indirect gas ■ Steam (indicate pressure): ■ Electric ■ Hot Water (indicate temperatures): Cooling/Heating ■ Refrigerant type (R 22 is standard): additional ■ % glycol (ethylene or polypropylene): information Other Notes: ______