Chilled-Water System Design Decisions

Total Page:16

File Type:pdf, Size:1020Kb

Chilled-Water System Design Decisions providing insights for today’s hvac system designer Engineers Newsletter volume 47–3 impacts of Chilled-Water System Design Decisions Primary-secondary system bypass This Engineers Newsletter walks through a number of design decisions, with Bypass line sizing sizing. The premise of a primary- secondary system is to hydraulically discussion and examples to explain how This seemingly simple decision can have and why those decisions are made. separate (decouple) the primary (chiller) significant consequences if not done flow from the secondary (system) flow. correctly. This decoupling prevents the operating • In a primary-secondary system, the While designing a chilled-water pressures of chiller pumps from impacting bypass pipe should be the same system, a myriad of decisions must the operating pressures of the system diameter as the pipe going into the be made. Experienced engineers pumps. This is accomplished by installing largest chiller. Its length should be often make these decisions a bypass line with a small pressure drop. about 8-10 pipe diameters long or "automatically" as they have in the The bypass allows water to flow in either have an equivalent pressure drop. past, based on what they have direction and is used to indicate chiller and learned from experience. Today, all • In a variable primary flow (VPF) primary pump sequencing in this system engineers likely use an internet system, the bypass line should be arrangement (Figure 1). search engine to get direction, but sized for the largest minimum flow Chillers and constant flow primary pumps when there are differing—or even rate and it will have a control valve. are enabled in pairs, making the primary conflicting—recommendations a The reasons behind this guidance follow. flow rate a step function. As system load decision must be made. and flow increase, the excess flow rate Common decisions regarding (from supply to return) in the bypass line chilled-water system designs decreases. At the point that system flow include: rate exceeds chiller flow rate, deficit flow • bypass line sizing in variable Figure 1. Primary-secondary system flow systems • dynamically varying condenser water flow primary pumps • number of chilled-water pumps to operate secondary pumps with • series chillers and power VSDs consumption chilled-water coling coils • whether to use pressure- with two-way independent control valves valves bypass line, free of restrictions, sized the same as the largest chiller’s pipe, aim for a pressure drop equivalent to a pipe that is 8-10 pipe diameters long. ©2018 Trane. All rights reserved. 1 (from return to supply) in the bypass Figure 2. Oversized bypass can allow simultaneous flow in both directions line occurs. This warm, deficit water flow increases the system supply- chiller return chiller supply water temperature and at some point water water an additional chiller and primary pump are enabled. short-circuited chiller A chiller and pump are disabled when supply water excess flow rate in the bypass line is high enough to still have excess flow after a primary pump is turned off. Therefore the maximum flow rate the bypass line ever experiences is a little short-circuited system higher than the design flow rate of the return water largest chiller. Often designers wait for 10-15 percent excess flow, to ensure system that chillers are not cycled on and off system return water supply water rapidly. Therefore the bypass pipe should be sized for 110 to115 percent • Much of that water continues to the of the largest chiller's flow rate—which Add pressure drop. A better option chillers but some of the warm water most designers simplify to the same may be to place an orifice in the line. This (due to low pressure drop in the as the pipe size going into the largest can simply be a plate with a hole in it. bypass) flows in the deficit direction chiller. This imposes a pressure drop, but allows in the bypass line (from return to the water to flow freely in either the surplus supply). or deficit direction. In a few extreme What happens if bypass sizing is cases it has been neccessary to not right? Too little or too much As a result there is simultaneous flow in completely block off the oversized/short pressure can cause issues... opposite directions because the bypass bypass pipe and install a properly sized line has become so large it functions like pipe of sufficient length to eliminate the Too small, pressure too high? An a tank! mixing condition. undersized bypass line can result in high fluid velocity, which in extreme The diluted (higher) system supply-water The best way to avoid issues in a conditions may cause pipe erosion, temperature results in more pumping primary-secondary system is to size the vibration and acoustic issues. The high energy. The short-circuited supply water bypass line properly during the design fluid velocity can also result in high mixing with return water results in process. Simply check the drawings and enough pressure drop so that flow is reduced chiller return-water temperature. ensure that the bypass line is smaller restricted through the bypass, and This can restrict the chillers’ ability to than the manifold, and the same size as may actually cause the primary and fully load. the pipe going into the largest chiller and secondary pump pressures and flow 8 to 10 equivalent pipe diameters long. If rates to affect each other. If the pipes are already installed how the pipe is less than 8 to10 pipe can the situation be improved? A diameters long, using elbows to form a Too large, pressure too low? A resolution for too low of a pressure drop "U" adds an appropriate pressure drop. benefit of an oversized bypass pipe is a is to impose a modest restriction to keep very low pressure drop, however if it's water from short-circuiting. Aim for the too low, the water may not flow as Variable-primary-flow system bypass equivalent pressure drop of a pipe that is intended. Figure 2 illustrates the issue: line sizing. Conceptually a variable- 8 to 10 pipe diameters long. primary-flow system is simpler to get • Cold water leaves the chillers and right. The valve in the bypass line only Often the first solution considered is to flows into the chiller supply opens when the system flow rate add a valve. Given that the bypass line is manifold. approaches the minimum flow rate of the oversized, it’s likely the additional valve operating chiller(s). So the bypass pipe • A portion of that cold water flows will be big and expensive. It’s also likely and valve only need to be sized for the toward the secondary pump. that at some point a well-meaning but largest minimum flow rate. Usually that's However due to the very low uninformed operator will close the valve the largest chiller's minimum flow rate. pressure drop in the bypass, some too much. Or, they might open it all the However, depending on chiller of the cold water seeks the path of way and defeat this solution. Recall that selections, the largest minimum flow least resistance and flows through the bypass line in a primary-secondary rate might not be for the largest chiller in the bypass line in the excess system should allow water to flow freely, the plant. Also consider the combined direction. in either direction, as needed. minimum flow required when two • Similarily in the return-water side, chillers are operating at part load, just warm return water flows in the before sequencing off one chiller. system return manifold. 2 Trane Engineers Newsletter volume 47-3 providing insights for today’s HVAC system designer Should we dynamically vary Table 1. Plant annualized kW/ton and percent savings compared to two-chiller base for three alternatives Condenser Condenser Tower Plant the condenser water flow? Chiller Cooling water flow Alternative water flow control annualized Savings type tower fan rate type method* kW/ton Yes, savings are available in existing (gpm/ton) systems designed between 2.5 to 3.2 gpm/ton (12 to 9.4ºF ΔT) condenser water Base VS VS 3 CF Opt 0.5462 NA flow rate. Controls complexity should be accounted for and the system needs to be Variable CW flow VS VS 3 VF Opt 0.5260 3.7% properly commissioned. Reduced design VS VS 2 CF Opt 0.5255 3.8% No, in new systems designed for 1.8 to 2.2 CW flow gpm/ton (16.6 to 13.6ºF ΔT) condenser water flow rate since they already achieve Reduced design VS VS 2 VF Opt 0.5252 3.8% almost all the savings and reduce system CW flow and variable CW flow complexity—a lot. Systems designed at these flow rates do not require varying the *Near optimal control (Opt) is minimum the sum of chiller + cooling tower fan kW at each operating point during condenser water flow rate. the year Why? Varying condenser water flow rate Example. Let’s compare the condenser • Pumps are smaller with significantly can be complicated. There are several limit water flow options. lower power conditions and setpoints to manage: It's imperative that the sum of chiller, • Chiller power rises marginally • The flow rate has to stay above the condenser water pump and cooling tower minimum flow rate as defined by the • Cooling towers become more effective fan power is considered. Less-than-optimal highest of minimum tower flow, as heat exchangers, since warmer results can happen if decisions are based minimum chiller flow, or to produce the water is sent to the cooling tower, on only one component.
Recommended publications
  • Temperature & Humidity Control in Surgery Rooms
    This article was published in ASHRAE Journal, June 2006. Copyright 2006 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org. Health-Care HVAC Temperature & Humidity Control In Surgery Rooms By John Murphy, Member ASHRAE requirements. This analysis focuses on cooling and dehumidification; heating ccupant comfort, infection control, and drying of mucous and humidification are not addressed. coating are some reasons why temperature and humidity Impact on HVAC System Design O The temperature and humidity control control are important in surgery rooms.1 Temperature and humid- requirements for a surgery room, along with the high air change rate, significantly ity ranges, and minimum air-change rates often are prescribed by impact the design of the HVAC system. Using a rule of thumb (such as 400 local codes or by industry-accepted guidelines (Table 1). cfm/ton [54 L/s per kW]) or a traditional temperature-only design approach often Surgeons also have preferences when in Farmington, Maine, said, “We always leads to a system that is unable to meet it comes to temperature and humidity had problems being able to satisfy the requirements. conditions. Reasons for these prefer- surgeons, who wanted the temperature at The American Institute of Architects ences range from personal comfort while 62°F to 65°F (17°C to 18°C), while the (AIA) design guidelines2 recommend 15 dressed in heavy surgery clothing to the anesthesiologists and other staff wanted air changes per hour (ACH) of supply air perception of superior procedure success higher temperatures.” 4 for a surgery room, and 20% of that sup- rates.
    [Show full text]
  • GUIDE to INSULATING CHILLED WATER PIPING SYSTEMS with MINERAL FIBER PIPE INSULATION 33°F to 60°F (0.5°C to 15.6°C)
    GUIDE TO INSULATING CHILLED WATER PIPING SYSTEMS WITH MINERAL FIBER PIPE INSULATION 33°F to 60°F (0.5°C to 15.6°C) First Edition Copyright ©2015 NAIMA, ALL RIGHTS RESERVED GUIDE TO INSULATING CHILLED WATER PIPING SYSTEMS WITH MINERAL FIBER PIPE INSULATION 33°F to 60°F (0.5°C to 15.6°C) First Edition, 2015 Guide to Insulating Chilled Water Systems First Edition, 2015 CONTENTS PREFACE APPENDIX A-1 I Mineral Fiber Pipe Insulation . ii I Information Sources and References . A-2 I Vapor Retarder Jacketing Systems . ii I ASHRAE - American Society of Heating, Refrigerating, I Mineral Fiber Pipe Insulation Standards . ii and Air-Conditioning Engineers, Inc. A-2 I How This Guide Was Developed . ii i I ASTM - American Society for Testing and Materials . A-2 I ICC - International Code Council, Inc. A-2 SECTION 1: PERFORMANCE CRITERIA 1-1 I The National Research Council (NRC) . A-2 I I Role of Pipe Insulation . 1-2 NAIMA - North American Insulation Manufacturers Association . A-2 I Role of Pipe Insulation for Chilled Water Systems I 33°F to 60°F (0.5°C to 15.6°C) . 1-2 NFPA - National Fire Protection Association . A-2 I I General Requirements for Mineral Fiber Pipe National Institute of Building Sciences . A-2 Insulation in Chilled Water Applications . 1-2 I National Insulation Association . A-2 I Thermal Conductivity . 1-2 I ASHRAE Standard 90.1 Minimum Pipe Insulation I Standard Specification for Mineral Fiber Pipe Thickness Recommendations . A-3 Insulations (ASTM C547) . 1-3 I IECC Minimum Pipe Insulation Thickness I Specifications, Performance & Test Standards Recommendations .
    [Show full text]
  • Modified Version of High Efficiency Dehumidification System (HEDS) ESTCP Presentation EW-201344
    FEDERAL UTILITY PARTNERSHIP WORKING GROUP SEMINAR November 3-4, 2015 Houston, TX Modified Version of High Efficiency Dehumidification System (HEDS) ESTCP Presentation EW-201344 Hosted by: Original Presentation by: Dahtzen Chu U.S. Army Construction Engineering Research Laboratory Scot Duncan, PE, Retrofit Originality, Inc. Omar Chamma, Trane What We’ll Discuss • This presentation will discuss several different methods that are currently utilized for Relative Humidity (RH) control in DoD facilities and some of their comparative strengths and weaknesses. • The main focus of the discussion will be on the “High Efficiency Dehumidification System” or “HEDS” that is in the process of undergoing testing thru the ESTCP process. • The appendices contain FAQ’s and Psychrometric charts for typical reheat and recuperative designs. Federal Utility Partnership Working Group November 3-4, 2015 Houston, TX Comparative Baselines at DoD and Nationally Baseline for the demonstrated technology comes in several variations. 1. Simplest and most widespread comparative baseline system consists of an AHU with a chilled water or DX refrigerant sourced cooling coil that cools the air down to between 52F and 55F. 1. Removes moisture from the air via condensation, then utilizes a heating coil, either sourced by hot water or an electric reheat coil to raise the supply air temperature to lower the Relative Humidity of the air entering the spaces, drying the spaces out. 2. AHU’s equipped with Run Around coils for reheat duty in various configurations: 1. Upstream of main Cooling Coil (CC) to downstream of main CC, 2. Exhaust air to Supply air, (does not reduce plant energy in this configuration) 3.
    [Show full text]
  • With Chilled Water Systems Get Precise Cooling and Control for Research and Institutional Greenhouse Growing with Chilled Water Cooling Systems
    Control Cooling with Chilled Water Systems Get precise cooling and control for research and institutional greenhouse growing with chilled water cooling systems. Researchers and institutional greenhouse growers need precision, efficiency and reliability in cooling and control. Because this type of growing demands tightly controlled environments, many institutions turn to chilled water cooling. How Greenhouse Chilled Water vs. Cooling Works Evaporative Cooling Hydronics uses water as the heat-transfer medium in Many commercial greenhouses rely on evaporative cooling heating and cooling systems. Large-scale commercial and to cool air to about 10 to 20 degrees below the outside institutional buildings may include both a chilled and heated temperature. These systems lower air temperature using water loop for heating and air conditioning. While boilers mists, sprays, or wetted pads, because they introduce heat the water, chillers and cooling towers are often used water into ventilation air – increasing the relative humidity separately or together to cool the water. while lowering the air temperature. Chilled water cooling is a hydronic process that circulates While this is generally an efficient process, evaporative cooling chilled water through a loop piping system. Circulator is limited by the relative humidity of the outside air introduced pumps force the water through a heat exchanger, and a fan into the greenhouse. Under these conditions, evaporative draws warm air out and cools it as it passes over cold coils. cooling cannot provide effective space temperature control of the greenhouse under all operating conditions. Flexibility and Controlled Climate Growing The Delta T Solutions’ chilled water system uses hydronic cooling to precisely control greenhouse space temperature For flexibility, a chilled water system can be broken up into and humidity.
    [Show full text]
  • HVAC Water Systems
    HVAC Water Systems Dual Temperature Chilled Water Loops Summary Chiller energy can account for 10 to 20% of total cleanroom energy use. The majority of annual chilled water use goes to medium temperature chilled water requirements – 55°F for sensible cooling and 60 to 70°F for process cooling loads. When outside air temperatures are cool and humidity is low (i.e., no low-temperature water is needed for dehumidification), 100% of the chilled water is for medium temperature loop uses. Standard cleanroom chiller plant design provides chilled water at temperatures of 39 to 42°F. While this temperature is needed for dehumidification, the low setpoint imposes an efficiency penalty on the chillers. Typically, heat exchangers and/or mixing loops are used to convert the low temperature, energy intensive chilled water into warmer chilled water temperatures for sensible or process cooling loads. Chiller efficiency is a function of the chilled water supply temperature. All other things equal, higher chilled water temperatures result in improved chiller efficiency. For example, by dedicating a chiller in a dual chiller plant to provide chilled water at 55°F, 20 to 40% of chiller energy and peak power can be saved when compared to both chillers operating at 42°F. Table 1. Chiller Efficiency Chilled Water Supply Efficiency Temperature 42°F 0.49 kW/ton 60°F 0.31 kW/ton 1. The chiller efficiency reported is based on manufacturer’s simulated data of the same chiller. The water-cooled chiller was simulated running at 100% full load and had a condenser water supply temperature 70°F in both cases.
    [Show full text]
  • Solar Heating and Cooling System with Absorption Chiller and Latent Heat Storage - a Research Project Summary
    Available online at www.sciencedirect.com ScienceDirect Energy Procedia 48 ( 2014 ) 837 – 849 SHC 2013, International Conference on Solar Heating and Cooling for Buildings and Industry September 23-25, 2013, Freiburg, Germany Solar heating and cooling system with absorption chiller and latent heat storage - A research project summary - Martin Helm1*, Kilian Hagel1, Werner Pfeffer1, Stefan Hiebler1, Christian Schweigler1 1Bavarian Center for Applied Energy Research (ZAE Bayern), Walther-Meissner-Strasse 6,D-85748 Garching, Germany Abstract A reliable solar thermal cooling and heating system with high solar fraction and seasonal energy efficiency ratio (SEER) is preferable. By now, bulky sensible buffer tanks are used to improve the solar fraction for heating purposes. During summertime when solar heat is converted into useful cold by means of sorption chillers the waste heat dissipation to the ambient is the critical factor. If a dry cooler is installed the performance of the sorption machine suffers from high cooling water temperatures, especially on hot days. In contrast, a wet cooling tower causes expensive water treatment, formation of fog and the risk of legionella and bacterial growth. To overcome these problems a latent heat storage based on a cheap salt hydrate has been developed to support a dry cooler on hot days, whereby a constant low cooling water temperature for the sorption machine is ensured. Therefore the need of a wet cooling tower is avoided and neither make-up water nor maintenance is needed. The same storage serves as additional low temperature heat storage for heating purposes allowing optimal solar yield due to constant low storage temperatures.
    [Show full text]
  • Solar Assisted Cooling – WP3, Task 3.5 INDUSTRY FEDERATION Contract EIE/04/204/S07.38607
    EUROPEAN Key Issues for Renewable Heat in Europe (K4RES-H) SOLAR THERMAL Solar Assisted Cooling – WP3, Task 3.5 INDUSTRY FEDERATION Contract EIE/04/204/S07.38607 Solar Assisted Cooling – State of the Art – Solar Assisted Cooling – State of the Art –........................................................... 1 Executive Summary ................................................................................................. 3 Barriers to growth ................................................................................................................................. 3 Recommendations ................................................................................................................................ 4 Introduction............................................................................................................... 5 Components of a solar cooling system.................................................................. 5 Technical information on thermally driven chillers ........................................................................... 5 ABSORPTION CHILLERS .................................................................................................................. 7 ADSORPTION CHILLERS.................................................................................................................. 8 Technical information on desiccant cooling systems....................................................................... 9 SOLID DESICCANT COOLING WITH ROTATING WHEELS...........................................................
    [Show full text]
  • ADM-APN014-EN (01/05): Selecting Cooling Towers
    engineers newsletter volume 34–1 ● providing insights for today’s hvac system designer selecting cooling towers for efficiency: Tower selection 101 Range or approach? The thermodynamic realm of cooling towers can be defined by just three temperatures … from the editor … When was the last time you revised It’s tempting to rely on ARI standard your specifications or selection rating conditions for flow rates and parameters for cooling towers? Or do temperature differences when you specify unique parameters for designing chilled water systems. cooling tower selection on every job? But as valuable as these benchmarks Some HVAC designers specify 3 gpm are for verifying performance, they are of cooling water per ton of chiller unlikely to reflect optimal conditions for capacity; others specify less. Still … the “hot” water entering the cooling the entire system … especially as others base their selections on tower, the “cold” water leaving the mechanical efficiencies improve and something other than flow, such as a tower, and the design ambient wet customer requirements change. condenser ∆T of 85/95 in humid bulb of the geographic region where climates or 80/90 in less sultry locales. The same caveat applies to current the tower will be used. rules of thumb, such as a 10°F ∆T 99/85/78 95/85/78 Approach is the temperature across the cooling tower or a 90/80/71 102/83/78 difference between what is being condenser water flow rate of 3 gpm/ produced and the “power source” that ton. Basing the design of the Are your tower selection guidelines creates the product.
    [Show full text]
  • Chilled Water Pump Calculator Guide Table of Contents 1.0 Introduction
    Chilled Water Pump Calculator Guide Table of Contents 1.0 Introduction ............................................................................................................................. 2 1.1 Units .................................................................................................................................... 2 2.0 Disclaimer ............................................................................................................................... 2 3.0 Overall Chilled Water System ................................................................................................. 2 4.0 Chilled Water Pump Calculator - Inputs ............................................................................. 4 4.1 Fluid Information ............................................................................................................. 4 4.2 Pipe Information ............................................................................................................. 5 4.3 Valve & Fitting Information ............................................................................................. 6 4.4 Equipment Information ................................................................................................... 6 4.5 Pipe Expansions & Reductions Information ................................................................... 7 5.0 Chilled Water Pump Calculator - Outputs .......................................................................... 7 5.1 Fluid Velocity .................................................................................................................
    [Show full text]
  • Chiller System Design and Control
    Applications Engineering Manual Chiller System Design and Control November 2011 SYS-APM001-EN Chiller System Design and Control Susanna Hanson, applications engineer Mick Schwedler, applications manager Beth Bakkum, information designer Preface This manual examines chilled-water-system components, configurations, options, and control strategies. The goal is to provide system designers with options they can use to satisfy the building owners’ desires, but this manual is not intended to be a complete chiller-system design manual. System designers may get the most use from this manual by familiarizing themselves with chilled-water-system basics and understanding the benefits of various options. Thereafter, when a specific job will benefit from these advantages, consult appropriate sections of the manual in detail. The Engineers Newsletters that are referenced in this manual are available at: www.trane.com/commercial/library/newsletters.asp Trane, in proposing these system design and application concepts, assumes no responsibility for the performance or desirability of any resulting system design. Design of the HVAC system is the prerogative and responsibility of the engineering professional. “Trane” and the Trane logo are registered trademarks, and TRACE, System Analyzer and TAP are trademarks of Trane, a business of Ingersoll-Rand. © 2009 Trane All rights reserved Chiller System Design and Control SYS-APM001-EN Contents Preface .................................................................................................. i Primary System
    [Show full text]
  • Efficient Space Humidity Control with Active Chilled Beam Systems by Kenneth J
    This article was published in ASHRAE Journal, January 2012. Copyright 2012 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org. Efficient Space Humidity Control With Active Chilled Beam Systems By Kenneth J. Loudermilk, P.E., Member ASHRAE and Darren S. Alexander, P.Eng., Member ASHRAE ver the past few years, the use of chilled beams and radiant moisture removal occurs at the central air-handling unit. Ochilled ceilings has increased rapidly in North America due to Although outdoor humidity has some effect on space latent loads, the effect the space and energy savings inherent to air-water systems. Although is minimized in tightly constructed buildings with proper building pres- these systems have been widely used in Europe for more than 20 years, sure control. The 2009 ASHRAE Hand- book—Fundamentals1 classifies build- North American climates and other building design practices often result ing tightness by the leakage rate that in higher space loads and moisture removal requirements than their results from pressurizing the building to 0.3 in. w.c. (75 Pa). Leakage rates less 2 2 European counterparts generally encounter. than 0.1 cfm/ft (0.05 L/s·m ) of outside wall area are generally considered rep- Space humidity control is essen- chilled water temperature is critical to resentative of “tight” buildings. Build- tial for the proper application of any prevent condensation. ings of “average” construction exhibit HVAC system used in humid climates, As with most HVAC systems, mois- leakage rates of around 0.3 cfm/ft2 (0.14 but it is particularly critical for these ture is removed from a mixture of out- L/s·m2) of exterior wall area while leak- air-water systems.
    [Show full text]
  • Heat Transfer Performance and Piping Strategy Study for Chilled Water
    HEAT TRANSFER PERFORMANCE AND PIPING STRATEGY STUDY FOR CHILLED WATER SYSTEMS AT LOW COOLING LOADS A Thesis by NANXI LI Submitted to the Office of Graduate Studies of Texas A&M University in partial fulfillment of the requirements for the degree of MASTER OF SCIENCE Chair of Committee, David E. Claridge Committee Members, Charles H. Culp Michael B. Pate Head of Department, Jerald A. Caton December 2012 Major Subject: Mechanical Engineering Copyright 2012 Nanxi Li ABSTRACT The temperature differential of chilled water is an important factor used for evaluating the performance of a chilled water system. A low delta-T may increase the pumping energy consumption and increase the chiller energy consumption. The system studied in this thesis is the chilled water system at the Dallas/Fort Worth International Airport (DFW Airport). This system has the problem of low delta-T under low cooling loads. When the chilled water flow is much lower than the design conditions at low cooling loads, it may lead to the laminar flow of the chilled water in the cooling coils. The main objective of this thesis is to explain the heat transfer performance of the cooling coils under low cooling loads. The water side and air side heat transfer coefficients at different water and air flow rates are calculated. The coefficients are used to analyze the heat transfer performance of the cooling coils at conditions ranging from very low loads to design conditions. The effectiveness-number of transfer units (NTU) method is utilized to analyze the cooling coil performance under different flow conditions, which also helps to obtain the cooling coil chilled water temperature differential under full load and partial load conditions.
    [Show full text]