IEEE Grounding Transformers

Total Page:16

File Type:pdf, Size:1020Kb

IEEE Grounding Transformers Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc. [email protected] 1 • It is used to provide a ground path on either an ungrounded Wye or a Delta connected system • The relatively low impedance path to ground maintains the system neutral at ground potential • On Ungrounded systems you can have overvoltages of 6 to 8 times normal with arcing faults Arcing Ground Faults Intermittent or Re-strike •Plot of transient over-voltage for an arcing ground fault Arcing Ground Faults Intermittent or Re-strike •Intermittent ground fault: A re-striking ground fault can create a high frequency oscillator (RLC circuit), independent of L and C values, causing high transient over- voltages. – i.e. re-striking due to ac voltage waveform or loose wire caused by vibration 480V Delta Source 3Ø Load Rfe V V Cb Cb S fa THE HIGH RESISTANCE GROUNDED POWER SYSTEM CONTROL OF TRANSIENT OVERVOLTAGE • It supports the voltage on a faulted phase – If a single line-to-ground fault occurs on an ungrounded or isolated system, no return path exists and no current flows – The system will continue to operate but the other two un- faulted lines will rise in in voltage by the square root of 3, possibly overstressing the transformer insulation, and other components, by 173% UNGROUNDED SYSTEM NORMAL CONDITIONS UNGROUNDED SYSTEM GROUND FAULT ON PHASE A • Provides a metering point to measure faults A typical example is a Wind Farm. They utilize grounding transformers for fault protection on ungrounded lines When a ground fault occurs on a collector cable causes the substation circuit breaker to open, the wind turbine string becomes isolated Turbines do not always detect the fault and the generators continue to energize the cable. Voltages between the un-faulted cable and the ground rise by the 173% The transformer, placed on the turbine string, provides the ground path A typical example is a Wind Farm. When the feeder breaker Opens, the collector bus and the step up transformer delta connected MV windings rely on the Grounding Transformer for their ground path and voltage support. Two different constructions: ZIG ZAG (Zn) WYE CONNECTED •What if no neutral exists (i.e. delta systems)? – A grounding transformer is installed (either a zig-zag or a wye-delta) from all three phases to create an artificial neutral for grounding purposes only. AØ BØ CØ AØ BØ CØ AØ BØ CØ Zig-Zag HRG Grounding Transformer Wye-Delta Broken Delta Grounding Grounding Transformers Transformers HRG HRG • The zigzag transformer contains six coils on three cores. The first coil on each core is connected contrariwise to the second coil on the next core. • The second coils are then all tied together to form the neutral and the phases are connected to the primary coils. • Each phase, therefore, couples with each other phase and the voltages cancel out A Typical Wye connection with Neutral end of windings connected Together A B C C B Vector diagram of balanced system A B C Symmetrical three phase source a A c C The Zig-Zag connection has 2 windings on each leg. B b a A c C A b B a Each leg of the Zig-Zag Connection is connected b to a winding from another which C is out of phase c B The resulting Zig-Zag connection Is phase shifted with respect to the incoming three phase source Az Cz Bz • Limits circulation of triplen harmonics ( 3 rd, 6th, 9th, etc) • Can be used without a Delta connected or 5- legged core • Elimination of secondary winding results in smaller footprint, lower cost (25-30%) • Includes a Delta or Wye connected secondary • Utilizes 4 or 5 legged core when Wye connected secondary is specified • Multi-functional, provides benefit of auxiliary power Know the basic parameters • Primary Voltage • Impedance as a % or as an • Phase to Phase continuous ohms/phase value primary current (or Rated • Primary Winding kVA) connection • Continuous Neutral current • Secondary connection • Available Fault Current and • Basic overall construction Duration • This is the system voltage to which the grounded winding is to be connected. • Don’t forget to specify the BIL also. • In some cases the BIL will be dictated by equipment considerations, such as 150 kV BIL on 34.5 kV wind farms because of the limitation of dead front connectors • The Transformer must be sized to carry the rated continuous, phase-to-phase current without exceeding its temperature limit • The higher the current, the larger and more costly the transformer • Typical values can be as low as 5 amps to as high as a few hundred • Include any auxiliary loading requirements • Is defined as 3X the Phase-to-Phase current (Zero Sequence Current) • It is the value that is expected to flow in the neutral circuit without tripping protective circuits • Used to design for thermal capacity of the transformer • Used to determine the short time heating resulting from a fault on the system which returns through the transformer • Typical ranges run from a few hundred to a few thousand amps • Duration is expressed in seconds (i.e. 400 amps for 10 seconds) • Can be expressed as either a percentage or as an ohmic value • Either should be chosen such that the un-faulted phase voltages are within the temporary over- voltage capability of: • The Transformer • Associated equipment (i.e. arresters, terminal connectors, etc.) • Typical values can be as low as 8% and as much as 100% • Must be determined by the system designer • Zig Zag or Grounded Wye • Specify the secondary voltage and connection for primary Wye connected transformers • Specify size of auxiliary loading to be connected • If two winding with no secondary load, advise if the delta winding can be “buried” (not brought out) or if only one bushing is to be brought out for grounding to the tank or testing • Compartmental pad • Connectivity mount or unit • Dead Front or Live Front substation design • Spade terminals • Cover-mounted or • Indoor or outdoor sidewall • Fluid type (Mineral Oil, • Exposed or enclosed Silicone, or Envirotemp • Temperature Rise FR3) • 65 degrees C • Site Elevation or • 55 degrees C • 55/65 deg. C Environmental conditions • Special Coating requirements Round Coils 360 degree cooling ducts Radial forces are equalized during short circuits & overloads Cruciform stacked core construction The following transformers are for reference only to let you be aware of different type transformers for different applications. • A Scott – T Transformer is a transformer that is designed for converting 2 phase current to 3 phase current or vice-versa. • An autotransformer is a transformer that only have one winding with taps. No isolation is provided between the primary and secondary. • A Buck-Boost transformer is one that is designed to lower (buck) or raise (boost) the voltage in the range of 5% to 25%. This is a great (low cost) way to get between 208 and 240 Volts, or between 480 and 575 Volts. Used on 1 and 3 Phase applications. • A drive isolation transformer is one that is typically used on AC or DC Drive systems. It typically has the same primary and secondary voltages and is used for isolation. In addition you typically have a shield to attenuate line to ground noise. • A constant voltage transformer is one in which the secondary stays constant with large swings on the primary voltage. This is accomplished by operating the primary in a saturated mode so even when the primary voltage dips you can still maintain a constant output. Typical input may be 80% to 110% with the output maintaining 1% voltage regulation. A copy of this presentation can be found at: www.L-3.com For more information and specification sheets Contact: Levine Lectronics and Lectric, Inc. 770 565-1556 [email protected].
Recommended publications
  • Review of Ground Fault Protection Methods for Grounded, Ungrounded, and Compensated Distribution Systems
    REVIEW OF GROUND FAULT PROTECTION METHODS FOR GROUNDED, UNGROUNDED, AND COMPENSATED DISTRIBUTION SYSTEMS Jeff Roberts, Dr. Hector J. Altuve, and Dr. Daqing Hou Schweitzer Engineering Laboratories, Inc. Pullman, WA USA ABSTRACT This paper reviews ground fault protection and detection methods for distribution systems. First, we review and compare medium-voltage distribution-system grounding methods. Next, we describe directional elements suitable to provide ground fault protection in solidly- and low- impedance grounded distribution systems. We then analyze the behavior of ungrounded systems under ground fault conditions and introduce a new ground directional element for these systems. Then we examine the behavior of compensated systems during ground faults and describe traditional fault detection methods. We conclude by introducing new ground fault detection methods for compensated systems. INTRODUCTION Ground fault current magnitudes depend on the system grounding method. Solidly- and low- impedance grounded systems may have high levels of ground fault currents. These high levels typically require line tripping to remove the fault from the system. Ground overcurrent and directional overcurrent relays are the typical ground fault protection solution for such systems. However, high-impedance ground fault detection is difficult in multigrounded four-wire systems, in which the relay measures the ground fault current combined with the unbalance current generated by line phasing and configuration and load unbalance. Ungrounded systems have no intentional ground. For a single-line-to-ground fault on these systems, the only path for ground current to flow is through the distributed line-to-ground capacitance of the surrounding system and of the two remaining unfaulted phases of the faulted circuit.
    [Show full text]
  • Advanced Power Transformer Diagnostics – Detection of Core-Ground Issues
    CIGRE-346 2020 CIGRE Canada Conference Toronto, Ontario, October 19-22, 2020 Advanced Power Transformer Diagnostics – Detection of Core-Ground Issues ALI NADERIAN JAHROMI1, PRANAV PATTABI1, JAFAR MOHAMMADI1, MOHSEN TANGSIRI2 1METSCO Energy Solutions, Canada 2MS Hydro Power Plant, Iran SUMMARY The typical construction of a power transformer results in a high potential being induced in the core, due to the electromagnetic coupling that exists between the core and winding assembly. The transformer core is normally grounded at a single point, to safely divert this induced voltage to the local ground. The core-ground connection also provides a low- resistance path under a short circuit scenario between the transformer winding and core. This allows for the reliable operation of the associated transformer protection relay unit. The isolation of core from ground forms an integral part of the transformer’s insulation system. The core-ground connection must be accessible and further removable for testing. Any issue with the transformer core-ground connection can result in improper grounding, the presence of multiple ground paths, unintentional core-grounds, and a floated core. Multiple core-grounds are created when the core comes into direct contact with the grounded internal metallic structure of a power transformer. Based on the value of the core-to-ground resistance, sustained heating effects can be caused by circulating currents that can eventually result in the melting of the transformer core. This paper outlines the use of diagnostic procedures such as Dissolved Gas Analysis (DGA) and Duval’s Pentagon, Dielectric Frequency Response (DFR) testing, and core-to-ground resistance testing for identifying core-ground defects in power transformers.
    [Show full text]
  • Interlocking Coils Shall Be Wired up to Terminal Blocks in Mechanism Box Through G.I
    SECTION: V TECHNICAL SPECIFICATION For 5MW Floating Solar PV Power Plant at STPS of WBPDCL interlocking coils shall be wired up to terminal blocks in mechanism box through G.I. Conduits. v) The earthing blades shall be required to carry peak current and rated short time current as the main blades of the isolator and shall withstand dynamic stresses. vi) Each earth switch shall be provided with flexible copper braids for connection to the ground mat. These braids shall have same short time current carrying capacity as the earth blades. Assembly i) The disconnecting switch along with its base frame and operating mechanism shall be completely assembled and checked for correct alignment and operation at manufacturer's works prior to despatch. ii) All parts and accessories shall have appropriate benchmarks and part numbers for identifications at site. Grounding i) Each equipment shall be provided with two ground pads for connection to station ground. ii) The ground pad shall comprise buffed metal surface with two tapped holes, M10 G.I. bolts and spring washers for connection to G.S. flat of approved size. iii) Each disconnecting/earth switch-operating rod shall be separately grounded at a point above the mechanism box. This is done by flexible copper braid of adequate section but in no case less than 70 mm². Painting i) Base frame, operating rod and all hardwares shall be hot-dip galvanised. ii) Mechanism box will be finished with two coats of aluminium paints after surface treatment, involving chemical cleaning, phosphating and application of under coats. iii) Sufficient quantity of touch-up paints shall be furnished for application at site.
    [Show full text]
  • IEEE/PES Transformers Committee Fall 2017 Meeting Minutes
    Transformers Committee Chair: Stephen Antosz Vice Chair: Sue McNelly Secretary: Bruce Forsyth Treasurer: Greg Anderson Awards Chair/Past Chair: Don Platts Standards Coordinator: Jim Graham IEEE/PES Transformers Committee Fall 2017 Meeting Minutes Louisville, KY October 30 – November 2, 2017 Unapproved (These minutes are on the agenda to be approved at the next meeting in Spring 2018) TABLE OF CONTENTS GENERAL ADMINISTRATIVE ITEMS 1.0 Agenda 2.0 Attendance OPENING SESSION – MONDAY OCTOBER 30, 2017 3.0 Approval of Agenda and Previous Minutes – Stephen Antosz 4.0 Chair’s Remarks & Report – Stephen Antosz 5.0 Vice Chair’s Report – Susan McNelly 6.0 Secretary’s Report – Bruce Forsyth 7.0 Treasurer’s Report – Gregory Anderson 8.0 Awards Report – Don Platts 9.0 Administrative SC Meeting Report – Stephen Antosz 10.0 Standards Report – Jim Graham 11.0 Liaison Reports 11.1. CIGRE – Raj Ahuja 11.2. IEC TC14 – Phil Hopkinson 11.3. Standards Coordinating Committee, SCC No. 18 (NFPA/NEC) – David Brender 11.4. Standards Coordinating Committee, SCC No. 4 (Electrical Insulation) – Paulette Payne Powell 12.0 Hot Topics for the Upcoming – Subcommittee Chairs 13.0 Opening Session Adjournment CLOSING SESSION – THURSDAY NOVEMBER 2, 2017 14.0 Chair’s Remarks and Announcements – Stephen Antosz 15.0 Meetings Planning SC Minutes & Report – Gregory Anderson 16.0 Reports from Technical Subcommittees (decisions made during the week) 17.0 Report from Standards Subcommittee (issues from the week) 18.0 New Business 19.0 Closing Session Adjournment APPENDIXES – ADDITIONAL DOCUMENTATION Appendix 1 – Meeting Schedule Appendix 2 – Semi-Annual Standards Report Appendix 3 – IEC TC14 Liaison Report Appendix 4 – CIGRE Report Page 2 of 55 ANNEXES – UNAPPROVED MINUTES OF TECHNICAL SUBCOMMITTEES NOTE: The Annexes included in these minutes are unapproved by the respective subcommittees and are accurate as of the date the Transformers Committee meeting minutes were published.
    [Show full text]
  • Neutral Current Problem and Mitigation Techniques: an Overview
    IOSR Journal of Engineering (IOSR JEN) www.iosrjen.org ISSN (e): 2250-3021, ISSN (p): 2278-8719 PP 62-68 Neutral Current Problem and Mitigation Techniques: An Overview Karuna Nikum1, Rakesh Saxena2, Abhay Wagh3 1(Department of Electrical Engineering, ACE, Mumbai University, India) 2(SGSITS, RGPV University, Indore, India) 3(Directorate of Technical Education, Mumbai, India ) Abstract: In this paper, an attempt to overview a various number of mitigation techniques and power quality problems associated with neutral current for commercial loads are discussed. The load connected to three phase four wire system are generally single-phase loads and generate triplen harmonic currents due to unbalancing in phases at neutral. There are various neutral current mitigation techniques including active and passive has been discussed. The existing approach and a framework of references for researchers in this field are provided. I. ‘Introduction The ample use of electronic devices in all types of loads i.e. residential, commercial and industrial is adversely affecting the power quality (PQ) of the system[1]-[10]. When three-phase four-wire distribution (3P4W) systems are used to supply single-phase low voltage loads such as lighting ballasts (electronic type), light emitting diodes (LED), compact fluorescent lighting (CFL), personal computers, monitors, laser printers, variable speed drives, adjustable speeds drives (ASD) in air conditioner, UPS systems and other electronic equipment. These loads produces harmonics especially 3rd harmonics in the neutral. In general, the distribution systems designed for linear load type and no longer suitable for delivering large number of non-linear and harmonic generating loads [11]-[15]. The concern PQ issues are high reactive power requirement, harmonic current, low power factor and increased losses[16], [17].
    [Show full text]
  • Test Procedure for Distribution Transformers
    This document, concerning distribution transformers is an action issued by the Department of Energy. Though it is not intended or expected, should any discrepancy occur between the document posted here and the document published in the Federal Register, the Federal Register publication controls. This document is being made available through the Internet solely as a means to facilitate the public's access to this document. [6450-01-P] DEPARTMENT OF ENERGY 10 CFR Part 431 [EERE-2017-BT-TP-0055] RIN 1904-AB39 Energy Conservation Program: Test Procedure for Distribution Transformers AGENCY: Office of Energy Efficiency and Renewable Energy, Department of Energy. ACTION: Notice of proposed rulemaking and request for comment. SUMMARY: The U.S. Department of Energy (“DOE”) proposes clarifying amendments to the test procedure for distribution transformers to revise and add definitions of certain terms, to incorporate revisions based on the latest versions of relevant Institute of Electrical and Electronics Engineers (IEEE) industry standards, and to specify the basis for voluntary representations at additional per-unit loads (PULs) and additional reference temperatures. The proposals in this NOPR are minor revisions that do not significantly change the test procedure. Therefore, none of the revisions would pose undue burden on manufacturers. DOE is seeking comment from interested parties on the proposal. DATES: DOE will accept comments, data, and information regarding this notice of proposed rulemaking (NOPR) no later than [INSERT DATE 60 DAYS AFTER DATE OF 1 PUBLICATION IN THE FEDERAL REGISTER]. See section V, “Public Participation,” for details. ADDRESSES: Any comments submitted must identify the Test Procedure NOPR for Distribution Transformers and provide docket number EERE-2017-BT-TP-0055 and/or regulatory information number (RIN) 1904-AB39.
    [Show full text]
  • IP 202-1 List of Materials
    Changes to the List of Materials August 3, 2021 1. Page be(2.3) a. Added Siemens i. CMR May 6, 2021 1. Page Ugn-2 a. Added Aluma-Form i. ENC Series April 27, 2021 1. Page Ugk-2.2 a. Added Prysmian i. PCT Series (15, 25, 35kV) February 9, 2021 1. Page be(4.3) a. Added Southern States single-phase SSR type recloser. February 4, 2021 1. Pages rp(1), rp(1.2) a. Revised “Cantega” to “Hubbell Power Systems”. b. Added trademark to Reliaguard. December 10, 2020 1. Page ap-2 a. Modified page number from “1.1” to “2”. November 18, 2020 1. Pages an-3 and an(3.1) a. Moved Virginia Transformer from page an(3.1) Conditional to page an-3 Full Acceptance. November 6, 2020 1. Page ae-1 a. Added Celeco i. Catalog Numbers: HSCEL, RPCEL October 26, 2020 1. Page Uhb-1.1 a. Added TE Connectivity i. Catalog Numbers: 25 kV, used with loadbreak connectors (without test point) - ELB-25- 200 series without jacket seal, ELB-25-200-ES series with jacket seal October 23, 2020 1. Page p(1) a. Added TE Connectivity (Raychem) i. Catalog number: TIL Series September 30, 2020 1. Pages a(3), ea(4), ea(5) – Added new Hendrix insulator models. a. Catalog Numbers: HPI-15VTC, HPI-15VTP, HPI-25VTC-02, HPI-35VTC-02, HPI-35VTP-02, HPI-LP-14FS/FA, HPI-LP-16F, HPI-CLP-15, HPI-CLP-17, HPI-CLP-20 July 7, 2020 1. Page cm-2 – Added Aluma-Form, Inc.
    [Show full text]
  • Insulating Materials in Power Transformer.Pdf
    بسمميحرلا نمحرلا هللا UNIVERSITY OF KHARTOUM FACULTY OF ENGNEERING DEPARTMENT OF ELECTRICAL AND ELECTRONIC ENGNEERING INSULATING MATERIALS IN POWER TRANSFORMERS By HUSSAM MAGID AHMED ABDALLAH INDEX NO.124041 Supervisor Dr. Alfadel Zakariya A REPORT SUBMITTED TO University Of Khartoum In partial fulfillment for the degree of B.Sc. (HONS) Electrical and Electronics Engineering (POWER SYSTEM ENGINEERING) Faculty of Engineering Department of Electrical and Electronics Engineering October 2017 DECLARATION OF ORGINALITY I declare this report entitled “(Insulating materials in power transformers)” is my own work except as cited in references. The report has been not accepted for any degree and it is not being submitted currently in candidature for any degree or other reward. Signature: ____________________ Name: _______________________ Date: ________________________ ii ACKNOWLEDGEMENT All the thanks, praises and glorifying is due to the Almighty GOD, without his uncountable blesses and uninterrupted gifts I wouldn„t be here a grown man about to graduate. To my mother, who grew me up, fed me, guided me through the life, many thanks and thanks. To my father who learnt me the patience and self-confidence. For my supervisor Dr.alfadel Zakariya, for his endless guiding and support. For my colleague, my partner in this project. iii Abstract There are many types of transformers insulators, some of them are used with conductors and the others are used to insulate the metal slides from each other and the others used to insulate the windings form the iron core. After collecting the parts of the transformer, it has to be dry enough because the insulators affected by the humidity which is make its isolation properties to be less than usual.
    [Show full text]
  • Temporary Over-Voltages and System Grounding 20/761
    20/759 Temporary over-voltages and 20 system grounding Contents 20.1 Theory of over-voltages 20/761 20.2 Analysis of ungrounded and grounded systems 20/762 20.2.1 Analysis of an ungrounded system 20/762 20.3 The necessity for grounding an electrical system 20/765 20.4 Analysis of a grounded system 20/765 20.4.1 Solid neutral grounding system 20/766 20.4.2 Impedance neutral grounding system 20/766 20.5 Arc suppression coil or ground fault neutralizer 20/767 20.6 Ground fault factor (GFF) 20/768 20.6.1 An ungrounded or isolated neutral system 20/769 20.6.2 A grounded neutral system 20/769 20.7 Magnitude of temporary over-voltages 20/769 20.8 Insulation co-ordination 20/769 20.9 Artificial neutral grounding of a three-phase three-wire system 20/770 20.10 Grounding of generators 20/771 Relevant Standards 20/772 List of formulae used 20/772 Further Reading 20/772 Temporary over-voltages and system grounding 20/761 20.1 Theory of over-voltages IIgg¢¢ + (–120∞ ) = 3 I g¢ R A three-phase balanced system has all the three phasors Vᐉ I g¢ of voltage and current 120∞ apart, as illustrated in Figure N Y 20.1(a) for a conventional anti-clockwise rotation. These Vᐉ I g¢ phasors are known as positive sequence components. B During a fault, this balance is disturbed and the system becomes unbalanced being composed of two balanced components, one positive and the other negative sequence Cg Cg Cg Vᐉ (Figures 20.1(a) and (b)).
    [Show full text]
  • Phase Shifting with Transformers – New Approaches for Harmonic Mitigation & Power Factor Correction
    Phase Shifting with Transformers – New Approaches for Harmonic Mitigation & Power Factor Correction Abstract Improved designs for electrically powered equipment such as solid-state motor drives, electronic lighting ballasts, DC power supplies and computers offer the promise of dramatically improving energy efficiency. These new technologies can have power quality side effects, which must be considered along with the energy benefits. Current demand characteristics, harmonic production and power susceptibility requirements create new issues of compatibility with other devices in the electrical environment. Contrary to this new energy saving product design, the dry type transformer efficiency in the last 20 years has been decreasing to meet market price competition. Under these modern loads, the standard distribution transformer became much less efficient and in some cases obsolete. In view of the increasing cost of energy we are seeing improvements in the design of distribution transformers. C802.2 and TP1 became legislation in the U.S. on January 1st, 2007 and became law in Canada on January 1st, 2005. We will review the reasons and the new style of transformers being designed for these applications. The positive side is that the new energy saving designs are converging with the power quality needs for the new electronic rich environments of our modern facilities. Introduction At the turn of the century, electricity invaded homes all over North America. The power grid that evolved from the beginning has remained essentially the same to this day. Important power transmission over long distances has led to the use of alternating current technology to simplify power transfer. This has served us well for the needs of namely light bulbs and motors.
    [Show full text]
  • Grounding System Theory and Practice
    Grounding System Theory and Practice Course No: E04-027 Credit: 4 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 22 Stonewall Court Woodcliff Lake, NJ 07677 P: (877) 322-5800 [email protected] Grounding System Theory and Practice Introduction System grounding has been used since electrical power systems began. However, many companies and industrial plants have used system grounding methods differently. The problem of whether a system neutral should be grounded, and how it should be grounded, has many times been misunderstood completely. Therefore, grounding of many systems has been based upon past experience rather than engineering analysis. This course provides applicable information for grounding, such as definitions, reasons for having a system ground, the most desirable grounding method, and so on, and how to measure ground resistance in order to maintain the grounding system. The definition of grounding is commonly used for both, system grounding and equipment grounding. The National Electrical Code (NEC) defines system ground as a connection to ground from one of the current-carrying conductors of an electrical power system or of an interior wiring system, whereas an equipment ground is defined as a connection to ground from one or more of the noncurrent-carrying metal parts of a wiring system or equipment connected to the system. The following definitions describe power system grounding. - System neutral ground: A connection to ground from the neutral point or points of a circuit, transformer, motor, generator, or system. - Grounded system: A system of conductors in which at least one conductor or point is intentionally grounded. - Ungrounded system: A system of conductors in which there is no intentional connection to ground.
    [Show full text]
  • MO-201 Electric Power Distribution Systems
    ______________________________________________________________________ http://waterheatertimer.org/How-to-wire-3-phase-electric.html http://waterheatertimer.org/What-is-3-phase-electric.html Naval Facilities Engineering Command 200 Stovall Street Alexandria, Virginia 22332-2300 Electric Power Distribution Systems Operations NAVFAC MO-201 April 1990 SN 0525-LP-320-1900 FOREWORD This manual on electric power distribution systems is one of a series developed to aid utility supervisory personnel at shore establishments in the performance of their duties. It includes information obtained from extensive research of current literature on the subject and preferred practices based on practical experience. The principles and procedures described are in accordance with national professional society, association, and institute codes. Additional information concerning procedures, suggestions, recommendations or modifications that will improve this manual are invited and should be submitted through appropriate channels to the Commander, Naval Facilities Engineering Command, (Attention: Code 165), 200 Stovall Street, Alexandria, VA 22332-2300. This publication has been reviewed and approved in accordance with the Secretary of the Navy Instruction 5600.16A and is certified as an official publication of the Naval Facilities Engineering Command. It cancels and supersedes Operation of Electric Power Distribution Systems, NAVFAC MO-201, November 1963, in its entirety. D. B. CAMPBELL Assistant Commander for Public Works Centers and Departments ABSTRACT Application principles and procedures for the operation of electric power distribution systems and associated major apparatus are presented. The contents include principles of power systems, cabling systems, electrical equipment, power system protection and coordination, instruments and meters, operational procedures, and electrical utilization systems. i CONTENTS PAGE CHAPTER 1 PRINCIPLES OF POWER SYSTEMS 1-1 1.1 Typical Power Network...........................................................................
    [Show full text]