<<

THE GREAT CHILLED DEBATE

Michael Dagher Central Plant

• Direct-Primary, Variable Flow?

• Variable Primary / Variable Secondary (Decoupled)?

• Parallel Vs Series Counterflow?

• Pressure Control?

• What is right/wrong? Chilled Water Pumping Schemes

Way Before • Primary Only, Constant Flow • Constant flow variable return water temperature • Bypassed chilled water mixes with return water resulting in lower chilled water return temperature to the plant. This lower return water temperature reduces the temperature differential (∆T) across the and decreases the overall performance and efficiency of the entire system This phenomenon is known as low ∆T syndrome

Load Load Load

Constant Primary Chilled Water Pumping Schemes

Little Later in 1950s • Decoupled Constant Primary, Variable Secondary • Maintained use of 3-way valves • Decoupler pipe located in plantroom • +ve or –ve flow possible through decoupler • The low ∆T syndrome reduced but still a problem

-ve

Load Load Load

+ve

Constant Primary Variable Secondary Chilled Water Pumping Schemes

Then in Late 1980s • Decoupled Constant Primary, Variable Secondary • Two way control valves introduced • Secondary staged to match coil water flow demands • Some three-way control valves are used together with two-way valves to provide a means of maintaining a minimum secondary flow • The low ∆T syndrome further reduced but still a problem

Staged

-ve M M

Load Load Load

+ve

Constant Primary Variable Secondary Chilled Water Pumping Schemes

Early 1990s • Primary Only, Constant Flow • Constant flow variable return water temperature • Smaller less complex distribution with Bypass in plantroom with field predominantly 2 way control valves at coils. Constant flow in plantroom, variable flow in field. The configuration also suffers from the low ∆T syndrome.

M M M

Load Load Load

Constant Primary Chilled Water Pumping Schemes

Since late 1990s • Decoupled Variable Primary, Variable Secondary • Chiller manufacturers allow designers to vary flow through the chillers, provided tube velocities and rate of change of flow through the evaporator are managed. • With the introduction of variable primary flow, it was now possible to match the primary and secondary flows and the decoupler flow was minimised, addressing the low ∆T syndrome for majority of the time.

Variable Speed Pumps

-Ve M M

FM Load Load Load

+Ve

VSD VSD VSD

Variable Primary Variable Secondary Chilled Water Pumping Schemes

Since late 1990s • Variable Primary Only • Bypass located remotely in field with predominantly 2 way control valves at coils. Flow is modulated to maintain pressure in the field, while the by-pass modulates to maintain chiller minimum flow. The configuration relies on proper control loop tuning ensuring the chiller is not exposed to rapid flow changes. This configuration addresses the low ∆T syndrome issue for the majority of the time.

M M M

Load Load Load

Variable Primary Only Chiller Arrangement

Now • Variable Primary Only, Series Counterflow • This configuration improves overall chiller efficiency by reducing the lift on the . Pumping energy can be higher than parallel arrangement. Pump selection crucial and avoid oversizing (as they need to modulate flow between 100 down to 40%)

M M M

Load Load Load

Series Counterflow Chiller Arrangement Variable Primary Only Chilled Water Distribution Schemes Pressure M Sensors & By-

M M M Pass Load Load Load

M M M Load Load Load

M M M Load Load Load

M M M

Building A Load Load Load Building B Building C

M M M Load Load Load

VSD Booster Pump

Pressure Sensors & By- Pass M

VSD VSD VSD

Variable Primary + Booster Pressure Sensors & Pressure Sensors & Pressure Sensors & Chilled Water By-Pass By-Pass By-Pass M M M

M M M Distribution Load Load Load

M Schemes M M Load Load Load

M M M Load Load Load

M Variable M M Load

Building A Load

Load Building C Secondary Building B

M M M Load Load Load

VSD VSD VSD

Decoupler

FM

VSD VSD VSD

Variable Primary Advantages & Disadvantages of Decoupled Primary/Secondary

Advantages •Simple to apply to large complex precinct systems •Stable Flow through Chillers

Disadvantages •Costly (≈ 5% higher than Primary Only) •Greater pumping energy (≈ 5% higher overall plant energy than Primary Only) Pressure Control – Design Load

A B

C D

E F G H I DP Index Coil 100% Design Flow Setpoint Pressure Drop J K L M Pressure Drop N Node

F G H I C E

M M M Pressure Sensors & By- Load Load Load Pass

B D A VSD VSD VSD

N M L K J Variable Primary Only Pressure Control – Part Load

A B

C D F E G H I DP Index Coil Part Load Flow Setpoint Pressure Drop J K N M L Pressure Drop Node

F G H I C E

M M M Pressure Sensors & By- Load Load Load Pass

B D A VSD VSD VSD

N M L K J Variable Primary Only Pressure Control – Part Load

A B D C F E G H I

DP DP Design Setpoint Index Coil Part Load Flow Operating DP Pressure Drop

J L K M N Pressure Drop Node

F G H I C E &

M M

- Pass Load Load Load By B D Pressure Sensors A VSD VSD VSD

N M L K J Variable Primary Only What is right or wrong?

• Depends on the particular application • Look at all options don’t jump to conclusion too soon • Its about the system nothing but the whole system • Optimise each element, chillers, pumping, flow/pressure control, energy • Staging strategy • Temperature controlled • Reset T and DP • Avoid the temptation of oversizing, can hurt you at part load (+70% of time). Don’t optimise the plant for that one hour of the year. • Work with the chiller manufacturer don’t do it alone THE GREAT CHILLED WATER DEBATE

Stefan Sadokierski Primary – Secondary Arrangement

• Primary circuit: • Fixed or variable flow, • Pump controlled to bypass flow or system thermal load • Secondary circuit – variable flow controlled to pressure • Positives • Primary / secondary hydraulically decoupled, • Simple, robust, well understood, easy to operate • Issues • Excess pumping • Mixing of excess primary and secondary return Primary Only Arrangement

• Single pump set controlled to pressure • Bypass only opens below lowest turndown of smallest chiller • dP (as shown) • Flow • Positives – cost, plant space, efficiency • Issues • Complex controls • Loss of LWT set point on staging • Different chiller sizes means dissimilar pumps in parallel Primary Only – Pros and Cons

• PROS • Lower first cost • Less plant space • Improved efficiency (typically 3-8%) • Fewer components (possibly improved reliability) • CONS • Likely loss of LWT set point when staging on / off • Increased controls complexity • Best performance with chillers all same capacity • Additional commissioning

• RECOMMENDATION • Significant potential benefits – should be considered • Application – not recommended if stable LWT is needed for critical cooling or dehumidification processes • End User – must be informed and trained Series Counter-Flow Arrangement

• Variable primary arrangement • Chiller pairs in series • Counterflow – condenser water flows in opposite direction (not shown) • Compressor lift minimised Series Counter-Flow – Pros and Cons

• PROS • Improved compressor efficiency (~5% for 3+3 = 6°C dT CHW) • Transient chilled water flow issues on staging mitigated • CONS • Increased pumping power (out weighted by compressor savings) • Increased “N” chiller capacity – impact on redundancy • Increased controls complexity

• RECOMMENDATIONS • Standard approach for applications: • Well suited to high dT applications (dT > 7°C) – maintain compressor efficiency and reduce distribution costs • Well suited to large load applications – larger N capacity ok • Can be applied elsewhere, more suited to larger loads • Consider planned and unplanned maintenance activities Other ways to make similar savings

• Compressor power ~ mass flow x lift… • Increase evaporating temperature • Reduce condensing temperature

• Chilled water leaving temperature • Often at 6/12 or 7/14 °C • 10 / 17 °C common practice in UK (won’t work for LT VAV) • Condenser water temperature • Typically WB approach of 5.5 (24 °C wb + 5.5 = 29.5 °C LWT) • Larger tower can be reduced to 2.5 (26.5 °C LWT) • Compare extremes: • CHW at 6/12 and CDW at 29.5 = 23.5 °C lift • CHW at 10/17 and CDW at 26.5 = 16.5 C lift

• Optimised control of CDW temperature to minimise compressor and fan power (ASHRAE sequencing strategy) THE GREAT CHILLED WATER DEBATE

Barry Abboud Overview • The three basic piping systems • Low DeltaT Syndrome – causes, effects, and solutions • Design & Control Considerations (VPF) • Series Counter Flow Chilled Water Piping System Types (typical)

Load Configuration Valves Installed Cost Pumping Cost

Constant Primary Flow 3-way Lowest Highest

Primary / Secondary 2-way Highest Medium

Variable Primary Flow 2-way Medium Lowest Constant Primary Flow Load = Flow X DeltaT With Dedicated Pumping

Secondary Pumps

4 Per Chiller System

Constant Primary Flow Load 125 Tons (440kW) 375Tons (1320kW) With Dedicated Pumping Primary

Flow 3000gpm (189 l/s)

Delta T 3oF (1.7oC) 47 ºF 25% (8.3 ºC)

Secondary Pumps

47 ºF (8.3 ºC) (189 l/s) @ 6.7 ºC)

47 ºF (8.3ºC)

(1760 kW)

(63 l/s) 56 ºF (13.3 ºC) 47 ºF 47 ºF (189 l/s) @ 8.3 ºC) (8.3 ºC)

5 Constant Primary Flow

Advantages Lowest installed cost Less plant space than P/S Easy to Control & Operate Easy to Commission Disadvantages Highest Plant Energy Cost (must run all, even at low loads)

6 Primary (const.) / Secondary (Variable)

SLoad = Flow X DeltaT

Secondary Pumps

PLoad = Flow X DeltaT

7 PRIMARY (VARIABLE) / SECONDARY (VARIABLE) HEADERED PUMPING

Secondary Pumps

8 Per Chiller System PRIMARY/SECONDARY AT 25% LOAD Load 375 Tons (1320kW) 375 Tons (1320kW) Primary Secondary Bypass

Flow 1000gpm (126 l/s) 750gpm (47 l/s) 250gpm (16 l/s)

Delta T 9oF (5oC) 12oF (6.7oC) ----

25% Load25% = 25% Sec Flow Secondary Pumps 750 GPM @ 44 ºF 47 l/s @ 6.7 ºC

53 ºF 44.0 °F (11.7 ºC) (6.7 °C)

(1760 kW) 250 GPM @ 44 ºF 16 l/s @ 6.7 ºC (63 l/s)

1000 GPM @ 53 ºF 750 GPM @ 56 ºF 56 ºF (63 l/s) @ 11.7 ºC) (47l/s) @ 13.3 ºC) (13.3 ºC)

9 Set Point kPa) (76 ft P=25 ) P

PRESS URE DIFFER ENTIAL SENSO PD+Safety R CONTR OLS SECON

DARY PD+Piping PUMP SPEED WPD+Valve

controls speed (coil Point Set to end at located efficiency best for Index of Circuit . . . Differential Pressure sensor down stream down sensor Differential Pressure 10 Variable Primary Flow Load = Flow X DeltaT

Variable Primary Flow at 100% System Load Two-way valves control capacity By varying flow of water in coils

Primary Pumps Chillers Closed

11 Per Chiller System Variable Primary Flow at 25% Load Load 375 Tons (1320kW) 375 Tons (1320 kW)

Primary Bypass

Flow 750 gpm (95 l/s) 0 gpm (0 l/s)

Delta T 12oF (6.7oC) ---- Variable Primary Flow 25%at Load25% System = 25% Flow Load Two-way valves control capacity By varying flow of water in coils

750 GPM @ 44 ºF 47 l/s @ 6.7 ºC

56 ºF 44.0 °F (13.3 ºC) (6.7 °C)

0 GPM @ 44 ºF Primary Pumps 0 l/s @ 6.7 ºC 750 GPM Closed (47 l/s)

750 GPM @ 56 ºF 750 GPM @ 56 ºF 56 ºF (47 l/s) @ 13.3 ºC) (47 l/s) @ 13.3 ºC) (13.3 ºC)

12 Issues with Varying Flow through Chillers V ARYING

 Issue During Normal Operation F LOW  Chiller Type (centrifugal fast, absorbers slow)  Chiller Load (min load - no variance, full load - max variance) T

 System Water Volume (more water, more thermal capacitance, faster variance allowed) HROUGH  Active Loads (near or far from plant)  Typical VSD pump ramp rate setting of 10%/minute (guide for stable temp control)

 Issue Adding Chillers C HILLERS

 Modulating isolation valves on chillers - I SSUES

13 13 Variable Primary Flow (VPF) System Arrangement

 Advantages  Lower Installed Cost (approx. 5% compared P/S)  No secondary Pumps or piping, valves, electrical, installation, etc.  Offset somewhat by added 2W Bypass Valve and more complex controls  Less Plant Space Needed  Best Chilled Water Pump Energy Consumption (most optimised configuration)  VSD energy savings  Lower Pump Design Head  Higher Pump Efficiency  Lower potential impact from Low Delta T (can over pump chillers if needed)

14 PUMP CURVES - PUMP EFFICIENCY

With VPF you will need larger pumps compared to P/S, but they will be operating at a more efficient point, yielding energy savings 15 Variable Primary Flow (VPF) System Arrangement

 Disadvantages Requires more robust (complex and properly calibrated) control system Requires coordinated control of chillers, isolation valves, and pumps Potentially longer commissioning times to tune the system Need experienced facility manager to operate/maintain properly

16 MAJOR CAUSES OF LOW DELTA T

 Dirty Coils  Controls Calibration  Leaky 2-Way Valves  Coils Piped-Up Backwards  Mixing 2-Way with 3-Way Valves in the same system

17 NEGATIVE EFFECTS OF LOW DELTA T IN P/S SYSTEMS

Consequences:  Higher secondary pump energy  pumps run faster

 Higher chilled water plant energy  Ancillary equipment

 Can’t load up chillers  more than ratio Act DT / Des DT  10/12 = 83%

18 NEGATIVE EFFECTS OF LOW DELTA T IN VPF SYSTEMS

Consequences:  Higher secondary pump energy  pumps run faster

 Higher chilled water plant energy  Ancillary equipment

 Can’t load up chillers  more than ratio Act DT / Des DT  10/12 = 83% or 417 tons

19 SOLUTION TO (OR REDUCE EFFECTS OF) LOW DELTA T

 Address the causes  Clean Coils  Calibrate controls periodically  Select proper 2W valves (dynamic/close-off ratings) and maintain them  No 3W valves in design  Find and correct piping installation errors  Over deltaT chillers by resetting supply water down (P/S)  Over pump chillers at ratio of Design Delta T / Actual Delta T (VPF)  Use VSD Chillers & Energy-based sequencing (from 30 to 80% Load)

Solve at Load, Mitigate at Plant

20 VPF SYSTEMS DESIGN/CONTROL CONSIDERATIONS

Chillers  Equal Sized Chillers preferred, but not required  Maintain Min flow rates with Bypass control (manufacturer)  Maintain Max flow rates (3 m/s) and max WPDs (manufacturer)  Modulating Isolation Valves (or 2-position stroke-able) set to open in 1.5 to 2 min  Don’t vary flow too quickly through chillers (VSD pump Ramp rate – typical setting of 10%/min)  Sequence  If CSD Chillers – Load-based sequencing…run chillers to max load (Supply Temp rise). Do not run more chillers than needed (water-cooled, single compressor assumed)  If VSD Chillers – Energy-based sequencing…run chillers between 30% and 80% load (depending on ECWT and actual off-design performance curves). Run more chillers than load requires.  Add Chiller - CHW Supply Temp or Load (Flow X Delta T) or amps (if CSD)  Subtract Chiller - Load (Flow X Delta T) or Amps (if CSD)

21 21 VPF SYSTEMS DESIGN/CONTROL CONSIDERATIONS

Pumps  Variable Speed Driven  Headered arrangement preferred  Sequence  with chillers (but run an extra pump than # chillers for over-pumping in low delta T situations)  Flow-based sequencing  Energy-based sequencing (most efficient combination of pumps)  Speed controlled by pressure sensors at end of index circuit (fast response important)  Direct wired  Piggyback control for large distances  Optimized - Reset pressure sensor by valve position of coils

22 VPF SYSTEMS DESIGN/CONTROL CONSIDERATIONS

Bypass Valve  Maintain a minimum chilled water flow rate through the chillers  Differential pressure measurement across each chiller evaporator  Flow meter preferred  Modulates open to maintain the minimum flow through operating chiller(s).  Bypass valve is normally open, but closed unless Min flow breeched  Pipe and valve sized for Min flow of operating chillers (total min)  High Range-ability (100:1 or better preferred)  PSID Ratings for Static, Dynamic, And Close Off = Shut Off Head of Pumps  Linear Proportion (Flow to Valve Position) Characteristic preferred  Fast Acting Actuator  Control setpoint higher than absolute chiller minimum  Locate some distance from chillers/pumps (preferred)  Energy Storage / inertia

23 ENHANCED EFFICIENCY THROUGH SERIES COUNTER FLOW

Pressure Pressure

Condenser Condenser 2

Compressor 2 Lift 2 Condenser 1 Compressor Evaporator 2 Lift 1 Compressor 1 Evaporator 1 Evaporator

Enthalpy

140 C 100 C LCHWT 60 C ECHWT Evaporator Evaporator

LCWT

Condenser Condenser 0 35 C 0 32 C ECWT 290 C ENHANCED EFFICIENCY THROUGH SERIES COUNTER FLOW

Parallel Chillers SCF Chillers Total Capacity (kWr) 2 x 1500 2 x 1500 Evap Flow Total (L/s) 44.7 x 2 = 89.4 89.4 Evap DP (kPa) 82.4 78.9 Cond Flow Total (L/s) 69.8 x 2 = 139.6 138.7 Cond DP (kPa) 76.9 54.2 R134a Charge (kg) 2 x 603 = 1206 2 x 438 = 876 Cost ($) BASE Less than BASE

VPF Evap min (L/s) 13 22

Load (kWr) Parallel (kWe) SCF (kWe) Saving (kWe) % 3000 471.0 446.5 24.5 5.2% 2700 378.0 355.5 22.5 6.0% 2400 297.8 276.3 21.5 7.2% 2100 229.4 210.0 19.4 8.5% 1800 171.5 154.4 17.1 10.0% 1500 122.7 108.6 14.1 11.5% 1200 100.2 87.5 12.7 12.7% 900 80.9 69.5 11.4 14.1% 600 65.2 56.9 8.3 12.7% 300 75.4 66.0 9.3 12.4%