5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
MODULE 5 HVAC FUNDAMENTALS OF MODERN LABORATORY DESIGN
Module 5 PG1 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
MODULE 5 GOAL Provide a fundamental understanding of Laboratory Heating, Ventilating and Air Conditioning Concepts and Systems
Module 5 PG2 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 6 Outline
• Issues • Drivers • Concepts • Systems
Module 5 PG3 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Issues • “It’s too hot and humid in my lab!” Some of the most common concerns of • “It’s too cold and dry in laboratory facility users are relative to the my lab!” HVAC system, including: • “It’s like a tornado in my lab!”
Module 5 PG4 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Drivers
• Laboratory Equipment Heat Generation • Air Change Rates • Containment Equipment • Occupant Gowning Requirements • Type of Laboratory and Science
Module 5 PG5 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Drivers – Laboratory Equipment Heat Generation
Heat Generation Information • Heat is expressed in BTU/Hour • 1 Watt = 3.414 BTU/Hour • Sensible Heat: Energy Required to Change Temperature • Latent Heat: Energy Required to Remove Moisture • One Ton of Air Conditioning: 12,000 BTU/Hour or 3,515 Watts • 135 cfm of outside air equals 1 ton of cooling (Kansas City weather) Module 5 PG6 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Drivers – Laboratory Equipment Heat Generation
Loads for Bench Mounted Equipment (low density)
Item Bench L.F. Btuh Optical Microscope 2 222 Analytical balance 2 24 Computer & Monitor 4 461 Rotary Evaporator 3 253 Total 11 960 Btuh Per Linear Foot 87 Watts per linear foot 26
Sources: ASHRAE 2001 Fundamentals Handbook Labconco Catalog Revco Freezer Data Sheets NOTE: This is heat release, not equipment nameplate electrical data
Module 5 PG7 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Drivers – Laboratory Equipment Heat Generation
Loads for Bench Mounted Equipment (high density)
Item Bench L.F. Btuh Optical Microscope 2 222 Small Centrifuge 3 304 Thermal Cycler 2 795 Fluorescent Microscope 2 700 Flame Photometer 2 365 Rotary Evaporator 3 253 Total 14 2639 Btuh Per Linear Foot 189 Watts per linear foot 55 Sources: ASHRAE 2001 Fundamentals Handbook Labconco Catalog Revco Freezer Data Sheets
Module 5 PG8 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Drivers – Laboratory Equipment Heat Generation
Loads for Floor Mounted Equipment (high density)
Item Floor L.F. Btuh Ultra Low Freezer 4 3618 Large Centrifuge 4 4014 Large Incubator 4 4556 Refrigerator 3 1672 Total 15 13860 Btuh Per Linear Foot 924 Watts per linear foot 271
Sources: ASHRAE 2001 Fundamentals Handbook Labconco Catalog Revco Freezer Data Sheets
Module 5 PG9 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Drivers – Laboratory Equipment Heat Generation Two Module Lab Example (484 SF): • 16 feet of space allocated for floor mounted equipment • 48 feet of bench space • Assume half the bench is full – 24’ of equipment Heat Generated using moderate density: • Bench: 138 btuh/ft X 24’ = 3312 btuh • Floor: 662 btuh/ft X 16’ = 10,592 btuh • Total: *13,904 btuh More than 1 ton of A/C • Using 100% outside air in Kansas City: 57,300 btuh (4.75 tons) *There is no diversity in this number Module 5 PG10
5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Drivers – Laboratory Equipment Heat Generation When figuring equipment heat gain: • Use published or measured heat release information, not electrical nameplate • Apply diversity carefully based on expected lab use • Consider sub-metering loads in similar buildings prior to planning a new lab • The answer is not “10 watts/sq.ft.”
Module 5 PG11 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Drivers – Air Change Rates • 1 Air Change per Hour – The Amount of Air in Cubic Feet per Minute (CFM) it Takes to Completely Replace the Air in a Laboratory once in One Hour • CFM = (Floor Area x Ceiling Height x Air Change Rate)/60 • 135 CFM per One Ton of Cooling • Standards and Guidelines Vary from 4 to 12 AC/hr
Module 5 PG12 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Drivers – Air Change Rates • 2 Module Laboratory (22’ x 22’); 484 SF • CFM Requirement for varying ceiling heights and air change rates
MORE IS NOT NECESSARILY BETTER Airflow in CFM at Given Air Change Rate
Ceiling Height 6 8 10 12 9 436 581 726 871 10 484 645 807 968 11 532 710 887 1065 12 581 774 968 1162
Module 5 PG13 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Drivers – Air Change VS. Fume Hoods
• 2 Module Laboratory (22’ x 22’); 484 SF
• CFM Requirement for varying ceiling Nominal Fume Hood CFM heights and air changes
5' Fume 6' Fume 8' Fume Hood Hood Hood Airflow in CFM at Given Air Change Rate 960* 1180* 1660* Ceiling Height 6 8 10 12 610** 750** 1060** 9 436 581 726 871 * Sash full open; face 10 484 645 807 968 11 532 710 887 1065 velocity 100 fpm 12 581 774 968 1162 ** Sash at 18”; face velocity 100 fpm
Module 5 PG14 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Drivers – Containment Equipment Approximate Exhaust CFM for 6’ BSC • Class II Type A2 Cabinet without canopy: 0 cfm • Class II Type A2 Cabinet with canopy: 600 - 700 cfm • Class II Type B2 Cabinet : 1150 cfm (requires a dedicated exhaust fan
Select the correct cabinet for the application
Cabinets that use ECM motors have significantly lower heat gain and
higher efficiency than PSC motors Module 5 PG15 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Drivers – Air Changes VS. Containment Equipment
• *Laboratories often use 4 to 6 times more energy per sq. ft. than a typical office building • *Nearly half of electrical energy used in a laboratory building can be attributed to ventilation • The decision on air exchange rates and fume hood sash position affect both first cost and lifetime building energy Annual electricity use in Louis Stokes Laboratory, National Institutes of Health, Bethesda, MD costs Courtesy of Labs 21
*Courtesy of Labs 21
Module 5 PG16 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Drivers – Gowning/PPE
Impact of Gowning/PPE in Laboratory • May require reduction in Laboratory Design Temperature • Reducing Design Temperature from 72 deg. F to 70 deg. F results in: • A 12% increase in cooling airflow • A 12% increase in cooling capacity
Module 5 PG17 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Drivers – Type of Laboratory/Type of Science
Animal Holding Rooms • 10 to 15 Air Changes per hour
Module 5 PG18 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Drivers – Type of Laboratory/Type of Science
Instrument/Computational Laboratories • High Equipment Heat Loads
Module 5 PG19 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Drivers – Type of Laboratory/Type of Science
Chemistry/Analytical Laboratories • High Fume Hood Density
Module 5 PG20 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
MODULE 5 – BASIC CONCEPTS
Laboratory Hazards Containment Flexibility & Redundancy
Module 5 PG21 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Laboratory Hazards
Health Hazards • Irritants • Corrosive Substances • Allergens • Asphyxiants • Carcinogens • Reproductive Toxins • Neurotoxins Flammability Hazards Reactivity Hazards Explosive Hazards Biohazards Radioactive Hazards Module 5 PG22 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Containment Primary Containment • First Level of Containment; typically a containment device: chemical fume hood, biological safety cabinet, etc.
Module 5 PG23 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Containment Secondary Containment • Second Level of Containment: • Laboratory Envelope • Directional Airflow • 100% Outside Air • Differential Pressure or Volumetric Offset • Doors must be kept closed • Exhaust fans run continuously
Best Practices: Use Primary and Secondary Containment to Protect Personnel from Exposure to Hazards
ANSI Z9.5 requires air movement from lower hazard to higher hazard Module 5 PG24
5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Containment
Primary Containment Devices - Chemical Fume Hoods • Bench Mounted Chemical Fume Hoods • Each Fume Hood uses as much energy as an entire house*
* From Labs 21
Module 5 PG25 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Containment Primary Containment Devices - Chemical Fume Hoods • Floor Mounted Chemical Fume Hoods or Ventilated Enclosures
Module 5 PG26 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Primary Containment Devices - Chemical Fume Hoods • Floor Mounted Hood Location is Critical
Module 5 PG27 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Containment
Primary Containment Devices - Chemical Fume Hoods • Radioisotope Hood • Stainless steel interior • Requires dedicated exhaust fan • Coved corners for decontamination • May need HEPA filters • Consult your Radiation Safety Officer
Module 5 PG28 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Containment
Primary Containment Devices - Chemical Fume Hoods • Perchloric Acid Hood • Acid resistant interior • Dedicated acid resistant ran • Acid resistant sealed ductwork • Washdown system • Treat wastewater from washdown • Do NOT manifold these hoods
Module 5 PG29 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Containment
Primary Containment Devices - Chemical Fume Hoods • Variable Volume Fume Hood • Face velocity is maintained constant as sash is raised and lowered • Requires pressure independent control device • Requires variable control – usually exhaust air bypass damper • Must maintain a minimum flow when sash is fully closed (ANSI Z9.5 no longer specifies how much) Module 5 PG30 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Containment
Primary Containment Devices - Chemical Fume Hoods • “High Performance” Fume Hood • Hood provides containment at lower face velocity • Each manufacturer uses a different design • Apply with caution Labconco • “Low Flow does not necessarily equate to “High Performance” • More sensitive to cross drafts
Lawrence Berkeley Labs Module 5 PG31 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Containment
Primary Containment Devices - Chemical Fume Hoods • “Ductless” Fume Hood • Uses activated carbon and/or HEPA filters • Use only in tightly controlled conditions • NFPA 45 allows only for nuisance vapors & dusts
Module 5 PG32 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Containment
Primary Containment Devices – Biological Safety Cabinets • Personnel protection • Environmental protection • Can provide product protection • Not a chemical fume hood!!!! • Used for biological/microbiological work
Module 5 PG33 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Containment Biological Safety Cabinets (BSC’s) • Class I: Ventilated cabinet for personnel and environmental protection. No product protection • Class II: Ventilated cabinet for personnel, product, and environmental protection. Type A1, A2, B1, and B2 • Class III: Totally enclosed ventilated cabinet of leak-tight construction. Operations conducted through attached rubber gloves. Sometimes called glove boxes.
Select the correct cabinet for the application Module 5 PG34
5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Other Devices (Non Containment)
Other Devices – Not Chemical Fume Hoods • Canopy Hoods • Snorkels • Slot Hoods
Module 5 PG35 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Other Devices (Non Containment)
Other Devices – Canopy Hoods • Not appropriate for fumes • Hot applications only (ovens, GC/MS, non-hazardous hot tanks, glassware washing, cage washing, etc.) • Must have mass of hot moving air to contain
Module 5 PG36 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Other Devices (Non Containment)
Other Devices – Snorkel Hoods • Bench top activities that require exhaust • Ideal containment device for dissections • Good for bench top soldering, etc.
Module 5 PG37 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Flexibility and Redundancy
Three truths for the Laboratory HVAC Designer • What’s happening in the laboratory tomorrow will be different than what’s happening today • Fume hood density nearly always increases over time • The amount of heat generating equipment will increase over time
Module 5 PG38 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Concepts – Flexibility and Redundancy
Plan for flexibility and future growth • Allow extra space in the mechanical room to add equipment (chiller, boiler, air handler, exhaust fans) • Allow for additional shaft and ceiling space • Size ducts and pipe for spare capacity (inexpensive if done initially)
Module 5 PG39 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
MODULE 5 – SYSTEMS
HVAC
Module 5 PG40 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Systems – HVAC
Laboratory HVAC • Look at three different criteria and choose worst case: • Cooling load (primarily heat generating equipment) • Minimum air change rate • Exhaust requirement • Consider supplemental cooling for high density loads (freezer rooms, etc.)
Module 5 PG41 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Systems – HVAC Laboratory HVAC Design Considerations • “The effect of room air challenge is significant and of the same order of magnitude as the effect of face velocity” • “Consequently, improper design of replacement air supply can have a disastrous effect on the efficiency of a laboratory hood.”
ASHRAE RP-70, Caplan and Knutson, 1977
Module 5 PG42 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Systems – HVAC Laboratory HVAC Design Considerations • “Supply air distribution shall be designed to keep air jet velocities less than half, preferably less than one-third of the capture velocity or the face velocity of the laboratory chemical hoods at their face opening.” ANSI/AIHA Z9.5-2003, section 5.2.2
Module 5 PG43 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Systems – HVAC Laboratory Exhaust Systems • Fan discharge design must minimize risk of re-entrainment • Stack/Intake separation • Stack height • Stack effective height/momentum • Stack discharge velocity must be 3,000 fpm, minimum
Module 5 PG44 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Systems – HVAC
Laboratory Exhaust Systems • Heat Recovery • Air to air plate heat exchanger • Run around loop • Molecular sieve enthalpy wheel
Module 5 PG45 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Systems – HVAC
Laboratory Exhaust Systems • ANSI/ASHRAE/IESNA 90.1 – 2010 • Prescriptive path requires some combination of VAV and/or heat recovery for most lab HVAC systems • Alternative is Energy Cost Budget Method
Module 5 PG46 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Systems – HVAC
Laboratory Exhaust Systems • ANSI/ASHRAE 62.1 – 2010 • January, 2011 interpretation precludes using any technology for laboratory fume hood or chemical storage room exhaust heat recovery that results in any amount of cross contamination • This appears to disallow the use of total energy recovery wheels • Addendum K is out for public review
Module 5 PG47 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Systems – HVAC
COURTESY OF LABS 21
Module 5 PG48 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Systems – HVAC
How Much Mechanical Space? • Between 8 and 20% of gross building square footage • 8% for simpler academic buildings • 20% for complex labs or buildings with animal areas • Vivariums or BSL containment labs may require 50% of the gross building area for mechanical space
Module 5 PG49 5 HVAC FUNDAMENTALS OF MODERN LAB DESIGN
Module 5 Systems – HVAC
Applicable Standards and Guidelines
Module 5 PG50