COASTAL CITY OF HAMPTON E N G I N E E R I N G 2406 Princess Anne Road, Suite 200 Virginia Beach, VA 23456 Phone (757) 563-9027 Facsimile(757) 563-9028

TH EAL OF W V N IR O G M I N M I

O A

C RICHARD M. KLEIN No. 027864 P R R O E F E E N SS GI HVAC UPGRADE IONAL EN HAMPTON HEALTH DEPARTMENT

HAMPTON, VIRGINIA

COASTAL ENGINEERING CONSULTING ENGINEERS JAK RMK RMK

2406 PRINCESS ANNE RD, SUITE 200 15-041

VIRGINIA BEACH, VA 23456 01-06-2017 PHONE: (757) 563-9027 FAX: (757) 563-9028

LOCATION MAP

VICINITY MAP DRAWING INDEX: T-1.0 TITLE SHEET

S-101 STRUCTURAL FRAMING PLAN S-201 STRUCTURAL SECTIONS AND DETAILS

M-001 MECHANICAL LEGEND, NOTES, ABBREVIATIONS M-002 MECHANICAL PLAN - PHASING M-101 MECHANICAL FLOOR PLAN - DEMOLITION M-201 MECHANICAL FLOOR PLAN - NEW WORK M-202 MECHANICAL ROOF PLAN - NEW WORK M-401 MECHANICAL ENLARGED PLANS, DETAILS AND SCHEDULES CITY OF HAMPTON M-701 MECHANICAL SPECIFICATIONS TITLE SHEET

E-001 ELECTRICAL LEGEND, NOTES, ABBREVIATIONS E-101 ELECTRICAL FLOOR PLAN - DEMOLITION POWER E-102 ELECTRICAL FLOOR PLAN - DEMOLITION E-201 ELECTRICAL FLOOR PLAN - NEW WORK POWER E-202 ELECTRICAL FLOOR PLAN - NEW WORK LIGHTING HAMPTON, VA SITE LOCATION: E-501 ELECTRICAL PANEL BOARD SCHEDULES NORTH NORTH T-1.0 E-601 ELECTRICAL RISER DIAGRAM, PANEL BOARD NOT TO SCALE 3130 VICTORIA BLVD. NOT TO SCALE SCHEDULES, AND LOAD SUMMARY HAMPTON, VA 23661 1 18 E-701 ELECTRICAL SPECIFICATIONS

MECHANICAL LEGEND GENERAL NOTES NOTE: HEAVY LINE WEIGHT INDICATES NEW EQUIPMENT OR EQUIPMENT TO BE REMOVED, LIGHT LINE WEIGHT INDICATES EQUIPMENT WHICH IS 1. SCOPE OF WORK INCLUDES PROVIDING A FIRST CLASS WORKING SYSTEM IN COMPLIANCE WITH THESE DRAWINGS AND GRILLE REGISTER AND DIFFUSER SCHEDULE EXISTING TO REMAIN SPECIFICATIONS, TESTED READY FOR OPERATION COMPLETE WITH LABOR, MATERIALS, APPARATUS, TRANSPORTATION, AND TOOLS REQUIRED FOR THE INSTALLATION. MANUFACTURER / NECK MAX. MARK TYPE SERVICE APD "WC REMARKS POINT OF CONNECTION-NEW TO EXISTING AND MODEL SIZE CFM COASTAL POINT OF DEMOLITION TERMINATION 2. COORDINATE WORK WITH THAT OF OTHER TRADES. SEE ARCHITECTURAL REFLECTED PLANS FOR THE EXACT E N G I N E E R I N G LOCATIONS OF CEILING MOUNTED DEVICES. ANEMOSTAT / 24 X 24 A SUPPLY 6" Ø 120 .03 3 2 DUCT SMOKE DETECTOR MODEL EPL LAY-IN 2406 Princess Anne Road, 3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MODIFICATIONS, CHANGES, ETC. FOR THE EQUIPMENT HE PROVIDES, Suite 200 A GRILLE OR DIFFUSER MARK - SEE SCHEDULE OR EVEN IF APPROVED AS AN EQUAL. Virginia Beach, VA 23456 SPECIFICATION (CFM NOTE) SURFACE 100 ANEMOSTAT/ Phone (757) 563-9027 4. MISCELLANEOUS ITEMS NOT SHOWN ON THE PLANS BUT NECESSARY FOR A COMPLETE OPERABLE SYSTEM, SHALL BE B 1 MOUNT SUPPLY 6" Ø 155 .05 3 2 Facsimile(757) 563-9028 NEW WORK NOTE MARK MODEL E-1 SUPPLIED AND INSTALLED. 24 X 24 TH DEMOLITION WORK NOTE MARK 5. INSTALL EQUIPMENT PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. MAINTAIN ALL RECOMMENDED CLEARANCES. EAL OF W V N IR O G SURFACE M I N CHILLED WATER SUPPLY 6. REMOVE EXCESS MATERIAL, SCRAP, ETC. FROM THE JOB SITE. M ANEMOSTAT/ I C O A 1 MOUNT SUPPLY 6" Ø 120 .06 3 2 C RICHARD M. KLEIN CHILLED WATER RETURN 7. REPAIR ANY MATERIAL OR WORK WHICH HE HAS DAMAGED. MODEL E-1 12 X 12 No. 027864 P HOT WATER SUPPLY PIPING R R O E 8. BALANCE AIR AND WATER SYSTEMS WITHIN ±10% OF THE VALUES INDICATED. F E E N SS GI HOT WATER RETURN PIPING ANEMOSTAT/ 24 X 24 IONAL EN 9. TEST THE ENTIRE SYSTEM IN ALL MODES OF OPERATION TO INSURE PROPER OPERATION. D SUPPLY 8" Ø 245 .05 3 2 CONDENSER WATER SUPPLY MODEL EPL LAY-IN 10. FURNISH AND INSTALL ALL EQUIPMENT AND MATERIALS FOR A COMPLETE INSTALLATION IN ALL RESPECTS READY OF CONDENSER WATER RETURN INTENDED USE AND IN STRICT ACCORDANCE WITH ALL STATE AND LOCAL CODES AND MANUFACTURER'S RECOMMENDATIONS. PAY NECESSARY FEES AND OBTAIN PERMITS. INITIATE, MAINTAIN AND SUPERVISE ALL SAFETY SURFACE ANEMOSTAT/ DUAL TEMPERATURE SUPPLY PRECAUTIONS AND PROCEDURES. E MOUNT SUPPLY 4" Ø 60 .05 3 2 MODEL E-1 1 DUAL TEMPERATURE RETURN 11. ALL INDICATED DUCT DIMENSIONS ARE INSIDE CLEAR DIMENSIONS. 12 X 12 CONDENSATE DRAIN SEQUENCE OF OPERATION 24 X 24 GAS PIPING ANEMOSTAT / X 1 SURFACE RETURN 10x10 200 .05 3 2 ROOF TOP UNIT (RTU-1, RTU-2, RTU-3, RTU-4, RTU-5, RTU-6, RTU-7, RTU-8) MODEL 30 BACKFLOW PREVENTER MOUNT BALANCING VALVE (GLOBE VALVE/SQUARE HEAD COCK) THE PROGRAMMABLE SPACE THERMOSTAT SHALL INDEX THE OCCUPIED AND UNOCCUPIED MODE OF OPERATION BASED ON A USER SELECTED SCHEDULE. THE SPACE THERMOSTAT SHALL CONTROL THE HEATING SET POINT, 68 DEGREES F 24 X 24 BALL VALVE ANEMOSTAT / (ADJUSTABLE) THE COOLING SET POINT, 75 DEGREES F (ADJUSTABLE), AND THE SETUP/SET BACK TEMPERATURE. Y 1 SURFACE RETURN 12x12 300 .05 3 2 MODEL 30 CHECK VALVE MOUNT OCCUPIED MODE BUTTERFLY VALVE 24 X 24 ANEMOSTAT / Z 1 SURFACE RETURN 16x16 550 .05 3 2 STRAINER WITH BLOW DOWN VALVE THE SUPPLY FAN SHALL ENERGIZE AND RUN CONTINUOUSLY. THE UNITS CORRESPONDING CO2 SENSOR SHALL BE ACTIVATED MODEL 30 AND THE SENSOR SHALL MODULATE THE UNITS OUTSIDE AIR DAMPER TO MAINTAIN THE SPACE CO2 SET POINT. MOUNT 3-WAY AUTO CONTROL VALVE NOTES: PRESSURE REDUCING VALVE HEATING MODE 1 SURFACE MOUNT GRILLE, LAY-IN PANELS CAN BE USED WHERE CEILING GRID ALLOWS 2-WAY AUTO CONTROL VALVE ON A FALL IN SPACE TEMPERATURE BELOW THE HEATING SET POINT (ADJUSTABLE) THE PROGRAMMABLE SPACE 2 ALUMINUM CONSTRUCTION THERMOMETER THERMOSTAT SHALL CYCLE THE ROOF TOP UNITS GAS FIRED HEATING SECTION TO MAINTAIN THE HEATING SET POINT. ON A 3 COLOR TO BE WHITE RISE IN SPACE TEMPERATURE ABOVE THE SET POINT WITH A 3 DEGREE FAHRENHEIT DEAD BAND (ADJUSTABLE) THE REVERSE

FLEXIBLE PIPING CONNECTION JAK RMK SHALL OCCUR. RMK 15-041 PRESSURE GAUGE SHUT-OFF COCK COOLING MODE 01-06-2017 AUTOMATIC AIR VENT

UNION ON A RISE IN SPACE TEMPERATURE ABOVE THE COOLING SET POINT (ADJUSTABLE) THE PROGRAMMABLE SPACE THERMOSTAT SHALL CYCLE THE ROOF TOP UNITS COMPRESSOR SECTION TO MAINTAIN THE COOLING SET POINT. ON A ON A PIPE SLOPE (DOWN IN ARROW DIRECTION) FALL IN SPACE TEMPERATURE BELOW THE SET POINT WITH A 3 DEGREE FAHRENHEIT DEAD BAND (ADJUSTABLE) THE REVERSE FLOW CONTROL BALANCING VALVE WITH SHALL OCCUR. GAS SHUT-OFF COCK

PRESSURE TAPS (GPM NOTED) UNOCCUPIED MODE

RELIEF VALVE THE SPACE THERMOSTAT SHALL CYCLE THE UNITS SUPPLY AIR FAN AND HEATING AND COOLING SYSTEMS TO MAINTAIN THE ECCENTRIC PIPE REDUCER HEATING SET BACK TEMPERATURE, 55 DEGREES F (ADJUSTABLE) AND THE COOLING SET UP TEMPERATURE, 85 DEGREES F (ADJUSTABLE) WITH A 3 DEGREE FAHRENHEIT DEAD BAND (ADJUSTABLE). THE UNITS OUTSIDE AIR DAMPER SHALL REMAIN PIPE CAP CLOSED.

DIRECTION OF FLOW SMOKE DETECTOR PIPE ANCHOR

SUPPLY DUCT SECTION THE DUCT MOUNTED SMOKE DETECTOR SHALL SHUT DOWN THE SUPPLY AIR FAN AND CLOSE THE OUTSIDE AIR DAMPER UPON SENSING PRODUCTS OF COMBUSTION. THE SMOKE DETECTOR SHALL ALSO SEND A SIGNAL TO THE FIRE ALARM EXHAUST DUCT SECTION SYSTEM. ACTIVATION OF THE SMOKE DETECTOR SHALL REQUIRE MANUAL RESET PRIOR TO THE UNIT BEING PLACED BACK IN OPERATION. RETURN DUCT SECTION

FD FIRE DAMPER WITH ACCESS ABBREVIATIONS

T THERMOSTAT/SENSOR MOUNT 48" ABOVE FLOOR AD ACCESS DOOR EWB ENTERING WET BULB LDB LEAVING DRY BULB RTU-1 ROOF TOP UNIT MARK RTU-1 SUBSCRIPT INDICATES EQUIPMENT BEING CONTROLLED AFF ABOVE FINISHED FLOOR EWT ENTERING WATER TEMPERATURE LWB LEAVING WET BULB SA SUPPLY AIR AFG ABOVE FINISHED GRADE ESP EXTERNAL STATIC PRESSURE LWT LEAVING WATER TEMPERATURE SCT SATURATED CONDENSING TEMPERATURE ELBOW WITH TURNING VANES APD AIR PRESSURE DROP EXIST EXISTING MAX MAXIMUM SEER SEASONAL ENERGY EFFICIENCY RATING APPROX APPROXIMATELY FCU-1 FAN COIL UNIT MARK MOCP MAXIMUM OVER CURRENT PROTECTION SF SQUARE FEET BD MANUAL BALANCING DAMPER WITH LOCKING QUADRANT AS-1 AIR SEPARATOR MARK FD FIRE DAMPER WITH ACCESS DOOR MIN MINIMUM SP STATIC PRESSURE FDB DEGREE FAHRENHEIT DRY BULB MBH THOUSAND BTU/HR SST SATURATED SUCTION TEMPERATURE FLEXIBLE DUCT CONNECTION BD BALANCING DAMPER CITY OF HAMPTON

BDD BACK DRAFT DAMPER FF FINISHED FLOOR MCA MINIMUM CIRCUIT AMPS TS TIP SPEED MECHANICAL LEGEND, NOTES, ABBREVIATIONS LOW PRESSURE SUPPLY OR RETURN DUCT WORK BTUH BRITISH THERMAL UNIT PER HOUR FPM FEET PER MINUTE MFS MAXIMUM FUSE SIZE T'STAT THERMOSTAT CFH CUBIC FEET PER HOUR FT FEET NOM NOMINAL TYP TYPICAL CFM CUBIC FEET PER MINUTE FWB DEGREE FAHRENHEIT WET BULB NO NUMBER "WC INCHES WATER FLEXIBLE DUCT CONNECTION WITH BALANCING DAMPER CHLR-1 MARK - SEE SCHEDULE GA GAUGE OA OUTSIDE AIR WPD WATER PRESSURE DROP COP COEFFICIENT OF PERFORMANCE GPH GALLONS PER HOUR OD OUTSIDE DIAMETER CU-1 CONDENSING UNIT MARK GPM GALLONS PER MINUTE P-1 PUMP MARK CWR CHILLED WATER RETURN "HG INCHES OF MERCURY PD PRESSURE DROP CWS CHILLED WATER SUPPLY HP HORSE POWER PH PHASE DN DOWN HWR HOT WATER RETURN PSIG POUNDS PER SQUARE INCH GAGE DSS-1 DUCTLESS SPLIT SYSTEM MARK HWS HOT WATER SUPPLY RA RETURN AIR EAT ENTERING AIR TEMPERATURE ID INSIDE DIAMETER RBJ RUN BETWEEN JOIST M-001 EDB ENTERING DRY BULB KW KILOWATT RLA RATED LOAD AMPS EF-1 EXHAUST FAN MARK LAT LEAVING AIR TEMPERATURE RPM REVOLUTIONS PER MINUTE EMD END OF MAIN DRIP LBS/HR POUND PER HOUR RTJ RUN THRU JOIST 4 18 ALL WORK IN THIS AREA SHALL BE DONE ON NIGHTS OR WEEKENDS. THE ALL WORK IN THIS AREA SHALL BE DONE ON NIGHTS OR PHASING NOTES: (THIS SHEET ONLY) ENTRANCE AND TOILETS SHALL REMAIN OPEN TO THE PUBLIC WITH WEEKENDS, ENTRANCE SHALL REMAIN OPEN TO THE ACCESS TO THE AT ALL TIMES (TOILETS ARE THE ONLY PUBLIC AT ALL TIMES (THIS IS THE ONLY HANDICAPPED 1. ALL WORK ASSOCIATED WITH THIS PROJECT SHALL BE PHASED IN HANDICAPPED ACCESSIBLE TOILETS IN THE BUILDING). ACCESSIBLE ENTRANCE TO THE BUILDING.) ACCORDANCE WITH THE PHASING PLAN. THE CONTRACTOR SHALL COORDINATE CLOSELY WITH THE FACILITIES DIRECTOR AND MAKE COASTAL STOR STOR ADJUSTMENTS TO THE CONSTRUCTION OPERATIONS AS REQUIRED TO E N G I N E E R I N G DRUG 01 02 UTIL PHYSICIAN INSURE THAT THE AREAS OF THE PROJECT THAT ARE NOT UNDER THE CLINIC DRESSING PHYS. 01 & EXAM 2406 Princess Anne Road, OFFICE CURRENT PHASE OF WORK REMAIN OPEN AND FULLY ACCESSIBLE AND 01 Suite 200 SEE SHEET M-401 FOR EXAM EXAM X-RAY OPERATIONAL. 01 Virginia Beach, VA 23456 WORK IN THIS AREA 02 2. THE ONLY WHEEL CHAIR ACCESSIBLE ENTRANCE TO THE BUILDING IS Phone (757) 563-9027 X-RAY & Facsimile(757) 563-9028 PHYSICIAN EXAM MENTAL DARK LOCATED AT THE SOUTHWEST CORNER. THIS ENTRANCE SHALL TOILET 01 02 03 AFTERCARE 02 REMAIN OPEN AND FULLY ACCESSIBLE TO THE PUBLIC DURING ALL TH OPERATING HOURS. WORK IN THIS AREA SHALL BE PERFORMED AT EAL OF W V N IR VEST 02 NIGHT OR ON WEEKENDS. O G M I N VEST 01 01 M PHASE 2 I 3. PIPE INSULATION ON THE ELBOWS AND FITTING OF THE DUEL O A C TEMPERATURE AND DOMESTIC PIPING LOCATED ABOVE THE RICHARD M. KLEIN CEILING HAS BEEN IDENTIFIED AS ASBESTOS CONTAINING MATERIAL No. 027864 P DENTAL R R LAB DENTAL O E EXAM CLERICAL AND SHALL UNDERGO ABATEMENT PRIOR TO PREFORMING ANY WORK F E EXAM EXAM 02 03 EXAM E N 01 SS GI 08 09 10 04 IN THE ASSOCIATED AREA. THE CITY OF HAMPTON HAS A SEPARATE IONAL EN TOILET TOILET CONTRACT FOR ASBESTOS ABATEMENT WITH WACO INC. WHO WILL BE 11 10 WAITING CONTRACTED THROUGH THE CITY OF HAMPTON TO PERFORM THE LIBRARY EKG 01 ASBESTOS ABATEMENT FOR THIS PROJECT. THE CONTRACTOR SHALL COORDINATE AND SCHEDULE FOR WACO TO BE ONSITE FOR THE OBSERVATION CLERK DENTAL STOR 01 05 PHYSICIAN UTIL ABATEMENT AND TESTING OF EACH PHASE OF WORK PRIOR TO STOR STOR 03 02 COMMENCING ANY DEMOLITION WORK WHICH COULD DISTURB 03 04 DENTAL ASBESTOS CONTAMINATED MATERIALS. THE CONTRACTOR SHALL BE PSYCHOLOGIST HALL RESPONSIBLE FOR THE REMOVAL, STORAGE, AND REINSTALLATION OF CEILING COMPONENTS INCLUDING TILES, GRIDS, LIGHTING FIXTURES, AND CEILING MOUNTED DEVICES AS REQUIRED TO PROVIDE ACCESS TO PHASE 4 EXAM CLERICAL 05 PIPING REQUIRING ABATEMENT. 03 SOCIAL 4. THE EXISTING CHILLED / HOT WATER PLANT SHALL REMAIN WORKER WAITING OPERATIONAL THROUGHOUT THE CONSTRUCTION PHASE AS REQUIRED THIS AREA IS NOT IN 02 HALL TO PROVIDE COMFORT HEATING AND COOLING TO PHASED AREAS OF 04 CONTRACT, AREA SHALL REMAIN ACCESSIBLE THE BUILDING IN WHICH WORK HAS NOT YET BEEN PERFORMED. PRIOR NURSE HALL THROUGHOUT EXAM TO TURNING OVER ANY PHASED AREA OF THE BUILDING AND STARTING 02 06 CONSTRUCTION. ALL WORK IN THIS AREA WORK IN THE NEXT PHASE THE NEW HVAC SYSTEM SHALL BE SHALL BE DONE ON NIGHTS COMPLETELY OPERATIONAL. OR WEEKENDS, ROOM TOILET TOILET STORAGE SHALL REMAIN ACCESSIBLE 09 03 04 5. THE GENERAL LAYOUT OF THE DUEL TEMPERATURE PIPING UTILIZES TO USER AT ALL TIMES MAINS RUN THROUGH THE CORRIDOR CEILING WITH BRANCH RUN OUT AUDITORIUM UTIL PIPES WHICH SERVE GROUPS OF APPROXIMATELY 1-4 FAN COIL UNITS NURSES PHYSICIAN 03 LOCATE MAINLY ALONG THE EXTERIOR OF THE BUILDING. THE & CLERK 04 04 PIPE RUNOUTS SHALL BE REMOVED FROM THE CORRIDOR PHASE 1 PENETRATIONS THROUGH THE EXTERIOR WALL PENETRATIONS, THE MAINS AND PIPING LOCATED WITHIN THE EXTERIOR WALLS MAY BE JAK RMK ABANDONED IN PLACE. DURING WORK ON THE FIRST THREE PHASES RMK EXAM OF CONSTRUCTION THE REMAINING TAPS OFF OF THE MAINS SHALL BE 15-041 07 TOILET CAPPED TO ALLOW THE SYSTEM TO REMAIN IN OPERATION. THE 01-06-2017 09 RECORDS CONTRACTOR SHALL PERFORM ALL SYSTEM OUTAGES REQUIRED FOR STOR ROOM 08 THE DEMOLITION OF PIPING DURING EACH PHASE AT NIGHT OR OVER TOILET WEEKENDS AND HAVE THE REMAINING TAPS CAPPED AND THE SYSTEM NURSES 05 OPERATIONAL PRIOR TO THE NEXT SCHEDULED BUSINESS DAY. & CLERK TOILET 03 SYSTEM DOWN TIMES SHALL BE COORDINATED WITH WEATHER 08 CONDITIONS OR TEMPORARY PROVISIONS SHALL BE PROVIDED TO TOILET 06 INSURE THAT THE BUILDING IS NOT EXPOSED TO FREEZING LOUNGE hall CONDITIONS. MECH. STOR 6. THE RECORDS STORAGE ROOM SHALL REMAIN ACCESSIBLE TO THE EQUIP STORAGE STAFF DURING ALL BUSINESS HOURS; ALL WORK IN THIS AREA SHALL LOUNGE 06 BE PERFORMED AT NIGHT OR OVER WEEKENDS.

KITCHEN 7. THE PUBLIC TOILETS IN THE SOUTHEAST CORNER OF THE BUILDING SHALL REMAIN ACCESSIBLE TO THE PUBLIC AND OPERATIONAL DURING NURSES & NURSES NURSE & CLERICAL ALL BUSINESS HOURS; ALL WORK IN THIS AREA SHALL BE PERFORMED CLERK SUPER CLERK 01 02 AT NIGHT OR OVER WEEKENDS. SOCIAL 02 SERVICE 8. THE FOUR ENTRANCES SHALL REMAIN ACCESSIBLE AND ACCESSIBLE PHARMACY BY THE PUBLIC DURING ALL BUSINESS HOURS; ALL WORK IN THIS AREA SHALL BE PERFORMED AT NIGHT OR OVER WEEKENDS. 9. THE AUDITORIUM SHALL REMAIN ACCESSIBLE AND ACCESSIBLE BY THE VEST 04 HALL PHASE 3 03 PUBLIC DURING ALL BUSINESS HOURS; ALL WORK IN THIS AREA SHALL BE PERFORMED AT NIGHT OR OVER WEEKENDS. STOR 07 VEST 03

VITAL SANITARIANS SANIT. ADMIN ASST RECEPT. DIRECTOR CONF. SUPER ASST DIR. STATISTICS

TOILET CITY OF HAMPTON 07 MECHANICAL FLOOR PLAN - PHASING

WORK IN THIS AREA SHALL BE DONE ON NIGHTS OR WORK IN THIS AREA SHALL BE DONE ON NIGHTS OR WEEKENDS, ENTRANCE AREA SHALL REMAIN OPEN WEEKENDS, ENTRANCE AREA SHALL REMAIN OPEN TO THE PUBLIC FOR ACCESS TO THE PHASE WHICH TO THE PUBLIC FOR ACCESS TO THE PHASE WHICH IS NOT UNDER CONSTRUCTION AT ALL TIMES IS NOT UNDER CONSTRUCTION AT ALL TIMES

GRAPHIC SCALE M-002 MECHANICAL FLOOR PLAN - PHASING 0' 4' 8' 12' 20' 40' 1/8" = 1'-0" SCALE: 1/8" = 1'-0" 5 18 GENERAL NOTES: (THIS SHEET ONLY) DEMOLITION WORK NOTES: (THIS SHEET ONLY)

1. REMOVE AND REPLACE THE EXISTING CEILING AND ASSOCIATED LIGHTING REMOVE EXISTING 5 TON PACKAGED HORIZONTAL DISCHARGED AND FIXTURES AS REQUIRED FOR THE ASBESTOS ABATEMENT, DEMOLITION, AND RETURN ROOF TOP UNIT AND ALL ASSOCIATED DUCTWORK, ROOF CURB, NEW WORK. THE EXISTING CEILING TILES AND GRID SHALL BE RETAINED AND SUPPORTS, AND GAS PIPING BACK TO METER. COASTAL REINSTALLED AFTER COMPLETION OF THE WORK. HARD SHALL BE E N G I N E E R I N G REMOVE EXISTING 7.5 TON PACKAGED HORIZONTAL DISCHARGED AND PATCHED AND PAINTED TO MATCH EXISTING PROVIDE VALVE ACCESS AS RETURN ROOF TOP UNIT AND ALL ASSOCIATED DUCTWORK, ROOF CURB, REQUIRED TO ACCESS ABOVE CEILING VALVES. REFER TO THE ELECTRICAL 2406 Princess Anne Road, SUPPORTS, AND GAS PIPING BACK TO METER. Suite 200 LIGHTING PLANS (SHEETS E-102 AND 202) FOR CEILING TYPES AND NOTES. Virginia Beach, VA 23456 EXISTING PACKAGED ROOFTOP UNIT TO REMAIN, REMOVE GAS PIPING 12 13 (2) Phone (757) 563-9027 6 BACK TO METER, RETAIN EXISTING GAS TRAIN FOR RECONNECTION. Facsimile(757) 563-9028 STOR 01 STOR 02 REMOVE EXISTING GAS PIPE RUN ACROSS ROOF AND DOWN WALL AND 9 9 9 9 PHYSICIAN 9 9 TH UTIL ASSOCIATED SUPPORTS BACK TO METER. EAL OF (6) W V 6 01 12 DRUG CLINIC & EXAM N I PHYS. O R DRESSING G OFFICE M I SEE SHEET M-401 FOR 01 EXAM EXAM N X-RAY COORDINATE WITH VIRGINIA NATIONAL GAS TO PROVIDE NEW GAS M I WORK IN THIS AREA 01 02 6 O A 12 (18) 12 (6) 6 6 6 METER AND SERVICE. SEE NEW WORK PLANS. C 6 (18) 12 12 (6) RICHARD M. KLEIN PHYSICIAN 6 EXAM 6 X-RAY & No. 027864 6 TOILET REMOVE EXISTING SUPPLY AIR DIFFUSER AND ALL ASSOCIATED DUCT TOILET 02 03 MENTAL DARK P 1 R R 8 02 8 O E 01 AFTERCARE ROOM WORK, PATCH CEILING TO MATCH EXISTING. F E E N SS GI IONAL EN VEST 02 REMOVE EXISTING RETURN AIR GRILLE AND ALL ASSOCIATED VEST 01 9 HALL 01 9 DUCTWORK, PATCH CEILING TO MATCH EXISTING. 5 4 6 REMOVE EXISTING DUCTWORK AND ALL ASSOCIATED INSULATION AND 6 6 (6) 12 HANGERS FROM AIR DISTRIBUTION DEVICES COMPLETELY. 6 6 6 (16) 12 EXAM 6 CLERICAL LAB EXAM EXAM DENTAL DENTAL 9 6 08 6 6 6 01 6 6 EXAM REMOVE EXISTING FAN COIL UNIT AND ALL ASSOCIATED PIPING AND 12 (16) 09 10 (9) 12 02 6 03 HALL 04 HARDWARE, REMOVE DTS, DTR, AND CONDENSATE DRAIN PIPING TO 04 6 6 9 TOILET TOILET WITHIN THE WALL, PATCH AND PAINT WALL TO MATCH EXISTING. SEE WAITING 10 11 6 LIBRARY 6 6 01 6 DEMOLITION NOTE # 10, 11. (9) 12 6 DENTAL THE GENERAL LAYOUT OF THE DUEL TEMPERATURE PIPING UTILIZES CLERK 01 STOR 9 EKG OBSERVATION UTIL MAINS RUN THROUGH THE CORRIDOR CEILING WITH BRANCH RUN OUT 05 DENTAL 6 9 9 9 9 9 9 02 6 STOR HALL 6 PIPES WHICH SERVE GROUPS OF APPROXIMATELY 1-4 FAN COIL UNITS STOR PHYSICIAN PSYCHOLOGIST 03 LOCATED MAINLY ALONG THE EXTERIOR WALLS OF THE BUILDING. THE 04 03 PIPE RUN-OUTS SHALL BE REMOVED FROM THE CORRIDOR WALL 6 PENETRATIONS THROUGH THE EXTERIOR WALL PENETRATIONS, THE 6 MAINS AND PIPING LOCATED WITHIN THE EXTERIOR WALLS MAY BE 6 ABANDONED IN PLACE. DURING WORK ON THE FIRST THREE PHASES OF 9 CLERICAL 6 9 OF CONSTRUCTION THE REMAINING TAPS OFF OF THE MAINS SHALL BE 03 EXAM CAPPED TO ALLOW THE SYSTEM TO REMAIN IN OPERATION. 8 05 8 SOCIAL (6) 12 WORKER 6 REFER TO ASBESTOS NOTES FOR ABATEMENT PROCEDURES PRIOR TO WAITING HALL PERFORMING ANY DEMOLITION WORK. 6 02 02 9 9 EXAM ABATE ASBESTOS CONTAMINATED INSULATION ON THE DOMESTIC HOT 6 9 06 AND COLD WATER PIPE FITTINGS ABOVE THE CEILING AND RE-INSULATE NURSE 6 6 THE PIPES TO MATCH EXISTING, PROVIDE VAPOR BOUNDARIES ON COLD TOILET TOILET WATER PIPING. GENERAL AREA OF WORK INDICATED WITH APPROXIMATE STORAGE 2 03 04 6 NUMBER OF FITTINGS TO BE ABATED NOTED, FIELD VERIFY EXACT 09 NURSES & 6 NUMBER AND LOCATION. JAK RMK CLERK RMK 04 AUDITORIUM 15-041 6 3/4" DOMESTIC COLD WATER PIPE TO HOSE BIB CUT AND REROUTE AS 9 01-06-2017 6 PHYSICIAN UTIL REQUIRED FOR DUCT INSULATION. COURTYARD 04 03 6 ASBESTOS NOTES: (THIS SHEET ONLY) 6 6 9 1. PIPE INSULATION MASTIC ON THE ELBOWS, FITTINGS, AND SEAMS OF THE 9 (6) 12 EXAM 9 DUEL TEMPERATURE PIPING AND THE INSULATION ON THE FITTINGS OF THE TOILET 07 DOMESTIC HOT AND COLD WATER PLUMBING PIPING LOCATED ABOVE THE 09 6 NURSES & RECORDS 9 CEILING HAS BEEN IDENTIFIED AS ASBESTOS CONTAINING MATERIAL AND (14) 12 STOR CLERK ROOM SHALL UNDERGO ABATEMENT PRIOR TO PREFORMING ANY WORK IN THE 08 TOILET 12 (16) 03 ASSOCIATED AREA. THE CITY OF HAMPTON HAS A SEPARATE CONTRACT FOR 3 9 05 8 ASBESTOS ABATEMENT WITH WACO INC. WHO WILL BE CONTRACTED TOILET THROUGH THE CITY OF HAMPTON TO PERFORM THE ASBESTOS ABATEMENT 08 LOUNGE 6 (14) 12 9 hall FOR THIS PROJECT. THE CONTRACTOR SHALL COORDINATE AND SCHEDULE 6 12 (16) TOILET FOR WACO TO BE ONSITE FOR THE ABATEMENT AND TESTING OF EACH 06 PHASE OF WORK PRIOR TO COMMENCING ANY DEMOLITION WORK WHICH MECH. STOR COULD DISTURB ASBESTOS CONTAMINATED MATERIALS. THE CONTRACTOR EQUIP 9 SHALL BE RESPONSIBLE FOR THE REMOVAL, STORAGE, AND REINSTALLATION STORAGE LOUNGE 6 06 OF CEILING COMPONENTS INCLUDING TILES, GRIDS, LIGHTING FIXTURES, AND NURSES & NURSES CEILING MOUNTED DEVICES AS REQUIRED TO PROVIDE ACCESS TO PIPING CLERK SUPER 9 9 9 9 REQUIRING ABATEMENT. 02 6 6 6 2. THE PIPE MAINS IN THE CORRIDORS SHALL REMAIN AND BE ABANDONED IN NURSE & 9 9 CLERK 01 CLERICAL PLACE. IF THE CONTRACTORS WORK WILL DISTURB ANY OF PIPING IN THESE 02 AREAS, COORDINATE WITH THE CITY OF HAMPTON AND WACO TO HAVE ANY SOCIAL 10 11 (TYP.) WITH VARIATIONS BASED ON LOCATION, 9 FIELD VERIFY EXACT PIPE ROUTING AND ASBESTOS CONTAMINATED MATERIALS WHICH ME BE AFFECTED ABATED SERVICE 6 CONFIGURATION FOR EACH RUNOUT. PHARMACY PRIOR TO COMMENCING ANY WORK IN THE AREA. 3. WACO INC. WILL PERFORM THE ASBESTOS ABATEMENT WORK ON THIS HALL 9 9 9 PROJECT UNDER A DIRECT CONTRACT WITH THE CITY OF HAMPTON. THE 9 VEST 04 8 03 GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION

AND SCHEDULING OF ALL ASBESTOS ABATEMENT WORK TO BE PERFORMED CITY OF HAMPTON MECHANICAL FLOOR PLAN - DEMOLITION STOR UNDER THIS CONTRACT. ASBESTOS ABATEMENT WORK SHALL BE 07 9 SCHEDULED AND PHASED ALONG WITH THE WORK IN ACCORDANCE WITH THE VEST 03 VITAL PHASING PLAN SUCH THAT EACH PORTION OF THE BUILDING IS ONLY SHUT SANITARIANS SANIT. ADMIN ASST RECEPT. DIRECTOR SUPER ASST DIR. CONF. STATISTICS DOWN ONCE.

TOILET 4. ANY ADDITIONAL ASBESTOS WORK OR MOBILIZATION WHICH RESULTS FROM 9 9 9 9 9 9 9 9 9 9 9 07 THE CONTRACTOR'S LACK OF COORDINATION OR SCHEDULING WITH WACO INC. WHICH COULD HAVE BEEN AVOIDED SHALL BE RESPONSIBILITY OF THE CONTRACTOR. M-101 GRAPHIC SCALE MECHANICAL FLOOR PLAN - DEMOLITION 0' 4' 8' 12' 20' 40' SCALE: 1/8" = 1'-0" 1/8" = 1'-0" 6 18 NEW WORK NOTES: (THIS SHEET ONLY)

ROOM HAS A HARD CEILING, CUT, PATCH, AND PAINT TO MATCH EXISTING AS REQUIRED FOR WORK IN THIS AREA. WHERE WORK REQUIRES CEILING REPAIRS AND PAINTING, THE ENTIRE CEILING SHALL BE COASTAL REPAINTED. E N G I N E E R I N G SURFACE MOUNTED DIFFUSER. 2406 Princess Anne Road, Suite 200 Virginia Beach, VA 23456 Phone (757) 563-9027 2 2 2 GENERAL NOTES: (THIS SHEET ONLY) Facsimile(757) 563-9028 UTIL STOR DRUG CLINIC 01 01 STOR 02 1. THE DESIGN DOCUMENTS PROVIDE A DIAGRAMMATIC DEPICTION OF PHYSICIAN 6" Ø 6" Ø 6" Ø OFFICE TH EXAM 18x6 6" Ø THE GENERAL LOCATION OF THE NEW ROOF TOP UNITS, DUCT WORK EAL OF & EXAM 6" Ø 12x10 6x12 W V 02 N I PHYS. 10x12 8" Ø 14x12 DRESSING 10x12 O R 6x12 EXAM 24x14 AND ROUTING, AND AIR DISTRIBUTION DEVICES. THE SPACE ABOVE THE G 16x12 X-RAY M I SEE SHEET M-401 FOR 01 2 12x10 N 01 M CEILING IS EXTREMELY LIMITED AND CONGESTED IN SOME AREAS, THE I WORK IN THIS AREA O A C 4" Ø 8" Ø 6" Ø 4" Ø CONTRACTOR SHALL ROUTE DUCTWORK AND AIR DISTRIBUTION RICHARD M. KLEIN X-RAY & 6" Ø MENTAL 6" Ø TOILET 01 PHYSICIAN 8" Ø 6" Ø 6" Ø TOILET DARK DEVICES AS REQUIRED TO AVOID CONFLICTS FROM EXISTING No. 027864 8" Ø AFTERCARE P 02 EXAM 02 6" Ø R R ROOM CONDITIONS. O E 03 F E ES IN SION ENG 1 12x10 1 VEST 02 2. REMOVE AND REPLACE THE EXISTING CEILING AND ASSOCIATED AL VEST 01 8" Ø 10x12 18x12 RTU-1 2 22x12 2 HALL 01 10x12 LIGHTING FIXTURES AS REQUIRED FOR THE ASBESTOS ABATEMENT, 8" Ø 8" Ø 18x12 22x12 RTU-5 16x12 DEMOLITION, AND NEW WORK. THE EXISTING CEILING TILES AND GRID 8" Ø 6" Ø SHALL BE RETAINED AND REINSTALLED AFTER COMPLETION OF THE EXAM CLERICAL DENTAL LAB DENTAL EXAM EKG 09 01 02 03 04 WORK. HARD CEILINGS SHALL BE PATCHED AND PAINTED TO MATCH 1 1 6" Ø 6" Ø 2 EXISTING PROVIDE VALVE ACCESS DOORS AS REQUIRED TO ACCESS 18x12 6" Ø 2 6" Ø 4" Ø 4" Ø 28x14 2 8x12 ABOVE CEILING VALVES. REFER TO THE ELECTRICAL LIGHTING PLANS EXAM EXAM 8" Ø 8" Ø 8" Ø 2 2 2 (SHEETS E-102 AND 202) FOR CEILING TYPES AND NOTES. 08 10 6" Ø WAITING 8x12 TOILET TOILET 6" Ø 01 12x10 6" Ø LIBRARY 10 11 6" Ø 3. ALL OF THE WALL IN THE FACILITY ARE CONSTRUCTED OF CMU BLOCK. OBSERVATION 12x10 CLERK DENTAL THE CORRIDOR WALLS AR FULL HEIGHT, LOAD BEARING WALLS. THE 8" Ø 6" Ø 12x10 6" Ø 6" Ø DENTAL STOR HALL 6" Ø DEMISING WALLS BETWEEN THE INDIVIDUAL EXTEND TO ABOUT 6" Ø 01 12x10 2 8" Ø 8" Ø STOR STOR 05 9” ABOVE THE CEILING AND TERMINATE APPROXIMATELY 10” BELOW 03 04 PHYSICIAN 2 UTIL 03 THE 8” BAR JOIST. ONE CORSE OF THE DEMISING WALLS BETWEEN THE 6" Ø 20x14 02 PSYCHOLOGIST INDIVIDUAL ROOMS MAY BE REMOVED AS REQUIRED FOR THE 8x12 14x12 14x12 6" Ø INSTALLATION OF THE NEW DUCTWORK. 8" Ø 12x12 18x12 24x14 8" Ø EXAM 05 8" Ø 12x12 SOCIAL 8" Ø WORKER 16x12 8" Ø CLERICAL 6" Ø 03 HALL WAITING HALL 04 02 02 8" Ø 16x12 NURSE 12x12 6" Ø 18x12 8" Ø 1 EXAM 14x12 6" Ø TOILET TOILET 1 06 20x12 03 04 JAK RMK STORAGE RMK 09 AUDITORIUM 4" Ø 2 12x10 2 15-041 8" Ø RTU-8 4" Ø 22x14 20x12 34x14 6" Ø 01-06-2017 COURTYARD 8" Ø PHYSICIAN UTIL 30x14 04 6" Ø 03 NURSES & RTU-4 CLERK 1 6" Ø 04 RTU-6 18x12 12x12 8" Ø 6" Ø RECORDS TOILET 10x12 ROOM RTU-2 26x14 09 EXAM 6" Ø 07 14x12 STOR 08 8" Ø 1 TOILET NURSES & 05 18x12 TOILET CLERK 10x12 08 12x12 03 6" Ø 6" Ø 4" Ø 6x12 1 22x12 TOILET 06 1 6" Ø 12x10 8" Ø MECH. STOR EQUIP LOUNGE 8" Ø hall 6" Ø 6" Ø 12x12 24x12 6" Ø 8" Ø LOUNGE 16x12 10x12 STORAGE 10x12 06 KITCHEN 14x12 SOCIAL 6" Ø SERVICE 8x12 6" Ø 6" Ø 6" Ø 8" Ø 6" Ø 8" Ø 8" Ø 12x10 2 CLERICAL 8" Ø NURSES & NURSES NURSE & 18x12 8" Ø 8" Ø 2 CLERK SUPER CLERK 01 02 02 6" Ø 6" Ø 8" Ø 12x10 PHARMACY HALL 18x12 RTU-7 8" Ø 12x10 6" Ø 6" Ø 03 RTU-3 VEST 04 20x12 18x12 12x12 6x10 CITY OF HAMPTON SANITARIANS CONF. 6" Ø 6" Ø MECHANICAL FLOOR PLAN - NEW WORK STOR 07 12x10 2 6" Ø ASST 8" Ø 8" Ø 8" Ø 8" Ø 8" Ø 8" Ø DIRECTOR VEST 03 DIR. 1 SANIT. ADMIN 6" Ø 6" Ø 8" Ø 8" Ø VITAL SUPER ASST 8" Ø 8" Ø 8" Ø STATISTICS 8" Ø 6" Ø RECEPT. TOILET 4" Ø 07 10x12 16x12 24x14 14x12 8x12 GRAPHIC SCALE M-201 MECHANICAL FLOOR PLAN - NEW WORK 0' 4' 8' 12' 20' 40' 1/8" = 1'-0" SCALE: 1/8" = 1'-0" 7 18 NEW WORK NOTES: (THIS SHEET ONLY)

PROVIDE GAS COCK, PRESSURE REGULATOR AND DIRT LEG AND 12" FLEXIBLE CONNECTION, GAS TRAIN SHALL BE IN ACCORDANCE WITH THE EQUIPMENT MANUFACTURERS RECOMMENDATIONS. COASTAL E N G I N E E R I N G CONNECT NEW GAS PIPING TO EXISTING ROOF TOP UNIT. FIELD VERIFY EXACT SIZE REQUIRED BY EXISTING EQUIPMENT AND RECOMMENDED BY 2406 Princess Anne Road, MANUFACTURER. Suite 200 Virginia Beach, VA 23456 PROVIDE TEMPORARY RECONNECTION OF EXISTING BOILER GAS PIPE, Phone (757) 563-9027 TO BE REMOVED WHEN ALL PHASES OF CONSTRUCTION ARE COMPLETE. Facsimile(757) 563-9028 PROVIDE NEW PRESSURE REGULATOR AS REQUIRED FOR 5 PSI DISTRIBUTION PRESSURE. TH EAL OF W V N IR O G M I N M I

O A

GAS SHUT C ROOF NOTES: (THIS SHEET ONLY) RICHARD M. KLEIN OFF VALVE No. 027864 THE EXISTING ROOF IS UNDER WARRANTY, COORDINATE ALL ROOF P R R O E RTU-1 MOUNTED WORK WITH THE ROOF MANUFACTURER TO INSURE THAT THE F E 1-1/4" GAS E N SS GI UP WORK IN NO WAY INTERFERES OR VOIDS THE EXISTING WARRANTY. IONAL EN 1 1" PROVIDE NEW 3 RTU-5 CONTACT CITY OF HAMPTON FACILITY'S FOR ROOF WARRANTY REGULATOR INFORMATION. RATED AT 1,440 GAS SHUT FT³/HR AT 5 PSIG OFF VALVE 1" DISCHARGE

(E) GAS METER 1-1/4" 1 1"

1"

1" GAS SHUT OFF VALVE 1 1" JAK RMK RMK 15-041 RTU-4 RTU-8 1" 01-06-2017 GAS SHUT OFF VALVE 1 1" GAS SHUT RTU-6 RTU-2 OFF VALVE 1 1" 1-1/4"

1"

1" GAS SHUT 1 1" GAS SHUT OFF VALVE OFF VALVE 1" 2 1 1"

1" (E) ROOF TOP UNIT (224 MBH)

1 1" RTU-7

GAS SHUT 1" OFF VALVE

RTU-3 CITY OF HAMPTON

1 1" MECHANICAL ROOF PLAN - NEW WORK

GAS SHUT OFF VALVE

GRAPHIC SCALE M-202 MECHANICAL ROOF PLAN - NEW WORK 0' 4' 8' 12' 20' 40' 1/8" = 1'-0" SCALE: 1/8" = 1'-0" 8 18 DEMOLITION WORK NOTES: (THIS SHEET ONLY) PREFAB ROOF CURB REMOVE ALL CHWR/CHWS, CWR/CWS, HWS/HWR AND DTS/DTR AND ALL FURNISHED WITH PVC CURB ASSOCIATED PUMPS, HANGERS AND HARDWARE COMPLETE. CAP, FAN OR AIRINTAKE PROVIDE HARD DUCT ELBOW OR SECURE CAP TO CURB WITH FLEX RIGHT ELBOW SUPPORT REMOVE EXISTING CHILLER COMPLETE. GALVANIZED SHEET METAL SCREWS (MIN 6" ON CENTER) FACTORY COASTAL REMOVE EXISTING COMPLETE. INSULATED E N G I N E E R I N G COUNTER FLASHING FLEXIBLE DUCT. REMOVE EXISTING BOILER AND FLUE COMPLETE. PATCH ROOF TO FULL NECK SIZE 2406 Princess Anne Road, MATCH EXISTING. OF DIFFUSER. Suite 200 CANT STRIP INSULATION CEILING Virginia Beach, VA 23456 REMOVE EXISTING COLD WATER PIPING FROM POINT INDICATED. LAP SEALANT Phone (757) 563-9027 VOLUME DAMPER Facsimile(757) 563-9028 REMOVE EXISTING GAS PIPING AND ALL ASSOCIATED HANGERS AND WOOD NAILER HARDWARE COMPLETE. DIFFUSER EXIST MEMBRANE TH ROOF CURB 2"x4" WOOD NAILER EAL OF ROOF W V STRIP (PROVIDE WITH UNIT) N IR REFER TO ASBESTOS NOTES FOR ABATEMENT PROCEDURES PRIOR TO O G M I N PERFORMING WORK. M I FLEXIBLE DUCT CONNECTION DETAIL O A SUPPORT FRAME C INSULATION NO SCALE RICHARD M. KLEIN 4" ELBOW ON CHILLER CONNECTION HAS BEEN IDENTIFIED AS ASBESTOS (WHERE APPLICABLE) METAL No. 027864 CONTAMINATED MATERIAL. P R R O E F E E N SS GI ROOF MOUNTED UNIT CURB DETAIL IONAL EN ELECTRIC UNIT HEATER SCHEDULE NO SCALE CAPACITY FAN DATA MOUNTING ELECTRICAL SERVICE MANUFACTURER/ EAT LAT MARK TYPE HEIGHT REMARKS MODEL NO. OF AIRFLOW °FDB °FDB TOTAL KW MBH RPM FT VOLTS PH STAGES CFM FLA ROOF TOP UNIT ELECTRIC P-TRAP UH-1 3.3 11.2 1 - - 8'-0" AFF 15.9 208 1 1 2 3 4 MARKEL UNIT 400 1550 VIBRATING NOTES: ISOLATION BARS 1 PROVIDE WITH INSULATED SUB-BASE 3 PROVIDE WITH MANUFACTURERS REMOTE WALL (TYP) CONDENSATE DRAIN SPILL ON ROOF 2 PROVIDE WITH AUTOMATIC RESET HIGH LIMIT CONTROLS. MOUNTED THERMOSTAT 4 PROVIDE WITH MANUFACTURERS WALL BRACKET. ROOF CURB (SEE "ROOF SUPPLY RETURN AIR MOUNTED UNIT CURB AIR (TYP) DETAIL" THIS SHEET) FLEXIBLE DUCT (TYP) CONNECTION ROOF (TYP)

1 2 7 8 (E) CHILLER ROOF TOP UNIT INSTALLATION DETAIL

PHYSICIAN NO SCALE 01

1 1 ROOF TOP UNIT SCHEDULE 3 4 FAN DATA COOLING COIL DATA NATURAL GAS DATA ELECTRICAL DATA (E) COOLING 4 1 MANUFACTURER/ MIN CAPACITY MBH EAT LAT CAPACITY MBH MAX TOWER (E) MARK ESP HEATING REMARKS BOILER MODEL OA EAT LAT RLA MCA FUSE VOLTS PH CFM "WC TYPE 5 TOTAL SENSIBLE °EDB °EWB °LDB °LWB INPUT OUTPUT JAK RMK

CFM AMPS RMK 15-041 NATURAL 1 TOILET RTU-1 TRANE / YSC060 1960 0.5 140 55.5 48.7 76.9 63.2 53.6 55.2 80.0 68.6 66.1 97.4 24.2 28.2 40.0 208 3 1 2 3 4 5 GAS 01-06-2017 1 01 NATURAL RTU-2 TRANE / YHC092 2400 0.6 210 82.9 60.6 77.0 63.4 52.5 51.4 150.0 120.0 65.7 112.2 38.4 42.4 50.0 208 3 1 2 3 4 5 GAS NATURAL RTU-3 TRANE / YSC072 2000 0.6 210 68.8 49.5 77.4 63.6 51.5 52.2 120.0 97.2 64.0 109.8 30.9 36.5 50.0 208 3 1 2 3 4 5 6 (E) 3/4" GAS GAS UP TO ROOF NATURAL RTU-4 TRANE / YSC072 2200 0.6 160 70.0 50.2 76.9 63.4 54.5 52.2 120.0 97.2 66.1 107.3 30.9 36.5 50.0 208 3 1 2 3 4 5 GAS NATURAL RTU-5 TRANE / YSC072 2000 0.6 290 69.6 48.9 77.9 64.0 54.0 52.3 120.0 97.2 67.3 108.9 30.9 36.5 50.0 208 3 1 2 3 4 5 GAS NATURAL RTU-6 TRANE / YSC072 2400 0.6 295 72.1 52.1 77.7 63.9 56.3 53.3 120.0 97.2 63.7 101.5 30.9 36.5 50.0 208 3 1 2 3 4 5 GAS NATURAL ENLARGED MECHANICAL ROOM PLAN - DEMOLITION RTU-7 TRANE / YSC060 2000 0.5 150 54.4 51.3 76.4 62.0 52.5 52.5 80.0 65.6 67.6 98.3 24.2 28.8 40.0 208 3 1 2 3 4 5 SCALE: 1/4" = 1'-0" GAS NATURAL RTU-8 TRANE / YSC060 960 0.5 170 37.5 23.85 81.0 67.9 58.41 55.71 60.0 48.0 53.4 99.9 24.2 28.8 45 208 3 1 2 3 4 5 GAS

------MECHANICAL ROOM ------UH-1 ------

PHYSICIAN NOTES: PROVIDE A DUCT MOUNTED SMOKE DETECTOR IN 01 3 PROVIDE WITH A MODULATING OUTSIDE AIR DAMPER 5 1 BASED ON 95 °FDB AMBIENT TEMPERATURE CONTROLLED BY A RETURN AIR DUCT MOUNTED CO2 SENSOR THE RETURN AIR DUCT TO SHUT DOWN THE UNIT AND CLOSE ALL DAMPERS UPON SENSING PRODUCTS OF 2 PROVIDE WITH HONEYWELL 5000 THERMOSTAT 4 PROVIDE WITH FACTORY ROOF CURB COMBUSTION. CITY OF HAMPTON MECHANICAL ENLARGED PLANS, SCHEDULES AND DETAILS

TOILET 01

HALLWAY

ENLARGED MECHANICAL ROOM PLAN - NEW WORK GRAPHIC SCALE M-401 SCALE: 1/4" = 1'-0" 0' 4' 8' 12' 1/4" = 1'-0" 9 18 MECHANICAL SPECIFICATIONS:

1. GENERAL BROCHURE IS DEEMED COMPLETE BY THE ARCHITECT, ENGINEER, AND OWNER. AWAY FROM THE UNITS, SUPPORTED AS REQUIRED TO ASSURE PROPER FLOW, AND AT THE MECHANICAL CONTRACTOR'S OPTION, CONDENSATE DRAIN LINES MAY BE SCHEDULE 40 PVC OR COPPER. ALL JOINTS SHALL BE 1.1. GENERAL REQUIREMENTS: 1.8. WARRANTIES: SECURELY GLUED OR SOLDERED AS REQUIRED. INSULATE 3/4" THICK PIPE INSULATION WHERE REQUIRED. 1.1.1. REQUIREMENTS UNDER DIVISION ONE AND THE GENERAL AND SUPPLEMENTARY CONDITIONS OF THESE 1.8.1. WARRANT EACH SYSTEM AND EACH ELEMENT THEREOF AGAINST ALL DEFECTS DUE TO FAULTY WORKMANSHIP, SPECIFICATIONS SHALL BE A PART OF THIS SECTION. EACH CONTRACTOR SHALL BECOME THOROUGHLY DESIGN OR MATERIAL FOR A PERIOD OF 12 MONTHS OF DATE OF SUBSTANTIAL COMPLETION (COMPRESSORS IN 2.6. CONTROLS: ACQUAINTED WITH ITS CONTENTS AS TO REQUIREMENTS THAT AFFECT THIS DIVISION OR SECTION. THE WORK AND REFRIGERATION EQUIPMENT WITH A 60 MONTH WARRANTY), UNLESS SPECIFIC ITEMS ARE 2.6.1. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR SUPPLYING AND INSTALLING A COMPLETE OPERATIVE COASTAL REQUIRED UNDER THIS SECTION INCLUDES MATERIAL, EQUIPMENT, APPLIANCES, TRANSPORTATION, SERVICES, NOTED TO CARRY A LONGER WARRANTY IN THE CONSTRUCTION DOCUMENTS OR MANUFACTURER'S STANDARD SYSTEM OF CONTROLS, INCLUDING THERMOSTATS, CONTROL DEVICES, TIME CLOCKS, DDC COMPONENTS, AND E N G I N E E R I N G AND LABOR REQUIRED TO COMPLETE THE ENTIRE SYSTEM AS REQUIRED BY THE DRAWINGS AND SPECIFICATIONS. WARRANTY EXCEEDS 12 MONTHS. REMEDY ALL DEFECTS, OCCURRING WITHIN THE WARRANTY PERIOD(S), AS CONTROL WIRING.. 1.1.2. THE SPECIFICATIONS AND DRAWINGS FOR THE PROJECT ARE COMPLEMENTARY, AND PORTIONS OF THE WORK STATED IN THE GENERAL CONDITIONS AND DIVISION 1. 2.6.2. SMOKE DETECTORS AND SAMPLING TUBES PROVIDED AND INSTALLED TO THE UNITS AND IN THE DUCTWORK BY 2406 Princess Anne Road, DESCRIBED IN ONE, SHALL BE PROVIDED AS IF DESCRIBED IN BOTH. IN THE EVENT OF DISCREPANCIES, NOTIFY 1.8.2. WARRANTIES SHALL INCLUDE LABOR AND MATERIAL. MAKE REPAIRS OR REPLACEMENTS WITHOUT ANY THE MECHANICAL CONTRACTOR. THE SMOKE DETECTORS SHALL DISABLE HVAC UNIT OPERATION UPON Suite 200 THE ENGINEER AND/OR OWNER AND REQUEST CLARIFICATION PRIOR TO PROCEEDING WITH THE WORK INVOLVED. ADDITIONAL COSTS TO THE OWNER. ACTIVATION. Virginia Beach, VA 23456 1.8.3. PERFORM THE REMEDIAL WORK PROMPTLY, UPON WRITTEN NOTICE FROM THE ENGINEER OR OWNER. Phone (757) 563-9027 1.2. INSPECTION OF THE SITE: 1.8.4. AT THE TIME OF SUBSTANTIAL COMPLETION, DELIVER TO THE OWNER ALL WARRANTIES, IN WRITING AND 2.7. ELECTRICAL: Facsimile(757) 563-9028 1.2.1. PRIOR TO SUBMITTING BID, THE CONTRACTOR SHALL VISIT THE SITE OF THE PROPOSED WORK AND BECOME PROPERLY EXECUTED, INCLUDING TERM LIMITS FOR WARRANTIES EXTENDING BEYOND THE ONE YEAR PERIOD, 2.7.1. LOW VOLTAGE WIRING - ALL PROVISIONS FOR LOW VOLTAGE WIRING SHALL BE PERFORMED BY THE MECHANICAL FULLY INFORMED AS TO THE CONDITIONS UNDER WHICH THE WORK IS TO BE DONE. FAILURE TO DO SO WILL NOT EACH WARRANTY INSTRUMENT BEING ADDRESSED TO THE OWNER AND STATING THE COMMENCEMENT DATE AND CONTRACTOR UNLESS CODES OR LABOR SITUATIONS DO NOT PERMIT. IF THE MECHANICAL CONTRACTOR CAN BE CONSIDERED SUFFICIENT JUSTIFICATION TO REQUEST OR OBTAIN EXTRA COMPENSATION OVER AND ABOVE TERM. NOT PERFORM LOW VOLTAGE WIRING, THE MECHANICAL CONTRACTOR SHALL INFORM THE GENERAL TH EAL OF THE CONTRACT PRICE. CONTRACTOR, AS A PART OF THE HVAC BID DOCUMENT, TO HAVE THE ELECTRICAL SUBCONTRACTOR INCLUDE HIS W V N IR O G 1.9. CUTTING AND PATCHING: WORK IN THEIR BID. M I N M 1.3. MATERIAL AND WORKMANSHIP: 1.9.1. PERFORM CUTTING OF WALLS, , CEILINGS, ETC., AS REQUIRED TO INSTALL WORK UNDER THIS SECTION. I 2.7.2. POWER WIRING - ALL ELECTRICAL POWER WIRING TO INCLUDE FINAL CONNECTIONS SHALL BE PROVIDED BY THE A O

C 1.3.1. PROVIDE NEW MATERIAL, EQUIPMENT, AND APPARATUS UNDER THIS CONTRACT UNLESS OTHERWISE STATED OBTAIN PERMISSION FROM THE ARCHITECT PRIOR TO CUTTING. DO NOT CUT OR DISTURB STRUCTURAL MEMBERS GENERAL CONTRACTOR'S ELECTRICAL SUBCONTRACTOR. RICHARD M. KLEIN HEREIN, OF BEST QUALITY NORMALLY USED FOR THE PURPOSE IN GOOD COMMERCIAL PRACTICE, AND FREE FROM WITHOUT PRIOR APPROVAL FROM THE ARCHITECT. CUT HOLES AS SMALL AS POSSIBLE. PATCH WALLS, FLOORS, 2.7.3. MOTOR STARTERS SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR AND TURNED OVER TO THE No. 027864 ANY DEFECTS. MODEL NUMBERS LISTED IN THE SPECIFICATIONS OR SHOWN ON THE DRAWINGS ARE NOT ETC., AS REQUIRED BY WORK UNDER THIS SECTION. PATCHING SHALL MATCH THE ORIGINAL MATERIAL AND ELECTRICAL CONTRACTOR FOR INSTALLATION. P R R O E NECESSARILY INTENDED TO DESIGNATE THE REQUIRED TRIM, WRITTEN DESCRIPTIONS OF THE TRIM GOVERN CONSTRUCTION. REPAIR AND REFINISH AREAS DISTURBED BY WORK TO THE CONDITION OF ADJOINING SURFACES F E E N SS GI MODEL NUMBERS. IN A MANNER SATISFACTORY TO THE ARCHITECT. 2.8. GAS PIPING: IONAL EN 1.3.2. WORK PERFORMED UNDER THIS CONTRACT SHALL PROVIDE A NEAT AND "WORKMANLIKE" APPEARANCE WHEN 2.8.1. SCHEDULE 40 BLACK CARBON STEEL WITH MALLEABLE IRON THREADED FITTINGS. PROVIDES SHUT-OFF VALVE, COMPLETED, TO THE SATISFACTION OF THE ARCHITECT AND ENGINEER. WORKMANSHIP SHALL BE THE FINEST 1.10. ROUGH-IN: DIRT LEG, AND UNION AT EACH ROOFTOP UNIT. PAINT ALL GAS PIPING EXPOSED TO WEATHER WITH ONE COAT OF POSSIBLE BY EXPERIENCED MECHANICS. INSTALLATIONS SHALL COMPLY WITH APPLICABLE CODES AND LAWS. 1.10.1. COORDINATE WITHOUT DELAY ROUGH-IN WITH GENERAL CONSTRUCTION. CONCEAL PIPING AND CONDUIT PRIMER, AND TWO COATS OF RUST-PROOF PAINT. COLOR SHALL MATCH BUILDING COLORS. COORDINATE WITH 1.3.3. THE COMPLETE INSTALLATION SHALL FUNCTION AS DESIGNED AND INTENDED WITH RESPECT TO EFFICIENCY, ROUGH-IN EXCEPT IN UNFINISHED AREAS AND WHERE OTHERWISE SHOWN. OWNER'S CONSTRUCTION MANAGER. CAPACITY, NOISE LEVEL, ETC. ABNORMAL NOISE CAUSED BY VIBRATING EQUIPMENT, PIPING, DUCTS, AIR DEVICES, 1.10.2. RUN ALL PIPING AND DUCTWORK NEAT AND PARALLEL TO THE BUILDING STRUCTURE UNLESS OTHERWISE NOTED. 2.8.2. TREATED WOOD BLOCKING 6X6X12, 8'-0" OC MAX WITH GALVANIZED PIPE STRAP 1 1/4" ZINC COATED LAG SCREWS, AND SQUEAKS IN ROTATING COMPONENTS WILL NOT BE ACCEPTABLE. IN GENERAL, MATERIALS AND EQUIPMENT AND RUBBER WALKPAD ADHERED TO THE ROOF. SHALL BE OF COMMERCIAL SPECIFICATION GRADE IN QUALITY. LIGHT DUTY AND RESIDENTIAL TYPE EQUIPMENT 1.11. STRUCTURAL STEEL: WILL NOT BE ACCEPTABLE. 1.11.1. STRUCTURAL STEEL USED FOR PIPE SUPPORTS, EQUIPMENT SUPPORTS, ETC., SHALL BE NEW, CLEAN, AND 2.9. REFRIGERATION LINES: 1.3.4. REMOVE FROM THE PREMISES WASTE MATERIAL PRESENT AS A RESULT OF WORK, INCLUDING CARTONS, CRATING, CONFORM TO ASTM DESIGNATION A-36. 2.9.1. REFRIGERATION LINE SETS FOR HVAC UNITS ARE TO BE PROVIDED WITH THE EQUIPMENT AND SIZED BY THE PAPER, STICKERS, AND/OR EXCAVATION MATERIAL NOT USED IN BACKFILLING, ETC. CLEAN EQUIPMENT INSTALLED 1.11.2. SUPPORT EQUIPMENT AND PIPING FROM THE BUILDING STRUCTURE. DO NOT SUPPORT EQUIPMENT FROM MANUFACTURER BASED ON ACTUAL JOB SITE CONDITIONS INCLUDING LENGTH AND ELEVATION CHANGES, AND UNDER THIS CONTRACT TO A NEW AND CLEAN CONDITION AT THE TERMINATION OF WORK. CEILINGS, OTHER PLUMBING, MECHANICAL,FIRE PROTECTION, OR ELECTRICAL COMPONENTS, AND OTHER INSTALLED BY THE CONTRACTOR. 1.3.5. REPAIR OR REPLACE PUBLIC AND PRIVATE PROPERTY DAMAGED AS A RESULT OF WORK PERFORMED UNDER THIS NON-STRUCTURAL ELEMENTS. 2.9.2. INSULATE ALL REFRIGERANT LIQUID LINES AND PROVIDE AN ALL WEATHER COATING ON EXTERIOR INSULATION. CONTRACT TO THE SATISFACTION OF OWNER, ENGINEER AND AUTHORITIES HAVING JURISDICTION. 1.3.6. MISCELLANEOUS ITEMS NOT SHOWN ON THE PLANS BUT NECESSARY FOR A COMPLETE OPERABLE SYSTEM, SHALL 1.12. ACCESS DOORS: 2.10. HYDRONIC PIPING: BE SUPPLIED AND INSTALLED. 1.12.1. PROVIDE ACCESS DOORS IN CEILINGS AND WALL WHERE INDICATED OR REQUIRED FOR ACCESS TO CONCEALED 2.10.1. HARD COPPER TUBING: ASTM B 88, TYPE L (ASTM B 88M, TYPE B) WITH ASME B16.22 WROUGHT-COPPER SOLDER 1.3.7. CONTRACTOR SHALL FURNISH AND INSTALL ALL EQUIPMENT AND MATERIALS FOR A COMPLETE INSTALLATION IN VALVES, DAMPERS, AND EQUIPMENT INSTALLED UNDER THIS SECTION. PROVIDE CONCEALED HINGES, FITTINGS AND ASTM B 32, 95-5 TIN ANTIMONY SOLDER. ALL RESPECTS READY OF INTENDED USE AND THE STRICT ACCORDANCE WITH STATE AND LOCAL CODES AND SCREWDRIVER-TYPE LOCK, ANCHOR STRAPS; MANUFACTURED BY MILCOR, ZURN, TITUS OR EQUAL. OBTAIN 2.10.2. ON PIPING 2 1/2" OR GREATER, MECHANICAL CONTRACTOR MAY USE: STEEL PIPE: ASTM A 53, SCHEDULE 40, PLAIN MANUFACTURER'S RECOMMENDATIONS. PAY NECESSARY FEES AND OBTAIN PERMITS. INITIATE, MAINTAIN AND ARCHITECT'S APPROVAL OF TYPE, SIZE, LOCATION, AND COLOR BEFORE ORDERING. ENDS WITH CAST-IRON THREADED FITTINGS. SUPERVISE ALL SAFETY PRECAUTIONS AND PROCEDURES. 2.10.3. INSULATION: 1 1/2" WALL ONE-PIECE FIBERGLASS COVERING HAVING A CONDUCTIVITY NOT EXCEEDING 0.27 WITH 1.3.8. EQUIPMENT AND MATERIALS SHALL BE OF THE TYPE, SIZE AND MANUFACTURERS INDICATED ON THE DRAWINGS 1.13. PENETRATIONS: FIRE RESISTANT JACKET WITH SELF-SEALING LAP TO PROVIDE A CONTINUOUS VAPOR BARRIER BY CERTAINTEED, OR AN APPROVED EQUIVALENT. 1.13.1. SEAL FLOOR, EXTERIOR WALL AND ROOF PENETRATIONS WATER AND WEATHER TIGHT WITH APPROPRIATE OWENS-CORNING OR ARMSTRONG. 1.3.9. THE CONTRACTOR SHALL SUPPLY AND INSTALL THE MATERIALS AND EQUIPMENT COVERED BY THE PLANS AND NON-SHRINK, NON-HARDENING COMMERCIAL CONSTRUCTION SEALANT. SEAL ROOF PENETRATIONS WITH 4 2.10.3.1. ARMAFLEX INSULATION SHALL NOT BE USED. SPECIFICATIONS TO THE OWNER COMPLETE AND IN FIRST CLASS CONDITION IN EVERY RESPECT. HE SHALL POUND PER SQUARE FOOT LEAD FLASHING. PROVIDE A SLEEVE, AND SEAL NON-FIRE-RATED FLOOR AND WALL GUARANTEE THAT THE MATERIAL, EQUIPMENT, AND WORKMANSHIP SUPPLIED AND INSTALLED BY HIM SHALL BE PENETRATIONS WITH FIBERGLASS PACKING AND SILICONE CAULK (FOR ACOUSTICAL INSULATION). 2.11. MECHANICAL CONTRACTOR RESPONSIBILITIES: ENTIRELY FREE FROM DEFECTS AND THAT HE WILL REPAIR OR REPLACE AT HIS OWN EXPENSE, ANY MATERIALS, 1.13.2. COORDINATE FIRE RATING REQUIREMENTS AND LOCATIONS WITH THE ARCHITECTURAL DRAWINGS OR EXISTING 2.11.1. AFTER COMPLETION OF THE WORK DESCRIBED IN THIS SPECIFICATION AND SHOWN ON THE DRAWINGS, THE EQUIPMENT, AND WORKMANSHIP IN WHICH DEFECTS ARE FOUND. BUILDING CONDITIONS AND RATINGS. SEAL PENETRATIONS OF FIRE-RATED ASSEMBLIES WITH 3M # CP-25 FIRE MECHANICAL CONTRACTOR SHALL THOROUGHLY CLEAN ALL EXPOSED EQUIPMENT, REMOVING ALL LABELS AND BARRIER CAULK (PROVIDE THICKNESS AND METHOD AS REQUIRED AND RECOMMENDED BY MANUFACTURER) TO STICKERS NOT CONTAINING OPERATION INSTRUCTION. MECHANICAL CONTRACTOR SHALL REMOVE CRATING 1.4. COORDINATION: MAINTAIN THE FIRE RESISTANCE RATING OF FIRE-RATED ASSEMBLIES. DEBRIS. LEAVING THE INSTALLATION FINISHED AND READY FOR OPERATION, TO INCLUDING CLEAN FILTERS IN AIR 1.4.1. COORDINATE WORK WITH THAT OF OTHER TRADES SO THAT THE VARIOUS COMPONENTS OF THE SYSTEMS WILL 1.13.3. SEAL EXTERIOR WALL PENETRATIONS BELOW GRADE WITH CASE IRON WALL PIPES AND MODULAR MECHANICAL HANDLING UNITS. BE INSTALLED AT THE PROPER TIME, WILL FIT THE AVAILABLE SPACE, AND WILL ALLOW PROPER SERVICE ACCESS SLEEVE SEALS, MANUFACTURED BY THUNDERLINE/LINK SEAL, CALPICO, INC, METRAFLEX OR APPROVED EQUAL. 2.11.2. TEST AND DEMONSTRATE TO THE OWNER THE ENTIRE SYSTEM IN ALL MODES OF OPERATION TO INSURE PROPER TO THOSE ITEMS REQUIRING MAINTENANCE. COMPONENTS WHICH ARE INSTALLED WITHOUT REGARD TO THE 1.13.4. PROVIDE SLEEVE FOR HORIZONTAL PIPE PASSING THROUGH OR UNDER . SLEEVES SHALL BE CAST OPERATION. ABOVE SHALL BE RELOCATED AT NO ADDITIONAL COST TO THE OWNER. IRON SOIL PIPE TWO NOMINAL PIPE SIZES LARGER THAN THE PIPE SERVED. SEAL WATER-TIGHT WITH SILICON 1.4.2. UNLESS OTHERWISE INDICATED, THE CONTRACTOR WILL PROVIDE CHASES AND OPENINGS IN BUILDING CAULK. JAK RMK CONSTRUCTION REQUIRED FOR THE INSTALLATION OF THE SYSTEMS SPECIFIED HEREIN. MECHANICAL RMK CONTRACTOR SHALL FURNISH THE GENERAL CONTRACTOR WITH THE INFORMATION WHERE CHASES AND 2. HEATING, VENTILATION, AND AIR CONDITIONING 15-041 OPENINGS ARE REQUIRED. COORDINATE HE WORK OF THE OTHER TRADES ENGAGED IN THE CONSTRUCTION OF 01-06-2017 THE PROJECT, AND EXECUTE WORK IN A MANNER AS TO NOT INTERFERE WITH OR DELAY THE WORK OF OTHER 2.1. DUCTWORK: TRADES. 2.1.1. PROVIDE ANY DUCTWORK NECESSARY FOR A COMPLETE INSTALLATION OF HVAC SYSTEMS (INCLUDING EXHAUST 1.4.3. FIGURED DIMENSIONS SHALL BE TAKEN IN PREFERENCE TO SCALE DIMENSIONS. THE CONTRACTOR SHALL TAKE SYSTEMS AND MAKE-UP AIR SYSTEMS). ALL DUCTWORK IDENTIFICATION AND INSTALLATION TO ADHERE TO HIS OWN MEASUREMENTS AT THE BUILDING, AS VARIATIONS MAY OCCUR. THE CONTRACTOR WILL BE HELD SMACNA STANDARDS AND ALL GOVERNING CODES. RESPONSIBLE FOR ERRORS THAT COULD HAVE BEEN AVOIDED BY PROPER CHECKING AND INSPECTION. 2.1.2. DUCTWORK SHALL BE GALVANIZED STEEL, CONSTRUCTED AND INSTALLED AS RECOMMENDED BY SMACNA AND 1.4.4. PROVIDE MATERIALS WITH TRIM THAT WILL PROPERLY FIT THE TYPES OF CEILING, WALL, OR FLOOR FINISHES INSULATED WITH 2" THICK FIBERGLASS DUCT WRAP WITH FOIL VAPOR BARRIER JACKET. SHEET METAL GAUGES ACTUALLY INSTALLED. MODEL NUMBERS LISTED IN THE SPECIFICATIONS OR SHOWN ON THE DRAWINGS ARE NOT SHALL BE IN ACCORDANCE WITH SMACNA. FLEXIBLE DUCTWORK SHALL BE FACTORY INSULATED WITH VAPOR INTENDED TO DESIGNATE THE REQUIRED TRIM. BARRIER JACKET. 1.4.5. MECHANICAL CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR DUCTWORK LAYOUT TO THE CONSTRUCTION 2.1.3. DUCTWORK CONNECTIONS TO AIR DEVICES MUST BE MADE WITH HARD PIPE ELBOWS, COVERED WITH SLEEVE PROJECT MANAGER FOR OWNER APPROVAL PRIOR TO INSTALLATION. INSULATION. FLEX DUCT MUST NOT BE UTILIZED FOR A 90 DEGREE CONNECTION TO AN AIR DEVICE. 1.4.6. CONTRACTOR TO SUBMIT 6 SETS (OWNER WILL RETURN 3 SETS NOTED WITH ACTION TAKEN)SPECIFICATIONS AND 2.1.4. BALANCING DAMPERS WITH DOUBLE LOCKING QUADS SHALL BE PROVIDED IN ALL ROUND DUCT TAKE-OFFS FROM DETAIL FOR EQUIPMENT AND FABRICATED MATERIALS FOR OWNER'S APPROVAL PRIOR TO ISSUING PURCHASE THE MAIN TRUNKS, UNLESS OTHERWISE NOTED ON PLANS. ORDER. OWNER'S APPROVAL DOES NOT RELIEVE CONTRACTOR OF ANY RESPONSIBILITY FOR PERFORMANCE AND 2.1.5. A MAXIMUM OF 7'-0" OF FLEX DUCT MAY BE USED FOR FINAL CONNECTION OF SUPPLY AIR DIFFUSERS AND GRILLES. OPERATION. 2.1.6. FLEX DUCT MUST BE PROPERLY SUPPORTED WITH ONE INCH STRAPS AND CUT TO PROPER LENGTH TO PREVENT SAGGING. 1.5. ORDINANCES AND CODES: 2.1.7. FLEX DUCT SHALL BE OWENS-CORNING FOIL-BACK HIGH QUALITY U/L APPROVED. PLASTIC WRAPPED FLEX DUCT IS 1.5.1. WORK PERFORMED UNDER THIS CONTRACT SHALL, AT A MINIMUM, BE IN CONFORMANCE WITH APPLICABLE NOT ACCEPTABLE. FLEXIBLE DUCTWORK MAYBE USED FOR RUN-OUTS TO AIR DISTRIBUTION DEVICES AS NATIONAL, STATE AND LOCAL CODES HAVING JURISDICTION. EQUIPMENT FURNISHED AND ASSOCIATED INDICATED BUT SHALL NOT BE USED IN NON-ACCESSIBLE, CONCEALED SPACES. INSTALLATION WORK PERFORMED UNDER THIS CONTRACT SHALL BE IN STRICT COMPLIANCE WITH CURRENT 2.1.8. RIGID DUCT SHALL BE USED FOR RETURN EXHAUST AND MAKE-UP AIR. APPLICABLE CODES ADOPTED BY THE LOCAL AUTHORITY HAVING JURISDICTION INCLUDING ANY AMENDMENTS AND STANDARDS AS SET FORTH BY THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), UNDERWRITERS 2.2. INSULATION: LABORATORIES (UL), OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA), AMERICAN SOCIETY OF 2.2.1. SUPPLY AND RETURN DUCTWORK INSIDE THE BUILDING SHALL BE INSULATED WITH 2" THICK EXTERIOR MECHANICAL ENGINEERS (ASME), AMERICAN SOCIETY OF HEATING, REFRIGERATION, AND AIR CONDITIONING FIBERGLASS DUCT WRAP WITH A VAPOR BARRIER, SEAL ALL JOINTS AND LAPS TO MAINTAIN VAPOR BARRIER. ENGINEERS (ASHRAE), AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI), AMERICAN SOCIETY OF TESTING 2.2.2. SUPPLY AND RETURN DUCTWORK OUTSIDE THE BUILDING SHALL BE INSULATED WITH 2" LINER WITH A MINIMUM MATERIALS (ASTM), AND OTHER NATIONAL STANDARDS AND CODES WHERE APPLICABLE. WHERE THE CONTRACT R-VALUE OF 8.0 AND SEAL SEAMS WEATHER TIGHT. DOCUMENTS EXCEED THE REQUIREMENTS OF THEIR REFERENCED CODES, STANDARDS, ETC., THE CONTRACT 2.2.3. DEDICATED OUTSIDE AIR SUPPLY AND RELIEF DUCTWORK INSIDE THE BUILDING SHALL BE INSULATED WITH 2" DOCUMENTS SHALL TAKE PRECEDENCE. THICK DUCT WRAP WITH A MINIMUM R-VALUE OF 6.0. 1.5.2. PROCURE AND PAY FOR PERMITS AND LICENSES REQUIRED FOR THE ACCOMPLISHMENT OF THE WORK HEREIN DESCRIBED. WHERE REQUIRED, OBTAIN, PAY FOR AND FURNISH CERTIFICATES OF INSPECTION TO THE OWNER. 2.3. FINAL TESTING AND ADJUSTMENTS: THE CONTRACTOR WILL BE HELD RESPONSIBLE FOR VIOLATIONS OF THE LAW. 2.3.1. AIR BALANCE SHALL BE PERFORMED AT THE COMPLETION OF THE PROJECT. BALANCE EACH SUPPLY, RETURN, OUTSIDE AIR DEVICE WITHIN 5% OF REQUIREMENTS AND FURNISH AN AABC OR NEBB CERTIFIED REPORT TO THE 1.6. PROTECTION OF EQUIPMENT AND MATERIALS: OWNER AND ENGINEER. THE ENTIRE HVAC SYSTEM MUST BE FULLY OPERABLE, BALANCED, AND APPROVED BY 1.6.1. STORE AND PROTECT FROM DAMAGE EQUIPMENT AND MATERIALS DELIVERED TO JOB SITE. COVER WITH OWNER'S REPRESENTATIVE ON OR BEFORE THE DAY OF SUBSTANTIAL COMPLETION. WATERPROOF, TEAR-RESISTANT, HEAVY TARP OR POLYETHYLENE PLASTIC AS REQUIRED TO PROTECT FROM 2.3.2. ADJUST THERMOSTATS AND CONTROL DEVICES TO OPERATE AS INTENDED. ADJUST PUMPS, FANS, ETC. FOR PLASTER, DIRT, PAINT, WATER, OR PHYSICAL DAMAGE. EQUIPMENT AND MATERIAL THAT HAS BEEN DAMAGED BY PROPER AND EFFICIENT OPERATION. CERTIFY TO ARCHITECT THAT ADJUSTMENTS HAVE BEEN MADE AND THAT CONSTRUCTION ACTIVITIES WILL BE REJECTED, AND MECHANICAL CONTRACTOR IS OBLIGED TO FURNISH NEW SYSTEMS IS OPERATING SATISFACTORILY. CALIBRATE, SET AND ADJUST AUTOMATIC TEMPERATURE CONTROLS. EQUIPMENT AND MATERIAL OF A LIKE KIND AS APPROVED BY OWNER. CHECK PROPER SEQUENCES OF INTERLOCK SYSTEMS, AND OPERATION OF SAFETY CONTROLS. CITY OF HAMPTON 1.6.2. KEEP PREMISES ROOM CLEAN FROM FOREIGN MATERIAL CREATED DURING WORK PERFORMED UNDER THIS 2.3.3. VERIFY ECONOMIZER OPERATION PER MANUFACTURER PROCEDURE. MECHANICAL SPECIFICATIONS CONTRACT. PIPING, EQUIPMENT, ETC., SHALL HAVE A NEAT AND CLEAN APPEARANCE AT THE TERMINATION OF THE WORK. 2.4. DIFFUSERS AND GRILLES: 1.6.3. PLUG OR CAP OPEN ENDS OF DUCTWORK AND PIPING SYSTEMS WHILE STORED OR INSTALLED DURING 2.4.1. ALL SUPPLY AND RETURN AIR DEVICES SHALL BE INSTALLED BY THE CONTRACTOR. CONSTRUCTION WHEN NOT IN USE TO PREVENT THE ENTRANCE OF DEBRIS INTO THE SYSTEMS. 2.4.2. ALL AIR TERMINAL DEVICES SHALL BE INSTALLED AS SHOWN ON THE PLANS IN ORDER TO HANDLE THE DESIGNED AIR FLOW CAPACITIES WITH A MINIMUM AMOUNT OF NOISE AND STATIC PRESSURE, PROVIDE BALANCING DAMPERS 1.7. OPERATION AND MAINTENANCE INSTRUCTIONS: FOR ALL AIR FLOW DEVICES TO ALLOW ADJUSTMENT WITH A LOCKING SET POINT, ROOM OPERATED SLIDE 1.7.1. COMPILE A COMPLETE BROCHURE OF FIXTURES, MATERIALS, AND EQUIPMENT FURNISHED AND INSTALLED ON ACTUATED DAMPERS ON SUPPLY GRILLES DO NOT MEET THE REQUIREMENTS OF A BALANCING DAMPER. THIS PROJECT. INCLUDE OPERATIONAL AND MAINTENANCE INSTRUCTIONS, MANUFACTURER'S CATALOG SHEETS, WIRING DIAGRAMS, PARTS LISTS, APPROVED SHOP DRAWINGS, AND DESCRIPTIVE LITERATURE FURNISHED BY THE 2.5. CONDENSATE DRAINS: MANUFACTURER. INCLUDE AN INSIDE COVER SHEET THAT LISTS THE PROJECT NAME, DATE, OWNER, ARCHITECT, 2.5.1. THE MECHANICAL CONTRACTOR SHALL PROVIDE AND INSTALL AS A MINIMUM A 4" DEEP P-TRAP ON CONDENSATE ENGINEER, GENERAL CONTRACTOR, SUBCONTRACTOR, AND AN INDEX OF CONTENTS. DRAIN OUTLETS WHERE THE CONDENSATE WATER WILL EXIT THE P-TRAP AT A POINT 1" LOWER THAN THE DRAIN M-701 1.7.2. SUBMIT COPIES OF LITERATURE BOUND IN APPROVED BINDERS TO THE ARCHITECT AND OWNER AT THE CONNECTION AT THE UNIT. THE MECHANICAL CONTRACTOR SHALL PROVIDE AND INSTALL CONDENSATE LINES AS TERMINATION OF THE WORK. PAPER CLIPS, STAPLES, RUBBER BANDS, AND MAILING ENVELOPES ARE NOT REQUIRED TO MEET LOCAL CODES AND AS SHOWN ON THE MECHANICAL PLANS. THESE LINES SHALL BE SLOPED CONSIDERED APPROVED BINDERS. FINAL APPROVAL OF MECHANICAL WILL BE WITHHELD UNTIL THIS EQUIPMENT 10 18 LEGEND GENERAL NOTES 1. THE INSTALLATION OF ALL ELECTRICAL EQUIPMENT, DEVICES AND FIXTURES SHALL NOTE: ALL SYMBOLS BELOW MAY NOT BE USED ON PLANS, SYMBOLS NOT SHOWN BELOW CONFORM TO ALL LOCAL CODES, ORDINANCES, NATIONAL ELECTRIC CODE, AND UTILITY ARE IDENTIFIED WHERE THEY OCCUR. COMPANY REQUIREMENTS. FLUORESCENT LIGHTING FIXTURES. LETTER INDICATES POINT OF WORK, DEMO AND NEW WORK. TYPE, SEE LIGHTING FIXTURE SCHEDULE 2. THE ELECTRICAL DRAWINGS ARE GENERALLY DIAGRAMMATIC. THE ELECTRICAL COASTAL ROOM NUMBER INSTALLATION SHALL BE COORDINATED WITH ALL OTHER TRADES SO THAT INTERFERENCES E N G I N E E R I N G FLUORESCENT NIGHT LIGHTING FIXTURE. BETWEEN THE ELECTRICAL INSTALLATION AND MECHANICAL, PLUMBING, FIRE PROTECTION NEW WORK NOTE SYMBOL AND EQUIPMENT INSTALLATION WILL BE AVOIDED. REFER TO ARCHITECTURAL DRAWINGS 2406 Princess Anne Road, INCANDESCENT LIGHTING FIXTURE, CEILING OR WALL DEMO WORK NOTE SYMBOL Suite 200 MOUNTED. 3. CONTRACTOR SHALL PROVIDE ALL DISCONNECTS TO MEET LOCAL CODES. Virginia Beach, VA 23456 FIRE ALARM SYSTEM SMOKE DUCT DETECTOR. Phone (757) 563-9027 EXIT LIGHTING FIXTURE. ARROW, WHEN USED 4. ALL FINAL CONNECTIONS SHOWN ON THE DRAWINGS ARE ACTUAL REQUIREMENTS OF THE MOUNTED IN DUCT WORK BY MECH. CONTRACTOR. Facsimile(757) 563-9028 INDICATES DIRECTION (SHADING INDICATES FACE OF EQUIPMENT AND ARE SHOWN IN THEIR APPROXIMATE LOCATION. SIGN ORIENTATION). CEILING OR WALL MOUNTED FIRE ALARM SYSTEM HEAT SENSOR, CEILING MOUNT, RESPECTIVELY. TH 5. ALL MOTOR STARTERS SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR FURNISHING EAL OF U.O.N. W V THE EQUIPMENT AND INSTALLED, WIRED AND CONNECTED BY ELECTRICAL CONTRACTOR N IR O G EMERGENCY BATTERY POWERED LIGHTING UNIT. (TWIN M I N FIRE ALARM SYSTEM CONNECTION TO FLOW SWITCH M I HEAD) O A

6. ALL EXTERIOR EQUIPMENT AND DEVICES SHALL BE WEATHERPROOF AND RAIN TIGHT. C FIRE ALARM SYSTEM CONNECTION TO TAMPER SWITCH RICHARD M. KLEIN LIGHTING FIXTURE TYPE SYMBOL. SEE "LIGHTING 7. FINAL DETERMINATION OF FIRE STOPPING REQUIREMENTS SHALL BE BASED ON LOCAL CODE No. 027864 P FIXTURE SCHEDULE" FIRE ALARM SYSTEM CONNECTION TO ALARM CHECK R R REQUIREMENT. O E F E VALVE E N SS GI LIGHTING CONTACTOR. IONAL EN 8. ALL POWER OUTAGES SHALL BE CONDUCTED DURING OFF HOURS AND WEEKEND HOURS. FIRE ALARM SYSTEM MANUAL PULL STATION, MOUNT CONTRACTOR SHALL MINIMIZE DOWNTIME BY PROVIDING ADEQUATE LABOR FORCES AND SINGLE POLE LIGHT SWITCH. 20A, 120/277V, MOUNT +42" +42" AFF, U.O.N. AFF U.O.N. SUBSCRIPT INDICATES SWITCH FIXTURE MATERIALS TO COMPLETE POWER OUTAGE TASKS IN A TIMELY MANNER AND NOT INTERRUPT CONFIGURATION FIRE ALARM SYSTEM AUDIO ALARM, MOUNT 6" BELOW OWNER'S OPERATION. PROVIDE A 72 HOUR NOTICE OF ANY AND ALL POWER OUTAGES TO CEILING OR 90" AFF MAXIMUM ENGINEER AND OWNER (CITY) FOR APPROVAL. SEE PHASING PLAN FOR SEQUENCING OF THREE WAY SWITCH, 20A 120/277V, MOUNT +42" AFF WORK. COORDINATE ALL WORK WITH GENERAL CONTRACTOR AND OTHER TRADES. U.O.N. FIRE ALARM SYSTEM VISUAL ALARM, MOUNT 6" BELOW F CEILING OR 90" AFF MAXIMUM FOUR WAY SWITCH, 20A 120/277V, MOUNT +42" AFF U.O.N. FIRE ALARM SYSTEM AUDIO/VISUAL ALARM, MOUNT 6"BELOW CEILING OR 90" AFF MAXIMUM FRACTIONAL HORSEPOWER MANUAL MOTOR STARTER WITH OVERLOADS, 20A, 120V FIRE ALARM SYSTEM CONTROL PANEL

DUPLEX CONVENIENCE RECEPTACLE. 20A, 125VAC, NEMA 5-20R, MOUNT +18" AFF U.O.N. S = SURFACE MOUNT WP = WEATHERPROOF GFI = GROUND FAULT INTERRUPTER ABBREVIATIONS +48 = MOUNTING HEIGHT AFF IN INCHES W = SURFACE MOUNTED WIREMOLD Ø, PH PHASE NTS NOT TO SCALE JB JUNCTION BOX ℄ CENTERLINE TWO CONVENIENCE TYPE RECEPTACLES, A, AMP AMPERE P POLE EACH NEMA 5-20R, MOUNT IN TWO GANG RECEPTACLE KVA KILOVOLT AMPERES EF EXHAUST FAN BOX WITH SINGLE COVER PLATE, MOUNT +18" AFF AFF ABOVE FINISHED FLOOR RTU ROOF TOP UNIT U.O.N. AND COMPUTER WIRING NOTE 4. KW KILOWATT EQUIP EQUIPMENT TYP TYPICAL AFG ABOVE FINISHED GRADE EXIST EXISTING CONDUIT HOMERUN WITH PANELBOARD & CIRCUIT MLO MAIN LUGS ONLY UON UNLESS OTHERWISE NOTED DESIGNATIONS BRANCH CIRCUIT OF FEEDER WIRING AIC AMPERE INTERRUPTING F FUSE IN CONDUIT. PROVIDE SIZE AND QUANTITY OF CAPACITY V VOLT, VOLTAGE CONDUCTORS AS REQUIRED TO FACILITATE CIRCUIT MT MOUNT (RMS SYMMETRICAL) FLEX FLEXIBLE BPM BPM MTD MOUNTED ALTERNATE ALT W WIRE RMK

CONFIGURATION AND/OR SWITCHING INDICATED. 15-041 MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG (OR AS MTG MOUNTING GFI GROUND FAULT INTERRUPTER

INDICATED), MINIMUM CONDUIT SIZE SHALL BE 1/2". MCB MAIN CIRCUIT BREAKER WP WEATHERPROOF 01-06-2017 APPROX APPROXIMATELY GND GROUND NF NONFUSIBLE HP HORSE POWER BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT. NO C CONDUIT TICK MARKS INDICATE 2 CONDUCTORS & 1 GROUND IN CONDUIT UON. TICK MARKS, WHEN SHOWN, INDICATE QUANTITY OF CONDUCTORS IF OTHER THAN THREE; ( ) INDICATES GROUND, ( ) INDICATES INSULATED ISOLATED GROUND. FOR CONDUIT AND WIRE SIZES REFER TO PANELBOARD SCHEDULES.

HOMERUNS TO PANEL. PANEL & CIRCUIT DESIGNATIONS AS INDICATED.

CIRCUIT BREAKER

PANELBOARD, 120/240V

PANELBOARD 208Y/120V

DISCONNECT SWITCH CONNECTION (FURNISHED WITH EQUIPMENT UON.) 3P = NO. OF POLES 60 = SWITCH RATING 40 = FUSE RATING (NF INDICATES NON-FUSIBLE).

MOTOR STARTER, CONTROLLER, OR RELAY FOR MECHANICAL EQUIPMENT. DEVICE SUPPLIED BY MECHANICAL CONTRACTOR; INSTALLED AND CONNECTED BY ELECTRICAL CONTRACTOR. VERIFY CITY OF HAMPTON

EXACT LOCATION. ELECTRICAL LEGEND, NOTES, ABBREVIATIONS

MOTOR CONNECTION, HP, AND CHARACTERISTICS AS NOTED

ELECTRICAL CONNECTION AS NOTED.

JUNCTION BOX (J.B.) FLUSH MOUNTED 4"SQ x DEPTH REQ'D UON. S=SURFACE MOUNTED

JUNCTION BOX (J.B.) SURFACE MOUNTED ABOVE CEILING 4"SQ X DEPTH REQ'D UON. E-001 WATER HEATER CONNECTION. 11 18 DEMOLITION WORK NOTES: (THIS SHEET ONLY)

DISCONNECT ELECTRICAL TO FAN COIL UNIT. REMOVE WIRING BACK TO RESPECTIVE ELECTRICAL PANEL. CONDUIT SHALL BE CUT FLUSH WITH FLOOR. PACK AND SEAL CONDUIT WITH APPROVED SEALANT. SEE COASTAL ELECTRICAL PANEL SCHEDULES FOR CIRCUIT IDENTIFICATION. E N G I N E E R I N G

REMOVE COOLING TOWER CIRCUIT BACK TO PANEL. 2406 Princess Anne Road, Suite 200 REMOVE CONDENSER PUMP CIRCUIT BACK TO PANEL Virginia Beach, VA 23456 Phone (757) 563-9027 STOR 02 UTIL STOR REMOVE CHILLED WATER PUMP CIRCUIT BACK TO PANEL. 1 1 01 1 1 DRESSING Facsimile(757) 563-9028 1 01 DRUG PHYSICIAN & EXAM 18 1 OFFICE 21 (R) CHILLER 4 PHYSICIAN CLINIC REMOVE CHILLER CIRCUIT BACK TO PANEL. TH 01 OFFICE EAL OF ELECTRICAL 5 W V MECHANICAL N I REMOVE CIRCULATING PUMP BACK TO PANEL. O R ROOM PHYSICIAN G (E) COOLING ROOM EXAM M I TOWER (E) EXAM N 02 EXAM M BOILER 8 03 I X-RAY & MENTAL AFTERCARE A 01 O 02 REMOVE BOILER CIRCUIT BACK TO PANEL. C TOILET TOILET RICHARD M. KLEIN 01 02 DARK ROOM PHASE 1 REMOVE EXISTING PANEL "MDP". SEE RISER DIAGRAM SHEET E-601 FOR No. 027864 6 7 P R R EXISTING CIRCUITS AND FEEDERS TO BE TIED BACK INTO NEW PANEL O E 2 3 F E ES IN "MDP". SIO NG 1 1 NAL E

WAITING EXAM EXAM CLERICAL 01 DENTAL DENTAL EXAM LAB 1 08 09 01 02 03 10 OFFICE 1 TOILET TOILET 10 11 EKG

UTIL ROOM 11 DENTAL 02 OBSERVATION CLERK 42 01 STOR STOR STOR 05 1 1 1 1 1 1 1 03 04 PHYSICIAN PSYCHOLOGIST 03

PHASE4 EXAM 05

ROOM 10 WAITING SOCIAL 1 1 02 WORKER PHASE 3

1 NURSE EXAM 1 03

1 TOILET TOILET 03 04 LUNCH ROOM AUDITORIUM BPM PHYSICIAN UTIL BPM RMK

04 03 15-041 COURTYARD 1 01-06-2017

NURSES & CLERK EXAM 04 071 1 TOILET 1 09 STOR 08 1 RECORDS NURSES & TOILET ROOM CLERK 05 03 TOILET 1 08 (E) ROOF TOP 1 UNIT (224 MBH) TOILET 06

MECH. STOR LOUNGE EQUIP PHASE 2 STORAGE OFFICE 06 1 NURSES SUPER 1 1 1 1

NURSES & CLERK NURSE & CLERK CLERICAL 02 01 02 ROOM 8 1 1 1 PHARMACY

1 1 1 1

ROOM 6 CITY OF HAMPTON ELECTRICAL FLOOR PLAN - DEMOLITION POWER STOR 1 ADMIN ASST 07 SANITARIANS ASST RECEPTIONIST DIRECTOR CONFERENCE VITAL DIRECTOR STATISTICS

1 1 1 1 1 1 1 1 1 1 1 TOILET 07

GRAPHIC SCALE E-101 ELECTRICAL FLOOR PLAN - DEMOLITION POWER 0' 4' 8' 12' 20' 40' 1/8" = 1'-0" SCALE: 1/8" = 1'-0" 12 18 DEMOLITION WORK NOTES: (THIS SHEET ONLY)

TYPICAL- REMOVE EXISTING LIGHTING FIXTURES AS REQUIRED FOR INSTALLATION TO INSTALLATION OF NEW HVAC DUCTWORK AND EQUIPMENT. COASTAL E N G I N E E R I N G TYPICAL- CONTRACTOR TO REMOVE EXISTING ACOUSTICAL CEILING PANELS AND GRID AS REQUIRED FOR INSTALLATION OF NEW HVAC 2406 Princess Anne Road, EQUIPMENT, DUCTWORK, AND ASSOCIATED HARDWARE. RETAIN Suite 200 ACOUSTICAL CEILING PANELS & GRID FOR REINSTALLATION AFTER HVAC Virginia Beach, VA 23456 WORK IS COMPLETED IN THE AREA. INCLUDE IN BID PROPOSAL TEN Phone (757) 563-9027 UTIL STOR STOR 02 PERCENT NEW ACOUSTICAL CEILING COMPONENTS/MATERIALS TO 01 DRESSING Facsimile(757) 563-9028 01 DRUG PHYSICIAN & EXAM 18 OFFICE 21 MATCH EXISTING. SEE GENERAL PHYSICIAN CLINIC WORK NOTE 1 SEE GENERAL TH 01 OFFICE TYPICAL- CONTRACTOR TO REMOVE EXISTING GYPBOARD CEILING AND EAL OF ELECTRICAL W V WORK NOTE 2 MECHANICAL TYP. 3 N I SUPPORTS AS REQUIRED FOR INSTALLATION OF NEW HVAC EQUIPMENT, O R ROOM PHYSICIAN G ROOM EXAM M I EXAM DUCTWORK, AND ASSOCIATED HARDWARE. INSTALL NEW GYPBOARD N 02 EXAM M 2 TYP. 03 I X-RAY & MENTAL AFTERCARE A 01 CEILING AND PAINT TO MATCH EXISTING CONDITIONS & COLORS AFTER O 02 C TOILET TOILET HVAC WORK IS COMPLETED IN THE AREA. RICHARD M. KLEIN DARK ROOM 01 2 TYP. 02 PHASE 1 No. 027864 P R R O E F E 2 TYP. E N TYP. 3 TYP. 3 TYP. 3 SS GI TYP. 2 IONAL EN

WAITING EXAM EXAM CLERICAL 01 DENTAL DENTAL EXAM LAB 08 09 01 02 03 10 OFFICE

2 TYP. TOILET TOILET 10 11 EKG

UTIL ROOM 11 DENTAL 02 OBSERVATION CLERK 42 01 STOR 05 TYP. 3 STOR STOR 03 04 PHYSICIAN GENERAL WORK NOTES: (THIS SHEET ONLY) PSYCHOLOGIST 03 1. ALL WORK IN THIS AREA SHALL BE DONE ON NIGHTS OR WEEKENDS. PHASE4 EXAM ENTRANCE SHALL REMAIN OPEN TO THE PUBLIC AT ALL TIMES. THIS IS 05 THE ONLY HANDICAPPED ACCESSIBLE ENTRANCE TO THE BUILDING.

ROOM 10 WAITING 2. ALL WORK IN THIS AREA SHALL BE DONE ON NIGHTS OR WEEKENDS. SOCIAL 02 WORKER PHASE 3 ENTRANCE SHALL REMAIN OPEN TO THE PUBLIC FOR ACCESS TO THE PHASE WHICH IS NOT UNDER CONSTRUCTION AT ALL TIMES.

NURSE EXAM 03

TOILET TOILET 03 04 LUNCH ROOM AUDITORIUM BPM PHYSICIAN UTIL BPM RMK

04 03 15-041 COURTYARD 01-06-2017

NURSES & TYP. 3 CLERK EXAM 04 07

TOILET 09 STOR 08 RECORDS TYP. 3 NURSES & TOILET ROOM CLERK 05 03 TOILET 3 TYP. 08 TOILET TYP. 3 06

MECH. STOR LOUNGE EQUIP PHASE 2 2 TYP STORAGE NURSES OFFICE 06 SUPER

NURSES & CLERK NURSE & CLERK CLERICAL 02 01 02 ROOM 8 2 TYP.

PHARMACY

2 TYP.

ROOM 6 CITY OF HAMPTON ELECTRICAL FLOOR PLAN - DEMOLITION LIGHTING STOR ADMIN ASST 07 TYP. 3 SANITARIANS ASST RECEPTIONIST DIRECTOR TYP. 3 CONFERENCE VITAL TYP. 3 DIRECTOR STATISTICS SEE GENERAL WORK NOTE 2 TOILET 07

SEE GENERAL WORK NOTE 2 GRAPHIC SCALE E-102 ELECTRICAL FLOOR PLAN - DEMOLITION LIGHTING 0' 4' 8' 12' 20' 40' 1/8" = 1'-0" SCALE: 1/8" = 1'-0" 13 18 NEW WORK NOTES: (THIS SHEET ONLY)

ROUTE (3)#8 THHN CU, (1)#10 CU GND IN 3/4 " CONDUIT ABOVE CEILING THROUGH BAR JOISTS TO NEW PANEL "LD". MARK EACH DISCONNECT WITH PHENOLIC ENGRAVED TAG INDICATING CIRCUIT AND PANEL ID. COASTAL E N G I N E E R I N G DISCONNECT FOR UNIT HEATER "UH-1". 2406 Princess Anne Road, NEW SMOKE DUCT DETECTOR FURNISHED AND INSTALLED BY Suite 200 MECHANICAL CONTRACTOR. PROVIDE NEW NOTIFICATION CIRCUIT Virginia Beach, VA 23456 CONNECTED TO EXISTING FIRE ALARM PANEL. PROVIDE ADDITIONAL Phone (757) 563-9027 UTIL STOR STOR 02 ADDRESSABLE MODULE IN FIRE ALARM PANEL OR NAC PANEL AS 01 DRESSING Facsimile(757) 563-9028 01 DRUG PHYSICIAN & EXAM 18 OFFICE 21 REQUIRED..

PHYSICIAN CLINIC TH 2 01 OFFICE EAL OF ELECTRICAL W V MECHANICAL N I O R ROOM PHYSICIAN G ROOM EXAM 3 M I EXAM N 02 EXAM M 03 I X-RAY & MENTAL AFTERCARE A 01 O 02 C TOILET TOILET RICHARD M. KLEIN 01 02 DARK ROOM No. 027864 RTU-1 PHASE 1 P R R O E F E E N SS GI IONAL EN 3

WAITING

EXAM EXAM RTU-5 CLERICAL 01 DENTAL DENTAL EXAM LAB 08 09 01 02 03 10 1 OFFICE

TOILET TOILET 10 11 EKG

UTIL ROOM 11 DENTAL 02 OBSERVATION CLERK 42 01 STOR STOR STOR 05 03 04 PHYSICIAN PSYCHOLOGIST 03

PHASE4 EXAM 05

ROOM 10 WAITING SOCIAL 02 WORKER PHASE 3

NURSE EXAM 03

TOILET TOILET 03 04 LUNCH ROOM 3 AUDITORIUM BPM RTU-8 PHYSICIAN UTIL BPM RMK

04 03 15-041 1 3 COURTYARD RTU-4 3 01-06-2017 1 NURSES & CLERK EXAM

04 RTU-6 1 07

TOILET 09 1 RTU-2 STOR 08 3 RECORDS NURSES & TOILET ROOM CLERK 05 03 TOILET 08 (E) ROOF TOP UNIT (224 MBH) TOILET 06

MECH. STOR LOUNGE EQUIP PHASE 2 STORAGE NURSES OFFICE 06 SUPER

NURSES & CLERK NURSE & CLERK CLERICAL 3 02 01 02 ROOM 8 3 RTU-7 1 RTU-6 PHARMACY 1

3 RTU-3 ROOM 6 CITY OF HAMPTON ELECTRICAL FLOOR PLAN - NEW WORK POWER 1 STOR ADMIN ASST 07 SANITARIANS ASST RECEPTIONIST DIRECTOR CONFERENCE VITAL DIRECTOR STATISTICS

TOILET 07

GRAPHIC SCALE E-201 ELECTRICAL FLOOR PLAN - NEW WORK POWER 0' 4' 8' 12' 20' 40' 1/8" = 1'-0" SCALE: 1/8" = 1'-0" 14 18 NEW WORK NOTES: (THIS SHEET ONLY)

TYPICAL- RE-INSTALL EXISTING LIGHTING FIXTURES AFTER NEW HVAC WORK IS COMPLETED. CONNECT TO EXISTING LIGHTING CIRCUIT FROM DEMOLITION. COASTAL E N G I N E E R I N G RE-INSTALL ACOUSTICAL CEILING PANELS AND GRID AFTER INSTALLATION OF NEW HVAC EQUIPMENT, DUCTWORK, AND ASSOCIATED 2406 Princess Anne Road, HARDWARE HAS BEEN COMPLETED. INCLUDE IN BID PROPOSAL TEN Suite 200 PERCENT NEW ACOUSTICAL CEILING COMPONENTS/MATERIALS TO Virginia Beach, VA 23456 MATCH EXISTING. Phone (757) 563-9027 UTIL STOR STOR 02 01 DRESSING Facsimile(757) 563-9028 01 DRUG PHYSICIAN & EXAM 18 OFFICE 21 SEE GENERAL PHYSICIAN CLINIC WORK NOTE 1 SEE GENERAL TH 01 OFFICE EAL OF ELECTRICAL W V WORK NOTE 2 MECHANICAL N I O R ROOM PHYSICIAN G ROOM EXAM M I EXAM N 02 EXAM M 03 I X-RAY & MENTAL AFTERCARE A 01 O 02 C TOILET TOILET RICHARD M. KLEIN DARK ROOM 01 02 PHASE 1 No. 027864 P R R O E F E E N TYP 1 TYP 2 SS GI IONAL EN

WAITING EXAM EXAM CLERICAL 01 DENTAL DENTAL EXAM LAB 08 09 01 02 03 10 OFFICE

TOILET TOILET 10 11 EKG

UTIL ROOM 11 DENTAL 02 OBSERVATION CLERK 42 01 STOR STOR STOR 05 03 04 PHYSICIAN PSYCHOLOGIST 03

PHASE4 EXAM 05

ROOM 10 WAITING SOCIAL 02 WORKER PHASE 3

TYP. 2

NURSE EXAM 03 TYP. 1 TOILET TOILET 03 04 LUNCH ROOM AUDITORIUM BPM PHYSICIAN UTIL BPM RMK

04 03 15-041 COURTYARD 01-06-2017

NURSES & CLERK EXAM 04 07 TYP 1 TYP 2 TOILET 09 STOR 08 RECORDS NURSES & TOILET ROOM CLERK 05 03 TOILET 08 TOILET 06

MECH. STOR LOUNGE EQUIP PHASE 2 STORAGE NURSES OFFICE 06 SUPER

NURSES & CLERK NURSE & CLERK CLERICAL 02 01 02 ROOM 8

PHARMACY TYP TYP TYP 1 TYP 2 1 2

ROOM 6 CITY OF HAMPTON ELECTRICAL FLOOR PLAN - NEW WORK LIGHTING STOR ADMIN ASST 07 SANITARIANS ASST RECEPTIONIST DIRECTOR CONFERENCE VITAL DIRECTOR STATISTICS SEE GENERAL WORK NOTE 2 TOILET 07

SEE GENERAL WORK NOTE 2 GRAPHIC SCALE E-202 ELECTRICAL FLOOR PLAN - NEW WORK LIGHTING 0' 4' 8' 12' 20' 40' 1/8" = 1'-0" SCALE: 1/8" = 1'-0" 15 18 COASTAL E N G I N E E R I N G

2406 Princess Anne Road, Suite 200 Virginia Beach, VA 23456 Phone (757) 563-9027 Facsimile(757) 563-9028

TH EAL OF W V N IR O G M I N M I

O A

C RICHARD M. KLEIN No. 027864 P R R O E F E E N SS GI IONAL EN BPM BPM RMK 15-041 01-06-2017 CITY OF HAMPTON ELECTRICAL PANELBOARD SCHEDULES

E-501

16 18 COASTAL E N G I N E E R I N G

2406 Princess Anne Road, Suite 200 Virginia Beach, VA 23456 Phone (757) 563-9027 Facsimile(757) 563-9028

TH EAL OF W V N IR O G M I N M I

O A

C RICHARD M. KLEIN No. 027864 P R R O E F E E N SS GI IONAL EN

(E)100/3 (N)60/3/40 (N)60/3/50 (N)60/3/50 (N)60/3/50 (N)60/3/50 (N)60/3/50 (N)60/3/40 (N)60/3/40 N3R N3R N3R N3R N3R N3R N3R N3R

FEEDER #11 (N)(3)#8,(1)#10 (N)(3)#8,(1)#10 (N)(3)#8,(1)#10 (N)(3)#8,(1)#10 CU IN 3/4 "C. CU IN 3/4 "C. CU IN 3/4 "C. CU IN 3/4 "C.

(N)(3)#8,(1)#10 (N)(3)#8,(1)#10 (N)(3)#8,(1)#10 (N)(3)#8,(1)#10 CU IN 3/4 "C. CU IN 3/4 "C. CU IN 3/4 "C. CU IN 3/4 "C. BPM BPM RMK 15-041 01-06-2017

NEW (4) 500 CU,(1) 3 CU GND IN 4"C

(E) CT (E) METER

30/2 EXIT LTS

EXISTING PANEL MDP 800A MCB 120/208V PROVIDE NEW 800AMP RATING 3PH 4W PLUG IN MAIN BREAKER. SURFACE SEE PANEL SCHEDULE FOR OTHER WORK IN PANEL.

INSTALL NEW 225A 3P ENCL CB TO TEMPORARY POWER EXISTING CHILLER WHILE NEW RTU CIRCUITS AND PANEL "LD" ARE INSTALLED PER PHASING SEQUENCE. TAP FROM MAIN WITH (3)-#4/0 THHN CU, (1)# 4 CU GND IN 2" C. DISCONNECT AND REMOVE WHEN CHILLER IS REMOVED. CITY OF HAMPTON ELECTRICAL RISER DIAGRAM, PANEL BOARD SCHEDULES, AND LOAD SUMMARY

ELECTRICAL RISER DIAGRAM NO SCALE E-601

17 18 ELECTRICAL SPECIFICATIONS

1. GENERAL CONDITIONS 5.a.d. FLEXIBLE METAL CONDUIT - UL-1 10.b. WIRE AND CABLE SHALL BE GENERAL ELECTRIC, ANACONDA, ROME, GENERAL CABLE, 1.a. WORK UNDER THIS DIVISION SHALL BE SUBJECT TO THE AIA GENERAL AND SPECIAL 5.a.e. PLASTIC CONDUIT (PVC) - NEMA TC-2 AND TC-3 OR PHELPS DODGE. NO MC CABLING ALLOWED ON THIS PROJECT. CONDITIONS. 5.b. CONDUIT SHALL BE RUN CONCEALED, EXCEPT CONDUIT MAY BE EXPOSED ABOVE 10.c. WIRE AND CABLE SHALL BE COPPER 600 VOLT INSULATION, MINIMUM SIZE NO. 12, TYPE 2. SCOPE JOIST IN MECHANICAL ROOMS AND SPACES WITH EXPOSED CONSTRUCTION AS "THW", "THWN" OR "THHN" AS APPLICABLE, UNLESS OTHERWISE INDICATED ON COASTAL 2.a. THE WORK REQUIRED FOR THIS SECTION INCLUDES LABOR, MATERIALS, EQUIPMENT, APPROVED BY THE ENGINEER. CONDUIT INDICATED CONCEALED IN WALLS AND ABOVE DRAWINGS. E N G I N E E R I N G APPURTENANCES, SERVICE AND SUPERVISION TO PROVIDE COMPLETE ELECTRICAL CEILINGS SHALL BE THIN-WALL TYPE ELECTRICAL METALLIC TUBING FOR SIZES UP TO SYSTEMS AS SHOWN ON THE DRAWINGS. TWO INCHES. 10.d. BRANCH CIRCUIT WIRING SHALL BE TYPE "THHN". 2406 Princess Anne Road, Suite 200 3. SPECIFICATIONS, CODES AND STANDARDS 5.c. INTERMEDIATE METAL CONDUIT SHALL BE PERMITTED IN LIEU OF RIGID WHERE 10.e. WIRES NO. 10 AND 12 AWG SHALL BE CONNECTED WITH COIL SPRING INSERT "WIRE- Virginia Beach, VA 23456 3.a. THE LATEST EFFECTIVE PUBLICATIONS OF THE FOLLOWING STANDARDS, CODES, ETC. ALLOWED IN ARTICLE 345 OF THE NEC. NUT" OR "WING-NUT" CONNECTORS MANUFACTURED BY IDEAL INDUSTRIES OR Phone (757) 563-9027 FORM A PART OF THESE SPECIFICATIONS: APPROVED EQUAL. CONNECTORS SHALL BE RATED 600 VOLTS. COPPER WIRES NO. 8 Facsimile(757) 563-9028 3.a.a. NATIONAL ELECTRICAL CODE (NEC) 5.d. MINIMUM SIZE CONDUIT SHALL BE ONE-HALF INCH WITH LARGER SIZES AS REQUIRED AND LARGER SHALL BE JOINED OR TERMINATED WITH PRESSURE TYPE COPPER 3.a.b. STANDARD RULES OF THE INSTITUTE OF ELECTRICAL AND ELECTRONIC BY THE NATIONAL ELECTRICAL CODE FOR NUMBER OF WIRES CONTAINED THEREIN. CONNECTORS. ENGINEERS. TH EAL OF 3.a.c. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION 5.e. RIGID CONDUIT FITTINGS SHALL BE THREADED, EXCEPT WHERE RIGID CHANGES TO 10.f. WIRE SHALL BE COLOR CODED AS FOLLOWS: W V N IR O G 3.a.d. INTERNATIONAL BUILDING CODE EMT ABOVE SLAB, FITTING MAY BE THREADLESS TYPE. ELECTRICAL METALLIC TUBE 10.f.a. 120/208 VOLT SYSTEM M I N M I

FITTINGS SHALL BE GALVANIZED STEEL SET SCREW; CAST METAL NOT ACCEPTABLE. 10.f.a. PHASE A - BLACK A 3.a.e. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) O

C 10.f.b. PHASE B - RED RICHARD M. KLEIN 3.b. THIS CONTRACTOR SHALL GIVE REQUIRED NOTICES, OBTAIN NECESSARY PERMITS, 5.f. FLEXIBLE CONDUIT SHALL BE GALVANIZED, SINGLE STRIP TYPE. IN AREAS SUBJECT TO 10.f.c. PHASE C - BLUE No. 027864 AND PAY PERMIT FEES. MOISTURE, OR WHERE CALLED FOR ON THE DRAWINGS, FLEXIBLE CONDUIT SHALL 10.f.d. NEUTRAL - WHITE P R R O E F E HAVE PLASTIC COVERING IN ACCORDANCE WITH NEC, ARTICLE 351-A. FITTINGS SHALL 10.f.e. GROUND - GREEN E N SS GI 4. DRAWINGS BE STANDARD UL APPROVED WITH GROUND CONNECTOR. WATERTIGHT IONAL EN 4.a. THE DRAWINGS INDICATE DIAGRAMMATICALLY THE EXTENT OF THE WORK. MINOR CONNECTORS SHALL BE USED WITH PLASTIC COVERED CONDUIT, FLEXIBLE CONDUIT, 10.g. ELECTRICAL DESIGNS ARE BASED ON COPPER WIRE AND CABLE. (ALUMINUM WIRE VARIATIONS IN LOCATION OF EQUIPMENT SHALL BE MADE UPON WRITTEN APPROVAL MINIMUM 18 INCHES IN LENGTH, SHALL BE USED FOR CONNECTIONS TO MOTORS AND AND CABLE SHALL NOT BE PERMITTED.) OF THE ARCHITECT AT NO ADDITIONAL CHARGE. OTHER EQUIPMENT SUBJECT TO VIBRATION. 11. CUTTING AND PATCHING 5. EQUIPMENT 5.g. EXPOSED CONDUITS SHALL BE RUN PARALLEL AND PERPENDICULAR TO BUILDING 11.a. CUTTING, DRILLING, AND CHANNELING REQUIRED FOR THIS WORK SHALL BE DONE 5.a. STARTERS, CONTROLLERS, ETC; SHALL BE PROVIDED UNDER THE DIVISION CONSTRUCTION AND SHALL BE SUPPORTED AS HEREINAFTER SPECIFIED AND IN UNDER THIS SECTION BY SKILLED MECHANICS OF TRADE INVOLVED. FURNISHING THE EQUIPMENT UNLESS OTHERWISE NOTED. ACCORDANCE WITH NEC. THE METHODS OF INSTALLATION SHALL BE REVIEWED BY THE ENGINEER PRIOR TO INSTALLATION. 12. EQUIPMENT MARKING AND PAINTING 5.b. POWER WIRING AND POWER CONNECTIONS TO EQUIPMENT SHALL BE PROVIDED 12.a. SAFETY SWITCHES, CABINETS, ETC., SHALL BE PROVIDED WITH PERMANENTLY UNDER "ELECTRICAL" UNLESS OTHERWISE INDICATED ON THE ELECTRICAL DRAWINGS. 5.h. CONDUIT SUPPORTS SHALL BE APPROVED WALL BRACKETS, TRAPEZE, STRAP HANGER ATTACHED (ADHESIVES NOT ACCEPTABLE) ENGRAVED BAKELITE DESIGNATION PLATES OR PIPE STRAPS SECURED TO HOLLOW MASONRY WITH TOGGLE BOLTS; TO METAL TO INDICATE EQUIPMENT OR CIRCUIT CONTROLLED. 5.c. WHEN SUBSTITUTED MOTORS AND/OR EQUIPMENT REQUIRES ELECTRICAL SURFACES WITH MACHINE SCREWS; AND TO WOOD WITH WOOD SCREWS. ANY FORM 12.b. EXPOSED CONDUIT, SUPPORTS, HANGERS, AND UNFINISHED EQUIPMENT SHALL MODIFICATIONS, THE COST OF THE ELECTRICAL MODIFICATIONS AND COORDINATION OF TIE WIRE IS UNACCEPTABLE. RECEIVE A MINIMUM OF TWO COATS OF PAINT SUITABLE FOR SERVICE INTENDED. SHALL BE INCLUDED UNDER THE DIVISION PROVIDING THE MOTOR AND/OR EQUIPMENT. COLORS SHALL BE AS SELECTED OR APPROVED BY THE ENGINEER. 5.i. PROVIDE O.Z. TYPE "AX" EXPANSION FITTINGS WHERE CONDUITS CROSS EXPANSION 6. COORDINATION JOINTS. 13. ACCESS DOORS 6.a. COOPERATE AND COORDINATE THE WORK OF THIS DIVISION WITH OTHER TRADES. 13.a. THIS CONTRACTOR SHALL FURNISH, AND THE GENERAL CONTRACTOR SHALL INSTALL 5.j. CONDUIT TERMINATIONS ONE AND ONE-QUARTER INCH AND LARGER AND CONDUIT STEEL ACCESS DOORS WHERE REQUIRED, STYLE NECESSARY FOR SURFACE IN WHICH 6.b. CONTRACTOR TO SUBMIT 6 SETS (OWNER WILL RETURN 3 SETS NOTED WITH ACTION STUBS SHALL HAVE O.Z. TYPE "B" INSULATING BUSHINGS. RIGID CONDUIT PLACED. SUBMIT SHOP DRAWINGS OF PROPOSED MATERIAL, INSTALLATION AND TAKEN)SPECIFICATIONS AND DETAIL FOR EQUIPMENT AND FABRICATED MATERIALS TERMINATIONS ONE INCH AND SMALLER SHALL HAVE O.Z. TYPE "A" INSULATING EXACT LOCATIONS TO THE ENGINEER FOR APPROVAL. FOR OWNER'S APPROVAL PRIOR TO ISSUING PURCHASE ORDER. OWNER'S APPROVAL BUSHINGS. DOES NOT RELIEVE CONTRACTOR OF ANY RESPONSIBILITY FOR PERFORMANCE AND 14. SUBSTANTIAL COMPLETION OPERATION. 5.k. CONDUITS AND CABLES PASSING THROUGH FIRE RATED ASSEMBLIES SHALL BE 14.a. UPON COMPLETION OF THE ENTIRE WORK, THE CONTRACTOR SHALL PERFORM SUCH SEALED BY APPROVED METHODS OR BY INSTALLING O.Z. FIRE-SEALS TO MAINTAIN "UL" TESTS AS REQUIRED BY THE ARCHITECT. THE ENGINEER SHALL BE GIVEN 48 HOURS 2. MATERIAL AND EQUIPMENT CLASSIFIED FIRE RATING. NOTICE BEFORE TESTS ARE MADE. THE CONTRACTOR SHALL FURNISH THE 2.a. ELECTRICAL MATERIALS AND EQUIPMENT SHALL BE NEW, LISTED, AND LABELED BY AN ARCHITECT A CERTIFICATE OF APPROVAL FROM THE LOCAL INSPECTION AUTHORITY APPROVED TESTING AGENCY. 5.l. CONDUITS PASSING THROUGH EXTERIOR CONCRETE WALLS, FLOORS OR FOOTINGS HAVING JURISDICTION. 2.a.a. INSTALL MATERIALS AND EQUIPMENT IN A FIRST CLASS AND WORKMANLIKE BELOW GRADE AND SLAB ON GRADE SHALL BE MADE WATERTIGHT. PROVIDE PIPE MANNER AND RUN CONCEALED THROUGHOUT THE BUILDING, EXCEPT AS SLEEVES IN THE CONCRETE WITH ONE-HALF INCH MINIMUM CLEARANCE AROUND THE 15. WARRANTY INDICATED. CONDUIT AND CAULK WITH ASKUM AND SEALANT OR PROVIDE O.Z. TYPE "FSK" 15.a. CONTRACTOR SHALL FURNISH WRITTEN WARRANTY, COUNTERSIGNED, AND CONDUIT ENTRANCE SEALS. PROVIDE CONDUIT SEALING BUSHINGS O.Z. TYPE "CSB" GUARANTEED BY THE GENERAL CONTRACTOR, STATING THAT THE WORK EXECUTED 2.b. MATERIAL AND EQUIPMENT SHALL BE PROPERLY STORED AND PROTECTED AT THE OR "CSBG" SERIES AS APPLICABLE AND PROVIDE WITH CABINET ADAPTER PLATES UNDER THIS DIVISION OF THE SPECIFICATIONS SHALL BE FREE FROM DEFECTS OF BPM BPM RMK

PROJECT SITE. WHEN REQUIRED. MATERIAL AND WORKMANSHIP FOR A PERIOD OF 12 MONTHS FROM DATE OF FINAL 15-041 ACCEPTANCE. DEFECTS DEVELOPING DURING THAT PERIOD SHALL BE CORRECTED 2.c. SIX COMPLETE SCHEDULES OF MATERIALS AND EQUIPMENT PROPOSED FOR 6. RECEPTACLE BOXES WITHOUT COST TO THE OWNER. 01-06-2017 INSTALLATION SHALL BE SUBMITTED TO THE ARCHITECT WITHIN 30 DAYS AFTER 6.a. RECEPTACLE BOXES SHALL BE HOT DIPPED GALVANIZED STEEL TYPE WITH STANDARD AWARD OF THE CONTRACT. THE SCHEDULES SHALL INCLUDE CATALOG CUTS, KNOCKOUTS AS REQUIRED FOR CONDUIT TERMINATION. MINIMUM SIZE OF DIAGRAMS AND SUCH OTHER DESCRIPTIVE DATA AND/OR SAMPLES AS MAY BE RECEPTACLE BOX SHALL BE FOUR INCHES SQUARE, ONE AND ONE-QUARTER INCHES REQUIRED BY THE ARCHITECT. LIGHTING FIXTURE SUBMITTALS SHALL INCLUDE DEEP. RECEPTACLE BOXES FOR EXPOSED TILE AND BLOCK SHALL BE PROVIDED WITH PHOTOMETRIC REPORTS BY INDEPENDENT TESTING LABORATORIES FOR EACH SQUARE CORNERED TILE RING, SIZE AS REQUIRED. FIXTURE INDICATED BASED ON ITS PUBLISHED PROCEDURES. 6.b. RECEPTACLE BOXES OCCURRING IN FINISHED OUTSIDE WALLS AND WET AREAS SHALL 2.d. SUBMITTALS THAT DO NOT BEAR THE GENERAL CONTRACTORS STAMP OF APPROVAL BE CAST AND PROVIDED WITH GASKETS BETWEEN BOX AND WATERPROOF COVER. THEREON WILL BE REJECTED WITHOUT REVIEW. 6.c. WHERE SEVERAL FEEDERS PASS THROUGH A COMMON PULL BOX OR JUNCTION BOX, 2.e. CONTRACTOR SHALL FURNISH AND INSTALL ALL EQUIPMENT AND MATERIALS FOR A THE FEEDERS SHALL BE TAGGED TO INDICATE CLEARLY THEIR ELECTRICAL COMPLETE INSTALLATION IN ALL RESPECTS READY OF INTENDED USE AND THE STRICT CHARACTERISTICS, CIRCUIT NUMBER, AND PANEL DESIGNATION. PAINT SAME ACCORDANCE WITH STATE AND LOCAL CODES AND MANUFACTURER'S INFORMATION ON COVER OF THE BOX. RECOMMENDATIONS. PAY NECESSARY FEES AND OBTAIN PERMITS. INITIATE, MAINTAIN AND SUPERVISE ALL SAFETY PRECAUTIONS AND PROCEDURES. 7. WIRING DEVICES 7.a. WIRING DEVICES SHALL BE AS MANUFACTURED BY LEVITON, ARROW-HART, BRYANT, 2.f. EQUIPMENT AND MATERIALS SHALL BE OF THE TYPE, SIZE AND MANUFACTURERS PASS AND SEYMOUR, OR HUBBELL. INDICATED ON THE DRAWINGS OR AN APPROVED EQUIVALENT. 7.b. DEVICE PLATES SHALL BE SATIN STAINLESS STEEL. 2.g. THE CONTRACTOR SHALL SUPPLY AND INSTALL THE MATERIALS AND EQUIPMENT COVERED BY THE PLANS AND SPECIFICATIONS TO THE OWNER COMPLETE AND IN 7.c. DEVICES SHALL BE IVORY FIRST CLASS CONDITION IN EVERY RESPECT. HE SHALL GUARANTEE THAT THE MATERIAL, EQUIPMENT, AND WORKMANSHIP SUPPLIED AND INSTALLED BY HIM SHALL 8. DISCONNECT SWITCHES BE ENTIRELY FREE FROM DEFECTS AND THAT HE WILL REPAIR OR REPLACE AT HIS 8.a. SWITCHES SHALL NEMA TYPE "GD" OR "HD" AS REQUIRED. FUSED SWITCHES SHALL BE OWN EXPENSE, ANY MATERIALS, EQUIPMENT, AND WORKMANSHIP IN WHICH DEFECTS NEMA TYPE "HD" UNLESS OTHERWISE INDICATED, WITH CLASS "R" FUSE CLIPS. MAIN ARE FOUND. DISCONNECT SWITCHES AND SWITCHES RATED 600 VOLTS SHALL BE TYPE "HD" AND HAVE FULL COVER INTERLOCKS AND QUICK-MAKE, QUICK-BREAK MECHANISM. 3. SUBSTITUTION OF MATERIAL AND EQUIPMENT 3.a. THE NAME OF A CERTAIN BRAND, MAKE, MANUFACTURER OF DEFINITE SPECIFICATION 8.b. FUSED SWITCHES SHALL BE PROVIDED COMPLETE WITH FUSES. IS TO DENOTE THE QUALITY STANDARD OF ARTICLE DESIRED. SUBSTITUTION OF ANY OTHER BRAND, MAKE, OR MANUFACTURER, WHICH IN THE OPINION OF THE ENGINEER 8.c. SWITCHES SHALL BE SQUARE D, GENERAL ELECTRIC, I.T.E., CUTLER HAMMER, OR IS RECOGNIZED THE EQUAL OF THAT SPECIFIED, MAY BE ACCEPTED. WESTINGHOUSE.

3.b. WHERE THREE OR MORE MANUFACTURERS ARE SPECIFIED, THERE WILL BE NO 8.d. SWITCHES SHALL BE SECURELY MOUNTED TO WALL, STRUCTURE, OR EQUIPMENT.

SUBSTITUTIONS PROVIDE MISCELLANEOUS ACCESSORIES FOR MOUNTING SWITCHES, INCLUDING CITY OF HAMPTON STEEL ANGLES WHERE REQUIRED. ELECTRICAL SPECIFICATIONS 4. RECORD DRAWINGS 4.a. UPON COMPLETION OF THE WORK, THE CONTRACTOR SHALL SUBMIT SEPIAS AND/OR 9. FUSES MARKED UP DRAWINGS AND SKETCHES TO THE ARCHITECT. 9.a. FUSES FOR PROTECTION OF MECHANICAL AND PLUMBING EQUIPMENT SHALL BE "FUSETRON" UL CLASS "RK5" SIZED PER MANUFACTURERS RECOMMENDATION, 5. CONDUIT UNLESS OTHERWISE INDICATED. 5.a. CONDUIT AND FITTINGS SHALL CONFORM TO THE FOLLOWING: 5.a.a. RIGID STEEL - ANSI C80.1 10. WIRE AND CABLE 5.a.b. INTERMEDIATE METAL CONDUIT - UL 1242 10.a. WIRE AND CABLE SHALL BE INSTALLED IN CONDUIT. 5.a.c. ELECTRICAL METALLIC TUBING (EMT) - ANSI C80.3 E-701

18 18