BI-DIRECTIONAL FLOW RATE INDICATOR / TOTALIZER WITH ANALOG, PULSE SIGNAL AND FLOW DIRECTION OUTPUTS

Advantages Signal output • Robust IP67 (NEMA4X) field enclosure. • (0)4 - 20mA / 0 - 10V DC according to positive It is so rugged, you can even stand on it! and/or negative flow rate. • Intrinsically Safe available - ATEX and IECEx • Scaled pulse output according to accumulated total approval for gas and dust applications. - count up and count down. • Programming can be done by your own crew, with • Switch output related to flow direction and the sensible menu-driven structure, saving cost and accumulated total. irritation. Know one, know them all! • Very diverse mounting possibilities: walls, pipes, Signal input panels or directly onto outdoor sensors! Flow • Ability to process all types of flow meter signals: Features Reed-switch, NAMUR, NPN/PNP pulse, Sine wave • Detects flow direction with quadrature signal inputs. (coil), Active pulse signals. • Displays positive / negative flow rate ref. flow direction. Applications • Displays forward & reverse total and accumulated • The F-Series is your first and safest choice for field total count up and count down ref. flow direction. mount indicators. Especially in harsh weather • Large 17mm (0.67") digits for flow rate or total. conditions like rain, snow, salty atmosphers and • Selectable on-screen engineering units; volumetric temperatures between -40°C up to +80°C (-40°F up or mass. to 176°F) for safe and hazardous area applications! • Explosion/flame proof II 2 GD EEx d IIB T5. • Bi-directional flow measurement applications like • Full Modbus communication RS232/485/TTL. loading / unloading through the same flow meter • Loop or battery powered, 8 - 24V AC/DC or or where undesired backflow disturbs a correct 115 - 230V AC power supply. totalisation. For DIN panel mount indicators, check • Sensor supply 3.2 / 8.2 / 12 / 24V DC. our D-Series.

1 DATASHEET F115 - BI-DIRECTIONALTOTALIZER INDICATOR / RATE FLOW General information Signal input Introduction The F115 accepts most pulse input signals for The F115 has been developed for applications where volumetric flow or mass flow measurement. To detect the direction of flow is an issue. Applications can be the direction of flow, it is required to offer two signals found by loading and unloading of ships where one 90° or 270° out of phase. The input signal types can bi-directional flow meter is used. An other application be selected for both inputs in the configuration menu is the correction of back-flow due to shocks in a without having to adjust any sensitive mechanical pipeline caused by piston pumps or valve behavior. It dip-switches or jumpers. Different types of sensors is required to offer two pulse signals from the flow and K-factors are allowed for both inputs. meter which are 90° or 270° degrees out of phase. A wide selection of options further enhances this Communication models capabilities. All process data and settings can be read and modified manually or through the Modbus Display communication link (RS232 / RS485). The display has large 17mm (0.67”) and 8mm (0.31”) Full Modbus functionality remains available for the digits which can be set to show flow rate and totals. Intrinsically Safe version (TTL). On-screen engineering units are easily configured from a comprehensive menu. In case of a reverse Hazardous areas flow, the flow rate will be displayed as a negative This model has been ATEX and IECEx certified value. The totalizers will count down. Intrinsically Safe for gas and dust applications, with an allowed ambient temperature of Configuration -40°C to +70°C (-40°F to +158°F). All configuration settings are accessed via a simple A flame proof enclosure with ATEX certification operator menu which can be password protected. offers the rating II 2 GD EEx d IIB T5. Each setting is clearly indicated with an alpha- numerical description, which avoides confusing Enclosures abbreviations and baffling codes. Once familiar with Various types of enclosures can be selected, all ATEX one F-series product, you will be able to program all and IECEx approved. As standard the F115 is supplied models in the series without a manual. All settings in an GRP panel mount enclosure, which can be and totals are safely stored in EEPROM memory in the converted to an GRP field mount enclosure. Most event of sudden power failure. popular is our rugged aluminum field mount enclosu- re with IP67 / NEMA 4X rating. Both European or U.S. Analog output signal cable gland entry threads are available. The positive and / or negative flow rate is re-trans- mitted with the (0)4 - 20mA or 0 - 10V DC output Overview application F115 signal. The output signal is updated eight times per second. The output value is user defined in relation to the flow rate, e.g. 4mA equals the minimum flow rate (not negative) and 20mA equals to + or -200L/Hr. The output signal can be passive, active or isolated where Pulse output Negative total output Analog output Communication link the passive output type will loop power the F115.

Pulse output The scaleable pulse output, reflects the count on the accumulated display. Moreover, if the transmitted pulse reflects a count-down situation due to reverse 90º or 270º flow, the second output will be switched. The pulse out of phase length is user defined from 0.001 second up to 9.999 seconds. The maximum output frequency is 500Hz. The output signal can be a passive NPN, active PNP or an isolated electro-mechanical relay.

2 F115 Dimensions enclosures Terminal connections Aluminum & GRP panel mount enclosure 31 YZ 30 31 mm 29 mm (1.22") (1.14") 130 mm (5.12") B B 29

115 (4.53") A A 28 RXD TXD RXD TXD COMMUNICATION 27 DTR DTR +12V +12V 26 120 mm (4.72") 98 (3.86") CB: RS232 CH: RS485 - 2 wire CI: RS485 - 4 wire Intrinsically Safe TTL CT: 25

HB & HC enclosures panel cut-out 24 23 Aluminum & GRP field / wall mount enclosures 22

130 mm (5.12") Ø 7mm (0.27") Ø 7mm (0.27") 21 20 19 120 mm (4.72") 18 60 mm (2.36")

75 mm (2.95") 112 mm (4.40") 17 Aluminum GRP

30mm 30mm 15 16 22,50 mm HD

PG9 M20 x 1,5 PG9 14 + + 1.18" 1.18" 30mm 30mm 13 + + - - 0.9" 22,50 mm

HL HE 12 FLOW METER INPUT B FLOW METER INPUT P: coil P: reed switch / NPN P: PNP P: namur P: active signal 1 1/2"NPT /2"NPT Ø16Ø20 Ø16

30mm 30mm 11 + + 10 + + - - 22,50 mm HM HF 22,50 mm ( 0.9") 9

M16 x 1,5 7 A FLOW METER INPUT M20 x 1,5 M16 x 1,5 Ø22 ( /8") P: coil P: reed switch / NPN P: PNP P: namur P: active signal

25mm 25mm + + + + + + I I I I I U 22,50 mm 22,50 mm 78 I

HN HG - - U I I I I AA: 4 - 20mA AB: 0 - 20mA AF: 4 - 20mA AI: 4 - 20mA AP: 4 - 20mA AU: 0 - 10V ANALOG OUTPUT M20 x 1,5 Ø20 Ø20

12mm 12mm 25mm 25mm = + + 17 mm 56 = 22,50 mm

HH OA: active 24V DC passive trans. OT: OR: mech. relay HO R1 PULSE OUTPUT 14 mm

M20 x 1,5 M20 x 1,5 24mm 24mm Ø12 36mm 36mm = 12mm 12mm + + 30mm (1.18") 30mm (1.18") NEGATIVE 34 17 mm = OA: active 24V DC passive trans. OT: OR: mech. relay HP HJ R2 OUTPUT TOTAL 22,50 mm ( 0.9") 14 mm 24mm 24mm 6 x M12 7 7 7 2 Ø22 ( / ") Ø22 ( / ") Ø22 ( / ") + 36mm 36mm 8 8 8 1 + + + + 0.9" - - - - GND PD: 8 - 24V AC PD: 8 - 24V PD: 8 - 24V DC PD - XI: 16 30V DC PF: 24V AC PF: 24V DC AC - 230V PM: 115 (With PD / PF PM terminals 1 2 are not available, backlight power supply is integrated.) PX-ZB: Backlight supply PX: 8 - 30V DC AP Output loop powered unit with type (terminals GND - 1 2 are not available) PB / PC: battery powered Internal long life Lithium battery (terminals GND - 1 2 are not available) HT HK POWER REQUIREMENTS

1/2"NPT Flat bottom, no holes available.

1.18" 1.18" Display example - 90 x 40mm (3.5” x 1.6”)

0.9" HU

1 1 /2"NPT 1/2"NPT /2"NPT

15mm 15mm 15 mm HV 16 mm

38mm 4 x M20 x 1.5

HZ

F115 3 Typical wiring diagram F115-P-(AP)-CH-(OT)-PB Typical wiring diagram F115-P-AP-CH-OT-PX

TERMINAL CONNECTORS BATTERY POWERED TERMINAL CONNECTORS OUTPUT LOOP POWERED F100 - series F100 - series

Modbus communication type CH: RS485 - 2 wire Modbus communication type CH: RS485 - 2 wire

B B 29 29

A A 28 2827

Common ground Common ground 26 26

Supply * Supply * 14 14 Signal Flow meter input Signal Flow meter input type: P type: P

type of signal pulse type of signal pulse Circuit depends on Circuit depends on Common ground Common ground 12 13 12 13

Supply * Supply * 11 11 Signal Flow meter input Signal Flow meter input type: P type: P

type of signal pulse type of signal pulse Circuit depends on Circuit depends on

Common ground 9 10 Common ground 9 10 Analog output type AP: passive 4 - 20mA (loop powered) +

8 Analog output type AP: 8 8 - 30V DC (not used in this example) e.g. indicator

Common ground Common ground - 7 7 e.g. counter

Pulse output type OT: 65 65 123456 passive transistor Pulse output type OT: (not used in this example) passive transistor Common ground Common ground negative total value

Switch output type OT: 43 43 passive transistor Switch output type OT: (not used in this example) passive transistor Common ground Common ground

Please note: AP may be used in combination with the battery!

AP will power the unit (output loop powered); the battery will be disabled automatically untill power is disconnected).

*Supply voltage: 1.2 / 3.2V DC to sensor *Supply voltage: 1.2 / 3.2V DC to sensor

4 F115 Typical wiring diagram F115-P-AA-CB-OA-PD Typical wiring diagram F115-P-AI-CI-OR-PM

TERMINAL CONNECTORS 24V AC / DC POWER SUPPLY TERMINAL CONNECTORS 115 - 230V AC POWER SUPPLY F100 - series F100 - series

Z 3130

Y Modbus communication type CB: RS232 Modbus communication type CI: RS485 - 4 wire

TXD B 29 29

A

RXD 2827 28

DTR 12V Common ground Common ground 26 26

Supply * Supply * 14 14 Signal Flow meter input Signal Flow meter input type: P type: P

type of signal pulse type of signal pulse Circuit depends on Circuit depends on Common ground Common ground 12 13 12 13

Supply * Supply * 11 11 Signal Flow meter input Signal Flow meter input type: P type: P

type of signal pulse type of signal pulse Circuit depends on Circuit depends on

Common ground 9 10 Common ground 9 10

e.g. indicator + +

8 Analog output type AA: 8 Analog output type AI: - 8 - 30V DC e.g. indicator active 4 - 20mA passive isolated 4 - 20mA

Common ground - 7 7

e.g. counter +

65 123456 Pulse output type OA: 65 123456 - e.g. counter active 24V DC signal Common ground Switch output type OR:

negative total value mechanic relay +

43 Switch output type OA: 43 - active 24V DC signal negative total value Common ground

N 2 2 Power supply type PM: Main supply Main supply

8 - 24V AC 115 - 230V AC + L1 1 Power supply type PD: 1

8 - 24V AC / DC 8 - 24V DC -

Common ground 0 Common ground 0 Earth Protective earth

*Supply voltage: 1.2 / 3.2 / 8.2 / 12 / 24V DC to sensor *Supply voltage: 1.2 / 3.2 / 8.2 / 12 / 24V DC to sensor

F115 5 Hazardous area applications Configuration example IIB / IIIC and IIC The F115-XI has been certified according ATEX F115-P-(AP)-(CT)-(OT)-PC-XI - Battery powered unit and IECEx by DEKRA for use in Intrinsically Safe applications with an ambient temperature of

HAZARDOUS AREA SAFE AREA -40°C to +70°C (-40°F to +158°F). TERMINAL CONNECTORS F100 - series • The ATEX markings for gas and dust applications are: II 1 G Ex ia IIB/IIC T4 Modbus communication type CT: TTL II 1 D Ex ia IIIC T100 °C Da IP6X. Possible for battery powered applications TXD • The IECEx markings for gas and dust 29 (not used in this example). RXD Please note: communciation type CT 28 applications are: Ex ia IIC/IIB T4 Ga and is not allowed in IIC applications.

DTR 27 Ex ia IIIC T100 °C Da IP6X. +12V Common ground

Besides the two I.S. power supply for the pulse 26 and flow-direction outputs, it is allowed to connect up to four I.S. power supplies in IIB/IIIC applications or one in IIC applications. Consult the certificate for the maximum input and output values of the circuits. Full functionality of the F115 remains available, including 4 - 20mA output, pulse and flow-direction outputs and Modbus communication (type CT). Power supply type PD-XI offers a 8.2V sensor supply e.g. for one Namur sensor. A flame proof enclosure with rating ATEX II 2 GD EEx d IIB T5 is available as well. Please contact your supplier for further details.

Certificate of conformity KEMA 03ATEX1074 X Supply * • IECEx DEK 11.0042X Signal Flow meter input type: P

type of signal Ci is negligibly 13 pulse

Circuit depends on small Common ground 12 14

Supply * 11 Signal Flow meter input type: P

type of signal Ci is negligibly pulse

Circuit depends on small Common ground 9 10

Analog output type AP: 8 passive 4 - 20mA (not used in this example).

Common ground 7 6

Pulse output type OT:

Common ground 5 passive transistor (not used in this example). 4

Common ground 3 Please note: type AP may be used in combination with the battery (type PC), but only in IIB applications!

AP will power the unit (output loop powered); the battery will be disabled automatically till power is disconnected).

* Note sensor supply voltage: 1.2V DC for coil sensors or 3.2V DC for other pulse sensors.

6 F115 Configuration example IIB / IIIC and IIC - F115-P-AP-(CT)-OT-PX-XI - Output loop powered

HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F100 - series

Modbus communication type CT: TTL Please note: communciation type CT is not allowed in IIC applications.

TXD 29 ISOLATOR: Uo=max 30V I.S. Certified Isolator

RXD e.g. PC 28 TTL to + Io=max 250mA RS232 / RS422 / TTL Po=max 850mW

DTR 27 For example: MTL5051 +12V

Common ground - 26

* Note: Communication only allowed when configured as IIB / IIIC.

Supply *

Signal Flow meter input type: P

type of signal Ci is negligibly 13 pulse

Circuit depends on small Common ground

Supply * 11 12 14 Signal Flow meter input type: P

type of signal Ci is negligibly pulse

Circuit depends on small

Common ground 9 10 e.g. indicator + Uo=max 30V POWER SUPPLY e.g. MTL 5525 8 Ci = 17nF Analog output type AP:

passive 4 - 20mA (output loop powered) Io=max 100mA and / or - REPEATER Po=max 750mW

Common ground 7 e.g. MTL 5541 e.g. indicator e.g. counter + Uo=max 30V POWER SUPPLY e.g. MTL 5525 6 Ci is negligibly Pulse output type OT: 123456 Io=max 100mA or

small passive transistor 123456 - SWITCH INTERFACE Po=max 750mW

Common ground 5 e.g. MTL 5511 e.g. counter negative total value + Uo=max 30V POWER SUPPLY e.g. MTL 5525 4 Ci is negligibly Switch output type OT: Io=max 100mA or

small passive transistor - SWITCH INTERFACE Po=max 750mW Common ground 3 e.g. MTL 5511 e.g. relay

* Note sensor supply voltage: 1.2V DC for coil sensors or 3.2V DC for other pulse sensors.

F115 7 Configuration example IIB / IIIC and IIC - F115-P-AF-(CT)-OT-PD-XI - Power requirement 16 - 30V DC

HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F100 - series

Modbus communication type CT: TTL Please note: communciation type CT is not allowed in IIC applications.

TXD 29 ISOLATOR: Uo=max 30V I.S. Certified Isolator

RXD e.g. PC 28 + Io=max 250mA TTL to RS232 / RS422 / TTL Po=max 850mW

DTR 27 +12V For example: MTL5051

Common ground - 26

* Note: Communication only allowed when configured as IIB / IIIC.

Supply *

Signal Flow meter input type: P

type of signal Ci is negligibly 13 pulse small Circuit depends on Common ground TOTAL Co OF ALL CONNECTED ANALOG APPARATUS IN IIC Supply * APPLICATIONS MAY NOT EXCEED 66nF MINUS 17nF

11 12 14 (17nF IS USED BY THE ANALOG Flow meter input Signal OUTPUT SIGNAL TERMINAL 7 + 8). type: P

type of signal Ci is negligibly pulse small Circuit depends on Analog output type AF: Common ground 9 10 passive floating 4 - 20mA

8 Ci = 17nF e.g. indicator 7

+ Uo=max 30V POWER SUPPLY e.g. MTL 5525 6 Ci is negligibly Pulse output type OT: 123456

e.g. counter Io=max 100mA or

small passive transistor 123456 - SWITCH INTERFACE Po=max 750mW

Common ground 5 e.g. MTL 5511 e.g. counter negative total value + Uo=max 30V POWER SUPPLY e.g. MTL 5525 4 Ci is negligibly Control output type OT:

Io=max 100mA or

small passive transistor - SWITCH INTERFACE Po=max 750mW Common ground 3 e.g. MTL 5511 e.g. relay

2 Due to analog output type AF, the unit has to be powered with with external power supply type PD. + Uo=max 30V POWER SUPPLY

Main supply 1 Io=max 100mA

For example - Po=max 750mW MTL 5525

Common ground 0 Power supply type PD: 16 - 30V DC (please note: two power supplies PD and battery supply (type PC) is NOT allowed in IIC applications). Note: above values are safety values. Consult the technical specification for operational values.

* Note power supply type PD: the supply voltage to pulse sensors is maximum 8.7V (Uo=max 8.7V Io=max 25mA Po=max 150mW) and to analog sensors as connected to terminal 1 (internally linked).

8 F115 Configuration example IIB / IIIC - F115-P-AP-CT-OT-(PD)-XI - Power requirement 16 - 30V DC

HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F100 - series

Modbus communication type CT: TTL

TXD 29 ISOLATOR: Uo=max 30V I.S. Certified Isolator

RXD TTL to e.g. PC 28 + Io=max 250mA RS232 / RS422 / TTL Po=max 850mW

DTR 27 For example: MTL5051 +12V

Common ground - 26

Supply *

Signal + Uo=max 30V POWER SUPPLY Flow meter input Ci is negligibly type of signal 13 type: P Io=max 100mA

Circuit depends on small For example pulse - Common ground Po=max 750mW MTL 5525

Supply * 11 12 14

Signal + Uo=max 30V POWER SUPPLY Flow meter input Ci is negligibly type of signal type: P Io=max 100mA

Circuit depends on small For example pulse -

Common ground Po=max 750mW MTL 5525 9 10 e.g. indicator + Uo=max 30V POWER SUPPLY e.g. MTL 5525 8 Ci = 17nF Analog output type AP: Io=max 100mA

passive 4 - 20mA (output loop powered) and / or - REPEATER Po=max 750mW

Common ground 7 e.g. MTL 5541 e.g. indicator e.g. counter + Uo=max 30V POWER SUPPLY e.g. MTL 5525 6 Ci is negligibly Pulse output type OT: 123456 Io=max 100mA or

small passive transistor 123456 - SWITCH INTERFACE Po=max 750mW

Common ground 5 e.g. MTL 5511 e.g. counter negative total value + Uo=max 30V POWER SUPPLY e.g. MTL 5525 4 Ci is negligibly Control output type OT: Io=max 100mA or

small passive transistor - SWITCH INTERFACE Po=max 750mW Common ground 3 e.g. MTL 5511 e.g. relay

2 Please note: power supply type PD is not required - unit is output loop powered - type AP. + Uo=max 30V POWER SUPPLY

Main supply 1 Power supply type PD: 16 - 30V DC Io=max 100mA

For example - Po=max 750mW MTL 5525

Common ground 0 Note: above values are safety values. Consult the technical specification for operational values.

* Note power supply type PD: the supply voltage to pulse sensors is maximum 8.7V (Uo=max 8.7V Io=max 25mA Po=max 150mW) and to analog sensors as connected to terminal 1 (internally linked).

F115 9 Technical specification Enclosure General General Display Window Polycarbonate window. Type High intensity reflective numeric and Sealing Silicone. alphanumeric LCD, UV-resistant. Control keys Three industrial micro-switch keys. UV-resistant Dimensions 90 x 40mm (3.5” x 1.6”). silicone keypad. Digits Seven 17mm (0.67") and eleven 8mm (0.31") digits. Various symbols and measuring units. Aluminum wall / field mount enclosures Refresh rate User definable: fast, 1sec , 3sec, 15sec, 30sec, off. General Die-cast aluminum wall/field mount enclosure IP67 / Option ZB Transflective LCD with adjustable green LED NEMA 4X with 2-component UV-resistant coating. backlight. Good readings in full sunlight and Dimensions 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D. darkness. Weight 1100 gr. Note ZB Only available for safe area applications. Type HA Cable entry: 2 x PG9 and 1 x M20. 1 Type HL Cable entry: 2 x /2" NPT. Ambient temperature Type HM Cable entry: 2 x M16 and 1 x M20. Safe areas -40°C to +80°C (-40°F to +176°F). Type HN Cable entry: 1 x M20. Intrinsically Safe -40°C to +70°C (-40°F to +158°F). Type HO Cable entry: 2 x M20. Type HP Cable entry: 6 x M12. Type HT Cable entry: 1 x 1/ " NPT. Power requirements 2 Type HU Cable entry: 3 x 1/ " NPT. Type PB Long life Lithium battery - life-time depends upon 2 Type HV Cable entry: 4 x M20. settings and configuration - up to 5 years. Type HZ Cable entry: no holes. Type PC Intrinsically Safe long life lithium battery - life-time depends upon settings and configuration - up to 5 years. GRP wall / field mount enclosures Type PD 8 - 24V AC / DC ± 10%. Power consumption max. 10 General GRP wall/field mount enclosure IP67 / NEMA 4X, Watt. Intrinsically Safe: 16 - 30V DC; power UV-resistant and flame retardant. consumption max. 0.75 Watt. Dimensions 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D. Type PF 24V AC / DC ± 10%. Power consumption max. 15 Watt. Weight 600 gr. Type PM 115 - 230V AC ± 10%. Power consumption max. 15 Watt. Type HD Cable entry: no holes. Type PX 8 - 30V DC. Power consumption max. 0.5 Watt. Type HE Cable entry: 2 x Ø 16mm and 1 x Ø 20mm. 7 Type ZB 12 - 24V DC ± 10% or internally powered with type PD Type HF Cable entry: 1 x Ø 22mm ( /8"). / PF / PM. Power consumption max. 1 Watt. Type HG Cable entry: 2 x Ø 20mm. Note PB/PF/PM Not availble Intrinsically Safe. Type HH Cable entry: 6 x Ø 12mm. 7 Note PF/PM The total consumption of the sensors and outputs Type HJ Cable entry: 3 x Ø 22mm ( /8"). may not exceed 400mA @ 24V. Type HK Flat bottom, cable entry: no holes. Note For Intrinsically Safe applications, consult the safety values in the certificate. Panel mount enclosures Dimensions 130 x 120 x 60mm (5.12" x 4.72" x 2.36") - W x H x D. Sensor excitation Panel cut-out 115 x 98mm (4.53" x 3.86") L x H. Type PB/PC/PX 3.2V DC for pulse signals and 1.2V DC for coil pick-up. Type HB Die-cast aluminum panel mount enclosure IP65 / Note This is not a real sensor supply. Only suitable for NEMA 4X. sensors with a very low power consumption like coils Weight 600 gr. (sine wave) and reed-switches. Type HC GRP panel mount enclosure IP65 / NEMA 4X, Type PD 1.2 / 3.2 / 8.2 / 12 / 24V DC - max. 50mA @ 24V DC. UV-resistant and flame retardant. Type PD-XI 1.2 / 3.2 / 8.2V DC - max. 7mA @ 8.2V DC and mains Weight 450 gr. power supply voltage (as connected to terminal 1). Type PF / PM 1.2 / 3.2 / 8.2 / 12 / 24V DC - max. 400mA @ 24V DC.

Terminal connections Type Removable plug-in terminal strip. Wire max. 1.5mm2 and 2.5mm2.

Data protection Type EEPROM backup of all settings. Backup of running totals every minute. Data retention at least 10 years. Password Configuration settings can be password protected.

Directives & Standards EMC Directive 2004/108/EC, FCC 47 CFR part 15. Low voltage Directive 2006/95/EC ATEX / IECEx Directive 94/9/EC, IEC 60079-0, IEC 60079-11, IEC 60079-26. IP & NEMA EN 60529 & NEMA 250

10 F115 Hazardous area Communication option Intrinsically Safe (Type XI) Function Reading display information, reading / writing all configuration settings. ATEX II 1 G Ex ia IIB/IIC T4 Ga. Protocol Modbus RTU. certification II 1 D Ex ia IIIC T100 °C Da IP6X. Speed 1200 - 2400 - 4800 - 9600 baud. IECEx Ex ia IIC/IIB T4 Ga. Addressing Maximum 255 addresses. certification Ex ia IIIC T100 °C Da IP6X. Type CB RS232 Ambient Ta -40°C to +70°C (-40°F to +158°F). Type CH RS485 2-wire Type CI RS485 4-wire Explosion proof (Type XF) Type CT TTL Intrinsically Safe. ATEX certification II 2 GD EEx d IIB T5. Dimensions 300 x 250 x 200mm (11.8" x 9.9" x 7.9") L x H x D. Operational Weight Appr. 15kg. Operator functions Displayed • Positive and negative flow rate. functions • Total (count up and down) and accumulated total. Signal inputs • Total can be reset to zero by pressing the Flow meter CLEAR-key twice. Type P Coil / sine wave (HI: 20mVpp or LO: 80mVpp - sensitivity selectable), NPN/PNP, open collector, reed- Total switch, Namur, active pulse signals 8 - 12 and 24V DC. Digits 7 digits. Note Different sensor types can be used for both inputs. Units L, m3, GAL, USGAL, kg, lb, bbl, no unit. Frequency Minimum 0Hz - maximum 7kHz for total and flow rate Decimals 0 - 1 - 2 or 3. and single pulse. Double pulse max. 3.5kHz without Note Total can be reset to zero. communications and 2.5kHz with communications. Maximum frequency depends on signal type and Accumulated total internal low-pass filter. E.g. reed switch with Digits 11 digits. low-pass filter: max. frequency 120Hz. Units / decimals According to selection for total. K-Factors 0.000010 - 9,999,999 with variable decimal position. Note Can not be reset to zero. Low-pass filter Available for all pulse signals. Option ZF coil sensitivity 10mVpp. Flow rate Digits 7 digits. Signal outputs Units mL, L, m3, Gallons, kg, Ton, lb, bl, cf, RND, ft3, scf, Analog output Nm3, Nl, igal - no units. Function Transmitting positive (and negative) flow rate. Decimals 0 - 1 - 2 or 3. 4mA or 0V equals the minimum (zero) flow rate, it Time units /sec - /min - /hr - /day. cannot equal a negative flow rate value Accuracy 10 bit. Error < 0.05%. Accessories Update time Eight times per second. Mounting accessories Type AA Active 4 - 20mA output (requires PD, PF or PM). ACF02 Stainless steel wall mounting kit. Type AB Active 0 - 20mA output (requires PD, PF or PM). ACF05 Stainless steel pipe mounting kit (worm gear clamps Type AF Passive floating 4 - 20mA output for Intrinsically not included). Safe applications (requires XI + PC or PD). ACF06 Two stainless steel worm gear clamps Ø 44 - 56mm. Type AI Passive galvanically isolated 4 - 20mA output - also ACF07 Two stainless steel worm gear clamps Ø 58 - 75mm. available for battery powered models (requires PB, ACF08 Two stainless steel worm gear clamps Ø 77 - 95mm. PD, PF or PM). ACF09 Two stainless steel worm gear clamps Ø 106 - 138mm. Type AP Passive 4 - 20mA output - not isolated. Unit will be loop powered. Intrinsically Safe isolators Type AU Active 0 - 10V DC output (requires PD, PF or PM). ACG01 MTL5511 - One channel pulse or switch output transfer from hazardous area to safe area. Digital outputs ACG02 MTL5525 - One channel power supply from safe area Function Pulse output and indication negative totalisation. to hazardous area (e.g. to power the unit with PD or Frequency Max. 500Hz. Pulse length user definable between to power a switching or analog device in hazardous 0.001 second up to 9.999 seconds. area). Type OA Two active 24V DC transistor outputs (PNP); ACG03 MTL5541 - One channel 4 - 20mA repeater from max. 50mA per output (requires PD, PF or PM). hazardous area to safe area. Type OR Two electro-mechanical relay outputs (N.O.) - isolated; ACG04 MTL 5051 - Bi-direction serial-data-isolator max. switch power 230V AC - 0.5A per relay (for Modbus communication). (requires PF or PM). ACG05 MTL5516C - Two channel pulse or switch output Type OT Two passive transistor outputs (NPN) - not isolated. transfer from hazardous area to safe area. Max. 50V DC - 300mA per output. ACG06 MTL5513 - One channel pulse or switch output Note Output 2 is switched in case a negative acc. total transfer from hazardous area to safe area. is transmitted. ACG07 MTL5546Y - One channel isolated driver bringing 4 - 20mA from safe area to hazardous area, HART transparent, OCD.

F115 11 Ordering information Standard configuration: F115-P-AP-CX-EX-HC-IX-OT-PX-TX-XX-ZX. Ordering information: F115 -_ -A _ -C _ -EX -H _ -IX -O _ -P _ -TX -X _ -Z _ Flow meter input signal P Pulse input: coil, npn, pnp, namur, reed-switch. Analog output signal AA Active 4 - 20mA output - requires PD, PF or PM. AB Active 0 - 20mA output - requires PD, PF or PM. AF I.S. floating 4 - 20mA output - requires XI + PC or PD. AI Isolated 4 - 20mA output - requires PB, PD, PF or PM. AP Passive 4 - 20mA output, loop powered unit. AU Active 0 - 10V DC output - requires PD, PF or PM. Communication CB Communication RS232 - Modbus RTU. CH Communication RS485 - 2-wire - Modbus RTU. CI Communication RS485 - 4-wire - Modbus RTU. CT Intrinsically Safe TTL - Modbus RTU. CX No communication. Flow equations EX No flow equations. Panel mount enclosures - IP65 / NEMA4X HB Aluminum enclosure. HC GRP enclosure. GRP field / wall mount enclosures - IP67 / NEMA4X HD Cable entry: no holes. HE Cable entry: 2 x Ø 16mm & 1 x Ø 20mm. HF Cable entry: 1 x Ø 22mm (7/8”). HG Cable entry: 2 x Ø 20mm. HH Cable entry: 6 x Ø 12mm. HJ Cable entry: 3 x Ø 22mm (7/8”). HK Flat bottom, cable entry: no holes. Aluminum field / wall mount enclosures - IP67 / NEMA4X HA Cable entry: 2 x PG9 flow rate 1 x M20. HL Cable entry: 2 x 1/2”NPT. HM Cable entry: 2 x M16 flow rate 1 x M20. HN Cable entry: 1 x M20. HO Cable entry: 2 x M20. HP Cable entry: 6 x M12. HT Cable entry: 1 x 1/2”NPT. HU Cable entry: 3 x 1/2”NPT. HV Cable entry: 4 x M20. HZ Cable entry: no holes. Additional input signal IX No additional input. Digital output signals OA Two active transistor outputs - requires PD, PF or PM. OR Two mechanical relay outputs - requires PF or PM. OT Two passive transistor outputs - standard configuration. Power requirements PB Lithium battery powered. PC Lithium battery powered - Intrinsically Safe. PD 8 - 24V AC/DC + sensor supply - with XI: 16 - 30V DC. PF 24V AC/DC + sensor supply. PM 115 - 230V AC + sensor supply. PX Basic power supply 8 - 30V DC (no real sensor supply). Unit requires external loop AP. Temperature input signal TX No temperature input signal. Hazardous area XI Intrinsically Safe, according ATEX and IECEx. XF EExd enclosure - 3 keys. XX Safe area only. Other options ZB Adjustable backlight. ZF Coil input 10mVpp. ZX No options. The bold marked text contains the standard configuration. Available Intrinsically Safe.

Specifications are subject to change without notice. Fluidwell bv P.O. Box 6 5460 AA - Veghel - The Netherlands Telephone: +31 (0)413 343 786 Telefax: +31 (0)413 363 443 email: [email protected] Internet: www.fluidwell.com 12 Copyright: Fluidwell bv - 2015 - F115-DATA-EN-V1540