Test Report No. 70.405.19.4513.01R1 Dated 2019-03-19 ORIGINAL
Test Report No. 70.405.19.4513.01R1 Dated 2019-03-19 ORIGINAL Applicant : Taya Canvas (Shanghai) Company Limited Address : No 777, Fengguan Road Fengjing Industrial Park, Jinshan District Shanghai China Post Code: 201501
Sample description : Spiderweb 300 Color : White End Use : Curtain
Receipt date of sample : Received on 2019-02-25 Date of testing : From 2019-02-25 to 2019-03-18 Sample submitted : The sample(s) was (were) submitted by applicant and identified. Test result : Refer to next page.
Description of the test subject Sample Description Photo
001 Spiderweb 300
TÜV SÜD Certification and Testing (China) Co., Ltd. Shanghai Branch Testing Center Prepared by: Authorized by:
______Nick Shen Elyn Yao Softlines Department Softlines Department
Note: (1)The TÜV SÜD Certification and Testing (China) Co., Ltd.“General Terms & Conditions” applied. For full version, please visit: http://www.tuv-sud.cn/cn-scn/terms-and-conditions (2)The results relate only to the Items tested,(3)The test report shall not be reproduced except in full without the written approval of the laboratory
Laboratory: Phone: +86 21 6037 6300 Regd. Office: TÜV SÜD Certification and Testing (China) Co., Fax: +86 21 6037 6350 TÜV SÜD Certification and Testing (China) Co., Ltd. Shanghai Ltd. Shanghai Branch Testing Center E-mail: [email protected] Branch Testing Center Softlines Lab Softlines Lab www.tuv-sud.cn/softlines 2F Building B, No. 1999 Du Hui Rd, Minhang District, Shanghai 201108 P.R. China Page 1 of 3 Test Report No. 70.405.19.4513.01R1 Dated 2019-03-19 ORIGINAL
Conclusion Test Items 001 1. DIN 4102-1:1998 Fire behaviour of building materials and elements Part 1: Classification of building materials requirements and testing Pass -B1 Requirement
Remarks: Pass = Meet General Requirement Fail = Below General Requirement * = No Specified Requirement # = No Comments N/A = Not Applicable - = Not Conducted
Disclaimer Measurement Uncertainty: Unless otherwise agreed upon, Pass or Fail verdicts are given based on the measured values without any considerations of measurement uncertainties. Please note, every test method has a measurement uncertainty which has been evaluated by the laboratory according to ISO/IEC 17025 requirements. By taking measurement uncertainties into account it might happen that measured values can neither be assessed as Pass nor as Fail.
Test Results
1. DIN 4102-1:1998 Fire behaviour of building materials and elements Part 1: Classification of building materials requirements and testing Sample 001 All materials, except flooring, may be classed as B1 materials if they: ‘ ’ B1 requirement: - Withstand the test specified in DIN 4102-16 using the Brandschacht apparatus specified in DIN 4102-15, and - meet the requirements for class B2 materials. This test shall be deemed passed if, for any of the five specimens tested, flaming does B2 requirement: not reach the gauge mark within 20 seconds after flame application.
Test method: 1.DIN 4102-16 Fire behaviour of building materials and elements – ‘Brandschacht’ tests Sample size 190mm*1000mm Parameter Test result Requirement The minimum remaining 610 0 length of burning (mm) The average remaining 620 150 length of burning (mm) The maximum average flue 128 200 gas temperature peaks(ć)
According to the test results, the submitted sample meets the requirements of DIN 4102- Conclusion: 16 requirement.
Laboratory: Phone: +86 21 6037 6300 Regd. Office: TÜV SÜD Certification and Testing (China) Co., Fax: +86 21 6037 6350 TÜV SÜD Certification and Testing (China) Co., Ltd. Shanghai Ltd. Shanghai Branch Testing Center E-mail: [email protected] Branch Testing Center Softlines Lab Softlines Lab www.tuv-sud.cn/softlines 2F Building B, No. 1999 Du Hui Rd, Minhang District, Shanghai 201108 P.R. China Page 2 of 3 Test Report No. 70.405.19.4513.01R1 Dated 2019-03-19 ORIGINAL
2. DIN 53438: Response to ignition by a small flame Sample details Edge ignition: 5 pieces 90mm*190mm Sample size Surface ignition:5 pieces 90mm*230mm
Temperature Relative humidity Duration Conditioning 23±2°C 50±5%R.H. 24h
Test result Test item No. Whether flaming reach the gauge mark within 20 seconds after flame application(Yes/No) 1 No 2 No Edge ignition 3 No 4 No 5 No 1 No 2 No Surface ignition 3 No 4 No 5 No
Conclusion According to the test results, the submitted sample comply the requirements of DIN 4102-1 B2 requirement.
Overall Conclusion According to the test results, the submitted sample comply the requirements of DIN 4102-1 B1 requirement.
Remark: This Report is to Supersede Test Report No.70.405.19.4513.01 Issued on 2019-03-18.
-End of Test Report-
Laboratory: Phone: +86 21 6037 6300 Regd. Office: TÜV SÜD Certification and Testing (China) Co., Fax: +86 21 6037 6350 TÜV SÜD Certification and Testing (China) Co., Ltd. Shanghai Ltd. Shanghai Branch Testing Center E-mail: [email protected] Branch Testing Center Softlines Lab Softlines Lab www.tuv-sud.cn/softlines 2F Building B, No. 1999 Du Hui Rd, Minhang District, Shanghai 201108 P.R. China Page 3 of 3