tche -d HOME APPLIANCES

Pa_ No. 9751596

ALL RANGES CAN TIP • INJURY TO PERSONS COULD RESULT • INSTALL ANTI-TIP DEVICE PACKED WITH RANGE • SEE INSTALLATION INSTRUCTIONS

IMPORTANT: Read and save these instructions. IMPORTANT: Installer: Leave Installation Instructions with homeowner. 30" (76.2 cm) Homeowner: Keep Installation Instructions and anti-tip bracket template for future reference. Electric Slide-in Range Save Installation Instructions for local electrical with self-cleaning inspector's use. thermal/convection oven Cabinet opening dimensions Before you start... 25" (63.5 cm) countertop Read electrical and carpentry instructions. Proper installation is your responsibility.A 24" (61 cm) base qualified technician must install this range. Make sure you have everything necessary for correct J upper cabinet depth _J For minimum installation. It is the customer's responsibility to .... |..Jancat?thetop make sure that the countertop has been properly _J 30." (76.2 cm)rnin.., of the cooktop, sea prepared and that the installation clearances specified on the seriaVrating plate are met. The serial/rating plate is located on the frame behind the drawer. 18" (45.7cm!, / c°_/_,,...,.,,1"'"_ _22-3/4" (67.8 cm) _loPP_[,c_,_tne' _-/// I _ opening depth Check location where range will installed. The range should be located for convenient use in the kitchen. Recessed installations must provide complete enclosure of the sides and rear of range. ALL OPENINGS IN THE WALL OR FLOOR WHERE RANGE ISTO BE INSTALLED MUST BE SEALED. Cutout shown is for a 25-inch (63.5 cm) countertop with a 24-inch (61 cm) base cabinet and no backsplash. If countertop has a backsplash, see "Countertop preparation." Cabinet construction: This appliance is designed for use in a base cabinet with a depth of 24 inches (61 cm). The maximum depth for overhead cabinets is 13" inches outlet is required. See _ between (33 cm). For the minimum vertical clearance cutout and between the cooking surface and the overhead "Electrical re_u,rements,"-:" cabinet door *** Note: 24" (61 cm) min. when bottom of 36" (91.4 era) wood or metal cabinet is protected by cabinets, see Note.*** Overhead cabinets Panel B. or hinge. counter top not less than 1/4" (0.64 cm) flame -% height installed at either side of the appliance must be retardant miflboard covered with not a minimum of 18 inches (45.7 cm) above the Cabinet opening less than No. 28 MSG sheet steel, 0.015" dimensions that are (0.4 ram) stainless steel, 0.024" (0.6 ram) cooking surface. The minimum horizontal shown must be used. aluminum or 0.020" (0.6 ram) copper, distance between the overhead cabinets is 30 30" (76.2 cm) min. clearance between inches (76.2 cm). the top of the cooking platform and the bottom of an unprotected wood or metal cabinet. Countertop preparation Personal Injury Hazard The cooktop sides of the slide-in range fit over If countertop opening width is greater than To eliminate the dsk of burns or fire, avoid the cutout edge of your countertop. 30-318" (77,2 cm), adjust the 1/4" (0.64 cm) installing cabinet storage above the cooking If you have a square finish (flat) countertop dimension. surface, If cabinets are already installed, and the opening width is 30-318" (77,2 cm), no Counterfop must be level. Place level on reduce the hazard of reaching over a heated countertop preparation is required. countertop, first side to side; then front to back. If cooking surface by installing a range hood. Formed front-edged countertops: Must have countertop is not level, range will not be level. The range hood should extend a minimum of 5 inches out from the bottom front of the molded edge shaved flat 1/4" (0.64 cm) from Oven must be level for satisfactory baking each front corner of opening. conditions. cabinets. Tile countertops may need trim cut back Reaching over a heated cooking surface could result in a serious burn or other 1/4" (0.64 cm) from each front corner and/or rounded edge flattened. psmonal injury. Electrical Shock Hazard It is the customer's responsibility: 22-518" • To contact a qualified electrical installer. (57.5 cm) (0.64 cm) • To assure that the electrical installation is adequate and in confonnanca with National Electrical Code, ANSI/NFPA 70 -- latest edition*, or CSA Standard C22,1, Cooktop sides 30-718" of range fit Canadian Eleetdcal Code, Part I --latest (78.4 cm) over edges of edition**, and all local codes and ordinances. countertop Failure to do so could result in fire, electrical opening. Formed or tiled countertop shock or other personal injury. trimmed tJ4" (0.64 cm) back at front corners of counter top opening. Mobile home installation The installation of this range must conform to the Manufactured Home Construction and Safety Product dimensions Standards, Title 24 CFR, Part 3280 (formerly the Anti-tip Federal Standard for Mobile Home Construction 30-z/6" | bracket: and Safety, Title 24, HUD, Part 280); or when such (78.4 cm) standard is not applicable, the Standard for t-t12" cooktop / ' Manufactured Homes Installations (Manufactured (3.6 cm) width Home Sites, Communities and Setups), ANSI A225.1/NFPA 501A, or with local codes*. In Canada, the installation of this range must conform with the current standards CAN/CSA - Z240 -- latest edition** or with local codes. In Canada, the installation of this range must conform withthe current standards CAN/CSA-Z240 36 _ -- latest edition***, or with local codes. (91.4 cm) countertop The floor anti-tip bracket When this range is installed in a mobile home, it height MUST be installed. To install must be secured to the floor during transit. Any the anti-tip bracket shipped method of securing the range is adequate as long with the range, see Panels D as it conforms to the standards listed above. and E and the anti-tip Four-wire power supply cable must be used in a bracket template. mobile home installation. The appliance wiring will need to be revised. See four-wire electrical connection, Panels C and D. Note: The metal chassis of the range MUST be earth- grounded in order for the control panel to 30" (76.2 cm) ) width work. If the metal chassis of the range is not earth- grounded, NO keypads will operate. Check with a 25-3/4" _65.4 ore) qualified electrician if you are in doubt as to whether epth with the metal chassis of range is earth-grounded. handle "_ When installed in a 24" (61 cm) Copies of the standards listed may be obtained from: base cabinet with 25 (63.5 cm) * National Fire ProtectionAssociation countertop -- front of oven door BattarymarchPark _4rotrudea 1-7/8" (4,8 cm) beyond " (61 cm) base cabineL Quincy,Massachusetts 02269 ** Canadian Standard Association 178 Rexdale Boulevard Panel A Rexdale (Toronto),Ontario MgW tR3 Tools needed for Power supply cord Electrical Use a new 40-amp power supply cord. installation: Local codes may permit the use of a .L.-listed, connections 250-volt, 40-ampere range power supply cord NOTE: The metal chassis of the range MUST be flat-blade screwdriver (pigtail). Power supply cord should be Type SRD earth-grounded in order for the control panel to work, or 5/16" (0,8 cm) nut or SRDT and be at least four feet long. The wires If the metal chassis of the range is not earth- level driver that connect to the range must end with ring grounded, NO keypads will operate. Check with a terminals. A 3/4" (1.9 cm), U.L.-listed strain relief qualified electrician if you are in doubt as to whether must be installed where the power supply cord the metal chassis of range is earth-grounded. connects to the range. (See Figures 1 and 2.)

318" (0.95 ¢m) Phillips ratchet Where local codes permit connecting the screwdriver frame-grounding conductor to the neutral ring (white) junction box wire: terminals This appliance is manufactured with the NEUTRAL _1 This blade connected _/ neutral terminal connected to the cabinet. If wrench local codes Do Not permit connecting _to thi_ cabinet-grounding conductor to neutral wire, use "Four-wire connection" instructions.

U.L-listed3,,(,;; NEUTRAL.=,/,.=.T strain relief (white or center)

measuringtape Three-wire power supply cord Electrical Shock/Fire Hazard hand or electric drill wood NEMA 10-50P floor: 1/8" (0,3 cm) drill bit Check that wiring you are using matches concrete/ceramic floor: Figure 1 colors shown in illustrations and specified 3/16" (0.48 cm) carbide- in instruction steps. If wiring does Not tipped masonry drill bit 3/4" (1.9 cm) match, it is your responsibility to have a U.L.4isted NEUTRAL qualified electrician install correct wiring. Parts supplied for Failure to follow these instructions could result in fire, electrical shock or death. installation: strain _e)

anti-tip bracket

1.Turn power supply off. Four-wire power supply cord (Mobile home or other four-wire installations) 2 plastic anchors NEMA 10-50P

(#10 x 1-1/2") Figure 2 (Bracket must be securely mounted to sub- The power supply cord must have three No.-lO floor, Thickness of flooring may require longer copper wires to match a three-wire receptacle of screws to anchor the bracket to sub-floor,) I _ terminal NEMA Type 10-50R. (See Figure 3.) block For mobile home or other four-wire installations: Figure 5 cover This appliance is manufactured with ground Electrical 2 • Remove the terminal block cover located on connected to cabinet. The ground must be revised so the green grounding wire of the four- back of range. Remove the 3/8" (0.95 cm) brass terminal nuts attached to the knockout. requirements wire power cord is connected to the cabinet. See Save Installation Instructions for the local four-wire electrical connection section, Panels C and D. electrical inspector's use. Power supply cord is not provided and is When a four-wire receptacle of NEMA Type available through your local electrical 14-50R is used (See Figure 4.), a matching supply houses. U.L.-listed, four-wire, 250-volt, 40-ampere, range Remove l power supply cord (pigtail) must be used. This cord contains four copper conductors with ring knockout / terminals on the appliance end, terminating in a openingfor 40-am pare _ Electrical Shock Hazard NEMA Type 14-50P plug on the supply end. The power _ A I F fourth (grounding) conductor must be identified • Electrical ground is required on this by a green or green/yellow cover and the neutral supply cord _ appliance, conductor by a white cover. Cord should be Type Figure 6 • Use only a new power supply cord kit rated SRD or SRDT with a U.L.-listed strain relief and at 250 volts, 40 amperes and investigated be at least four feet long. 3, Remove the knockout for the 40-ampere for use with ranges. Do Not reuse an old The MINIMUM conductor sizes for the copper power supply cord. power supply cord. 4-wire power supply cord are: • Do Not modify the power supply cord plug. silver-colored 40-ampere circuit If it does not fit the outlet, have a proper 2, No.-8 conductors outlet installed by a qualified electrician. 1, No.-10 white neutral • Do Not use an extension cord with this 1, No.-8 green grounding appliance. • Do Not ground to a gas pipe. • Do Not have a fuse in the neutral or _rounding nk (white) wire grounding circuit. A fuse in the neutral or For use where grounding circuit could result in an local codes electrical shock. _lermit use of 40-ampere exible power • Check with a qualified electrician if you are supply cord. in doubt as to whether the appliance is , U.L,-listed properly grounded, strain relief three-wire wall four-wirewall Figure 7 Failure to follow these instructions could receptade receptacle result in serious injury or death. (10-50R) (14-S0R) 4. Attach a 3/4" (1.9 cm) U.L.-listed strain Figure 3 Figure 4 relief (U.L. marking on strain relief) to the If codes permit and a separate grounding wire opening. Tighten strain relief firmly to cabinet. is used, it is recommended that a qualified Place power supply cord through strain relief. electrician determine that the grounding path Direct wire is adequate. 5. Using the 3/8" (0.95 cm) brass nuts, A three-wire or four-wire, single-phase, 120/240- The range can be connected directly to fused volt, 60-Hz, AC-onty, electrical supply (or three- disconnect or circuit breaker box through flexible, attach the neutral (white) wire of power supply wire or four-wire 120/208-volt if specified on the armored or non-metallic sheathed, copper cable cord to the center, silver-colored screw of the terminal block. serial/rating plate) is required on a separate (with grounding wire). Do Not use two-wire with 40-ampere circuit, fused on both sides of the line. A bare grounding wire. All current-carrying wires Connect the other two wires to the outer must be insulated. time-delay fuse or circuit breaker is recommended. terminal block screws. (See Figure 7.) THE RANGE MUST BE CONNECTED WITH A U.L-listed conduit connector must be provided Do Not loosen the factory-installed nuts on COPPER WIRE ONLY. at each end of the power supply cord (at the the terminal block. appliance and at the junction box). USE ONLY Be sure the wiring nuts are installed tight. Wire sizes (COPPER WIRE ONLY) and 10-GAUGE SOLID COPPER WIRE. DO NOT connections must conform with the rating of the USE ALUMINUM. Allow two or three feet of slack appliance (40 amperes). Tighten strain relief screws. in the line so the range can be moved if servicing 6, A wiring diagram is located on back of range. is ever necessary. 7, Reattach terminal block cover. Panel B Mobile home or other four-wire installations: 1, Turn power supply off. 1.Turn power supply off.

Electrical Shock/Fire Hazard Electrical Shock Hazard Check that wiring you are using matches J_(7"3"cm---'_) U-shaped Do Not use two wire with a bare colors shown in illustrations and specified hook grounding wire. All current-carrying wires in instruction steps. If wiring does Not must be insulated. match, it is your responsibility to have a Failure to follow these instructions could qualified electrician install the correct Figure 17 Figure result in fire, electrical shock or death• wiring. Direct wire preparation Failure to follow these instructions could 2. Strip outer covering back 3 inches (7.6 cm) result in fire, electrical shock or death. from end exposing the wires. (See Figure 17.) Strip the insulation back 1 inch (2.5 cm) from the end of each wire. Form the bare wire into a U-shard "U" shaped hook. (See Figure 18,) hook

• I 4

/ • Turn power supply off. Figure 8 Figure 9 _'_ .. terminal Direct wire preporolion block 2. Strip outer covering back 3 inches (7.6 cm) from end exposing the wires. (See Figure 8.) i/terminal block brass _ cover Strip the insulation back 1 inch (2.5 cm) from cover the end of each wire, Form the bare wire into a terminal "U" shaped hook, (See Figure 9.) Figure 19 brass terminal 3, Remove the terminal block cover located on Figure 13 back of range. Remove the 3/8" (0.95 cm) brass i. Remove the terminal block cover located on terminal nuts attached to the knockout. back of range. Remove the 3/8" (0.95 cm) brass terminal nuts attached to the knockout. terminal block cover brass terminal J Do Not / conduit Figure 10 remove connector 3. Remove the terminal block cover located on Remove knockout ,pening for )ack of range. Remove the 3/8" (0,95 cm) brass I_ockout_ terminal nuts attached to the knockout. Figure 20

Figure 3. Remove the knockoutfor the 40-ampere power supply cord.

Do Not 4, Attach a 3/4" (1.9 cm) U.L.-listed strain U.L listed remove knockou L-_ _ J conduit relief (U.L marking on strain relief) to the COnduit opening. Tighten strain relief firmly to cabinet. opening Place power supply cord through strain relief. connector Figure 11 r 4. Attach a U.L.-listed conduit connector to 4, Attach a U.L.-listed conduit connector to the the opening, Do Not remove the knockout. Place power supply cable through conduit opening. Do Not remove the knockout. Place connector, allowing enough slack to easily power supply cable through conduit connector, allowing enough slack to easily attach the wiring attach the wiring to the terminal block. (See link screw to the terminal block. (See Figures 20 and 21 .) Figures 11 and 12.) Figure 15 5, Remove the grounding-link screw from the terminal / ! range frame. Save the grounding-link screw, block screw _iL Bend up the grounding link so that it does not contact the range. silver- ,_ IIH/ \\/l \\_l l groundi colored I/ terminal _. link _ block Figure 22 si,v. ,ored ,/I neutral 5, Remove the grounding-link screw from the - (white) Greenscrew wire range frame. Save the grounding-link screw. insulated \\ Bend up the grounding link so that it does not onduit _re MUST contact the range. connected before silver- Figure 12 connecting colored - 5, Using the 3/8" (0.95 cm) brass nuts, attach terminal _.,U.L. listed block the neutral (white) of power supply cable to the Figure 16 strain relief screw silver-colored center screw of the terminal block. Place the hook-shaped end of the wire 6. Connect the green grounding wire to the over the terminal block screw with open side of ,(white) range using the grounding-link screw removed wire the hook facing to the right. Squeeze hook end Green in Step 5. The green grounding wire must be insulated wire of wire together to form a loop. attached first and must Not contact any other MUST be Connect the other two wires to the outer terminal. Connected before terminal block screws. Attach wires using the connecting same method as the neutral wire. (See Figure 7. Using the 318" (0.95 cm) brass nuts, other wires. 12.) attach the neutral (white) wire of power supply cord to the center, silver-colored screw of the ', U.L. listed conduit Do Not loosen the factory-installed nuts on the connector terminal block. terminal block, Figure 23 Connect the other two wires to the outer Center wire MUST be connected to center 6, Connect the green grounding wire to the terminal block screws. (See Figure 16.) screw, range using the grounding-link screw removed Do Not loosen the factory-installed nuts on the terminal block. in Step 5. The green grounding wire must be 6. Tighten conduit connector, locking ring and attached first and must Not contact any other clamping screws. Be sure the wiring nuts are installed tight. terminal.

7 • Reattach terminal block cover. 8. Tighten strain relief screws. 9o Reattach terminal block cover.

Panel C 7. Using the 3/8" (0,95 cm) brass nuts, attach Now start... the neutral (white) of power supply cable to the With range in kitchen. silver-colored center screw of the terminal block. Place the hook-shaped end of the wire over the terminal block screw with open side of I_I emove shipping materials, tape and the hook facing to the right. Squeeze hook end protective film from range. Keep of wire together to form a loop. cardboard bottom and shipping base under Connect the other two wires to the outer range. Remove oven racks and parts package Use an adjustable wrench to from inside oven. terminal block screws. Attach wires using the loosen the leveling legs 1-1/2 turns. same method as the neutral wire (See Figure 23.) Take 4 cardboard range. Stand range back up onto Do Not loosen the factory-installed nuts on the corners from I_ Piece cardboard or hardboard in front of terminal block. cardboard or hardboard. the carton. Stack one Center wire MUST be connected to center ; cardboard cardboard corner on corners screw. top of another. Repeat with the other 8. Tighten conduit connector, locking ring and two corners. Place clamping screws. corners lengthwise on Personal Injury Hazard the floor in back of 9, Reattach terminal block cover. range so corners will support outer side spacers edges of range as shown.

• To reduce the dsk of tipping of the appliance, the appliance must be secured Personal Injury Hazard by a properly installed floor-mounted anti-tip Because of the weight and size of the bracket supplied with the range. range, two or more people are needed to • Save these Installation Instructions. If range move and safely install it. is moved to a new location, the anti-tip bracket must be removed and reinstalled in Failure to do so could result in personal the new location. injury. Electrical Shock Hazard • Take special care when ddlling holes into Flr , ° re,no eno,zit n e,rthe floor. Electrical wires or plumbing may be located beneath floor. • Locate the electrical circuits that could be affected by the installation of this bracket -_ ull cardboard bottom and shipping base and turn off power to these circuits. firmly to remove. Failure to follow these instructions may result in electrical shock or other personal injury.

Numbers correspond to steps.

=

5.13

12. 15.

Panel D 25"(63.5cm) countertop over 24"(61 crn)

Control panels may vary,

1 OFF Move range close to cabinet opening. template 1u• Make electrical connection. See , .,, "Electrical requirements" and "Electrical 7L7._m Place the anti-tip bracket template for connection;' Panels B - D, for details. "8888" slide-in ranges on the floor in the should appear in the clock display. Refer to Use cabinet opening so that the left edge is against and Care Guide for information on electronic cabinets and the top edge is against the rear controls. P wall, molding or cabinet. If countertop opening is deeper than 25 inches (63.5 cm), measure and mark a distance 25 inches (63.5 cm) in from front of countertop opening and align template with -_ Remove cardboard or hardboard from mark (or subtract 25 inches (63.5 cm) from under range. Carefully move range into Push in and turn each surface unit control knob final position. countertop depth and add the difference to the to "HI" position. Check the operation of the 2-1/4-inch (5.7 cm) dimension). cooktop elements and indicator lights.

A 25" ( [1 7=_ Check the operation of the oven element. Press the "BAKE" pad. "350°F " will appear in the temperature display. Countettop Press the "Start/Enter" pad. "Ld' will appear in overhangs the display; then "170°F " (when oven reaches \ cabinet side. 170°F). A = Difference between Press on front of storage drawer and release to The bottom element should glow red and the countertop depth an open. Pull open to first stop position. Lift front of indicator light should be on. The upper element 25" (63.5 cm). should become hot but not glow red. As the oven drawer to clear white wheels in drawer guides. Remove drawer and set it aside on a protected temperature rises, the temperature in the display (A surface. witl increase in 5°F increments until the oven 3 bracket reaches the set temperature. template Press "Cancel/OFF" pad.

If countertop is not flush to the side of cabinet opening, align the left side of the template to allow for the countertop overhang. Tape the slide- ClhemCkth_oPsert thi°n°f t hc_bo_°ipIress in range anti-tip bracket template in place. the "BROIr' pad. "500°F " will appear in the temperature display. Press the "Start/Enter" pad. Look through the oven window. The top element should glow red. Press the "Cancel/OFF" pad. Property Damage • Contact a qualified floor covering installer To get the most efficient use from your for the best procedure of drilling mounting new electric range, read your KitchenAid holes through your type floor covering. Use and Care Guide. Keep Installation • Before moving, slide range onto cardboard Look under range (a flashlight may be needed) to Instructions and Guide close to the or hardboard. check that left rear leveling leg is engaged in the electric range for easy reference. Failure to follow these instructions may anti-tip bracket. If leveling leg is not properly result in damage to floor covering. engaged, remove and reposition the anti-tip bracket to insure that the leveling leg fits properly in the anti-tip bracket.

To mount anti-tip bracket to wood floor, use the anti-tip bracket template to mark where to drill mounting holes. Use a drill with a 1/8" (0.3 cm) drill bit to drill the two holes. Remove Place rack in oven. Place level on rack, first side template from floor. to side; then front to back. If the range is not To mount anti-tip bracket to concrete or level, pull range forward until the rear leveling leg ceramic floor, use the anti-tip bracket template is removed from the anti-tip bracket. Adjust the to mark where to drill mounting holes. Use a drill leveling legs up or down. Then slide range back with a 3/16" (0.48 cm) masonry drill bit to drill the into position. Check that leveling leg is engaged two holes. Remove template from floor. Tap in anti-tip bracket. plastic anchors into mounting holes in floor with NOTE: Oven must be level for satisfactory baking hammer. conditions.

Line up holes in anti-tip Insert storage drawer into slide rails on sides of bracket with holes in floor. drawer opening. Lift front of drawer slightly and Use the screws provided push firmly to close drawer. to fasten anti-tip bracket to floor. bracketNOTE: Anti-tipmust be _.. mounted securely to the sub floor. Depending on the thickness of your flooring, longer screws may be necessary to anchor the bracket to the sub floor. Longer screws are available from your local hardware store.

Panel E If the range does For cleani and If you need not operate... maintenance... assistance... • Check that the circuit breaker is not tripped or If removing the range is necessary for cleaning The KitchenAid Consumer Assistance Center will the house fuse blown, or maintenance, disconnect the electric supply. answer any questions about operating or • Check that power supply cord is plugged into If electrical supply is inaccessible, lift the range maintaining your range not covered in the wall receptacle. slightly at the front and pull the range away from Installation Instructions. The KitchenAid the wall. Pull the range out only as far as Consumer Assistance Center is open 24 hours a necessary to disconnect the electric supply line. day, 7 days a week. Just dial 1-800_422q230 - the call is free within the continental United Refer to Use and Care Guide for operating Remove the range to complete cleaning or I NOTE: I States. instructions and cleaning instructions. maintenance. When you call, you will need the range model Move range back into operating position. number and serial number. Both numbers can be Remove drawer. Level the range. Reconnect the found on the serial/rating plate located on the electrical supply. Make sure that left rear leveling oven frame behind the door. leg is engaged in the anti-tip bracket. Personal Injury/Product Damage Hazard Do Not step, lean or sit on the range, or the If you need drawer or door of the range. Accessories Failure to follow this instruction could service... result in personal injury and/or product • Horizontal Backguard Kit damage. Part No. 9752007 - Brushed aluminum In the event that your KitchenAid appliance • Vertical Backguard Kit should need service, call the dealer from whom Part No. 9752009 - White you purchased the appliance or a KitchenAid- 9752032 - Almond authorized service company. A KitchenAid- 9752033 - Black authorized service company is listed in the Yellow Pages of your telephone directory under "Appliances - Household - Major - Service & Repair." You can also obtain the service company's name and number by dialing, free within the continental United States, the KitchenAid Consumer Assistance Center telephone number, 1-800-422-1230. A special operator will tell you the name of your nearest KitchenAid-authorized service company, Maintain the quality built into your KitchenAid appliance -- can a KitchenAid-authorized service company.

Kitchen kid ° Pa_ No. 9751596 HOME APPLIANCES © 1994 KitchenAid ®RegisteredTrademark of KitchenAid. Prepared by KitchenAid, St. Joseph, Michigan 49085 Printed in Canada