Cedral Lap Vertical
Construction Details
New Zealand Table of contents
General information 3
Ventilation 4
General components 5
Cedral Lap Vertical with timber batten construction 8
Cedral Lap Vertical with metal top hat construction 24
2 General information
This document provides generic construction details for Cedral Lap façade systems to assist with the design of Cedral Lap façade.
Construction details in this document have been independently certified for the purpose of compliance with Clause E2, External moisture, of the New Zealand Building Code within the scope of E2/VM1.
The weatherproofing performance of any project specific detail or application that is different from or not included in the construction details of this document shall be evaluated by the project engineer or consultant.
It is the responsibility of the project designer, architect and engineer to ensure that the information and construction details provided in this document are appropriate for the intended application.
Cladding support frame and its connection to substructure shall be designed by the project engineer in accordance with the relevant standards. The support frame maximum deflection under the influence of load shall be limited to Span/250.
The support frame, fixings, flashings and the like shall be of adequate corrosion resistance appropriate to the corrosivity category of the project location.
Non-proprietary flashings and capping shall be designed with respect to project wind loading, relevant standards and regulations.
This document is not designed to serve as an installation guide, and is intended to be used in conjunction with other relevant technical and installation documents.
Construction details contained in this document are not to a specific scale, and are for illustration purposes only.
The information in this document is correct at the time of issuing. However, due to our committed program of continuous material and system development we reserve the right to amend or alter the information contained therein without prior notice. Please contact your local Cedral sales organisation to ensure you have the most current version.
This document is supplied in good faith and no liability can be accepted for any loss or damage resulting from its use. All the content of this document is © Copyright of Etex Group. All rights reserved.
This document is protected by International copyright laws. Reproduction and distribution in whole or in part without prior written permission is strictly prohibited. Cedral and logos are trademarks of Etex NV or an affiliate thereof. Any use without authorisation is strictly prohibited and may violate trademark laws.
3 Ventilated facade
Cedral Lap and Click are designed for a ventilated façade system.
A ventilated façade is a kind of two stage construction, an inner structure with a protective outer skin, and the cladding panel or rainscreen. A ventilated façade consists of an insulated and weathertight structure, a ventilated cavity formed with a cladding support frame, and the cladding panel.
Allowance for adequate ventilation is paramount in ensuring a successful Cedral façade. Ventilated façades provide a number of added benefits to the building and its occupants. These may include but are not limited to the following:
· Positive contribution to energy savings · Minimises thermal bridges · Assists with condensation management · Reduces thermal movement of the structure and cladding support frame · Dissipates radiant heat · Increases acoustic performance of the external wall · Provides an effective drainage path for any moisture passing the cladding skin · Eliminates the need for exposed caulking and sealant, therefore reducing maintenance requirements · Assists with keeping the weather barrier dry and healthy · Provides opportunities for concealing external services such as downpipes within the cavity · Proven to be a more sustainable and healthier façade construction · Architectural design freedom
Air must be allowed to enter the cavity from bottom of the façade, window head, soffit, slab junctions, and the like, and exit from top of the façade, capping, window sill, slab and soffit interfaces, and the like.
All air inlets and outlets shall be protected against entry of birds and vermin into the cavity with a corrosion resistant perforated profile (angle).
The perforated angle should be of maximum 0.9mm in thickness, where placed between the cladding panel and support frame, and be of a minimum 50% open area with aperture size of maximum 3mm to 5mm. The perforations must be kept open and unobstructed to maintain drainage and ventilation of the cavity. The perforated angle shall be positioned to allow an adequate drip edge to the cladding panel.
4 General components
CEDRAL LAP WOOD CEDRAL LAP SMOOTH
Cedral Lap is supplied in a range of 22 factory applied colours and two wood stain finishes, providing an aesthetic option to suit most project requirements. Refer to https://www.cedral.world/en-nz/cladding/ for all available colours and finishes. Bespoke colours are subject to minimum order quantities and extended lead times.
CEDRAL LAP profiles
Starter profile
Symmetrical external corner profile
Asymmetrical external corner profile
External corner junction (connector) profile
5 General components
Internal corner profile
End profile
EPDM strip 0,75mm flat EPDM strip 100mm wide.
Applied on timber cavity battens for moisture protection as specified on the construction details
EPDM compressible gasket Tesa® 61102
A compressible closed-cell EPDM gasket used for sealing interfaces with flashings and the like Minimum width: 9mm.
Expanding foam gasket pro clima CONTEGA® FIDEN EXO
A pre-compressed sealing tape used to seal interfaces with window joineries and the like as specified on the construction details.
The required tape size depends on the gap which needs to be sealed. Refer to pro clima CONTEGA® FIDEN EXO datasheet to determine the required tape size.
Weather resistive barrier option 1 pro clima SOLITEX EXTASANA®
Cedral façade systems have been certified with pro clima SOLITEX EXTASANA® to E2/VM1 for the purpose of compliance with Clause E2 of the NZBC for the following scope: · Serviceability wind pressure: Up to ±1515Pa · Ultimate wind pressure: Up to ±2500Pa · Building height: Up to 10m pro clima SOLITEX EXTASANA® shall be applied in accordance with pro clima SOLITEX EXTASANA® installation guidelines and relevant standards.
6 General components
Weather resistive barrier option 2 pro clima SOLITEX EXTASANA® AHERO
Where a rigid air barrier is required the ADHERO version of pro clima SOLITEX EXTASANA® may be used with 6mm Kalsi (RigidBacker) fibre cement sheeting. pro clima SOLITEX EXTASANA® AHERO and Kalsi shall be applied in accordance with their respective installation guidelines and recommendations. Same wind pressure and building height limits as those of Option 1 apply unless otherwise specified by project engineer.
Flashing tape pro clima TESCON EXTORA®
A pressure sensitive adhesive tape for overlaps and end laps used with both weather resistive barrier options.
Sill tape pro clima TESCON EXTOSEAL®
A flexible tape for use around window and door openings, used with both weather resistive barrier options.
Sealing tape pro clima TESCON® NAIDECK mono patch
A single-sided adhesive nail or screw sealing adhesive used with both weather resistive barrier options.
Foil tape pro clima TESCON® ADHISO WS
A pure aluminium tape for wet seal connections to TESCON EXTOSEAL® and EXTORA® and SOLITEX EXTASANA®.
Grommet pro clima ROFLEX and KALFEX pro clima ROFLEX is used to seal pipe and pro clima KAFLEX for cable penetrations. pro clima ROFLEX and KALFEX are used with both weather resistive barrier options.
7 Cedral Lap Vertical With Timber Batten Construction Fixings and support frame
CEDRAL LAP Vertical with timber batten construction
Cedral Lap may be fixed vertically in traditional lapped style to horizontal timber battens.
Fixings
Cedral dome head colour matched screw for screw fixing Cedral Lap to timber batten as specified on the construction details (4,2 x 52 mm, head diameter ~ 8,5 mm, drill point, Torx T20, stainless steel 304)
Cedral Lap countersunk timber screw for screw fixing Cedral Lap to timber batten as specified on the construction details (4.0 x 45 mm, head diameter ~ 7,7 mm, drill point, countersunk head with milling ribs, TORX T20, stainless steel 304)
Support frame
Cedral Lap may be fixed vertically to horizontal timber battens with minimum depth of 35mm and width of 70mm (35 x 70 mm) chamfered at the top with 15-degree slope. Suitable vertical 45x20mm cavity battens are used behind the horizontal chamfered battens to form a 20mm gap between weather barrier and the horizontal battens for ventilation and drainage purposes.
Timber battens shall be of minimum preservative treatment of H3.1, and of minimum structural grade of SG6 as per the relevant standards.
Maximum deflection of support framing must be limited to Span/250. Structure and support frame shall be designed to relevant standards including, but not limited to, the following:
· AS/NZS 4600 – Cold-formed steel structures · NZS 3404 – Steel structures · NZS 3604 – Timber framed buildings
9 20 - 100 mm 20 mm 20 mm
20 - 100 mm
CEDRAL LAP
< 600 mm
CEDRAL LAP 52mm colour matched screw
< 600 mm
20 - 100 mm
20 - 100 mm
Figure 1: CEDRAL LAP fixings arrangement - Elevation
Pro clima SOLITEX EXTASANA pliable membrane
EPDM strip
CEDRAL LAP 52mm colour matched screw
70 x 35 mm timber batten with 15 degree chamfered top
Substructure
Standard 45 x 20 mm cavity batten
CEDRAL LAP
Figure 2: CEDRAL LAP typical vertical section
10 Substructure
Standard 45 x 20 mm Pro clima SOLITEX EXTASANA cavity batten pliable membrane
70 x 35 mm timber batten with 15 degree chamfered top
EPDM strip
CEDRAL LAP EPDM compressible gasket 20 mm 20 mm CEDRAL LAP 52mm colour matched screw 40 mm overlap
Figure 3: CEDRAL LAP vertical joint
10 mm or as required
EPDM strip
CEDRAL LAP 20 mm EPDM compressible gasket Max. 150 mm CEDRAL LAP screw CEDRAL LAP 52mm colour matched screw
Figure 4: CEDRAL LAP vertical control joint - Detail 1
10 mm or as required
EPDM strip Other materials CEDRAL LAP 52mm colour matched screw Backing rod & sealant CEDRAL LAP starter profile EPDM compressible gasket
Figure 5: CEDRAL LAP vertical control joint - Detail 2
Note Support frame (battens) must NOT be fixed crossing over a control joint.
11 10 mm or as required
Other materials
EPDM strip Min. 10 mm or as required
EPDM Backing rod & sealant compressible gasket CEDRAL LAP 52mm colour matched screw
Figure 6: CEDRAL LAP vertical control joint - Detail 3
60mm flashing tape
CEDRAL LAP 52mm colour matched screw
Min. 100 mm Corrosion resistant perforated angle
10 - 15 mm drip edge
Min. 10 mm
Min. 10mm or larger as specified by project engineer
Min. 40 mm
5 mm Suitable flashing with min. 15 degree slope 15 mm
Figure 7: CEDRAL LAP horizontal control joint and inter-storey detail
Notes 1) Support frame (battens) must NOT be fixed crossing over a control joint. 2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% open area.
12 60mm flashing tape
Suitable head flashing with min. 15mm upstand each end, and min. 15 degree slope CEDRAL LAP 52mm colour matched screw
Corrosion resistant Min. 100 mm Air seal option 2 perforated angle Min. 60mm flashing tape Sealant for Very High and Extra Min. 10 mm cover High wind zones Air seal option 1 Backing rod & sealant Min. 10 mm Min. 10 mm
Foil tape over sill tape and membrane for wet Outline of jamb flashing sealing (sealant)
Corrosion resistant sill flashing with min. 15mm upstand each end Air seal option 2 Sill tape Min. 60mm flashing tape
5 mm Air seal option 1 Suitable sill flashing with min. 15mm upstand each Backing rod & sealant Min. 8 mm cover end passing behind jamb flashing, and min. 15 Min. 35 mm cover degree slope Min. 50 mm
Corrosion resistant 10 mm perforated angle
Min. 40 mm
5 mm 15 mm
Figure 8: CEDRAL LAP window head and sill junction or the like
Air seal option 2 Min. 60mm flashing tape
Air seal option 1 Backing rod & sealant
Foil tape over sill tape and membrane for wet sealing (sealant)
Outline of head flashing
Backing rod & sealant
Outline of sill flashing (jamb flashing) EPDM strip 5 - 10 mm CEDRAL LAP asymmetric external corner profile (jamb flashing) CEDRAL LAP 52mm colour matched screw Backing rod & sealant
CEDRAL LAP starter profile EPDM compressible gasket
Figure 9: CEDRAL LAP window jamb junction or the like
Notes 1) ONLY sealant compatible with the foil tape should be used. Should any sealant be intended to be used directly on the flashing and/or sill tape it must be confirmed with its manufacturer to ensure compatibility with these tapes in accordance with the relevant standards. 2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% open area. 13 60mm flashing tape
Corrosion resistant perforated angle CEDRAL LAP 52mm colour matched screw
Suitable flashing with min. 15mm upstand on each end with all gaps between upstands, flashing and CEDRAL sealed, and min. 15 degree slope
Min. 100 mm 10 - 15 mm drip edge
10 mm Min. 10 mm
Backing rod & sealant Sealant
Foil tape over sill tape and membrane for wet Sill tape sealing (sealant)
Backing rod & sealant Min. 50 mm
EPDM strip
Figure 10: CEDRAL LAP meter box junction - Section
Backing rod & sealant
Foil tape over sill tape and membrane for wet sealing (sealant)
Backing rod & sealant
Outline of head flashing
EPDM strip CEDRAL LAP 52mm colour matched screw EPDM compressible gasket Min. 20 mm 5 - 10 mm
Figure 11: CEDRAL LAP meter box junction Plan view
Notes 1) ONLY sealant compatible with the foil tape should be used. Should any sealant be intended to be used directly on the flashing and/or sill tape it must be confirmed with its manufacturer to ensure compatibility with these tapes in accordance with the relevant standards. 2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% open area.
14 Min. 100 mm Sill tape to the top corners with min. 50mm cover onto membrane (Applied second)
Min. 100 mm
Min. 100 mm Foil tape between sealant and sill tape, and membrane (Applied last); only applies when using sealant (wet seal)
Sill tape to the sill reveal with min. 50mm cover onto membrane (Applied first)
Figure 12: Isometric view of window/meter box opening - Tape application
60mm flashing tape
EPDM strip
CEDRAL LAP 52mm colour matched screw
Suitable flashing with min. 15 degree slope
Min. 10 mm Min. 15 mm Min. 20 mm Max. 100 mm
Min. 10 mm Corrosion resistant 10 mm Soffit lining perforated angle Min. 15 mm
Perforated angle
EPDM strip
Figure 13: CEDRAL LAP soffit junction
Notes 1) ONLY sealant compatible with the foil tape should be used. Should any sealant be intended to be used directly on the flashing and/or sill tape it must be confirmed with its manufacturer to ensure compatibility with these tapes in accordance with the relevant standards. 2) Support frame (battens) must NOT be fixed crossing over a control joint. 3) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% open area.
15 60mm flashing tape
CEDRAL LAP 52mm colour matched screw
Corrosion resistant perforated angle Min. 50 mm cover
10 - 15 mm drip edge
Min. 150 mm ground clearance or larger to regulatory requirements
Figure 14: CEDRAL LAP base detail
60mm flashing tape
CEDRAL LAP 52mm colour matched screw
Corrosion resistant perforated angle
Min. 12 mm Min. 50 mm cover
10 - 15 mm drip edge Min. 35 mm or larger to regulatory requirements
Figure 15: CEDRAL LAP base detail - Covered area
60mm flashing tape
CEDRAL LAP 52mm colour matched screw
Corrosion resistant perforated angle Min. 50 mm cover 10 - 15 mm drip edge
Min. 20 mm or larger to regulatory requirements
Figure 16: CEDRAL LAP base detail - Balcony
Notes 1) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% open area. 2) Refer to pro clima's application guide for the application of the flashing tape and any pre-treatment required on various substrates including concrete and masonry. 16 Suitable flashing with min. 15 degree slope
Corrosion resistant perforated angle 10 mm
Min. 40 mm
5 mm 15 mm
EPDM strip
60mm flashing tape
CEDRAL LAP 52mm colour matched screw
Corrosion resistant perforated angle
Min. 150 mm Suitable flashing with min. 15 degree slope
10 - 15 mm drip edge
Min. 15 mm
Min. 35 mm
Figure 17: CEDRAL LAP junction with other materials - Flush detail
Min. 10 mm Corrosion resistant perforated angle
Soffit lining Min. 40 mm
Suitable flashing 5 mm 15 mm
EPDM strip
60mm flashing tape
Corrosion resistant perforated angle
CEDRAL LAP 52mm colour matched screw
Suitable flashing with min. 15 degree slope Min. 150 mm 10 - 15 mm drip edge
Min. 15 mm
Min. 35 mm
Figure 18: CEDRAL LAP junction with other materials, eaves or the like - Recessed detail
Notes 1) Support frame (battens) must NOT be fixed crossing over a control joint. 2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% open area.
17 Sealant Corrosion resistant perforated angle fixed only to slab
Min. 10mm or larger as specified by project engineer 60mm flashing tape Min. 40 mm
Suitable flashing 5 mm 15 mm
EPDM strip
60mm flashing tape
CEDRAL LAP 52mm colour matched screw
Corrosion resistant perforated angle Min. 150 mm Suitable flashing with min. 15 degree slope 10 - 15 mm drip edge Min. 15 mm
Min. 35 mm
60mm flashing tape
Figure 19: CEDRAL LAP junction with exposed concrete slab or beam - Cladding flush
Sealant Corrosion resistant perforated angle fixed only to slab
Min. 10mm or larger as specified by project engineer 60mm flashing tape Min. 40 mm Suitable flashing 5 mm 15 mm
EPDM strip
60mm flashing tape
CEDRAL LAP 52mm colour matched screw
Corrosion resistant perforated angle Min. 150 mm Suitable flashing with min. 15 degree slope
10 - 15 mm drip edge Min. 15 mm
Min. 35 mm
60mm flashing tape
Figure 20: CEDRAL LAP junction with exposed concrete slab or beam - Cladding recessed
Notes 1) Support frame (battens) must NOT be fixed crossing over a control joint. 2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% open area. 3) Refer to pro clima's application guide for the application of the flashing tape and any pre-treatment required on various substrates including concrete and masonry. 18 EPDM strip
CEDRAL LAP 52mm colour matched screw
EPDM compressible gasket
Backing rod and sealant
5 - 10 mm
CEDRAL LAP symmetric external 5 - 10 mm corner profile
Bond breaker and sealant
Figure 21: CEDRAL LAP typical external corner
EPDM strip
CEDRAL LAP 52mm colour matched screw
Bond breaker and sealant EPDM compressible gasket
5 - 10 mm 5 - 10 mm Backing rod and sealant
Suitable external corner profile
Figure 22: CEDRAL LAP 45 degree external corner
19 Bond breaker and sealant
CEDRAL LAP internal corner profile
Backing rod and sealant
EPDM compressible gasket
CEDRAL LAP 52mm colour matched screw EPDM strip
Figure 23: CEDRAL LAP internal corner
60mm flashing tape
10 mm CEDRAL LAP 52mm colour matched screw
Backing rod & sealant
Figure 24: CEDRAL LAP abutment - Detail 1
60mm flashing tape
10 mm CEDRAL LAP 52mm colour matched screw EPDM compressible gasket
Backing rod & sealant
Figure 25: CEDRAL LAP abutment - Detail 2
Note Refer to pro clima's application guide for the application of the flashing tape and any pre-treatment required on various substrates including concrete and masonry.
20 60mm flashing tape Grommet
Supporting collar, backing rod & sealant
Figure 26: Pipe penetration - Plan view
60mm flashing tape
Grommet Grommet
Supporting collar, backing rod & sealant
60mm flashing tape Once the grommet is installed, first apply this tape, and then continue anti- clockwise with the others
Figure 27: Pipe penetration - Elevation Figure 28: Pipe penetration - Section
21 Min. 5 degree slope Suitable capping structural support
60mm flashing tape Sill or sealing tape Corrosion resistant perforated angle EPDM strip
Min. 10 mm
To regulatory requirements Min. 50 mm or larger to regulatory requirements
5 mm 15 mm
Roof or gutter CEDRAL LAP 52mm colour matched screw flashing, or membrane
Figure 29: CEDRAL LAP typical capping detail
Non-continuous packer Min. 5 degree slope Suitable capping structural support Sill or sealing tape
60mm flashing tape
Min. 15 mm Min. 50 mm or larger to regulatory requirements Min. 50 mm or larger to regulatory requirements
Corrosion resistant Air perforated angle EPDM strip 10 - 15 mm Roof or gutter flashing, or membrane
Figure 30: CEDRAL LAP flush capping detail
60mm flashing tape
Backing rod & sealant Capping with two rows of sealant to saddle flashing
Corrosion resistant Saddle flashing with two rows of sealant to capping support
Min. 50mm Capping support
Sill tape Min. 100 mm
Figure 31: CEDRAL LAP parapet junction - Section
Notes 1) Capping profiles are indicative and for illustration purposes. 2) Any face fixings of capping shall be through an over sized hole (by min 5mm) in the capping as well as the panel. 3) Capping shall be designed and engineered accordingly to provide adequate allowance for ventilation as shown in Figures 29 & 30.
22 EPDM strip
Bond breaker and sealant
CEDRAL LAP internal corner profile
Backing rod and sealant Outline of saddle flashing EPDM compressible gasket
CEDRAL LAP 52mm colour matched screw
Figure 32: Parapet junction - Plan view
Min. 30 mm
Min 5 degree slope
Min. 30 mm Min. 100 mm
Min. 50 mm
Min. 150 mm
Min. 20 mm
Min. 70 mm Min.30 mm
Figure 33: Corrosion resistant saddle flashing
23 Cedral Lap Vertical With Top Hat Construction Fixings and support frame
CEDRAL LAP Vertical with metal top hat construction
Cedral Lap may be fixed vertically in traditional lapped style to metal top hat support frame.
Fixings
Cedral metal screw for fixing Cedral Lap to metal support frame (Drill point, Phillips n°2, stainless steel 304)
Support frame
Cedral Lap may be fixed vertically to horizontal metal top hat profiles with minimum gauge (thickness) of 1.1mm BMT, minimum depth of 25mm, and minimum width of 40mm and 70mm for intermediate and joint profiles, respectively. A layer of minimum 15mm deep (minimum 1.1.mm BMT) vertical top hats are used between the horizontal top hats and weather barrier to form a minimum 15mm gap behind the horizontal top hats for ventilation and drainage purposes. Examples of standard top hat sections
Metal top hats shall be of adequate corrosion resistance required for the project. Min. 25 Min. 25 mm mm Maximum deflection of support framing must be limited to Span/250. Structure and support frame shall be designed to relevant standards Intermediate top hat’s minimum size including, but not limited to, the following:
· AS/NZS 4600 – Cold-formed steel structures · NZS 3404 – Steel structures Min. 25 Min. 25 · NZS 3604 – Timber framed buildings mm mm
Joint top hat’s minimum size
25 20 - 100 mm 20 mm 20 mm
70 - 100 mm
CEDRAL LAP
< 600 mm
CEDRAL LAP 52mm metal screw
< 600 mm
70 - 100 mm
20 - 100 mm
Figure 1: CEDRAL LAP fixings arrangement - Elevation
Pro clima SOLITEX EXTASANA pliable membrane
CEDRAL LAP metal screw
Min. 25mm deep(min. 1.1mm BMT) horizontal support frame profile
Substructure
Min. 15 mm deep (min. 1.1mm BMT) vertical support frame profile
CEDRAL LAP
Figure 2: CEDRAL LAP typical vertical section
26 Substructure
Min. 15 mm deep (min. Pro clima SOLITEX EXTASANA 1.1mm BMT) vertical pliable membrane support frame profile
Min. 25mm deep(min. 1.1mm BMT) horizontal support frame profile
EPDM compressible gasket 20 mm 20 mm CEDRAL LAP 40 mm overlap CEDRAL LAP metal screw
Figure 3: CEDRAL LAP vertical joint
10 mm or as required
Min. 15 mm deep (min. 1.1mm BMT) vertical support frame profile
Min. 25mm deep(min. 1.1mm BMT) horizontal support frame profile
20 mm Max. 150 mm EPDM compressible gasket CEDRAL LAP CEDRAL LAP metal screw
Figure 4: CEDRAL LAP vertical control joint - Detail 1
10 mm or as required
CEDRAL LAP metal screw Other materials
CEDRAL LAP starter profile Backing rod & sealant
EPDM compressible gasket
Figure 5: CEDRAL LAP vertical control joint - Detail 2
Note Support frame (battens) must NOT be fixed crossing over a control joint.
27 10 mm or as required
Other materials
Min. 10 mm or as required
EPDM compressible gasket Backing rod & sealant
CEDRAL LAP metal screw
Figure 6: CEDRAL LAP vertical control joint - Detail 3
60mm flashing tape
CEDRAL LAP metal screw
Min. 100 mm Corrosion resistant perforated angle 10 - 15 mm drip edge Min. 10 mm
Min. 10mm or larger as specified by project engineer
Min. 40 mm
Suitable flashing with min. 15 degree slope 5 mm 15 mm
Figure 7: CEDRAL LAP horizontal control joint and inter-storey detail
Notes 1) Support frame (battens) must NOT be fixed crossing over a control joint. 2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% open area.
28 60mm flashing tape
Suitable head flashing with min. 15mm upstand each end, and min. 15 degree slope
CEDRAL LAP metal screw
Min. 100 mm Corrosion resistant perforated angle Air seal option 2 Min. 60mm flashing tape Sealant for Very High and Extra High Min. 10 mm cover wind zones Air seal option 1 Backing rod & sealant Min. 10 mm Min. 10 mm
Foil tape over sill tape and membrane for wet sealing Outline of jamb flashing (sealant)
Corrosion resistant sill flashing with min. 15mm upstand each end Air seal option 2 Sill tape Min. 60mm flashing tape Suitable sill flashing with min. 15mm upstand each 5 mm end passing behind jamb flashing, and min. 15 Air seal option 1 degree slope Backing rod & sealant Min. 8 mm cover
Min. 50 mm Min. 35 mm cover Corrosion resistant perforated angle
10 mm
Min. 40 mm
5 mm 15 mm
Figure 8: CEDRAL LAP window head and sill junction or the like
Air seal option 2 Min. 60mm flashing tape
Air seal option 1 Backing rod & sealant
Foil tape over sill tape and membrane for wet sealing (sealant)
Min. 1.1mm angle
Outline of head flashing
Backing rod & sealant
Outline of sill flashing (jamb flashing)
5 - 10 mm CEDRAL LAP asymmetric external corner CEDRAL LAP metal screw profile (jamb flashing) Backing rod & sealant
CEDRAL LAP starter profile EPDM compressible gasket
Figure 9: CEDRAL LAP window jamb junction or the like
Notes 1) ONLY sealant compatible with the foil tape should be used. Should any sealant be intended to be used directly on the flashing and/or sill tape it must be confirmed with its manufacturer to ensure compatibility with these tapes in accordance with the relevant standards. 2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% open area. 29 60mm flashing tape
CEDRAL LAP metal screw
Corrosion resistant perforated angle
Suitable flashing with min. 15mm upstand on each end with all gaps between upstands, flashing and CEDRAL sealed, and min. 15 degree Min. 100 mm slope 10 - 15 mm drip edge
10 mm Min. 10 mm
Backing rod & sealant Sealant
Foil tape over sill tape and membrane for wet Sill tape sealing (sealant)
Backing rod & sealant Min. 50 mm
Figure 10: CEDRAL LAP meter box junction - Section
Backing rod & sealant
Foil tape over sill tape and membrane for wet sealing (sealant)
Backing rod & sealant
Outline of head flashing
CEDRAL LAP metal screw Min. 20 mm 5 - 10 mm
EPDM compressible gasket
Figure 11: CEDRAL LAP meter box junction Plan view
Notes 1) ONLY sealant compatible with the foil tape should be used. Should any sealant be intended to be used directly on the flashing and/or sill tape it must be confirmed with its manufacturer to ensure compatibility with these tapes in accordance with the relevant standards. 2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% open area.
30 Min. 100 mm Sill tape to the top corners with min. 50mm cover onto membrane (Applied second) Min. 100 mm
Foil tape between sealant and sill tape, and Min. 100 mm membrane (Applied last); only applies when using sealant (wet seal)
Sill tape to the sill reveal with min. 50mm cover onto membrane (Applied first)
Figure 12: Isometric view of window/meter box opening - Tape application
60mm flashing tape
CEDRAL LAP metal screw
Suitable flashing with min. 15 degree slope
Perforated angle Min. 15 mm
Min. 10 mm Max. 100 mm Min. 20 mm
Min. 10 mm 10 mm Soffit lining Corrosion resistant Min. 15 mm perforated angle
CEDRAL LAP metal screw
Figure 13: CEDRAL LAP soffit junction
Notes 1) ONLY sealant compatible with the foil tape should be used. Should any sealant be intended to be used directly on the flashing and/or sill tape it must be confirmed with its manufacturer to ensure compatibility with these tapes in accordance with the relevant standards. 2) Support frame (battens) must NOT be fixed crossing over a control joint. 3) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% open area.
31 60mm flashing tape
CEDRAL LAP metal screw
Corrosion resistant perforated angle Min. 50 mm cover
10 - 15 mm drip edge
Min. 150 mm ground clearance or larger to regulatory requirements
Figure 14: CEDRAL LAP base detail
60mm flashing tape
CEDRAL LAP metal screw
Corrosion resistant perforated angle
Min. 12 mm Min. 50 mm cover
10 - 15 mm drip edge Min. 35 mm or larger to regulatory requirements
Figure 15: CEDRAL LAP base detail - Covered area
60mm flashing tape
CEDRAL LAP metal screw
Corrosion resistant perforated angle Min. 50 mm cover 10 - 15 mm drip edge Min. 20 mm or larger to regulatory requirements
Figure 16: CEDRAL LAP base detail - Balcony
Notes 1) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% open area. 2) Refer to pro clima's application guide for the application of the flashing tape and any pre-treatment required on various substrates including concrete and masonry. 32 Suitable flashing with min. 15 degree slope
Corrosion resistant perforated angle 10 mm
Min. 40 mm
5 mm 15 mm
60mm flashing tape
CEDRAL LAP metal screw Corrosion resistant perforated angle
Suitable flashing with min. 15 degree slope Min. 150 mm 10 - 15 mm drip edge
Min. 15 mm
Min. 35 mm
Figure 17: CEDRAL LAP junction with other materials - Flush detail
Min. 10 mm Corrosion resistant perforated angle
Soffit lining Min. 40 mm Suitable flashing
5 mm 15 mm
60mm flashing tape
Corrosion resistant perforated angle
CEDRAL LAP metal screw
Min. 150 mm Suitable flashing with min. 15 degree slope
10 - 15 mm drip edge Min. 15 mm
Min. 35 mm
Figure 18: CEDRAL LAP junction with other materials, eaves or the like - Recessed detail
Notes 1) Support frame (battens) must NOT be fixed crossing over a control joint. 2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% open area.
33 Sealant Corrosion resistant perforated angle fixed only to slab
Min. 10mm or larger as specified by project engineer 60mm flashing tape Min. 40 mm
Suitable flashing 5 mm 15 mm
60mm flashing tape
CEDRAL LAP metal screw
Corrosion resistant perforated angle
Suitable flashing with min. 15 degree slope Min. 150 mm
10 - 15 mm drip edge
Min. 15 mm
Min. 35 mm
60mm flashing tape
Figure 19: CEDRAL LAP junction with exposed concrete slab or beam - Cladding flush
Sealant Corrosion resistant perforated angle fixed only to slab
Min. 10mm or larger as specified by project engineer 60mm flashing tape Min. 40 mm
Suitable flashing 5 mm 15 mm
60mm flashing tape
CEDRAL LAP metal screw
Corrosion resistant perforated angle
Suitable flashing with min. 15 degree slope Min. 150 mm 10 - 15 mm drip edge
Min. 15 mm
Min. 35 mm
60mm flashing tape
Figure 20: CEDRAL LAP junction with exposed concrete slab or beam - Cladding recessed
Notes 1) Support frame (battens) must NOT be fixed crossing over a control joint. 2) Corrosion resistant perforated angle shall be of max. thickness of 0.9mm where located between panel and support frame, and be of min. 50% open area. 3) Refer to pro clima's application guide for the application of the flashing tape and any pre-treatment required on various substrates including concrete and masonry. 34 Min. 100 X 100 X 1.1mm flashing
CEDRAL LAP metal screw
EPDM compressible gasket
Backing rod and sealant 5 - 10 mm
CEDRAL LAP symmetric external 5 - 10 mm corner profile
Bond breaker and sealant
Figure 21: CEDRAL LAP typical external corner
CEDRAL LAP metal screw Bond breaker and sealant EPDM compressible gasket 5 - 10 mm 5 - 10 mm Backing rod and sealant
Suitable external corner profile
Figure 22: CEDRAL LAP 45 degree external corner
35 Bond breaker and sealant
CEDRAL LAP internal corner profile
Backing rod and sealant
EPDM compressible gasket
CEDRAL LAP metal screw
Figure 23: CEDRAL LAP internal corner
60mm flashing tape
10 mm CEDRAL LAP metal screw
Backing rod & sealant
Figure 24: CEDRAL LAP abutment - Detail 1
60mm flashing tape
10 mm CEDRAL LAP metal screw
EPDM compressible gasket
Backing rod & sealant
Figure 25: CEDRAL LAP abutment - Detail 2
Note Refer to pro clima's application guide for the application of the flashing tape and any pre-treatment required on various substrates including concrete and masonry.
36 60mm flashing tape Grommet Supporting collar, backing rod & sealant
Figure 26: Pipe penetration - Plan view
60mm flashing tape
Grommet Grommet
Supporting collar, backing rod & sealant
60mm flashing tape Once the grommet is installed, first apply this tape, and then continue anti- clockwise with the others
Figure 27: Pipe penetration - Elevation Figure 28: Pipe penetration - Section
37 Min. 5 degree slope Suitable capping structural support 60mm flashing tape Sill or sealing tape Corrosion resistant perforated angle
Min. 10 mm
To regulatory requirements Min. 50 mm or larger to regulatory requirements
5 mm 15 mm
Roof or gutter flashing, or CEDRAL LAP metal screw membrane
Figure 29: CEDRAL LAP typical capping detail
Non-continuous packer Min. 5 degree slope Suitable capping structural support Sill or sealing tape
60mm flashing tape
Min. 15 mm Min. 50 mm or larger to regulatory requirements Min. 50 mm or larger to regulatory requirements
CEDRAL LAP metal screw Corrosion resistant
perforated angle Air 10 - 15 mm Roof or gutter flashing, or membrane
Figure 30: CEDRAL LAP flush capping detail
60mm flashing tape
Backing rod & sealant Capping with two rows of sealant to saddle flashing
Corrosion resistant Saddle flashing with two rows of sealant to capping support
Min. 50mm Capping support
Sill tape Min. 100 mm
Figure 31: CEDRAL LAP parapet junction - Section
Notes 1) Capping profiles are indicative and for illustration purposes. 2) Any face fixings of capping shall be through an over sized hole (by min 5mm) in the capping as well as the panel. 3) Capping shall be designed and engineered accordingly to provide adequate allowance for ventilation as shown in Figures 29 & 30.
38 Bond breaker and sealant
CEDRAL LAP internal corner profile
Backing rod and sealant Outline of saddle flashing
EPDM compressible gasket
CEDRAL LAP metal screw
Figure 32: Parapet junction - Plan view
Min. 30 mm
Min 5 degree slope
Min. 30 mm Min. 100 mm
Min. 50 mm
Min. 150 mm
Min. 20 mm
Min. 70 mm Min.30 mm
Figure 33: Corrosion resistant saddle flashing
39 Ed. 2 FEB2021