Grounding Transformers John S. Levine, P.E. Levine Lectronics and Lectric, Inc.
[email protected] 1 • It is used to provide a ground path on either an ungrounded Wye or a Delta connected system • The relatively low impedance path to ground maintains the system neutral at ground potential • On Ungrounded systems you can have overvoltages of 6 to 8 times normal with arcing faults Arcing Ground Faults Intermittent or Re-strike •Plot of transient over-voltage for an arcing ground fault Arcing Ground Faults Intermittent or Re-strike •Intermittent ground fault: A re-striking ground fault can create a high frequency oscillator (RLC circuit), independent of L and C values, causing high transient over- voltages. – i.e. re-striking due to ac voltage waveform or loose wire caused by vibration 480V Delta Source 3Ø Load Rfe V V Cb Cb S fa THE HIGH RESISTANCE GROUNDED POWER SYSTEM CONTROL OF TRANSIENT OVERVOLTAGE • It supports the voltage on a faulted phase – If a single line-to-ground fault occurs on an ungrounded or isolated system, no return path exists and no current flows – The system will continue to operate but the other two un- faulted lines will rise in in voltage by the square root of 3, possibly overstressing the transformer insulation, and other components, by 173% UNGROUNDED SYSTEM NORMAL CONDITIONS UNGROUNDED SYSTEM GROUND FAULT ON PHASE A • Provides a metering point to measure faults A typical example is a Wind Farm. They utilize grounding transformers for fault protection on ungrounded lines When a ground fault occurs on a collector cable causes the substation circuit breaker to open, the wind turbine string becomes isolated Turbines do not always detect the fault and the generators continue to energize the cable.