GENERAL MECHANICAL NOTES MECHANICAL EQUIPMENT SCHEDULE MECHANICAL LEGEND 1. THE DRAWINGS ARE INTENDED TO COVER SYSTEMS WHICH WILL FIT THE AVAILABLE SPACE, WHICH WILL NOT INTERFERE WITH THE GENERAL AC-1 AIR CONDITIONER GAS HEAT LENNOX LGH150S4M PACKAGED ROOFTOP UNIT, 147,800 BTUH GROSS TOTAL COOLING @ 95 AMBIENT, 4800 CFM @ 2.2"TSP, STRUCTURAL DESIGN. CAREFULLY EXAMINE THE DRAWINGS FOR ALL BRANCHES OF WORK AND BE RESPONSIBLE FOR THE PROPER 800 CFM OA MIN, GAS FIRED STAINLESS STEEL , FIRST STAGE 156,000 INPUT BTUH, SECOND STAGE FITTING OF MATERIAL AND APPARATUS INTO THE BUILDING. COORDINATE THE EXACT LOCATION OF EQUIPMENT AND EQUIPMENT 240,000 INPUT BTUH, 5 HP MOTOR WITH MSAV CONTROL, 67 MCA, 208V/3 PH/60 HZ. PROVIDE 14" HIGH DETAIL DESCRIPTION CONNECTIONS WITH THE ARCHITECT AND EQUIPMENT SUPPLIER. STANDARD ROOF CURB, OUTDOOR AIR HOOD, MODULATING DAMPERS W/ CONTROL, HUMIDITROL RELATIVE CONTROL, LOW AMBIENT CONTROL, GFCI SERVICE OUTLET, FACTORY INSTALLED DISCONNECT, CONDENSATE SUPPLY, RETURN, EXHAUST DUCTWORK 2. INSTALLATION SHALL BE PERFORMED IN ACCORDANCE WITH 2012 INTERNATIONAL MECHANICAL CODE AND LOCAL APPLICABLE CODES. DRAIN PAN OVERFLOW SWITCH TO SHUT DOWN UNIT, SMOKE DETECTOR IN RA SECTION. RECTANGULAR OR ROUND DIMENSIONS 3. GIVE ALL NECESSARY NOTICES, OBTAIN ALL PERMITS, AND PAY ALL COSTS IN CONNECTION WITH THE WORK FILE ALL NECESSARY PLANS, AC-2 AIR CONDITIONER GAS HEAT LENNOX LGH092H4M PACKAGED ROOFTOP UNIT, 93,000 BTUH GROSS TOTAL COOLING @ 95 AMBIENT, 3000 CFM @ 2.2"TSP, NOTED ON DRAWINGS INDICATE INSIDE PREPARE ALL DOCUMENTS AND OBTAIN ALL NECESSARY APPROVALS OF ALL REGULATING AUTHORITIES HAVING JURISDICTION OBTAIN 600 CFM OA MIN, GAS FIRED STAINLESS STEEL HEAT EXCHANGER, FIRST STAGE 84,500 INPUT BTUH, SECOND STAGE DIMENSTIONS ALL REQUIRED CERTIFICATES OF INSPECTION FOR WORK AND DELIVER SAME TO ARCHITECT BEFORE REQUEST FOR ACCEPTANCE AND 130,000 INPUT BTUH, 3 HP EVAPORATOR MOTOR WITH MSAV CONTROL, 45 MCA, 208V/3 PH/60 HZ. PROVIDE 14" HIGH FINAL PAYMENT WORK. STANDARD ROOF CURB, OUTDOOR AIR HOOD, MODULATING ECONOMIZER DAMPERS W/ ENTHALPY CONTROL, HUMIDITROL RISE OR DROP IN DUCTWORK RELATIVE HUMIDITY CONTROL, LOW AMBIENT CONTROL , GFCI SERVICE OUTLET, FACTORY INSTALLED DISCONNECT, 4. DRAWINGS ARE DIAGRAMMATIC FOR PIPING, CONDUITS AND DUCTWORK THAT IS NOT SHOWING DETAIL. SIZES OF PIPING, CONDUITS AND CONDENSATE DRAIN PAN OVERFLOW SWITCH TO SHUT DOWN UNIT, SMOKE DETECTOR IN RA SECTION. DUCTWORK AND THEIR LOCATIONS ARE INDICATED, BUT IT IS NOT INTENDED TO SHOW EVERY OFFSET, FITTING OR EVERY STRUCTURAL SUPPLY AIR OR OUTSIDE AIR SECTION DIFFICULTY THAT MAY BE ENCOUNTERED DURING INSTALLATION OF THE WORK. THE ALIGNMENT OF PIPING, CONDUIT, OR DUCTWORK SHALL AC-3 AIR CONDITIONER GAS HEAT LENNOX LGH150S4M PACKAGED ROOFTOP UNIT, 147,800 BTUH GROSS TOTAL COOLING @ 95 AMBIENT, 4800 CFM @ 2.2"TSP, BE VERIFIED FROM THAT INDICATED ON THE DRAWINGS WITHOUT EXTRA EXPENSE TO THE OWNER WHERE NECESSARY TO AVOID 800 CFM OA MIN, GAS FIRED STAINLESS STEEL HEAT EXCHANGER, FIRST STAGE 156,000 INPUT BTUH, SECOND STAGE STRUCTURAL OR MECHANICAL DIFFICULTIES, OR TO AVOID THE WORK OF ANY OTHER TRADES. 240,000 INPUT BTUH, 5 HP EVAPORATOR MOTOR WITH MSAV CONTROL, 67 MCA, 208V/3 PH/60 HZ. PROVIDE 14" HIGH STANDARD ROOF CURB, OUTDOOR AIR HOOD, MODULATING ECONOMIZER DAMPERS W/ ENTHALPY CONTROL, HUMIDITROL SUPPLY CEILING DIFFUSER 5. CHECK AND VERIFY ALL DIMENSIONS, SITE CONDITIONS, DRAWINGS AND SPECIFICATIONS. REPORT ANY AND ALL DISCREPANCIES TO THE RELATIVE HUMIDITY CONTROL, LOW AMBIENT CONTROL, GFCI SERVICE OUTLET, FACTORY INSTALLED DISCONNECT, CONDENSATE ARCHITECT AT ONCE. DRAIN PAN OVERFLOW SWITCH TO SHUT DOWN UNIT, SMOKE DETECTOR IN RA SECTION.

6. PERFORM LABOR IN A THOROUGH AND COMPLETE WORKMAN LIKE MANNER AND WITH ALL REASONABLE RAPIDITY TO THE SATISFACTION EF-1 EXHAUST GREENHECK CUE-121-VG UPBLAST ROOF FAN, 980 CFM @ 0.375" ESP, 1/4HP, 120V/1 PH/60 HZ, VARI-GREEN DIRECT DRIVE EC RADIAL CEILING DIFFUSER OF THE ARCHITECT. MOTOR WITH POTENTIOMETER DIAL SWITCH, NEMA-A TOGGLE DISCONNECT TO BE FIELD INSTALLED, BACKWARD INCLINED ALUMINUM WHEEL, ALUMINUM HOUSING, ALUMINUM CURB CAP WITH PRE-PUNCHED MOUNTING HOLES, DRAIN DESCRIPTION 7. CUT COMPLETED WORK ONLY IF SLEEVES, OPENINGS, CHASES, ETC., WERE INADVERTENTLY OMITTED AND ONLY WITH THE TROUGH, PROVIDE PRE-FABRICATED ROOF CURB WITH FAN. SPECIFIED APPROVAL OF THE ARCHITECT. RETURN DUCT SECTION EF-2 EXHAUST FAN NOT USED.

8. ALL EQUIPMENT SHALL BE INSTALLED ACCORDING TO THE MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS. SHOULD ANY REVISIONS VARIANCE BETWEEN PLANS AND SPECIFICATION OCCUR WITH THESE INSTRUCTIONS, THE ARCHITECT OR ENGINEER SHOULD BE CONTACTED EF-3 HOOD & EXHAUST FAN CAPTIVE-AIRE STAINLESS STEEL HOOD MODEL 4224 VHB-G, EXHAUST FAN MODEL DU30HFA, ROOF TOP EXHAUST 617 CFM @ IMMEDIATELY SO THAT ANY VARIATIONS IN INSTALLATION CAN BE KNOWN BY ALL PARTIES CONCERNED. RETURN (WAREWASHER) TYPE II (DISHWASHER) 0.25 HP, 115V, 1 PHASE, 60 HZ, CENTRIFUGAL DIRECT DRIVE BLOWER, ALUMINUM HOUSING, MOTOR MOUNTED ON VIBRATION ISOLATORS, WITH FACTORY INSTALLED DISCONNECT SWITCH. PROVIDE PRE-FABRICATED ROOF CURB, INSECT 9. UNLESS OTHERWISE NOTED ON THE EQUIPMENT SCHEDULE, ALL MECHANICAL EQUIPMENT SHALL BE MOUNTED ON VIBRATION ISOLATORS TO SCREEN. ATC CONTRACTOR SHALL INTERLOCK FAN TO TURN ON/OFF WITH DISHWASHER THRU CONTACTOR PANEL, FAN SHALL PREVENT THE TRANSMISSION OF VIBRATION AND MECHANICALLY TRANSMITTED SOUND TO THE BUILDING STRUCTURE. VIBRATION OPERATE 5 MINUTES AFTER THE POWER IS NO LONGER SENSED. EXHAUST DUCT SECTION ISOLATORS SHALL BE SELECTED IN ACCORDANCE WITH THE WEIGHT DISTRIBUTION SO AS TO PRODUCE REASONABLY UNIFORM DEFLECTION. CURB MOUNTED ROOF TOP EQUIPMENT SHALL BE MOUNTED ON VIBRATION ISOLATION BASES THAT FIT OVER THE ROOF CURB AND UNDER EF-4 HOOD & EXHAUST FAN CAPTIVE-AIRE 37" BACKSHELF STAINLESS STEEL HOOD MODEL 3044 CBD-2-BR (THIS HOOD IS TESTED PER UL 710 AND MEETS THE ISOLATED EQUIPMENT. (FRYER) TYPE 1 ITS REQUIREMENTS), EXHAUST FAN - MODEL NCA8FA, ; 694 CFM @ (FRYER) 1/2 HP, 208 V, 1 PHASE, 60 HZ, BELT DRIVE, 10. EACH COMPLETED SYSTEM SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE OF THE WORK BY CENTRIFUGAL BLOWER, ALUMINUM HOUSING, MOTOR MOUNTED ON VIBRATION ISOLATORS, WITH FACTORY INSTALLED THE OWNER, THE CONTRACTOR SHALL GUARANTEE EACH SYSTEM IN WRITING TO BE FREE OF DEFECTS OF MATERIALS AND WORKMANSHIP DISCONNECT SWITCH, PREFABRICATED ROOF CURB, ALL DUCTWORK BEYOND THE EXHAUST DUCT COLLAR TO BE PROVIDED AND TO PERFORM SATISFACTORILY UNDER ALL CONDITION OF LOAD OR SERVICE. AND INSTALLED IN ACCORDANCE WITH THE JURISDICTIONAL CODES, AND MUST BE MECHANICALLY STRONG AND GREASE AND WATERTIGHT BLOWER SHALL BE NON-OVERLOADING TYPE, THE BLOWER WHEEL SHALL BE FORWARD CURVED CENTRIFUGAL, VOLUME CONTROL 11. DETERMINE IN ADVANCE OF CONSTRUCTION THE LOCATION OF ALL DUCTWORK, HANGERS, EQUIPMENT, ETC. COORDINATE THE LOCATION CONSTRUCTED G-90 GALVANIZED STEEL DESIGN WHICH WILL DELIVER THE SPECIFIED VOLUME OF AIR AT THE REQUIRED STATIC OF DUCTWORK, PIPING AND DIFFUSERS WITH ALL OTHER TRADES. IN GENERAL, INSTALL DUCTWORK AND PIPING AS HIGH AS POSSIBLE, PRESSURE, TOP HORIZONTAL DISCHARGE IS DESIRED. FAN SHALL BE INTERLOCKED TO EF-4M SUPPLY FAN VIA CAPTIVES THROUGH OR BETWEEN STRUCTURAL MEMBERS IF SPACE PERMITS. AIRE CONTROL PANEL. FLEXIBLE CONNECTOR 12. ALL CONCEALED SUPPLY AND RETURN DUCTWORK SHALL BE EXTERNALLY INSULATED WITH 3" THICK FOIL BACKING FIBERGLASS WITH .75 EF-4 MAKE-UP AIR SUPPLY FAN GAS HEAT CAPTIVE - AIRE MAKE-UP AIR SUPPLY FAN MODEL D76, 625 CFM @ 0.4" ESP, .5 MTR HP, 1005 RPM, LOW CFM DIRECT FIRED PCF DENSITY. (INSTALLED R-VALUE @ 25% COMPRESSION = R-8.4 MIN). THE DUCT INSULATION SHALL CONFORM TO NCMC SECTIONS 604.2 GAS WITH 44,928 BTUH INPUT, 41,334 BTUH OUTPUT, 0 DEGREE F EAT WITH A 60 DEGREE F TEMPERATURE RISE, GAS INLET THROUGH 604.13. PRESSURE 7 - 14 INCHES OF WC, FLA 4.0 AMPS 208 V, 1 PHASE, 60 HZ ROOF TOP MODULAR DOWN DISCHARGE WITH RTS REMOTE TEMPERATURE SENSOR SCREENED INTAKE HOOD, SIDE ACCESS FILTER SECTION WITH (1) 16"x20"x2" EZ KLEEN METAL MESH FILTER, PRE-FABRICATED BY 13. THE AIR DISTRIBUTION SYSTEM AND RELATED ITEMS SHALL BE INSTALLED IN ACCORDANCE WITH 1995 SECOND EDITION SMACNA HVAC ROOF CURB AND SUPPORT LEG. PROVIDE COOLING INTERLOCK RELAY, 24 VAC COIL 120V CONTACT TO LOCK OUT BURNER DUCT CONSTRUCTION STANDARDS FOR METAL AND FLEXIBLE DUCTS AT SEAL / PER CLASS SPECIFIED: SA @ +2"SP SEAL CLASS 'B', RA @ CIRCUIT WHEN AC IN ENERGIZED ALL DUCTWORK BEYOND THE VENTILATOR DUCT COLLAR TO BE PROVIDED AND INSTALLED IN -2"SP SEAL CLASS 'C', EA -2"SP SEAL CLASS 'B'. ACCORDANCE WITH THE JURISDICTIONAL CODES. FAN SHALL BE INTERLOCKED TO EF-4 EXHAUST FAN VIA CAPTIVE AIRE CONTROL PANEL. T DATE 14. RIGID DUCTS SHALL BE CONSTRUCTED OF GALVANIZED SHEET METAL. CHANGES IN DUCT SIZE OR SHAPE SHALL BE MADE WITH TRANSITIONS AS LONG AS PRACTICABLE, WITH THE ANGLE BETWEEN THE SIDE AND AXIS OF THE DUCT BETWEEN 15 AND 30 DEGREES, EF-5 HOOD & EXHAUST FAN CAPTIVE-AIRE STAINLESS STEEL HOOD MODEL 4218 VH1-PYRAMID, EXHAUST FAN MODEL DU30HFA, ROOF TOP EXHAUST 450 UNLESS OTHERWISE SHOWN ON THE DRAWINGS OR AUTHORIZED BY ARCHITECT. THE MINIMUM GALVANIZED SHEET METAL THICKNESS FOR (TURBO CHEF) CFM @ (TURBO CHEF OVEN) 0.25 HP, 115V, 1 PHASE, 60 HZ , CENTRIFUGAL DIRECT DRIVE BLOWER, ALUMINUM HOUSING, MOTOR AV AUDIBLE / VISIBLE ALARM DUCT CONSTRUCTION SHALL BE 24 GAUGE THRU 30" DUCTS, 22 GAUGE FOR 31" THRU 42" DUCTS. MOUNTED ON VIBRATION ISOLATORS, WITH FACTORY INSTALLED DISCONNECT SWITCH. PROVIDE PRE-FABRICATED ROOF CURB, INSECT SCREEN. PROVIDE PRE-WIRED STAINLESS STEEL CONTROL BOX WITH LIGHTED SWITCH ON WALL. FURNISHED BY OWNER 15. FLEXIBLE DUCT SHALL BE FACTORY FABRICATED ASSEMBLY, SPIRAL CONSTRUCTION, 3" FIBERGLASS BLANKET INSULATION AND COATED HUMIDITROL SENSOR FIBERGLASS MESH LINER. MINIMUM R-8 FLEXIBLE DUCT SHALL BE SUITABLE FOR 1-1/2 TIMES THE DUCT PRESSURE AT THE CONNECTION. CD-1 CEILING DIFFUSER HART AND COOLEY H.V.S. OR TITUS MODEL TMS 24"X24" SQUARE FACE, ROUND NECK, CONSTRUCTED OF 22 GA STEEL, HS INSTALL WITH A MINIMUM OF BENDS AND EXTENDED STRAIGHT WHERE POSSIBLE, MAXIMUM RUN OF FIVE FEET, MINIMUM BEND RADIUS OF STANDARD WHITE FINISH, LAY-IN MOUNTING. PROVIDE OPPOSED BLADE DAMPER AND PROVIDE SECTORIZING BAFFLES BRAD S. BLICKENDERFER 1-1/2 TIMES THE DUCT DIAMETER MEASURED FROM THE CENTER LINE. SEAL FLEXIBLE DUCT TO MAIN DUCT INSULATION. WHERE REQUIRED, 4-WAY THROW. CEILING DIFFUSERS FOR THE CEILING IN THE SALE AREA SHALL BE PROVIDED WITH A WHITE FINISH. ALL SUPPLY DIFFUSERS SHALL HAVE AN INSULATED BACKING ON EACH DIFFUSER. SMOKE DETECTOR 16. GREASE DUCT SHALL BE CONSTRUCTED OF STEEL, MINIMUM 16 GAUGE, OR SHALL BE LISTED AND LABELED FACTORY- BUILT COMMERCIAL SD KITCHEN GREASE DUCT. PROVIDE A SEALED DUCT-ENCLOSED VENTED TO THE OUTSIDE, WITH TOTALLY FOIL-ENCAPSULATED, SRW-1 SIDEWALL REGISTER WALL HART AND COOLEY MODEL H.V. GRILLE OR TITUS MODEL 300FL, SATIN ANODIZED FINISH, SIZE AS LISTED ON DRAWINGS. NON-COMBUSTIBLE 2000 DEGREE F RATED, FLEXIBLE ZERO CLEARANCE WRAP INSULATION FOR HORIZONTAL AND EXTRUDED ALUMINUM CONSTRUCTION, HORIZONTAL FRONT BARS, VERTICAL SECOND BARS, TWO ROWS OF INDIVIDUALLY VERTICAL COMMERCIAL KITCHEN GREASE DUCT APPLICATIONS. THE INSULATION SHALL BE APPLIED AS PER MANUFACTURERS ADJUSTED FACE BARS FOR HORIZONTAL AND VERTICAL DEFLECTION, PIVOTED BARS FOR EASY POSITIVE SETTING. RECOMMENDATIONS. THE FIRE WRAP INSULATION SHALL MEET ASTM E2336. (AS MANUFACTURED BY THERMAL CERAMICS) PROVIDED BY RADIUS ELBOW USE 1.5 RADIUS RCD-1 RADIAL CEILING DIFFUSER TITUS TRITEC HIGH VOLUME LOW VELOCITY RADIAL AIR DIFFUSION TECHNOLOGY SUPPLY DIFFUSER, LAY-IN MOUNTING, STEEL THE MECHANICAL CONTRACTOR. THE GREASE DUCT SHALL BE TESTED IN ACCORDANCE TO NCMC SECTION 506.3.2.5. WHEREVER POSSIBLE. USE 1.0 RADIUS FACE AND BACK PAN, 51% FREE AREA PERFORATED FACE, LOW VELOCITY 2-WAY HEMISPHERICAL AIR PATTERN. RADIAL 1.0 1.5 WHERE A 1.5 RADIUS WILL NOT FIT 17. DUCTS SHALL BE INSTALLED AND CONNECTED TO EQUIPMENT SO AS TO BE COMPLETELY FREE OF VIBRATION UNDER CONDITIONS OF SUPPLY DIFFUSER WILL BE PROVIDED BY THE MECHANICAL CONTRACTOR. DIFFUSER SHALL HAVE AN INSULATED BACKING. OPERATION. FLEXIBLE CONNECTORS SHALL BE USED WHEN CONNECTING TO ANY VIBRATING EQUIPMENT. RG-1 RETURN GRILLE HART AND COOLEY MODEL 659T, 24" X 24", 1" FILTER FRAME, FIXED DEFLECTION BLADES, STEEL CONSTRUCTION, STANDARD 18. UPON COMPLETION OF THE INSTALLATION, CONTRACTOR SHALL COMPLETELY BALANCE ALL MECHANICAL SYSTEMS. ALL SUPPLY EXHAUST WHITE FINISH, LAY-IN MOUNTING. PROVIDE DISPOSABLE 1" FILTERS. FOR THE OPEN SALES AREA SHALL BE PROVIDED FANS SHALL BE TESTED AND ADJUSTED TO OBTAIN THE DESIRED AIR QUANTITIES. ALL AIR SUPPLY OUTLETS, RETURN AND EXHAUST WITH A WHITE FINISH. GRILLES, FRESH AIR INTAKES AND SHALL BE BALANCED UNTIL EACH DELIVERS SUBSTANTIALLY ITS SPECIFIED AMOUNT, BUT NO TURNING VANE (USE ONLY WHEN RADIUS TYPE MORE THAN 10% OF DESIGN. AIR BALANCE OF ALL SYSTEMS SHALL BE ACCOMPLISHED WITH THE RESPECTIVE EQUIPMENT UNDER FULL EG-1 EXHAUST GRILLE TITUS EGG CRATE EXHAUST GRILLE, STANDARD WHITE FINISH,SURFACE MOUNTed, PROVIDE DISPOSABLE 1" FILTERS. EXHAUST ELBOWS ARE NOT POSSIBLE) COOLING CONDITIONS. SHEETZ WILL SCHEDULE A CERTIFIED BALANCING CONTRACTOR TO CHECK AND COMPARE CONTRACTORS GRILLES WILL BE PROVIDED BY MECHANICAL CONTRACTOR. REPORT. TGC-1 TRANSFER AIR GRILLE TITUS EGG CRATE TRANSFER GRILLE, STANDARD WHITE FINISH, SURFACE MOUNTed. EXHAUST TRANSFER GRILLES WILL BE 19. ALL MECHANICAL EQUIPMENT SHALL BEAR THE LABEL OF AN APPROVED AGENCY AND THAT THE MECHANICAL EQUIPMENT WILL BE PROVIDED BY MECHANICAL CONTRACTOR. DIFFUSER SHALL HAVE AN INSULATED BACKING. TESTED TO THE APPROPRIATE STANDARDS IN THE 2012 INTERNATIONAL MECHANICAL CODE. CHAPTER 9 AND 11, AND THE RESULTS PROVIDED. VCD VOLUME CONTROL DAMPERS GREENHECK VOLUME CONTROL DAMPER MODEL MBDR-50 OR RUSKIN MODEL MDRS25 FOR ROUND DAMPERS, GREENHECK MODEL MBD-10 OR RUSKIN MODEL MD25 FOR RECTANGULAR DAMPERS. DAMPERS SHALL BE FACTORY FABRICATED SINGLE MECHANICAL ABBREVIATIONS 20. ALL OUTSIDE AIR INTAKE OPENINGS WILL BE LOCATED A MINIMUM OF 15 FEET FROM ANY PLUMBING VENTS, AND 10 FEET FROM FUEL-FIRED BLADE, CENTER PIVOTED WITH SQUARE AXLE SHAFT AND LOCKING HAND QUADRANT, FRAME AND BLADE SHALL BE APPLIANCE VENTS OR EXHAUST FAN DISCHARGES. CONSTRUCTED OF MINIMUM 20 GAUGE GALVANIZED SHEET STEEL, PROVIDE OPTIONAL 2" HAND QUADRANT STAND OFF ABV ABOVE INSUL INSULATION BRACKET. AFF ABOVE FINISHED FLOOR INT INTERIOR 21. THE LENNOX HVAC UNITS WILL EACH BE SUPPLIED WITH A FACTORY INSTALLED SMOKE DETECTION SYSTEM LOCATED IN THE AC UNITS ARCH ARCHITECT RETURN AIR SECTION. THE SMOKE DETECTORS WILL BE LOCATED UPSTREAM OF FILTERS, EXHAUST AIR AND OUTDOOR AIR CONNECTORS. T THERMOSTAT HONEYWELL MODEL T-7300D SERIES 2000 COMMERCIAL MICROELECTRONIC COOLING/HEATING 24V THERMOSTAT, AUTOMATIC APD AIR PRESSURE DROP MAT MIXED AIR TEMPERATURE THE SMOKE DETECTORS WILL BE LABELED FOR INSTALLATION IN THE AIR DISTRIBUTION SYSTEM AND INSTALLED IN ACCORDANCE WITH OR MANUAL CHANGE OVER FOR MULTI-STAGE SYSTEMS, BUILT IN TIME DELAYS, LCD READOUT WITH SET POINT TEMPERATURE APPROX APPROXIMATE MAX MAXIMUM NFPA 72. ACTIVATION OF THE SMOKE DETECTOR WILL SHUT DOWN THE HVAC UNITS AND ACTIVATE A VISIBLE AND AN AUDIBLE SIGNAL AND ACTUAL TEMPERATURE IN F PLUS SYSTEM STATUS AND OPERATIONAL MODE, FAN BUTTON TO ALLOW CONTINUOUS (ON) OR ATC AUTOMATIC TEMPERATURE CONTROL MFG MANUFACTURER LOCATED AT THE SALES COUNTER. INTERMITTENT (AUTO) BLOWER SETTING, KEYBOARD LOCKOUT TO PREVENT TAMPERING, SOLID-STATE ELECTRONIC AUTO AUTOMATIC MIN MINIMUM TECHNOLOGY TO ELIMINATE BATTERY BACK-UP AND MAINTAINS THERMOSTAT SETTINGS DURING POWER FAILURE. TO BE AUX AUXILLIARY MTD MOUNTED 22. ALL DUCTS SHALL BE SUPPORTED WITH APPROVED HANGERS AT INTERVALS NOT EXCEEDING TEN FEET (10') OR BY OTHER APPROVED LOCATED IN THE OFFICE. FURNISHED BY OWNER. CONTRACTOR TO INSTALL AND FIELD WIRE. @ AT MTL METAL DUCT SUPPORT SYSTEMS DESIGNED IN ACCORDANCE WITH THE BUILDING CODES AND SMACNA REQUIREMENTS. MORE STRINGENT OF TWO RTS REMOTE TEMPERATURE SENSOR AIR SENSOR MODEL 27C.40 LOCATE AND CONNECT TO APPROPRIATE THERMOSTAT AS SHOWN ON THE PLANS. REMOTE SHALL BE FOLLOWED. BD BACKDRAFT DAMPER NOM NOMINAL TEMPERATURE SENSORS TO MONITOR AND CONTROL HEATING AND COOLING UNITS. FURNISHED BY OWNER. CONTRACTOR TO BLW BELOW 23. ALL DUCT COVERINGS AND LININGS, INCLUDING ADHESIVES WHEN USED SHALL HAVE A FLAME SPREAD RATING NOT MORE THAN TWENTY INSTALL IN THE RA DUCTWORK AND FIELD WIRE. OA OUTSIDE AIR FIVE (25) AND SMOKE DEVELOPMENT RATING NOT MORE THAN FIFTY (50), WHEN TESTED IN ACCORDANCE WITH ASTM-E-84. HS HUMDITROL SENSOR HUMDITROL RELATIVE HUMIDITY WALL SENSOR MODEL 17M50 LOCATE AND CONNECT TO APPROPRIATE HVAC UNIT AS SHOWN CD CEILING DIFFUSER OC ON CENTER CFM CUBIC FEET PER MINUTE OS&Y OUTSIDE SCREW & YOKE 24. CONDENSATE FROM ALL COOLING COILS AND WILL BE CONVEYED FROM THE DRAIN PAN OUTLET AND THE SECONDARY ON THE PLANS. HUMDITROL SENSOR TO MONITOR HUMIDITY AND CONTROL AC UNITS CONDENSER REHEAT FOR HUMIDITROL. OR AUXILIARY OUTLET TO AN APPROVED LOCATION FOR DISPOSAL, SEE PLUMBING PLANS. ADJUST UNIT SETPOINT TO INITIATE HUMIDITROL FUNCTION WHENEVER THE SPACE HUMIDITY SENSOR READS 40%RH OR CLG COOLING GREATER. FURNISHED BY OWNER. CONTRACTOR TO MOUNT ON WALL AND FIELD WIRE. CO CLEANOUT PC PLUMBING CONTRACTOR 25. PROVIDE STAND-OFF BRACKETS FOR VOLUME CONTROL DAMPERS. CONN CONNECTION PCF POUNDS PER CUBIC FOOT CONT CONTINUATION PD PRESSURE DROP 26. MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR EACH MECHANICAL APPLIANCE SHALL BE MADE AVAILABLE TO THE LOCAL FIELD INSPECTOR ON JOB SITE AT TIME OF INSPECTION. DETL DETAIL RA RETURN AIR DIA DIAMETER RCD RADIAL CEILING DIFFUSER 27. PRIOR TO WRAPPING THE DUCTWORK WITH INSULATION ALL RELATED CODE INSPECTIONS MUST BE COMPLETED AND APPROVED BY THE DISCH DISCHARGE REQ'D REQUIRED INSPECTOR HAVING JURISDICTION. DN DOWN RET RETURN DPR DAMPER RG RETURN GRILLE 28. PROVIDE 3-RING BINDER FOR THE OPERATING AND MAINTENANCE MANUAL OF HVAC EQUIPMENT CUT SHEETS OF CONTRACTOR AND DWG DRAWING OWNER FURNISHED EQUIPMENT. THE MANUAL SHALL INCLUDE THE FOLLOWING SA SUPPLY AIR EA EACH SD SMOKE DETECTOR x EQUIPMENT CUT SHEET/SUBMITTAL DATA HIGHLIGHTED SHOWING MODEL NUMBER, EAT ENTERING AIR TEMPERATURE SHT SHEET CAPACITY (INPUT/OUTPUT) AND OPTIONS FURNISHED. EC ELECTRICAL CONTRACTOR SP STATIC PRESSURE EG EXHAUST GRILLE SPECS SPECIFICATIONS Ɣ MANUFACTURER OPERATION AND MAINTENANCE MANUAL. IDENTIFY REQUIRED MAINTENANCE ACTIONS. EQUIP EQUIPMENT SRW SUPPLY REGISTER WALL MECHANICAL EQUIPMENT FURNISHED BY INSTALLED BY ESP EXTERNAL STATIC PRESSURE STD STANDARD Ɣ NAME AND ADDRESS OF SERVICING AGENCY. AC-1 - AIR CONDITIONER GAS HEAT OWNER MECHANICAL CONTRACTOR EWT ENTERING WATER TEMPERATURE STRUCT STRUCTURE EXH EXHAUST SUP SUPPLY Ɣ HVAC CONTROL SYSTEM MAINTENANCE AND CALIBRATION INFORMATION. (WIRING DIAGRAMS, SCHEMATICS, CONTROL SEQUENCES AC-2 - AIR CONDITIONER GAS HEAT OWNER MECHANICAL CONTRACTOR EXT EXTERIOR DESCRIPTIONS) AC-3 - AIR CONDITIONER GAS HEAT OWNER MECHANICAL CONTRACTOR TGC TRANSFER GRILLE CEILING FC FLEXIBLE CONNECTOR Ɣ CLEARLY INDICATED FIELD DETERMINED SET POINT TRANS TRANSITION EF-1 - EXHAUST FAN MECHANICAL CONTRACTOR MECHANICAL CONTRACTOR FD FLOOR DRAIN TSP TOTAL STATIC PRESSURE Ɣ SYSTEM NARRATIVE ON INTENDED OPERATIONS EF-2 - not used ------FIN FINISHED TYP TYPICAL FLEX FLEXIBLE EF-3 - EXHAUST FAN OWNER MECHANICAL CONTRACTOR Ɣ NAME AND ADDRESS OF CONTRACTOR, SUBCONTRACTORS, EQUIPMENT SUPPLIERS, AND DESIGN ENGINEER (H.F. LENZ COMPANY) FLR FLOOR VCD VOLUME CONTROL DAMPER EF-4 - EXHAUST FAN OWNER MECHANICAL CONTRACTOR FR FROM VEL VELOCITY Ɣ TEST AND BALANCE REPORT. VERT VERTICAL EF-4M - MAKE UP FAN GAS HEAT OWNER MECHANICAL CONTRACTOR GA GAUGE EF-5 - EXHAUST FAN OWNER MECHANICAL CONTRACTOR GALV GALVANIZED W/ WITH 29. CONTRACTOR SHALL IN THE PRESENCE OF THE ENGINEER OF RECORD DEMONSTRATE EQUIPMENT OPERATIONS, SYSTEM TO SYSTEM W/O WITHOUT INTERFACING RELATIONSHIPS, AND DEMONSTRATE CONTROL OPERATIONS AS REQUIRED BY CODE. CD-1 - CEILING DIFFUSER MECHANICAL CONTRACTOR MECHANICAL CONTRACTOR HC HEATING CONTRACTOR SRW-1 - SIDEWALL REGISTER MECHANICAL CONTRACTOR MECHANICAL CONTRACTOR HOA HAND OFF AUTOMATIC HORIZ HORIZONTAL RCD-1 - RADIAL CEILING DIFFUSER MECHANICAL CONTRACTOR MECHANICAL CONTRACTOR AUDIBLE / VISIBLE OWNER MECHANICAL CONTRACTOR RG-1 - RETURN GRILLE MECHANICAL CONTRACTOR MECHANICAL CONTRACTOR EG-1 - EXHAUST GRILLE MECHANICAL CONTRACTOR MECHANICAL CONTRACTOR STIFFENED INSULATION SEE 3/8" SQUARE AXLE SHAFT BLADE AS SPECIFICATION TGC-1 - TRANSFER GRILLE CEILING MECHANICAL CONTRACTOR MECHANICAL CONTRACTOR REQUIRED DUCT T T - THERMOSTAT OWNER MECHANICAL CONTRACTOR OUTSIDE END BEARING INSULATION RECTANGULAR DUCT REINFORCEMENT RTS - REMOTE TEMPERATURE SENSOR OWNER MECHANICAL CONTRACTOR STAND-OFF HS - HUMIDITROL SENSOR OWNER MECHANICAL CONTRACTOR BRACKET DUCTWORK IS 2"W.G. STATIC UP TO 30" DIMENSION, MINIMUM RIGIDITY CLASS E, vcd - volume control damper mechanical contractor MECHANICAL CONTRACTOR DAMPER BLADE MINIMUM 24 GAGE, WITH MINIMUM REINFORCEMENT SPACING OF 5'. H HANDLE WITH H LOCKING DETAIL IS MINIMUM CONSTRUCTION FOR DUCTWORK. ALTERNATIVE METHODS SHALL BE QUADRANT SUBMITTED TO ENGINEER FOR APPROVAL. INSIDE END BEARING DAMPER BLADE 1/8" CLEARANCE SIDE ELEVATION ALL AROUND SECTION SCALE: NO SCALE H NOTE: ANGLE T-10 STANDING S DATE: 09-03-15 1. DELETE INSULATION STAND-OFF BRACKET ON DUCTWORK WITHOUT EXTERIOR INSULATION. REINFORCEMENT CLASS - E REINFORCEMENT CLASS - E COLD FORMED (H) 1 1/4 x (T) 12 GA (H) 1 1/8 x 18 GA 2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR DRAWN BY: RCM HOT ROLLED - (H) 1 x (T) 1/8 ROUND DAMPERS FILENAME: M-1 INTERMEDIATE REINFORCEMENT TRANSVERSE JOINT REINFORCEMENT Corporate Headquarters VOLUME CONTROL DAMPER DETAIL 615 West Highland Avenue Ebensburg, PA 15931 phone (814) 472-7700 fax (814) 472-7712 email [email protected] M-1 web site www.lrkimball.com ” CDI-Infrastructure, LLC dba L.R. Kimball