Innovative Airflow Solutions for Critical Environments
Principles of Laboratory Design and Fume Hood Operation Jim Hall CEO
The art of efficiency. The science of safety. TODAY’S OBJECTIVES
The ASHRAE 110 2016 Standard’s position on fume hood safety require new considerations in fume hood operation and lab design. Today’s presentation will review current lab control options and important design parameters.
TODAY’S OBJECTIVES
PRESENTATION OUTLINE
Lab Design Parameters History of Fume Hoods Review of Control Strategies Containment Testing and Performance ASHRAE 110-2016 Standard
FUME HOOD SPECIFICATIONS
WHERE ARE FUME HOODS TYPICALLY SPECIFIED? GENERALLY AN ARCHITECTURAL ITEM SPECIFICATION DRIVEN BY: ARCHITECT INDUSTRIAL HYGIENIST INTERIOR DECORATOR AMERICAN INSTITUTE OF ARCHITECTS (AIA)- MASTERSPEC - SECTION 115313 – LABORATORY FUME HOODS
HOWEVER, WE KNOW THAT CHEMICAL HOODS & THEIR OPERATION ARE CODIFIED LIFE SAFETY DEVICES CHEMICAL HOODS ARE INTRICATE PIECES OF MECHANICAL EQUIPMENT WITH SOPHISTICATED CONTROLS SUCCESSFUL IMPLEMENTATION REQUIRES COMPREHENSIVE SYSTEMS KNOWLEDGE
UPDATED STANDARDS FOR FACE VELOCITY
FACE VELOCITY HAS BEEN USED AS THE PRIMARY INDICATOR OF LABORATORY HOOD PERFORMANCE FOR SEVERAL DECADES.
FACE VELOCITY SHALL BE ADEQUATE TO PROVIDE CONTAINMENT. FACE VELOCITY NOT A MEASURE OF SAFETY. (SEFA 1-2002 SECTION 4.3.1 & 5.3.4)
“METHOD OF TESTING THE PERFORMANCE OF LABORATORY FUME HOODS” (ASHRAE 110 CONTAINMENT BASED TEST) REVEALS THAT THE FACE VELOCITY IS ACTUALLY AN INADEQUATE INDICATOR OF HOOD PERFORMANCE.
HOODS WITH EXCELLENT CONTAINMENT CHARACTERISTICS MAY OPERATE ADEQUATELY BELOW 80 FPM WHILE OTHERS MAY REQUIRE HIGHER FACE VELOCITIES. IT IS, THEREFORE, INAPPROPRIATE TO PRESCRIBE A RANGE OF ACCEPTABLE FACE VELOCITIES FOR ALL HOODS.
THE AVERAGE FACE VELOCITY ALONE IS INADEQUATE TO DESCRIBE HOOD PERFORMANCE REFERENCE ANSI/AIHA Z9.5-2012 CHALLENGE TO THE STANDARD THINKING
FUME HOODS USE SIGNIFICANT ENERGY FUME HOODS ARE LIFE SAFETY EQUIPMENT BALANCING SAFETY AND ENERGY IS A CHALLENGE FUME HOODS ARE A CRITICAL COMPONENT OF THE MECHANICAL SYSTEM FUME HOODS COME IN A WIDE VARIETY OF SPECIFICATIONS AND PERFORMANCE WHEN PROPERLY CONSIDERED, FUME HOODS CAN HAVE A SIGNIFICANT IMPACT ON THE ENTIRE BUILDING DESIGN, ENERGY AND SAFETY OF A LAB PROJECT Therefore, FUME HOODS SHOULD BE PART OF THE MECHANICAL SPECIFICATION and considered as an important piece of the mechanical design
Critical Lab Design Parameters
• SAFETY – Occupant safety at fume hood and room level. – Accurate measurement that reliably responds to changes and restores safe set points. – Face Velocity of hoods must be measured and exhaust systems modulated rapidly to hold defined set points. – Rapid restoration to safe set points for fume and pathogen containment to prevent roll-outs or containment breaches.
• CONTAINMENT – Removal of airborne substances, fumes and contaminants. – Labs and Isolation Rooms must have supply/make up air systems which can track the total exhaust for each area or zone to achieve proper air balance and minimum air change per hour specifications while maintaining predetermined room air static pressure.
Once safety parameters are defined, it is recommended to use a Closed Loop Control in order to reach and hold safety set points effectively
Secondary Lab Design Parameters
STABILITY – Accurate measurement that reliably responds to changes and restores safe set points. – Vacillations of less than 5% from desired set point (or as determined by engineer/TAB) to ensure that the system is measuring relatively stable and actual airflow
COMFORT – Effective temperature and humidity control.
FLEXIBILITY AND SCALABILITY – Adaptation to a variety of technologies. – Adjustability to meet site design specification and regulatory requirements as well as modifications to environment.
Laboratory Containment
Reduce or eliminate exposure of laboratory workers, other persons, and the outside environment to potentially hazardous agents! Primary Containment: Protection of personnel and the immediate laboratory environment from exposure to infectious agents. Achieved through a combination of appropriate selection and operation of safety equipment. Hood level. Secondary Containment: Protection of the environment external to the laboratory from exposure to infectious materials. Achieved through a combination of facility design and operational practices. Room level. Laboratory Containment
Proper fume hood face velocity control impacts overall lab air control.
Good system design must accommodate the strong interrelationship between the laboratory air supply and the large and varying air supply demands created by fume hood operation
A lab equipped with fume hoods must design the supply airflow capacity with a substantial increase over that of conventional HVAC design for the same size space. Larger supply airflow is needed to provide the airflow required by the fume hoods when in use.
General exhaust flow capacity is not necessarily increased for the lab with fume hoods.
Temperature control is secondary to airflow control needed for meeting fume hood needs.
Supply air control must be designed to enable the airflow rate to be modulated in response to the varying demands of fume hood activity. Airflow variations will frequently be in the order of several hundred CFM to several thousand CFM in labs containing multiple fume hoods. Changes are sudden and may be large, requires control that is different from conventional rooms. Control must be capable of adjusting the supply airflow requirements substantially and quickly, to ensure the safety of personnel who are using fume hoods.
Laboratory Containment
There are three separate control systems that make up the overall control system in a variable volume laboratory:
A control system for each fume hood to control the flow into the fume hood to assure capture and containment by the fume hood (to maintain a constant sash opening velocity).
A control system for the bypass air damper on the exhaust fan system to ensure sufficient velocity through the exhaust stack.
A room ventilation control system which maintains; room pressurization, a minimum number of air changes, and comfort levels within the laboratory. LAB DESIGN POSSIBILITIES
NEW CONSTRUCTION RETROFIT OF EXISTING LAB EXPANSION OF EXISTING LAB REDESIGN OF EXISTING LAB
DESIGN DRIVERS
PRIORITIES MAY VARY DEPENDING ON PROJECT SAFETY IS ALWAYS PARAMOUNT BUDGET ENERGY USAGE CAPACITY OF SYSTEMS CODE COMPLIANCE
LAB CONSTRUCTION OPTIONS
DEPENDING ON OWNER NEEDS CAN INCLUDE: NEW LAB CONSTRUCTION IN-SITU RETROFIT OF MECHANICAL LEAVE MECHANICAL SYSTEMS IN PLACE UPGRADE FROM ANALOG TO DIGITAL CONTROLS ADDITION OF Fume Hood controls IN-SITU RETROFIT OF FUME HOODS CONVERSION TO LOW FLOW HIGH PERFORMANCE TO INCREASE CAPACITY GRANDFATHERED BUILDINGS
BRIEF HISTORY OF THE FUME HOOD BASIC FUME HOOD OPERATION
EXTENSION OF MECHANICAL DUCTWORK (PROPER DESIGN AND SYSTEM CONSIDERATION ARE CRITICAL FOR SUCCESS) APPLICABLE AIRFLOW FUNDAMENTALS
VELOCITY PRESSURE ENERGY AVAILABLE IN FUME HOODS
FUME HOOD FACE VELOCITY – VELOCITY PRESSURE
120 fpm - 0.000898 in. of w.c. 100 fpm - 0.000623 in. of w.c. 80 fpm - 0.000399 of w.c.
FUME HOOD FACE VELOCITY EXPRESSED AS MPH
120 fpm - 1.36 mph 100 fpm - 1.13 mph 80 fpm - 0.91 mph APPLICABLE AIRFLOW FUNDAMENTALS
• Dynamic changes in sash position can cause fumes to spill from the fume hood.
• Turbulence can bring contaminants back into the user's breathing zone.
• Too low a velocity: the hood will not be capable of containing generated fumes.
• Too high and turbulent: can cause fumes to escape.
• Turbulent events include: – operator movement – blockages of the fume hood opening – air diffusion patterns – pedestrian traffic in front of the hood – room static pressure changes – duct static pressure challenges – fan failures – air distribution – thermal convection – container storage within the hood – poor air register placement – discharge that produces a shear flow – disruptive supply terminal velocity
HOOD FAILURE - SPILLAGE
TYPICAL LOCATION OF HOOD SPILL IS AT SASH HANDLE
HOOD SPILLS WHEN VORTEX COLLAPSES! HOOD FAILURE - SPILLAGE
CONTAINMENT TEST W/ LP MSV HOOD: SF6 TRACER GAS @ 100 FPM FACE VELOCITY CASE 1: PROPER USE CASE 2: ADVERSE USE CASE3: ADVERSE USE EQUIPMENT 6” FROM EQUIPMENT 1” FROM EQUIPMENT 1” FROM SASH SASH SASH EQUIPMENT RAISED EQUIPMENT RAISED EQUIPMENT ON WORK SURFACE CFD CONTAINMENT MODELING
CONTAINMENT = SAFETY 51 FPM FACE VELOCITY 0 PPM LEAKAGE BY CFD AND EMPIRICAL TEST CFD CONTAINMENT MODELING
CONTAINMENT = SAFETY 51 FPM FACE VELOCITY 0 PPM LEAKAGE BY CFD AND EMPIRICAL TEST NOTION OF HOOD PERFORMANCE
SCIENTIFIC APPARATUS MAKER ASSOCIATION (SAMA) STANDARD FOR LABORATORY FUME HOODS (NOW KNOWN AS THE LABORATORY PRODUCTS ASSOCIATION)
5.1.3 SPECIFIC MATERIALS THAT ARE TO BE USED IN THE FUME HOODS WHICH MAY AFFECT FACE VELOCITY. LIGHT WEIGHT POWDERS THAT HAVE NO TOXICITY HAZARD MAY DICTATE VERY LOW FACE VELOCITIES. KYMOGRAPH HOODS ALSO REQUIRE VERY LOW VELOCITIES. HOODS USED TO HOUSE LABORATORY TYPE MACHINE TOOLS , GRINDERS OR CENTRIFUGES MAY REQUIRE HIGHER FACE VELOCITIES THAN TOXICITY LEVELS MIGHT DICTATE.
5.2 FACE VELOCITY GUIDE. FACE VELOCITIES OF LABORATORY FUME HOODS MAY BE ESTABLISHED ON THE BASIS OF THE TOXICITY OR HAZARD OF THE MATERIALS USED OR THE OPERATIONS CONDUCTED WITHIN THE FUME HOOD. A SUGGESTED GUIDE FOR DETERMINING FACE VELOCITIES THAT MAY BE SUITABLE FOR LABORATORY FUME HOODS IS AS FOLLOWS:
5.2.1 CLASS A FUME HOODS. FUME HOODS IN THIS CLASSIFICATION ARE USED FOR MATERIALS OF EXTREME TOXICITY OR HAZARD SUCH AS TETRAETHYL LEAD, BERYLLIUM COMPOUNDS, METAL CARBONYLS AND VOLATILE CARCINOGENS. THE RECOMMENDATIONS FOR AVERAGE VELOCITY AT THE FACE OF THE FUME HOOD IS 125 TO 150 FEET PER MINUTE (38.1M/MIN TO 45.7 M/MIN) (.64M/S TO .76M/S) WITH THE CORRESPONDING MINIMUMS AT ANY ONE POINT 100 TO 125 FEET PER MINUTE (30.48 M/MIN TO 38.1 M/MIN) (.51M/S TO .64 M/S).
5.2.2 CLASS B FUME HOODS. FUME HOODS IN THIS CLASSIFICATION ARE USED FOR MOST MATERIALS AND OPERATIONS IN THE LABORATORY. THE RECOMMENDATION FOR AVERAGE VELOCITY AT THE FACE OF THE FUME HOOD IS 100 FEET PER MINUTE (30.48 M/MIN) (.51 M/S), WITH A MINIMUM AT ANY ONE POINT OF 80 FEET PER MINUTE (24.4 M/MIN), (.41 M/S).
5.2.3 CLASS C FUME HOODS. FUME HOODS IN THIS CLASSIFICATION ARE USED FOR MATERIALS OR OPERATIONS WHERE THE HAZARD IS NOT HIGH. CLASS C FUME HOODS MAY BE USED FOR LOW TOXICITY MATERIALS SUCH AS ACETONE, ETHANOL AND STRAIGHT-CHAIN HYDROCARBONS, AND FOR OPERATIONS CREATING NUISANCE DUSTS AND FUMES. THE RECOMMENDATIONS FOR AVERAGE VELOCITY AT THE FACE OF THE FUME HOOD RANGE FROM 75 TO 80 FEET PER MINUTE (22.9 M/MIN TO 24.4 M/MIN) (.38 M/S TO .41 M/S). WITH CORRESPONDING MINIMUMS AT ANY ONE POINT OF 50TO 60 FEET PER MINUTE (15.24 M/MIN TO 18.3 M/MIN) (.25 M/S TO .31 M/S). NOTION OF HOOD PERFORMANCE
ASHRAE HVAC APPLICATION HANDBOOK 1999 & 2003 EDITION COMPARISON
TYPICAL SYSTEM PARAMETERS
DESIGN FOR LIFE SAFETY AND CODE COMPLIANCE PARADIGMS VARIABLE-AIR-VOLUME (VAV) CONSTANT-AIR-VOLUME (CAV) HIGH PERFORMANCE EXHAUST AND SUPPLY CAPACITY TURNDOWN / SETBACK SYSTEM STABILITY & RESPONSE TIME SUPPLY DIFFUSER (LOCATION) EXHAUST DUCTWORK CONFIGURATION DIVERSITY (MORE LATER) INITIAL/ONGOING COMMISSIONING LAB PROGRAMMING & FUNCTION STANDARD OPERATING PROCEDURE LIFE-CYCLE COSTING / ENERGY USAGE TYPICAL LABORATORY ANATOMY FUNDAMENTAL CONTROL STRATEGIES SYSTEM ARCHITECTURE
VARIABLE AIR VOLUME CONSTANT AIR VOLUME
FUNDAMENTAL CONTROL STRATEGIES
COMMON COMPONENTS SAFETY MONITOR FLOW/VELOCITY SENSING TECHNOLOGY EXHAUST SYSTEM SUPPLY/MAKE-UP AIR SYSTEM
VARIABLE AIR VOLUME VFD CONTROL OUTPUT (SASH POSITION/OCCUPANCY SENSOR) VAV EXHAUST VALVE W/ ACTUATOR VAV SUPPLY VALVE W/ ACTUATOR ROUTERS/GATEWAYS SYSTEM CONTROLLER
CONSTANT AIR VOLUME BALANCING DAMPER 2 POSITION STRATEGY TO TAKE ADVANTAGE OF MINIMUM HOOD AIRFLOWS PER NFPA VFD OR BYPASS PLENUM 2 POSITION ACTUATORS CONTROLLER FUNDAMENTAL CONTROL STRATEGIES VARIABLE AIR VOLUME (VAV) BASIC PRINCIPLES
SUPPLY TEMPERATURE IS CONSTANT AND AIR VOLUME IS VARIED TO CONTROL SPACE CONDITION
EXHAUST VOLUME VARIES TO MEET VENTILATION DEMAND
FUME HOOD EXHAUST VOLUME VARIES BASED ON FACE VELOCITY
FUME HOOD REVERTS TO MINIMUM ACCEPTABLE FLOWS BASED ON OPERATOR PRESENCE/SASH POSITION HOOD LEVEL CONTAINMENT
Options Sash Sensing Velocity Sensing Sash Sensing with Velocity Sensing Constant Volume Venturi Valve Venturi Valve with Electronic Actuation Venturi Valve with Pneumatic Actuation ROOM LEVEL CONTAINMENT
Constant Volume Venturi Valves at the Hood and/or Room Level Fixed Volume Offset with Venturi Valve at the Room Level Pressure Monitoring/Control at the Room Level Sash Sensing with Room Level Volumetric Offset Sash Sensing with Velocity Sensor Safety Override at the Hood and Room Level Volumetric Offset Velocity Sensor Safety Override at Both the Hood and the Room Level Sash Sensing with Velocity Safety Override at Both the Hood and the Room Level FUNDAMENTAL CONTROL STRATEGIES CONSTANT AIR VOLUME (CAV) BASIC PRINCIPLES
SUPPLY AIR VOLUME REMAINS CONSTANT AND TEMPERATURE VARIES TO CONTROL SPACE CONDITIONS
VENTILATION DEMAND IS HANDLED BY CONSTANT EXHAUST VOLUMES TWO-POSITION/SET BACK STRATEGIES OFTEN EMPLOYED
FUME HOOD EXHAUST VOLUME IS CONSTANT FUME HOODS CAN BE BYPASS TYPE AUXILIARY AIR TYPE HIGH PERFORMANCE FUNDAMENTAL CONTROL STRATEGIES CAV WITH VARIABLE FACE VELOCITY (VFV) Variable Face Velocity
Available on Low Flow High Performance Hoods VENTILATION DEMAND IS HANDLED BY CONSTANT EXHAUST VOLUMES TWO-POSITION/SET BACK STRATEGIES OFTEN EMPLOYED FUME HOOD EXHAUST VOLUME IS CONSTANT MEASURING AND MAINTAINING A STABLE VORTEX RATHER THAN CONTROLING TO FACE VELOCITY NO LONGER MEASURING OR CONTROLLING TO FACE VELOCITY CONSTANT VOLUME WITH VFV STABILIZED VORTEX
HENRI COANDA SHOWED THAT A STABLE VORTEX REMAINS STATIONARY ON TWO OR MORE OPPOSING SURFACES AND IS FULLY DEVELOPED EVEN WITH TURBULENCE ON ONE OF IT’S CONTROLLING JET STREAMS
A STABLE VORTEX HAS MEMORY AND MOMENTUM
CONSTANT VOLUME WITH VFV
STABILIZED VORTEX = CONTAINMENT
CONSTANT VOLUME EXHAUST
STABLE VORTEX VFV CONTROLLER
VFV-C LO PRESS DROP LINEAR DAMPER
AIRFLOW PROBE
VORTEX
ALARM VANVURI VALVE ACTUATOR
TOTAL PRESS VORTEX SENSOR
CONSTANT VOLUME VENTURI VALVE (ROOM AIR)
R NEW - STABLE VORTEX FUME HOOD DATE: 07/2009 CONSTANT VOLUME WITH VFV
STABLE VORTEX AT MULTIPLE SASH POSITIONS
CV CV CV
Stable Vortex Stable Vortex Stable Vortex VFV Controller VFV Controller VFV Controller
Lo Press Drop VFV-C VFV-C Lo Press Drop VFV-C Lo Press Drop Linear Damper Linear Damper Linear Damper
Airflow Airflow Airflow Probe Probe Probe
Vanvuri Valve Vanvuri Valve Vanvuri Valve Total Press Actuator Total Press Actuator Total Press Actuator Vortex Sensor Vortex Sensor Vortex Sensor
Venturi Venturi Venturi Valve Valve Valve CV
CV
CV
Sash Full Open Sash Half Open Sash Fully Closed (Venturi Valve Full Open) (Venturi Valve Partially Closed) (Venturi Valve 90% Closed)
New - Stable VortexR Fume Hood DATE: 07/2009 APPLICABLE CODES & STANDARDS
NFPA – 45 STANDARD ON FIRE PROTECTION FOR LABORATORIES USING CHEMICALS – 2015 EDITION NFPA – 30 FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE – 2015 EDITION OSHA - CODE OF FEDERAL REGULATIONS (CFR) TITLE 29, LABOR, PART 1910 – REVISED JULY 2016 §1910.1450 OCCUPATIONAL EXPOSURE TO HAZARDOUS CHEMICALS IN LABORATORIES ANSI/AIHA z9.2 – 2012 FUNDAMENTALS GOVERNING THE DESIGN AND OPERATION OF LOCAL EXHAUST VENTILATION SYSTEMS ANSI/AIHA z9.5 – 2012 LABORATORY VENTILATION § 3.3.1 Face Velocity and 3.3.2 Laboratory Hood Minimum Flow Rate ASHRAE HANDBOOK - HVAC APPLICATIONS ASHRAE STANDARD 110 - 2016 METHOD OF TESTING PERFORMANCE OF LABORATORY HOODS PERFORMANCE TESTING
ASHRAE STANDARD 110 – 2016 METHOD OF TESTING PERFORMANCE OF LABORATORY HOODS PERFORMANCE TESTING
SCOPE METHOD APPLIES TO CONVENTIONAL, BYPASS, AUXILIARY AIR, AND VARIABLE AIR VOLUME LABORATORY FUME HOODS
THE METHOD CONSISTS OF THE FOLLOWING TESTS 1. FLOW VISUALIZATION 2. FACE VELOCITY MEASUREMENTS 3. TRACER GAS CONTAINMENT
WHAT IS NOT DESCRIBED IN THE STANDARD (BUT CRITICAL) 1. CROSS-DRAFTS 2. WORK PROCEDURES 3. INTERNAL OBSTRUCTIONS 4. THE PROCEDURE BEING PERFORMED 5. THERMAL CHALLENGE 6. RATE OF RESPONSE PERFORMANCE TESTING - CONTAINMENT
PERFORMANCE RATING
A RATING DESIGNATED BY A SERIES OF LETTERS AND NUMBERS CONSISTING OF THE LETTERS AM, AI, OR AU AND A TWO- OR THREE-DIGIT NUMBER:
AM yyy AI yyy AU yyy
WHERE: AM IDENTIFIES AN “AS MANUFACTURED” TEST THE LABORATORY HOOD IS BUILT AND ASSEMBLED BY THE MANUFACTURER AND TESTING IS PERFORMED AT THE FACTORY. AI IDENTIFIES AN “AS INSTALLED” TEST THE LABORATORY HOOD IS INSTALLED AT THE LOCATION OF THE CUSTOMER. THE HOOD IS TESTED EMPTY, BUT WITH THE VENTILATION SYSTEM IN THE INSTALLATION BALANCED AND THE HOOD IN ITS FINAL LOCATION. AU IDENTIFIES AN “AS USED” AND TEST THE TEST IS CONDUCTED AFTER THE HOOD HAS BEEN INSTALLED AND USED BY THE CHEMIST. THE TYPICAL EQUIPMENT REMAINS IN THE HOOD AND OTHER ACTIVITIES IN THE LABORATORY CONTINUE. YYY IS THE CONTROL LEVEL OF TRACER GAS ESTABLISHED BY THE TEST IN PPM PERFORMANCE TESTING - CONTAINMENT
SASH PERFORMANCE RATING
A RATING DESIGNATED BY A SERIES OF LETTERS AND NUMBERS CONSISTING OF THE LETTERS SME-AM, SME- AI, OR SME-AU AND A TWO- OR THREE-DIGIT NUMBER:
SME-AM yyy SME-AI yyy SME-AU yyy
WHERE: SME MEANS “SASH MOVEMENT EFFECT THE MAXIMUM 45-SECOND ROLLING AVERAGE OF THE POSITIONAL TRACER GAS CONCENTRATION OBSERVED DURING A SERIES OF SASH MOVEMENT EFFECTS FOR ALL TESTS AT THE POSITIONS TESTED ON A CENTER OF THE HOOD OPENING. AM IDENTIFIES AN “AS MANUFACTURED” TEST AI IDENTIFIES AN “AS INSTALLED” TEST AU IDENTIFIES AN “AS USED” AND TEST YYY IS THE SASH MOVEMENT EFFECT IN PPM PERFORMANCE TESTING
IF USING THE STANDARD AS PART OF A SPECIFICATION THE FOLLOWING MUST BE SPECIFIED: 1. SASH TEST OPENING OR OPENINGS, WHICH SHOULD ADDRESS BOTH THE DESIGN OPENINGS AND TYPICAL USE OPENINGS 2. AVERAGE FACE VELOCITY 3. RANGE OF FACE VELOCITIES 4. AVERAGE FACE VELOCITY FOR SASH AT 25% AND 50% OF THE DESIGN HOOD OPENING 5. ACCEPTABLE SMOKE VISUALIZATION TESTS 6. PERFORMANCE RATING (AS DEFINED IN THE STANDARD) 7. SASH MOVEMENT PERFORMANCE RATING 8. FOR VARIABLE AIR VOLUME HOODS, THE SPEED OF RESPONSE AND TIME TO STEADY STATE THE TIME, MEASURED FROM THE FIRST MOVEMENT OF THE SASH, FOR THE VAV SYSTEM TO RESTORE THE SLOT VELOCITY OR AIRFLOW TO 90% OF THE AVERAGE STEADY-STATE VALUE. AND TIME TO STEADY STATE THE TIME, MEASURED FROM THE FIRST MOVEMENT OF THE SASH, FOR THE VAV SYSTEM TO RESTORE AND MAINTAIN THE AVERAGE SLOT VELOCITY OF AIRFLOW BETWEEN 90% AND 110% OF THE AVERAGE STEADY-STATE VALUE 9. FOR AUXILIARY AIR HOODS, THE PERCENTAGE OF AUXILIARY AIR SUPPLY 10. SPECIAL CONDITIONS OR TESTS CAV WITH VFV
FACE VELOCITY ALONE IS NOT AN ADEQUATE INDICATOR OF HOOD PERFORMANCE
CONTAINMENT IS ACHIEVED BY CONTROLLING / MAINTAINING A STABLE VORTEX IN THE HOOD IN RESPONSE TO STATIC AND DYNAMIC CHALLENGES
PROPER HOOD DESIGN RESULTS IN A STABLE VORTEX AT SIGNIFICANTLY LOWER AIRFLOW SUMMARY
FACE VELOCITY ALONE IS NOT AN ADEQUATE INDICATOR OF HOOD PERFORMANCE
FUME HOODS ARE AN IMPORTANT COMPONENT OF THE LAB MECHANICAL SYSTEMS
INCREASED FLEXIBILITY IN LAB DESIGN OPTIONS MEAN THE HOOD SHOULD BE CONSIDERED PART OF THE MECHANICAL SPECIFICATION
SUMMARY
LAB SAFETY RESPONSIBILITY IS NOT SATISFIED SOLELY BY TESTING FACE VELOCITY.
FUME HOODS WIDELY VARY IN PERFORMANCE, SPECIFICATION, AND HOW THEY ARE USED.
FUME HOODS SHOULD BE CONSIDERED AN INTEGRAL PART OF THE MECHANICAL SYSTEM AND THE CONTROL STRATEGY. CONSIDER ALL THE RIGHT CONTROL STRATEGIES IN CHOOSING THE BEST ONE FOR THE PROJECT NEEDS.