Understanding Chilled Beam Systems
Total Page:16
File Type:pdf, Size:1020Kb
engineers newsletter volume 38–4 • providing insights for today’s hvac system designer understanding Chilled Beam Systems Active chilled beams (ACB). An ACB Primary air system. To comply with Although chilled beam systems have been also consists of a fin-and-tube heat most building codes in the U.S., outdoor used in Europe and Australia for many exchanger contained in a housing that is air must be supplied to each space for years, they are a new concept to many in ventilation. And since a chilled beam the U.S. Those interested in learning suspended from, or recessed in, the more about these systems, as with any ceiling (Figure 1). The primary difference is (whether passive or active) typically new concept, are faced with the task of that an active chilled beam contains an does not contain a condensate drainage discerning its true strengths and integral air supply. This primary air passes system, the primary air system must weaknesses. The goal of this EN is to through nozzles, which induce air from the also maintain the dew point of the investigate the common claims about chilled beam systems. space up through the cooling coil. This indoor air below the surface induction process allows an active chilled temperature of the chilled beam to beam to provide much more cooling avoid moisture from condensing on the capacity than a passive chilled beam. For coil and dripping into the space. Overview of Chilled Beam this reason, active chilled beams are more Systems commonly used, and are the focus of this Therefore, the purpose of the primary EN. air system for active chilled beams is to: Passive chilled beams (PCB). A PCB Figure 2 includes examples of active 1) Deliver at least the required amount consists of a fin-and-tube heat chilled beams. They have pipe connections of outdoor air to each space for exchanger, contained in a housing (or and a primary air connection. Note that ventilation, and casing), that is suspended from the either two- or four-pipe designs are 2) Deliver air which is dry enough to ceiling (Figure 1). Chilled water passes available. With the two-pipe design, all offset the space latent load and through the tubes. Warm air from the zones receive either cold water or hot maintain the indoor dew point low space rises toward the ceiling, and the water. The benefit of the four-pipe design enough to avoid condensation on the air surrounding the chilled beam is is that some zones can receive cold water chilled beams, and cooled, causing it to descend back for space cooling, while other zones toward the floor, creating convective air simultaneously receive hot water for space 3) Deliver enough air to induce motion to cool the space. This allows a heating. passive chilled beam to provide space sufficient room airflow to offset the cooling without the use of a fan. space sensible cooling load. Figure 1. Passive versus active chilled beams Figure 2. Examples of active chilled beams primary air coil passive chilled beam ceiling induced air + induced air primary air coil active chilled beam perforated metal casing © 2011 Trane, a business of Ingersoll-Rand. All rights reserved l 1 Table 1 demonstrates the impact of Figure 3. Primary airflow (PA) in an active chilled beam. Closer Investigation of these three functions for an example Advantages office space. Using the default PA occupant density from The goal of this section is to assess the ASHRAE 62.1-2007, the minimum common claims about active chilled outdoor airflow required for an office beam systems. space is 0.085 cfm per square foot of floor area. Claimed advantage 1: An ACB Based on typical occupant latent loads system typically allows for smaller in an office space, if primary airflow is ductwork and smaller air-handling only 0.085 cfm/ft2, it must be SARA SA units than a variable-air-volume dehumidified to 47°F dew point to (VAV) system. Because active chilled offset the space latent load and For this same example office space, beams provide some of the space maintain the indoor dew point at 55°F the design airflow delivered by a cooling using induced airflow, primary (75ºF dry bulb and 50 percent RH). conventional VAV system would be 2 airflow delivered by the central air- However, if primary airflow is 0.90 cfm/ft . At design cooling handling unit (AHU) is typically less increased, the primary air would not conditions, primary airflow required for than the design primary airflow need to be dehumidified as much the ACBs serving this space is 60 delivered by the AHU in a conventional (Table 1). percent less than for the conventional VAV system. Therefore, ACB systems VAV system. However, this does not typically allow for smaller ductwork and Finally, based on typical sensible translate to a 60 percent reduction in AHUs than a conventional VAV system. cooling loads in an office space, fan energy use, as will be discussed catalog performance data from several later in this EN under the claimed Depending on how the ductwork is manufacturers of active chilled beams advantage 3 section. routed, smaller ducts can sometimes indicates that between 0.35 and allow for shorter floor-to-floor heights. 0.40 cfm/ft2 of primary air is required to As you can see from this example And because the primary AHUs will provide the required sensible cooling (Table 1), the primary airflow required likely be smaller, a building with chilled capacity. for space sensible cooling in the ACB beams may require less floor space for system is four times larger than the mechanical rooms. minimum outdoor airflow requirement The primary airflow delivered to an active chilled beam must be the largest Table 1. Zone-level primary airflow for an example office space of the following: Minimum outdoor airflow required 0.085 cfm/ft2 1 1) The minimum outdoor airflow (per ASHRAE 62.1-2007) (for LEED® EQ credit,1.3 x 0.085 = 0.11 cfm/ft2) required by ASHRAE Standard 62.1 Active chilled-beam system or the local building code.[1] 2 2 Primary airflow required to offset space latent load 0.085 cfm/ft (DPTPA=47ºF or WPA=47 gr/lb) 2) The dry airflow needed to offset the 2 0.11 cfm/ft (DPTPA=49ºF or WPA=51 gr/lb) indoor latent load and maintain the 2 0.36 cfm/ft (DPTPA=53ºF or WPA=60 gr/lb) space dew point low enough to avoid 2 condensation on the chilled beams. Primary airflow needed to induce sufficient room mfr A: 0.36 cfm/ft (DBTPA = 55ºF) airflow to provide sensible cooling3 2 Of course, the quantity of air needed mfr B: 0.38 cfm/ft (DBTPA = 55ºF) 2 for this purpose depends on how dry mfr C: 0.35 cfm/ft (DBTPA = 55ºF) that air is. If the primary air is Conventional VAV system delivered drier (at a lower dew point), 4 2 then less airflow is needed. Primary airflow needed to provide sensible cooling 0.90 cfm/ft (DBTPA = 55ºF) 1 For an office space, Table 6-1 of ASHRAE Standard 62.1-2007, Ventilation for Acceptable Indoor Air Quality, requires 2 2 3) The primary airflow (PA) needed to 5 cfm/p (Rp) plus 0.06 cfm/ft (Ra), and suggests a default occupant density of 5 people/1000 ft : Vbz = (5 cfm/person x 5 people/1000 ft2) + 0.06 cfm/ft2 = 0.085 cfm/ft2. induce sufficient room air (RA) to 2 For moderately active office work, the 2009 ASHRAE Handbook-Fundamentals (Table 1, Chapter 18) suggests a latent load 2 offset the design space sensible of 200 Btu/h/person. Using the same default occupant density (5 people/1000 ft ): Qlatent = (200 Btu/h/person x 5 people/ 2 2 1000 ft ) = 1.0 Btu/h/ft = 0.69 x VPA x (Wspace - WPA). Assuming a space dew point target of 55°F (64 gr/lb): VPA = 1.0 2 2 2 2 cooling load (Figure 3). If more Btu/h/ft / (0.69 x (64 - 47 gr/lb) = 0.085 cfm/ft , VPA = 1.0 Btu/h/ft / (0.69 x (64 - 51 gr/lb) = 0.11 cfm/ft , 2 2 primary air is delivered through the or VPA = 1.0 Btu/h/ft / (0.69 x (64 - 60 gr/lb) = 0.36 cfm/ft . 3 For an office space, the space sensible cooling load typically ranges from 17 to 24 Btu/h/ft2 (which equates to about 0.8 nozzles, more room air will be to 1.1 cfm/ft2 if a conventional VAV system is used). Assuming a space sensible cooling load of 19.5 Btu/h/ft2, a zone cooling setpoint of 75°F, and a primary-air dry-bulb temperature of 55°F, product literature from manufacturer A indicates induced through the chilled beam that four (4) 6-ft long, 4-pipe, 2-way discharge active chilled beams require 0.36 cfm/ft2 to offset the design space sensible coils, resulting in greater cooling cooling load. With the same type of chilled beam, manufacturers B and C require about 0.38 and 0.35 cfm/ft2 of primary air, respectively. capacity. 4 Assuming the same space sensible cooling load of 19.5 Btu/h/ft2, a zone cooling setpoint of 75°F, and a primary-air dry- 2 2 bulb temperature of 55°F: VPA = 19.5 Btu/h/ft / (1.085 x (75 - 55°F) = 0.90 cfm/ft . 2 l Trane Engineers Newsletter volume 38–4 providing insights for today’s HVAC system designer of 0.085 cfm/ft2.