Life Safety Dampers - International • Fire • Combination Fire Smoke • Smoke • Ceiling Radiation

June 2018 Fire Dampers

Greenheck’s employees are deeply committed Our commitment to our customers is what drives to being easy to do business with anywhere in our long-standing sustainability practices. We the world. As an industry-leading manufacturer, continuously strive to reduce energy usage and our focus is to build value in air ... by offering the other production costs to ensure competitive widest range of reliable air movement and control prices for you and ongoing business success. products and to exceed your expectations for We support the health, safety and training of our on-time delivery, easy installation, performance employees to achieve the high quality product and operating efficiency. performance you expect from Greenheck — and deserve. And we take on the industry’s most complex challenges by introducing innovative new product solutions to meet your future needs.

Our Mission: To be the market leader in the development, manufacture and worldwide sale of quality air moving and control equipment Our Vision: Greenheck will be a company with total commitment to the customer. that exceeds customer expectations and that others strive to emulate. We will be the worldwide leader in providing timely, flexible and cost-effective solutions focused on the movement, cleaning, tempering, and control of air.

2 Building value in air — from the beginning. Today, we’re the world’s largest manufacturer of commercial, institutional and industrial air movement and control equipment.

Greenheck’s worldwide leadership in providing cost-effective, value-added solutions for air movement and control challenges evolved from rather humble beginnings. Bernie and Bob Greenheck weren’t sure what lay ahead when they opened their small sheet metal The first factory. 1947 shop in Schofield, Wisconsin USA in 1947. But they were determined that no product would ever leave their shop, unless it met the most stringent quality standards—their own. At first, the company manufactured a variety of sheet metal products. In 1956, Greenheck engineers developed a highly efficient power roof ventilator. This product and the innovative ventilation solutions that followed ultimately enabled us to expand our distribution throughout the world. Today, quality Greenheck products are efficiently moving air in commercial buildings, institutions and factories throughout North America, Latin America, the Middle East, and Asia. Customer driven employees. Greenheck employees continue to share an extraordinary commitment to meeting and exceeding customers’ Bernie and Bob Greenheck expectations. We know our future success depends on the 1956 value we bring to the market: reliable, top-quality products and exceptional service.

Schofield WI, USA

ShelbyS & Kings Mountain NC, USA Rocklin CA, USA

Bawal Frankfort India KY, USA Saltillo 3 Mexico Table of Contents

Introduction ...... 5-19 Fire Dampers ...... 7-21 Application ...... 7 UL Standards ...... 8 Installation Requirements ...... 9-11 Special Installations ...... 12 Difference Between Curtain and Multi-Blade Fire Dampers...... 13-14 Accessories ...... 15 Selection and Sizing Charts ...... 16-21 Smoke Dampers ...... 22-30 Application ...... 22 UL Standards ...... 23 Installation Requirements ...... 24 Construction ...... 25-26 Actuators...... 27-28 Selection and Sizing Charts ...... 29-30 Combination Fire Smoke Dampers ...... 31-39 Application ...... 31 Installation Requirements ...... 32-33 Construction ...... 34-35 Actuators...... 36 Closure Devices ...... 37 Selection and Sizing Charts ...... 38-39 Round Dampers...... 40-41 Ceiling Radiation Dampers...... 42-44 Application ...... 42 Non-Combustible Assemblies ...... 42 Combustible Assemblies ...... 43 Options and Selection Chart...... 44 Performance (Pressure Drop) ...... 45-49 Accessories ...... 50-55 Factory Mounted Accessories ...... 50 Testing Devices ...... 51 Blade Indicators and Smoke Detectors ...... 52 Transitions and installation...... 53 Convenience Features ...... 54 Cost Saving Products ...... 55 General Information ...... 56-63 Model Definition ...... 56 Drive Arrangement Definition ...... 57 Specification Checklist ...... 58 Modifications to Life Safety Dampers ...... 59 Most Commonly Asked Questions ...... 60 Inspection, Maintenance and Testing ...... 61 Models by Manufacturing Location ...... 62

4 Life Safety Dampers

Life safety dampers are intended to protect openings in walls, ceilings, floors and/or partitions to prevent the spread of fire and/or smoke. The four types are: Fire Dampers Smoke Dampers Combination Fire Smoke Dampers Ceiling Radiation Dampers

Fire Dampers are required by building codes to maintain the required fire resistance ratings of walls, partitions and floors when they are penetrated by air ducts and transfer openings. These products are tested and classified in accordance with UL Standard 555.

Smoke Dampers have two applications: 1. They may be applied in a passive smoke control system where they simply close and prevent the circulation of air and smoke through a or a ventilation opening in a smoke barrier. 2. They may be applied as part of an engineered smoke control system designed to control the spread of smoke using the building’s HVAC system and/or dedicated fans to create pressure differences. These products are tested and classified in accordance with UL Standard 555S.

Combination Fire Smoke Dampers perform the function of both a fire and a smoke damper. These products are tested and classified in accordance with both UL 555 and UL 555S.

Ceiling Radiation Dampers are designed to protect penetrations through the ceiling membrane of fire resistive floor ceiling and/or roof ceiling assemblies. These products are tested and listed in accordance with UL Standard 555C and 263.

5 Codes and Standards

The terms “code” and “standard” are often used interchangeably but there is a fine point of difference. A code is a set of regulations and requirements written in appropriate language with the expectation that it will become law. A code is enacted into law when it is adopted by formal action of a governing body or other authority having jurisdiction. A standard is not necessarily written with the expectation that it will be adopted by some authority having jurisdiction and become law. Rather, a standard is intended to establish a defined level of performance or requirements, and often includes a listing of the necessary tests and qualifications for compliance with the standard. Codes often reference standards making them a part of the referencing code. For example, the 2018 International Building Code references UL (Underwriters Laboratory Standard 555 as the appropriate standard for qualifying fire dampers for use under the International Building Code. Compliance with the Applicable Building Codes is Mandatory If a state, city, or other authority having jurisdiction has adopted one or more codes governing construction within that jurisdiction, these codes are the law and must be followed. As there are many code documents in existence that have not been adopted by every authority with jurisdiction, it is important that both the designer and contractor know exactly what codes are applicable to the building in question. The intent of the International Building Code is to provide minimum requirements to safeguard the public health, safety, and general welfare of the occupants of new and existing buildings and structures (2018 IBC, page ix). The subject of codes and standards cannot be treated in any depth in the space available in this manual. See installation instructions and installation supplements for specific information. The National Fire Protection Association The National Fire Protection Association merits special mention because of its significance as a standard writing and trend setting organization in the fire and life safety arena. NFPA, a non-profit membership organization founded in 1896, brings together all interested parties to promote safety from fire, electricity, and related hazards through research, codes and standards, technical services, and public education. Many of NFPA’s Codes and Standards provide the basis for model building code requirements or actually become a part of these codes. New concepts and other changes in various NFPA Standards are usually adopted by the several model building codes during the code review and revision process. The codes that affect fire dampers, combination fire smoke dampers, and smoke dampers are NFPA 80, 90A, 90B, 92, 101, and 105. California State Fire Marshal (CSFM) The office of State Fire Marshal requires products to go through an approval, testing, and listing process for California. The CSFM listing service provides building authorities, architectural and engineering communities, contractors, and the fire service with a reliable and readily available source of information. FM Global FM Global manages a non-profit research and testing organization which tests and provides approvals for building products to help minimize losses in buildings they insure. FM approved products meet rigorous property loss prevention testing and certification standards. This approval gives the building owner an edge on receiving and maintaining advantageous financing and insurance rates. AMCA The AMCA Certified Rating Program seal assures you that a product line has been tested to the appropriate AMCA standards in accordance with a legal license agreement and that the manufacturer’s cataloged certified ratings have been submitted to AMCA for approval.

6 Fire Dampers 7 Fire Dampers Fire by fire damper by fire Partition protected Partition protected Unprotected partition Unprotected to the compartment of fire origin. to the compartment of fire Fire rated partitions contain fire damage rated partitions contain fire Fire Rating 3 hours ½ hours 1 Minimum Damper for either HVAC system. for either HVAC Type of Penetration Type hour rated fire dampers. hour rated fire 2 ⁄ 1 3 hour or greater fire resistance resistance fire 3 hour or greater rated assemblies Less than 3 hour fire resistance resistance Less than 3 hour fire rated assemblies Static vs. Dynamic dampers carry a UL 555 rating and can be Fire or DYNAMIC rated. either STATIC dampers have no airflow closure Static rated fire systems rating and can only be applied in HVAC in the designed to shut down automatically that are event of a fire. dampers carry a UL 555 Dynamic rated fire system is running. rating to close while the HVAC dampers carry both an airflow Dynamic rated fire differential velocity (ft/min) rating and a pressure rating (in. wg) and should be selected to operate against the conditions they will see in their always dampers are application. Dynamic rated fire selection an appropriate Hourly Fire Rating Hourly Fire rating resistance floors, or partitions with a fire Walls, dampers with a 3 hour fire require of 3 hours or more ratings less than 3 hours require resistance rating. Fire an 1 Application Application to by building codes required are dampers Fire ratings of resistance fire maintain the required and floors when they are walls, partitions, barriers, ducts or other air transfer openings. penetrated by air of building fire One of the basic requirements or dividing up is the compartmentation, protection walls and floors. This rated fire of buildings using concept is intended to contain compartmentation and thereby to the compartment of origin any fire the lives of protect and to property minimize damage working in the building. A duct or people living and/or rated partitions in any of the fire ventilation opening the compartment from to spread could permit a fire dampers are Fire of origin to adjoining compartments. openings. They installed in these duct or ventilation of heat by a heat- close automatically upon detection device (usually by the melting of a fusible responsive the spread link), blocking the opening and preventing into the adjoining compartment. of fire Fire Dampers 8 pressure of30psi(207kPa)for1 pressure hosestream test.Duringthetestawater of thefire test,thedampersare subjectedtoahigh curve illustrated.Immediatelyaftertheconclusion test iscontrolled tofollowthetimetemperature the rigorsofmostsevere fire conditions. dampers are structurallystrong enoughtowithstand test provides an extreme shockthatensures the at adistanceof20feet(6meters).Thehosestream and 45psi(310kPa)for3hourdampersisapplied temperature withinthe ductsystem”. In addition,theIBCstates “The operatingtemperature shallbeapproximately 50°F(10°C)abovethenormal temperature ratingis212°F(100°C)forstaticrateddampersand350°F(177°C)dynamicdampers. UL 555requires closure devicestohaveaminimumtemperature ratingof160°F(71°C).Themaximum UL Standards forTesting andRatingofFire Dampers during itsintendedapplication. fouling thanthedamperislikelytoexperience damper’s abilitytofunction afteramore severe if alatchisprovided). Thistestdemonstratesa this exposure, thedampermustclose(andlatch test chamberforaperiodof120hours.After A dampersampleisexposedtosaltsprayina Salt SprayExposure Test (UL555&UL555S) damper toclose. damper’s temperature response devicecausesthe then afourthtimewiththeairheatedsuchthat tested three timesatambientairconditionsand 400 fpmabovethedesired rating.Thedamperis achieve agivenrating,thedamperistestedat in increments of1000fpm.Asasafetyfactorto is 2000fpm.Extendedratingscanbeachieved at whichadynamicclosure ratingcanbeissued damper tocloseunderairflow. Theminimumvelocity ability ofafire damperorcombinationfire smoke The UL555dynamicclosure testevaluatesthe Dynamic Closure Test (UL555) period ofeither1 Dampers are exposedtoastandard fire testfora 555) Fire EnduranceTest andHoseStream Test (UL test requirements thatUL555classifieddampersare subjectedto. Dampers”. Theyare alwayssuppliedwithanappropriate ULlabel.Beloware someofthe UL (UnderwritersLaboratories)Classifiedfire dampersare testedtoULStandard 555“Fire 1 ⁄ 2 or3hours.Thisstandard fire 1 ⁄ 2 hourdampers open orclosedoperations. operation cannotexceed75secondsforanyofthe the damperopenandclosedthree times.Timeof temperature, thedamperactuatormust operate minutes ofexposure andwhilestillattheelevated 100°F [38°C])foraperiodof30minutes.After 250°F (121°C)minimum(orhigherinmultiplesof Test isexposedtoanelevatedtemperature of been subjectedtotheOperationalReliabilityCycle A damperwithanactuatorthathaspreviously actuated dampermustbecycled20,000times. must becycledopenandclosed250times.An A non-actuateddamper(gravityorspringforce) Cycling Test (UL555)

Degrees Fahrenheit 1000 1200 1400 1600 1800 2000 2200 2400 200 400 600 800 0 0 1 2 Time-Temperature Curve 3 Hours 4 56 7 8 -17.8 93.3 204.4 315.6 426.7 537.8 648.8 760.0 871.1 962.2 1093.3 1204.4 1315.6

Degrees Celsius Fire Dampers 9 in. (6mm) 4 ⁄ 1 in. (3mm) per Damper Maximum 6 in. 8 ⁄ in. (5mm) per 1 16 Sleeve (See Sleeve Requirements) ⁄ Wall or floor Wall 3 Installation in. (6mm). 4 ⁄ 1 in. (22mm) larger than in. (22mm) larger 8 ⁄ 7 inches (38mm). Type A Type 2 ⁄ 1 1/4 in. minimum total clearance Maximum 6 in. Retaining Angles Duct in. (6mm) and a maximum of 2 inches in. (6mm) and a maximum of 2 inches 4 ⁄ 1 For stainless steel dampers: foot of damper width or height for galvanized foot of damper width or height for galvanized steel dampers with a minimum of (51mm). dampers, the wall/floor opening On true round must be a minimum of the outside diameter of the damper. For galvanized steel dampers: and a maximum of 1 foot of damper width or height with a minimum foot of damper width or height with of • in. (3mm) per foot of damper width and height in. (3mm) per foot of damper width 8 ⁄ • • • • Vertical mount single side angle installation has no Vertical we However, minimum clearance requirements. clearances between the wall opening recommend A easier. and the sleeve to make installation clearances of horizontal mount installation requires 1 Clearances required between damper sleeves between Clearances required openings and wall or floor between different are Clearance requirements (See two sided and single side angle installation. wall and floor Installing damper/sleeve assembly in openings, page 9, for limitations). clearances of: angle installations require Two-sided with a minimum clearance of These Vertical Label Vertical (curtain style) (curtain style) Horizontal Label Mounting Orientation separate tests for to pass required dampers are Fire horizontal mounting applications. vertical mount and correct Dampers need to be installed in the fire life safety and proper orientation to ensure damper is supplied with a label Every fire protection. mounting orientation. identifying the required mounting orientations are not interchangeable. mounting orientations are mount dampers must be installed in Vertical mount block, or stud walls. Horizontal masonry, floors except dampers must be installed in concrete when using the I503 horizontal non-concrete application (see Special Installations). The IBC (International Building Code) requires life safety dampers to be installed in accordance with the with be installed in accordance safety dampers to life The IBC (International Code) requires Building listing. and the damper’s installation instructions manufacturer’s to publish specific damper smoke damper manufacturers smoke, and combination fire all fire, UL requires install each to properly methods and procedures installation detailing the required installation instructions UL the validity of the damper’s must be followed to maintain These instructions damper. specific model of smoke, with each shipment of UL fire, installation instruction(s) is included appropriate listing. A copy of the as damper manufacturers between differ may Installation requirements smoke dampers. or combination fire alternate may qualify be additional tests. Dampers must installation methods by conducting a manufacturer the dampers. company that manufactured with instructions published by the installed in accordance Fire Dampers 10 Greenheck’s standard andmosteconomicalsleevelengthsare 16,21,and24inches(406,533,610mm) wall orflooropeningontheaccessdoorside. extend amaximumof16in.(406mm)beyondthe mounted accessdoorisprovided, thesleevemay opening oneachside.Whenafactory in. (152mm)beyondthewallorfloor Sleeves shallextendamaximumof6 requirements asdefinedbyUL555. fire smokedampersleevethickness provides minimumfire andcombination to-sleeve connectionused.Table 1 on thedampersizeandtypeofduct- Sleeve gaugerequirements depend of thedampersleeve. connecting ductsterminateateachend attached tothesleeve.ULrequires that as partofthestructure byangles in thewallorflooropeningandretained together. Thesleeveddamperisinstalled of attachingthesleeveanddamper instructions showyouthemethod installed inthefield,installation will beready toinstall.Ifthesleeveis correct gaugeisusedandthedamper A factorysuppliedsleeveensures the gauge andlengthpriortoinstallation. be mountedinasleeveofrequired damper listingsrequire thatthedamper All ULfire andcombinationfire smoke Sleeve Requirements Installation * actuatorsideorfactorymountedaccessdoor general area in this mounted are accessories Actuator and 16 in.Max.* SleeveLengthConsiderations AB Overall SleeveLength Damper L Wall Thickness min T Max. 6 in. UL Standard 555requires allductstoterminateatfire dampersleeves. Sleeve thicknessmustnotbelessthanthegaugeofconnectingduct. 14 ga.(0.075in.)- 10 ga.(0.138in.) 16 ga.(0.060in.) 18 ga.(0.048in.) 16 ga.(0.060in.) 20 ga.(0.036in.) 26 ga.(0.018in.) leeGueDuctDimension Sleeve Gauge 22 ga.(.030in.) [2mm -3.5mm] 24 ga.(0.024) [0.76mm] [0.46mm] [1.5mm] [1.2mm] [1.5mm] [0.9mm] [0.6mm] TABLE 1:MinimumSleeveThicknessesfor L L min Fire/Combination Fire SmokeDampers min B A T Wall orFloorThickness 24 in.(610mm)max.height 36 in.(914mm)max.width 85 in.(2159mm)wideand 24 in.(610mm)diameter 12 in.wideandunder = = = = A+BT = (1397mm -2134mm) (787mm -1372mm) Inches (mm) 31 in.-54wide 55 in.-84wide 13 in.-30wide (330mm -762mm) Typical SleeveLengthRequirements (178 -254) (102 -152) (279 -330) All ductsizes All ductsizes 11 -13 wall thickness actuator orfactorymountedaccessdoor) length ofsleevebeyondwall(onsidewithout factory mountedaccessdoor) length ofsleevebeyondwall(actuatorsideor minimum sleevelength 7 -10 4 -6 (305mm) Sleeve LengthEquation over Sleeve LengthRequired Type ofDucttoSleeve Connection Permitted Inches (mm) (533 -610) (406 -533) (610 -711) Rigid orBreakaway 21 -24 16 -21 24 -28 Breakaway only Breakaway Rigid or Fire Dampers 11 ners Fire Damper Sleeve Fire between all angles 3/8 in. bolts in cor 4w 4MJQ OHi4w "MU Neoprene or Butyl gasket Neoprene between all angles 4UBOEJOHi4w Installation  "OHMF3FJOGPSDFE Wall or Floor Wall Damper Maximum 6 in. Type A Type 1/4 in. minimum1/4 in. minimum total clearancetotal clearance Transverse Joints Transverse Maximum 6 in. Manufactured Flanged Systems Manufactured Duct Retaining Angles *OTJEF4MJQ+PJOU4UBOEJOHi4w4UBOEJ 1MBJOi4w 4MJQ)FNNFEi4w 4MJQ%PVCMFi Duct Flanged system angles 4UBOEJOHi4w "MU 4UBOEJOHi4w  #BS3FJOGPSDFE  6 in. long metal cleat or 1/16 in. maximum thickness plastic cleat; 12 in. c-c (minimum 1 per side) (Attach per manufacturer’s instructions) Drive Slip Joint hour rated fire dampers, hour rated fire 2 ⁄ 1 Duct Typical TDC/TDF Joint Typical Sleeve Transverse joints on the top and bottom Transverse flanged systems manufactured Manufactured Nexus, Radiant Ward, by Ductmate, Durodyne, and MEZ T-35m, flange system: TDC by Lockformer Proprietary and TDF by Engle Vertical mount: 80 in. W x 50 in. H, mount: 80 in. W x 50 in. H, Vertical in. H 50 in. W x 80 in. H or 40 in. W x 100 (2032mm x 1270mm, 1270mm x 2032mm, or 1016mm x 2540mm) H Horizontal mount: 144 in. W x 96 in. (3658mm x 2438mm) With the exception of dampers that are specifically of dampers that are With the exception outside the plane of the designed to be mounted (see special installation), the fire wall/floor opening such that the centerline of damper must be installed of the wall or mounted in the plane the blades are sided angle dampers may utilize the two All fire floor. On 1 installation method. Installing damper/sleeve assembly in wall and assembly in wall damper/sleeve Installing floor openings Duct-to-sleeve connections duct-to-sleeve connection, UL Dampers requiring connection. allows a rigid or breakaway any definition, A rigid connection is, by UL’s as a connection that has not been qualified connection. breakaway connections, A number of qualified breakaway for qualifying additional as well as procedures defined in UL Standard connections, are breakaway connections must 555. All qualified breakaway fire be described in the damper manufacturer’s smoke damper installation and combination fire instructions. connections are: Examples of qualified breakaway • • Drive slip joints on the sides R or O damper transitions • Type • • you may use the single side angle installation you may use the single following maximum sizes: method up to the • • Fire Dampers 12 owner, more flexibility forthedesignprofessional, andreduces installationtimeforthecontractor. approved tobeused inthisinnovativedesign.Thisinstallationmethodresults inmore usablespaceforthe gypsum board thatisapproved withdamperpenetrations. Greenheck seriesDFD,FDandFSDdampersare UL Fire ResistanceDesign NumberI503isthefirstULlistedfloor/ceiling designmadefrom steel studsand Method 3:Usinga2hour fire ratedfloor/ceilingdesign(I503) penetrations canthenbeprotected withverticallymountedfire smokedampers. equal tothefire resistive ratingoftheshaft. Duct the remainder ofthebuildingwithconstruction The shaftandroom needtobeseparatefrom Method 2:Terminate theshaftinaroom smoke dampers. then beprotected withverticallymountedfire applicable buildingcodes.Ductpenetrationscan any penetrationsintheshaftbeprotected per passed thefire testinthe horizontalpositionand construction, itisrequired thattheassemblyhas enclosed atthebottomwithfire resistant rated It isimportanttonotethatwhenashaft construction Method 1:Usingafire resistant rated the bottomofshaftwhenitdoesnotextendtotoporbuildingstructure. horizontal openingatthetoporbottomofratedshaft.There are three typicalmethodsusedtoenclose contractors, andinspectorswhenworkingwithashaftthatispenetratedbyduct,protecting the vertical openingsinsuccessivefloors,orfloorsandroof. Oneofthemore difficult tasksfacingdesigners, Fire ratedshaftsenclosethespaceextendingthrough oneormore storiesofabuilding,connecting Horizontal Fire SmokeDamperinaNon-Concrete Barrier meet allrequirements ofUL555and555S. controls. ModelOFSDandGFSDseriesdampers to allow‘through thegrille’accesstoactuatorsand and OFSD).Thisdamperseriesisprimarilydesigned of theplanewall(modelsOFD,ODFD,GFSD combination fire smokedampersforinstallationout Greenheck hastestedandqualifiedfire and What ifaDamperCannotbeInstalledintheWall? Special Installation others) (supplied by 7½ in. M a x. Thermal Blanket Factory Supplied Damper OFSD Floor rest directly onthewallopening. on thebottomsideofdamper. Thedampershall sides ofthedamper. Aretaining angleisnotrequired stud walls.Aretaining angleisusedonthetopand dampers mountedinmasonry, block,metalorwood angle installationfire andcombinationfire smoke Greenheck hastestedandqualified3sidedretaining Single 3SidedRetainingAngle Ductwork Shaft Retaining Angle Rated Wall Floor Combination Fire Smoke Damper Fire Dampers 13 Fire Damper Fire Factory Supplied Thermal Blanket (212°F. available) (212°F. Fire Rated Partition Fire 7½ inch Max. (replaceable) * H OFD/ODFD SERIES OUT-OF-THE-WALL OUT-OF-THE-WALL * Fusible Link standard 165°F. W Grille (supplied by others) Damper Damper Fram Damper Frame LL CC ‘K’ Side K 12 in. = DFD/FD-150X12 14 in. = DFD/FD-150X14 16 in. = DFD/FD-150X16 Overall Sleeve Length Sleeve Damper Location (212°F. available) (212°F.

(replaceable) Curtain Style Fire Dampers Style Fire Curtain Fusible Link standard 165°F. HORIZONTAL MOUNT HORIZONTAL Stainless Steel Spring Closure VERTICAL MOUNT VERTICAL W* H* 3-11/16 inch Integral Sleeve (X series) damper frame as one with the fire X series dampers in the FD and DFD model lines have the sleeve formed is dampers. The frame with integral sleeve the most economical solution for sleeved fire piece, providing constructed of galvanized steel. Close Indicator Switch dampers is the close indicator switch. fire An optional accessory for curtain style confirmation when the damper has closed. remote The switch provides Mounting in the field). interchangeable horizontally (not either vertically or for mounting available are dampers Fire installation. dampers for out-of-the-wall fire also offers Greenheck Fire Dampers 14 that resists “racking”betterthanweldedconstruction. Variable SymmetricBladeDesign(VSB) -aGreenheck Exclusive! improved damperperformance. top andbottomframetomaximizefree area, allowingforlowerpressure drop and On dampersthatare 17in.(432mm)highorless,Greenheck usesalowprofile Maximize Performance-LowProfile Frame by ourTog-L-Loc channel frame.Eachframeisbuiltwithfourseparatepiecesofmaterialandjoined Greenheck multi-bladefire dampersutilizea5in.x1(127mm25mm)hat Frame -Tog-L-Loc ordered. horizontal. Multiplesectionmulti-bladefire dampersmustbemountedinthe orientationinwhichtheywere Single sectionmulti-bladefire dampersmaybemountedverticallyorhorizontallyaslongthebladesstay Mounting Multi-Blade Fire Dampers • • Dampercanbemountedineitherdirection ofairflow • • • Bladesare symmetricabouttheiraxis power consumption. reduces firstcostsfor thebuildingownerandon-goingelectrical reduces thesizeand quantityofactuatorsusedondampers.This using variousbladesizesreduces required actuator torque which Through extensivetesting ofourdampers,wehavedetermined performances Reduces theneedforclosure stripswhichoptimizepressure drop widths are usedinasingledamper Combination of4,5,6,and7in.(102,127,152,178mm) blade ® process. TheTog-L-Loc Quadrant Manual ® Advantage Blade ® process provides amore rigidframe Airflow works Requires HigherTorque actuator against Unbalanced Blade Axle Linkage Frame Actuator Torque Reinforced Corner Airflow works works with actuator Airflow Tog-L-Loc actuator Requires LessTorque against Balanced Blade ® Actuator Torque

Fire Dampers 15 “K” side Fusible Link (replaceable) Horizontal Mount Accessories Stainless Steel Spring Closure Damper Damper Frame L L C A Sleeve Damper Type CO Type CR Type R Type Location Multi-Blade Fire Damper in a Sleeve Multi-Blade Fire * ) H * replaceable ( Fusible Link W Damper Damper Fram Damper Frame LL CC Type R Type O Type C Type K Overall Sleeve Length Sleeve Damper Curtain Fire Damper in a Sleeve Curtain Fire Location Type A Type B/B2 Type C Type Transitions for Multi-Blade Style Fire Dampers for Multi-Blade Style Fire Transitions Transitions for Curtain Style Fire Dampers for Curtain Style Fire Transitions Transitions they can or oval ductwork, square damper is being used in conjunction with round, fire When a rectangular on one or both ends of the sleeve. or oval transitions square round, be supplied in a factory sleeve with can seal ductwork, Greenheck to the duct dimensions. For medium pressure Dampers should be ordered air leakage. the transition and sleeve seams to prevent Multi-Blade Fire Dampers Multi-Blade Fire within the sleeve. specifies the location of the damper The “A” dimension Curtain Style Fire Dampers Fire Curtain Style The “K” of the damper within the sleeve. dimension specifies the location on the top must be installed with the “K” dimension Horizontal dampers (K-side facing up). Factory Sleeve Option Factory or stainless steel, galvanized steel with factory-furnished available sleeves. Sleeves are are dampers Fire and 1 mm) thicknesses, 20 (3 through available in gauges 10 through model, and are depending on the (1219mm). lengths up to 48 in. Fire Dampers 16 Quick Reference Guide SSFD-350 FD-350 FD-310 FD-300 OFD-150 FD-150X series SSFD-150 FD-150 FD-110 FD-100 SSDFD-350 DFD-350 DFD-310 SSDFD-210 SEDFD-210 DFDAF-330 DFDAF-310 DFD-210 ODFD-150 DFD-150X series SSDFD-150 DFD-150 DFD-110 O =Optional X =Standard DFD/FD

Ultrathin Frame X X 1 1/2 in. (38 mm)

Narrowline Frame F/DXSre DFD-210 DFD/FD XSeries X X X X

2 3/16 in. (56 mm) Construction

Integral Sleeve 12, 14, 16 in. X X length (305, 356, 406 mm)

Standard Frame X X X X X X X X X X 3 11/16 in. (94 mm)

5 in. x 1 in. 16 ga.

X X X X X (127 x 25 x 1.5 mm) Hat Channel Frame Material

X X X X X X X X X X X X X X X X X Galvanized Steel

X X X X X 304 Stainless Steel

X 316 Stainless Steel DFDAF-310/330

X X X X X X X X X X X X X X X X X X Curtain Profile Blade

X X Airfoil

X X X 3V Rating Fire

X X X X X X X X X X X X X X X 1 ½ Hour

X X X X X X X X 3 Hour Temperature X X X X X X X X X X X X X X X X X X X X X X X 165°F (74°C) Closure

O O O O O O O O O O O O O O O O O O O O O O O 212°F (100°C)

O O O O O O O O O O O O O O O O O O O O O 286°F (141°C)

O O O O O 350°F (177°C) Accessories

O O O O O O O O O O O O O O O O O O O O O O O Retaining Angles Fire Dampers 17 68 41 ------(1727) (1041) or or ------78 x 34 72 x 68 118 x 34 118 x 34 94 x 41 or 94 x 41 or 2997 x 864) 2997 x 864) (1981 x 964) (2438 x 1041 (2438 x 1041 (1829 x 1727) ------or or 80 x 35 74 x 69 96 x 42 120 x 35 120 x 35 96 x 42 or 96 x 42 or 3048 x 889) 3048 x 889) (2032 x 889) (2438 x 1067 (2438 x 1067 (1880 x 1753) (2438 x 1067) A B/B2 C & CO CR or or 80 x 40 74 x 74 96 x 48 120 x 40 120 x 40 96 x 48 or 96 x 48 or (2438 x 1219 3048 x 1016) (2438 x 1219 3048 x 1016) (2032 x 1016) (1880 x 1880) (2438 x 1219) 34 46 46 46 38 35 46 46 2 in. (864) (965) (889) offset (1168) (1168) (1168) (1168) (1168) R 35 47 47 47 39 36 47 47 1 in. 1 in. (889) (991) (914) offset (1194) (1194) (1194) (1194) (1194) 30 30 30 30 30 30 30 30 0 in. (762) (762) (762) (762) (762) (762) (762) (762) offset 30 41 41 41 34 31 41 41 (762) (864) (787) (1041) (1041) (1041) (1041) (1041) ------Maximum Damper Size Limitations Size Damper Maximum 34 x 30 46 x 41 46 x 41 46 x 41 38 x 34 37 x 31 46 x 41 46 x 41 (864 x 762) (965 x 864) (940 x 787) (1168 x 1041) (1168 x 1041) (1168 x 1041) (1168 x 1041) (1168 x 1041) B/B2 C & CO CR 36 x 31 36 x 31 48 x 42 48 x 42 48 x 42 40 x 35 37 x 32 48 x 42 48 x 40 48 x 40 48 x 42 48 x 42 48 x 42 (914 x 787) (914 x 787) (940 x 813) (1016 x 889) (1219 x 1067) (1219 x 1067) (1219 x 1067) (1219 x 1067) (1219 x 1016) (1219 x 1016) (1219 x 1067) (1219 x 1067) (1219 x 1067) Maximum Single Section Size W x H, in inches (mm) in inches W x H, Maximum Single Section Size (mm)* in inches W x H, Maximum Multi section or A style 36 x 36 36 x 36 48 x 48 48 x 48 48 x 48 40 x 40 37 x 37 48 x 48 48 x 48 48 x 48 48 x 48 48 x 48 48 x 48 (914 x 914) (914 x 914) (940 x 940) (1219 x 1219) (1219 x 1219) (1219 x 1219) (1016 x 1016) (1219 x 1219) (1219 x 1219) (1219 x 1219) (1219 x 1219) (1219 x 1219) No Transitions (121 9 x 1219) V V V H H H or V H or H or V H or (H or V) (H or Mounting or Vertical Horizontal

SSFD-150 Model OFD-150V H or SSFD-350 V FD-150X12 FD-150X14 FD-150X16 FD-150 FD-300FD-310 V V FD-100 V FD-350 FD-110V H or

Static Fire Dampers – Models and Sizes Dampers – Models Static Fire The maximum size opening that can be protected by any manufacturer’s fire damper is specifically stated damper is specifically fire by any manufacturer’s that can be protected size opening The maximum under website (www.ul.com) on UL’s can be found These listings, which UL Listing. in the manufacturer’s section multiple size and the maximum single section both the maximum EMME, provide the category to single section listed, the damper is limited strictly If no multiple section size is size of a damper model. applications. with UL conducted in accordance based on tests are sizes found in the UL Listings The maximum damper not approved the maximum tested damper size is than larger dampers). Filling openings 555 (fire Standard systems Oversized openings in dynamic damper. a static rated fire only requires by UL unless the opening having jurisdiction mullions. As always, the authority into smaller sections using support cannot be divided an installation. or not to approve can decide whether

3 Hour 3 Hour ⁄ 1 2 1 *Multiple section size see page 39. dampers, For round fire Note: Fire Dampers 18 Dynamic Fire Dampers(1½Hour)–ModelsandSizes Maximum DamperSizeLimitations DFD-110 DFD-150 Model Horizontal or Vertical Mounting (H or V) H H H H H H V V V V V V Temperature 212° (100°) 286° (141°) 212° (100°) 286° (141°) 165° (74°) 165° (74°) °F (°C) aiu MaximumSize W xH, ininches (mm) Maximum 3000 or4000 3000 or4000 3000 or4000 3000 or4000 (15.2 or20) (15.2 or20) (15.2 or20) (15.2 or20) Velocity ft/min. (15.2) (15.2) (m/s) 2000 3000 4000 2000 2000 3000 2000 2000 4000 2000 2000 2000 2000 2000 2000 2000 (10) (20) (10) (10) (10) (10) (20) (10) (10) (10) (10) (10) (10) (10) Pressure in. wg (kPa) (1) (1) 4 4 (610 x610or (610 x610or (610 x610or (610 x610or (914 x914) (762 x762) (610 x610) (762 x762) (457 x762) (610 x610) (610 x610) (762 x762) (457 x762) (610 x610) (914 x914) (762 x762) (457 x762) (610 x610) (457 x762) (610 x610) 457 x762) 457 x762) 457 x762) 457 x762) 24 xor 24 xor 24 xor 24 xor Section 36 x 30 x 18 x30 30 x 24 x 18 x30 30 x 24 x 24 x 18 x30 18 x30 24 x 36 x 30 x 18 x30 18 x30 24 x 18 x30 18 x30 24 x Single No Transitionsstyle or A 72 x48, 60x 1524 xor (1219 x914or (1829 x1219) (1829 x1219, Multi section (1219 x914) (457 x1219) (1219 x914) (1219 x914) (1219 x914) (457 x1524) 457 x1219) 3048 x762) 457 x1524) (1219 x914 or 120x30 48 x36or 48 x36or 72 x48 48 x36 18 x48 18 x48 48 x36 48 x36 18 x60 48 x36 18 x60 ------72 x45, 60x58 1524 x1422or (1219 x787or (1219 x787or (1829 x1143) (1829 x1143, (610 x533or (610 x533or (610 x533or (1219 x838) (457 x1143) (1219 x838) (1219 x838) (1219 x838) 457 x1143) 3048 x660) 457 x1422) 457 x1422) or 120x26 (762 x660) (457 x660) (762 x660) (457 x660) (610 x533) (457 x660) (457 x660) (610 x533) 457 x660) 457 x660) 24 x21or 48 x31or 24 x21or 48 x31or 24 x21or 72 x45 30 x26 18 x26 48 x33 18 x45 18 x26 30 x26 18 x45 48 x33 18 x26 18 x26 24 x21 48 x33 18 x26 18 x56 48 x33 18 x56 18 x26 24 x21 /2C&C CR C&CO B/B2 70 x44, 58x55 1473 x1397or (1168 x762or (1778 x1118, (559 x508or (559 x508or (1168 x813) (1168 x813) 2997 x635) 406 x1397) 406 x1397) or 118x25 (711 x635) (406 x635) (406 x635) (559 x508) 406 x635) 22 x20or 46 x30or 22 x20or 28 x25 16 x25 16 x55 46 x32 16 x25 46 x32 16 x55 16 x25 22 x20 ------(1397) (635) (508) (762) (813) (406) (813) (508) (406) (508) 55 25 20 30 32 16 32 20 16 20 offset (762) (762) (610) (762) (762) (457) (762) (610) (457) (610) 0 in. 30 30 24 30 30 18 30 24 18 24 (1499) offset (737) (584) (889) (889) (432) (889) (584) (432) (584) 1 in. 59 29 23 35 35 17 35 23 17 23 R (1473) offset (711) (559) (864) (864) (406) (864) (559) (406) (559) 2 in. 58 28 22 34 34 16 34 22 16 22 Fire Dampers 19 22 28 16 22 22 22 22 28 16 22 28 34 2 in. (559) (711) (406) (559) (559) (559) (711) (406) (559) (559) (711) (864) offset R 23 29 17 23 23 23 29 23 17 23 29 35 1 in. (737) (584) (432) (584) (584) (584) (584) (737) (432) (584) (737) (889) offset 30 24 18 24 24 24 24 30 18 24 30 30 0 in. (610) (762) (457) (610) (610) (610) (610) (762) (457) (610) (762) (762) offset ------20 25 22 16 22 22 22 25 16 22 25 30 (635) (508) (559) (406) (559) (559) (559) (635) (406) (559) (635) (762) 22 x 20 28 x 25 16 x 25 22 x 20 16 x 25 22 x 20 16 x 25 28 x 25 16 x 25 16 x 25 28 x 25 34 x 30 22 x 20 or 22 x 20 or 22 x 20 or 406 x 635) 406 x 635) 406 x 635) (711 x 635) (559 x 508) (406 x 635) (559 x 508) (559 x 508) (711 x 635) (406 x 635) (762 x 635) (864 x 762) (559 x 508 or (559 x 508 or (559 x 508 or B/B2 C & CO CR 24 x 21 30 x 26 24 x 21 18 x 26 36 x 31 36 x 31 18 x 26 36 x 31 36 x 31 18 x 26 24 x 21 30 x 26 18 x 26 36 x 31 18 x 26 18 x 26 24 x 21 30 x 26 18 x 26 18 x 26 30 x 26 36 x 31 24 x 21 or 24 x 21 or 24 x 21 or 24 x 21 or 457 x 660) 457 x 660) 457 x 660) (762 x 660) (610 x 533) (610 x 533) (457 x 660) (914 x 787) (914 x 787) (457 x 660) (914 x 787) (914 x 787) (457 x 660) (610 x 533) (762 x 660) (457 x 660) (914 x 787) (610 x 533) (762 x 660) (457 x 660) (762 x 660) (914 x 787) (610 x 533 or (610 x 533 or (610 x 533 or (610 x 533 or ------36 x 36 36 x 36 36 x 36 36 x 36 (914 x 914) (914 x 914) (914 x 914) (914 x 914) Multi section No Transitions or A style No Transitions Single 30 x 30 24 x 24 24 x 24 18 x 30 18 x 30 24 x 24 18 x 30 18 x 30 30 x 30 18 x 30 24 x 24 30 x 30 18 x 30 36 x 36 24 x 24 24 x 24 24 x 24 18 x 30 30 x 30 24 x 24 30 x 30 36 x 36 Section 24 x 24 or 24 x 24 or 24 x 24 or 457 x 762) 457 x 762) 457 x 762) (762 x 762) (610 x 610) (610 x 610) (457 x 762) (610 x 610) (457 x 762) (762 x 762) (610 x 610) (762 x 762) (457 x 762) (914 x 914) (610 x 610) (610 x 610) (610 x 610) (457 x 762) (762 x 762) (610 x 610) (762 x 762) (914 x 914) (610 x 610 or (610 x 610 or (610 x 610 or Maximum Damper Size Limitations Size Damper Maximum 4 4 4 (1) (1) (1) (kPa) in. wg Pressure (10) (10) (10) (10) (10) (10) (20) (10) (10) (10) (10) (10) (10) (20) (10) 2000 2000 2000 2000 2000 2000 4000 2000 2000 3000 2000 2000 2000 2000 4000 3000 2000 (m/s) (15.2) (15.2) ft/min. Velocity (15.2 or 20) (15.2 or 20) (15.2 or 20) (15.2 or 20) 3000 or 4000 3000 or 4000 3000 or 4000 3000 or 4000 Maximum (mm) in inches H, W x Maximum Size Up to °F (°C) 165° (74°) 165° (74°) 286° (141°) 212° (100°) 286° (141°) 212° (100°) 286° (141°) 212° (100°) Temperature V V V V V V H H H H H H (H or V) (H or Mounting or Vertical Horizontal Dynamic Fire Dampers (1½ Hour) – Models and Sizes – Models (1½ Hour) Dampers Fire Dynamic Model ODFD-150 SSDFD-150 V DFD-150X12 DFD-150X14 DFD-150X16 Fire Dampers 20 Dynamic Fire Dampers(3Hour)–ModelsandSizes Maximum DamperSizeLimitations SF-5 V SSDFD-350 DFD-310 DFD-350 Model Horizontal or Vertical Mounting (H or V) H H H H H H V V V V V V Temperature 286° (141°) 212° (100°) 286° (141°) 212° (100°) 212° (100°) 286° (141°) 165° (74°) 165° (74°) °F (°C) up to Maximum 3000 or4000 3000 or4000 3000 or4000 3000 or4000 (15.2 or20) (15.2 or20) (15.2 or20) (15.2 or20) Velocity ft/min. (15.2) (15.2) (m/s) 2000 3000 2000 2000 4000 2000 2000 2000 2000 2000 2000 4000 2000 2000 2000 3000 2000 (10) (10) (10) (20) (10) (10) (10) (10) (10) (10) (20) (10) (10) (10) (10) Pressure in. wg (kPa) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 (610 x610or (610 x610or (610 x610or (914 x914) (610 x610) (762 x762) (610 x610) (762 x762) (457 x762) (610 x610) (762 x762) (762 x762) (610 x610) (610 x610) (457 x762) (457 x762) (762 x762) (457 x762) (610 x610) (610 x610) (762 x762) (914 x914) 457 x762) 457 x762) 457 x762) 24 xor 24 xor 24 xor Section 36 x 30 x 24 x 24 x 30 x 18 x30 18 x30 24 x 30 x 30 x 24 x 24 x 18 x30 18 x30 18 x30 18 x30 30 x 18 x30 24 x 24 x 30 x 36 x Single No Transitionsstyle or A (1219 x914or (1219 x914or (1219 x1219) (1219 x1219) (457 x12190 Multi section (457 x1219) (1016 x914) (1016 x914) (1016 x914) (1016 x914) 457 x1219) 457 x1219) 48 x36or 48 x36or 48 x 18 x48 40 x36 40 x36 18 x48 18 x48 40 x36 40 x36 18 x48 48 x ------Maximum Size W xH, ininches (mm) (1219 x787or (1219 x787or (1219 x1143) (1219 x1143) (610 x533or (610 x533or (610 x533or (610 x533or (1016 x838) (1016 x914) (1016 x838) (1016 x914) (457 x1143) 457 x1143) 457 x1143) 457 x1143) (610 x533) (762 x660) (610 x533) (762 x660) (457 x660) (457 x660) (457 x660) (457 x660) (762 x660) 457 x660) 457 x660) 457 x660) 24 x21or 24 x21or 48 x31or 48 x31or 24 x21or 24 x21or 48 x45 24 x21 30 x26 24 x21 30 x26 18 x26 18 x26 18 x45 40 x33 40 x33 18 x45 18 x45 18 x26 18 x26 40 x33 18 x26 18 x26 40 x33 18 x26 18 x45 30 x26 48 x45 /2C&C CR C&CO B/B2 (1168 x762or (1168 x1118) (559 x508or (559 x508or 406 x1118) 406 x1118) (559 x508) (559 x508) (711 x635) (406 x635) (965 x813) (406 x635) (965 x813) (711 x635) 406 x635) 22 x20or 46 x30or 22 x20or 22 x20 22 x20 28 x25 16 x25 16 x44 38 x32 16 x44 16 x25 16 x25 38 x32 28 x25 46 x44 ------(1118) (508) (508) (635) (406) (508) (813) (406) (762) (813) (635) (508) 20 20 25 16 32 20 16 30 32 25 20 44 offset (610) (610) (762) (457) (762) (610) (457) (762) (762) (610) (762) (762) 0 in. 24 24 30 18 30 24 18 30 30 30 24 30 (1194) offset (584) (584) (737) (432) (889) (584) (432) (889) (889) (584) (737) 1 in. 23 23 29 17 35 23 17 35 35 23 29 47 R (1168) offset (559) (559) (711) (406) (864) (559) (406) (864) (864) (711) (559) 2 in. 22 22 28 16 34 22 16 34 34 22 28 46 Fire Dampers 21 82 48 30 82 34 34 82 30 82 82 28 28 48 30 30 34 82 2 in. (762) (864) (711) (762) (864) (762) (711) (762) (864) offset (2083) (1219) (2083) (2083) (2083) (1219) (2083) (2083) R 83 31 49 83 35 31 83 83 35 29 83 49 31 29 31 83 35 1 in. (787) (889) (889) (787) (737) (737) (787) (787) (889) offset (2108) (1245) (2108) (2108) (2108) (2108) (1245) (2108) 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 0 in. (762) (762) (762) (762) (762) (762) (762) (762) (762) (762) (762) (762) (762) (762) (762) (762) (762) offset C & O 92 x 48 30 x 48 34 x 34 30 x 46 34 x 34 46 x 28 62 x 48 30 x 46 28 x 46 30 x 48 34 x 34 C: 92 x 82 C: C: 92 x 82 C: C: 92 x 82 C: C: 92 x 82 C: C: 92 x 82 C: C: 92 x 82 C: O: 92 x 80 O: O: 92 x 80 O: O: 92 x 80 O: O: 92 x 80 O: O: 92 x 80 O: O: 92 x 80 O: (864 x 864) (864 x 864) (864 x 864) (762 x 1219) (762 x 1219) (711 x 1168) (1168 x 711) (762 x 1168) (762 x 1219) (2337 x 1219) (2337 x 2083) (2337 x 2032) (2337 x 2083) (2337 x 2032) (2337 x 2083) (2337 x 2032) (2337 x 2083) (2337 x 2032) (2337 x 2083) (2337 x 2032) (1575 x 1219) (2337 x 2083) (2337 x 2032) ------96 x 50 32 x 48 32 x 48 48 x 30 64 x 50 144 x 96 144 x 96 120 x 96 128 x 96 128 x 100 128 x 100 (813 x 1219) (813 x 1219) (1219 x 762) (3251 x 2540) (2438 x 1219) (3658 x 2438) (3658 x 2438) (3251 x 2540) (3048 x 2438) (1626 x 1270) (3251 x 2438) No Transitions 32 x 50 32 x 50 32 x 50 32 x 50 32 x 50 36 x 36 32 x 50 36 x 36 30 x 48 30 x 48 30 x 48 24 x 30 32 x 50 36 x 36 32 x 50 (914 x 914) (914 x 914) (610 x 762) (914 x 914) 762 x 1219) (813 x 1219) (813 x 1219) (813 x 1219) (813 x 1219) (762 x 1219) (762 x 1219) (762 x 1219) (813 x 1270) (813 x 1270) (813 x 1270) (813 x 1270) (813 x 914 or 32 x 36 or 30 x 48 32 x 36 or 30 x 48 Single Section Size Multi section (813 x 914 or 762 x 1219) Maximum Damper Size Limitations Size Damper Maximum 8 4 4 8 4 4 10 10 (2) (1) (1) (2) (1) (1) (2.5) (2.5) (kPa) in. wg Pressure (20) (20) (10) (10) (20) (10) (10) 4000 4000 2000 2000 4000 2000 2000 (m/s) ft/min. Velocity Maximum (mm) in inches V Installation, Maximum Sizes H or Up to Up to Up to Up to Up to Up to Up to Up to Up to Up to Up to Up to Up to Up to Up to Up to Up to °F (°C) 286° (141°) 350° (177°) 350° (177°) 212° (100°) 286° (141°) 350° (177°) 350° (177°) 286° (141°) 350° (177°) 350° (177°) 350° (177°) 212° (100°) 350° (177°) 286° (141°) 350° (177°) 350° (177°) 286° (141°) Temperature V V V H H H H or V H or H or V H or H or V H or (H or V) (H or Mounting or Vertical or Vertical Horizontal DFD-210

DFDAF-310 DFDAF-330 SEDFD-210V H or Model

Multi-Blade Dynamic Fire Dampers – Models and Sizes and – Models Dampers Fire Dynamic Multi-Blade

3 Hour 3 1½ Hour 1½ Smoke Dampers 22 • • smoke damper: determine thefollowingratingswhenapplyingaUL Standard 555S“Smoke Dampers”.Itisnecessaryto UL Classifiedsmokedampersare testedtoUL intent ofthedesign. detector orasmokecontrol systemtoaccomplishthe pneumatic actuatorsandare controlled byasmoke Smoke dampersare motorizedwithelectricor also usedinairhandlingequipmentforisolation. into otherareas ofthebuilding.Smokedampersare and prevent thespread ofsmokefrom thefire zone differences. Higherpressures surround thefire zone system and/ordedicatedfanstocreate pressure control thespread ofsmokeusingthebuilding’s HVAC an “Engineered SmokeControl System” designedto smoke barrier. Theyalsomaybeappliedaspartof of smokethrough aductorventilationopeningin where theysimplyclosetominimizethepassage may beappliedina“PassiveSmokeControl System” Smoke dampershavetwogeneralapplications.They openings insmokebarriers. the passageofsmokethrough ductsorairtransfer Smoke dampersare required tocloseandresist Application Smoke Dampers •

(10.2 m/s). a minimumof4in.wg(1kPa)and2000ft/min they willbeexposedtointheirapplication,with selected tooperateatthepressures andvelocities velocity ofairflow(ft/min).Dampersshouldbe differential (in.wg)andtocloseagainsta specific for operationtoopenagainstaspecificpressure smoke damperwithitsinstalledactuatortoberated to provide thesafestlevelofprotection. Leakage ClassII.Iisrecommended Code (IBC),section717.3.2requires aminimumof Building III (highestleakage).The2015International Elevated Temperature: Velocity andPressure: Leakage: level ofsafety. Most often350°F(177°C)isselectedforthehighest temperature atwhichtheleakagetestisconducted. must beabletooperatethedamperand 177°C) isthetemperature atwhichtheactuator ClassI(lowestleakage),II,or UL555Srequires each 250°For350°F(121°C Supply Supply Air Typical EngineeredSmokeControlSystem Smoke iscontainedtothefirezonebyhigher Typical SmokeDamper Damper positionedtocreatenegativepressurization Damper positionedtocreatepositivepressurization pressures inadjacentzones Typical FireSmokeZone Typical Non-SmokeZone Exhaust Return/ Fan Return/Exhaust Air Smoke Dampers 23 2 Maximum Leakage in cmh/m 2 @ 4 in. wg @ 8 in. wg @ 1 kPa @ 2 kPa Maximum Leakage in cfm/ft Class Class I 8 11 146 201 Class II 20 28 366 512 Class III 80 112 1463 2048 Leakage min (5 m/s) increments from the minimum airflow and in 2 in. wg (0.5 kPa) increments from the from the minimum airflow and in 2 in. wg (0.5 kPa) increments from min (5 m/s) increments UL Standards for Testing and Rating of Smoke Dampers of Smoke Rating and Testing for UL Standards Leakage Test (UL 555S) Leakage Test maximum height, maximum damper sizes of each model being tested (minimum width by At least three been subjected to width by maximum height) that have previously width by minimum height, and maximum The minimum airflow must be tested for leakage. Degradation Test and the Temperature both the Cycle Test 4 in. wg. (1 kPa). Ratings shall be set ratings of dampers shall be 2000 ft/min (10.2 m/s) and and pressure in 1000 ft/ damper three leakage rating is based on the worst-case performance of the damper’s A minimum pressure. sizes tested. Temperature Degradation Test (UL 555S) Test Degradation Temperature (described above) is Test been subjected to the Operational previously A damper with an actuator that has multiples of 100°F [38°C]) for of 250°F (121°C) minimum (or higher in exposed to an elevated temperature the damper temperature, and while still at the elevated exposure a period of 30 minutes. After 30 minutes times. Time of operation cannot exceed 75 and closed three actuator must operate the damper open operations. seconds for any of the open or closed Salt Spray Exposure Test (UL 555 & UL 555S) Test Salt Spray Exposure this exposure, for a period of 120 hours. After is exposed to salt spray in a test chamber A damper sample the damper of this test is to make sure The purpose close (and latch if a latch is provided). the damper must operates after build-up. (UL 555S) Operational Test and actuator assembly must demonstrate the ability to operate During an operation test a smoke damper times under assembly must cycle three conditions for which it is rated. The under the velocity and pressure (250°F or 350°F) for 15 after being exposed to the rated temperature ambient conditions and then one time minutes. Cycle Test (UL 555S) Cycle Test 20,000 times. Smoke dampers cycled open and closed (by their actuator) dampers are UL classified smoke open and closed 100,000 damper must be cycled use as a volume control also intended for that are below) and ensure prior to all other tests (described performed tests are cycles. These cycling repositioning operations. after repeated function reliably that the damper will UL (Underwriters Laboratories) Classified smoke dampers are tested to UL Standard 555S “Smoke Dampers”. Dampers”. 555S “Smoke tested to UL Standard dampers are Classified smoke Laboratories) UL (Underwriters that UL 555S requirements some of the test label. Below are UL with an appropriate always supplied They are to. subject dampers are classified Smoke Dampers 24 instructions tosleeveorsideplate. rivets. Attachmentsmustbemadeperinstallation screws, boltsandnuts,tackorspotweld,pop Attach thedampertoductusingsheetmetal Attaching DampertotheDuct before anyductinletsoroutlets. (610mm)oftheratedsmokebarrierand 24 in. The centerlineofthedamperbladesmustbewithin Location ofDamper published bythecompanythatmanufactured thedampers. methods byconductingadditionaltests.Dampersmustbeinstalledinaccordance withinstructions requirements maydiffer betweendampermanufacturers asamanufacturerinstallation mayqualifyalternate is includedwitheachshipmentofULfire, smoke,orcombinationfire smokedampers.Installation to maintainthevalidityofdamper’s ULlisting.Acopyoftheappropriate installationinstruction(s) procedures toproperly installeachspecificmodelofdamper. Theseinstructionsmustbefollowed to publishspecificdamperinstallationinstructionsdetailingtherequired installationmethodsand UL (UnderwritersLaboratories)requires allfire, smoke,andcombinationfire smokedampermanufacturers manufacturer’s installationinstructionsandthedamper’s listing. BuildingCode)requiresThe IBC(International lifesafetydamperstobeinstalledinaccordance withthe Installation Outlet Duct Ductwork maximum 24 in. Damper Sealant UL 555S. combination fire smoke dampers isrequired by Factory installationofactuatorsonsmokeand Actuator ductwork isoptionalforClassIIorIIIdampers. for ClassIleakage.Sealingthedamperframeand This prevents unwantedairleakage.Thisisrequired damper andductworkusingULapproved sealant. After installingthedamper, sealthejointbetween Ductwork Sealing theDamperFrameto Barrier Smoke Smoke Dampers 25

® Single Flange Reverse (opposite actuator) Tog-L-Loc Reinforced CornerReinforced Single Flange

(actuator side) ® Construction Blade Jamb Seal Frame Frame in duct) Channel (for inserting - can Axle Advantage Blade Seal process provides a more rigid frame that resists “racking” “racking” that resists rigid frame a more provides process Bearing ® ® Linkage - allows damper to be insert mounted into be insert mounted or directly mounted to the wall or mating be insert mounted or directly surfaces such as a plenum wall. Single flange or single reverse flange (SMD-401EF only) Single flange or single reverse Channel (standard) an opening or duct • • better than welded construction. process. The Tog-L-Loc process. Maximize Performance - Low Profile Frame Maximize Performance - Low Profile uses a low profile 17 in. (432mm) high or less, Greenheck On dampers that are and drop allowing for lower pressure area, top and bottom frame to maximize free damper performance. increased Frame Options The frame options available are: Greenheck smoke dampers utilize a 5 in. x 1 in. (127mm x 25mm) hat channel frame. smoke dampers utilize a 5 in. x 1 in. (127mm Greenheck pieces of material and joined by our Tog-L-Loc Each frame is built with four separate Frame - Tog-L-Loc Smoke Dampers 26 •316SS-UsedonSESMDandSEFSDseries •304SS-Standard Bearings adjustment. engineered toaccuratelycontrol eachandeverybladewithoutneedfor to prevent additionalpressure drop andunwantednoise.Thelinkageis Greenheck smokedampershavebladelinkagesconcealedintheframe Linkage Construction • • Seals are usedfor lowleakageapplications. Seals • •Damperisbi-directional airflowrated • • •Bladesare symmetricabouttheiraxis Variable SymmetricBladeDesign(VSB)-aGreenheck Exclusive! Blades Steel AirfoilBlade Aluminum Airfoil edges. compression typematerialtohelpreduce leakagealongtheblade power consumption. reduces firstcostsforthebuildingownerandon-goingelectrical reduces thesizeandquantityofactuatorsusedondampers.This using variousbladesizesreduces required actuatortorque which Through extensivetestingofourdampers,wehavedetermined drop performances Reduces theneedforclosure stripswhichoptimizepressure widths are used in asingledamper Combination of4,5,6,and7in.(102,127,152,178mm)blade Jamb seals Blade seals 3V Blade Blade : Jambsealsare constructedoffllexible304SS : Silicone • Highvelocityandpressure applications • Thisbladedesignresults inlowerresistance toairflowandincreased strength • Constructedofheavygaugeextrudedaluminum • Highvelocityandpressure applications • Thisbladedesignresults inlowerresistance toairflowandincreased strength • Constructedofdouble-skingalvanizedsteel • Lowtomediumvelocityandpressure applications • Three V-type grooves runningthefulllengthofbladetoincrease strength • Fabricatedfrom asinglethicknessgalvanizedsteelorstainless Airflow works Requires HigherTorque actuator against Unbalanced Blade Linkage Actuator Torque Airflow works works with actuator Airflow actuator Requires LessTorque against Balanced Blade Jamb Seal Actuator Torque Smoke Dampers 27 Actuators Figure 3 Figure Greenheck also offers also offers Greenheck pneumatic actuator options. Control pressure start point and operating pressure Control field adjustable span are Modulating (damper position determined by Modulating (damper position determined signal) modulating pressure • Open or close • Internal or external to the sleeve/ductwork • • Solenoid valve • 20 or 25 psi or position (damper position is open • Two closed) • Mounting Location only) Signal (for modulating Control Accessories Pneumatic Actuator Checklist Pneumatic 3 See Figure Air Pressure Operation Fail Direction Figure 2 Figure Figure 1 Figure installation external or internal to the sleeve/ductwork. Greenheck offers a wide variety of electric actuators for offers Greenheck Modulating (damper position determined by Modulating (damper position determined signal) modulating control • Auxiliary switches (end switches built into actuator) • Auxiliary switches (end switches built • Transformer • 0/2-10 VDC, 4-20 mAdc • 1 or 7 (specify one for specific application) • Open or close • Internal or external to the sleeve/ductwork • 24, 120, or 240 VAC • 24, 120, or 240 in Hz • Frequency or closed) position (damper position is open • Two • Control Signal (for modulating only) Control NEMA Enclosure Accessories Fail Direction Mounting Location Power Supply Operation Electric Actuator Checklist Electric Actuator 1 and 2 See Figures A variety of electric and pneumatic actuators are available for all damper models. Each actuator-damper Each actuator-damper all damper models. available for are actuators of electric and pneumatic A variety ratings as with pressures, velocities and specific maximum to operate up to is UL Classified combination be mounted internally kPa). Actuators can and 8 in. wg (2 ft/min. (20 m/s) high as 4000 externally. or as an assembly. its installed actuator must be tested UL 555S testing, the damper and Under UL 555 and are Modulating actuators furnishedActuators must be factory-installed by the damper manufacturer. volume applications. available for variable Smoke Dampers 28 Class Ileakageratingand350°F(177ºC)temperature rating. the actuatormountedonsides.TheSMD-301Vand FSD-311Vhavea the toporbottomofdamperwhenobstructionsprevent installationwith Vertical on bladedampersallowtheinstallertomountactuatorexternally Vertical Blade space. or PRV), whichoccupymuchoftheavailableinternal sizes withoptions(suchastheTOR,RRL/OCI,OCI installation.There areexternal limitationsonsmall space constraintsprevent themore desirable airstream) toaccommodate installationswhere (inthe Most actuatorscanbemountedinternally Factory Mounting-Internal covering theslotinsideofduct. installed inaslottedductsectionwiththesideplate be provided usingasideplate.Thesedampersare installationoftheactuatorcan installation. External Smoke dampersdonotrequire sleevesforproper onaSideplate Factory Mounting-External option forcombinationfire smokedampers. standard andrecommended actuatormounting installed ontheoutsideofsleeve.Thisis factory, completewithasleeveandtheactuator bythe choice isforthedampertobefurnished sleeve forproper installation,themostpractical As allcombinationfire smokedampersrequire a onaSleeve Factory Mounting-External servicing. be avoidedifpossible,asitincreases pressure drop andthedifficulty ofactuatorinspecting,testing,and actuatormounting(where Internal theactuatorismountedinairstream)sideplate) orinternal. should (onadampersleeveor Actuators mustbefactorymounted.Factorymountingoptionsmayexternal Actuator Mounting actuator externally mounted. actuator externally Damper withsideplate Damper mountedinsleevewith Damper mountedinsleevewith actuator internally mounted. actuator internally actuator externally mounted. actuator externally Smoke Dampers

29

Greenheck Test Switch (GTS) Switch Test Greenheck

Transformer

Open or Close Indicator (OCI) Indicator Close or Open Momentary Switches Momentary

OOOO OOOO OOOO Smoke Detector Smoke

OOOOO OOOOO Retaining Angles Retaining

OOOOOO OOOOOO OOOOOO OOOOOO OOOOOO OOOOOO OOOOOO

Class III Class

Class II Class Class I Class

Quick Reference Guide Reference Quick

Aluminum Airfoil Aluminum Steel Airfoil Airfoil Steel

SMD-301V HSD-401

3V

Steel Hat Channel Hat Steel

8 x 2 in. x 12 ga. Galvanized Galvanized ga. 12 x in. 2 x 8

Aluminum 316 Stainless Steel Stainless 316

Frame Blade Profile Leakage Class Accessories

304 Stainless Steel Stainless 304

Steel Hat Channel Hat Steel 5 x 1 in. x 16 ga. Galvanized Galvanized ga. 16 x in. 1 x 5 SMD-201 X = Standard O = Optional HSD-401 X X X O O O O O SMD-401EFSMD-401M X X X X X X O O O O O O SMD-401 X X X SMD-302M X X X SMD-302 X X X O SMD-301V X X X O O SMD-301M X X X O O O O O O SSSMD-201SESMD-201SMD-301 X X X X X X X X X SMD-203 X X X SMD-201MSMD-202 X X X X X X O O O SMD-201 X X X O O Smoke Dampers 30 Maximum DamperSizeLimitations SSSMD-201 SESMD-201 M-0E I SMD-401EF M-0MI SMD-401M M-0MI SMD-201M SMD-302M SMD-301M M-0VI- -- -- I SMD-301V M-0 I SMD-401 SMD-302 SMD-301 SMD-203 SMD-202 SMD-201 S-0 I HSD-401 Model Leakage Class III II II II I I I I (203 X152) (152 x159) (203 x203) (203 x203) (203 x152) (203 x152) (203 x152) (203 x152) (203 x152) iiu aiu iiu aiu Maximum Maximum Minimum Maximum Minimum 6 x6¼ 8 x 8 x 8 x6 8 x6 8 x6 8 x6 8 x6 8 x6 oiotlVria oiotlVertical Horizontal Vertical Horizontal (813 x1270or (1524 x1524) (1219 x1524) (1219 x1219) (1219 x914) (914 x1219) (813 x1270) (914 x1219) (813 x1270) 914 x1219) (914 x914) (610 x762) (914 x914) 32 x50or 24 X30 60 x 36 x 48 x36 36 x48 48 x60 48 x 32 x50 36 x 36 x48 36 x48 32 x50 igeScinMultisection Single Section ieLmttos-WxH nice m)Maximum Size Limitations- W xH, ininches (mm) (152x159) (203 x203) (203 x203) (203 x152) (203 x152) (203 x152) (203 x152) (203 x152) (152 x203) (203 x152) 6 x6¼ 8 x 8 x 8 x6 8 x6 8 x6 8 x6 8 x6 6 x8 8 x6 (813 x1270or (1524 x1524) (1219 x1524) (1219 x1219) (914 x1219) (1219 x914) (813 x1270) (1270 x813) (914 x1219) (813 x1270) 914x1219) (914 x914) (610 x762) (914 x914) 32 x50or 60 x 36 x 48 x36 48 x60 36 x48 48 x 32 x50 24 x30 36 x 36 x48 50 x32 36 x48 32 x50 (2235x1829) (6096 x3048) (4877 x3048) (3658 x2438) (4877 x3048) (4877 x2540) (2235 x1219) (4877 x1829) (3658 x1219) (3251 x2540) (4877 x1270) 3251 x2540) (4877 x1270 (3658 x2540 3251 x2540) (4877 x1270 144 x100or (914 x1829) (914 x1829) 192 x72or 192 x72or 240 x120 192 x120 192 x120 192 x100 128 x100 128 x100 128 x100 or 7315x 144 x96 288 x50 192 x72 144 x48 192 x50 36 x72 88 x72 88 x48 36 x72 1270) or or ------(2235x1829) (6096 x3048) (4877 x3048) (3658 x2438) (4877 x3048) (2235 x1219) (4877 x1829) (3251 x2540) (3658 x1219) (3251 x2540) (4877 x1270) 3251 x2540) (4877 x1270 7315 x1270) (3658 x2540 3251 x2540) (4877 x1270 144 x100or (914 x1829) (914 x1829) (2540 x813) 192 x72or 192 x72or 240 x120 192 x120 192 x120 192 x100 128 x100 128 x100 128 x100 144 x96 288 x50 100 x32 192 x72 144 x48 192 x50 36 x72 88 x48 36 x72 88 x72 or or or Temperature 250° (121°) 250° (121°) 250° (121°) 250° (121°) 350° (177°) 250° (121°) 350° (177°) 350° (177°) 350° (177°) 250° (121°) Ratings °F (°C) Velocity ft/min. (15.2) (10.2) (10.2) (15.2) (10.2) (20.3) (10.2) (10.2) (10.2) (10.2) (15.2) (10.2) (10.2) (20.3) (15.2) (m/s) 3000 2000 2000 3000 4000 2000 2000 2000 2000 2000 3000 2000 2000 4000 3000 Pressure in. wg (kPa) (1.5) (1.5) (1.5) (1.5) (1.5) (1) (1) (1) (1) (1) (1) (1) (1) (1) (2) (1) (1) (2) 6 4 4 6 4 4 6 4 4 4 4 6 6 4 8 4 4 8 Fire Smoke Dampers 31 Typical Combination Fire Smoke Damper Combination Fire Typical Combination Fire Smoke Dampers Smoke Fire Combination or 3 hour 2 ⁄ 1 Minimum of 4 in. wg and 2000 fpm Velocity and Pressure: and Pressure: Velocity • Fire Endurance Test and Hose Stream Test (UL555) Test and Hose Stream Endurance Test • Fire (UL555) Test • Dynamic Closure (UL 555 and UL 555S) Test • Salt Spray Exposure (UL 555 and UL 555S) • Cycling Test (UL 555S) • Operational Test (UL 555S) Degradation Test • Temperature (UL 555S) • Leakage Test • Hourly Fire Rating: • Hourly Fire 1 UL Standards for Testing and Rating Combination Fire Smoke Smoke Combination Fire and Rating for Testing UL Standards Dampers 555 tested to UL Standard smoke dampers are combination fire UL (Underwriters Laboratories) Classified UL label. always supplied with an appropriate are Dampers” and UL 555S “Smoke Dampers”. They “Fire subjected to. that UL 555 and UL 555S classified dampers are some of the test requirements Below are Damper and the Smoke Damper section, page 6 and to the Fire information on these tests, refer For more 21, respectively. Application the damper performs smoke fire A combination and a smoke damper. damper fire function of both a designs often combine fire Building layouts and partitions and barriers requiring and smoke rated and smoke damper both a fire the installation of smoke location. Combination fire damper at the same 555 qualified under UL Standard dampers must be 555S as a UL Standard damper AND under as a fire listed in the fire The considerations smoke damper. damper sections apply to the damper and smoke of combination fire selection and application smoke dampers. ratings when It is necessary to determine the following smoke damper: applying an UL combination fire • Leakage: 250° or 350°F • Elevated Temperature: • Class I, II, or III Fire Smoke Dampers 32 (see SpecialInstallationsinthefire dampersection). using theI503horizontalnon-concrete application must beinstalledinconcrete floorsexceptwhen masonry, block,orstudwalls.Horizontalmount Vertical mountdampersmustbeinstalledin required mountingorientation. damper issuppliedwithalabelcallingoutthe proper fire protection. Everycombinationfire smoke in thecorrect orientationtoensure lifesafetyand mounting applications.Dampersneedtobeinstalled pass separatetestsforverticalmountandhorizontal Combination fire smokedampersare required to Mounting Orientation installed inaccordance withinstructionspublishedbythecompanythatmanufactured thedampers. a manufacturer installationmethodsbyconductingadditionaltests.Dampersmustbe mayqualifyalternate or combinationfire smokedampers.Installationrequirements maydiffer betweendampermanufacturers as listing. Acopyoftheappropriate installationinstruction(s)isincludedwitheachshipmentofULfire, smoke, specific modelofdamper. Theseinstructionsmustbefollowedtomaintainthevalidityofdamper’s UL installation instructionsdetailingtherequired installationmethodsandprocedures toproperly installeach UL requires allfire, smoke,andcombinationfire smokedampermanufacturers topublishspecificdamper manufacturer’s installationinstructionsandthedamper’s listing. BuildingCode)requiresThe IBC(International lifesafetydamperstobeinstalledinaccordance withthe Installation •Actuator •Sealingthedamperframetoductwork forthefollowingguidelines: (page 22) Refer tothesmokedamperinstallationsection •Duct-to-sleeveconnection • •Sleeverequirements • forthefollowingguidelines: (pages 7-9) Refer tothefire damperinstallationsection floor openings Installing damper/sleeveassemblyinwalland and wallorflooropenings Clearance required betweendampersleeves Fire Smoke Dampers 33 GFSD Series Configuration #2 FSD-311V Special Installations Special OFSD Series Configuration #3 Configuration #1 : Used in a fire rated ceiling that rated ceiling : Used in a fire : Used in a fire rated ceiling that : Used in a fire : Used where the fire rated ceiling the fire : Used where Configuration #3 Configuration #2 Configuration #1 is also the finished ceiling. The damper is installed is also the finished ceiling. The damper device with access to the actuator and closure must be above the finished ceiling. Clearance grille for maintained between the damper and operation. proper is also the finished ceiling. The damper is installed is also the finished and closure is access to the actuator so there diffuser. register,or the grille, device through is above the finished ceiling. GFSD Series: 3V blade style. A separate compartment on the side of the damper houses the actuator for installations with limited depth. • • • OFSD Series: 3V or airfoil blade style. • • Vertical Blade Vertical blade dampers (shown) allow the installer to Vertical mount the actuator externally on the top or bottom installation of the damper when obstructions prevent with the actuator mounted on the sides. The FSD-311V has a Class I leakage rating and 350°F rating. (177ºC) temperature Out of Wall Fire Smoke Dampers Fire Out of Wall has tested and qualified combination fire Greenheck dampers are smoke dampers for installations where rated wall. This installed out of the plane of the fire of UL 555 damper series meets all the requirements and floors and UL 555S for use in walls, partitions, rating less than 3 hours. resistance with a fire easy access damper series allows The Out of Wall device, and closure the grille to the damper, through The damper/sleeve assembly is wrapped the actuator. in a thermal blanket. Corridor Ceiling Fire Smoke Damper Smoke Ceiling Fire Corridor to list classification a separate UL has established UL 555 and 555S dampers for this application. tests in actual corridor qualification plus additional by UL to classify as a required are ceiling construction smoke damper. fire corridor combination installation different available in three They are configurations: Fire Smoke Dampers 34 frame thatresists “racking”betterthanweldedconstruction. Blades increased damperperformance. and bottomframetomaximizefree area whichallowsforlowerpressure drop and On dampersthatare 17in.(432mm)highorless,Greenheck usesalowprofile top Maximize Performance-LowProfile Frame joined byourTog-L-Loc hat channelframe.Eachframeisbuiltwithfourseparatepiecesofmaterialand Greenheck combinationfire smokedampersutilizea5in.x1(127mm25mm) Frame -Tog-L-Loc Construction Steel AirfoilBlade 3V Blade Linkage Bearing • Highvelocityandpressure applications • Thisbladedesignresults inlowerresistance toairflowandincreased strength • Constructedofdouble-skin galvanizedsteel • Lowtomediumvelocityandpressure applications • Three V-type grooves runningthefulllengthofbladetoincrease strength • Fabricatedfrom asinglethicknessgalvanizedsteelorstainless Seal Blade Axle ® ® process. TheTog-L-Loc Advantage ® process provides amore rigid Frame Jamb Seal Blade Reinforced Corner Tog-L-Loc ®

Fire Smoke Dampers 35 Torque Actuator Jamb Seal Balanced Blade against Requires Less Torque Less Requires actuator Airflow actuator works with Airflow works Torque Actuator Construction Linkage Unbalanced Blade against actuator Requires Higher Torque Higher Requires Airflow works have blade linkages dampers : Silicone : Jamb seals are constructed of flexible 304SS compression constructed of flexible 304SS compression : Jamb seals are Blade seals Jamb seals Combination of 4, 5, 6, and 7 in. (102, 127, 152, and 178mm) blade 5, 6, and 7 in. (102, 127, 152, and 178mm) Combination of 4, damper used in a single widths are which optimize pressure strips for closure Reduces the need performances drop have determined extensive testing of our dampers, we Through which torque actuator required sizes reduces using various blade used on dampers. This the size and quantity of actuators reduces owner and on-going electrical first costs for the building reduces power consumption. type material to help reduce leakage along the blade edges. type material to help reduce • concealed in the frame to prevent additional pressure drop and unwanted drop additional pressure concealed in the frame to prevent each and every to accurately control noise. The linkage is engineered blade without need for adjustment. • 304SS - Standard • 316SS - Used on SEFSD series Bearings Linkage smoke combination fire Greenheck’s Seals used for low leakage applications. Seals are • Variable Symmetric Blade Design (VSB) - a Greenheck Exclusive! (VSB) - a Greenheck Blade Design Symmetric Variable about their axis symmetric • Blades are • • airflow rated is bi-directional • Damper • Fire Smoke Dampers 36 which occupy much of the available internal space. which occupymuchoftheavailableinternal options (suchastheRRL/OCI,OCI,PRV orTOR), installation. There are limitationsonsmallsizeswith space constraintsprevent themore desirableexternal airstream) toaccommodate thoseinstallationswhere (inthe Most actuatorscanbemountedinternally Factory Mounting-Internal option forcombinationfire smokedampers. standard andrecommended actuatormounting installed ontheoutsideofsleeve.Thisis factory completewithasleeveandtheactuator bythe choice isforthedampertobefurnished sleeve forproper installation,themostpractical As allcombinationfire smokedampersrequire a Sleeve Factory Mounting-Externalona and servicing. should beavoidedifpossible,asitincreases pressure drop andthedifficulty ofactuatorinspecting,testing, actuatormounting(where theactuatorismountedinairstream) Internal sideplate, ormountedinternal. onadampersleeveor Actuators mustbefactorymounted.Factorymountingoptionsmayexternal Actuator Mounting See SmokeDampersectionformore information. available forvariablevolumeapplications. factory-installed bythedampermanufacturer.Actuators mustbefurnished Modulatingactuatorsare Under UL555and555Stesting,thedamperitsinstalledactuatormustbetestedasanassembly. orexternally.high as4000ft/min.(20m/s)and8in.wg(2kPa).Actuatorscanbemountedinternally combination isULClassifiedtooperateupspecificmaximumvelocitiesandpressures, withratingsas A varietyofelectricandpneumaticactuatorsare availableforalldampermodels.Eachactuator-damper Actuators Damper mountedinsleevewith Damper mountedinsleevewith actuator externally mounted. actuator externally actuator internally mounted. actuator internally Fire Smoke Dampers 37 PRV RRL TOR EP Switch RRL/OCI Closure Devices Closure - The RRL/OCI combines the The TOR option provides damper closure, usually damper closure, The TOR option provides -

- This is also known as a three-way solenoid valve and is - This is also known as a three-way The PRV is a heat responsive device that activates is a heat responsive The PRV - The RRL replaces the fusible link with a bi-metal heat responsive with a bi-metal heat responsive the fusible link - The RRL replaces resettable link (RRL) and the open close indicator (OCI) into one device. RRL/OCI option link (RRL) and the open close indicator (OCI) resettable 212ºF (100ºC), 250ºF (121ºC) and ratings of 165ºF (74ºC), is available with temperature 350ºF (177ºC). when temperatures in excess of 165°F (74°C) or 212°F (100°C) are detected. When the in excess of 165°F (74°C) or 212°F (100°C) are when temperatures No electrical to close the damper. the actuator is exhausted fusible link melts, air from in must be installed at the factory and cannot be added The PRV connection is required. an electrical a RRL with EP switch which requires the field. An alternative is to the PRV connection. Electro-Pneumatic Switch (EP) Electro-Pneumatic Temperature Override Control (TOR) Override Control Temperature Pneumatic Relief Valve (PRV) - (PRV) Pneumatic Relief Valve Resettable Link with Open Closed Indicator (RRL/OCI) Resettable Link with Open Closed Indicator Resettable Link (RRL) UL 555 requires closure devices to have a minimum temperature rating of 160°F (71°C). The maximum of 160°F (71°C). The rating a minimum temperature devices to have closure UL 555 requires dampers. for dynamic rated and 350°F (177°C) rated dampers (100°C) for static rating is 212°F temperature normal 50°F (10°C) above the shall be approximately states “The operating temperature In addition, the IBC within the duct system”. temperature device that is easily reset from outside the duct (on units with externally outside the duct (on mounted from reset device that is easily spring return devices cut power to the damper heat responsive actuators). Bi-metal of the closure controlled This ensures setpoint is reached. temperature actuator when the sudden instantaneous from of duct damage resulting eliminating the possibility damper, (74ºC), 212ºF ratings of 165ºF available with temperature are RRL options type closures. and 350ºF (177ºC). (100ºC), 250ºF (121ºC) at 165°F (74°C), with the ability to override this closure (reopen damper) so the duct (reopen at 165°F (74°C), with the ability to override this closure system functions as long as the system can accomplish its intended smoke control device at the damper does not exceed the secondary heat responsive temperature setting, usually 350°F (177°C). used to electronically open and close a pneumatic actuated damper. It is wired in series It is wired actuated damper. open and close a pneumatic used to electronically smoke damper to initiate closure with a normally closed when used with a fire when used on a smoke damper to initiate closure It can also be at elevated temperatures. system. in a smoke control required Fire Smoke Dampers 38 3 2 1 Quick Reference Guide

FD32XX X OFSD-312 FD31XXXXX X X X X OFSD-311 FD22XXXXXOOOOOXOO O X O O O O O X X X X X OFSD-212 FD21XXXXXOOOOOXOOO O O X O O O O O X X X X X OFSD-211 FD22XXXXXOOOOXOO O X O O O O X X X X X GFSD-212 FD21XXXXXOOOOXOOO O O X O O O O X X X X X GFSD-211 S-3 X O O O O O X X X X X FSD-331 S-1VXXXXXOOOXOOOO O O O X O O O X X X X X FSD-311V S-1MXXXXXOOXO X O O X X X X X FSD-312M S-1MXXXXXOOXOOOOOOO O O O O O O X O O X X X X X FSD-311M S-1 O X X X X X FSD-312 S-1 X O O O O O X X X X X FSD-311 For usewithpneumaticactuators. Includes OpenorClosedIndicator;EPswitchrequired ifpneumaticactuator used. Available withorwithoutOpenClosedIndicator;EPswitch required ifpneumatic actuatorisused. SS-1 X X X X X SSFSD-211 ES-1 O X X X X X SEFSD-211 S-1 X O O O O O X X X X X FSD-213 S-1 X X X X X FSD-212 S-1 O O O O O O O O X O O O O O X X X X X FSD-211 FD22XXXXXOOOOOX O O O O O X X X X X CFSD-212 FD21X CFSD-211 O =Optional X =Standard

5 x 1 in. x 16 ga. Galvanized Steel Hat Channel 304 Stainless Steel Frame 316 Stainless Steel Aluminum 8 x 2 in. x 12 ga. Galvanized Steel Hat Channel

XXXXOOOOOXOOOOOOOO3V Profile Blade Steel Airfoil Aluminum Airfoil

Class I Leakage Class XOOOOOXOOOOOOOO X X Class II Class III 1 Hour Rating Fire 1½ Hour 3 Hour 165°F (74°C) Temperature OOOOOXOOOOOOOO OOOOOXOOOOOOOO OOOOOXOOOOOOOO

212°F (100°C) Closure OOOOXOOOOOOOO OOOOXOOOOOOOO 250°F (121°C) 286°F (141°C) 350°F (177°C) Fusible Link Closure 1 Reusable Resettable Link (RRL) Device OOOOOOOO OOOOOOOO OOOOOOOO OOOOOOOO 2 Temperature Limited Override (TOR)

OOOOOOO 3 Pneumatic Relief Valve (PRV) OOOOOO OOOOOO OOOOOO Retaining Angles OOOOO

Smoke Detector Accessories

OOOO Momentary Switches Open or Close Indicator (OCI) Transformer Greenheck Test Switch (GTS) Fire Smoke Dampers 39 6 4 4 8 4 4 8 4 4 6 4 4 8 4 6 4 6 (1) (1) (2) (2) (1) (1) (1) (1) (1) (1) (2) (1) (1) (1.5) (1.5) (1.5) (1.5) (kPa) in. wg Pressure 2000 4000 3000 4000 2000 2000 2000 2000 2000 2000 4000 3000 2000 4000 2000 (m/s) (10.2) (20.3) (15.2) (20.3) (10.2) (10.2) (10.2) (10.2) (10.2) (10.2) (15.2) (20.3) (10.2) (20.3) (10.2) ft/min. Velocity OFSD Series °F (°C) Ratings 250° (121°) 350° (177°) 350° (177°) 350° (177°) 350° (177°) 250° (121°) 350° (177°) 350° (177°) 350° (177°) 350° (177°) 350° (177°) 350° (177°) Temperature Temperature 88 x 48 48 x 48 36 x 72 88 x 72 36 x 36 128 x 50 128 x 48 100 x 32 120 x 96 120 x 96 128 x 100 128 x 100 128 x 100 128 x 100 (914 x 914) (2540 x 813) (914 x 1829) (2235 x 1219) (3251 x 2540) (3251 x 1270) (1219 x 1219) (3251 x 2540) (3251 x 1219) (3251 x 2540) (2235 x 1829) (3251 x 2540) (3048 x 2438) (3048 x 2438) -- 350° (177°) -- 350° (177°) -- -- 350° (177°) -- 48 x 30 48 x 48 36 x 72 48 x 30 36 x 36 128 x 96 128 x 96 128 x 96 144 x 96 144 x 48 144 x 96 120 x 96 144 x 96 (914 x 914) (1219 x 762) (914 x 1829) (1219 x 762) (3251 x 2438) (3251 x 2438) (1219 x 1219) (3251 x 2438) (3658 x 2438) (3658 x 1219) (3658 x 2438) (3048 x 2438) (3658 x 2438) GFSD Series 24 x 30 32 x 50 42 x 48 50 x 32 22 x 36 50 x 32 36 x 36 24 x 24 32 x 50 36 x 48 36 x 48 30 x 48 36 x 36 32 x 30 24 x 30 or 32 x 50 or 32 x 36 or (610 x 762) (914 x 914) (559 x 914) (610 x 610) (914 x 914) (813 x 762) 914 x 1219) 762 x 1219) (813 x 1270) (1270 x 813) (813 x 1270) (1270 x 813) (914 x 1219) (610 x 762 or (813 x 914 or (1067 x 1219) (813 x 1270 or 8 x 6 6 x 8 8 x 6 8 x 6 6 x 8 8 x 6 8 x 6 8 x 6 8 x 6 14 x 12 12 x 12 12 x 12 Maximum Damper Size Limitations Size Damper Maximum (203 x 152 (203 x 152) (356 x 305) (152 x 203) (203 x 152) (203 x 152) (152 x 203) (203 x 152) (203 x 152) (203 x 152) (305 x 305) (305 x 305) Size Limitations - W x H, in inches (mm) in inches W x H, - Size Limitations Maximum Single Section Multi-section 32 x 50 42 x 48 24 x 30 36 x 36 32 x 50 24 x 24 36 x 48 36 x 48 36 x 36 32 x 30 32 x 50 or (610 x 762) (914 x 914) (610 x 610) (914 x 914) (813 x 762) 914 x 1219) (813 x 1270) (813 x 1270) (914 x 1219) (1067 x 1219) (813 x 1270 or Horizontal Vertical Horizontal Vertical ------8 x 6 8 x 6 8 x 6 8 x 6 8 x 6 8 x 6 14 x 12 12 x 12 12 x 12 Minimum Maximum Minimum Maximum Maximum (203 x 152) (356 x 305) (203 x 152) (203 x 152) (203 x 152) (203 x 152) (203 x 152) (305 x 305) (305 x 305) CFSD Series I I I I I I I I II II II II II II II III Class Leakage

FSD-311 FSD-312 FSD-211 FSD-212 FSD-213 FSD-331 I -- --

FSD-311V I CFSD-211 CFSD-212 GFSD-211 GFSD-212 OFSD-211 OFSD-212 OFSD-311 OFSD-312 FSD-311M FSD-312M FSD-211M I SEFSD-211 SSFSD-211 Model

3 Hour 3 1½ Hour 1½ Round Dampers 40 Axle combination fire smokedamper. plate isprovided standard witheachround fire and hold thedamperinopening.Oneretaining are designedtomountflushthewall/floorand the clampingscrew forsimplified installation.They around thesleeveofdamperandtightenwith Square one-pieceretaining plateseasily wrap Retaining Plates ductwork. horizontally. Allround lifesafetydampersfeature anintegralsleeveforeasyconnectiontoadjoining Round fire, smoke,andcombinationfire smokedampersare availableformountingeitherverticallyor Mounting in applicationswithround ductwork. UL (UnderwritersLaboratories)Classifiedround fire, smoke,andcombinationfire smokedampersare used Application Round Dampers Blade Orientation 30° Off Horizontal Model FDR-510 (Maximum) 30° Axle 30° Off Horizontal Retainer Plate Duct Connection Area (Maximum) n. 2 in 6 in.max. AIRFLOW Wall Thickness Sleeve Length 30° Axle plate inthisgroove Do notplaceretainer 6 in.max. Clearance forExpansion 2nd RetainerPlate(optional) Clamping Screw n. 2 in Blade Latch Assembly Plate Retaining Nut Normal same sideasbladelatch Access doortobeon Area Duct Connectio n Round Dampers

41 SSSMDR-501 4 24

(1)

350° 3000 (610) (15.2) (177°) SSFSDR-511 4 24

(1)

350° 3000 (610) (15.2) (177°) SSFDR-510 -OO 4 24

(1)

286° 2000 (610) (10.2) (141°) SSDFDR-510 - - XXXX 24

286° (610) (141°) SMDR-502 4 24

(1)

350° 3000 (610) (15.2) (177°) SMDR-501 4 24

(1)

350° 3000 (610) (15.2) (177°) SESMDR-501 4 24 (1)

350°

3000 (610) (15.2) (177°) Quick Reference Guide Reference Quick SEFSDR-511 4 24

(1)

350° 3000 (610) (15.2) (177°) FSDR-512 4 24

(1)

350° 3000 (610) (15.2) (177°) FSDR-511 4 24

(1)

350° 3000 (610) (15.2) (177°) FDR-510 - - 24

286° (610) (141°) DFDR-510 -X------X-- --X-XXX---XX --XXX-----X- ---X---X------XXX---X ------XX------OOO-----O- --OOO-----O- --OOO-----O- --OOO-----O- --OOO-----O- --OOO-----O- - -OOOOOO- -OO - -OOOOOO- -OO - -OOOOOO- -OO --OO--OO--OO - -OOO-OO- 4 XXXXX- - -XXX- X------X--- XXXX- -XX- - - - XXXXX- - -XXX- XXXXX- - -XXX- XXXXXXXXXXXX XXXXXXXXXXXX XXXXX- - -XXX- OOOOO- - -OOO- OOOOO- - -OOO- 24 (1) 286° 2000 (610) (10.2) (141°) hour Fire hour Fire 2 ⁄ 1 Static Fire Diameter in. (mm) Rating Velocity Velocity fpm (m/s) Dynamic Fire UL 555S Class I Leakage Combination Fire Combination Fire Smoke UL 555S Class II Leakage Pressure Pressure in. wg (kPa) Smoke Galvanized Steel Temperature Temperature °F (°C) UL 555 1 304 Stainless Steel 316SS Stainless Steel Fusible Link RRL RRL/OCI TOR PRV 165°F (74°C) 212°F (100°C) 250° (121°C) 286°F ( 148°C) 350°F (177°C) Horizontal Vertical Retaining Plates Momentary Test Momentary Test Switch Transformer Greenheck Test Test Greenheck Switch (GTS) Smoke Detector Open Close Indicator (OCI) Damper Type X = Standard O = Optional Maximum Material UL Listing Closure Closure Device Closure Closure Temperature Mounting Accessories Ceiling Radiation Dampers 42 within theductsystem. *The IBCstatesthattheclosure temperature shallbeapproximately 50°Fabovethe normaltemperature fire resistance ratingsofthree hours orless. Greenheck’s UL555C listeddampersare approved foruseinfloor/ceilingandroof/ceiling assemblieswith 555C listeddampersmaybeused. specific dampermodelsandmanufacturers, thenUL damper construction,asopposedtocallingout as anallowablecomponentanddescribestherequired Resistance Directory. Ifthedesigncallsoutdampers the constructionfeatures ofthedesigninULFire 555C listeddamperscanbeidentifiedbyreviewing and roof/ceiling assembliesthatallowtheuseofUL 555C listedceilingradiationdamper. Floor/ceiling through theceilingmembranemayutilizeanyUL door typedampers”protecting HVAC penetrations that were fire testedwithwhatare knownas“hinged membrane forthestructuralmembers.Assemblies the useofacousticalceilingtilesasaprotective ceiling members. Manynon-combustibleassembliesrequire ceiling designsthatdonotusewoodastheirstructural Non-combustible assembliesare floor/ceilingandroof/ Non-Combustible and roof/ceiling designsallowdamperstobeinstalled. be toreview itslisteddesignintheULFire ResistanceDirectory (orequivalentdirectory). Notallfloor/ceiling building elements.Thefirststepindeterminingtheappropriate ceilingdamperforagivenapplicationshould The ULFire ResistanceDirectory containsthedesignspecificationsofhundreds ofdifferent fire rated 165°F (74°C)fusiblelink*). activation ofatemperature response devicedesignedtorelease ataselectedtemperature (thisisusuallya membrane ofratedfloor/ceilingandroof/ceiling assemblies.Ceilingradiationdamperscloseuponthe Ceiling radiationdampers(alsocalledceilingdampers)are designedtoprotect openingsintheceiling Application Ceiling RadiationDampers CRD-1 butterfly CRD-60 curtainbladestyle CRD-1LP lowprofile butterfly CRD-60 curtainbladestyle Typical non-combustible floor/ceilingassembly that utilizesanUL555Cdamper with skirt CRD-2 round butterfly Ceiling Radiation Dampers 43 CRD-501 CRD-1WT shown Typical floor/ceiling assembly with wood truss Typical Ceiling Radiation Dampers Radiation Ceiling

t CRD-1WJ shown Typical floor/ceiling assembly with wood joist Typical Low Leakage Ceiling Radiation Damper ceiling radiation damper with a Class I Smoke The CRD-501 is a round Leakage Rating. It is UL Classified as a ceiling radiation (UL 555C) and as a smoke damper (UL 555S). As a UL 555C ceiling radiation damper, assemblies to maintain the it is used in floor/ceiling and roof/ceiling As a UL exposure. integrity of the assembly during fire resistance fire Class I smoke leakage rated model CRD-501 is a 555S smoke damper, of smoke. the spread damper designed to control Combustible structural joists as their trusses or wood that utilize wood assemblies and roof/ceiling Rated floor/ceiling are Because their structural members to as “Combustible Assemblies”. often referred membrane are Combustible ceiling membrane. use of a gypsum board the of these assemblies require combustible, most use of better the ceiling membrane require penetrations in their with HVAC tested assemblies that were these applications. for approved not listing are Dampers that only carry a UL 555C insulated dampers. the specific call out damper, tested with a that were Resistance Directory in the UL Fire Combustible designs the tests for many of these designs to be used. Because approved and models that are damper manufacturer a given design number may be damper models in the approved by a damper manufacturer, sponsored were to often approved damper models are manufacturer’s other damper However, manufacturer. limited to a single material and methods. that permit the same construction design numbers be used in different Ceiling Radiation Dampers 44 Ceiling RadiationDampers-ModelsandSizes models. will openorclosetheblades.Available onallCRD the bladestoagivenangle.Adjustingscrew airflow through the damperbymanuallysetting A volumecontroller givesyoutheabilitytoregulate Volume Controller asbestos mineralwoolthermalblanket. two layersoffiberglass cloth.TheTB-24isanon- temperature ceramicfiberblanketquiltedbetween thermal blanketconsistingofanon-asbestoshigh as battandblanketmaterial.QB-24isarefractory blankets withceilingradiationdamperstobeused Greenheck offers twodifferent typesofthermal Thermal Blankets customer suppliedplenum. ductboard plenum,ortheycanchoosetodoa installed perUL.We canoffer steelplenum, The CRD-1WTdampersmusthaveaplenum Plenum Grille mountorductfortheCRD-1WT. Mounting CRD-2. extensions are availableonCRD-1,CRD-1LP, and Top, bottom,orbothtopandbottomframe Frame Extensions Options Ceiling RadiationDampers Maximum Size Minimum Size in. (mm) in. (mm) Model (610 x610) (102 x152) 24 x CRD-1 4 x6 Low Profile (610 x610) (102 x305) CRD-1LP 24 x 4 x12 utrySyeCranSyeRound CurtainStyle Butterfly Style (406 x305) (102 x152) R-W R-W R-W R-0CD6XCD2CRD-501 CRD-2 CRD-60X CRD-60 CRD-2WT CRD-1WT CRD-1WJ 16 x12 4 x6 (533 x457) (102 x152) 21 x18 4 x6 (305 x305) (127 x127) 12 x 5 x Frame Extensions Volume Controller (610 x610) (152 x102) 24 x 6 x4 (610 x610) (152 x102) 24 x 6 x4 6WDQGDUG (610) (127) ([WHQVLRQ %RWWRP 24 5 ([WHQVLRQ 7RS %RWWRPDQG7RS ([WHQVLRQ (305) (152) 12 6 Performance Data 45 (1.2 kg/ 3 Figure 5.5 Figure Performance Data Performance 6D D = Duct length W = Damper width H = Damper height Greenheck Fan Corporation certifies that the models CFSD-211, 212; certifies that the models CFSD-211, Fan Corporation Greenheck 213, 212, 211M, 330; SEDFD-210; FSD-211, DFD-210; DFDAF-310, 212, 331; SSFSD-211; SEFSD-211; OFSD-211, 312M, 312, 311M, 311, 401EF; 302M, 302, 301M, 301, 203, 202, 201M, 312; SMD-201, 311, the licensed to bear are herein SESMD-201 and SSSMD-201 shown based on tests and procedures are shown The ratings AMCA Seal. AMCA Publication 511 and comply with performed with in accordance AMCA The AMCA Certified Ratings Programs. of the the requirements Certified Ratings Seal applies to air performance only. the models DFD-210; India Pvt. Ltd. certifies that Greenheck 301 202, 331; SMD-201, 312, 311, 212, 330; FSD-211, DFDAF-310, The ratings AMCA Seal. licensed to bear the are herein and 302 shown performed based on tests and procedures in accordance are shown of the the requirements AMCA Publication 511 and comply with with Certified Ratings Seal AMCA The AMCA Certified Ratings Programs. applies to air performance only. 5D 5D 3.14 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower area. This configuration has a lower damper exhausting air into an open Illustrates a ducted This configuration has the highest pressure drop Illustrates a plenum mounted damper. Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three the lowest pressure drop of the damper. This configuration has Illustrates a fully ducted 4 (W) (H) (W) 4 = ). D Figure 5.2 Figure Figure 5.3 Figure 3 test configurations because entrance and exit losses are minimized by straight duct runs upstream and are minimized by straight duct runs because entrance and exit losses test configurations damper. downstream of the run upstream of are minimized by a straight duct Figure 5.5 because entrance losses pressure drop than the damper. due to the sudden changes of area in the system. because of high entrance and exit losses Actual pressure drop found in a HVAC system is a combination of many factors. This pressure drop drop factors. This pressure system is a combination of many found in a HVAC drop Actual pressure actual pressure should be used to estimate with an analysis of other system influences information, along system. installed in an HVAC losses for a damper Figure 5.2 Figure 5.5 Figure 5.3 Pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three three 500-D using the Standard with AMCA in accordance was conducted testing drop Pressure a density of .075 lb/ft air at standard to represent has been corrected shown. All data configurations m Performance Data 46 and SSSMD-201. 211M, 212,213;OFSD-211,212;SEFSD-211;SSFSD-211;SMD-201,201M,202,203;SESMD-201; These pressure drop chartsapplytothefollowingmodels:CFSD-211, 212;DFD-210;SEDFD-210;FSD-211, Pressure Drop Dimension Dimension Dimension in. (mm) in. (mm) in. (mm) (ft/min.) (ft/min.) (ft/min.) Velocity Velocity Velocity 0035 .718 .12.67 2.11 1.86 2.17 3.55 4000 1.14 .70 .42 .63 1.44 4000 1.62 .92 .64 1.16 2.20 4000 5027 .614 .22.05 1.62 1.42 1.66 3500 2.72 .88 .53 .33 .48 3500 1.10 1.24 .70 .49 .89 3500 1.69 0020 .210 .91.50 1.19 1.05 1.22 3000 2.00 .64 .39 .24 .35 3000 .81 .91 .52 .36 .65 3000 1.24 5013 8 7 8 1.04 .83 .73 .85 2500 1.39 .45 .27 .17 .25 2500 .56 .63 .36 .25 .45 2500 .86 00.9.4.6.3.67 .53 .46 .54 2000 .89 .29 .17 .11 .16 2000 .36 .41 .23 .16 .29 2000 .56 50.0.1.6.0.38 .30 .26 .31 1500 .50 .16 .10 .06 .09 1500 .20 .23 .13 .09 .16 1500 .32 00.2.4.2.3.17 .13 .12 .14 .22 1000 .07 .04 .03 .04 .09 1000 .10 .06 .04 .07 .14 1000 0 0 0 0 0 .04 .03 .03 .03 500 .06 .02 .01 .01 .01 500 .02 .03 .01 .01 .02 500 .04 (305 x305) (305 x305) (305 x305) 12 x 12 x 12 x AMCA Figure 5.2Pressure Drop AMCA Figure 5.5Pressure Drop AMCA Figure 5.3Pressure Drop (610 x610) (610 x610) (610 x610) 24 x 24 x 24 x Pressure Drop-in.wg Pressure Drop-in.wg Pressure Drop-in.wg (914 x914) (914 x914) (914 x914) 36 x 36 x 36 x (305 x1219) (305 x1219) (305 x1219) 12 x48 12 x48 12 x48 (1219 x305) (1219 x305) (1219 x305) 48 x12 48 x12 48 x12 Performance Data 47 Pressure Drop Pressure 48 x 12 48 x 12 48 x 12 (1219 x 305) (1219 x 305) (1219 x 305) 12 x 48 12 x 48 12 x 48 (305 x 1219) (305 x 1219) (305 x 1219) 36 x 36 36 x 36 36 x 36 (914 x 914) (914 x 914) (914 x 914) Pressure Drop - in. wg Pressure Pressure Drop - in. wg Pressure Pressure Drop - in. wg Pressure 24 x 24 24 x 24 24 x 24 (610 x 610) (610 x 610) (610 x 610) AMCA Figure 5.2 Pressure Drop Drop 5.2 Pressure AMCA Figure AMCA Figure 5.3 Pressure Drop Drop 5.3 Pressure AMCA Figure AMCA Figure 5.5 Pressure Drop Drop 5.5 Pressure AMCA Figure 12 x 12 12 x 12 12 x 12 (305 x 305) (305 x 305) (305 x 305) 500 .03 .01 .01 .01 .02 500 .04 .03 .03 .03 .03 500 .01 .01 .01 .01 .01 1000 .11 .06 .05 .05 .08 1500 .24 .12 .12 .12 .18 2000 .42 .22 .21 .21 .33 2500 .66 .34 .32 .33 .51 3000 .95 .49 .47 .48 .74 3500 1.30 .67 .63 .65 1.00 4000 1.70 .87 .83 .85 1.31 1000 .18 .13 .12 .12 .14 1000 .06 .02 .02 .03 .04 1500 .42 .29 .27 .27 .32 1500 .13 .06 .05 .06 .10 2000 .75 .52 .48 .49 .57 2000 .23 .10 .09 .11 .18 2500 1.17 .81 .75 .77 .89 2500 .36 .16 .14 .18 .29 3000 1.68 1.17 1.08 1.11 1.28 3000 .53 .23 .21 .25 .42 3500 2.29 1.60 1.48 1.51 1.75 3500 .73 .32 .29 .34 .57 4000 2.09 2.14 1.93 1.97 2.29 4000 .95 .42 .38 .45 .74 Velocity Velocity (ft/min.) in. (mm) Velocity Velocity Velocity Velocity (ft/min.) (ft/min.) in. (mm) in. (mm) Dimension Dimension Dimension These pressure drop charts apply to the following models: DFDAF-310, 330; FSD-311, 311M; FSD-312, 312M; FSD-312, 312M; FSD-311, 311M; DFDAF-310, 330; following models: charts apply to the drop These pressure and 302M. SMD-301, 302; SMD-301M OFSD-311, 312; FSD-331; Performance Data 48 These pressure drop chartsapplytothefollowingmodels:SMD-401, SMD-401M,andSMD-401EF. Pressure Drop Dimension Dimension Dimension in. (mm) in. (mm) in. (mm) (ft/min.) (ft/min.) (ft/min.) Velocity Velocity Velocity 00.1.4.7.5.31 .45 .17 .34 .51 4000 .39 .93 .46 .70 .88 4000 0021 .115 .71.83 1.87 1.56 1.91 2.19 4000 50.9.6.3.4.24 .34 .13 .26 3500 .39 .30 .71 .35 .54 3500 .68 5016 .711 .31.40 1.43 1.19 1.47 3500 1.67 00.9.9.9.5.18 .25 .09 .19 3000 .29 .23 .51 .26 .40 3000 .50 0012 .7.710 1.02 1.05 .87 1.07 3000 1.23 50.1.3.6.7.12 .17 .06 .13 2500 .21 .16 .36 .18 .28 2500 .35 50.6.5.1.2.72 .72 .61 .75 2500 .86 00.4.8.4.1.08 .11 .04 .08 2000 .14 .10 .23 .12 .18 2000 .23 00.5.8.9.6.46 .46 .39 .48 2000 .55 50.7.4.2.6.04 .06 .02 .04 1500 .07 .06 .13 .06 .10 1500 .13 50.1.7.2.5.26 .25 .22 .27 1500 .31 00.3.2.1.3.02 .03 .01 .02 .03 1000 .03 .06 .03 .04 .06 1000 00.4.2.0.1.11 .11 .10 .12 .14 1000 0 0 0 0 0 .01 .01 .01 .01 500 .01 .01 .01 .01 .01 500 .01 0 0 0 0 0 .03 .03 .03 .03 500 .04 (305 x305) (305 x305) (305 x305) 12 x 12 x 12 x AMCA Figure 5.5Pressure Drop AMCA Figure 5.3Pressure Drop AMCA Figure 5.2Pressure Drop (610 x610) (610 x610) (610 x610) 24 x 24 x 24 x Pressure Drop-in.wg Pressure Drop-in.wg Pressure Drop-in.wg (914 x914) (914 x914) (914 x914) 36 x 36 x 36 x (305 x1219) (305 x1219) (305 x1219) 12 x48 12 x48 12 x48 (1219 x305) (1219 x305) (1219 x305) 48 x12 48 x12 48 x12 Performance Data 49 Pressure Drop Pressure 48 x 12 48 x 12 48 x 12 (1219 x 305) (1219 x 305) (1219 x 305) 12 x 48 12 x 48 12 x 48 (305 x 1219) (305 x 1219) (305 x 1219) 36 x 36 36 x 36 36 x 36 (914 x 914) (914 x 914) (914 x 914) Pressure Drop - in. wg Pressure Pressure Drop - in. wg Pressure Pressure Drop - in. wg Pressure 24 x 24 24 x 24 24 x 24 (610 x 610) (610 x 610) (610 x 610) AMCA Figure 5.2 Pressure Drop Drop 5.2 Pressure AMCA Figure AMCA Figure 5.3 Pressure Drop Drop 5.3 Pressure AMCA Figure AMCA Figure 5.5 Pressure Drop Drop 5.5 Pressure AMCA Figure 12 x 12 12 x 12 12 x 12 (305 x 305) (305 x 305) (305 x 305) 500 .10 .09 .07 .10 .09 500 .02 .01 .005 .02 .02 500 .06 .02 .016 .05 .05 1000 .19 .16 .14 .18 .15 1000 .04 .03 .02 .04 .04 1000 .11 .08 .06 .10 .09 1500 .43 .36 .34 .41 .35 1500 .09 .05 .04 .09 .09 1500 .26 .17 .15 .21 .20 2000 .72 .65 .60 .72 .63 2000 .17 .10 .07 .16 .15 2000 .48 .31 .26 .38 .37 2500 1.18 .98 .92 1.14 .97 2500 .27 .15 .11 .24 .23 2500 .72 .49 .41 .58 .58 3000 1.66 1.45 1.31 1.61 1.40 3000 .38 .23 .16 .36 .33 3000 1.02 .70 .59 .83 .85 3500 2.30 1.97 1.85 2.25 1.92 3500 .52 .29 .21 .49 .45 3500 1.40 .94 .80 1.18 1.17 4000 3.30 2.64 2.37 2.95 2.54 4000 .69 .40 .28 .63 .60 4000 1.84 1.27 1.04 1.55 1.58 Velocity Velocity Velocity Velocity Velocity Velocity (ft/min.) (ft/min.) (ft/min.) in. (mm) in. (mm) in. (mm) Dimension Dimension Dimension These pressure drop charts apply to the following models: DFD-110, 150, 310, 350; DFD-150X series; DFD-150X series; 150, 310, 350; models: DFD-110, apply to the following charts drop These pressure 350. SSDFD-150 and ODFD-150; Accessories 50 breakaway connectionthree different ways: smoke dampers.You canorder yourdamperswith on fire dampers,smoke,andcombinationfire to choosetheuniversalbreakaway connection or Ward flangesystems.You nowhavetheoption Ductmate, Durodyne, RadiantT35m,MEZ,Nexus, duct connectionthatiscompatiblewithTDC,TDF, successfully ULQualifyauniversalbreakaway Greenheck wasthefirstmanufacturer to Quick ConnectBreakaway Connections different ways: for you.You canorder yourretaining anglesfour angles Save timebylettingGreenheck installretaining Retaining Angle to saveontimeandlaborcostsinthefield. Let Greenheck installtheaccessdoorinsleeve smoke damperformaintenanceandinspection. each fire damper, smokedamper, orcombinationfire door needstobeprovided inairductsadjacentto According toNFPA 80andNFPA 90A,anaccess Access Doors Factory MountedAccessories visit ourresource videolibraryatgreenheck.com. benefit ofaQuickConnect Breakaway Connection, To viewtheUL555DuctImpact Test showingthe are usedontopand bottom. on thesideofhemmed sleeveandS-slipjoints S andDriveconnectionusesdriveslip • Oneendattachedandoneshippedloose • • • • • • in thelocationyouwant damper fastened andoneanglewrappedaround the wrapped, butwith2setsofretaining angles around thedampersleeveandwire tied sleeve Universal flangeattachedtobothendsofthe sleeve Universal flangeattachedtooneendofthe Fastened andWrapped - Double Wrapped - Single Wrapped - Single Fastened- oneretaining anglewrapped one retaining angle mounted thesamefeature assingle one retaining angle Accessories 51 GTS-2 GTS-4 Toggle Switch Toggle Testing Devices Testing GTS-1 GTS-3 Momentary Test Switch Momentary Test - Red for closed damper for open damper - Green - Red for closed damper for open damper - Green - Red for closed damper for open damper - Green - Red for closed damper for open damper - Green Combination fire smoke damper equipped with Combination fire RRL/OCI or TOR Combination fire smoke damper equipped with Combination fire RRL/OCI or TOR • Combination fire smoke or smoke damper • Combination fire • Open and closes the damper • Factory mounted • Combination fire smoke or smoke damper • Combination fire and cycle the damper on location • Test • Factory mounted • • Smoke damper with an OCI • Indicator lights only • Factory mounted or shipped loose • • Smoke damper with an OCI • Indicator lights • Momentary test switch • Factory mounted or shipped loose • Combination fire smoke damper equipped with • Combination fire TOR • Key switch • Indicator lights • Shipped loose • Combination fire smoke damper equipped with smoke damper • Combination fire TOR switch • Toggle • Indicator lights or shipped loose • Factory mounted Two Position Toggle Switch Position Toggle Two Momentary Test Switch Momentary Test GTS-4 GTS-3 GTS-2 Greenheck has a wide range of devices to test your of devices to has a wide range Greenheck smoke or smoke damper. fire combination GTS-1 Accessories 52 true “positivebladeindications”. physically linkedtoadamperbladeandtherefore give indicates whenthedamperisclosed.Theswitchesare indicates whenthedamperisopen,andother two switches,providing positivebladeindication.One mounted andwired orshippedloose. 20.3 m/s).Thesesmokedetectorscaneitherbefactory rated forvelocitiesfrom 100to4000ft/min.(0.5 security barsare available: products andare weldedintothesleeve. Two typesof Security barsmaintaintheULClassificationforall reduces securityrisksandreinforces theequipment. assembled. Installationofsecuritybarsintodampers installed withthedamper, theycanbeshipped When aspecificationrequires securitybars tobe Security Bars No FlowSmokeDetector- Low FlowSmokeDetector- and combinationfire smokedampers. smoke. Thedetectorscanbeusedtocontrol smoke through aductandprovide analarmupondetectionof A smokedetector’s purposeistosampleairpassing Smoke Detectors option basedonpreference ofthedesignengineer. end switchesare offered totheOCI asanalternative Station), orusedforotherpurposesasrequired. The to indicatorlights(attheFirefighter’s SmokeControl OCI option.Theseswitchesare alsonormallywired the actuatorandperformsamefunctionas as auxiliaryswitches.Theseswitchesareto internal Actuator endswitchesare alsocommonlyreferred to Actuator EndSwitches Open CloseIndicator(OCI)- Blade Indication Blade IndicatorsandSmokeDetectors flow smokedetectorhasabuilt-intestswitch. dampers withamaximumoftwoactuators.Theno tothedampersleeve.Itcanbeusedon internally from 0to3000ft/min.(015.2m/s)andismounted velocity. Thissmokedetectorisratedforairvelocities is ratedforsystemswithoutaminimumoperating • • 24 inches(610mm). mid barsplacedhorizontal ondampershigherthan on center, basedoncustomer selection,withflat Punched midbar-round steelbarsplacedvertical vertical oncenter, based oncustomerselectionor Cross bar-round steelbarsplacedhorizontaland Thenoflowsmokedetector Thissmokedetectoris The OCIoptionprovides Security Bars Low Flow No Flow OCI Accessories 53 TYPE C TYPE O TYPE R Transitions and Installation Transitions Transitions for Smoke and Combination Fire Smoke Dampers Fire for Smoke and Combination Transitions Installation Booklets includes installation booklets in every Greenheck shipment of dampers. These booklets include installation guidelines such as field-supplied sleeves, to help angles, and much more single side retaining with your installation needs. Greenheck dampers feature decals highlighting dampers feature Greenheck important to an accurate that are damper areas damper areas installation. Our decals point out critical hassle-free. and include messages to make installation these to offer the only damper manufacturer are We simple, yet very helpful tips, right on the damper. Helpful Installation Decals In the section of the Green Building Building Green In the Indoor Air Quality section of the Guide, you need to protect Concepts and LEED Core dust and air quality during construction and prevent to Clean Wrap offers particulate buildup. Greenheck is a thin film Clean Wrap help meet this requirement. to the ends of the damper sleeve to that adheres entering the damper dust, dirt and debris from prevent at the construction site. Clean Wrap Transitions smoke or fire combination When a rectangular being used in conjunction with smoke damper is supplied with or oval ductwork, it must be round both ends of the or oval transitions on one or round may be used to increase C transition sleeve. A Type Dampers drop. minimize pressure and area free to the duct dimensions. should be ordered Accessories 54 with retaining anglesorplateson exceeding thesemaximumsizesmustbesecured plates on sleeve assembliesmaybeinstalledwithretaining one side qualified forinstallationswithretaining angleson Rectangular dampersandsleeveassembliesare Plates Single SideRetainingAnglesand simplified installation. the damperandtightenwithclampingscrew for retaining plateseasilywraparound thesleeveof their rectangular counterparts,round one-piece installation instructions,andthat’s it!Simple!Like damper, connections are madeasdescribedinour The POCsimplywrapsaround thesleeveof combination fire smokedamperinstallationabreeze. (literally namedforbeinga“PieceofCake”)makes Greenheck’s onepieceretaining angle,thePOC One PieceRetainingAngles information. directed towww.greenheck.com formodelspecific scan theQRcodewithyoursmartphone,youwillbe you willseeaQRcodeonthelabeltoo.When combination fire smoke,smokeandfire dampers, multiple locationsfordampersonthejobsite.On label willhelpsavetimeinthefieldwhenyouhave actuator model,andpurchase order number. This limit). Thislabelprovides thedampermodel,size, the taginformationforyourorder (30character Greenheck labels— Tag Label Convenience Features the damper. retaining angleisnotrequired onthebottomsideof wall opening(example:underfloorapplication).A where thedamperrests directly onthebaseof A 3-sideretaining angleisqualifiedinapplications partition. oiotl14x9 3658x2438 144 x 96 Fire Smoke Round Fire and Horizontal Vertical onigIce Millimeters Inches Mounting for SingleSideand3-Side*RetainingAngle *

one side of thepartitiononly. Rounddampersand Maximum QualifiedDamperSize only. Damperassemblies on alldampers (Width xHeight) 4daee 610diameter 24 diameter 0x101016x 2540 40 x100 0x8 1270x 2032 2032x 1270 50 x80 80 x50 both sides —include ofthe Retaining Platefor Round Dampers Accessories 55 Cost Saving Products Cost (Width x Height) Maximum Damper Size Maximum Damper Inches Millimeters 72 x 962438 1829 x and Retaining Clip Installation and Retaining Firestop Two Dampers in One - Modulating Fire in One - Modulating Fire Dampers Two Smoke or Smoke Dampers modulating actuators UL approved offers Greenheck smoke dampers. A on smoke and combination fire modulating actuator combines the functions of a smoke or smoke damper damper and a fire control the number of dampers needed into one unit reducing cost. and the overall project Two Dampers in One - Manual Balancing Dampers in One - Manual Balancing Two Damper Fire and damper a fire This allows them to function as both multi-blade All Greenheck manual balancing damper. supplied with a manual quadrant. dampers are fire Tight Space Constraints – Use Firestop Constraints Tight Space not installations will angle retaining standard Where and firestop has a UL approved work, Greenheck contractors to clip installation which allows retaining space limits capabilities. where meet UL requirements Damper Model Definition

A Product Type: Multi-Blade and Round FSD-311V CFSD Corridor Ceiling Combination Fire Smoke Damper DFD Dynamic Fire Damper A B C D V = Vertical Blade DFDAF Dynamic Fire Damper - Airfoil Blade Damper M = Modulating Blade DFDR Round Dynamic Fire Damper EF = Extruded Frame FDR Round Static Fire Damper EXAMPLE: Combination Fire-Smoke Damper with FSD Combination Fire Smoke Damper Vertical Steel Airfoil Blades 1 1 ⁄2 Hour Fire Rating FSDR Round Combination Fire Smoke Damper Class I Leakage GFSD Grille Access Combination Fire Smoke Damper HSD Heavy Duty Smoke Damper OFSD Out-of-Wall Combination Fire Smoke Damper SEDFD 316 Stainless Steel Dynamic Fire Damper DFD -150X12 SEFSD 316 Stainless Steel Combination Fire Smoke Damper 1 2 3 4 5 SEFSDR Round 316 Stainless Steel Combination Fire EXAMPLE: Dynamic Fire Damper with Smoke Damper 1 1 ⁄2 Hour Fire Rating SESMD 316 Stainless Steel Smoke Damper 11 3- ⁄16 inch Frame Low to Medium Pressure SESMDR Round 316 Stainless Steel Smoke Damper 12 inch Integral Sleeve SMD Smoke Damper SMDR Round Smoke Damper 1 Product Type: Curtain SSDFDR Round 304 Stainless Steel Dynamic Fire Damper DFD Dynamic Fire Damper SSFDR Round 304 Stainless Steel Static Fire Damper FD Static Fire Damper SSFSD 304 Stainless Steel Combination Fire Smoke Damper ODFD Out-of-Wall Dynamic Fire Damper SSFSDR Round 304 Stainless Steel Combination Fire OFD Out-of-Wall Static Fire Damper Smoke Damper SSDFD 304 Stainless Steel Dynamic Fire Damper SSSMD 304 Stainless Steel Smoke Damper SSFD 304 Stainless Steel Static Fire Damper SSSMDR Round 304 Stainless Steel Smoke Damper 2 Fire Resistance Rating B Blade Style 1 1½ Hour 2 Fabricated Steel with Triple Vee Reinforcements 3 3 Hour (3V) 3 Frame Style 3 Fabricated Steel Airfoil 0 Ultrathin - 1½ in. (38mm) 4 Extruded Aluminum Airfoil 3 1 Narrowline - 2 ⁄16 in. (56mm) 5 Round 11 5 Standard - 3 ⁄16 in. (94mm) C Fire Rating 4 Pressure Rating 0 Smoke Damper-No Fire Rating 0 Pressure (up to 4 in. wg) 1 1½ Hour 5 Damper with Integral Sleeve 3 3 Hour X12 12 in. long D Leakage X14 14 in. long 0 No Leakage Rating X16 16 in. long 1 Leakage Class l 2 Leakage Class lI 3 Leakage Class lII

56 Drive Arrangement Definition

The following breakdown of a drive arrangement code is a good reference in understanding what each number and letter signifies. 22-2FEL-2

Actuator 1 2 3 4 5 6 7

1 Number of sections wide 2 Number of sections high Jackshaft 3 Number of actuators 4 Who supplies the actuators F = Factory (always) on UL dampers 5 Actuator mounting E = External

Actuator Damper Height I = Internal B = Both internal and external 6 Actuator location (viewed from jackshaft side) Jackshaft L = Left hand drive R = Right hand drive B = Both right and left Damper Width 7 Number of jackshafts

Listings/Approvals UL Category EMME/CABS California State Fire Marshal (all models) DFD-2xx; DFDAF-3xx; SSDFD-2xx 3225-0981:0103 All DFD/FD curtain style 3225-0981:0102 GFSD/FSD/OFSD/SSFSD (fire) 3225-0981:0103 GFSD/FSD/OFSD/SSFSD/SMD/SSSMD (leakage) 3230-0981:0104 EMME R13317 CFSD (leakage) 3230-0981:0105 CFSD (fire) 3225-0981:0106 DFDR/FDR/FSDR/SSFSDR (fire) 3225-0981:0112 FSDR/SSFSDR/SMDR/SSSMDR (leakage) 3230-0981:0113 EMME R13317 CRD-501 3230-0981:0113 CABS R13446 CRD-1/CRD-1xx/CRD-2 3225-0981:0101 CABS R13446 CRD-60, -60X 3226-0981:0111 CRD-2WT 3226-0981:0500

57 Specification Checklist

Ceiling Radiation Combination Fire Fire Dampers Smoke Dampers Dampers Smoke Dampers UL Standard UL 555 33 UL 555C 3 UL 555S 33 NFPA 80 33 90A 333 92 33 101 3333 105 33 Fire Resistance 1½ Hour 333 3 Hour 33 Fire Closure Temperature 165°F (74°C) 333 212°F (100°C) 333 250°F (121°C) 33 286°F (141°C) 3 350°F (177°C) 33 Elevated Operational Temperature 250°F (121°C) 33 350°F (177°C) 33 Differential Pressure (applies to dynamic rated fire dampers, combination fire smoke dampers, smoke dampers) 4 in. wg (1 kPa) 333 6 in. wg (1.5 kPa) 333 8 in. wg (2 kPa) 333 10 in. wg (2.5 kPa) 3 Velocity 2000 ft/min. (10 m/s) 333 3000 ft/min. (15 m/s) 333 4000 ft/min. (20 m/s) 333 Leakage Class I 33 Class II 33 Class III 33 Mounting Horizontal 3333 Vertical 333 Factory Mounted Actuators 33 Please visit our website at www.greenheck.com/products/air-control/dampers for complete specifications.

58 Modifications to Life Safety Dampers

Field Modifications Steps to Take When an Unapproved The UL mark applies to the product as it is originally Installation Must be Provided manufactured when shipped from the factory. UL 1. Identify the problem and be ready to explain does not know what effect a modification may why an approved installation cannot be made. have on the safety of the product or the continued 2. Research the alternate installation methods validity of the UL certification mark unless the field that may be applicable and select a practical modifications have been specifically investigated by alternative that provides relative equivalency UL. Unless UL investigates a modified product, UL based on engineering principles. cannot indicate that the product continues to meet UL’s safety requirements. 3. Illustrate your proposed alternative and discuss it with the damper manufacturer (or Design Modifications representative), job design engineer, or both. Careful considerations need to be given to Obtain an agreement that it is an acceptable alterations or modifications of the fire resistance alternative. assemblies. When field issues arise, it is 4. Submit your alternative damper installation recommended the first contact for assistance be the to the authority having jurisdiction and technical staff provided by the product manufacturer obtain formal approval. Only the authority noted for the design. Users of fire resistance having jurisdiction can approve an alternative assemblies are advised to consult the general combination fire smoke damper installation. It is Guide Information for each product category and usually much easier to obtain approval before a each group of assemblies. The Guide Information damper has been installed. After an installation includes specifics concerning alternate materials and has been rejected by the inspector, it is often alternate methods of construction. quite difficult to obtain approval. Contacting UL UL provides assistance to the users of fire resistance assemblies and products, which includes clarification of the published information. UL also provides a service to investigate modifications to the fire resistance assemblies when requested by the design submitter. Requests for clarification should describe the change and include drawings, if necessary. Requests for clarifications or investigations can be made by contacting UL at: • Phone 1-877-ULHELPS (1-877-854-3577) ext. 49590 • Email: [email protected] or • Website: www.ul.com.

59 Most Commonly Asked Questions

Q. Are pneumatic actuators available on smoke and combination fire smoke dampers? A. Smoke and combination fire smoke dampers are available with pneumatic or electric actuators (internal or external mount). Reference: Actuator Selection, page 27

Q. Does the smoke and combination fire smoke damper actuator have to be factory mounted by the damper manufacturer? A. Yes. The 7th Edition of UL 555 and 4th Edition of UL 555S require all actuators on smoke and combination fire smoke dampers to be factory mounted. Reference: Smoke Dampers Installation, page 24

Q. Are there any specific sleeve gauge requirements for combination fire smoke damper installation? A. Sleeve gauge or thickness requirements depend on damper size and the type of duct-to-sleeve connections used. Reference: Sleeve Requirements, page 10

Q. How much space outside the damper sleeve is required to accommodate the actuator installation? Can the actuators be installed inside the sleeve to eliminate external space requirements? A. Clearance requirements for externally mounted actuators vary with actuator type. Enough space should be provided to allow for connection of wiring or piping and the replacement of the actuator and/or control components. If clearance is potentially a problem, the damper manufacturer should be contacted for specific clearance requirements. Installing the actuators internally should be considered only as a last resort, as it creates wiring/piping and service difficulties.

Q. How should combination fire smoke dampers be installed? A. Combination fire smoke dampers must always be installed in accordance with the manufacturer’s installation instructions. References: Fire Dampers Installation, page 9 through 12 Smoke Dampers Installation, page 24 Combination Fire Smoke Dampers Installation, page 32 through 33

Q. Is there any fire, smoke or combination fire smoke dampers that can be used in corrosive environment applications? A. Greenheck has Severe Environment dampers that are constructed out of 316 stainless steel for this application. Reference: Damper Model Definition, page 56

Q. When do I use a ceiling radiation damper versus a fire damper? A. Both dampers are intended to protect openings in horizontal fire barriers. A fire damper is required in a fire rated wall, floor or ceiling or partition when it is penetrated by air ducts or other air transfer openings. A ceiling radiation damper, according to the 2015 IBC (International Building Code). should be used in the following situations: 1. A ceiling radiation damper installed where a duct penetrates the ceiling of a fire resistance rated floor/ ceiling or roof/ceiling assembly. 2. A ceiling radiation damper installed at the ceiling line where a diffuser with no duct attached penetrates the ceiling of a fire resistance rated floor/ceiling or roof/ceiling assembly. Reference: Ceiling Radiation Dampers, page 42 through 44

60 Inspection, Maintenance and Testing

Inspection and Testing Once a building is commissioned, the dampers are required to be inspected and tested one year after installation. After one year, the dampers are inspected and tested every 4 years, except in a building containing a hospital, the frequency is every six years per NFPA 80 and NFPA 105. Dampers are part of the smoke control system and are required to be tested along with the system. Per NFPA 92, the smoke control system is inspected and tested: • At least semi-annually if it’s a dedicated system • At least annually if it’s a non-dedicated system The damper actuator shall be inspected and cycled per the manufacturer’s recommendations. Maintenance Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings, and jamb seals, do not use oil-based lubricants or any other lubricants that attracts contaminants such as dust. If the damper and/or the actuator are not operable, repairs shall begin as soon as possible.

61 Models by Manufacturing Location

Fire Dampers Combination Fire Smoke & Smoke Dampers Manufacturing Location Manufacturing Location

Greenheck Fan Greenheck India Greenheck Fan Greenheck India Corporation Pvt., Ltd. Corporation Pvt., Ltd. DFD-110 3 CFSD-211 3 DFD-150 33CFSD-212 3 SSDFD-150 3 FSD-211 33 DFD-150X series 33FSD-211M 3 ODFD-150 3 FSD-212 33 DFD-210 33FSD-213 3 DFDAF-300 3 SEFSD-211 3 DFDAF-310 33SSFSD-211 3 DFDAF-330 33FSD-311 33 SEDFD-210 3 FSD-312 33 SSDFD-210 3 FSD-311M 3 DFD-310 3 FSD-312M 3 DFD-350 33FSD-311V 3 SSDFD-350 3 FSD-331 33 FD-100 3 GFSD-211 3 FD-110 3 GFSD-212 3 FD-150 33OFSD-211 3 SSFD-150 3 OFSD-212 3 FD-150X series 33OFSD-311 3 OFD-150 3 OFSD-312 3 FD-300 3 SMD-201 33 FD-310 3 SMD-201M 3 FD-350 3 SMD-202 33 SSFD-350 3 SMD-203 3

SSSMD-201 Round UL Dampers 3 SESMD-201 3 Manufacturing Location SMD-301 33 Greenheck Fan Greenheck India Corporation Pvt., Ltd. SMD-301M 3 DFDR-510 3 SMD-301V 3 FDR-510 3 SMD-302 33 FSDR-511 3 SMD-302M 3 FSDR-512 3 SMD-401 3 SEFSDR-511 3 SMD-401M 3 SESMDR-501 3 SMD-401EF 3 SMDR-501 3 HSD-401 3

SMDR-502 3 NOTE: Accessories and options vary by manufacturing location. Refer to CAPS to determine what is available. SSDFDR-510 3 SSFDR-510 3 Greenheck Fan Corporation Greenheck India Pvt., Ltd. P.O. Box 410 541/542, 5th Floor, Tower B3 SSFSDR-511 3 Schofield, WI 54476 Spaze I-Tech Park, Sector-49 U.S.A. Sohna Road, Gurgaon, India SSFSDR-512 3 Tel. (715) 359-6171 +91-124-4272494 SSSMDR-501 3 www.greenheck.com www.greenheck.co.in

62 We don’t “value engineer” - we engineer value.

63 Design and Selection Support Fire Dampers

Enjoy Greenheck’s extraordinary service, before, during and after the sale.

Greenheck offers added value to our wide selection of top performing, energy- efficient products by providing several unique Greenheck service programs. • Greenheck’s free Computer Aided Product Selection program (CAPS), rated by many as the best in the industry. CAPS helps you conveniently and efficiently select the right products for the challenge at hand.

• Greenheck has been Green for a long time! Our energy-saving products and ongoing corporate commitment to sustainability can help you qualify for LEED credits.

Find out more about these special Greenheck services at greenheck.com or greenheck.co.in.

Building Value in Air

Greenheck delivers value top quality, innovative air- And building owners and to mechanical engineers by related equipment. We offer occupants value the energy helping them solve virtually extra value to contractors efficiency, low maintenance any air quality challenges by providing easy-to-install, and quiet dependable operation their clients face with a competitively priced, reliable they experience long after the comprehensive selection of products that arrive on time. construction project ends.

Our Commitment

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.

Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. Prepared to Support Green Building Efforts

International 00.DMP.1000 R5 6-2018 Copyright © 2018 Greenheck Fan Corp.

Greenheck India: 541/542, 5th Floor, Tower B, Spaze i Tech Park, Sector-49, Sohna Road, Gurgaon • 011-91-124-4272494 • greenheck.co.in 64 Greenheck U.S.A.: P.O. Box 410 • Schofield, WI 54476-0410 • Phone 715-359-6171 • greenheck.com