Understanding Chilled Beam Systems
Total Page:16
File Type:pdf, Size:1020Kb
Load more
Recommended publications
-
Heat Transfer Pathways in Underfloor Air Distribution (UFAD) Systems
UC Berkeley HVAC Systems Title Heat transfer pathways in underfloor air distribution (UFAD) systems Permalink https://escholarship.org/uc/item/52f04592 Authors Bauman, F. Jin, H. Webster, T. Publication Date 2006 Peer reviewed eScholarship.org Powered by the California Digital Library University of California © 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Vol 112, Part 2. For personal use only. Additional distribution in either paper or digital form is not permitted without ASHRAE's permission. QC-06-053 Heat Transfer Pathways in Underfloor Air Distribution (UFAD) Systems Fred S. Bauman, PE Hui Jin, PhD Tom Webster, PE Member ASHRAE Member ASHRAE Member ASHRAE Please note that the following two statements have been of cooling airflow needed to remove heat loads from a building added as a result of the peer-review process for this paper: space using the assumption of a well-mixed room air condi- Results of heat gain shown in this theoretical steady-state tion. The familiarity of designers with this relatively simple model may be greater than those found in actual practice for equation has led to a situation in which design space heat gains UFAD systems. This may be for a number of reasons that are (i.e., total room cooling loads) are considered synonymous not now understood and should be the basis for further research with return air extraction rates, and cooling airflows are found and study. from the (mixed) room-supply temperature difference, typi- cally assumed to be 11°C (20°F). In a stratified underfloor air ABSTRACT distribution (UFAD) environment, the assumption of perfect This paper reports on a modeling study to investigate the mixing is no longer valid, requiring a different way of thinking primary pathways for heat to be removed from a room with about energy flows and airflow quantities. -
Optimal Forced-Air Distribution in New Housing
ptimal F fee ~ ir istributi n in New H usin John ~ Andrews Introduction Cooling~Load Characteristics of the Optimized House Studies of forced-air thermal distribution systems in small buildings show that significant energy losses are common A calculation of the peak cooling load in New York State in ductwork. These losses stem from several mechanisms, was performed for both a conventional house and the opti including duct leakage, thermal conduction through duct mized design that would replace it (Andrews et aL 1989). walls, and selective pressurization and depressurization of The conventional house was a single-story 1500 ft2 different zones of the house when the air-distribution fan 2 [140 m ] structure with R-l1 insulation in the wans, R-20 is operating. One way to reduce or eliminate duct losses is in the ceiling, unshaded window area 15 % of the south to place the ductwork within the conditioned space, rather wall and 10% of the other wans, and an average summer than the more usual attic, crawlspace, or basement loca time air infiltration rate of 0.7 air changes per hour tions. This approach is encouraged by new standards such (ACH) .. Calculated heat gains from various sources are as ASHRAE 90.2. shown in the first column of Table 1e Duct losses equal to 30% of the cooling input are assumed here, within the A major impediment to this solution is the size and range of recent results (Cummings and Tooley 1989, unsightliness of the ductwork. If ducts could be made Modera et ale 1991). smaller in cross section, builders might be motivated to them within the conditioned space. -
Chilled-Beam Basics Getting Better Acquainted with This Type Nighttime Air Is Blown Through a Cooling Tower
Chilled-Beam Basics Getting better acquainted with this type nighttime air is blown through a cooling tower. The resulting cooled water is moved through a plate- of convection HVAC system designed and-frame heat exchanger and circulated through to heat or cool nonresidential buildings cross-linked-polyethylene (PEX) tubing attached to the underside of floor slabs. During the day, warmer By JOHN VASTYAN building air is blown through narrow plenums below Common Ground the slabs. The air is cooled and discharged through Manheim, Pa. perforated grilles in a radiant ceiling (Figure 1). “The movement of cooler air formed a gentle As a consulting engineer during the 1970s, Greg convection within enclosed spaces, but not enough air Cunniff worked closely with another engineering volume for evaporative cooling,” Cunniff said. professional, Dan Prill, at the request of Montana Bell. This approach has two advantages: The project: a new 100,000-sq-ft facility to house • Reduced energy consumption. The use of nighttime telephone switching equipment. economizer thermal storage in building slabs can reduce “Our first energy crisis was upon us, and the telephone daytime cooling energy consumption by up to 30 percent. giant—with all that energized gear— wanted to find ways to reduce their energy Floor slab used for thermal storage Aconsumption,” Cunniff, now application engineering manager for Taco Inc., Chilled water from recalled. wet-side economizer (plate-and-frame heat Cunniff and Prill won the engineering exchanger) at night contract based in part on their offbeat plan to build in “nighttime economizer Perforated ceiling panel cooling.” Preparations would entail Daytime dedicated-outdoor-air-system doubling the thickness of the facility’s airflow standard 6-in. -
Chilled Ceiling Guide, Passive Beams Theory Water Cooling
lindab | we simplify construction Chilled ceiling guide, passive beams Theory water cooling © 10.2018 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB. Lindab's products, systems, product and product group designations are protected by intellectual property rights (IPR). lindab | chilled ceiling guide Chilled ceiling guide, passive beams Function A chilled beam is a heat exchanger that transfers the heat in the room air to a cooling water circuit. Heat transfer between the room air and a surface is achieved in two ways, in part, through heat radiation between the surface of the beam and the surrounding surfaces of the room and, in part, as convection between the air closest to the surface and the surface itself. These two heat transfer values are then added together to form the total heat transfer. 2 Lindab reserves the right to make changes without prior notice 2018-10-23 lindab | chilled ceiling guide Chilled ceiling guide, passive beams Natural convection technology has an ε value of 0.95. The total εt value is the value of the surface of the chilled beam multiplied by the ε value of the surfaces of the room. The ε value of the surfaces of Heat transfer the room can vary a bit, but as a rule, a ε value of 0.94 is selected for ordinary rooms. A chilled beam is a heat exchanger which transfers the heat in the room air to a cooling water circuit. To avoid The total εt value is therefore: condensation, the temperature of the water supplied to 0.95 × 0.94 ≈ 0.9 the beam must not be too low (approx. -
6.0 Analysis 2: Chilled Beams Cost & Schedule Impact
6.0 Analysis 2: Chilled Beams Cost & Schedule Impact (Mechanical Breadth) 6.1 Background The mechanical package for the JHH project accounts for 29.1% of the construction cost. The HVAC system alone totals $79,444,970 or 13.9% of the construction cost. The critical path of the project largely involves the installation of the HVAC system. The JHH campus has a central utility plant that is capable of supplying the NCB with chilled water and high pressure steam. Therefore, the new facility does not include any boilers or chillers. The current HVAC system is a variable air volume (VAV) with reheat coils in each VAV box. On average each VAV box serves 3 rooms that are on one zone. There are 19 air handling units with sizes ranging from 11,000 – 133,000 CFM. They are primarily located on the 6th and 7th floor. When designing a HVAC system for a healthcare facility, the engineer must consider infection control, filtration requirements, outdoor air requirements, recirculated air requirements, air change rates, etc. Hospitals have much stricter design criteria than typical buildings. A VAV system is the most common system used in invasive areas of healthcare facilities. However, non‐invasive areas such as office space, waiting rooms, cafeterias, patient rooms, etc. do not have as strict of guidelines. For this reason, these areas have the potential to use a different HVAC system, such as chilled beams that could potentially save time and money. 6.2 Problem Statement Analysis 1 showed that the top two goals for the owner, A/E, and contractor are to deliver the project on/under budget and on time. -
Energy Savings Potential of Passive Chilled Beam System As a Retrofit Option for Commercial Buildings in Different Climates Janghyun Kim Ray W
View metadata, citation and similar papers at core.ac.uk brought to you by CORE provided by Purdue E-Pubs Purdue University Purdue e-Pubs International High Performance Buildings School of Mechanical Engineering Conference 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Janghyun Kim Ray W. Herrick Laboratories, School of Mechanical Engineering, Purdue University, United States of America, [email protected] James E. Braun [email protected] Athanasios Tzempelikos [email protected] Follow this and additional works at: http://docs.lib.purdue.edu/ihpbc Kim, Janghyun; Braun, James E.; and Tzempelikos, Athanasios, "Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates" (2014). International High Performance Buildings Conference. Paper 107. http://docs.lib.purdue.edu/ihpbc/107 This document has been made available through Purdue e-Pubs, a service of the Purdue University Libraries. Please contact [email protected] for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html 3254, Page 1 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Janghyun KIM1*, James E. BRAUN1,2, Athanasios TZEMPELIKOS1,2 1Ray W. Herrick Laboratories, School of Mechanical Engineering, Purdue University, 140 S. Martin Jischke Dr., West Lafayette, IN 47907, USA [email protected], [email protected], [email protected] 2School of Civil Engineering, Purdue University, 550 Stadium Mall Dr., West Lafayette, IN 47907, USA * Corresponding Author ABSTRACT This study considers a cooling system retrofit for a commercial building in different climates by introducing a passive chilled beam system. -
Analysis of Cooling Load Calculations for Underfloor Air Distribution Systems
The 13th Asia Pacific Conference on the Built Environment: Next Gen Technology to Make Green Building Sustainable , 19-20 Nov 2015 (Thu-Fri), Hong Kong. Analysis of cooling load calculations for underfloor air distribution systems Dr. Sam C. M. Hui * and Miss ZHOU Yichun Department of Mechanical Engineering, The University of Hong Kong Pokfulam Road, Hong Kong * E-mail: [email protected] Abstract Underfloor air distribution (UFAD) systems use an underfloor supply plenum located between the structural floor slab and a raised floor system to supply conditioned air through floor diffusers or terminal units directly into the building’s occupied zone. If designed properly, they have the potential to enhance energy efficiency, indoor air quality and building life cycle performance. However, the application of UFAD system is still obstructed by the information gap in some fundamental issues, such as cooling load calculation. All the cooling load calculation methods for UFAD systems nowadays have limitations and drawbacks and most building designers are not familiar with them. This research aims to investigate the cooling loads calculation methods for UFAD systems. Fundamental principles of UFAD with different configurations are studied to analyse the effects on cooling load components. Critical evaluation is made on the key factors and issues affecting the cooling load and how they differ from the overhead air distribution systems. It is found that thermal stratification, management of solar and lighting loads, architectural design and thermal properties of structural floor slab will influence the cooling load and must be evaluated carefully. It is hoped that the findings could improve the understanding of UFAD systems and provide practical information for performing the cooling load calculations and optimising the system performance. -
Matching the Sensible Heat Ratio of Air Conditioning Equipment with the Building Load SHR
Matching the Sensible Heat Ratio of Air Conditioning Equipment with the Building Load SHR Final Report to: Airxchange November 12, 2003 Report prepared by: TIAX LLC Reference D5186 Notice: This report was commissioned by Airxchange on terms specifically limiting TIAX’s liability. Our conclusions are the results of the exercise of our best professional judgement, based in part upon materials and information provided to us by Airxchange and others. Use of this report by any third party for whatever purpose should not, and does not, absolve such third party from using due diligence in verifying the report’s contents. Any use which a third party makes of this document, or any reliance on it, or decisions to be made based on it, are the responsibility of such third party. TIAX accepts no duty of care or liability of any kind whatsoever to any such third party, and no responsibility for damages, if any, suffered by any third party as a result of decisions made, or not made, or actions taken, or not taken, based on this document. TIAX LLC Acorn Park • Cambridge, MA • 02140-2390 USA • +1 617 498 5000 www.tiax.biz Table of Contents TABLE OF CONTENTS............................................................................................................................ I LIST OF TABLES .....................................................................................................................................II LIST OF FIGURES .................................................................................................................................III -
Air Conditioning Clinic
Air Conditioning Clinic Cooling and Heating Load Estimation One of the Fundamental Series April 2011 TRG-TRC002-EN Cooling and Heating Load Estimation One of the Fundamental Series A publication of Trane, a business of Ingersoll Rand Preface Figure 1 The Trane Company believes that it is incumbent on manufacturers to serve the industry by regularly disseminating information gathered through laboratory research, testing programs, and field experience. The Trane Air Conditioning Clinic series is one means of knowledge sharing. It is intended to acquaint a nontechnical audience with various fundamental aspects of heating, ventilating, and air conditioning. We have taken special care to make the clinic as uncommercial and straightforward as possible. Illustrations of Trane products only appear in cases where they help convey the message contained in the accompanying text. This particular clinic introduces the reader to cooling and heating load estimation. It is intended to introduce the concepts of estimating building cooling and heating loads and is limited to introducing the components that make up the load on a building, the variables that affect each of these components, and simple methods used to estimate these load components. It is not intended to teach all the details or latest computerized techniques of how to calculate these loads. If you are interested in learning more about the specific techniques used for cooling and heating load estimating, this booklet includes several references in the back. © 2011 Trane. All rights reserved ii TRG-TRC002-EN Contents period one Human Comfort .................................................... 1 period two Cooling Load Estimation ................................... 8 Outdoor Design Conditions ................................... 13 Conduction through Surfaces ............................... -
Temperature & Humidity Control in Surgery Rooms
This article was published in ASHRAE Journal, June 2006. Copyright 2006 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org. Health-Care HVAC Temperature & Humidity Control In Surgery Rooms By John Murphy, Member ASHRAE requirements. This analysis focuses on cooling and dehumidification; heating ccupant comfort, infection control, and drying of mucous and humidification are not addressed. coating are some reasons why temperature and humidity Impact on HVAC System Design O The temperature and humidity control control are important in surgery rooms.1 Temperature and humid- requirements for a surgery room, along with the high air change rate, significantly ity ranges, and minimum air-change rates often are prescribed by impact the design of the HVAC system. Using a rule of thumb (such as 400 local codes or by industry-accepted guidelines (Table 1). cfm/ton [54 L/s per kW]) or a traditional temperature-only design approach often Surgeons also have preferences when in Farmington, Maine, said, “We always leads to a system that is unable to meet it comes to temperature and humidity had problems being able to satisfy the requirements. conditions. Reasons for these prefer- surgeons, who wanted the temperature at The American Institute of Architects ences range from personal comfort while 62°F to 65°F (17°C to 18°C), while the (AIA) design guidelines2 recommend 15 dressed in heavy surgery clothing to the anesthesiologists and other staff wanted air changes per hour (ACH) of supply air perception of superior procedure success higher temperatures.” 4 for a surgery room, and 20% of that sup- rates. -
GUIDE to INSULATING CHILLED WATER PIPING SYSTEMS with MINERAL FIBER PIPE INSULATION 33°F to 60°F (0.5°C to 15.6°C)
GUIDE TO INSULATING CHILLED WATER PIPING SYSTEMS WITH MINERAL FIBER PIPE INSULATION 33°F to 60°F (0.5°C to 15.6°C) First Edition Copyright ©2015 NAIMA, ALL RIGHTS RESERVED GUIDE TO INSULATING CHILLED WATER PIPING SYSTEMS WITH MINERAL FIBER PIPE INSULATION 33°F to 60°F (0.5°C to 15.6°C) First Edition, 2015 Guide to Insulating Chilled Water Systems First Edition, 2015 CONTENTS PREFACE APPENDIX A-1 I Mineral Fiber Pipe Insulation . ii I Information Sources and References . A-2 I Vapor Retarder Jacketing Systems . ii I ASHRAE - American Society of Heating, Refrigerating, I Mineral Fiber Pipe Insulation Standards . ii and Air-Conditioning Engineers, Inc. A-2 I How This Guide Was Developed . ii i I ASTM - American Society for Testing and Materials . A-2 I ICC - International Code Council, Inc. A-2 SECTION 1: PERFORMANCE CRITERIA 1-1 I The National Research Council (NRC) . A-2 I I Role of Pipe Insulation . 1-2 NAIMA - North American Insulation Manufacturers Association . A-2 I Role of Pipe Insulation for Chilled Water Systems I 33°F to 60°F (0.5°C to 15.6°C) . 1-2 NFPA - National Fire Protection Association . A-2 I I General Requirements for Mineral Fiber Pipe National Institute of Building Sciences . A-2 Insulation in Chilled Water Applications . 1-2 I National Insulation Association . A-2 I Thermal Conductivity . 1-2 I ASHRAE Standard 90.1 Minimum Pipe Insulation I Standard Specification for Mineral Fiber Pipe Thickness Recommendations . A-3 Insulations (ASTM C547) . 1-3 I IECC Minimum Pipe Insulation Thickness I Specifications, Performance & Test Standards Recommendations . -
Modified Version of High Efficiency Dehumidification System (HEDS) ESTCP Presentation EW-201344
FEDERAL UTILITY PARTNERSHIP WORKING GROUP SEMINAR November 3-4, 2015 Houston, TX Modified Version of High Efficiency Dehumidification System (HEDS) ESTCP Presentation EW-201344 Hosted by: Original Presentation by: Dahtzen Chu U.S. Army Construction Engineering Research Laboratory Scot Duncan, PE, Retrofit Originality, Inc. Omar Chamma, Trane What We’ll Discuss • This presentation will discuss several different methods that are currently utilized for Relative Humidity (RH) control in DoD facilities and some of their comparative strengths and weaknesses. • The main focus of the discussion will be on the “High Efficiency Dehumidification System” or “HEDS” that is in the process of undergoing testing thru the ESTCP process. • The appendices contain FAQ’s and Psychrometric charts for typical reheat and recuperative designs. Federal Utility Partnership Working Group November 3-4, 2015 Houston, TX Comparative Baselines at DoD and Nationally Baseline for the demonstrated technology comes in several variations. 1. Simplest and most widespread comparative baseline system consists of an AHU with a chilled water or DX refrigerant sourced cooling coil that cools the air down to between 52F and 55F. 1. Removes moisture from the air via condensation, then utilizes a heating coil, either sourced by hot water or an electric reheat coil to raise the supply air temperature to lower the Relative Humidity of the air entering the spaces, drying the spaces out. 2. AHU’s equipped with Run Around coils for reheat duty in various configurations: 1. Upstream of main Cooling Coil (CC) to downstream of main CC, 2. Exhaust air to Supply air, (does not reduce plant energy in this configuration) 3.