Technical Specification for 5 Mva and 10 Mva Power Transformer

Total Page:16

File Type:pdf, Size:1020Kb

Technical Specification for 5 Mva and 10 Mva Power Transformer TECHNICAL SPECIFICATION FOR 5 MVA AND 10 MVA POWER TRANSFORMER SPECIFICATION NO. APDCL/PP&D/T&C/STS/PTR/2020/1 1. SCOPE 1.1. ThisSpecificationprovidesfordesign,engineering,manufacture,assembly,stageinspection, finalinspectionandtestingbeforedispatch,packinganddeliveryatdestinationSub-stationby road transport, transit insurance, unloading at site/stores of 5 MVA and 10MVA,33/11 KV Power Transformer(s) with on load tap changer, complete with all fittings, accessories, associated equipment‘s, spares, 10% extra Transformer Oil, required for its satisfactory operation in any of the sub-stations of the purchaser 1.2. The core shall be constructed either from high grade, non-aging Cold Rolled Grain Oriented (CRGO) siliconsteellaminationsconformingtoM-4grade of BIS certified with lamination thickness not more than 0.23mm to 0.27mm or better (Quoted grade and type shall be used). The maximum flux density in any part of the cores and yoke at normal voltage and frequency shall be such that, at 12.5% overvoltage conditions it should not be more than 1.9Tesla. The supplier shall provide saturation curve of the core material, proposed to be used. Prior to inspection and testing of the transformer the supplier shall submit on request following curves of the core manufacturer: 1.2.1. i. Flux Density vs Core Loss 1.2.2. Flux Density vs Excitation. 1.3. Laminations of different grade(s) and different thickness(s) are not allowed to be used in any manner or under any circumstances. The core shall have magnate coating as insulation. The assembled core shall be securely clamped on the limbs and yoke with uniform pressure so as to minimize noise emission from it. The insulation structure for the core to bolts and core to clamp plates shall be such as to withstand a voltage of 200V at 50Hz for 1min. 1.4. The scope of supply includes the provision of type test. The equipment offered should have been successfully type tested within five years from date of tender and the designs should have been in satisfactory operation for a period not less than three years as on the date of order. Compliance shall be demonstrated by submitting, (i) authenticated copies of the type test reports and (ii) performance certificates from the users, specifically from Central Govt. /State Govt. or their undertakings. However, if it is found that the bidder has submitted type test reports but those have not been conducted on identical design of equipment/material as per APDCL specification, the same may be accepted subjected to the following condition: 1.4.1. APDCL at its discretion may request the successful bidder to conduct type test on the identical design as per APDCL specification. 1.4.2. Such type tests, if required to be carried out at CPRI/ERDA in presence of APDCL Engineer for which no extra cost shall be charged to APDCL. 2. SYSTEM CONDITIONS The equipment shall be suitable for installation in supply systems of the following characteristics. 50 Hz± 5% Frequency 33 KV Nominal system voltages 11 KV 33KV System 36.3KV Maximum system voltages 11 KV System 12 KV 33KV System 31.5KA Nominal short circuit level (Based on apparent 11 KV System 25KA power) Insulation levels : 33KV System 170KV (peak) 11 KV System 75 KV (peak) 1.2/50 μ sec impulse withstand voltage 33KV System 70KV (rms) Power frequency 1 minute withstand (wet and 11 KV System 28KV (rms) dry) voltage 11 KV System Solidly earthed Neutral earthing arrangements 3. SERVICE CONDITIONS: maximum altitude above sea level 1000m minimum ambient air temperature 45° C maximum daily average ambient air 40° C temperature minimum ambient air temperature 2° C maximum temperature attainable by an 60 ° C object exposed to the sun maximum yearly weighted average 32° C ambient temperature 2 APDCL/ BIDDING DOCUMENT / TS maximum relative humidity 100% average number of thunderstorm days 4550(MV) per annum (isokeraunic level) average number of rainy days per annum 120 average annual rainfall 2200 mm maximum annual rainfall 3500 mm maximum wind pressure 260Kg/m² Seismic Level 0.24g to 0.48g Environmentally, the region where the equipment will be installed is subject to high relative humidity, which can give rise to condensation. Outdoor material and equipment shall be designed and protected for use in exposed, heavily polluted, corrosive, tropical and humid atmosphere. ALTITUDE FACTOR If the equipment is to be installed in the hilly area, necessary correction factors as given in the Indian Standard for oil temperature rise, insulation level etc. shall be applied to the Standard Technical Parameters given above. 4. CODES & STANDARDS 4.1 The design, material, fabrication, manufacture, inspection, testing before dispatch and performance of power transformers at site shall comply with all currently applicable statutory regulations and safety codes in the locality where the equipment will be installed. The equipment shall also conform to the latest applicable standards and codes of practice. Nothing in this specification shall be construed to relieve the contractor of this responsibility. 4.2 The equipment and materials covered by this specification shall conform to the latest applicable provision of the following standards. IS:5 Colour for ready mixed paints IS:325 Three Phase Induction Motors IS:335 New insulating oil for transformers, switch gears IS:1271 Classification of insulating materials for electrical machinery and apparatus in relation to their stability in services 3 APDCL/ BIDDING DOCUMENT / TS IS:2026(Part I to IV) Power Transformer IS:2071 Method of high voltage testing IS:2099 High voltage porcelain bushings IS:2147 Degree of protection IS:2705 Current Transformers IS:3202 Code of practice for climate proofing of electrical equipment IS:3347 Dimensions for porcelain Transformer Bushings IS:3637 Gas operated relays IS:3639 Fittings and accessories for power Transformers IS:5561 Electric Power Connectors IS:6600/BS:CP‟10:0 Guide for loading of oil immersed Transformers IS:10028 Code of practice for selection, installation and maintenance of transformers, Part I. II and III C.B.I.P. Publication Manual on Transformers If the standard is not quoted for any item, it shall be presumed that the latest version of Indian Standard shall be applicable to that item. The equipment complying other internationally accepted standards, may also be considered if they ensure performance superior to the Indian Standards. 5. SPECIFIC TECHNICAL REQUIREMENTS Sl Particulars 33/11 KV Power Transformer 1 Rated MVA 5MVA & 10 MVA (ONAN rating) 2 Number of Phases Three 3 Vector group Dyn-11 4 Type of installation Outdoor 5 Frequency 50HZ ( +/- )5% 6 Cooling Medium Insulating Oil (ONAN) 7 Type of Cooling ONAN (Oil natural / Air natural) 8 MVA Rating 100% corresponding to ONAN 4 APDCL/ BIDDING DOCUMENT / TS 9 Rated Voltage :- High Voltage winding 33kV Low Voltage winding 11kV 10 Highest continuous system voltage a) Maximum system 36.3KV / 12 KV voltage ratio (HV / LV ) b) Rated voltage ratio 33KV /11 KV (HV / LV ) 11 Winding Material Electrolytic Copper 12 Winding Connection :- High Voltage Winding DELTA Low Voltage Winding STAR 13 Vector group reference Dyn11 14 No. of windings Two winding Transformers 15 Method of System Solidly grounded on LV side Earthing 16 Neutral terminal to be On LV side only brought out 17 Core Material CRGO ( M-4 / higher grade) 18 Core Assembly Boltless type 19 Type of Tap Changer On-load tap changer (OLTC) 20 Range of Tapping + 5% to – 15% in 17 equal steps of 1.25% each on HV winding 21 Intended regular cyclic As per IEC –76-1, Clause 4.2 overloading of windings The Power transformer shall be suitable for operating under overload condition as specified in IS 6600 and a separate Over Loading chart should be submitted along with offer. 22 a) Anticipated Around 10% unbalanced loading 5 APDCL/ BIDDING DOCUMENT / TS b) Anticipated continuous 110 % of rated current loading of windings (HV / LV) 23 Over Voltage operating 112.5 % of rated voltage (continuous) capability and duration 24 Withstand time for three 2 Seconds phase short circuit 25 Maximum current density 2.4Amp/ Sqmmfor copper conductor at any working for HV and LV winding tap including extreme tap 17 (-15% voltage). for rated current 26 Magnetizing Current 1% of full load current. 26 Maximum flux densityin 1.55 Tesla any part of the core and yoke at rated MVA, rated voltage i.e 33kV / 11kV and system frequency of 50 Hz 27 Maximum Flux Density in 1.9 Tesla any part of the core and yoke at 112.5 % of rated voltage i.e 33 KV /11 KV and system frequency of 50 HZ 28 Insulation 33kV 11kV a) Type of insulation Uniform Uniform b) One minute power 70kV 28kV frequency withstand Voltage(kV rms) c)1.2 / 50 microsecond 170 75 wave shape Lighting Impulse withstand voltage (KVP) 29 Nominal short circuit 31.5KA 25KA level (Basing on apparent power) 30 Insulation level of bushing a) Lightning Impulse 170 75 withstand (KVP) 6 APDCL/ BIDDING DOCUMENT / TS b) 1 Minute Power 70 28 Frequency withstand voltage (KV –rms ) 31 Minimum clearances in Phase to Phase to ground Phase to ground air (mm) Phase in Oil a) HV 400 320 40 b) LV 280 140 25 32 c) Creepage distance 972 324 (mm) (minimum) 33 Percentage impedance MVA Rating %Impedance Tolerance % voltage on normal tap and MVA base at 75o C 5 7.15 10 corresponding to HV/ LV rating and applicable 10 8.35 10 tolerances: (No negative tolerance shall be allowed) 34 Permissible Temperature Rise over ambient temperature of 40 / 45˚C a) Of top oil measured by 40˚C thermometer b) Of winding measured 45˚ C by resistance 35 Noise level at rated Transformers shall be designed with particular care voltage and frequency to suppress at least the third and fifth harmonic voltages so as to minimize interference with communication circuits.
Recommended publications
  • Electricity Today Issue 4 Volume 17, 2005
    ET_4_2005 6/3/05 10:41 AM Page 1 A look at the upcoming PES IEEE General Meeting see page 5 ISSUE 4 Volume 17, 2005 INFORMATION TECHNOLOGIES: Protection & Performance and Transformer Maintenance PUBLICATION MAIL AGREEMENT # 40051146 Electrical Buyer’s Guides, Forums, On-Line Magazines, Industry News, Job Postings, www.electricityforum.com Electrical Store, Industry Links ET_4_2005 6/3/05 10:41 AM Page 2 CONNECTINGCONNECTING ...PROTECTING...PROTECTING ® ® ® HTJC, Hi-Temperature Joint Compound With a unique synthetic compound for "gritted" and "non-gritted" specifications, the HTJC high temperature "AA" Oxidation Inhibitor improves thermal and electrical junction performance for all connections: • Compression Lugs and Splices for Distribution and Transmission • Tees, Taps and Stirrups on any conductor • Pad to Pad Underground, Substation and Overhead connections For oxidation protection of ACSS class and other connector surfaces in any environment (-40 oC to +250 oC), visit the Anderson ® / Fargo ® connectors catalogue section of our website www.HubbellPowerSystems.ca Anderson® and Fargo® offer the widest selection of high performance inhibitor compounds: Hubbell Canada LP, Power Systems TM ® ® 870 Brock Road South Inhibox , Fargolene , Versa-Seal Pickering, ON L1W 1Z8 Phone (905) 839-1138 • Fax: (905) 831-6353 www.HubbellPowerSystems.ca POWER SYSTEMS ET_4_2005 6/3/05 10:41 AM Page 3 in this issue Publisher/Executive Editor Randolph W. Hurst [email protected] SPECIAL PREVIEW Associate Publisher/Advertising Sales 5 IEEE PES General Meeting has
    [Show full text]
  • Maintenance Manuals
    1ZVN460100 – D Maintenance Manuals 1ZVN460100 – D 2 / 3 Table of contents 1 Maintenance............................................................................................................... 3 2 Trouble Shooting ....................................................................................................... 5 1ZVN460100-D 1. Maintenance: Subject Check Time period Remarks Year Month Insulating oil Dielectric strength 3 Moisture content 1 Neutralisation value 1 Interfacial surface tension 1 Water content 1 Sludge content 1 Gas analysis 1 Oil tightness Tank 3 Conservator 3 Cooling equipment 3 Piping 3 Bushings 3 Cable sealing ends 3 If applicable Cable boxes 3 If applicable Buchholz relay 3 Gate valves 3 Valves 3 Oil level Tank 1 Conservator 1 Bushings 1 Cable sealing ends 1 If applicable Cable boxes 1 If applicable Thermometer pockets 1 Venting devices Tank 1 Release vent screws until Cooling equipment 1 Oil emerges. Afterwards Intermediate piping 1 screw plugs tight Bushings 1 Piping 1 Buchholz relay 1 Cable sealing ends 1 If applicable Earthing devices All metal parts 1 Tank 1 Motors 1 Star points 1 If applicable Surge arresters 1 If applicable Control cabinet 1 Steal armoured cabling 1 Shut-off devices In position “service” As required See plan “Position of shut off devices” (if provided) Buchholz relay Direction of oil flow At erection Float 1 Contacts 1 Gas sampling device 1 If applicable Functional test 1 Dial-type thermometers Contact setting 1 See the Technical data Position of maximum pointer 1 Functional test 1 Current
    [Show full text]
  • Type VRLTC™ Load Tap Changer
    Technical guide Type VRLTC™ load tap changer Table of contents 2 General information 4 Switching sequences 6 Tank characteristics 6 Terminal board 7 Tap selector 7 Stationary contacts 7 Reversing switch or change over selector 8 Drive shaft 8 By-pass switch and vacuum interrupter mechanism 10 Current detector module 11 Motor drive enclosure 12 Digital servo motor system 13 Decision making and monitoring 14 Maintenance and inspection features 14 Service recommendations 15 Mechanical components 15 Electrical engineering information 16 Type tests 17 Notes Technical guide | VRLTC load tap changer 01 General information ABB designed, developed and will manufacture the type VRLTC The drive motor is a digitally controlled servo motor which load tap changer (LTC) at its facility in Alamo, Tennessee. The precisely responds to the commands from the digital drive. LTC meets all of the required specifications according to IEEE Cam switches and electromechanical relays are not used in this C57.131 and IEC 60214. The LTC is an on-tank, vacuum tap changer. The entire system is monitored and controlled reactance type suitable for either automatic or manual control. by the Tap Logic Monitoring System (TLMS™) mounted in the motor compartment. Three major components make up the LTC: the tap changing components, the driving components, and the decision making/ The components of the tap changing circuit are: monitoring components. The tap changing components are — The preventive autotransformer - a separate device mounted contained in an oil-filled steel tank. The transformer’s tap leads inside the transformer which provides the switching impedance and preventive autotransformer (PA or switching reactor) leads — The tap changing module - consists of the tap selector and are connected to the back of the LTC terminal board.
    [Show full text]
  • Power Transformer Protection
    Power Transformer Protection Course No: E06-003 Credit: 6 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 22 Stonewall Court Woodcliff Lake, NJ 07677 P: (877) 322-5800 [email protected] POWER TRANSFORMER PROTECTION The advancement of electrical power systems has been reflected in the developments in power transformer manufacturing. This has led to a wide range of power transformers. Their ratings range from a few kVA to several hundred MVA and are used for a wide variety of applications. Power transformer protection varies with the application and transformer importance. In the case of a fault within the power transformer it is important to minimize tripping time in order to decrease the impact of thermal stress and electrodynamic forces. Distribution power transformers can be protected by using fuses or overcurrent protection relays. This leads to time-delayed protection due to downstream co-ordination requirements. Nevertheless, time delayed short circuit clearance is unacceptable on larger power transformers due to system operation/stability and cost of repair. Power transformer short circuits are typically grouped into five categories: - Winding and terminal short circuits - Core short circuits - Tank and transformer accessory short circuits - On–load tap changer short circuits - Prolonged or uncleared external short circuits Summary of short circuit causes initiated in the power transformer itself, is shown in Figure 1. Winding and Terminal Core Tank and Accessories OLTC Figure 1. Power transformer short circuit statistics TRANSFORMER WINDING FAULTS A transformer winding fault is limited in magnitude by the following factors: - source impedance - neutral grounding impedance - winding connection arrangement - fault voltage - power transformer leakage reactance Few distinct cases come up and are described below.
    [Show full text]
  • B. Tech Electrical.Pdf
    JECRC University Course Structure for Electrical Engineering (B.Tech.) JECRC UNIVERSITY Faculty of Engineering & Technology B.Tech in Electrical Engineering Teaching Scheme Semester III Subject Code Subject Contact Hrs Credits L-T-P Electronics Devices & Circuits 3-1-2 5 Circuit Analysis – I 3-1-0 4 Electrical Machines – I 3-1-2 5 Electrical Measurements 3-1-2 5 Mathematics – III 3-1-0 4 Computer Programming – I 3-0-2 4 Total 18-5-8 27 JECRC UNIVERSITY Faculty of Engineering & Technology B.Tech in Electrical Engineering Teaching Scheme Semester IV Subject Code Subject Contact Hrs Credits L-T-P Analogue Electronics 3-1-2 5 Digital Electronics 3-0-2 4 Circuit Analysis – II 3-1-0 4 Electrical Machines – II 3-1-2 5 Advanced Mathematics 3-1-0 4 Generation of Electric Power 3-0-0 3 Total 18-4-6 25 JECRC UNIVERSITY Faculty of Engineering & Technology B.Tech in Electrical Engineering Teaching Scheme Semester V Subject Code Subject Contact Hrs Credits L-T-P Power Electronics-I 3-1-2 5 Microprocessor & Computer 3-0-2 4 Architecture Transmission & Distribution – I 3-1-0 4 Control Systems 3-1-2 5 Utilization of Electrical Power 3-0-0 3 Digital Signal Processing 3-0-0 3 Total 18-3-6 24 JECRC UNIVERSITY Faculty of Engineering & Technology B.Tech in Electrical Engineering Teaching Scheme Semester VI Subject Code Subject Contact Hrs Credits L-T-P Power Electronics –II 3-1-2 5 Power System Analysis 3-1-2 5 EHV AC/DC Transmission 3-0-0 3 Switch Gear & protection 3-0-0 3 Instrumentation 3-0-0 3 Transmission & Distribution – II 3-1-0 4 Economics 0-0-2 1
    [Show full text]
  • Section 5 Protection Related Functions
    1MAC050144-MB C Section 5 Protection related functions Section 5 Protection related functions 5.1 Three-phase transformer inrush detector INR 5.1.1 Identification IEC 61850 IEC 60617 ANSI/IEEE C37.2 Function description identification identification device number Three-phase inrush detector INRPHAR 3I2f> INR 5.1.2 Function block Figure 184: Function block 5.1.3 Functionality The transformer inrush detection INR is used to coordinate transformer inrush situations in distribution networks. Transformer inrush detection is based on the following principle: the output signal BLK2H is activated once the numerically derived ratio of second harmonic current I_2H and the fundamental frequency current I_1H exceeds the set value. The trip time characteristic for the function is of definite time (DT) type. The function contains a blocking functionality. Blocking deactivates all outputs and resets timers. 5.1.4 Operation principle The function can be enabled and disabled with the Operation setting. The corresponding parameter values are Enable and Disable. The operation of an inrush current detection function can be described by using a module diagram. All the blocks in the diagram are explained in the next sections. 615 series ANSI 383 Technical Manual Section 5 1MAC050144-MB C Protection related functions Figure 185: Functional module diagram. I_1H and I_2H represent fundamental and second harmonic values of phase currents. I_2H/I_1H This module calculates the ratio of the second harmonic (I_2H) and fundamental frequency (I_1H) phase currents. The calculated value is compared with the set Pickup value. If the calculated value exceeds the set Pickup value, the module output is activated.
    [Show full text]
  • Fist 3-30 Transformer Maintenance
    FIST 3-30 TRANSFORMER MAINTENANCE FACILITIES INSTRUCTIONS, STANDARDS, AND TECHNIQUES U0+,'&*5,7,'5*&'<7R,9'0,*1F*,'*+0,'R+1R �UR'7U*1F*R'/�797,+10 &'0'R*/1�1R7&1 F+5,*W F7/+�+,+'5*+05,RU/,+105 5,70&7R&5*70&*,'/0+3U'5 TRANSFORMER MAINTENANCE 1E%46*2WWW (&R1'�'/,R+/*R'5'7R/*70&* ,'/0+/7�*5'R+/'5*)R1U< &�HW U0+,'&*5,7,'5*&'<7R,9'0,*1F*,'*+0,'R+1R �UR'7U*1F*R'/�797,+10 &'0'R*/1�1R7&1 Acronyms and Abbreviations A air ANA self-cooled, nonventilated kW kilowatt ANSI American National Standards IEEE Institute of Electrical and Institute Electronic Engineers CEGB Central Electric Generating M/DW moisture by dry weight Board mg milligram cfm cubic feet per minute mva mega-volt-amps CH4 methane ND not detected C2 H2 acetylene N2 nitrogen C2 H4 ethylene O oil C2 H6 ethane O2 oxygen CO carbon monoxide OD outer diameter CO2 carbon dioxide ppb parts per billion CT current transformer ppm parts per million DBPC Ditertiary Butyl Paracresol psi pounds per square inch DGA dissolved gas analysis Reclamation Bureau of Reclamation EHV extra high voltage SCADA Supervisory Control and Data FA forced air (fans) Acquisition FO forced oil (pumps) STP standard temperature and G some type of gas pressure GA gas, self-cooled TDCG total dissolved combustible gas gm grams TOA Transformer Oil Analyst GSU generator step up TTR transformer turns ratio test H2 hydrogen TSC Technical Service Center ID inner diameter UV ultraviolet IFT interfacial tension V volts IEC International Electrotechnical W water/oil heat exchanger Commission IR infrared JHA job hazard analysis KOH potassium hydroxide kV kilovolt kVA kilovoltampere Contents Page 1.
    [Show full text]
  • Power Transformer Protection Author Application Guide R Nylen Senior Application Engineer
    A GO3-5005 E March 1988 Power Transformer Protection Author Application Guide R Nylen Senior application engineer ) ABB Relays Power transformer protection AGO3-5005 E Page 2 List of contents 1. INTRODUCTION 2. CONDITlONS LEADING TO FAULTS 4.4 Grou~d fault protection 2.1 Insulation breakdown 4.4.1 General 2.2 Aging of insulation 4.4.2 Low irrnpedance residual overcurrent relay 2.3 Overheating due to overexcitation 4.4.3 Harmonic restraint relay 2.4 Oil contamination and leakage 4.4.4 High impedance restricted relay 2.5 Reduced cooling 4.4.5 Low impedance restricted relay 3. FAULT CURRENT 4.4.6 Tank protection 3.1 Ground faults in a solidly grounded 4.4.7 Residual voltage relay star-connected secondary winding 4.5 Overexcitation protection 3.2 Ground faults in a high impedance grounded star-connected 4.6 Flashover and ground fault protections for low voltage systems secondary winding 3.3 Ground faults in a delta-connected 4.6.1 Systems without rectifiers or frequency converters winding 3.4 Turn-to-turn faults 4.6.2 Systems with rectifiers and frequency converters without 3.5 Phase-to-phase faults pulse'width-modulation 4. PROTECTIVE RELAVS 4.6.3 Systems with rectifiers and pulse- 4.1 General width-modulated frequency converters 4.2 Differential relays 4.2.1 General 5. MONITORS ) 4.2.2 Differential relays for fully insulated 5.1 Gener,al transformers 5.2 Gas d~tector relay 4.2.3 Differential relays for auto- 5.3 Temperature monitoring transformers 5.4 PresslUre relay for on-load tap- 4.3 Overcurrent protection and changsrs impedance relays 5.5 PresslUre relief valve 4.3.1 Time-overcurrent relays 5.6 Oil level monitor 4.3.2 Under-impedance relays 5.7 Silica gel dehydrating breather 4.3.3 Distance relays 6.
    [Show full text]
  • Chromatographic Analysis of Gases from the Transformer the Process of Creating and Detecting Gases in the Transformers
    EVENTSDIAGNOSTICS Photo courtesy of Končar D&ST, Zagreb, Croatia Zagreb, D&ST, Končar of courtesy Photo Chromatographic analysis of gases from the transformer The process of creating and detecting gases in the transformers 1. Introduction ABSTRACT Given the demands of today’s power systems, the question ince the beginning of production of oil for transformers of the transformer reliability is one of the top priorities. it has been shown that during their work, due to various The need for monitoring the performance of transformers Sphenomena, certain gases may appear [1]. In 1928, Buch- is imposed since the beginning of their use. This article holz relay was first used to collect gas bubbles passing through aims to analyse the impact of the gases released during the oil to the conservator. Due to the occurrence of gas in the breakdowns and energy discharge within the transformer transformer, the oil is gradually being displaced, which in a cer- that could accelerate the degradation of the insulation sys- tain amount pulls down the float and turns on a warning signal. tem and gradually lead to major faults and incidents. In larger amounts of gas, Buchholz relay trips the transformer. Consequently, there was a need for a quality analysis of the situ- ation inside the transformer in order to detect and eliminate po- KEYWORDS tential failures. In the early sixties gas chromatograph appeared, transformer, analysis, oil, gas, insulation a device used to identify gases dissolved in transformer oil. Since the seventies, this analysis is used to detect a number of different 36 TRANSFORMERS MAGAZINE | Volume 2, Issue 1 Emir ŠIŠIC Chromatography is a separation me- thod in which components are sepa- rated and isolated in stationary and mobile phases of materials (out of which many are forming gases in the oil and above), damage to the insulation, reduction of operational safety, and ultimately failure or breakdown.
    [Show full text]
  • Failure Analysis of a Power Transformer Using Dissolved Gas Analysis – a Case Study
    IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 FAILURE ANALYSIS OF A POWER TRANSFORMER USING DISSOLVED GAS ANALYSIS – A CASE STUDY Ankush Chander1 Nishant2 1M. Tech Scholar, EEE Department Arni University Indora Himachal Pradesh, India 2Assistant Professor, EEE Department, Arni University Indora Himachal Pradesh, India Abstract Reliable and continued performance of power Transformer is the key to profitable generation and transmission of electric power. Failure of a large power transformer not only results in the loss of very expensive equipment, but it can cause significant guarantied damage as well. Replacement of that transformer can take up to a year if the failure is not disastrous and can result in tremendous revenue losses and fines. A Power Transformer in operation is subjected to various stresses like thermal stress and electrical stress, resulting in liberation of gases from the hydrocarbon mineral oil which is used as insulant and coolant. Dissolved Gas Analysis is a technique used to assess incipient faults of the transformer by analyzing specific dissolved gas concentrations arising from the deterioration of the transformer. DGA is used not only as a diagnostic tool but also to track apparatus failure. In this case study the fault and defects that occurred in 400kV/220kV/132kV/66kV Sub Station can be found by DGA. Keywords: Power Transformer, Dissolved Gas Analysis, ----------------------------------------------------------------------***---------------------------------------------------------------------- 1. INTRODUCTION Table 2.1 Failure Mode of Transformer A power transformer is one of the most important and costly Description Failures Duration devices in electrical systems. Its importance is attributed No % TTF ATF directly to the continuity of power supply, since its loss through failure or defect means a supply stoppage.
    [Show full text]
  • Numerical Differential Protection of 220/132KV, 250 MVA Auto Transformer Using Siemens Make Differential Relay 7UT612
    International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 07 | July 2019 www.irjet.net p-ISSN: 2395-0072 Numerical Differential Protection of 220/132KV, 250 MVA Auto Transformer using Siemens make differential relay 7UT612 Hashmat Hussain1, Dr. Muhammad Naeem Arbab2, Junaid Khalil3 1Senior Engineer NPCC NTDC Islamabad, Pakistan 2Professor, Deptt of Electrical Engg, UET Peshawar, Pakistan 3Senior Engineer Protection GSO Training Centre NTDC Tarbela, Pakistan ---------------------------------------------------------------------***---------------------------------------------------------------------- Abstract – Differential protection of power transformer is 1. Power T/F phase shift between HV & LV Currents as the main protection of power transformer. First generation of per Vector group of Power T/F. Electromechanical differential relays were difficult to balance 2. Different CT Ratios on HV & LV side of T/F. and had limited setting ranges while 3rd Generation 3. Power T/F Magnetization Inrush current [2] microprocessor based Numerical Differential relays are multi 4. Zero sequence current elimination [3] functional, has user friendly HMI, more sensitive, reliable and 5. CT saturation on external faults [4]. have vast setting ranges & options. Setting calculation and 6. Tap change operation. balancing of differential relay for a power transformer is a 7. CT Errors. difficult job for protection engineers. Methods used in field for 8. Through fault stability of differential relay. elimination
    [Show full text]
  • W.E.F. : 2016-2017
    R.V.R. & J.C. College of Engineering (Autonomous) R-16 R V R & J C COLLEGE OF ENGINEERING, CHOWDAVARAM, GUNTUR-19 (Autonomous) R-16 REGULATIONS & SCHEME CHOICE BASED CREDIT SYSTEM Regulations, Scheme of Instruction, Examination and Detailed Syllabi for 4-Year B.Tech Degree Course in Electrical & Electronics Engineering (Semester System) w.e.f. : 2016-2017 B.Tech.(EEE)/R-16/2016-2017 Page 1 of 187 R.V.R. & J.C. College of Engineering (Autonomous) R-16 EEE Department Vision: “To impart education leading to highly competent professionals in the field of Electrical & Electronics Engineering who are globally competent and to make the Department a Centre for Excellence”. EEE Department Mission: “Integrated development of professionals with knowledge and skills in the field of specialization, ethics and values needed to be employable in the field of Electrical Engineering and contribute to the economic growth of the employing organization and pursue lifelong learning” Program Educational Objectives of B. Tech Program in Electrical & Electronics Engineering: PEO I. To facilitate the students to become Electrical & Electronics Engineers who are competent, innovative and productive in addressing the broader interests of the organizations & society. PEO II. To prepare the students to grow professionally with necessary soft skills. PEO III. To make our graduates to engage and excel in activities to enhance knowledge in their professional works with ethical codes of life & profession. Program Specific Outcomes of B. Tech Program in Electrical & Electronics Engineering: PSO1 Graduates of the program will be able to demonstrate knowledge and hands on competence in developing, Testing, Operation and Maintenance of Electrical & Electronics systems.
    [Show full text]