Neutral Grounding Resistors Technical Information

Total Page:16

File Type:pdf, Size:1020Kb

Neutral Grounding Resistors Technical Information NEUTRAL GROUNDING RESISTORS TECHNICAL INFORMATION 1369 Cox Avenue Erlanger, KY 41018 USA Phone: 859-283-0778 Toll-Free: 800-537-6144 Fax: 859-283-2978 Web: www.postglover.com Serving the Electrical Industry Since 1892 Quality System Certified to ISO 9001 With over 130 years of combined industrial and utility experience, Post Glover delivers the industry’s strongest, broadest and most technologically advanced products available. Experienced Post Glover has grown into the world’s largest power resistor company, based on its industry leading positions in grounding solutions and dynamic braking resistors. Post Glover can be trusted to deliver cost- effective, reliable products to the marketplace. Efficient Post Glover’s factory in Erlanger, Kentucky integrates computer aided design and manufacturing with the industry’s strongest engineering team for greater manufacturing capabilities and efficiencies. Post Glover continues to improve through Kaizen events, third party certifications and regular audits of our internal practices. Focused Service The industry’s most experienced sales and engineering team and largest independent sales representative network insure a timely and accurate, same day response to your typical and complex applications. With 16 engineers on staff, we are poised to answer your product and application questions. Certified Products Post Glover prides itself on designing and manufacturing in accordance with all applicable standards, be they IEEE, ANSI, NEMA or IEC. Taking safety one step further, we offer the only UL listed high resistance grounding unit in the industry, as well as UL and CSA offerings in low resistance grounding resistors and dynamic braking resistors. Table of Contents Grounding of Industrial Power Systems ...................................................4 Definition of Grounding ................................................................................4 Characteristics of Ungrounded Systems .....................................................4 System Neutral Grounding ................................................................................5 Importance ...................................................................................................5 Solid Grounding ...........................................................................................5 Resistance Grounding .................................................................................6 • Low Resistance ...................................................................................6 • High Resistance...................................................................................6 Grounding Recap .....................................................................................................7 Comparative Performance Rating Table .....................................................7 Rating & Testing Neutral Grounding Resistors ....................................8 IEEE-32 Standards ......................................................................................8 Time Rating ................................................................................................. 8 Tests ............................................................................................................8 CSA Standards ............................................................................................9 Selection of Neutral Grounding Resistors............................................ 10 Factors to Consider ................................................................................... 10 The Selection Process ............................................................................... 10 Other Methods of Grounding ........................................................................ 12 Single Phase Transformer & Loading Resistor .......................................... 12 Grounding Transformers ............................................................................ 12 • Zigzag ................................................................................................ 13 • Wye-Delta .......................................................................................... 14 • Alternate Wye-Delta .......................................................................... 14 Specifications ......................................................................................................... 15 Neutral Grounding Resistors ..................................................................... 15 • High Voltage, Low Resistance ........................................................... 15 • Low or Medium Voltage, High Resistance ......................................... 16 Zigzag Grounding Transformers ................................................................ 17 Glossary of Terms ................................................................................................... 18 3 PGR Document #NG112-06 Grounding of Industrial Power Systems Definition of Grounding FIGURE 2 Phase A conductors The term grounding is commonly used in the electrical Phase B conductors industry to mean both “equipment grounding” and Phase C conductors “system grounding”. “Equipment grounding” means the connection of earth ground to non-current carrying conductive materials such as conduit, cable trays, Delta configuration junction boxes, enclosures and motor frames. “System grounding” means the deliberate connection of earth ground to the neutral points of current carrying the normal voltage is present on all insulation in the conductors such as the neutral point of a circuit, a system, as shown in Figure 3b. This situation can often transformer, rotating machinery, or a system, either cause failures in older motors and transformers, due to solidly or with a current limiting device. Figure 1 insulation breakdown. illustrates the two types of grounding. The interaction between the faulted system and FIGURE 1 its distributed capacitance may cause transient Metal enclosures overvoltages (several times normal) to appear from line to ground during normal switching of a circuit having To a line to ground fault (short). These overvoltages Source Neutral load may cause insulation failures at points other than the Bonding jumper original fault. In addition, a second fault on another SYSTEM phase may occur before the first fault can be cleared. Transformer bank GROUNDING This can result in very high line to line fault currents, equipment damage and disruption of both circuits. EQUIPMENT GROUNDING In addition to the cost of equipment damage, ungrounded systems present fault locating problems. Characteristics of Ungrounded Systems This involves a tedious process of trial and error, first isolating the correct feeder, then the branch, and finally An ungrounded system is one in which there is no the equipment at fault. The result is unnecessarily intentional connection between the conductors and lengthy and expensive downtime. earth ground. However, in any system, a capacitive coupling exists between the system conductors and Despite the drawbacks of an ungrounded system, the adjacent grounded surfaces. Consequently, the it does have one main advantage. The circuit may “ungrounded system” is, in reality, a “capacitively continue in operation after the first ground fault, grounded system” by virtue of the distributed assuming it remains as a single fault. This permits capacitance. This is shown in Figure 2. Under normal continued production, until a convenient shutdown can operating conditions, this distributed capacitance be scheduled for maintenance. causes no problems. In fact, it is beneficial, because it establishes, in Phase A and B are now at full effect, a neutral point for the system, FIGURE 3 line-to-line voltage above ground as shown in Figure 3a. As a result, the A B phase conductors are stressed at only Line-to-line voltage line-to-neutral voltage above ground. A B Each phase is at C However, problems can arise under line-to-neutral Neutral point Phase C is now at ground voltage above ground established potential. Virtually no fault current ground fault conditions. A ground C by distribution flows as there is no return fault on one line results in full line-to- capacitance path back to the source line voltage appearing throughout the (a) NORMAL OPERATION (b) GROUND FAULT ON PHASE C system. Thus, a voltage 1.73 times Voltage relationships 4 PGR Document #NG112-06 System Neutral Grounding Importance Advantages of Grounded Neutral Systems This section is devoted to the proven benefits of Resistance grounding is by far the most effective and proper system grounding, and in particular, the added preferred method. It solves the problem of transient advantages of resistance (current limited) grounding. overvoltages, thereby reducing equipment damage. It accomplishes this by allowing the magnitude of the The intentional connection of the neutral points of fault current to be predetermined by a simple ohms law transformers, generators and rotating machinery to calculation (see Table 1). Thus the fault current can be the earth ground network provides a reference point limited, in order to prevent equipment damage. of zero volts. This protective measure offers many advantages over an ungrounded system, including: Table 1 E I = Where: I = Limit of Fault Current • Reduced magnitude of transient overvoltages R • Simplified ground fault location E = Line-to-Neutral Voltage • Improved system and equipment fault of System protection R = Ohmic Value of Neutral • Reduced maintenance time and expense Grounding
Recommended publications
  • What Is a Neutral Earthing Resistor?
    Fact Sheet What is a Neutral Earthing Resistor? The earthing system plays a very important role in an electrical network. For network operators and end users, avoiding damage to equipment, providing a safe operating environment for personnel and continuity of supply are major drivers behind implementing reliable fault mitigation schemes. What is a Neutral Earthing Resistor? A widely utilised approach to managing fault currents is the installation of neutral earthing resistors (NERs). NERs, sometimes called Neutral Grounding Resistors, are used in an AC distribution networks to limit transient overvoltages that flow through the neutral point of a transformer or generator to a safe value during a fault event. Generally connected between ground and neutral of transformers, NERs reduce the fault currents to a maximum pre-determined value that avoids a network shutdown and damage to equipment, yet allows sufficient flow of fault current to activate protection devices to locate and clear the fault. NERs must absorb and dissipate a huge amount of energy for the duration of the fault event without exceeding temperature limitations as defined in IEEE32 standards. Therefore the design and selection of an NER is highly important to ensure equipment and personnel safety as well as continuity of supply. Power Transformer Motor Supply NER Fault Current Neutral Earthin Resistor Nov 2015 Page 1 Fact Sheet The importance of neutral grounding Fault current and transient over-voltage events can be costly in terms of network availability, equipment costs and compromised safety. Interruption of electricity supply, considerable damage to equipment at the fault point, premature ageing of equipment at other points on the system and a heightened safety risk to personnel are all possible consequences of fault situations.
    [Show full text]
  • Notes for Lab 1 (Bipolar (Junction) Transistor Lab)
    ECE 327: Electronic Devices and Circuits Laboratory I Notes for Lab 1 (Bipolar (Junction) Transistor Lab) 1. Introduce bipolar junction transistors • “Transistor man” (from The Art of Electronics (2nd edition) by Horowitz and Hill) – Transistors are not “switches” – Base–emitter diode current sets collector–emitter resistance – Transistors are “dynamic resistors” (i.e., “transfer resistor”) – Act like closed switch in “saturation” mode – Act like open switch in “cutoff” mode – Act like current amplifier in “active” mode • Active-mode BJT model – Collector resistance is dynamically set so that collector current is β times base current – β is assumed to be very high (β ≈ 100–200 in this laboratory) – Under most conditions, base current is negligible, so collector and emitter current are equal – β ≈ hfe ≈ hFE – Good designs only depend on β being large – The active-mode model: ∗ Assumptions: · Must have vEC > 0.2 V (otherwise, in saturation) · Must have very low input impedance compared to βRE ∗ Consequences: · iB ≈ 0 · vE = vB ± 0.7 V · iC ≈ iE – Typically, use base and emitter voltages to find emitter current. Finish analysis by setting collector current equal to emitter current. • Symbols – Arrow represents base–emitter diode (i.e., emitter always has arrow) – npn transistor: Base–emitter diode is “not pointing in” – pnp transistor: Emitter–base diode “points in proudly” – See part pin-outs for easy wiring key • “Common” configurations: hold one terminal constant, vary a second, and use the third as output – common-collector ties collector
    [Show full text]
  • Review of Ground Fault Protection Methods for Grounded, Ungrounded, and Compensated Distribution Systems
    REVIEW OF GROUND FAULT PROTECTION METHODS FOR GROUNDED, UNGROUNDED, AND COMPENSATED DISTRIBUTION SYSTEMS Jeff Roberts, Dr. Hector J. Altuve, and Dr. Daqing Hou Schweitzer Engineering Laboratories, Inc. Pullman, WA USA ABSTRACT This paper reviews ground fault protection and detection methods for distribution systems. First, we review and compare medium-voltage distribution-system grounding methods. Next, we describe directional elements suitable to provide ground fault protection in solidly- and low- impedance grounded distribution systems. We then analyze the behavior of ungrounded systems under ground fault conditions and introduce a new ground directional element for these systems. Then we examine the behavior of compensated systems during ground faults and describe traditional fault detection methods. We conclude by introducing new ground fault detection methods for compensated systems. INTRODUCTION Ground fault current magnitudes depend on the system grounding method. Solidly- and low- impedance grounded systems may have high levels of ground fault currents. These high levels typically require line tripping to remove the fault from the system. Ground overcurrent and directional overcurrent relays are the typical ground fault protection solution for such systems. However, high-impedance ground fault detection is difficult in multigrounded four-wire systems, in which the relay measures the ground fault current combined with the unbalance current generated by line phasing and configuration and load unbalance. Ungrounded systems have no intentional ground. For a single-line-to-ground fault on these systems, the only path for ground current to flow is through the distributed line-to-ground capacitance of the surrounding system and of the two remaining unfaulted phases of the faulted circuit.
    [Show full text]
  • Advanced Power Transformer Diagnostics – Detection of Core-Ground Issues
    CIGRE-346 2020 CIGRE Canada Conference Toronto, Ontario, October 19-22, 2020 Advanced Power Transformer Diagnostics – Detection of Core-Ground Issues ALI NADERIAN JAHROMI1, PRANAV PATTABI1, JAFAR MOHAMMADI1, MOHSEN TANGSIRI2 1METSCO Energy Solutions, Canada 2MS Hydro Power Plant, Iran SUMMARY The typical construction of a power transformer results in a high potential being induced in the core, due to the electromagnetic coupling that exists between the core and winding assembly. The transformer core is normally grounded at a single point, to safely divert this induced voltage to the local ground. The core-ground connection also provides a low- resistance path under a short circuit scenario between the transformer winding and core. This allows for the reliable operation of the associated transformer protection relay unit. The isolation of core from ground forms an integral part of the transformer’s insulation system. The core-ground connection must be accessible and further removable for testing. Any issue with the transformer core-ground connection can result in improper grounding, the presence of multiple ground paths, unintentional core-grounds, and a floated core. Multiple core-grounds are created when the core comes into direct contact with the grounded internal metallic structure of a power transformer. Based on the value of the core-to-ground resistance, sustained heating effects can be caused by circulating currents that can eventually result in the melting of the transformer core. This paper outlines the use of diagnostic procedures such as Dissolved Gas Analysis (DGA) and Duval’s Pentagon, Dielectric Frequency Response (DFR) testing, and core-to-ground resistance testing for identifying core-ground defects in power transformers.
    [Show full text]
  • Interlocking Coils Shall Be Wired up to Terminal Blocks in Mechanism Box Through G.I
    SECTION: V TECHNICAL SPECIFICATION For 5MW Floating Solar PV Power Plant at STPS of WBPDCL interlocking coils shall be wired up to terminal blocks in mechanism box through G.I. Conduits. v) The earthing blades shall be required to carry peak current and rated short time current as the main blades of the isolator and shall withstand dynamic stresses. vi) Each earth switch shall be provided with flexible copper braids for connection to the ground mat. These braids shall have same short time current carrying capacity as the earth blades. Assembly i) The disconnecting switch along with its base frame and operating mechanism shall be completely assembled and checked for correct alignment and operation at manufacturer's works prior to despatch. ii) All parts and accessories shall have appropriate benchmarks and part numbers for identifications at site. Grounding i) Each equipment shall be provided with two ground pads for connection to station ground. ii) The ground pad shall comprise buffed metal surface with two tapped holes, M10 G.I. bolts and spring washers for connection to G.S. flat of approved size. iii) Each disconnecting/earth switch-operating rod shall be separately grounded at a point above the mechanism box. This is done by flexible copper braid of adequate section but in no case less than 70 mm². Painting i) Base frame, operating rod and all hardwares shall be hot-dip galvanised. ii) Mechanism box will be finished with two coats of aluminium paints after surface treatment, involving chemical cleaning, phosphating and application of under coats. iii) Sufficient quantity of touch-up paints shall be furnished for application at site.
    [Show full text]
  • IEEE Grounding Transformers
    Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc. [email protected] 1 • It is used to provide a ground path on either an ungrounded Wye or a Delta connected system • The relatively low impedance path to ground maintains the system neutral at ground potential • On Ungrounded systems you can have overvoltages of 6 to 8 times normal with arcing faults Arcing Ground Faults Intermittent or Re-strike •Plot of transient over-voltage for an arcing ground fault Arcing Ground Faults Intermittent or Re-strike •Intermittent ground fault: A re-striking ground fault can create a high frequency oscillator (RLC circuit), independent of L and C values, causing high transient over- voltages. – i.e. re-striking due to ac voltage waveform or loose wire caused by vibration 480V Delta Source 3Ø Load Rfe V V Cb Cb S fa THE HIGH RESISTANCE GROUNDED POWER SYSTEM CONTROL OF TRANSIENT OVERVOLTAGE • It supports the voltage on a faulted phase – If a single line-to-ground fault occurs on an ungrounded or isolated system, no return path exists and no current flows – The system will continue to operate but the other two un- faulted lines will rise in in voltage by the square root of 3, possibly overstressing the transformer insulation, and other components, by 173% UNGROUNDED SYSTEM NORMAL CONDITIONS UNGROUNDED SYSTEM GROUND FAULT ON PHASE A • Provides a metering point to measure faults A typical example is a Wind Farm. They utilize grounding transformers for fault protection on ungrounded lines When a ground fault occurs on a collector cable causes the substation circuit breaker to open, the wind turbine string becomes isolated Turbines do not always detect the fault and the generators continue to energize the cable.
    [Show full text]
  • Resistors, Diodes, Transistors, and the Semiconductor Value of a Resistor
    Resistors, Diodes, Transistors, and the Semiconductor Value of a Resistor Most resistors look like the following: A Four-Band Resistor As you can see, there are four color-coded bands on the resistor. The value of the resistor is encoded into them. We will follow the procedure below to decode this value. • When determining the value of a resistor, orient it so the gold or silver band is on the right, as shown above. • You can now decode what resistance value the above resistor has by using the table on the following page. • We start on the left with the first band, which is BLUE in this case. So the first digit of the resistor value is 6 as indicated in the table. • Then we move to the next band to the right, which is GREEN in this case. So the second digit of the resistor value is 5 as indicated in the table. • The next band to the right, the third one, is RED. This is the multiplier of the resistor value, which is 100 as indicated in the table. • Finally, the last band on the right is the GOLD band. This is the tolerance of the resistor value, which is 5%. The fourth band always indicates the tolerance of the resistor. • We now put the first digit and the second digit next to each other to create a value. In this case, it’s 65. 6 next to 5 is 65. • Then we multiply that by the multiplier, which is 100. 65 x 100 = 6,500. • And the last band tells us that there is a 5% tolerance on the total of 6500.
    [Show full text]
  • Fundamentals of MOSFET and IGBT Gate Driver Circuits
    Application Report SLUA618A–March 2017–Revised October 2018 Fundamentals of MOSFET and IGBT Gate Driver Circuits Laszlo Balogh ABSTRACT The main purpose of this application report is to demonstrate a systematic approach to design high performance gate drive circuits for high speed switching applications. It is an informative collection of topics offering a “one-stop-shopping” to solve the most common design challenges. Therefore, it should be of interest to power electronics engineers at all levels of experience. The most popular circuit solutions and their performance are analyzed, including the effect of parasitic components, transient and extreme operating conditions. The discussion builds from simple to more complex problems starting with an overview of MOSFET technology and switching operation. Design procedure for ground referenced and high side gate drive circuits, AC coupled and transformer isolated solutions are described in great details. A special section deals with the gate drive requirements of the MOSFETs in synchronous rectifier applications. For more information, see the Overview for MOSFET and IGBT Gate Drivers product page. Several, step-by-step numerical design examples complement the application report. This document is also available in Chinese: MOSFET 和 IGBT 栅极驱动器电路的基本原理 Contents 1 Introduction ................................................................................................................... 2 2 MOSFET Technology ......................................................................................................
    [Show full text]
  • Using Embedded Resistor Emulation and Trimming to Demonstrate Measurement Methods and Associated Engineering Model Development*
    IJEE 1830 Int. J. Engng Ed. Vol. 22, No. 1, pp. 000±000, 2006 0949-149X/91 $3.00+0.00 Printed in Great Britain. # 2006 TEMPUS Publications. Using Embedded Resistor Emulation and Trimming to Demonstrate Measurement Methods and Associated Engineering Model Development* PHILLIP A.M.SANDBORN AND PETER A.SANDBORN CALCE Electronic Products and Systems Center, Department of Mechanical Engineering, University of Maryland, College Park, MD, USA.E-mail: [email protected] Embedded resistors are planar resistors that are fabricated inside printed circuit boards and used as an alternative to discrete resistor components that are mounted on the surface of the boards.The successful use of embedded resistors in many applications requires that the resistors be trimmed to required design values prior to lamination into printed circuit boards.This paper describes a simple emulation approach utilizing conductive paper that can be used to characterize embedded resistor operation and experimentally optimize resistor trimming patterns.We also describe a hierarchy of simple modeling approaches appropriate to both college engineering students and pre-college students that can be verified with the experimental results, and used to extend the experimental trimming analysis.The methodology described in this paper is a simple and effective approach for demonstrating a combination of measurement methods, uncertainty analysis, and associated engineering model development. Keywords: embedded resistors; embedded passives; trimming INTRODUCTION process that starts with a layer pair that is pre- coated with resistive material that is selectively EMBEDDING PASSIVE components (capaci- removed to create the resistors.The layer contain- tors, resistors, and possibly inductors) within ing the resistor is laminated together with other printed circuit boards is one of a series of technol- layers to make the finished printed circuit board.
    [Show full text]
  • Resistor Selection Application Notes Resistor Facts and Factors
    Resistor Selection Application Notes RESISTOR FACTS AND FACTORS A resistor is a device connected into an electrical circuit to resistor to withstand, without deterioration, the temperature introduce a specified resistance. The resistance is measured in attained, limits the operating temperature which can be permit- ohms. As stated by Ohm’s Law, the current through the resistor ted. Resistors are rated to dissipate a given wattage without will be directly proportional to the voltage across it and inverse- exceeding a specified standard “hot spot” temperature and the ly proportional to the resistance. physical size is made large enough to accomplish this. The passage of current through the resistance produces Deviations from the standard conditions (“Free Air Watt heat. The heat produces a rise in temperature of the resis- Rating”) affect the temperature rise and therefore affect the tor above the ambient temperature. The physical ability of the wattage at which the resistor may be used in a specific applica- tion. SELECTION REQUIRES 3 STEPS Simple short-cut graphs and charts in this catalog permit rapid 1.(a) Determine the Resistance. determination of electrical parameters. Calculation of each (b) Determine the Watts to be dissipated by the Resistor. parameter is also explained. To select a resistor for a specific application, the following steps are recommended: 2.Determine the proper “Watt Size” (physical size) as controlled by watts, volts, permissible temperatures, mounting conditions and circuit conditions. 3.Choose the most suitable kind of unit, including type, terminals and mounting. STEP 1 DETERMINE RESISTANCE AND WATTS Ohm’s Law Why Watts Must Be Accurately Known 400 Stated non-technically, any change in V V (a) R = I or I = R or V = IR current or voltage produces a much larger change in the wattage (heat to be Ohm’s Law, shown in formula form dissipated by the resistor).
    [Show full text]
  • Single Resistor Sets the Gain of the Best Instrumentation Amplifier
    The LT1167: Single Resistor Sets the Gain of the Best Instrumentation Amplifi er – Design Note 182 Alexander Strong and Kevin R. Hoskins Introduction 0.14% accuracy. At very high gains (≥1000), the error Linear Technology’s next generation LT®1167 instru- is less than 0.2% when using 0.1% precision resistors. mentation amplifi er uses a single resistor to set gains Low Input Bias Current and Noise Voltage from 1 to 10,000. The single gain-set resistor eliminates The LT1167 combines the pA input bias current of expensive resistor arrays and improves V and CMRR OS FET input amplifi ers with the low input noise voltage performance. Careful attention to circuit design and characteristic of bipolar amplifi ers. Using superbeta layout, combined with laser trimming, greatly enhances input transistors, the LT1167’s input bias current is only the CMRR, PSRR, gain error and nonlinearity, maximiz- 350pA maximum at room temperature. The LT1167’s ing application versatility. The CMRR is guaranteed to low input bias current, unlike that of JFET input op be greater than 90dB when the LT1167’s gain is set at amps, does not double for every 10°C. The bias cur- 1. Total input offset voltage (V ) is less than 60μV at a OS rent is guaranteed to be less then 800pA at 85°C. The gain of 10. For gains in the range of 1 to 100, gain error low noise voltage of 7.5nV√Hz at 1kHz is achieved by is less than 0.05%, making the gain-set resistor toler- idling a large portion of the 0.9mA supply current in ance the dominant source of gain error.
    [Show full text]
  • OP-AMP Basics
    OP-AMP Basics Operational amplifiers are convenient building blocks that can be used to build amplifiers, filters, and even an analog computer. Op-amps are integrated circuits composed of many transistors & resistors such that the resulting circuit follows a certain set of rules. The most common type of op-amp is the voltage feedback type and that's what we'll use. The schematic representation of an op-amp is shown to the left. There are two input pins (non-inverting and inverting), an output pin, and two power pins. The ideal op- amp has infinite gain. It amplifies the voltage difference between the two inputs and that voltage appears at the output. Without feedback this op-amp would act like a comparator (i.e. when the non-inverting input is at a higher voltage than the inverting input the output will be high, when the inputs are reversed the output will be low). Two rules will let you figure out what most simple op-amp circuits do: 1. No current flows into the input pins (i.e. infinite input impedance) 2. The output voltage will adjust to try and bring the input pins to the same voltage (this rule is valid for the circuits shown below) Simple OP-AMP circuits Voltage Follower: Vin No current flows into the input, Rin = ∞ Vout The output is fed back to the inverting input. Since the RL output adjusts to make the inputs the same voltage Vout = Vin (i.e. a voltage follower, gain = 1). This circuit is used to buffer a high impedance source (note: the op-amp has low output impedance 10-100Ω).
    [Show full text]