Evaluation of Air Mixing and Thermal Comfort From High Sidewall Supply Air Jets
El Hassan Ridouane
NREL is a national laboratory of the U.S. Department of Energy, Office of Energy Efficiency & Renewable Energy, operated by the Alliance for Sustainable Energy, LLC.
Technical Report NREL/TP-5500-48664 September 2011 Contract No. DE-AC36-08GO28308
Evaluation of Air Mixing and Thermal Comfort From High Sidewall Supply Air Jets
El Hassan Ridouane Prepared under Task No. BE11.0102
NREL is a national laboratory of the U.S. Department of Energy, Office of Energy Efficiency & Renewable Energy, operated by the Alliance for Sustainable Energy, LLC.
National Renewable Energy Laboratory Technical Report 1617 Cole Boulevard NREL/TP-5500-48664 Golden, Colorado 80401 September 2011 303-275-3000 • www.nrel.gov Contract No. DE-AC36-08GO28308
NOTICE
This report was prepared as an account of work sponsored by an agency of the United States government. Neither the United States government nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States government or any agency thereof. The views and opinions of authors expressed herein do not necessarily state or reflect those of the United States government or any agency thereof.
Available electronically at http://www.osti.gov/bridge
Available for a processing fee to U.S. Department of Energy and its contractors, in paper, from:
U.S. Department of Energy Office of Scientific and Technical Information P.O. Box 62 Oak Ridge, TN 37831-0062 phone: 865.576.8401 fax: 865.576.5728 email: mailto:[email protected]
Available for sale to the public, in paper, from:
U.S. Department of Commerce National Technical Information Service 5285 Port Royal Road Springfield, VA 22161 phone: 800.553.6847 fax: 703.605.6900 email: [email protected] online ordering: http://www.ntis.gov/help/ordermethods.aspx
Cover Photos: (left to right) PIX 16416, PIX 17423, PIX 16560, PIX 17613, PIX 17436, PIX 17721
Printed on paper containing at least 50% wastepaper, including 10% post consumer waste.
Nomenclature
ACH Air changes per hour ADPI Air diffusion performance index 2 Ac Room ceiling area, ft 2 Af Room floor area, ft 2 Aw Exterior wall area, ft 2 Ao Area of supply inlet, ft CFD Computational fluid dynamics PMV Predicted mean vote PPD Predicted percentage of dissatisfied 2 Ceiling heat flux, Btu/h·ft 2 Room load density, Btu/h·ft 2 Exterior wall heat flux, Btu/h·ft Total heat transfer rate into the room, Btu/h Q flow rate from supply inlet, cfm 2 Ceiling R-value, ft ·h·˚F/Btu 2 Exterior wall R-value, ft ·h·˚F/Btu SHGC Solar heat gain coefficient
TS Supply air temperature, ˚F
Tset Thermostat set point, ˚F
VS Supply air velocity, fpm
Vx Local air velocity, fpm X Throw of the inlet jet, ft θ Effective draft temperature, ˚F
Acknowledgments
The author thanks Ren Anderson for his guidance and for his valuable contributions to this report.
iii Executive Summary
Effective mixing of conditioned air with room air is an essential factor for providing uniform comfort in homes. The higher the supply air flow rates, the easier it is to reach good mixing within the space. In high performance homes, however, the flow rates required to meet the small remaining thermal loads may not be large enough to maintain uniform mixing in the space. The objective of this study is to evaluate operating conditions required to maintain uniform mixing, within high performance homes, under both heating and cooling conditions. This can be achieved by creating proper combination of temperature and air motion in the occupied zone of the conditioned space. Lack of uniform conditions in the space or excessive fluctuation of conditions produces discomfort. Discomfort can be caused by excessive air motion (draft), excessive room air temperature variations, or failure to deliver or distribute air according to load requirements. To address this question we used computational fluid dynamics modeling to evaluate the performance of high sidewall air supply for residential applications in heating and cooling modes. Parameters that were varied in the study include the supply velocity, supply temperature, and inlet dimensions. The model provided high resolution velocity and temperature distributions in the room, which were used to determine the effective draft temperature. The latter is then used to calculate the Air Diffusion Performance Index (ADPI). This parameter was used to evaluate the air distribution and thermal comfort in the occupied zone. ADPI is the percentage of locations where the effective draft temperature and air speed meet comfort specifications. The higher the ADPI value is, the more comfortable the space will be for most occupants. The results provide information to guide the selection of high sidewall air supply inlets to maintain proper room mixing for heating and cooling of high performance homes. It is demonstrated that these systems can achieve good mixing and provide acceptable comfort levels. Recommendations are given for the operating conditions to guarantee occupant comfort.
iv Contents
Nomenclature ...... iii Acknowledgments...... iii Executive Summary ...... iv Contents ...... v Background ...... 1 Problem Definition...... 3 Approach ...... 3 Methodology ...... 4 Model Setup ...... 5 Conditioning Jet Performance Metrics ...... 7 Results and Discussion ...... 8 Heating Mode...... 8 Cooling Mode ...... 16 Conclusions ...... 25 Heating Mode...... 25 Cooling Mode ...... 26 References ...... 29
Tables
Table A. Reference house construction type and assumptions used to calculate loads ...... 4 Table B. Recommended System Operating Conditions ...... 28
v Figures
Figure 1. Sketch of the computational domain (not to scale) showing the locations of supply, return, and thermostat in the room. Thermal loads are applied only to the ceiling and to the right wall to approximate load distributions in a perimeter zone...... 6 Figure 2. Time history of air temperature near the thermostat (a) and velocity at the inlet (b) from an 8×1 inlet when supplied by Ts of 120°F (322 K) ...... 9 Figure 3. Air temperature near the thermostat (a) and velocity at the inlet from an 8×4 inlet (b) as a function of time when supplied by Ts of 120°F (322 K) ...... 10 Figure 4. Temperature distribution at the symmetry plane of the room with an 8×4 inlet when supplied by Ts of 120°F (322 K): (a) Vs = 558 fpm (2.83 m/s) and (b) Vs = 714 fpm (3.62 m/s) 11 Figure 5. Temporal evolution of air temperature near the thermostat (a) and supply velocity at the inlet (b) of the room with 8×4 inlet when supplied by two different temperatures, 95ºF (308 K) and 120°F (322 K) with Vs = 558 fpm (2.83 m/s) ...... 12 Figure 6. Temperature distribution in the room, with an 8×4 supply inlet, at 1 air change when supplied by Ts of 95 F (308 K): (a) Vs = 214 fpm (1.1 m/s), (b) Vs = 558 fpm (2.83 m/s), and (c) Vs = 714 fpm (3.62 m/s). Left plots are at the symmetry plane and right plots are at different cross sections throughout the room...... 13
Figure 7. Distribution of draft temperature in the room, with an 8×4 inlet, when TS = 95˚F (308 K): (a) VS = 214 fpm (1.1 m/s), (b) VS = 558 fpm (2.83 m/s), and (c) VS = 714 fpm (3.62 m/s). Top row shows the draft temperature at full scale and the bottom row shows acceptable draft temperature, between -3 and 2˚F...... 14 Figure 8. Temporal evolution of air temperature near the thermostat and the supply velocity at the 10×6 inlet when the room is supplied by Vs = 329 fpm (1.67 m/s) and Ts = 95°F (308 K) ... 15 Figure 9. Temperature distribution in the room, with a 10×6 inlet, at 1 air change when supplied by Ts of 95°F (308 K): (a) Vs = 329 fpm (1.67 m/s) and (b) Vs = 788 fpm (4 m/s). Left plots are at the symmetry plane and right plots are at different cross sections throughout the room ...... 16 Figure 10. Temporal evolution of air temperature near the thermostat (a) and supply velocity at the inlet (b) of the room with 8×1 inlet when supplied by two different velocities, 591 fpm (3 m/s) and 788 fpm (4 m/s) with Ts = 55 ˚F (286 K) ...... 17 Figure 11. Temperature distribution in the room, with an 8×1 inlet, at 1 air change when supplied by Ts of 55°F (286 K): (a) Vs = 591 fpm (3 m/s) and (b) Vs = 788 fpm (4 m/s). Left plots are at the symmetry plane and right plots are at different cross sections along the room ...... 18 Figure 12. Temporal evolution of air temperature near the thermostat (a) and supply velocity at the inlet (b) of the room with 8×4 inlet when supplied by two different velocities, 394 fpm (2 m/s) and 591 fpm (3 m/s) with Ts = 55 ˚F (286 K) ...... 19 Figure 13. Temperature distribution at the symmetry plane of the room, with an 8×4 inlet, when Vs = 788 fpm (4 m/s) and Ts = 55°F (285.9 K) ...... 20 Figure 14. Temperature distribution in the room, with an 8×4 inlet, at 1 air change when supplied by Vs = 591 fpm (3 m/s): (a) TS = 55˚F (285.9 K) and (b) TS = 65˚F (291.5 K) ...... 21
vi Figure 15. Distribution of draft temperature in the room, with an 8×4 inlet, when TS = 55˚F (285.9 K): (a) VS = 394 fpm (2 m/s), (b) VS = 591 fpm (3 m/s), and (c) VS = 788 fpm (4 m/s).Top row shows the draft temperature at full scale and the bottom row shows the acceptable draft temperature, between -3 (-1.7) and 2˚F (1.1 K)...... 22 Figure 16. Temporal evolution of air temperature near the thermostat when the room is supplied by a 10×6 inlet at Vs = 788 fpm (4 m/s) ...... 23 Figure 17. Temperature distribution (a–c) and velocity vectors (d) at the symmetry plan of the room, with a 10×6 inlet: (a) VS = 329 fpm (1.67 m/s), (b) VS = 558 fpm (2.83 m/s), and (c–d) VS = 788 fpm (4 m/s). The supply temperature is 55°F (285.9 K)...... 24 Figure 18. Capacity of different systems relative to peak load in heating mode: (a) 8×1 inlet, (b) 8×4 inlet, and (c) 10×6 inlet...... 25 Figure 19. Variations of ADPI as a function of supply velocity in heating mode: (a) 8×1 inlet, (b) 8×4 inlet, and (c) 10×6 inlet...... 26 Figure 20. Capacity of different systems relative to peak load in cooling mode: (a) 8×1 inlet, (b) 8×4 inlet, and (c) 10×6 inlet...... 27 Figure 21. Variations of ADPI as a function of supply velocity in cooling mode: (a) 8×1 inlet, (b) 8×4 inlet, and (c) 10×6 inlet...... 28
All figures in this report were produced by NREL employees.
vii Background Understanding indoor air distribution and the draft risk in the occupied zone are essential to the design of HVAC systems. Thermal comfort of occupants is directly affected by indoor air velocity. Therefore air velocity is specified in the common thermal comfort indices such as the predicted mean vote (PMV), the predicted percentage of dissatisfied (PPD), and the air diffusion performance index (ADPI) (Chow and Wong, 1994). Evaluation of the location where the jet enters the room is also necessary to minimize the draft risk (Corgnati et al., 2002).
Numerous studies were carried out in the past two decades to predict indoor airflow patterns using two main approaches: experimental investigation and numerical calculation. Experimental models have been widely used for predicting air distribution performance in buildings. Chow and Wong (1994) studied the air speed induced by a diffuser in an environmental chamber under different flow conditions. The measurements showed no obvious correlation between ADPI and the supply flow rate. The diffuser throw was found to be linearly related to the Archimedes number, which represents the ratio of buoyancy to inertial force exerted on the fluid. Yu et al. (2007) studied airflow in a ceiling slot-ventilated enclosure in a 1:3 scale model. They measured the velocity and temperature profiles, temperature decays, and thermal boundary layers. The data was used to develop empirical models. Zang et al. (2009) used an environmental chamber to mimic a section of an airliner cabin. The experimental model used tracer gas and particles for contaminant transport simulation. The experiment approximated thermo-fluid boundary conditions and simulated passengers by heated boxes. Ultrasonic anemometers were used to measure the air velocity, temperature distribution, and contaminants concentration.
Full scale experimental models limit simplifying assumptions associated with small scale and analytical models. However, they are generally expensive and time consuming and can not easily cover all possible operating conditions. There is a growing trend that consists of using laboratory experiments to obtain data to validate computer models, and then use the validated models to predict ventilation performance or design of HVAC systems (Chen, 2009). Corgnati et al. (2009) performed a numerical study in cooling mode, using CFD, which was validated against experimental data from a full scale test room, simulating a typical two-desk office. The numerical study was then extended to couple mixing ventilation and cold radiant ceiling panels. The results showed that the use of coupled systems led to an increase in the jet throw and to a significant decrease of the draft risk.
Pure numerical studies were most popular and dominate the research literature in the past decade. CFD models in particular have been widely used to study indoor air distribution, air quality, thermal comfort, and HVAC system performance. Norton et al. (2006, 2007) conducted reviews of CFD applications for ventilation studies in food and agricultural industry such as green houses and animal production facilities. Three different air diffusion models were investigated by Chung and Lee (1996) in cooling mode. These include a room with one inlet – one outlet, two inlets – one outlet, and one inlet – two outlets. Evaluation of thermal comfort is made in terms of the percentage dissatisfied (PD) and the air diffusion performance index (ADPI). Variations of PD and ADPI with the inlet velocity and temperature showed that a higher PD or lower ADPI is associated with a higher velocity and lower inlet temperature. This study also underscores the importance of inlet/outlet locations for evaluating indoor thermal comfort.
1 CFD program EXACT3 has been used by Lam and Chan (2001) to analyze the temperature distribution and air movement within an air-conditioned gymnasium. Different exhaust positions were considered, sharing one inlet located high on a sidewall. The effects of thermal stratification on the energy performance were examined with respect to the HVAC plant oversizing issue. The smallest cooling load requirement was found in the configuration with ceiling exhaust. This configuration was identified, in terms of energy efficiency, as the best design arrangement. CFD models have also been used to improve other building simulation tools so that ventilation performance can be more accurately predicted (Chen, 2009). Wang and Chen (2007) coupled CFD with a multizone airflow program to improve the prediction of airflow and contaminant in an entire building.
This study evaluates the thermal performance of high sidewall inlet jets in heating and cooling modes using CFD. The three dimensional model considers a single room in a high performance home and evaluates the thermal comfort as a function of operating conditions. This report describes details of the numerical model, discusses the simulation results and provides recommendations for improving thermal comfort in energy efficient homes.
2 Problem Definition
The development of air distribution systems for very low load homes is an integral part of residential system research and development in systems integration. As American homes begin to reach high energy savings levels, space conditioning systems will be downsized to the point where the air flow volumes required to meet the small remaining heating and cooling loads may be too small to maintain uniform room air mixing. Most important are concerns about thermal comfort, which can be affected by poor distribution of conditioned air at reduced design flow rates.
American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE 2009, 2010) and Air Conditioning Contractors of America (ACCA Manual T 1992, ACCA Manual D 1995) provide overall design guidance documents for conventional homes; however, these have limitations and discrepancies. Room air distribution design guidelines need to be developed to address these. The guidelines should also be appropriate for heating and cooling operation in high performance homes. Good air mixing for heating/cooling is not guaranteed for a system that might work well in both cooling and heating modes, particularly under part-load conditions.
Well-designed high sidewall inlet jets are one of the simplest and most promising approaches for delivering conditioned air in high-performance homes because they are not blocked by furniture and can provide uniform air mixing of the conditioned air within the space. The system of interest incorporates a high sidewall supply air inlet and a low return air directly below. Potential poor air mixing is possible with this type of air distribution particularly in heating mode. Because of the reduced design flow rate of HVAC systems, stratification may form in energy efficient homes.
Approach
We used computational fluid dynamics modeling to evaluate the performance of high sidewall air supply inlets in heating and cooling seasons. We simulated three air inlet sizes: 8-in. (0.2 m) × 1-in. (0.025 m), 8-in. (0.2 m) × 4-in. (0.1 m) and 10-in. (0.25 m) × 6-in. (0.15 m). For each inlet, we varied the supply velocity and supply temperature and controlled the supply via a thermostat set at 71ºF (294.81K). Simulations ended when 1 air change was supplied to the room and the performance of the three inlets was then compared for heating and cooling modes. At the end of each simulation, thermal comfort is evaluated by determining the Air Diffusion Performance Index (ADPI). ADPI is defined in the occupied zone and is a thermal comfort criterion based on the air velocity and temperature distributions obtained from the numerical simulation output. The definition of the occupied zone and the criteria used in calculating ADPI are discussed in more details in Conditioning Jet Performance Metrics section. The thermal loads studied were applied as heat gain/loss through the exterior wall and ceiling and were considered to mimic peak load conditions. A wide range of system capacities was considered by varying the supply jet velocity and temperature.
3 Methodology
The finite volume method (software FLUENT 6.3, 2006) was used to model simple and representative room and inlet geometries, air supply flow rates, and temperatures. Details on the boundary conditions used are provided in the following section.
The model addressed peak loads that are representative of perimeter zones high-performance homes. Load densities of 14.6 Btu/h·ft2 (46.02 W/m2) for heating and 10 Btu/h·ft2 (31.52 W/m2) for cooling were applied. Load density is defined as the room thermal load divided by the room floor area. As a reference point, a Chicago house in January has a heating peak load density of about 14.5 Btu/h·ft2 (45.7 W/m2). For cooling in July, the same house in Phoenix has a cooling peak load density of about 11.2 Btu/h·ft2 (35.3 W/m2). These loads were calculated using BEoptE+ 1.1 (Christensen et al., 2006). Table A lists the thermal characteristics of the reference house, which are found in high performance homes. These densities were multiplied by the floor area and the outcome was distributed between the ceiling and at the exterior wall opposite to the air jet. The proportional thermal load distribution between the ceiling and the wall was based on their respective R-values. The room load density, , was used to determine the total rate of heat transfer into the room, as