<<

Synchronous Machines Construction 1. - (Same as the stator of an Induction Machine) 2. - Field Winding ( DC Field) Generator I As a generator, this machine is widely used. I This is the machine which is used in all conventional power plants. I A synchronous generator is called as an .

Motor I Since it runs only at synchronous speed, it is not widely used as a motor but for certain applications like electric . I However, it is used to either produce or absorb reactive power. Construction

1. Stator I It is a distributed winding. I The windings of each phase are distributed over several slots. I Three phase windings are wound 120◦ (electrical angle) apart in space 2. Rotor I It is excited by a DC current. There are two types. 2.1 Cylindrical Rotor - used where the turbine speed is high 2.2 Salient Pole Rotor - used where the turbine speed is low Synchronous machine is a doubly excited machine.

We can have field winding placed in stator and armature winding in rotor. This type is called an inverted synchronous machine. Synchrnous Generator

B

2π θe

2π θm

e

ωt B

4π(θe )

2π(θm)

e

ωt

In general P θ = θ e 2 m Source: A. E. Fitzgerald, et.al., “ Electric Machinery” v

ωt

In a 2-pole machine, one revolution makes one cycle of alternating voltage. In a P-pole machine, 1 P 1 revolution/min × cycle/sec 60 2 N P N rpm × cycle/sec 60 2 PN f = Hz 120 The flux linkage with stator coil a is

λa = Nφf cos ωt

Where N is the number of turns in each pahse and φf is the flux per pole due to excitation current If . By Faraday’s law, the voltage induced in phase a is dλ e = − a = ωNφ sin ωt a dt f The rms value in voltage is

Ea = 4.44fNφf

φf

E I The field winding is excited by DC. I When the rotor rotates, the field will revolve in the air gap. I The revolving field induces an emf in the armature winding placed in the stator. I The speed of the field (N) is determined by the of induced voltage. PN f = Hz 120 I Rotor and field due to field winding rotate at the same speed called the synchrnous speed. I When the stator terminals are connected to a load, a three phase armature current flows out of the machine. I When a three phase balanced current flows in the three phase armature winding, a revolving mmf is produced whose speed is

120f N = rpm P I The field due to armature current also rotates at the synchronous speed in the air gap.

I Finally the net air gap field is the resultant of field due to If and stator current Ia.

Fr = Ff + Fa

φr = φf + φa

I The resultant and component fluxes rotate in the air gap at the same speed. φf E φr

θ E

If

φa Figure: OCC Ia Figure: Field diagram Equivalent Circuit

Since the operation is balanced, the per phase equivalent circuit of a synchronous machine is

Xar Xal Ra +

+ E Vt −

where Xar is the reactance of armature reaction. Xal is the leakage reactance. Ra is the armature resistance. Xs Ra Ia +

+ E Vt −

The synchronous reactance

Xs = Xar + Xal

The synchronous impedance

Zs = Ra + Xs

E = Vt + Ia(Ra + Xs ) Determination of Xs Open Circuit Test :

R

+

Field V E

If − N V + f −

Y

B

Vary If and measure E. Repeat till E reaches its rated value. Short Circuit Test :

Ia R A

Field

If

V + f −

Y

B

Vary If and measure Ia. Repeat till Ia reaches its rated value. The open circuit characteristics is a non linear curve. However, the short circuit characteristics is a straight line because the flux inside the machine is low (no saturation).

φf

Xs Ra Ia φr

+ E E − θ

φa Figure: SC Test Ia Figure: Field diagram E Ia

Eda d

OCC V t c SCC I b a

a If I Unsaturated synchronous impedance,

Eda Zs(unsat) = Ia

If Ra is known, Xs(unsat) can be found. q 2 2 Xs(unsat) = (Zs(unsat)) − Ra

I Saturated synchronous impedance,

Vt Zs(sat) = == Ra + Xs(sat) Ia

If Ra is known, Xs(sat) can be found. q 2 2 Xs(sat) = (Zs(sat)) − Ra

Saturated synchronous reactance Xs is normally used in calculations. Alternator - Phasor Diagrams

E

IaXs δ φ Vt IaRa Ia Figure: lagging load

E

IaXs

δ

Ia Vt IaRa Figure: unity power factor load E I X Ia a s δ φ IaRa Vt Figure: leading power factor load

In

I E leads Vt by δ. δ is positive. I This δ is also the angle between the main field φf and the resultant field φr .

I φf leads φr by δ. Let us neglect Ra.

φf

φa φr

δ E

IaXs δ

φ Vt

Ia Figure: Alternator supplies a lagging power factor load - Field diagram Synchronization of Alternators

R RGrid

L1

Field Y YGrid If L2

V + f − L3

B BGrid The alternator and the grid must have the same 1. Voltage 2. Frequency 3. Phase Sequence 4. Phase I When all the above conditions are satisfied, the three lamps will be dark. It is time to close the switch. I Once it is synchronized, the terminal voltage and frequency of the alternator can not be changed. I By changing the prime mover speed, Real Power (P) can be controlled. I By changing the excitation, Reactive Power (Q) and hence power factor can be controlled. Power Characteristic It always works with an infinite bus.

Xs Ra Ia +

+ ◦ E δ Vt 0 −

Figure: Per phase equivalent circuit

To find the power delivered by the alternator,

∗ S = Vt Ia  ◦ ∗ ◦ (E δ − Vt 0 ) S = Vt 0 |Zs | θ EV θ − δ V 2 θ S = t − t |Zs | |Zs | By taking Real and Imaginary parts,

EV cos(θ − δ) V 2 cos(θ) P = t − t |Zs | |Zs |

EV sin(θ − δ) V 2 sin(θ) Q = t − t |Zs | |Zs | ◦ If we neglect Ra, |Zs | = |Xs | and θ = 90 .

EV sin δ P = t Xs

EV cos δ V 2 Q = t − t Xs Xs Three phase real and Reactive power

EVt sin δ P = 3 = Pmax sin δ Xs

EV cos δ V 2  Q = 3 t − t Xs Xs

P

Pmax

δ Figure: Power angle curve V - Curves:

Xs Ia + + ◦ E δ Vt 0 − − Figure: Per phase equivalent circuit

E

IaXs δ

φ Vt

Ia Figure: Supplying a lagging power factor load Let us keep the real power delivered constant and change the excitation. EVt sin δ P = = Vt Ia cos φ Xs where φ is the angle difference between Vt and Ia. if If is varied, Ef will vary (linearly if magnetic linearity is assumed). Since Vt is fixed,

E sin δ = const

Ia cos φ = const E2 E E1

Ia2Xs IaXs Ia1Xs δ Ia2

Ia cos φ sin E

Ia Vt

Ia1 Figure: Different excitation for a constant P

E1 sin δ1 = E sin δ = E2 sin δ2

Ia1 cos φ1 = Ia cos φ = Ia2 cos φ2 1. Over Excitation : E cos δ > Vt Alternator supplies lagging current and supplies reactive power. 2. Normal Excitation : E cos δ = Vt Alternator supplies unity power factor current and supplies zero reactive power. 3. Under Excitation : E cos δ < Vt Alternator supplies leading current and draws reactive power. If we plot Ia Vs If ,

Ia

P2

P1

P2 > P1

Under Excitation Over Excitation

leading pf lagging pf If Figure: V-Curves of an Alternator Example 1 : (Example 8.13 : Kothari) A 3φ, 10 kVA, 400 V, 4-pole, 50 Hz star connected synchronous machine has synchronous reactance of 16 Ω and negligible resistance. The machine is operating as generator on 400 V bus-bars (assumed infinite). 1. Determine the excitation emf (phase) and angle when the machine is delivering rated kVA at 0.8 pf lagging. 2. While supplying the same real power as in part (1), the machine excitation is raised by 20 %. Find the stator current, power factor, torque angle and reactive power delivered. 3. With the field current held constant as in part (1), the power (real) load is increased till the steady state power limit is reached. Calculate the maximum power and kVAR delivered and also the stator current and power factor. Draw the phasor diagram under these conditions. 1. P = 10 × 0.8 = 8kW (three phase) 8000 Ia = √ = 14.43 A 3 × 400 × 0.8 400 E δ = √ 0◦ + 14.43 −36.87◦ × 16 90◦ 3 E = 413.3 V (phase) δ = 26.5◦ 2. E1 = 1.2 × E = 496 V

E sin δ = E1 sin δ1 ◦ δ1 = 21.9 The stator current ◦ E1 δ1 − Vt 0 Ia1 = Xs ◦ Ia1 = 18.4 −50.9 A pf = 0.63 lagging √ Q = 3Vt Ia sin φ = 9.89 kVAR (3-phase) Q can also be found by the following formula.

EV cos δ V 2  Q = 3 t − t Xs Xs Q is positive which means the machine is supplying it. 3. E = 413.3 V When the real power reaches its maximum value, δ = 90◦.

EVt 413.3 × 231 Pmax = = = 5.96 kW/phase Xs 16

Pmax = 17.38 kW (3-phase) 413.3 90◦ − 231 0◦ I = = 29.56 29.2◦ A a 16 90◦ pf = 0.873 leading √ Q = 3×400×29.56×sin(−29.2◦) = −9.99 kVAR (3-phase) Since Q is negative, the machine is drawing it.

E IaXs

Ia δ φ

Vt Synchronous Motor

I Stator (armature) is connected to a three phase AC supply. I Rotor (field winding) is connected to a DC supply.

Unlike three phase induction motors and DC motors, synchronous motors are not self-starting. let us consider a 4-pole synchronous machine. I When the three phase armature winding (stator) is supplied with a three phase balanced supply, It produces a rotating mmf in the air gap whose speed is the synchronous speed 120f N = s P

For a 4-pole machine and 50 Hz supply, Ns =1500 rpm. I When the field winding (rotor) is excited by DC, it will produce a stationary field. I When the revolving field rotates, the rotor experiences torque and is trying rotate in the direction of revolving filed. I Due to inertia of the rotor, rotor filed poles have hardly moved. By the time stator poles have moved. I Therefore, the rotor experiences torque in the opposite direction. I Hence there is no net torque and the motor will not develop any starting torque.

Source: P. C. Sen, “Principles of Electric Machines and Power Electronics” Methods of Starting

1. Use a variable frequency supply I The motor is started with a low frequency supply. I This will make stator field move slowly so that the rotor can follow. I Then the frequency is gradually increased. 2. Start as an induction machine I Synchronous machines normally have damper or amortisseur winding mounted on the rotor. I Do not excite the rotor. I If the stator is connected to the three phase ac supply, the machine will start as . I After reaching the steady speed (Nr < Ns ), excite the rotor with the DC supply. I The rotor will get locked to the revolving field and rotate at Ns . I At Ns , damper winding will get no induced emf (no relative motion). Figure: Synchronous Machine Rotor

Source: A. E. Fitzgerald, et. al., “Electric Machinery” Synchronous Motor - Equivalent Circuit

Xs Ra Ia +

+ E Vt −

E = Vt − Ia(Ra + Xs ) Synchronous Motor - Phasor Diagrams

IaRa φ δ V E t IaXs Ia Figure: lagging current

δ Ia IaRa Vt

E IaXs Figure: unity power factor current Ia φ V δ t IaRa E IaXs Figure: leading current

In Syn. Motors

I E lags Vt by δ. δ is negative. I This δ is also the angle between the main field φf and the resultant field φr .

I φf lags φr by δ. Let us neglect Ra.

φr φa φf

δ

Vt φ δ

Ia E IaXs Figure: Syn. Motor draws a lagging current - Field diagram Torque Characteristics

P T = 3φ ωs 2πN where ω is the synchronous speed in rad/sec. ω = s s s 60 3EVt sin δ T = = Tmax sin δ Nm ωs Xs

T T

Tmax

Ns N (rpm)

δ Figure: Torque angle curve Figure: Torque speed curve Power Factor Control

Xs Ia + + ◦ E −δ Vt 0 − − Figure: Per phase equivalent circuit

φ δ Vt

Ia E IaXs Figure: Drawing a lagging current Let us keep the real power supplied to the motor constant and change the excitation.

EVt sin δ P = = Vt Ia cos φ Xs if If is varied, Ef will vary (linearly if magnetic linearity is assumed). Since Vt is fixed,

E sin δ = const

Ia cos φ = const Ia1

Vt Ia δ

Ia2 sin

E2 E1 E Ia cos φ E Ia2Xs IaXs Ia1Xs Figure: Different excitation

E1 sin δ1 = E sin δ = E2 sin δ2

Ia1 cos φ1 = Ia cos φ = Ia2 cos φ2 1. Over Excitation : E cos δ > Vt Syn. motor draws leading current and supplies reactive power. 2. Normal Excitation : E cos δ = Vt Syn. motor draws unity power factor current and draws zero reactive power. 3. Under Excitation : E cos δ < Vt Syn. motor draws lagging current and draws reactive power. If we plot Ia Vs If ,

Ia

P2

P1

P2 > P1

Under Excitation Over Excitation

lagging pf leading pf If Figure: V-Curves of a Syn. Motor Synchronous Condenser

Xs + + E Vt − −

Let us vary the excitation. Since Vt is fixed, Ia2

E1 E E2 Vt Ia1Xs Ia2Xs

Ia1 Figure: Phasor diagram - Generator Convention Ia1

E1 E E2 Vt Ia1Xs Ia2Xs

Ia2 Figure: Phasor diagram - Motor Convention

I An overexcited unloaded synchronous machine supplies a pure lagging current (draws a pure leading current). I An under excited unloaded synchronous machine supplies a pure leading current (draws a pure lagging current). When the synchronous machine is not transferring any real power, I its power factor is zero. I the stator current either leads or lags the voltage by 90◦. I the magnitude of the stator current can be changed by changing the excitation. I it behaves like a variable inductor or capacitor.

An unloaded synchronous machine is called synchronous condenser and is used to improve the power factor of the system. Example 2 : A 3φ, 10 kVA, 400 V, 4-pole, 50 Hz star connected synchronous machine has synchronous reactance of 16 Ω and negligible resistance. The machine is operating as a motor on 400 V bus-bars (assumed infinite). The field excitation is adjusted so that the power factor is unity when the machine draws 6 kW. 1. Determine the excitation emf and torque angle. Draw the phasor diagram. 2. If the field excitation is held constant and the shaft load is suddenly increased, determine the maximum torque that the motor can deliver. 1. P3φ = 6 kW; pf = 1 6 × 103 Ia = √ = 8.66 A 3 × 400 × 1 ◦ ◦ ◦ E = Vt − IaXs = 231 0 − 8.66 0 × 16 90 E = 269.37 −30.96◦ V (phase)

δ Ia Vt

E IaXs 2. Maximum torque will be developed at δ = 90◦.

3 × 231 × 269.37 P = = 11.67 kW max (3φ) 16

11.67 × 103 T = = 74.28 Nm max 2 × π × 1500/60