Temporary Over-Voltages and System Grounding 20/761

Total Page:16

File Type:pdf, Size:1020Kb

Temporary Over-Voltages and System Grounding 20/761 20/759 Temporary over-voltages and 20 system grounding Contents 20.1 Theory of over-voltages 20/761 20.2 Analysis of ungrounded and grounded systems 20/762 20.2.1 Analysis of an ungrounded system 20/762 20.3 The necessity for grounding an electrical system 20/765 20.4 Analysis of a grounded system 20/765 20.4.1 Solid neutral grounding system 20/766 20.4.2 Impedance neutral grounding system 20/766 20.5 Arc suppression coil or ground fault neutralizer 20/767 20.6 Ground fault factor (GFF) 20/768 20.6.1 An ungrounded or isolated neutral system 20/769 20.6.2 A grounded neutral system 20/769 20.7 Magnitude of temporary over-voltages 20/769 20.8 Insulation co-ordination 20/769 20.9 Artificial neutral grounding of a three-phase three-wire system 20/770 20.10 Grounding of generators 20/771 Relevant Standards 20/772 List of formulae used 20/772 Further Reading 20/772 Temporary over-voltages and system grounding 20/761 20.1 Theory of over-voltages IIgg¢¢ + (–120∞ ) = 3 I g¢ R A three-phase balanced system has all the three phasors Vᐉ I g¢ of voltage and current 120∞ apart, as illustrated in Figure N Y 20.1(a) for a conventional anti-clockwise rotation. These Vᐉ I g¢ phasors are known as positive sequence components. B During a fault, this balance is disturbed and the system becomes unbalanced being composed of two balanced components, one positive and the other negative sequence Cg Cg Cg Vᐉ (Figures 20.1(a) and (b)). For a description of the effects G of these components, refer to (Section 12.2(v)). During I g¢ I g¢ a ground fault, zero phase sequence components also appear, which are single phasor components and combine three equal phasors in phase, as shown in Figure 20.1(c). G This is the residual voltage, V , that appears across the g IIgg = ÷3 ¢ ground circuit, i.e. between the neutral and the ground as illustrated in Figure 20.12. This voltage is responsible for a fault current, Ig · Ig will flow through the grounded Figure 20.2 An ungrounded or isolated neutral system (circuit neutral when it is a three-phase four-wire neutral grounded completing through the ground leakage capacitances) system, as shown in Figure 20.12. It will also flow through a three-phase three-wire artificially grounded system when it is grounded through a neutral grounding transformer (Section 20.9) as illustrated in Figures 20.17 and 20.18. In a three-phase three-wire system, which has neither its own grounded neutral nor an artificially created grounded R neutral, there will be no direct ground fault current. But charging currents through the ground leakage capacitances, N Y particularly on an HV system, may still exist, as illustrated B in Figures 20.2–20.4. These currents may develop dangerous over-voltages across the healthy phases, under certain ground circuit a impedance conditions, as discussed in Section 20.2.1(1). It is thus possible to encounter a ground fault, even when Cg Cg Cg Load Ground leakage the system is not grounded, the fault current finding its capacitances return path through the ground leakage capacitances. While c b an LV system, in view of a far too low ground voltage, G Vg (equal to line voltage, Section 20.2.1(1)), as compared to high ground capacitive leakage reactance, X , would cg G Ig cause a near open circuit (Vg/Xcg being too meagre) and stay immune, leaving the grounded conductor floating at Vg = Vᐉ. Figure 20.3 Case of ground fault within the load B B V V V R V V 3 3 3 N Y V V B R R a G V V Y Y Load Cg Cg Cg (a) (b) (c) Ground leakage c b capacitances Positive sequence Negative sequence Zero sequence or residual quantities G Ig Vr = Vy = Vb = V Figure 20.1 Phasor representation of an unbalanced power Figure 20.4 Case of a ground fault on a power system on system on a ground fault the load side 20/762 Electrical Power Engineering Reference & Applications Handbook 20.2 Analysis of ungrounded and 2 2 = IIg¢¢ + g + 2 ◊ IIgg¢ ◊ ¢ ◊◊∞ cos 60 (as in Section grounded systems 15.4.3) 2 2 2 This is related more to an HV system. = (IIIg¢¢¢ + g + g ) = 3 I (but this current may not be enough to trip 20.2.1 Analysis of an ungrounded system ◊ g¢ a protective relay) This is common to The voltage across the healthy phases is now 3 times or •A three-phase three-wire, star connected isolated 73% more than the phase to neutral voltage under healthy neutral system, conditions (voltage across healthy phases = 3 Vg (on a •A delta connected system, or ground fault Vg = Vᐉ)). •A three-phase four-wire, ungrounded system. Under certain line to ground impedance conditions, when the ground circuit may also contain some inductive An ungrounded a.c. system is more often subject to over- reactance, the voltage of the healthy phases may rise voltages. The reason is that even when the system is not further, much above the system voltage, due to resonance connected to ground, it makes a ground connection through and ferro-resonance effects discussed hereafter. All this the coupling of the leakage ground capacitances, as in turn may tend to swing the system to an unstable illustrated in Figure 20.2. For all purposes these state. It may also cause arcing grounds* at the supporting capacitances may be regarded as equal and uniformly insulators, leading to voltage surges, travelling in both distributed, providing a balanced system. In the event of directions along the line, and may be enough to cause a ground fault, this circuit is closed as shown and a damage to the line insulators and the terminal equipment. capacitive current, Ig¢ flows back to the healthy phases The magnitude of over-voltage will depend upon the via these capacitances Cg, Analysing the circuit of Figure actual inductive reactance introduced through the ground 20.2, the following may be derived: circuit. The unintentional introduction of an impedance into the ground leakage capacitive circuit is generally a result of If Cg = electrostatic or leakage capacitance to the ground a ground fault in the main equipment such as a generator, a per phase, providing the return path to the fault transformer, or an induction motor and when one or more current Ig, in the event of a ground fault on the of their phase windings form a part of the ground circuit, as system. This current will be capacitive in nature. illustrated in Figure 20.3. Under such conditions, they will Xcg = ground capacitive reactance per phase introduce their own inductive or resistive impedances or a combination of them into the ground circuit and alter the = 1 2 fC parameters of the ground capacitive circuit. Figure 20.5 p ◊ g illustrates the system of Figure 20.2, drawn simply on a Under transient conditions, f becomes surge frequency, single phase basis. The current through the ground circuit fs and will be zero when the system is healthy, the ground leakage capacitances finding no return path (Figure 20.6). It is X becomes, 1 cg 2 fC not necessary that the equipment itself should develop a p sg◊ ground fault and then only its impedance will be inducted where into the ground circuit. It may be introduced into the 1 circuit even when there is a line or a system ground fs = 2 LC fault, as illustrated in Figure 20.4. The ground circuit p ◊ g may give rise to dangerous voltages in the healthy phases, L being the inductance of the circuit. as analysed below. If Ig = ground fault current Vg = ground potential, which is the same as zero (1) When the external impedance is a resistance sequence voltage or residual voltage or a capacitive reactance Vᐉ = line voltage and Vp = phase voltage Referring to Figure 20.5, if Zg¢ is the external impedance introduced into the natural leakage ground circuit, as a then on a ground fault, say, in phase R, the voltage across consequence of a ground fault, as shown in Figures 20.3 this phase will reduce to zero, while the ground potential across the healthy phases will rise to Vᐉ from a zero level earlier. It will cause a fault current Ig¢ in the healthy *Arcing grounds: This occurs during a temporary ground fault on phases also, through the ground leakage capacitances an ungrounded HV system. It causes an arc between the line conductor such that I = V /X (assuming the ground circuit has and the ground, which may be direct or through the flashover of the g¢ I cg line insulators, due to over-voltage. The ground leakage capacitors no other impedance) and the ground fault current through that may be considered as charged with the line voltage are discharged the grounded circuit, to the ground on developing a ground fault. The supply voltage would charge them again and so the process will repeat until the Ig = IIYB + fault exists. The repeated discharges and charges of ground capacitors during the fault produce arcs and are termed arcing grounds, giving = IIgg¢¢ + (both phasors being 60∞ apart) rise to voltage surges. Temporary over-voltages and system grounding 20/763 Y May attenuate at about 8–10 · 2Vl 6 Xcg Zg Vl 5 3 V Z g¢ g¢ 4 l G V 2 Xcg = Ground leakage capacitive reactance 3 Z g¢ = Additional ground impedance (R, Xc or XL) Figure 20.5 Equivalent ground circuit representing the power 2 in terms of system of Figure 20.2 3 3 across the additional impedance R 1 (max) 1 ¢ g N Y V 2 B 0 123456 Ratio of additional impedance Zg¢ to Xcg a 1 Resistive reactance 2 Capacitive reactance Cg Cg Cg Load 3 Inductive reactance c b Figure 20.7 Influence of external impedance Z g in the ground G ¢ circuit on the system voltage in the event of ground fault in an On a healthy system the ground leakage capacitances find no return ungrounded system path and therefore do not activate.
Recommended publications
  • Review of Ground Fault Protection Methods for Grounded, Ungrounded, and Compensated Distribution Systems
    REVIEW OF GROUND FAULT PROTECTION METHODS FOR GROUNDED, UNGROUNDED, AND COMPENSATED DISTRIBUTION SYSTEMS Jeff Roberts, Dr. Hector J. Altuve, and Dr. Daqing Hou Schweitzer Engineering Laboratories, Inc. Pullman, WA USA ABSTRACT This paper reviews ground fault protection and detection methods for distribution systems. First, we review and compare medium-voltage distribution-system grounding methods. Next, we describe directional elements suitable to provide ground fault protection in solidly- and low- impedance grounded distribution systems. We then analyze the behavior of ungrounded systems under ground fault conditions and introduce a new ground directional element for these systems. Then we examine the behavior of compensated systems during ground faults and describe traditional fault detection methods. We conclude by introducing new ground fault detection methods for compensated systems. INTRODUCTION Ground fault current magnitudes depend on the system grounding method. Solidly- and low- impedance grounded systems may have high levels of ground fault currents. These high levels typically require line tripping to remove the fault from the system. Ground overcurrent and directional overcurrent relays are the typical ground fault protection solution for such systems. However, high-impedance ground fault detection is difficult in multigrounded four-wire systems, in which the relay measures the ground fault current combined with the unbalance current generated by line phasing and configuration and load unbalance. Ungrounded systems have no intentional ground. For a single-line-to-ground fault on these systems, the only path for ground current to flow is through the distributed line-to-ground capacitance of the surrounding system and of the two remaining unfaulted phases of the faulted circuit.
    [Show full text]
  • Advanced Power Transformer Diagnostics – Detection of Core-Ground Issues
    CIGRE-346 2020 CIGRE Canada Conference Toronto, Ontario, October 19-22, 2020 Advanced Power Transformer Diagnostics – Detection of Core-Ground Issues ALI NADERIAN JAHROMI1, PRANAV PATTABI1, JAFAR MOHAMMADI1, MOHSEN TANGSIRI2 1METSCO Energy Solutions, Canada 2MS Hydro Power Plant, Iran SUMMARY The typical construction of a power transformer results in a high potential being induced in the core, due to the electromagnetic coupling that exists between the core and winding assembly. The transformer core is normally grounded at a single point, to safely divert this induced voltage to the local ground. The core-ground connection also provides a low- resistance path under a short circuit scenario between the transformer winding and core. This allows for the reliable operation of the associated transformer protection relay unit. The isolation of core from ground forms an integral part of the transformer’s insulation system. The core-ground connection must be accessible and further removable for testing. Any issue with the transformer core-ground connection can result in improper grounding, the presence of multiple ground paths, unintentional core-grounds, and a floated core. Multiple core-grounds are created when the core comes into direct contact with the grounded internal metallic structure of a power transformer. Based on the value of the core-to-ground resistance, sustained heating effects can be caused by circulating currents that can eventually result in the melting of the transformer core. This paper outlines the use of diagnostic procedures such as Dissolved Gas Analysis (DGA) and Duval’s Pentagon, Dielectric Frequency Response (DFR) testing, and core-to-ground resistance testing for identifying core-ground defects in power transformers.
    [Show full text]
  • Interlocking Coils Shall Be Wired up to Terminal Blocks in Mechanism Box Through G.I
    SECTION: V TECHNICAL SPECIFICATION For 5MW Floating Solar PV Power Plant at STPS of WBPDCL interlocking coils shall be wired up to terminal blocks in mechanism box through G.I. Conduits. v) The earthing blades shall be required to carry peak current and rated short time current as the main blades of the isolator and shall withstand dynamic stresses. vi) Each earth switch shall be provided with flexible copper braids for connection to the ground mat. These braids shall have same short time current carrying capacity as the earth blades. Assembly i) The disconnecting switch along with its base frame and operating mechanism shall be completely assembled and checked for correct alignment and operation at manufacturer's works prior to despatch. ii) All parts and accessories shall have appropriate benchmarks and part numbers for identifications at site. Grounding i) Each equipment shall be provided with two ground pads for connection to station ground. ii) The ground pad shall comprise buffed metal surface with two tapped holes, M10 G.I. bolts and spring washers for connection to G.S. flat of approved size. iii) Each disconnecting/earth switch-operating rod shall be separately grounded at a point above the mechanism box. This is done by flexible copper braid of adequate section but in no case less than 70 mm². Painting i) Base frame, operating rod and all hardwares shall be hot-dip galvanised. ii) Mechanism box will be finished with two coats of aluminium paints after surface treatment, involving chemical cleaning, phosphating and application of under coats. iii) Sufficient quantity of touch-up paints shall be furnished for application at site.
    [Show full text]
  • IEEE Grounding Transformers
    Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc. [email protected] 1 • It is used to provide a ground path on either an ungrounded Wye or a Delta connected system • The relatively low impedance path to ground maintains the system neutral at ground potential • On Ungrounded systems you can have overvoltages of 6 to 8 times normal with arcing faults Arcing Ground Faults Intermittent or Re-strike •Plot of transient over-voltage for an arcing ground fault Arcing Ground Faults Intermittent or Re-strike •Intermittent ground fault: A re-striking ground fault can create a high frequency oscillator (RLC circuit), independent of L and C values, causing high transient over- voltages. – i.e. re-striking due to ac voltage waveform or loose wire caused by vibration 480V Delta Source 3Ø Load Rfe V V Cb Cb S fa THE HIGH RESISTANCE GROUNDED POWER SYSTEM CONTROL OF TRANSIENT OVERVOLTAGE • It supports the voltage on a faulted phase – If a single line-to-ground fault occurs on an ungrounded or isolated system, no return path exists and no current flows – The system will continue to operate but the other two un- faulted lines will rise in in voltage by the square root of 3, possibly overstressing the transformer insulation, and other components, by 173% UNGROUNDED SYSTEM NORMAL CONDITIONS UNGROUNDED SYSTEM GROUND FAULT ON PHASE A • Provides a metering point to measure faults A typical example is a Wind Farm. They utilize grounding transformers for fault protection on ungrounded lines When a ground fault occurs on a collector cable causes the substation circuit breaker to open, the wind turbine string becomes isolated Turbines do not always detect the fault and the generators continue to energize the cable.
    [Show full text]
  • Test Procedure for Distribution Transformers
    This document, concerning distribution transformers is an action issued by the Department of Energy. Though it is not intended or expected, should any discrepancy occur between the document posted here and the document published in the Federal Register, the Federal Register publication controls. This document is being made available through the Internet solely as a means to facilitate the public's access to this document. [6450-01-P] DEPARTMENT OF ENERGY 10 CFR Part 431 [EERE-2017-BT-TP-0055] RIN 1904-AB39 Energy Conservation Program: Test Procedure for Distribution Transformers AGENCY: Office of Energy Efficiency and Renewable Energy, Department of Energy. ACTION: Notice of proposed rulemaking and request for comment. SUMMARY: The U.S. Department of Energy (“DOE”) proposes clarifying amendments to the test procedure for distribution transformers to revise and add definitions of certain terms, to incorporate revisions based on the latest versions of relevant Institute of Electrical and Electronics Engineers (IEEE) industry standards, and to specify the basis for voluntary representations at additional per-unit loads (PULs) and additional reference temperatures. The proposals in this NOPR are minor revisions that do not significantly change the test procedure. Therefore, none of the revisions would pose undue burden on manufacturers. DOE is seeking comment from interested parties on the proposal. DATES: DOE will accept comments, data, and information regarding this notice of proposed rulemaking (NOPR) no later than [INSERT DATE 60 DAYS AFTER DATE OF 1 PUBLICATION IN THE FEDERAL REGISTER]. See section V, “Public Participation,” for details. ADDRESSES: Any comments submitted must identify the Test Procedure NOPR for Distribution Transformers and provide docket number EERE-2017-BT-TP-0055 and/or regulatory information number (RIN) 1904-AB39.
    [Show full text]
  • IP 202-1 List of Materials
    Changes to the List of Materials August 3, 2021 1. Page be(2.3) a. Added Siemens i. CMR May 6, 2021 1. Page Ugn-2 a. Added Aluma-Form i. ENC Series April 27, 2021 1. Page Ugk-2.2 a. Added Prysmian i. PCT Series (15, 25, 35kV) February 9, 2021 1. Page be(4.3) a. Added Southern States single-phase SSR type recloser. February 4, 2021 1. Pages rp(1), rp(1.2) a. Revised “Cantega” to “Hubbell Power Systems”. b. Added trademark to Reliaguard. December 10, 2020 1. Page ap-2 a. Modified page number from “1.1” to “2”. November 18, 2020 1. Pages an-3 and an(3.1) a. Moved Virginia Transformer from page an(3.1) Conditional to page an-3 Full Acceptance. November 6, 2020 1. Page ae-1 a. Added Celeco i. Catalog Numbers: HSCEL, RPCEL October 26, 2020 1. Page Uhb-1.1 a. Added TE Connectivity i. Catalog Numbers: 25 kV, used with loadbreak connectors (without test point) - ELB-25- 200 series without jacket seal, ELB-25-200-ES series with jacket seal October 23, 2020 1. Page p(1) a. Added TE Connectivity (Raychem) i. Catalog number: TIL Series September 30, 2020 1. Pages a(3), ea(4), ea(5) – Added new Hendrix insulator models. a. Catalog Numbers: HPI-15VTC, HPI-15VTP, HPI-25VTC-02, HPI-35VTC-02, HPI-35VTP-02, HPI-LP-14FS/FA, HPI-LP-16F, HPI-CLP-15, HPI-CLP-17, HPI-CLP-20 July 7, 2020 1. Page cm-2 – Added Aluma-Form, Inc.
    [Show full text]
  • Insulating Materials in Power Transformer.Pdf
    بسمميحرلا نمحرلا هللا UNIVERSITY OF KHARTOUM FACULTY OF ENGNEERING DEPARTMENT OF ELECTRICAL AND ELECTRONIC ENGNEERING INSULATING MATERIALS IN POWER TRANSFORMERS By HUSSAM MAGID AHMED ABDALLAH INDEX NO.124041 Supervisor Dr. Alfadel Zakariya A REPORT SUBMITTED TO University Of Khartoum In partial fulfillment for the degree of B.Sc. (HONS) Electrical and Electronics Engineering (POWER SYSTEM ENGINEERING) Faculty of Engineering Department of Electrical and Electronics Engineering October 2017 DECLARATION OF ORGINALITY I declare this report entitled “(Insulating materials in power transformers)” is my own work except as cited in references. The report has been not accepted for any degree and it is not being submitted currently in candidature for any degree or other reward. Signature: ____________________ Name: _______________________ Date: ________________________ ii ACKNOWLEDGEMENT All the thanks, praises and glorifying is due to the Almighty GOD, without his uncountable blesses and uninterrupted gifts I wouldn„t be here a grown man about to graduate. To my mother, who grew me up, fed me, guided me through the life, many thanks and thanks. To my father who learnt me the patience and self-confidence. For my supervisor Dr.alfadel Zakariya, for his endless guiding and support. For my colleague, my partner in this project. iii Abstract There are many types of transformers insulators, some of them are used with conductors and the others are used to insulate the metal slides from each other and the others used to insulate the windings form the iron core. After collecting the parts of the transformer, it has to be dry enough because the insulators affected by the humidity which is make its isolation properties to be less than usual.
    [Show full text]
  • Grounding System Theory and Practice
    Grounding System Theory and Practice Course No: E04-027 Credit: 4 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 22 Stonewall Court Woodcliff Lake, NJ 07677 P: (877) 322-5800 [email protected] Grounding System Theory and Practice Introduction System grounding has been used since electrical power systems began. However, many companies and industrial plants have used system grounding methods differently. The problem of whether a system neutral should be grounded, and how it should be grounded, has many times been misunderstood completely. Therefore, grounding of many systems has been based upon past experience rather than engineering analysis. This course provides applicable information for grounding, such as definitions, reasons for having a system ground, the most desirable grounding method, and so on, and how to measure ground resistance in order to maintain the grounding system. The definition of grounding is commonly used for both, system grounding and equipment grounding. The National Electrical Code (NEC) defines system ground as a connection to ground from one of the current-carrying conductors of an electrical power system or of an interior wiring system, whereas an equipment ground is defined as a connection to ground from one or more of the noncurrent-carrying metal parts of a wiring system or equipment connected to the system. The following definitions describe power system grounding. - System neutral ground: A connection to ground from the neutral point or points of a circuit, transformer, motor, generator, or system. - Grounded system: A system of conductors in which at least one conductor or point is intentionally grounded. - Ungrounded system: A system of conductors in which there is no intentional connection to ground.
    [Show full text]
  • Transformers Are Used Extensively for AC Power Transmissions
    www.PDHcenter.com PDH Course E164 www.PDHonline.org Overview & Energy Optimization of Power Distribution Transformers Course Content A transformer is a static piece of apparatus used for transferring power from one AC circuit to another at a different voltage, but without change in frequency. It can step up or step down the voltage level with a corresponding decrease or increase of current. These are used extensively for AC power transmissions and for various control and indication circuits. Knowledge of the basic theory of how these components operate is necessary to understand the role transformers play in today’s facilities. MUTUAL INDUCTANCE A transformer operates on the principal of magnetic induction. When an AC voltage is applied to a coil, it produces a varying magnetic field around the coil. If a second coil is placed within this magnetic field then a voltage is induced in this second coil. This is called mutual induction. The magnetic field strength H, required to produce a magnetic flux density B, is proportional to the current flowing in the coil. The figure below shows the flux produced by the currents in the primary and secondary windings of a transformer when source current is flowing in the primary winding. Relationship between current, magnetic field strength and flux BASIC TRANSFORMER ACTION Each transformer consists of two or more coils which are not electrically connected, but are arranged in such a way that the magnetic field surrounding one coil cuts through the other coil. When an alternating voltage is applied to the one coil, the varying magnetic field set up around this coil creates an alternating voltage in the other coil.
    [Show full text]
  • IEEE Guide for the Grounding of Instrument Transformer Secondary
    PC57.13.3 IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases OUTLINE Scope References Need for grounding; Warning Definition of Instrument transformers Grounding secondary circuits Grounding at a single location Conductor size for connecting to ground Scope The scope of the guide includes the grounding practices presently used and the practices that were not previously reported. Specifically, the issue of the grounding of cases of electronic transducers is addressed. Covers The practices described in this standard apply to all instrument transformers, including capacitive voltage transformers and linear couplers, irrespective of primary voltage or whether the primary windings are connected to, or are in, power circuits or are connected in the secondary circuits of other transformers as auxiliary cts or vts. Does not cover This guide does not discuss the grounding of some applications. For example, grounding of gas insulated substations and metal clad switchgear is not discussed in this guide; the reader will find these topics addressed in reference [9] listed in clause 2. The grounding of circuits of core-balance CTs is also not discussed in this guide. The reader can find this information also in reference [9] listed in clause 2. Another issue that is not discussed in this guide is the practice of using separate safety and control grounds. For discussion on this topic, the reader is directed to reference [12] listed in clause 2. References [1] NFPA 70-2002, National Electricity Code® (NESC®) [2] ANSI C2-2002, National Electrical Safety Code® (NESC®) [3] C37.103™-2004, IEEE Guide for Differential and Polarizing Relay Circuit Testing [4] C57.13.1™-1981 (Reaffirmed 1999), IEEE Guide for Field Testing of Relaying Current Transformers [5] C37.92™-2004, IEEE Trial Use Standard for Low Energy Analog Signal Inputs to Protective Relaying References [6] C62.92™-2000, IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems [7] Std.
    [Show full text]
  • Electrical Energy Systems
    Electrical Energy Systems (Power Applications of Electricity) Summary of selected topics from University of Washington course EE 351: Energy Systems taught Fall 2015 by Prof. Baosen Zhang (BXZ) compiled by Michael C. McGoodwin (MCM). Content last updated 5/17/2016 Table of Contents Table of Contents ......................................................................................................................................... 1 Introduction ................................................................................................................................................. 2 Book chapters included in the course {and/or discussed in this summary} .................................... 3 History and Basic Science ............................................................................................................................ 4 Notable Persons in the History of Electricity ........................................................................................ 4 Voltage ............................................................................................................................................... 5 Current and Charge ............................................................................................................................ 5 Relating Voltage, Current, and Power .................................................................................................. 6 Resistance and Conductance, Resistance of a Wire (Pouillet's law) ......................................................
    [Show full text]
  • Low Voltage Distribution Transformers
    Your Presenters > Thomas Patzner Product Manager, Low Voltage Transformers > Marquette University – Electrical Engineering > Apprentice Electrician > Low Voltage Transformers - Co-op (Square D Company) (lab testing, inoperative trouble shooting, designing of units) - Application Engineer (Square D Company) - Sales Engineer (Jefferson Transformer) - Marketing (Square D Company) - Product Manager (Square D Company) 8 The Energy Policy and Conservation Act of 1975 (EPCA), as amended, prescribes energy conservation standards for various consumer products and certain commercial and industrial equipment, including distribution transformers. 9 EPACT 1992 • Authorized Department of Energy to evaluate Distribution Transformers Market Response • Energy Star – added Distribution Transformers to program – 1994 • NEMA – publishes Standard for Higher Efficient Transformers - 1996 • States Mandated NEMA Standard Level for Low Voltage Products (1999 through 2005) Department of Energy • DOE start analysis process • Advance Notice of Public Ruling – July, 2004 10 EPACT 2005 • Authorized DOE to mandate efficiency levels on Distribution Transformers • Low Voltage Transformers – Mandated to TP1 standard effected Jan, 2007 Market Response • Energy Star Program discontinued May, 2007 Department of Energy • DOE stop all work being done on Low Voltage units from the EPACT1992 • DOE finalized Medium Voltage Final Rule – 2007 – mandating levels effected Jan, 2010 • 10 CFR 431 includes how to test the distribution transformers • 10 CFR 429 -CERTIFICATION, COMPLIANCE, AND 11 ENFORCEMENT… COMMERCIAL AND INDUSTRIAL EQUIPMENT Distribution transformer means a transformer that— (1) Has an input voltage of 34.5 kV or less; (2) Has an output voltage of 600 V or less; (3) Is rated for operation at a frequency of 60 Hz; and (4) Has a capacity of 10 kVA to 2500 kVA for liquid-immersed units and 15 kVA to 2500 kVA for dry-type units; but… Liquid-immersed distribution transformer means a distribution transformer in which the core and coil assembly is immersed in an insulating liquid.
    [Show full text]