Mechanical Study ·

Total Page:16

File Type:pdf, Size:1020Kb

Mechanical Study · .- B.AKER I WOHl ARCHITECTS · ~32 Lincoln Street Be,ston, MA 02111 T: 617 . ·350 . 7420 · www.baker-wohl.am MECHANICAL STUDY · ! I ' I I Prepared For . I I iI I WESTERN MASSACHUSETTS. H.o ·SPITAt. 91 .East Mountain Road Westfield, MA 01085 Prepared By · Wozny/Barbar & Associates, Inc. 1.0.90. Washington S~reet Hanover, MA 02339 '. And A M Fogarty ·& Associates, Inc. 17;5 Derby Street- Suite 5 . Hingham, MA 020.43 ! • Preface This study includes an engineering review of the existing mechanical heating, ventilating, and air­ conditioning systems serving five buildings located on the Western Massachusetts Hospital campus. At least, two HVAC options for each building are presented, keeping in mind the future potential uses of the buildings as expressed by the Massachusetts Department ofPublic Health. Executive Summary. Wozny Barbar and Associates (WB&A), partnered with Baker/WohlArchitects (BWA), have been tasked with evaluating the mechanical systems of five buildings located on the Western Massachusetts Hospital campus located at 91 East Mountain Road in Westfield, Massachusetts. The Main Hospital is a 93,000 square foot, three-story building with basement, circa 1910 that serves as a chronic care facility, with the goal to convert back to a medical facility. The unoccupied Quarry Hill dormitory consists of two-stories with basement and may be converted to a Veterans Administration dormitory with treatment, recovery, and outreach program support. The Clark building is two-stories supporting administrative services for the hospital. The Garage is an open floor plan pre-engineered metal building installed on a slab, providing maintenance for campus machinery. Finally, the Storeroom is a two-story warehouse providing storage and , shipping support. For all five buildings, the existing heating equipment consists of gas and/or f:/2 oil-fired boilers serving cast-iron radiators, unit ventilators, and unit heaters and is in average condition. This study describes the existing conditions of the mechanical systems serving each building in more detail below. Two options were considered for each building and the recommended option is discussed in detail further in this report. Project Justification Based on the existing equipment age, condition, code shortfalls, and a desire to upgrade the campus services offered, a study to establish a concept and baseline for equipment replacement is warranted. The systems are difficult to work on in making repairs due to the complexity and age of the distribution system, given all the temporary repairs and additiOn$ that have OCC1:11Ted over the years. Problem Statement The existing mechanical equipment has had the minimal necessary repairs and additio~ over a number of years, with little or no documentation, maKing· further repairs dif~cult and, in some cases unsafe for the staff. Existing Conditipns Based on field observations, review of existing documents and discussions with building management staff, WB&A provides descriptions of the existing mechanical services for the five buildings included as pait of this report. Main Hospital: Heating is provided for the building by one of two dual-fuel Cleaver Brooks packaged boilers, I . • located in the basement, installed in April, 1988, with input capacity of6,277,000 Btu per hour. The boilers, fired by either natural gas or #2 fuel-oil, produce low-pressure steam.(8-pounds) that is connected to distribution piping serving cast-iron radiators and baseboard located throughout the facility. Condensate returns to a duplex condensate receiver tank where it is pumped to a 1Joiler feed tank for delivery back to the boilers to repeat the process. Each steam heating radiator and baseboard device is controlled by a thermostatic radiator valve. Three Hurst boilers, installed in 2002, with input capacity of 420,000 Btu per hour, fired by either natural gas or #2 fuel-oil, produce medium-pressure steam (45-pounds) that is connected to distribution piping serving the kitchen and laundry. Condensate returns to a duplex condensate receiver tank where it is pumped to a boiler feed tank fot: delivery back to the :boilers to repeat the process. Mechanical ventilation of toilet areas is provided by exhaust duct risers up to roof-mounted exhaust fans. Operable windows provide ventilation for the bedrooms. Numerous packaged terminal air conditioners, located above the windows, provide cooling for selected bedrooms and office spaces. Several split-system air conditioning units, with roof­ mounted condensing un~ts, provide cooling for selected internal spaces. A 20,000-gallon single-wall underground storage tallk.supplies #2 fuel-oil to the Cleaver Brooks heating boilers. The Hurst boilers are fed from the 3,000-gallon undergroUnd storage tank used to operate the Emergency Power Generators. Main Hospital Cleaver Brooks Boilers Hurst Boilers Typical Steam Radiator with Typical bedroom with PTAC Roof Exhaust Fans and Thermostatic Radiator Valve and operable window Condensing Units Quarry Hill Dormitory: Heating is provided for the building by an HB Smith packaged steam boiler installed in 1987, installed in the basement, with input capacity of 1,125,000 Btu per hour. The gas-fired boiler produces low-pressure steam that is connected to distribution piping serving cast-iron radiators and baseboard located throughout the building. Condensate returns to a duplex condensate receiver tank where it is pumped back to the boiler to repeat the process. Each steam heating radiator and baseboard device is controlled by a thermostatic radiator valve. -- ·-::---~:.--::::-::::-----~---- -... Quarry Hill Dormitory HB Smith Boiler Condensate Receiver Tank Clark Building: Heating is provided for the building by an RBI hydronic boiler installed in 2001, located in the basement, with an input capacity of 1,000,000 Btu per hour. The gas-fired boiler produces hot water that is circulated by base-mounted pumps through distribution piping, delivered to unit ventilators and cabinet unit heaters located throughoutthe building. Ventilation is achieved through exterior wall louvers connected to the back of the unit ventilators. Roof-mounted exhaust fans provide ventilation o~toilet areas. Some packaged terminal a~r conditioners, located above windows, provide cooling for selected areas. A couple split-system air conditioning units, with grade-mounted condensing units, provide cooling for selected internal spaces. Clark Building RBI Boiler Base-mounted Pumps Garage: The main Garage floor area is heated by five gas-fired, <;:eiling suspended Modine unit heaters. The office space and toilet room are heated by electric baseboard. The toilet room is ventilated by a ceiling-mounted exhaust fan, terminating its exhaust within the building. No general ventilation system we obse1;ved for the open garage area. Garage Building Modine Unit Heater Garage Floor Plan Store Building: Heating is provided for the building by an HB Smith packaged steam boiler installed in 1992, installed in the basement, with input capacity of787,000 Btu per hour. The gas-fired boiler produces low-pressure steam that is connected to distribution piping serving unit heaters located throughout the building. Condensate returns to a duplex condensate receiver tank where it is pumped back to the boiler to repeat the process. Sidewall propeller fans provide general ventilation for the main floor area. Store 'Building Condensate Receiver Tank HB Smith Boiler Options Main Hospital: Option 1 : The existing steam building heating system, including Cleaver Brooks boilers, · associated condensate receivers, boiler feed tanks, breeching, fuel-oil pumps, underground fuel-oil storage tank, steam distribution piping, radiators, condensate return piping, steam traps, and all associated appurtenances would be removed in their entirety. A four-pipe system would be designed to provide simultaneous heating and cooling for the entire building. Bigh-efficiency gas­ fired condensing boilers and base-mounted variable-speed pumps located in the basement mechanical room would circulate the heating water to fan coil units located throughout the facility. A roof-mounted air-cooled chiller would be piped to the basement mechanical room where base­ mounted variable-speed pumps would circulate the chilled water to the same fan coil units located throughout the facility. A plate-and-frame heat exchanger, located in the basement mechanical room, would provide isolation between the chiller and the chilled water distribution loop so as to segregate the glycol solution to the chiller side of the system for freeze protection. Both the heating distribution system loop and the cooling distribution system loop would be provided with an air separator, expansion. tank, and chemical feed. The chilleq water loop would be provided with automatic glycol fill. Each vertical floor-mounted fan coil unit would consist 9f a filter, hot water coil, chilled water coil, blower fan, and controls. Miscellaneous heating devices would be utilized to heat entrances, staircases, mechanical spaces, etc. ·Packaged roof-mounted energy recovery ventilators, with heating and cooling capability, would provide code-required ventilation to the corridors. Exha~st from the toilet rooms would be connected to the energy recovery ventilators. The Hurst boilers would remain for service to the kitchen and laundry. It is assumed that the acoustical asbestos ceiling at the corridors will need to be abated. Option 2: The existing steam building heating system, including Cleaver Brooks boilers, associated condensate
Recommended publications
  • Airflow Simulations Around OA Intake Louver with Electronic Velocity
    Airflow Simulations around OA Intake Louver with Electronic Velocity Sensors Hwataik Han*1, Douglas P. Sullivan2 and William J. Fisk3 1 Professor, Kookmin University, Korea 2 Research Associate, Indoor Environment Department, Lawrence Berkeley National Laboratory, USA 3 Director, Indoor Environment Department, Lawrence Berkeley National Laboratory, USA Abstract It is important to control outdoor airflow rates into HVAC systems in terms of energy conservation and healthy indoor environment. Technologies are being developed to measure outdoor air (OA) flow rates through OA intake louvers on a real time basis. The purpose of this paper is to investigate the airflow characteristics through an OA intake louver numerically in order to provide suggestions for sensor installations. Airflow patterns are simulated with and without electronic air velocity sensors within cylindrical probes installed between louver blades or at the downstream face of the louver. Numerical results show quite good agreements with experimental data, and provide insights regarding measurement system design. The simulations indicate that velocity profiles are more spatially uniform at the louver outlet relative to between louver blades, that pressure drops imposed by the sensor bars are smaller with sensor bars at the louver outlet, and that placement of the sensor bars between louver blades substantially increases air velocities inside the louver. These findings suggest there is an advantage to placing the sensor bars at the louver outlet face. Keywords: ventilation; outdoor
    [Show full text]
  • Performance Measurements of a Unique Louver
    Performance Measurements Grant O. Musgrove Southwest Research Institute, of a Unique Louver Particle San Antonio, TX 78238 e-mail: [email protected] Separator for Gas Turbine Engines Karen A. Thole Mechanical and Nuclear Engineering Department, Solid particles, such as sand, ingested into gas turbine engines, reduce the coolant flow The Pennsylvania State University, in the turbine by blocking cooling channels in the secondary flow path. One method to University Park, PA 16802 remove solid particles from the secondary flow path is to use an inertial particle separa- tor because of its ability to incur minimal pressure losses in high flow rate applications. In this paper, an inertial separator is presented that is made up of an array of louvers Eric Grover followed by a static collector. The performance of two inertial separator configurations was measured in a unique test facility. Performance measurements included pressure Joseph Barker loss and collection efficiency for a range of Reynolds numbers and sand sizes. To comple- ment the measurements, both two-dimensional and three-dimensional computational United Technologies Corporation – results are presented for comparison. Computational predictions of pressure loss agreed Pratt & Whitney, with measurements at high Reynolds numbers, whereas predictions of sand collection East Hartford, CT 06108 efficiency for a sand size range 0–200lm agreed within 10% of experimental measure- ments over the range of Reynolds numbers. Collection efficiency values were measured to be as high as 35%, and pressure loss measurements were equivalent to less than 1% pres- sure loss in an engine application. [DOI: 10.1115/1.4007568] Introduction operating principle of inertial separators is to cause the particle- laden flow to abruptly change trajectory, whereby the particles do Aircraft gas turbines ingest solid particles during takeoff, land- not react to the change in flow direction due to their larger inertia ing, and while flying in dusty environments.
    [Show full text]
  • High Performance House Best Practices Guide
    New York State Energy Research & Development Authority High Performance House Best Practices Guide Design Intelligence for Energy Performance in Single Family Homes TABLE OF CON T EN T S High Performance House 1.1 Initial Work................................... 3 1.2 Process.......................................... 4 1.3 Testing........................................... 4 1.3.1 Building Construction.............................. 4 1.3.2 Building Form and Siting......................... 5 1.3.3 Passive Sustainable Strategies................ 6 1.3.4 Active Sustainable Strategies................... 14 1.4 Conclusions................................... 14 1.4.1 Additional Recommendations.................. 15 2 1.1 INitiAL WORK 1.1 Initial Work ON cti Preliminary analysis looked purely at geometric implications on energy use. This theoretical investigation tested a variety of building forms and found two general guidelines that govern performance. Across all building manipulations, results showed that forms minimizing volume and RODU T maximizing southern exposure perform best. This lines with rational thought; increased volume N increases the volume of required conditioned space, while maximizing southern exposure allows I for greatest winter solar gains and daylighting. Following this study, energy analysis was given for three, previously conceived housing designs – “Slope House”, “Underground House” and “X House”. In all cases, formal design (siting, building form, orientation) were given, fixed parameters. This proved a challenge to the energy optimization of the house. For the “Slope House”, building volume opens to the west without the benefit of southern expo- sure on the open face. Passive solar gains were minimal, with excessive shading on south facing windows. The majority of glazing is to the north, which effectively cuts the building’s thermal resistance/storage without the offsetting solar gains received on southern exposures.
    [Show full text]
  • Damper Application Guide 1.” 1 Common 2 2 + Hot
    Control of Dampers ®® INDEX I. INTRODUCTION A. Economizer Systems ............................................................................................................ 3 B. Indoor Air Quality ...................................................................................................................3 C. Damper Selection ..................................................................................................................3 II. DAMPER SELECTION A. Opposed and Parallel Blade Dampers ..................................................................................3 B. Flow Characteristics...............................................................................................................4 C. Damper Authority ..................................................................................................................4 D. Combined Flow ......................................................................................................................6 III. ADDITIONAL CONSIDERATIONS A. Economizer Systems .............................................................................................................6 B. Building Pressure ...................................................................................................................8 C. Mixed Air Temperature Control ..............................................................................................8 D. Actuators - General ................................................................................................................8
    [Show full text]
  • IAQ Economizer LOGIC BOX
    IAQ Economizer LOGIC BOX Split-system Economizing/Indoor Air Quality/CO Alarm Activated Works on forced air systems, with or without air conditioning installed Enables cost saving cooling strategy: Expensive mechanical cooling can be set at a higher temperature Fresh Air Cooling can be set at a lower temperature Supports a variety Indoor Air Quality configurations: Continuous introduction Timed introduction CO2 or VOC sensor activated introduction Provides alarm activated fresh air introduction supporting CO or other alarm installations Occupant interface provides easy override, along with readiness, damper and fault status, (continuous fault detection) Operational tests can be conducted from within the conditioned space Quick connect wiring harnesses provide fast, correct termination FRESH AIR MANUFACTURING CO. FAMCO IAQ Economizer Famcoiaq.com 649 N. Ralstin St., Meridian, ID 83642 * (208)884-8931 * (800)-234-1903 * FAX: (208)884-8943 IAQ Economizer ECONOMIZER SYSTEM Damper Actuator Exhaust Damper Transformer Thermostat Logic Literature Box Cables Damper Box Actuator – Honeywell MS8105A1030, 24 VAC, 44 lb-in torque Outdoor thermostat- Dayton RLZ94A Nema 4X, Range 30º-110º F Transformer – RIB Functional Devices, Inc. TR50VA005 , 50VA All required System Cables are provided: • Power 40’ • Furnace 40’, plenum rated, HVAC industry standard color coding for furnace board termination • Damper Box 50’, plenum rated • Outdoor thermostat, 70’ , shielded, non polarity sensitive FRESH AIR MANUFACTURING CO. FAMCO IAQ Economizer
    [Show full text]
  • Building Applications, Opportunities and Challenges of Active Shading Systems: a State-Of-The-Art Review
    energies Review Building Applications, Opportunities and Challenges of Active Shading Systems: A State-Of-The-Art Review Joud Al Dakheel and Kheira Tabet Aoul * ID Architectural Engineering Department, United Arab Emirates University, P.O. Box 15551 Al Ain, UAE; [email protected] * Correspondence: [email protected]; Tel.: +971-566-433-648 Academic Editor: Arman Hashemi Received: 28 June 2017; Accepted: 4 August 2017; Published: 23 October 2017 Abstract: Active shading systems in buildings have emerged as a high performing shading solution that selectively and optimally controls daylight and heat gains. Active shading systems are increasingly used in buildings, due to their ability to mainly improve the building environment, reduce energy consumption and in some cases generate energy. They may be categorized into three classes: smart glazing, kinetic shading and integrated renewable energy shading. This paper reviews the current status of the different types in terms of design principle and working mechanism of the systems, performance, control strategies and building applications. Challenges, limitations and future opportunities of the systems are then discussed. The review highlights that despite its high initial cost, the electrochromic (EC) glazing is the most applied smart glazing due to the extensive use of glass in buildings under all climatic conditions. In terms of external shadings, the rotating shading type is the predominantly used one in buildings due to its low initial cost. Algae façades and folding shading systems are still emerging types, with high initial and maintenance costs and requiring specialist installers. The algae façade systems and PV integrated shading systems are a promising solution due to their dual benefits of providing shading and generating electricity.
    [Show full text]
  • BIM Handbook
    BIM Handbook A Guide to Building Information Modeling for Owners, Managers, Designers, Engineers, and Contractors Chuck Eastman Paul Teicholz Rafael Sacks Kathleen Liston John Wiley & Sons, Inc. BIM Handbook: A Guide to Building InformationModeling for Owners, Managers,Designers, Engineers, and Contractors. Chuck Eastman, Paul Teicholz, Rafael Sacks and Kathleen Liston Copyright © 2008 John Wiley & Sons, Inc. ffirs.indd i 1/3/08 12:32:13 PM This book is printed on acid-free paper. ϱ Copyright © 2008 by John Wiley & Sons, Inc. All rights reserved Published by John Wiley & Sons, Inc., Hoboken, New Jersey Published simultaneously in Canada No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical, photocopying, recording, scanning, or otherwise, except as permitted under Section 107 or 108 of the 1976 United States Copyright Act, without either the prior written permission of the Publisher, or authorization through payment of the appropriate per-copy fee to the Copyright Clearance Center, 222 Rosewood Drive, Danvers, MA 01923, (978) 750-8400, fax (978) 646-8600, or on the web at www.copyright.com. Requests to the Publisher for permission should be addressed to the Permissions Department, John Wiley & Sons, Inc., 111 River Street, Hoboken, NJ 07030, (201) 748-6011, fax (201) 748-6008, or online at www.wiley.com/go/permissions. Limit of Liability/Disclaimer of Warranty: While the publisher and the author have used their best efforts in preparing this book, they make no representations or warranties with respect to the accuracy or completeness of the contents of this book and specifi cally disclaim any implied warranties of merchantability or fi tness for a particular purpose.
    [Show full text]
  • Studio Education for Integrated Practice Using
    STUDIO EDUCATION FOR INTEGRATED PRACTICE USING BUILDING INFORMATION MODELING A Dissertation by OZAN ÖNDER ÖZENER Submitted to the Office of Graduate Studies of Texas A&M University in partial fulfillment of the requirements for the degree of DOCTOR OF PHILOSOPHY December 2009 Major Subject: Architecture STUDIO EDUCATION FOR INTEGRATED PRACTICE USING BUILDING INFORMATION MODELING A Dissertation by OZAN ÖNDER ÖZENER Submitted to the Office of Graduate Studies of Texas A&M University in partial fulfillment of the requirements for the degree of DOCTOR OF PHILOSOPHY Approved by: Chair of Committee, Mark J. Clayton Committee Members, Robert E. Johnson Wei Yan José L. Fernández-Solís Head of Department, Glen Mills December 2009 Major Subject: Architecture iii ABSTRACT Studio Education for Integrated Practice Using Building Information Modeling. (December 2009) Ozan Önder Özener, B.Arch., Istanbul Technical University; M.Arch., Istanbul Technical University Chair of Advisory Committee: Dr. Mark J. Clayton This research study posits that an altered educational approach to design studio can produce future professionals who apply Building Information Modeling (BIM) in the context of Integrated Project Delivery (IPD) to execute designs faster and produce designs that have demonstrably higher performance. The combination of new technologies and social/contractual constructs represents an alternative to the established order for how to design and how to teach designers. BIM emerges as the key technology for facilitating IPD by providing consistent, computable and interoperable information essential to all AEC teams. The increasing trend of BIM adoption is an opportunity for the profession to dramatically change its processes and may potentially impact patterns of responsibility and the paradigms of design.
    [Show full text]
  • Flow, Heat Transfer, and Pressure Drop Interactions in Louvered-Fin Arrays
    Flow, Heat Transfer, and Pressure Drop Interactions in Louvered-Fin Arrays N. C. Dejong and A. M. Jacobi ACRC TR-I46 January 1999 For additional information: Air Conditioning and Refrigeration Center University of Illinois Mechanical & Industrial Engineering Dept. 1206 West Green Street Prepared as part ofACRC Project 73 Urbana. IL 61801 An Integrated Approach to Experimental Studies ofAir-Side Heat Transfer (217) 333-3115 A. M. Jacobi, Principal Investigator The Air Conditioning and Refrigeration Center was founded in 1988 with a grant from the estate of Richard W Kritzer, the founder of Peerless of America Inc. A State of Illinois Technology Challenge Grant helped build the laboratory facilities. The ACRC receives continuing support from the Richard W. Kritzer Endowment and the National Science Foundation. The following organizations have also become sponsors of the Center. Amana Refrigeration, Inc. Brazeway, Inc. Carrier Corporation Caterpillar, Inc. Chrysler Corporation Copeland Corporation Delphi Harrison Thermal Systems Eaton Corporation Frigidaire Company General Electric Company Hill PHOENIX Hussmann Corporation Hydro Aluminum Adrian, Inc. Indiana Tube Corporation Lennox International, Inc. rvfodine Manufacturing Co. Peerless of America, Inc. The Trane Company Thermo King Corporation Visteon Automotive Systems Whirlpool Corporation York International, Inc. For additional information: .Air.Conditioning & Refriger-ationCenter Mechanical & Industrial Engineering Dept. University ofIllinois 1206 West Green Street Urbana IL 61801 2173333115 ABSTRACT In many compact heat exchanger applications, interrupted-fin surfaces are used to enhance air-side heat transfer performance. One of the most common interrupted surfaces is the louvered fin. The goal of this work is to develop a better understanding of the flow and its influence on heat transfer and pressure drop behavior for both louvered and convex-louvered fins.
    [Show full text]
  • Facilities Standards for the Public Buildings Service (PBS-PQ100.1)
    CHAPTER 1. GENERAL REQUIREMENTS Facilities Standards for the Public Buildings Service (PBS-PQ100.1) Arrangement of Chapters Chapter 1: General Requirements Appendix 1.A: Life Cycle Cost Example Chapter 2: Site Planning and Landscape Design Chapter 3: Architectural and Interior Design Chapter 4: Structural Engineering (Includes Seismic Design) Chapter 5: Mechanical Engineering Chapter 6: Electrical Engineering Appendix 6.A: Energy Efficient Design of New Buildings Chapter 7: Fire Protection Engineering Chapter 8: Security Design Index PBS-PQ100.1 June 14, 1996 Page i FACILITIES STANDARDS FOR THE PUBLIC BUILDINGS SERVICE CHAPTER 1 GENERAL REQUIREMENTS Purpose of the Facilities Standards for the Public Buildings Service ......................................................................................................... 1 Arrangement of Chapters.................................................................................... 3 Applicability of the Facilities Standards ........................................................................ 4 GSA Building Types .......................................................................................... 4 Office Buildings...................................................................................... 4 Courts...................................................................................................... 4 Border Stations........................................................................................ 4 Child Care Centers.................................................................................
    [Show full text]
  • Louver Products Severe Duty, Stationary, Operable
    Louver Products Severe Duty, Stationary, Operable November 2017 Louver Selection Guide In an effort to help located and select the louver you need, this catalog organizes the more than 100 standard Greenheck louver models into easily navigated categories, organized by your application requirements. Conventional Application Louvers Fixed Blade These conventional fixed blade louvers are among our most popular. All shown are AMCA Licensed for Air EDJ-401 Performance and Water Penetration and may be applied 4-inch depth in conventional intake or exhaust applications where Stationary provisions to manage water are present or some nuisance Drainable Head weather infiltration is acceptable or accounted for. These Extruded Aluminum louvers shown are among the most economical options. J-Blade ESJ-401 ESD-435 4-inch depth 4-inch depth Stationary Stationary Non-Drainable Drainable Blades Extruded Aluminum Drainable Head J-Blade Extruded Aluminum 56% Free Area ESJ-602 ESD-635 6-inch depth 6-inch depth Stationary Stationary Non-Drainable Drainable Blades Extruded Aluminum Drainable Head J-Blade Extruded Aluminum 59% Free Area 2 Louver Selection Guide Wind Driven Rain Louvers Fixed Blade These high performance wind driven rain fixed blade louvers are among our most popular. All shown are AMCA Licensed for Air Performance, Water Penetration and Wind Driven Rain and may be applied in intake or exhaust applications where provisions to manage water are limited. Wind Driven Rain louvers offer far superior protection against driving rain when compared to conventional louvers. Horizontal blade wind driven rain louvers perform extremely well, but vertical blade products offer the best performance considering both weather resistance and airflow performance.
    [Show full text]
  • Passive Building Design Guide: Multifamily Construction Copyright 2018 Passive House Institute US, All Rights Reserved
    Passive Building Design Guide FOR DEVELOPERS, INVESTORS & CONSTRUCTION PROFESSIONALS MULTIFAMILY CONSTRUCTION ACKNOWLEDGEMENTS We would like to thank the MacArthur Foundation for making this design guide and its associated website, the Multifamily Construction Resource Center (www.multifamily.phius.org), possible. Through these new resources, they do vital work building a more just verdant, and peaceful world, specifically through slashing the effects of global climate change. We thank them for their investment and commend them for acting locally on issues with global implications. We would also like to thank all of the people who worked with us to put this guide together. Their help tracking down photos, photo credits, providing technical insight, and inside information was invaluable and has made this a better book. Among the people who dropped everything to help: Sam Rodell, Erin Cooperrider, Dylan Lamar, Matt Fine, HousingUp, REACH CDC, Community Housing of Maine, Tinsley Morrison, Vickey Rand, Ben Walter, Colin Schless, Michael Hindle, Steve Bluestone, Hammer and Hand, Ben Bogie, James Hartford, Hank Keating, and last—but not least—Sloan Ritchie. Passive Building Design Guide: Multifamily Construction Copyright 2018 Passive House Institute US, all rights reserved. CONTENTS Introduction 4 Passive Building Fundamentals 5 �� Passive Building Benefits 6 Detail drawings eliminate weak links. �� 8 10 Great windows make rooms bigger. Passive Building Works for D A RE RCH TE I S T I E GMICHAEL WILLIAM CLINEC T E R C D 15 5/23/2014 2:38:40 PM S PORTLAND, OREGON A4.25 R 61CC T N 4 12 A #2987 O T E G E OF O R all Building Types ™ T.O PLATE AT BRICK 136' - 8" 6720 SW MACADAM AVENUE, SUITE 100 PORTLAND, OR 97219 6111 T 503-245-7100 4 117 SOUTH MAIN STREET, SUITE 400 �� SEATTLE, WA 98104 T 206-576-1600 12 R 61GC © ANKROM MOISAN ARCHITECTS, INC.
    [Show full text]