Galvanic corrosion When different come into contact with each other, one is likely to corrode faster if they get wet, but there are ways to minimise or even prevent corrosion. By Zhengwei Li, BRANZ Corrosion Scientist

alvanic corrosion, sometimes referred to as bimetallic corrosion or dissimilar corrosion, can be defined as quick deterioration due to G (thin water film) corroded area contact between dissimilar metals. This type of corrosion is commonly seen when two metals are in electrical contact while moisture (or any conducting corrosive electrolyte) is present. The result is enhanced and aggressive corrosion of one metal at the joint area together with partial or complete protection of the other metal (see metal 1 metal 2 Figure 1). Rusting corrugated roofing is a prime example. When the galvanised coating is Figure 1: Schematic showing galvanic corrosion. partially damaged, both zinc and the underlying steel are exposed to the aggressive environment. The zinc is attacked while the underlying steel usually involves a direct metal-to-metal the corrosion effect could be. The less noble is protected. Only when zinc is consumed will contact, e.g. rivets, bolts, spot welds metal is the , or the one that will corrode. the steel rust in earnest. Another example is ❚❚ sustained cathodic reaction: in most For example, if is in contact with aluminium alloys. When they are joined to steel practical situations, this is the consumption AISI 304 , the potential difference or and exposed to a marine environment, of dissolved oxygen on the more noble (less would be around 450 mV and the aluminium aluminium alloys corrode faster than they do active) of the two metals. will corrode. when exposed alone. A criterion setting a maximum value of 250 The corrosion process mV difference in corrosion potential in sea water Why one material will corrode Various factors are important for enhancing the has sometimes been used as the safe limit for faster than another corrosion rate of one metal when it is in direct elimination of galvanic corrosion. However, the Different materials have different electrical electronic contact with another. magnitude of the potential difference alone is potentials. This difference is the main driving Corrosion potentials under different not sufficient and sometimes has little or no force for galvanic corrosion. In the presence environmental conditions technical significance. Metals with a potential of an electrolyte, such as a wet industrial The ‘corrosion potentials’ of any two metals in difference of only 50 mV have shown galvanic atmosphere, an electrochemical cell can be the environment will determine the direction of corrosion problems, whereas other metals with established between two metals if the difference the transfer of electrons. Electrons will transfer a potential difference of 800 mV have been in potential between them is enough to drive from the metal with a negative potential (less successfully coupled together. an electric current flow from one material noble) to the metal with a more positive potential However, the can be misleading to another. (noble). The standard electrode potentials, as when other environments are involved. It is more For galvanic corrosion to occur, certain basic given in the electromotive force (EMF) series realistic to determine the galvanic corrosion risk requirements are necessary such as elec­tro­ of metals, are often irrelevant in predicting by measuring the actual corrosion potentials lytes, noble and less noble metals and electron the galvanic effect of coupling two metals in of the metals under whatever environmental conductors. By eliminating any one of these service. conditions prevail. factors, corrosion can be prevented. The galvanic series in which metals are listed The ratio of metal areas in electrical Other conditions necessary for galvanic according to their corrosion potentials in sea contact corrosion include: water is more helpful (see Figure 2). The farther The intensity of galvanic corrosion is related to ❚❚ electrical connection: in a structure, this apart the metals are in the series, the greater the ratio of areas of the metals in electrical

BUILD August/September 2009 49 Noble (least (active) contact. When a with a large area is compatible with zinc or aluminium coated coupled to a less noble metal with a small area, products. Copper is not compatible with mild (0.2 0.29V) galvanic action will cause much more severe steel, galvanised steel, zinc/aluminium coated corrosion of the less noble metal. steel steel or prepainted roofing steel. Even when two (Pt) (0.22 0.25V) or aluminium bolts in stainless steel members incompatible metals are not in direct contact, should be avoided because the ratio of the area it is still possible for metals to be damaged AISI 316 (Passive) (–0.1 0V) of the stainless steel to the carbon steel is large by bimetallic cells set up indirectly. Therefore, and the bolts will be subject to enhanced attack; water run-off from copper to aluminium or zinc AISI 304 (Passive) (–0.1 –0.05V) similarly for aluminium or zinc-plated steel rivets should be avoided, as traces of dissolved copper used in copper sheet. would set up multiple small bimetallic cells on (Pb) (–0.25 –0.19V) The reverse situation, where the noble metal the aluminium or zinc surface. has a small area, produces little galvanic current. We recommend that designers use only one AISI 430 (Passive) (–0.28 –0.2V) Thus, stainless steel fasteners in aluminium material in a construction or choose metal plates or sheets are normally considered combinations in which the constituents are as AISI 410 (Passive) (–0.35 –0.26V) safe. In practice, the anode (less noble metal) close as possible in the corresponding galvanic should be designed to have a larger area than series. If there is contact between dissimilar (–0.29 –0.26V) the (noble metal) to decrease risk of metals, it is important to avoid large area ratios corrosion, even under extreme conditions (e.g. of noble metal to less noble metal. Copper (–0.37 –0.3V) no insulation between the metals). To eliminate a dissimilar metal junction, a (–0.4 –0.3V) Dissimilar metals that are in close physical transition piece can be used. This consists of the proximity usually suffer greater galvanic effects same metals as in the galvanic couple bonded Mild steel (–0.63 –0.57V) than those farther apart, because a long together in a laminar structure. The transition distance increases the resistance of the current piece is inserted between the members of the Aluminium (Al) (–1.0 –0.76V) path in the electrolyte and the external circuit. couple so that the similar metals are in contact Electrolyte (see Figure 3). The dissimilar metal junction where Zinc (Zn) (–1.03 –0.98V) Increased electrical conductivity of the electrolyte electrolyte may present is then eliminated. often increases the severity of galvanic corrosion. Electrical isolation (Mg) (–1.63 –1.6V) In practice, high conductivity is caused by the The physical contact between the dissimilar metals presence of aggressive such as chloride, can be isolated to break the conducting path. This Figure 2: Galvanic series of common metals and alloys in sea or by acid or alkali. So galvanic corrosion is can be easily achieved by using non-conductive water – V versus SCE (saturated calomel electrode). seldom a problem in pure water. plastic or rubber gaskets and nylon or Teflon The electrolyte in atmospheric galvanic washers and bushes and polymeric coatings at the corrosion contains soluble contaminants such joint area. This approach is popular in the building aluminium plate as acidic fumes from industrial atmospheres and construction industry for isolation between and chloride ions from marine atmospheres. fasteners and roofing steel sheets. Because such an electrolyte has a high electric Another example is insulating domestic

aluminium resistance parallel to the surface, it is rare for galvanised steel hot water heaters and tanks steel corrosion to extend much further than 12–25 from black or copper plumbing. The design mm from the bimetallic junction. and maintenance must ensure that the insulator is not bridged by accumulated debris, and water- Preventing galvanic corrosion run-off issues need to be kept in mind. In practice, it is possible to reduce or eliminate Painting galvanic corrosion damage between widely used Painting the galvanic couple can reduce the dissimilar metals in a particular environment corrosion risk and rate by excluding water from clad metal transition piece by altering one or more of the key factors the detail. Always paint both the anodic (less mentioned above. noble) and cathodic (noble) members of the couple to keep the exposed cathodic to anodic Materials selection – the fewer steel plate the better area ratio as small as possible. If only one Contact between austenitic stainless and member of the couple can be painted, the noble

Figure 3: Transition piece inserted between dissimilar zinc or aluminium may result in some additional metal should receive this treatment. metal plates. corrosion of the latter two metals. Lead is not

50 BUILD August/September 2009