<<

SAVING ENERGY IN COMMERCIAL BUILDINGS

Chilled System Assessment Guidelines

General Chilled Water System Assessment 8. energy use is primarily a function of Procedure load (part load), ECWT and LCHWT, although the energy use of the unit is primarily 1. Get copies of mechanical drawings (determine driven by part load performance. Because most chiller layout). chilled water plants are designed with constant 2. Determine type of (centrifugal, volume primary chilled water loops and condenser reciprocating, screw, etc.). water loops, in-field measurements of entering and 3. Fill out chilled water system data collection forms leaving chilled water and condenser water and sketch out the system configuration. temperature can be analyzed to develop actual 4. Get a copy of the chiller engineering specifications. chiller performance curves. In addition, chilled water 5. After the assessment, send the chiller manufacturer supply temperature and entering condenser water the worksheet to develop part load and leaving temperature are usually fixed, making it easier to chilled water temperature (LCHWT), entering measure part load performance. condenser water temperature (ECWT) performance  Chilled water and condenser water temperatures curves. should be trended and current transformers 6. Take screen shots of the chilled water system should be installed to the chillers to measure through the direct digital control (DDC) system. power output. 7. Go through the list of potential DDC points and  Chilled water and condenser water flow rates determine the points that are currently available and can be taken from curves, as described in the points that would be needed to implement sub- the pumping section. metering and continuous commissioning of the  Induced loads should be programmed into the chilled water system. Note: If a trend log hasn’t been control sequence during off-peak hours to started prior to the assessment, start trending the develop an in-situ performance curve (i.e., set following points every 30 minutes: the space temperatures to 55°F during  Chiller On/Off Status unoccupied hours to simulate full chiller load).  Chiller kilowatts (kW)  Chiller entering water temperature (EWT)  Chiller leaving water temperature (LWT)  Chilled Water Supply Temperature to Loads  Chilled Water Temperature Setpoint  Primary Chilled Water Flow Rate  Secondary Chilled Water Flow Rate to Loads  Chilled Water Return Temp from Loads  Pump Status On/Off  Pump Speed  Distribution Static Pressure  Static Pressure Setpoint  Tower On/Off Status  Tower Fan Speed  Tower EWT  Tower LWT

SAVING ENERGY IN COMMERCIAL BUILDINGS | Chilled Water System Assessment Guidelines

Note: The following retro-commissioning information Reset Controls was taken directly from PECI’s functional testing guide (www.peci.org/ftguide/) and modified for this energy  Verify proper reset parameters, which are verified assessment training. per the design sequence of operations. – The sequence may be revised to optimize This section highlights key functional testing issues for system operation relative to atmospheric chillers, including system integration with and conditions and system load. Since resetting the condensers. chilled water supply temperature is a fairly  Verify that the chiller meets the specified common control strategy, it warrants close performance requirements for temperature or part- attention. Reset strategies can impact chiller load operation, as well as specified energy capacity controls and staging. Typically, the efficiency requirements. chilled water supply temperature setpoint will – In some instances, verifying chiller capacity be reset based on some parameter(s) that and/or efficiency at peak load may be characterize(s) system load, such as valve required. However, creating a peak load position, outside air temperature, and operating condition and testing the system at position. ARI (American Institute)  Verify proper coordination between individual atmospheric conditions may be difficult, setpoints and reset strategies. especially if the system is tested during off- – The chilled water temperature reset strategy peak months. Verifying part load performance should be coordinated with the discharge air can be an easier and more cost-effective temperature (DAT) reset for each air handling solution than attempting to test peak load unit (AHU). Without this coordination, excess performance since most systems operate at equipment may be operated and energy will be part load a majority of the time. wasted. To illustrate this point, assume the chilled water setpoint is reset based on outside Staging air temperature but the AHU discharge air  Verify that isolation valves are installed and temperature setpoint is reset based on the operating correctly. variable air flow box damper position. – When an individual chiller is not operating, Without close coordination between the two the isolation valve should be closed to prevent reset strategies, it is possible that the chilled water from circulating through the unit. This water temperature could exceed the discharge configuration reduces pumping energy and air temperature setpoint. Additional chillers prevents of the chilled water and pumps may be staged ON due to the temperature due to blending of warm return increased flow, wasting significant pumping water flowing through the non-operational and chiller energy. chillers with chilled water coming from the  Verify that the chilled water supply temperature operating unit(s). reset does not adversely impact supply air  Verify that the chillers and primary CHW pumps dehumidification. stage up and down appropriately, per the sequence – Resetting the chilled water supply temperature of operations. upward will save chiller energy but may – This is especially important if multiple units prevent proper dehumidification of the supply are installed and they are unequal in size. air. This can result in discomfort and indoor Close coordination between chiller staging and air quality issues within the space(s) served. actual load will minimize energy usage. For example, it is beneficial to use a small chiller with good turn-down efficiency to meet low loads and to enable a larger chiller only when the load surpasses the cooling capacity of the smaller chiller. When this occurs, the small chiller should be turned off until load exceeds the large chiller capacity, then both chillers operate to meet the load.

SAVING ENERGY IN COMMERCIAL BUILDINGS | Chilled Water System Assessment Guidelines

 Verify proper fan control and staging, Cooling Towers especially if multiple units are installed. Regardless of whether the system is an open-circuit or – Regardless of the type of tower, optimizing the closed-circuit cooling tower, heat rejection is based on control strategy used to maintain the condenser both convective and evaporative principles. water at setpoint is important. For example, Condenser water temperature is controlled primarily by every tower system will vary the amount of air the modulation of air flow through the tower. The purpose flowing across the heat transfer elements as part of the tests is to ensure that individual components are of the control strategy. Commissioning the installed and integrated to operate on a system level per system and making sure that the particular the design intent and sequence of operations. control strategy (fan cycling, two-speed motor, or variable frequency drive [VFD]) is optimized Actuation and Sequencing will reduce system energy usage.  Verify proper stroke for control valves to ensure that  Verify proper condenser water pump staging and they open and close completely (for example, VFD control (if applicable). isolation valves and coil valves). – Many condenser systems are designed to – Control valve leakage testing should reveal no provide a constant flow of water through the detectable leakage when the valve is chiller condenser bundle, and the condenser commanded closed under normal operating water pumps should stage on and off per the conditions. design sequence. However, variable condenser  Verify proper cooling tower staging, water control, water flow is becoming increasingly accepted and fan control (including water distribution across as a way to further reduce energy consumption the fill and fan modulation) to maintain design and improve chiller performance. For example, condenser water temperature setpoint per the specific the flow rate may be modulated based on sequence of operations. maintaining a constant temperature differential – When an individual cooling tower is not across the chiller condenser. Another example operating, the isolation valve should be closed of variable flow would be a loop: As to prevent condenser water from circulating individual heat pumps cycle on and off, two- through the unit. Depending on the control way valves open and close to vary the flow of sequence, this configuration should reduce condenser water through the entire loop. pumping energy and prevent control problems. Testing will ensure that the control strategy  Verify proper control of both the spray pump and operates as designed. tower fan for evaporative and “fluid” coolers to maintain the fluid temperature setpoint per the specific sequence of operations. – Typically, the first stage of heat rejection in a closed-circuit system is to spray water over the coils and then modulate the tower fan to achieve the condenser water temperature setpoint. This control strategy may be altered during winter months to prevent operational problems or tower freezing: Some portion of the condenser water may flow through a bypass valve, rather than over the tower fill. Testing will ensure proper system performance throughout all operating conditions.  Note: A control strategy with potential to reduce cooling tower fan energy is to distribute condenser water across the entire fill (in multiple cooling tower applications) before modulating the fans to maintain water temperature. Care must be exercised to ensure that the expected performance is achieved.

SAVING ENERGY IN COMMERCIAL BUILDINGS | Chilled Water System Assessment Guidelines

Setpoints and Reset Controls  Verify the condenser water temperature setpoint reset strategy per the sequence of operations.  Verify the optimum condenser water temperature – The sequence may be revised to optimize setpoint. The condenser water temperature setpoint system operation relative to atmospheric is sometimes held constant based on the conditions, chiller energy, and tower fan performance characteristics of the chiller being (energy). For example, if the current served. atmospheric conditions will not allow the – Some chillers use less energy with lower condenser system to achieve setpoint, then the condenser water temperature, but the cooling setpoint may be raised to reduce condenser tower will expend additional energy to achieve energy in exchange for a slight increase in the lower temperature setpoint. Testing will chiller energy usage. A condenser water reset help determine the optimum setpoint to control strategy can be complicated and must minimize overall system energy usage. be tested in order to achieve design intent and proper system operation.

NREL/BR-7A20-50116 • June 2011