Chilled-Water System Design Issues- Learning from Past Mistakes

Total Page:16

File Type:pdf, Size:1020Kb

Chilled-Water System Design Issues- Learning from Past Mistakes providing insights for today’s hvac system designer Engineers Newsletter volume 43 –2 Chilled-Water Systems Design Issues Learning from past mistakes designed as variable primary flow (VPF). [9.0 kPa]. Even if the differential pressure As with anything in life, you can learn The bypass line (sized the same as the sensor is of high quality, it will be difficult to HVAC design the hard way, from supply manifold) and valve that allow select one that has the required precision to painful and costly mistakes, or the minimum chiller flow rate are located in accurately measure such a small difference easy way, from veteran engineers who can help you avoid those mistakes. the mechanical room, as are the air between design flow and minimum flow The purpose of this EN is to help new handlers. A differential pressure sensor pressure drops. engineers with the latter. across the evaporator is used to determine flow rate and to control the Solution 1: Select the proper flow bypass valve.(Figure 1). sensing technology. Flow meters are generally more expensive, require more Background See any red flags? Let’s take a look at the calibration, and must be installed per the problems that occurred on the job and manufacturer's requirements with a specific The following three cases are how to avoid making the same mistakes. amount of straight piping up- and down- composite scenarios of various chilled- stream. Despite these limitations, they're water system design issues we have Issue 1: Flow sensing device is not better suited to monitor flow for this witnessed over the years. In each accurate enough at the minimum flow system. scenario, the design issues are rate. As mentioned, the design highlighted and followed by possible evaporator pressure drop is 5 ft of head Issue 2: Loop volume does not meet the solutions. [15 kPa]. At the minimum flow rate of chiller unit control requirement. Chiller 1.2 gpm per ton [0.022 L/s per kWr], the unit controls often require a certain loop By sharing the hard-earned HVAC pressure drop will be about 3 ft of head design wisdom that comes from trial volume to maintain good chilled-water and error, we hope to shorten the learning curve for new engineers. Figure 1. Case 1: New variable primary flow (VPF) DP 200-ton helical rotary chillers: • minimum flow rate: 56ºF (13.3ºC) 40ºF (4.4ºC) Case 1: New Variable 1.2 gpm/ton Primary Flow • design pressure drop: 5 ft of head variable-speed A new system has been designed drive (VSD) using an increased system chilled- water temperature difference as recommended in the ASHRAE GreenGuide1 and by Taylor2. The 6 in pipe chillers are selected at low design VSD evaporator pressure drops (5 ft of head [15 kPa]) per chiller to minimize pump modulating AHUs in same power and energy. To reduce installed control valve equipment for minimum cost and operating costs, the system is room chiller flow © 2014 Trane, a business of Ingersoll Rand. All rights reserved. 1 temperature control and ensure that Many designers will use 4 in [10 cm] line The series chiller layout has two compressors are not cycled for this flow rate. Then select a valve to significant benefits: unnecessarily. The loop volume give proper bypass control. While not includes the fluid in the evaporator required, some consulting engineers • The upstream chiller operates at an bundle, pipes, and coils. In many close- specify a pressure independent valve for elevated temperature and increased coupled systems—for example where bypass. efficiency. Very often this the air handlers and chillers are in the compensates for any increase in pump energy. same equipment room—the loop Issue 4: Flow can't be significantly volume will not be adequate. The reduced. Chiller design flow rate is 1.5 • When chillers are piped in parallel in required loop volume varies by chiller gpm per ton [0.027 L/s per kWr] and the a VPF system, there is a significant manufacturer, chiller type, and unit minimum is 1.2 gpm per ton [0.022 L/s flow rate change in the operating control capabilities. Check with the per kWr]. This means the flow rate can chiller when the second chiller is manufacturer for each chiller specified. only be reduced 20 percent before added. When the chillers are piped in In this case, the required loop time reaching minimum. That's not much for series, there is no flow rate transition was two minutes. So the system water a system that is supposed to be variable when the second chiller is enabled. volume required is the loop time primary flow. This can greatly simplify system multiplied by the water flow: control. Solution 4: Put the chillers in series! 2 min. x 300 gpm = 600 gal It may be beneficial to pipe the chillers in [2 min. x 60 sec. per min. x 18.9 L/s = With chillers in series (Figure 2), the series if the system 2270 liters] design flow rate per chiller is about 3.0 • is designed for variable primary flow, gpm per ton [0.054 L/s per kWr], Solution 2: Increase the loop volume allowing significant turndown. Design • has a chilled-water design to the required level. If the loop evaporator pressure drop increases temperature difference of 14°F volume is close to that required, since water must flow through both [7.8°C] or larger, increasing the piping manifolds may be evaporator bundles. This increases • has two chillers, and adequate. Otherwise add a buffer tank, design pump power. However, in many preferably on the return side of the systems the flow rate is less than design • is not likely to require a future system, and on the chiller side of the flow much of the year, so the resulting expansion. bypass line. Ensure the system volume pump energy increase may be small. If the system ΔT is 10°F [5.6°C], consider with the tank meets the required loop increasing it to 14°F [7.8°C] or larger. volume. To attain smoother system To allow for servicing, engineers often control, consider making the tank a design manual bypass lines into the little larger than the absolute minimum system. requirement. The additional cost and space will likely be small. Issue 3: Oversized bypass line and Figure 2. New variable primary flow (VPF) series chillers valve do not provide adequate 56ºF (13.3ºC) 47.5ºF (8.6ºC) 40ºF (4.4ºC) control. The bypass line is the same size as the pipe manifold. Given this fact, if a large valve is installed in this line, control at the minimum flow rate Solution: may be a challenge, since initially • install flow meter opening the valve a little allows • increase loop volume by significant flow to be bypassed. VSD adding a buffer tank buffer manual bypass for servicing flow • size the bypass line for the tank meter Solution 3: Size the bypass line and largest minimum flow rate valve properly. In a variable primary flow system, size the bypass line for the largest minimum flow rate. In this case: 200 tons x 1.2 gpm per ton = 240 gpm [15 L/s] 2 Trane Engineers Newsletter volume 43–2 providing insights for today’s HVAC system designer Case 2: Conversion from Figure 3. Case 2: After value-engineered conversion to VPF Primary Secondary to DP VPF conversion plan: Variable Primary Flow 54ºF (12.2ºC) 44ºF (6.7ºC) • additional 30-tons of heat The system includes two 500-ton chillers recovery in a primary-secondary configuration. The Value engineering: owner wants to convert the system to • pumps variable primary flow (VPF) and add a small (30-ton) heat recovery chiller. - use secondary pumps, don’t move them This job is "value engineered" to: - remove primary pumps • $100 DP sensor rather than • use the existing secondary pumps magnetic flow meter (which can handle the flow and VSD VSD pressure drop requirements), control • switch out the high quality differential valve pressure sensor, which costs $1500, to a $100 sensor, and • connect the heat recovery chiller in • Add a matched pair of temperature and repeatability required to operate a parallel with the existing chillers sensors to monitor the system return- variable primary flow system. (Figure 3). water temperature and the chiller Unfortunately this seems to occur often. return-water temperature. We suggest you resist the temptation to reduce costs when value will be lost. A Issue 1: The pumps are positioned • Control the primary pump VSDs to VPF system operates on flow rate, so incorrectly to allow bypass for maintain the chiller return-water accuracy is critical. minimum flow. Water cannot flow temperature a degree or two lower from right-to-left in the bypass line, so than the system return-water minimum flow cannot be maintained. temperature. This ensures there is Solution 2: Specify and install an always a little more chilled water being accurate, reliable and repeatable flow- Solution 1: Rather than converting to produced than demanded. sensing device. It's very important that full variable primary flow, consider the flow-sensing device is accurate, • If the temperature control results in converting to variable primary/variable reliable, and repeatable. Another benefit chiller flow dropping below its secondary. As its name implies, a of a higher quality sensor is that, in minimum flow rate, increase the variable primary/variable secondary general, it requires less calibration. The pump speed to maintain the required system (Figure 4) employs variable cost of a proper flow-sensing device will minimum chiller flow rate. primary (chiller) flow as well as variable often be closer to $1000 than $100.
Recommended publications
  • Temperature & Humidity Control in Surgery Rooms
    This article was published in ASHRAE Journal, June 2006. Copyright 2006 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org. Health-Care HVAC Temperature & Humidity Control In Surgery Rooms By John Murphy, Member ASHRAE requirements. This analysis focuses on cooling and dehumidification; heating ccupant comfort, infection control, and drying of mucous and humidification are not addressed. coating are some reasons why temperature and humidity Impact on HVAC System Design O The temperature and humidity control control are important in surgery rooms.1 Temperature and humid- requirements for a surgery room, along with the high air change rate, significantly ity ranges, and minimum air-change rates often are prescribed by impact the design of the HVAC system. Using a rule of thumb (such as 400 local codes or by industry-accepted guidelines (Table 1). cfm/ton [54 L/s per kW]) or a traditional temperature-only design approach often Surgeons also have preferences when in Farmington, Maine, said, “We always leads to a system that is unable to meet it comes to temperature and humidity had problems being able to satisfy the requirements. conditions. Reasons for these prefer- surgeons, who wanted the temperature at The American Institute of Architects ences range from personal comfort while 62°F to 65°F (17°C to 18°C), while the (AIA) design guidelines2 recommend 15 dressed in heavy surgery clothing to the anesthesiologists and other staff wanted air changes per hour (ACH) of supply air perception of superior procedure success higher temperatures.” 4 for a surgery room, and 20% of that sup- rates.
    [Show full text]
  • GUIDE to INSULATING CHILLED WATER PIPING SYSTEMS with MINERAL FIBER PIPE INSULATION 33°F to 60°F (0.5°C to 15.6°C)
    GUIDE TO INSULATING CHILLED WATER PIPING SYSTEMS WITH MINERAL FIBER PIPE INSULATION 33°F to 60°F (0.5°C to 15.6°C) First Edition Copyright ©2015 NAIMA, ALL RIGHTS RESERVED GUIDE TO INSULATING CHILLED WATER PIPING SYSTEMS WITH MINERAL FIBER PIPE INSULATION 33°F to 60°F (0.5°C to 15.6°C) First Edition, 2015 Guide to Insulating Chilled Water Systems First Edition, 2015 CONTENTS PREFACE APPENDIX A-1 I Mineral Fiber Pipe Insulation . ii I Information Sources and References . A-2 I Vapor Retarder Jacketing Systems . ii I ASHRAE - American Society of Heating, Refrigerating, I Mineral Fiber Pipe Insulation Standards . ii and Air-Conditioning Engineers, Inc. A-2 I How This Guide Was Developed . ii i I ASTM - American Society for Testing and Materials . A-2 I ICC - International Code Council, Inc. A-2 SECTION 1: PERFORMANCE CRITERIA 1-1 I The National Research Council (NRC) . A-2 I I Role of Pipe Insulation . 1-2 NAIMA - North American Insulation Manufacturers Association . A-2 I Role of Pipe Insulation for Chilled Water Systems I 33°F to 60°F (0.5°C to 15.6°C) . 1-2 NFPA - National Fire Protection Association . A-2 I I General Requirements for Mineral Fiber Pipe National Institute of Building Sciences . A-2 Insulation in Chilled Water Applications . 1-2 I National Insulation Association . A-2 I Thermal Conductivity . 1-2 I ASHRAE Standard 90.1 Minimum Pipe Insulation I Standard Specification for Mineral Fiber Pipe Thickness Recommendations . A-3 Insulations (ASTM C547) . 1-3 I IECC Minimum Pipe Insulation Thickness I Specifications, Performance & Test Standards Recommendations .
    [Show full text]
  • Modified Version of High Efficiency Dehumidification System (HEDS) ESTCP Presentation EW-201344
    FEDERAL UTILITY PARTNERSHIP WORKING GROUP SEMINAR November 3-4, 2015 Houston, TX Modified Version of High Efficiency Dehumidification System (HEDS) ESTCP Presentation EW-201344 Hosted by: Original Presentation by: Dahtzen Chu U.S. Army Construction Engineering Research Laboratory Scot Duncan, PE, Retrofit Originality, Inc. Omar Chamma, Trane What We’ll Discuss • This presentation will discuss several different methods that are currently utilized for Relative Humidity (RH) control in DoD facilities and some of their comparative strengths and weaknesses. • The main focus of the discussion will be on the “High Efficiency Dehumidification System” or “HEDS” that is in the process of undergoing testing thru the ESTCP process. • The appendices contain FAQ’s and Psychrometric charts for typical reheat and recuperative designs. Federal Utility Partnership Working Group November 3-4, 2015 Houston, TX Comparative Baselines at DoD and Nationally Baseline for the demonstrated technology comes in several variations. 1. Simplest and most widespread comparative baseline system consists of an AHU with a chilled water or DX refrigerant sourced cooling coil that cools the air down to between 52F and 55F. 1. Removes moisture from the air via condensation, then utilizes a heating coil, either sourced by hot water or an electric reheat coil to raise the supply air temperature to lower the Relative Humidity of the air entering the spaces, drying the spaces out. 2. AHU’s equipped with Run Around coils for reheat duty in various configurations: 1. Upstream of main Cooling Coil (CC) to downstream of main CC, 2. Exhaust air to Supply air, (does not reduce plant energy in this configuration) 3.
    [Show full text]
  • With Chilled Water Systems Get Precise Cooling and Control for Research and Institutional Greenhouse Growing with Chilled Water Cooling Systems
    Control Cooling with Chilled Water Systems Get precise cooling and control for research and institutional greenhouse growing with chilled water cooling systems. Researchers and institutional greenhouse growers need precision, efficiency and reliability in cooling and control. Because this type of growing demands tightly controlled environments, many institutions turn to chilled water cooling. How Greenhouse Chilled Water vs. Cooling Works Evaporative Cooling Hydronics uses water as the heat-transfer medium in Many commercial greenhouses rely on evaporative cooling heating and cooling systems. Large-scale commercial and to cool air to about 10 to 20 degrees below the outside institutional buildings may include both a chilled and heated temperature. These systems lower air temperature using water loop for heating and air conditioning. While boilers mists, sprays, or wetted pads, because they introduce heat the water, chillers and cooling towers are often used water into ventilation air – increasing the relative humidity separately or together to cool the water. while lowering the air temperature. Chilled water cooling is a hydronic process that circulates While this is generally an efficient process, evaporative cooling chilled water through a loop piping system. Circulator is limited by the relative humidity of the outside air introduced pumps force the water through a heat exchanger, and a fan into the greenhouse. Under these conditions, evaporative draws warm air out and cools it as it passes over cold coils. cooling cannot provide effective space temperature control of the greenhouse under all operating conditions. Flexibility and Controlled Climate Growing The Delta T Solutions’ chilled water system uses hydronic cooling to precisely control greenhouse space temperature For flexibility, a chilled water system can be broken up into and humidity.
    [Show full text]
  • HVAC Water Systems
    HVAC Water Systems Dual Temperature Chilled Water Loops Summary Chiller energy can account for 10 to 20% of total cleanroom energy use. The majority of annual chilled water use goes to medium temperature chilled water requirements – 55°F for sensible cooling and 60 to 70°F for process cooling loads. When outside air temperatures are cool and humidity is low (i.e., no low-temperature water is needed for dehumidification), 100% of the chilled water is for medium temperature loop uses. Standard cleanroom chiller plant design provides chilled water at temperatures of 39 to 42°F. While this temperature is needed for dehumidification, the low setpoint imposes an efficiency penalty on the chillers. Typically, heat exchangers and/or mixing loops are used to convert the low temperature, energy intensive chilled water into warmer chilled water temperatures for sensible or process cooling loads. Chiller efficiency is a function of the chilled water supply temperature. All other things equal, higher chilled water temperatures result in improved chiller efficiency. For example, by dedicating a chiller in a dual chiller plant to provide chilled water at 55°F, 20 to 40% of chiller energy and peak power can be saved when compared to both chillers operating at 42°F. Table 1. Chiller Efficiency Chilled Water Supply Efficiency Temperature 42°F 0.49 kW/ton 60°F 0.31 kW/ton 1. The chiller efficiency reported is based on manufacturer’s simulated data of the same chiller. The water-cooled chiller was simulated running at 100% full load and had a condenser water supply temperature 70°F in both cases.
    [Show full text]
  • Solar Heating and Cooling System with Absorption Chiller and Latent Heat Storage - a Research Project Summary
    Available online at www.sciencedirect.com ScienceDirect Energy Procedia 48 ( 2014 ) 837 – 849 SHC 2013, International Conference on Solar Heating and Cooling for Buildings and Industry September 23-25, 2013, Freiburg, Germany Solar heating and cooling system with absorption chiller and latent heat storage - A research project summary - Martin Helm1*, Kilian Hagel1, Werner Pfeffer1, Stefan Hiebler1, Christian Schweigler1 1Bavarian Center for Applied Energy Research (ZAE Bayern), Walther-Meissner-Strasse 6,D-85748 Garching, Germany Abstract A reliable solar thermal cooling and heating system with high solar fraction and seasonal energy efficiency ratio (SEER) is preferable. By now, bulky sensible buffer tanks are used to improve the solar fraction for heating purposes. During summertime when solar heat is converted into useful cold by means of sorption chillers the waste heat dissipation to the ambient is the critical factor. If a dry cooler is installed the performance of the sorption machine suffers from high cooling water temperatures, especially on hot days. In contrast, a wet cooling tower causes expensive water treatment, formation of fog and the risk of legionella and bacterial growth. To overcome these problems a latent heat storage based on a cheap salt hydrate has been developed to support a dry cooler on hot days, whereby a constant low cooling water temperature for the sorption machine is ensured. Therefore the need of a wet cooling tower is avoided and neither make-up water nor maintenance is needed. The same storage serves as additional low temperature heat storage for heating purposes allowing optimal solar yield due to constant low storage temperatures.
    [Show full text]
  • Solar Assisted Cooling – WP3, Task 3.5 INDUSTRY FEDERATION Contract EIE/04/204/S07.38607
    EUROPEAN Key Issues for Renewable Heat in Europe (K4RES-H) SOLAR THERMAL Solar Assisted Cooling – WP3, Task 3.5 INDUSTRY FEDERATION Contract EIE/04/204/S07.38607 Solar Assisted Cooling – State of the Art – Solar Assisted Cooling – State of the Art –........................................................... 1 Executive Summary ................................................................................................. 3 Barriers to growth ................................................................................................................................. 3 Recommendations ................................................................................................................................ 4 Introduction............................................................................................................... 5 Components of a solar cooling system.................................................................. 5 Technical information on thermally driven chillers ........................................................................... 5 ABSORPTION CHILLERS .................................................................................................................. 7 ADSORPTION CHILLERS.................................................................................................................. 8 Technical information on desiccant cooling systems....................................................................... 9 SOLID DESICCANT COOLING WITH ROTATING WHEELS...........................................................
    [Show full text]
  • ADM-APN014-EN (01/05): Selecting Cooling Towers
    engineers newsletter volume 34–1 ● providing insights for today’s hvac system designer selecting cooling towers for efficiency: Tower selection 101 Range or approach? The thermodynamic realm of cooling towers can be defined by just three temperatures … from the editor … When was the last time you revised It’s tempting to rely on ARI standard your specifications or selection rating conditions for flow rates and parameters for cooling towers? Or do temperature differences when you specify unique parameters for designing chilled water systems. cooling tower selection on every job? But as valuable as these benchmarks Some HVAC designers specify 3 gpm are for verifying performance, they are of cooling water per ton of chiller unlikely to reflect optimal conditions for capacity; others specify less. Still … the “hot” water entering the cooling the entire system … especially as others base their selections on tower, the “cold” water leaving the mechanical efficiencies improve and something other than flow, such as a tower, and the design ambient wet customer requirements change. condenser ∆T of 85/95 in humid bulb of the geographic region where climates or 80/90 in less sultry locales. The same caveat applies to current the tower will be used. rules of thumb, such as a 10°F ∆T 99/85/78 95/85/78 Approach is the temperature across the cooling tower or a 90/80/71 102/83/78 difference between what is being condenser water flow rate of 3 gpm/ produced and the “power source” that ton. Basing the design of the Are your tower selection guidelines creates the product.
    [Show full text]
  • Chilled Water Pump Calculator Guide Table of Contents 1.0 Introduction
    Chilled Water Pump Calculator Guide Table of Contents 1.0 Introduction ............................................................................................................................. 2 1.1 Units .................................................................................................................................... 2 2.0 Disclaimer ............................................................................................................................... 2 3.0 Overall Chilled Water System ................................................................................................. 2 4.0 Chilled Water Pump Calculator - Inputs ............................................................................. 4 4.1 Fluid Information ............................................................................................................. 4 4.2 Pipe Information ............................................................................................................. 5 4.3 Valve & Fitting Information ............................................................................................. 6 4.4 Equipment Information ................................................................................................... 6 4.5 Pipe Expansions & Reductions Information ................................................................... 7 5.0 Chilled Water Pump Calculator - Outputs .......................................................................... 7 5.1 Fluid Velocity .................................................................................................................
    [Show full text]
  • Chiller System Design and Control
    Applications Engineering Manual Chiller System Design and Control November 2011 SYS-APM001-EN Chiller System Design and Control Susanna Hanson, applications engineer Mick Schwedler, applications manager Beth Bakkum, information designer Preface This manual examines chilled-water-system components, configurations, options, and control strategies. The goal is to provide system designers with options they can use to satisfy the building owners’ desires, but this manual is not intended to be a complete chiller-system design manual. System designers may get the most use from this manual by familiarizing themselves with chilled-water-system basics and understanding the benefits of various options. Thereafter, when a specific job will benefit from these advantages, consult appropriate sections of the manual in detail. The Engineers Newsletters that are referenced in this manual are available at: www.trane.com/commercial/library/newsletters.asp Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional. “Trane” and the Trane logo are registered trademarks, and TRACE, System Analyzer and TAP are trademarks of Trane, a business of Ingersoll-Rand. © 2009 Trane All rights reserved Chiller System Design and Control SYS-APM001-EN Contents Preface .................................................................................................. i Primary System
    [Show full text]
  • Efficient Space Humidity Control with Active Chilled Beam Systems by Kenneth J
    This article was published in ASHRAE Journal, January 2012. Copyright 2012 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org. Efficient Space Humidity Control With Active Chilled Beam Systems By Kenneth J. Loudermilk, P.E., Member ASHRAE and Darren S. Alexander, P.Eng., Member ASHRAE ver the past few years, the use of chilled beams and radiant moisture removal occurs at the central air-handling unit. Ochilled ceilings has increased rapidly in North America due to Although outdoor humidity has some effect on space latent loads, the effect the space and energy savings inherent to air-water systems. Although is minimized in tightly constructed buildings with proper building pres- these systems have been widely used in Europe for more than 20 years, sure control. The 2009 ASHRAE Hand- book—Fundamentals1 classifies build- North American climates and other building design practices often result ing tightness by the leakage rate that in higher space loads and moisture removal requirements than their results from pressurizing the building to 0.3 in. w.c. (75 Pa). Leakage rates less 2 2 European counterparts generally encounter. than 0.1 cfm/ft (0.05 L/s·m ) of outside wall area are generally considered rep- Space humidity control is essen- chilled water temperature is critical to resentative of “tight” buildings. Build- tial for the proper application of any prevent condensation. ings of “average” construction exhibit HVAC system used in humid climates, As with most HVAC systems, mois- leakage rates of around 0.3 cfm/ft2 (0.14 but it is particularly critical for these ture is removed from a mixture of out- L/s·m2) of exterior wall area while leak- air-water systems.
    [Show full text]
  • Heat Transfer Performance and Piping Strategy Study for Chilled Water
    HEAT TRANSFER PERFORMANCE AND PIPING STRATEGY STUDY FOR CHILLED WATER SYSTEMS AT LOW COOLING LOADS A Thesis by NANXI LI Submitted to the Office of Graduate Studies of Texas A&M University in partial fulfillment of the requirements for the degree of MASTER OF SCIENCE Chair of Committee, David E. Claridge Committee Members, Charles H. Culp Michael B. Pate Head of Department, Jerald A. Caton December 2012 Major Subject: Mechanical Engineering Copyright 2012 Nanxi Li ABSTRACT The temperature differential of chilled water is an important factor used for evaluating the performance of a chilled water system. A low delta-T may increase the pumping energy consumption and increase the chiller energy consumption. The system studied in this thesis is the chilled water system at the Dallas/Fort Worth International Airport (DFW Airport). This system has the problem of low delta-T under low cooling loads. When the chilled water flow is much lower than the design conditions at low cooling loads, it may lead to the laminar flow of the chilled water in the cooling coils. The main objective of this thesis is to explain the heat transfer performance of the cooling coils under low cooling loads. The water side and air side heat transfer coefficients at different water and air flow rates are calculated. The coefficients are used to analyze the heat transfer performance of the cooling coils at conditions ranging from very low loads to design conditions. The effectiveness-number of transfer units (NTU) method is utilized to analyze the cooling coil performance under different flow conditions, which also helps to obtain the cooling coil chilled water temperature differential under full load and partial load conditions.
    [Show full text]