CITY OF CASTLEGAR REF NO.: 181-09051-00

2017 ANNUAL WATER QUALITY REPORT ENGINEERING & PUBLIC WORKS

FINAL

2017 ANNUAL WATER QUALITY REPORT ENGINEERING & PUBLIC WORKS

CITY OF CASTLEGAR

FACILITY: CITY OF CASTLEGAR WATER DISTRIBUTION SYSTEM FACILITY NUMBER: #0210617

FINAL VERSION -

PROJECT NO.: WSP NO. 181-09051-00 CLIENT REF:.. DATE: OCTOBER 05, 2018

WSP LANDMARK 6, SUITE 700 1631 DICKSON AVENUE KELOWNA, BC CANADA V1Y 0B5 T: +1 250 980-5500

WSP.COM

WSP Canada Inc.

October 05, 2018 FINAL

City of Castlegar 460 Columbia Avenue Castlegar, BC V1N 1G7

Attention: Jesse Reel, Utilities Manager Dear Sir: Subject: 2017 Water Quality Report for City of Castlegar

WSP Canada was engaged to complete the City of Castlegar’s 2017 Annual Water Quality Report. The City of Castlegar is required under its water Operating Permit, issued by the Interior Health Authority, and mandated by the Drinking Water Protection Act of BC to provide an annual water quality report to the water customers. The Annual Water Quality Report is meant to provide water system users with a deeper understanding of where their drinking water comes from and how it is treated and tested prior to consumption. The report discusses Castlegar’s water supply and disinfection process, the water distribution system, the ongoing testing and monitoring program, water system maintenance and the training levels. The water system improvements completed in 2017 will also be described, and plans for future upgrades and capital works will be listed. If you have any questions or require further information, please do not hesitate to contact us.

Sincerely,

Sonya Vrtacic, P.Eng. Project Engineer

Encl. 2017 Water Quality Report and Appendices

WSP ref.: WSP NO. 181-09051-00

Landmark 6, Suite 700 1631 Dickson Avenue Kelowna, BC Canada V1Y 0B5

T: +1 250 980-5500 wsp.com

WSP Canada Inc.

SIGNATURES

PREPARED BY

Sonya Vrtacic, P.Eng., Project Engineer Date

APPROVED BY

October 5, 2018 Elise Paré, P.Eng., Senior Reviewer Date

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page ii

EXECUTIVE SUMMARY ...... 1 TABLE OF 1 INTRODUCTION ...... 3 CONTENTS 1.1 Regulating Authorities ...... 3 1.2 Drinking Water Objectives ...... 4

2 WATER CONSUMPTION ...... 5 2.1 Water Demand In 2017 ...... 5 2.2 Universal Water Metering ...... 6

3 SOURCE WATER QUALITY ...... 7 3.1 Raw Water Intake ...... 7 3.2 Raw Water Objectives ...... 8 3.2.1 Exclusion of Filtration Criteria ...... 8 3.3 Raw Water Quality Monitoring ...... 9 3.3.1 Bacteriological Testing in 2017...... 9 3.3.2 Turbidity Monitoring in 2017 ...... 9 3.3.3 Full Chemical Analysis Testing...... 9 3.3.4 Algae Blooms and Nutrients in 2017 ...... 11 3.4 Source Assessment Report ...... 11

4 WATER TREATMENT PROCESS ...... 12 4.1 Primary Treatment and Disinfection ...... 12 4.2 Chlorine Residual ...... 12

5 DISTRIBUTION SYSTEM ...... 14 5.1 Pressure Zones...... 14 5.2 Pump Stations and Reservoirs ...... 15 5.3 Water System Control ...... 16 5.4 Monitoring Program in 2017 ...... 17 5.5 System Maintenance in 2017 ...... 19 5.5.1 Site Security ...... 19

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page iii

5.5.2 Uni-directional Flushing (UDF) Program ...... 20 5.5.3 Cross-Connection Control Program ...... 21 5.6 Operator Education & Credentials...... 22

6 CUSTOMER SERVICE ...... 23 6.1 Customer Complaints ...... 23

7 SYSTEM IMPROVEMENTS ...... 24 7.1 Capital Works Projects in 2017 ...... 24 7.2 Planned Capital Projects for 2018 ...... 25

8 EMERGENCY RESPONSE PLANNING ...... 26 8.1 Emergency North Well System ...... 26

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page iv

TABLES TABLE 1 ANNUAL VOLUME OF WATER TREATED BY THE CITY OF CASTLEGAR FROM 2014 TO 2017...... 5 TABLE 2 CURRENT EOCP CERTIFICATION LEVELS FOR CITY OF CASTLEGAR EMPLOYEES, 2017...... 22 TABLE 3 WATER SYSTEM - CAPITAL WORKS PROJECTS IN 2017 24

FIGURES FIGURE 1 ANNUAL VOLUMES OF WATER TREATED BY CASTLEGAR (IN MILLIONS OF CUBIC METERS)...... 5 FIGURE 2 CITY OF CASTLEGAR 2017 MONTHLY CONSUMPTION (IN CUBIC METERS), COMPARISON TO 2016 VALUES. 6 FIGURE 3 PHOTO OF ARROW LAKE RESERVOIR NEAR INTAKE, FROM THE SOURCE ASSESSMENT REPORT, 2014. .... 7 FIGURE 4 RAW SOURCE WATER, AVERAGE MONTHLY TURBIDITY 2017 (ONLINE TESTING AT WTC)...... 10 FIGURE 5 SOURCE WATER, PH TESTING 2017 (PH IS NOT ADJUSTED BY THE CITY OF CASTLEGAR)...... 10 FIGURE 6 CITY OF CASTLEGAR CHLORINE RESIDUAL MONITORING THROUGHOUT DISTRIBUTION SYSTEM...... 13 FIGURE 7 THE CITY OF CASTLEGAR’S MEADOWLARK WATER PUMP STATION...... 13 FIGURE 8 DISTRIBUTION PIPE MATERIALS BREAKDOWN...... 14 FIGURE 9 EXAMPLE OF CONTROLS IN A CITY OF CASTLEGAR PRV STATION...... 16 FIGURE 10 THM AND HAA TESTING RESULTS FOR THE CITY OF CASTLEGAR IN 2017...... 18

APPENDICES

APPENDIX A City of Castlegar’s Water System Map APPENDIX B Monitoring Data & Laboratory Test Results APPENDIX C Annual Laboratory Test Results APPENDIX D Section 6 – From Arrow Reservoir Source Assessment: recommendations for the City APPENDIX E Operating Permit & Interior Health Permits

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page v

EXECUTIVE SUMMARY

Under the Province of ’s Drinking Water Protection Act and the Drinking Water Protection Regulation, the City of Castlegar is mandated to continually monitor drinking water quality and to make available to the public an annual water quality report. The Annual Water Quality Report is meant to provide water users with information about their drinking water’s quality based on ongoing monitoring. The annual reporting is also required under the City’s municipal water system operating permit, issued by the BC Interior Health Authority (IHA). This report summarizes the results of drinking water quality monitoring and operations in Castlegar in the year 2017.

· Universal Water Metering program continues, and the City is transitioning all customers to a volumetric-based utility billing system in 2017. (Paying for how much water you use.) · The Drinking Water Protection Act of BC requires that a water-source assessment be completed by each Water Utility. The City is continuing to implement the recommendations contained in the 2014 Arrow Reservoir Source Assessment. · Water samples are tested to meet the Objectives for Drinking Water Quality and the requirements for ongoing “exclusion of filtration”. Forty-nine raw water samples were taken in 2017, and were tested by an independent laboratory for bacteria. · In 2017, the raw water samples met the criteria for E.coli and fecal coliform bacteria and the sampling site was repositioned in order to meet the criteria for total coliforms which was showing some false-positive results. · The bacteriological quality of water distributed in 2017 was in full compliance with all regulations. · In 2017, the City’s water system met all regulatory requirements for drinking water quality as set out by the BC Drinking Water Protection Act. · No treated water samples tested positive for E. coli in 2017. And 100% of the treated samples had no Fecal and no Total Coliforms per 100 mL. · Average total Trihalomethane results were well below the Health Canada guideline of 100 ppb. · The City of Castlegar has experienced gradually increasing algae levels over the past few years. In 2017, an algae issue was noted as a concern and was addressed through the flushing program. · The raw water from the reservoir is treated by the City of Castlegar using ultraviolet (UV) irradiation (Primary Disinfectant) to inactivate protozoa, and using chlorine gas (Secondary Disinfectant) to inactivate viruses. Additional chlorine is added to the water as a “residual” disinfectant. · The UV disinfection system provides the residents of Castlegar with a reliable disinfection barrier to ensure consistently safe drinking water. · Some turbidity (cloudy water) was experienced by customers in 2017; however, this was usually caused by normal operation & maintenance activities, such as flushing. · In 2017, the City of Castlegar staff focused their flushing efforts on the North end of the City (to Twin Rivers area). The City continues to improve and advance their “Uni-Directional Flushing Program” each year. · In 2017 the City expended just under $948,000 for Capital Works on the City’s water treatment center and the water distribution system.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 1

The City of Castlegar is committed to providing clean, safe drinking water through the responsible management and maintenance of local water infrastructure. This report has been submitted to the Interior Health Authority and will be posted on the City of Castlegar’s website once it has been endorsed by Castlegar City Council.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 2

1 INTRODUCTION The City of Castlegar (population 8,992) is situated at the confluence of the Kootenay and Columbia Rivers in the southwestern corner of the Kootenays within the Regional District of Central Kootenay. The City’s primary water source is the Lower Arrow Lakes reservoir. The City of Castlegar water utility partners with the Zellstoff-Celgar pulp mill to provide potable water from an intake in Lower Arrow Lake and provides potable water to approximately 2,703 residential customers and 300 institutional/commercial connections. The Lucas Road Water System is serviced with bulk treated water from the City of Castlegar.

1.1 REGULATING AUTHORITIES The City of Castlegar is required by the BC Interior Health Authority (IHA) to contract a private laboratory, each month, to perform testing of total coliform and fecal coliform counts on water samples from five locations within the distribution system. These tests are representative of potential bacterial contamination in the water. Data results are entered into WaterTrax, a computer database that simultaneously alerts public health authorities, water operations staff, and management, if microbiological parameters exceed the Guidelines for Canadian Drinking Water Quality. The City holds a water license (No.C053338) on Lower Arrow Lake for waterworks dated October 20, 1978. The City is licensed to divert 10,786ML annually. The actual demand by the City has been substantially less than the available licensed volume. In 2015 demand was 3.15 ML for the year; and in 2017 the total water production was 3.20 ML. The City of Castlegar holds a permit to operate its Water Treatment Centre (Class II Facility #2239) and its distribution system (Class III System #125) from the IHA and adheres to the provisions of the Local Government Act.

Water quality requirements are legislated by the Drinking Water Protection Act and the Drinking Water Protection Regulation of BC

The water distribution system has been classified by the Environmental Operators Certification Program (EOCP) as a Class III System. In 2017, the City of Castlegar’s water utility was maintained by EOCP certified operators, as required.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 3

1.2 DRINKING WATER OBJECTIVES The Guidelines for Canadian Drinking Water Quality (GCDWQ) are established by the Federal-Provincial- Territorial Drinking Water Committee to outline the Maximum Acceptable Concentrations of drinking water contaminants. These guidelines, published by Health Canada, are used to assess the safety of drinking water and to help determine treatment needs. The GCDWQ are broken into three parts: microbiological parameters; chemical/physical parameters; and radiological parameters.

INTERIOR HEALTH AUTHORITY 4-3-2-1-0 DRINKING WATER OBJECTIVE

4 log inactivation of viruses (this means 99.99% removal);

3 log removal or inactivation of protozoa (Giardia Lamblia and Cryptosporidium Parvum) (this means 99.9% removal);

2 treatment barriers, (duel treatment for all surface water or unprotected groundwater);

1 NTU, maintaining turbidity levels of less than 1.0 NTU; and,

0 indicators of bacterial contamination (either Fecal Coliform or E.Coli bacteria).

The IHA summarizes the objectives as the 4-3-2-1-0 method1 (outlined above). Water suppliers are required to provide potable water to all users on their systems.

1 Interior Health – Health Protection – Drinking Water Program Brochure No. HPF9040, published January 2006. The 4-3-2-1-0 drinking water objective provides a performance target for water suppliers, to ensure the provision of microbiological safe drinking water. IHA supports water suppliers to meet this objective. All water suppliers serving populations greater than 50 people should meet this as a standard.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 4

2 WATER CONSUMPTION

2.1 WATER DEMAND IN 2017 Water demand in the City of Castlegar is generally influenced by weather. Hotter, drier weather typically drives higher demand, while cooler, wetter summers will tend to result in lower demand, for both peak- daily and total annual demand. Hot and dry springs and summers have a dramatic influence on the volume of potable water consumed, as seen in 2015 and again in 2017 (see Table 1, and Figure 1). Over the years the water demand in Castlegar has gradually increased, and is still showing a rising trend in 2017.

Year Volume of Treated Water

2014 2.81 million m3 2015 3.15 million m3 2016 3.12 million m3 2017 3.20 million m3 Table 1 Annual volume of water treated by the City of Castlegar from 2014 to 2017.

Gross Annual Volumes of Treated Water

4.0 3.5 3.0 2.5 Volume 2.0 (Millions m3) 1.5 1.0 0.5 0.0 2014 2015 2016 2017 New Baseline Year Year

Figure 1 Annual volumes of water treated by Castlegar (in millions of cubic meters).

Below is a graph showing the 2016 and 2017 consumption for the City of Castlegar Water Utility. There are large shifts in consumption seasonally, due to water/irrigation demands during the summer months. Peak season water demand can increase by as much as 30% (see Figure 2) over the average monthly demand.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 5

2017 City of Castlegar Monthly Demand 600,000

500,000

400,000 ³)

300,000

2017 Volume (m 200,000 2016 100,000

0

Months

Figure 2 City of Castlegar 2017 Monthly Consumption (in cubic meters), comparison to 2016 values.

2.2 UNIVERSAL WATER METERING The City of Castlegar has been implementing a Universal Water Metering program as a method of addressing excessive water usage and promoting water conservation since 2009. This program is a key component in demand-management. In 2016, the City, completed their Water-Smart Action Plan 2015-2020. “In 2013, the City installed new source water meters which measure more accurately than the older instrumentation. Therefore, comparisons with prior years’ water demand should not be made. The City should establish a new baseline year of 2014 to accurately assess change in demand year over year. Water demand in Castlegar is well above the provincial average… suggesting that there continue to be cost effective opportunities to reduce total and peak water consumption in the City”. Section 5 of the Water Smart Action Plan details several actions that the City can take to further their water conservation efforts2. The City of Castlegar has installed more than 2,500 water meters or 90% of residential service connections. All commercial service connections (over 300 connections) are now metered. In 2017, the City is completing the process to transition all customers to a volumetric based utility billing system (during 2017 to 2018). A record of household water consumption is available to customers on the City’s website, providing residents with information related to their water use compared to the community wide average.

2 City of Castlegar - Water-Smart Action Plan 2015-2020, October 2016. Written in partnership with the Columbia Basin Trust.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 6

3 SOURCE WATER QUALITY

3.1 RAW WATER INTAKE The City of Castlegar’s water intake is located on the west shore of the reservoir, off Arrow Lakes Drive, immediately upstream of the Hugh (owned and operated by BC Hydro). The dam (1968) created a single large reservoir from what were formerly known as Upper and Lower Arrow Lakes, part of the system. The minimum reservoir level is specified in the Columbia River Treaty (as 417.00 m ASL). According to the Arrow Reservoir Source Assessment report3, the Castlegar water intake “is set at an elevation of 405.4 m [and] is a submerged screened pipe in the reservoir… at an average depth of 26.5m. The intake is shared with Zellstoff Celgar” property. Water supply is not a significant issue for the City as the amount of storage in the reservoir/lake and the operational components of the Columbia River, provide robust supplies4. The Arrow Lakes reservoir has historically provided very high-quality drinking water to the City. The source area upstream of the City intake is the Columbia River watershed that is approximately 36,500 square kilometers. From the pump house at the intake, water is piped to the City of Castlegar’s Water Treatment Centre (WTC) where water is treated, tested and monitored for quality before being directed throughout the distribution system.

Figure 3 Photo of Arrow Lake reservoir near intake, from the Source Assessment report, 2014.

3 City of Castlegar - Arrow Reservoir Source Assessment report, Urban Systems, September 2014. 4 City of Castlegar- Water-Smart Action Plan 2015-2020, October 2016. In partnership with the Columbia Basin Trust.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 7

3.2 RAW WATER OBJECTIVES The 2003 Drinking Water Protection Act of BC (DWPA) enables provincial enforcement of the GCDWQ. Section 18 of the DWPA requires a water-source assessment be completed. A Drinking Water Source-to-Tap Assessment Guideline was released by the SOURCE-TO-TAP Ministry of Health in 2010. The primary aim of this assessment is ASSESSMENT to identify hazards and vulnerabilities that may threaten the safety CATEGORIES and sustainability of the water supply throughout the system. The Action Plan for Safe Drinking Water in BC recognizes source The drinking water protection as a critical part of drinking water protection. multiple source-to-tap barrier assessment comprises of analysing the Surface water sources – lakes, streams, creeks, rivers and precipitation, are open to the atmosphere, making these following six steps: sources particularly vulnerable to contamination by the actions of humans or animals or by natural events in the watershed such as landslides, fires or extreme runoff from 1) Source heavy rain. (BC Provincial Health Officer, 2001) Protection

2) Treatment

3) Water System 3.2.1 EXCLUSION OF FILTRATION CRITERIA Maintenance The City of Castlegar strives to maintain authorization for “drinking water filtration exclusion” as an interim strategy, until 4) Water such time that raw water quality triggers the necessity for the Monitoring addition of filtration to the treatment process. The strict criteria set out as conditions of filtration-exclusion are 5) Operator monitored by IHA and have been summarized herein for the year Training 2017.

6) Emergency Response Planning

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 8

3.3 RAW WATER QUALITY MONITORING

3.3.1 BACTERIOLOGICAL TESTING IN 2017 The City of Castlegar performs weekly bacteriological testing for Escherichia-coli (E.coli) and total coliform bacteria throughout the distribution system. The first sampling location is at the Water Treatment Centre (WTC), testing the raw water when it first arrives. This regular weekly testing monitors microbiological threats, which might be present in the source water from Arrow Lake (reservoir). Water samples are tested to meet the requirements for drinking water and exclusion of filtration. Forty-nine (49) bacteriological raw water samples were taken in 2017, and were tested by an independent laboratory. In 2017, the raw water met the criteria for E.coli, (only 1 weekly sample in 24 total samples taken in the previous six months, exceeded the limit of “20/100mL” in 2017. This amounts to 98% of samples meeting the criteria for E.coli. Although the E.coli criteria was achieved, the total coliform results did not always appear to meet the guideline of “less than 100/100mL in at least 90% of the weekly samples”. In the first half of 2017, the water samples were meeting the criteria for total coliforms; however, in the second half of 2017, 4-of-24 weekly samples had greater than 100/100mL total coliforms (16% had greater than 100 units of total coliforms per 100mL). This change in test results coincides with a relocation of the raw water sampling site, which occurred in late 2017. The new location seemed to be resulting in some false positives. The City of Castlegar staff investigated this matter, reconfigured the testing location and has since reduced the raw water total coliform counts to within the required criteria.

3.3.2 TURBIDITY MONITORING IN 2017 Turbidity is a measure of water clarity. It is measured in NTU’s (nephelometric turbidity units) and describes the percentage of light which is scattered and absorbed, versus being transmitted through the water. Turbidity is a crucial measurement as part of the drinking water monitoring process because extra sediment/silt/organic matter in the water can cover or hide bacteria, thus reducing the effectiveness of the disinfection process (especially using UV light treatment). It is noted that turbidity, total-suspended-solids (TSS), total-dissolved-solids (TDS), and UV-transmittance results vary at different times of the year. The IHA criteria for filtration exclusion requires that “the average daily turbidity levels measured at equal intervals (at least every four hours) immediately before the disinfectant is applied are around 1 NTU, but do not exceed 5 NTU for more than two days in a 12-month period.” Average monthly turbidity is shown in Figure 4, and was generated based on daily monitoring results throughout 2017. Turbidity is also monitored by the automatic SCADA sensor system (alarmed). See Appendix B for complete set of monitoring data and laboratory test results.

3.3.3 FULL CHEMICAL ANALYSIS TESTING City staff collect quarterly raw water samples at the WTC and submit it to the professional laboratory for a full chemical analysis. When a full chemical analysis is completed on the source water, it is testing for many additional constituents such as: alkalinity; hardness; conductivity; pH; fluoride; arsenic; lead;

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 9

mercury; and other chemicals and metals. Figure 5 shows the pH levels measured in 2017; however, pH is not a property which can be adjusted by the City. Alkalinity and hardness levels are generally low for this source5; pH levels range from about 7.7 at the surface to 7.0 at a 30m depth in the reservoir.

Monthly Average Turbidity (2017) 1.2

1.0

0.8

0.6

0.4 Turbidity Turbidity (NTU) 0.2 1.0 NTU 0.0

Months

Figure 4 Raw source water, average monthly turbidity 2017 (online testing at WTC).

Raw Water pH 2017 10

9

8 pH 7 Raw Water pH 6 pH Min 5 pH Max

Months

Figure 5 Source water, pH testing 2017 (pH is not adjusted by the City of Castlegar).

5 City of Castlegar - Water Management Plan-Phase 1, Urban Systems, March 2009.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 10

3.3.4 ALGAE BLOOMS AND NUTRIENTS IN 2017 Algae is a broad term including organisms of widely varying sizes, growth rates and nutrient requirements. There is no officially recognized threshold level as to what is defined as an algae bloom. Freshwater algae blooms are the result of an excess of nutrients, particularly some phosphates. These excess nutrients may originate from fertilizers that are applied to land for agricultural purposes, or nutrients being added to the lake water for recreational (fish stocking) purposes. They may also originate from household cleaning products containing phosphorus. These nutrients can enter watersheds through water runoff. Occasional algae blooms have been identified as a potential drinking water hazard in water intake systems, resulting in clogging of the lines, some poor odour/taste, and increases in THM (trihalomethane) concentrations. The City of Castlegar has experienced gradually increasing algae levels over the past few years. In 2017, an algae issue was noted as a concern and was addressed locally through the flushing program of the distribution system. Algae was more of a problem closer to the source intake end of the system than at the far end of the distribution system, and tended to settle out near the beginning of the system. Ultimately, the incidence of algae blooms will continue if the source water remains rich in nutrients. The upstream reservoir waters continue to be enriched with nutrients by the Provincial Government, to increase recreational fish stocks.

3.4 SOURCE ASSESSMENT REPORT Another exclusion of filtration criteria for the source water is the maintenance of a watershed protection program that minimizes the potential for contamination of the source water. In 2014, the City of Castlegar commissioned the preparation of the Arrow Reservoir Source Assessment6 report. The intent of the source assessment was to identify existing or potential hazards to the source water at the City’s intake and to make recommendations to reduce those threats or risks in the future. Section 6 recommendations for the City has been included as Appendix D. The City is continuing to work on implementing the recommendations contained in the Arrow Reservoir Source Assessment, as required by the conditions of IHA. However, due to the size of the Arrow Lakes reservoir and Columbia River watershed, implementing all the recommendations in the report would require substantial input and cooperation from many different organizations, governing bodies, and stakeholders, including senior government. The City of Castlegar is not currently kept appraised of the status of the Provincial (Forests, Lands, Natural Resource Operations & Rural Development ministry) nutrient program in the lake water. A formal water quality monitoring program was completed by the City in 2016 and was approved by IHA.

6 City of Castlegar - Arrow Reservoir Source Assessment report, Section 6, Urban Systems, September 2014.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 11

4 WATER TREATMENT PROCESS The treatment target for all water systems is to contain no detectable E. coli or fecal coliforms per 100mL. Total coliform objectives are also zero based on one sample in a 30-day period. For more than one sample in a 30-day period, at least 90% of the samples should have no detectable total coliform bacteria per 100mL and no sample should have more than 10 total coliform bacteria per 100mL. The City of Castlegar’s water system met these targets in 2017. No E. coli or Fecal Coliforms were detected in any of the treated water samples. Over 95% of samples tested had less than one count per 100mL of total coliforms. And the other 5% contained only 1/100mL, which may have been either a human sampling error or a laboratory error.

4.1 PRIMARY TREATMENT AND DISINFECTION The water diverted from the Arrow Lakes reservoir is treated by disinfection for the City of Castlegar. The disinfection process uses ultraviolet (UV) irradiation (Primary Disinfectant) to inactivate protozoa and chlorine gas (Secondary Disinfectant) to inactivate viruses. Then additional chlorine is added to the water, as a residual disinfectant prior to distribution. In August 2013 the City installed the Trojan-Ultra-Violet system (UV disinfection). The UV disinfection system provides the residents of Castlegar with a reliable disinfection barrier to ensure consistently safe drinking water. The City’s system achieves the requirement that “overall inactivation must be met using a minimum of two disinfections, providing 4-log reduction of viruses and 3-log reduction of Cryptosporidium and Giardia”. The UV system is designed to maintain a minimum a dose of 12.2 mJ/cm2 in order to provide the required 3_log (99.9%) inactivation of protozoa. The chlorination system is intended as the secondary disinfectant to provide 4_log (99.99%) inactivation of viruses.

4.2 CHLORINE RESIDUAL The free chlorine residual is extremely important to ensure potable (safe for drinking) water is delivered to the residents of the City of Castlegar. The rate of chlorine injection can vary throughout the year depending largely on source water temperature and organic concentrations. In 2017, the City maintained the provincial health standard of a minimum free chlorine residual of 0.20mg/L at the outermost areas of the water distribution system. Rate of injection at the WTC can vary from 0.75mg/L to 1.00mg/L, to achieve that free chlorine residual of 0.20mg/L. The City regularly measures residual chlorine at six locations throughout the distribution system (see Figure 6) and monitors minimum residual chlorine concentrations.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 12

2017 Monthly Average Free Chlorine (mg/L) 0.9

0.8 Celgar First Aid 0.7 Lunchroom Meadowlark 0.6

0.5 Park Pump Station

0.4 Works Yard 0.3 Free Free Chlorine (mg/L) Blueberry 0.2

0.1 Airport

0

Figure 6 City of Castlegar chlorine residual monitoring throughout distribution system.

Figure 7 The City of Castlegar’s Meadowlark water pump station.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 13

5 DISTRIBUTION SYSTEM Treated drinking water is then directed to eight reservoirs, five pump-stations, and thirteen pressure- reducing valve stations (PRVs), throughout the City of Castlegar7. The total available reservoir storage capacity is 11.5 Megaliters. The City’s 109 km of water distribution piping is made up of approximately 50.9km of Asbestos Cement pipe (46%), 29 km of PVC/HDPE pipe (27%), 18.0 km of Ferrous (steel/iron) pipe (16%), 11 km of reinforced concrete pipe (Hyprescon, 10%), and 1.2 km of copper or unknown pipe (1%). Pipe sizes range from 575mm (22”) to 100mm (4”). The system map is shown in Appendix A.

Figure 8 Distribution pipe materials breakdown.

5.1 PRESSURE ZONES There are seven water pressure zones in the City of Castlegar’s distribution system and these are referred to as follows: 1 North zone; 2 Woodland Drive zone; 3 Park zone; 4 School zone; 5 Upper Bench zone; 6 Blueberry zone; 7 Twin Rivers zone. The system operating pressure ranges from 40psi to approximately 150psi.

7 City of Castlegar Integrated Infrastructure Capital Plan – Prioritized Water Capital Plan, by Urban Systems, in September 2017.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 14

5.2 PUMP STATIONS AND RESERVOIRS

(1.) MEADOWLARK PUMP STATION The Meadowlark pump station consists of eight high capacity pumps, which are split into two stages. The three Stage I pumps assist in filling the Meadowlark Reservoir. The five Stage II booster pumps are utilised to fill the Park and School reservoirs, respectively.

(2.) MEADOWLARK RESERVOIR The Meadowlark reservoir is the City’s central distribution point and is located approximately 6 kilometers downstream of the treatment facility. The Meadowlark reservoir is a 22m diameter concrete tank of 2.25 Megaliter (ML) liquid volume. The top water level is 497m.

(3.) PARK PUMP STATION & UPPER BENCH RESERVOIRS (A, B & C) The Park pump station comprises of four high capacity pumps. The four pumps are referred to as the Stage III pumps. The Park reservoir level stops and starts the Stage II pumps at Meadowlark. The Stage III pumps at Park Station fill the upper bench reservoirs

(4.) UPPER BENCH RESERVOIRS A. Meadowbrook Reservoir (steel tank) B. Merry Creek Reservoir (concrete tank) C. Blueberry Reservoir (concrete tank)

(5.) GRANDVIEW BOOSTER STATION The Grandview booster pump station is equipped with two small and two large booster pumps. The pumps provide additional operating pressure for the Grandview Subdivision neighbourhood.

(6.) HIGHLAND DRIVE BOOSTER STATION The Highland Drive pump station is equipped with one booster pump to increase the pressure to the residents of Highland Drive in times of peak demand on the water distribution system.

(7.) SCHOOL RESERVOIRS (1 & 2) School Reservoir 1 is a concrete tank reservoir, on 24th Street. School Reservoir 2 is a larger steel tank reservoir, that is slated for decommissioning when the Park Reservoir replaces it.

(8.) AIRPORT RESERVOIR & PUMP STATION Airport reservoir is a concrete tank, on an independent groundwater source. It was constructed in the 1960s. There is also a 30 gallon/minute pump at this location, which has since been dedicated to the Ministry of Forestry fire-fighting efforts. There is a City of Castlegar sampling site here, off the City of Castlegar potable water system (3/4” sampling line).

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 15

5.3 WATER SYSTEM CONTROL The City of Castlegar currently utilizes a computerized SCADA system with its water treatment and distribution process.

SCADA is an acronym for “Supervisory Control and Data Acquisition”, which is a computer system for gathering and analyzing real time data.

SCADA systems are used to monitor and control a treatment plant or equipment (eg. pumps and valves). The SCADA system continuously monitors the City of Castlegar’s WTC and the water distribution system for the following parameters:

1 Raw Water Turbidity; 2 Treated Water Turbidity; 3 UV Transmittance; 4 UV dose; 5 Chlorine Residual; 6 Water Flow; and 7 Alkalinity (pH), (not online yet, future). In the case of a significant change in outputs or a component failure, an alarm is sent to the mobile phones of the appropriate personal and after-hours the alarm is sent to the City of Castlegar emergency phone. This gives the City of Castlegar confidence that all SCADA alarm conditions will be investigated promptly at the Water Treatment Center and throughout the distribution system. The SCADA system has been calibrated/upgraded every year since 2012 to ensure control of the potable water system is kept current. The free chlorine residual is continuously analyzed by online instrumentation throughout the water distribution system and is transferred to the City’s SCADA system. The SCADA system will alarm to staff cell phones if the chlorine concentration falls outside of the predetermined ranges.

Figure 9 Example of controls in a City of Castlegar PRV station.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 16

5.4 MONITORING PROGRAM IN 2017 WATER TREATMENT MONITORING

Continuous Monitoring:

· Turbidity (NTUs – high set-point = 1 NTU; high-high set-point = 3 NTU). · Chlorine Residual (at Blueberry, Airport, Park Pump House, Meadowlark Pump House, & Water Treatment Centre…the CL2 set-points vary throughout system; at WTC alarm settings are for low set-point = 0.50mg/L; and low-low set-point = 0.30mg/L) and if required, the online chlorine analyzers are also re-calibrated to ensure proper trending and alarm capabilities of the City’s SCADA system. · UV Light - Transmittance (low set-point - 90%UVT; low-low set-point = 88%UVT) this sets the Disinfection Dosage time/strength etc. · pH (monitored by staff for information only, not adjusted by treatment process).

Daily Monitoring:

· Operators check monitoring equipment’s performance and alarm set-points, and often take sample by hand. Chlorine residual is also checked at Airport five days per week. DISTRIBUTION WATER QUALITY MONITORING

Weekly Bacteriological Testing:

· As required under the Operating Permit, City staff perform weekly bacteriological testing for E-coli and Total Coliform bacteria throughout the distribution system. · Sampling locations are as follows: 1) Water Treatment Center (raw water); 2) Meadowlark Pump Station; 3) Civic Works Yard; 4) Airport Reservoir; and, 5) Blueberry Reservoir. · Every week, these five samples are sent to a third-party lab for bacteriological testing. See Appendix B for complete set of laboratory test results. · In 2017, only two (2) tests came back with counts greater than zero. On January 30th, the Public Works Yard water sample scored 1 count/100mL of Total Coliforms. It was retested within 48 hours, and was confirmed to be negligible (less than 1/100mL). On August 21st, the same location tested positive for 1 count/100mL and was also retested and confirmed to be negligible (less than 1/100mL). · In 2017, all water sample tests from the distribution system were negative for E.coli.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 17

Quarterly Testing:

· The City performs quarterly “General Potability” testing of source (raw) water.

Bi-Annual Testing:

· The City also completes bi-annual testing of raw water at the WTC, for Cryptosporidium and Giardia with a third-party laboratory. In 2017, both test samples came back negative for cysts/oocysts (0.00 detected). · Bi-annual testing is done for Trihalomethanes (THM) at the ends of the distribution system (at Blueberry reservoir and at Airport reservoir, Figure 9 below). · Bi-annual testing is also completed for Haloacetic-Acids (HAAs) at the mid-point of the distribution system (at the Park Pump Station, Figure 9 below). · Chlorophyll A is monitored from approximately August through October each year. Chlorophyll A is signal of algae growth patterns.

Trihalomethanes (THM) & Halo-Acetic Acid (HAA) 0.12

0.1

0.08 THM Blueberry 0.06 THM Airport

0.04 HAA5 Park

MAC THM 0.02 MAC HAA 0 First Quarter Second Quarter Third Quarter Fourth Quarter

Figure 10 THM and HAA testing results for the City of Castlegar in 2017.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 18

5.5 SYSTEM MAINTENANCE IN 2017 WATER TREATMENT CENTER MAINTENANCE · Daily: WTC is inspected to ensure that UV and chlorination disinfection systems are operating correctly. · Monthly: magnetic flow meter and UV reference sensor are validated. · Annually: UV reference probes are also validated by a third party. PUMP STATION MAINTENANCE · Daily: Meadowlark Pump Station & Park Pump Station are inspected daily. · Weekly: inspections of Grandview booster station. · Monthly: Highland Drive booster station inspected during summer (June to Sept.). · All Pumps and Motors are serviced as per the manufactures specifications. PRV STATION MAINTENANCE · Weekly: inspections of the City’s PRV stations, monitoring for leaks and verification of proper operation of all equipment. RESERVOIR MAINTENANCE · Daily: all reservoir levels are monitored on the City’s SCADA system, and alarms will be triggered if reservoir levels change drastically or a “high-level” or “low-level” situation occurs. · Bi-Weekly: inspections of all reservoirs to ensure that the sites are secure and that the equipment is operating as intended. · All Pumps and Motors are serviced as per the manufactures specifications.

5.5.1 SITE SECURITY A combination of measures is utilized to provide security for the distribution system. The WTC building(s) have been equipped with a security system, alarms, security cameras and has security guards (from Celgar mill). All City Reservoirs have been fenced with locked ladder access. Both Meadowlark and Park Pump Stations have been equipped with security systems and security cameras. All Pressure Reducing Valve station sites are also securely locked.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 19

5.5.2 UNI-DIRECTIONAL FLUSHING (UDF) PROGRAM In 2017, the City of Castlegar staff focussed their flushing efforts on the North end of the City (to Twin Rivers area) due to recognising that the north end (closer to the source intake) has been more prone to algae buildup. Staff performed UDF flushing on the water system, except for the community of Blueberry. All fire hydrants are inspected and flushed annually.

· Historically (approximately 1980-2004) the City would flush dead-end watermains. Due to the extremely high volume of residential water quality complaints generated from flushing, dead-end watermain flushing work was suspended in 2004.

· In approximately 2001 the Arrow Lakes provincial lake fertilization program begins, in support of sports fishing industry. The program has adverse effects on the City’s water quality and distribution system.

· In 2013, the City worked with a consultant (Urban Systems) to create a Uni-Directional Flushing (UDF) program. It was quickly identified that north Castlegar (downtown) didn’t have enough water system valves to achieve true UDF. The City worked with the consultant to complete the water system mapping project.

· In 2014, the City spent $110,000 installing water system valves in north Castlegar and continued to work with the consultant on water modelling and developing a draft UDF Program (routes/plans).

· In 2015, the City spent an additional $40,000 installing water system valves and continued working on verifying the draft UDF routes.

· In 2016, City staff flushed north Castlegar (Downtown).

· The City implements summer sprinkler regulations from June 15th to September 15th each year, and UDF work is not permitted during this period.

The City’s water system currently has approximately 250 UDF routes. Due to limited utilities staff, the City does not have the capacity to perform UDF on the entire water system each year. One concept that is being considered for the formal UDF Program is to establish three quadrants or “flushing-zones”. The City anticipates a schedule whereby each quadrant would be flushed on a three or four-year cycle, depending on staff work loads, alternating between “flushing zones”. The community of Blueberry and north Castlegar are scheduled to be flushed in 2018.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 20

An additional constraint on the UDF program has been disposal of the flushing water, since many roadways do not have curb & gutter. Areas with steep banks are prone to erosion problems, and therefore Cross- flushing water must be collected and trucked to another location for disposal. Connections

Plumbing cross-connections constitute a serious public 5.5.3 CROSS-CONNECTION CONTROL health hazard. Simply put, a PROGRAM cross-connection occurs when potable water comes into The City has developed and adheres to a Cross- contact with non-potable water Connection Control Program. This program was supplies. established to identify high risk water service connections that could compromise/contaminate the Because private plumbing City’s water supply. High risk service connections are systems are often altered, cross- required to install back-flow prevention devices. connection control programs require ongoing investment.

Regulatory policies regarding existing and future service connections are essential on top of educational programs to prevent cross-connection hazards.

The City’s cross-connection control program has a history of success and a priority step going forward is to reinvigorate the program to ensure safe reliable drinking water supply.

Source: The 2009 City of Castlegar Water Management Plan

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 21

5.6 OPERATOR EDUCATION & CREDENTIALS The City of Castlegar has established a training program that follows the “Environmental Operators Certification Program” (EOCP) guidelines. The 2017 City of Castlegar staff have the following levels of EOCP certification:

Table 2 Current EOCP certification levels for City of Castlegar employees, 2017. Employee Certification Number Active Levels Jesse Reel EOCP #6096 WD III, WWC I, MWWT III, WTII, Utilities Manager Chlorine Handling Ticket Bill McMillan EOCP # 2086 WD IV, WWC MU1, MWWT MU II, Chief Water and Wastewater WT II, Certified Backflow Inspector, Operator Chlorine Handling Ticket Brian McCreight EOCP # 6802 WD II, WWC I, Certified Backflow Foreman Water and Sewer Inspector Maintenance Crew

Brad Spender EOCP # 1436 WD II, WWC I, MWWT II, WT I, Treatment Plant Operator #2 Certified Backflow Inspector, Chlorine Handling Ticket Todd Chahley EOCP # 1000054 WD II, WWC II, MWWT I, WT I Water and Sewer Maintenance Crew Michael Gagnier EOCP # 9290 WD I, Chlorine Handling Ticket. Treatment Plant Operator #1 Kurt Thomson EOCP # 9277 WD I, Chlorine Handling Ticket. Treatment plant Operator #1 Graham Lindsey Uncertified Operator Water and Sewer Maintenance Crew

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 22

6 CUSTOMER SERVICE There were no watermain breaks in 2017; however, due to the extra cold winter season there were five calls to repair frozen water services. And throughout the year, eight ¾ inch water service connections had to be repaired for leaks located within the City’s right-of-way.

The City of Castlegar’s water utility did not issue any public Boil Water Advisories or Notices during 2017

6.1 CUSTOMER COMPLAINTS The following reports/complaints from water customers were received by the City of Castlegar’s Civic Works Department during the 2017 billing year:

FEBRUARY 3, 2017 – One resident called in to the City’s Civic Works Department to complain about “excessive chlorine odour and taste” in their drinking water.

JULY 28, 2017 – One customer called the City to report “poor water taste and odor”. It was suspected that this might be an algae issue. The City asked the homeowner to call back to discuss further; however, they never did call back.

JULY 31, 2017 – One customer reported “very low water pressure”. The matter was investigated and was found to be caused by their household filter clogging (due to algae/sediment).

OCTOBER 4, 2017 – Another customer called in to comment that “the water in the downtown area is cloudy, with a foul taste and odor”. City staff followed up with this individual.

The Civic Works Department received a few other complaints about high turbidity or coloured water; however, this was typically following water distribution system maintenance work in their neighbourhoods. There are no guidelines for drinking water colour, as this is more of an aesthetic quality. City staff always advise these customers to run their water for 15 minutes and if the water does not clear up, to call the City of Castlegar Civic Works Department back for further directions and assistance. To reduce these types of complaints in the future, the City is continuing to develop and implement the City of Castlegar’s UDF program.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 23

7 SYSTEM IMPROVEMENTS

7.1 CAPITAL WORKS PROJECTS IN 2017 In 2017 the City expended just under $948,000 for operation and maintenance of the City’s water treatment center and water distribution system.

In 2017 the City performed the following water system upgrades (see Table 3 below).

Table 3 Water System - Capital Works Projects in 2017

Description Budget

SCADA system upgrades $74,000

Residential water meters $99,000

Dumont watermain replacement $226,000

Backup generator at Meadowlark $225,000

Water system efficiency optimization $60,000

Meadowlark pump house check valve replacement $20,000

North well upgrades $8,850

Paint exterior of Meadowlark pump house $7,600

Meter for Meadowlark pump house $6,000

SCADA emergency work $75,000 (rough estimate)

Blueberry reservoir roof and interior concrete inspection $17,000

City parks metering $75,000

UDF mapping / program $54,000

Total $ 947,450 Source: City of Castlegar Utilities Manager pers comm of actual 2017 costs

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 24

7.2 PLANNED CAPITAL PROJECTS FOR 2018 The Water System Capital Projects planned for 2018 include the following:

· $110,000 for SCADA upgrades, redundancy in communications type and carrier(s). · $110,000 for 33rd Street PRV station upgrades, high tender/bids came in for this project in 2018. (Project has been postponed to 2019). · Southridge PRV station upgrades, after 33rd Street PRV is complete. · Completing reservoir integrity inspections on Meadowlark and Park concrete, (mid-life). · Completing cleaning of the Park and Meadowlark reservoirs. The most challenging task is to take them offline, so the City is scheduling cleaning by robotic crawler vacuum, so that they can remain in service. This work is planned for October 2018. · Replacement of two of the oldest fire hydrants in the City (replacement parts are no longer available), this exercise is budgeted annually. Gradually replacing all fire hydrants, over time. · Completing the last 50 Uni-Directional Flushing routes, and confirming their feasibility. The UDF routing should be 100% complete by end of 2018.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 25 Revised Oct.17, 2018

8 EMERGENCY RESPONSE PLANNING Emergency response planning is an essential part of the governance of a drinking water system. As required under the City’s operating permit, a Drinking Water - Emergency Response Plan (ERP) was drafted in 2014. The 2014 draft ERP was reviewed by IHA. The goal of the emergency response plan is to identify potential emergency conditions that could occur and have documented response procedures in place. The 2014 ERP has not yet been endorsed by the City of Castlegar’s Fire Department, or the RCMP. This Emergency Response Plan is scheduled for completion in 2019. The revised ERP will also expand on all requirements and procedures for utilizing the North Well as an Emergency Water Source.

8.1 EMERGENCY NORTH WELL SYSTEM The City of Castlegar maintains a groundwater well located adjacent to City Hall that can be brought online in case of a water source emergency. Such an emergency has not occurred in the recent past. The well and pump are rated at approximately 1,100 USGPM, and are regularly maintained in case of an emergency. The well is equipped with chlorine injection and connection to the distribution system. Consultation with IHA and communication with the residents of Castlegar would be required prior to running the emergency well water system. The well (and associated valves/appurtenances) was operated monthly in 2017 to ensure that it is ready for use in case of emergency. In 2017, a full comprehensive raw water analysis for the North Well was completed (see Appendix D); and a regular flushing program has been developed to include the North Well. The plan to provide a physical separation for the North Well from the rest of the distribution using a removable stub of pipe (spool) was completed in approximately 2009. In 2018, the City plans to install a soft-starter, and transfer switch and genset plug on the North Well. If the Celgar mill is shut down (in case of forest fire or other emergency) then there will no longer be a power supply to the water pumps, and if the supply pumps shut down, then Castlegar’s drinking water system will shut down as well. The North Well is no longer an approved or registered drinking water source and it needs to be re-tested and re-certified, with full geotechnical investigation and hydro-geotechnical assessment to be completed. It could be used in an emergency, with a full City-wide, mandatory boil water notice in place.

2017 ANNUAL WATER QUALITY REPORT WSP Project No. WSP NO. 181-09051-00 CITY OF CASTLEGAR Page 26

APPENDIX A

APPENDIX A

CITY OF CASTLEGAR’S WATER SYSTEM MAP

WATER TREATMENT CENTRE

NORTH WELL

MEADOWLARK PUMP STATION MEADOWLARK RESERVOIR

AIRPORT RESERVOIR

HIGHLAND DRIVE SCHOOL BOOSTER STATION RESERVOIRS (1 &2)

PARK PUMP STATION MEADOWBROOK & RESERVOIRS RESERVOIR

MERRY CREEK RESERVOIR

BLUEBERRY RESERVOIR

GRANDVIEW BOOSTER STATION

CIVIC WORKS YARD

PROJECT: SCALE: CITY OF CASTLEGAR - CASTLEGAR 1:30,000 DATE: WATER QUALITY REPORT 2018-08-22 PROJECT NO: TITLE: 700 - 1631 DICKSON AVENUE 181-09050-00 KELOWNA, BC CANADA V1Y 0B5 DRAWING NO: PHONE: 250-980-5500 FAX: 250-980-5511 WATER DISTRIBUTION FACILITIES WWW.WSPGROUP.COM C01

APPENDIX B

APPENDIX B

MONITORING DATA & LABORATORY TEST RESULTS

Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 01/05/2017 17:38 Report ID: 103CC113 Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Sampled: 01/03/2017 09:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Sampled: 01/03/2017 08:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Sampled: 01/03/2017 07:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 01/05/2017 5:41:01PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Sampled: 01/03/2017 10:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Sampled: 01/03/2017 11:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 01/05/2017 5:41:01PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 01/13/2017 15:05 Report ID: 109CC114 Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: water temp:10C Sampled: 01/09/2017 08:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: water temp: 10C Sampled: 01/13/2017 07:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: water temp: 10C Sampled: 01/09/2017 10:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 01/13/2017 3:04:20PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: water temp: 10C Sampled: 01/09/2017 11:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: WTC Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: water temp: 1C Sampled: 01/09/2017 10:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 3 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 01/13/2017 3:04:20PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 01/19/2017 14:30 Report ID: 116CC115 Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Sampled: 01/16/2017 10:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Sampled: 01/16/2017 08:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Sampled: 01/16/2017 08:10

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 01/19/2017 2:31:00PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Sampled: 01/16/2017 10:10

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Sampled: 01/16/2017 07:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 01/19/2017 2:31:00PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 01/26/2017 17:06 Report ID: 123CC116 Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Temperature 7 degrees celsius Sampled: 01/23/2017 09:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 4 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Temperature 7 degrees celsius Sampled: 01/23/2017 08:50

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Temperature 7 degrees celsius Sampled: 01/23/2017 08:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 01/26/2017 5:06:51PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Temperature 8 degrees celsius Sampled: 01/23/2017 10:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Temperature 7 degrees celsius Sampled: 01/23/2017 11:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 01/26/2017 5:06:51PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 02/03/2017 10:07 Report ID: 130CC117 Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: water temp: 10C Sampled: 01/30/2017 09:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: water temp: 11C Sampled: 01/30/2017 08:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: water temp: 11C Sampled: 01/30/2017 09:25

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/mL Final Fecal Coliforms (counts) 0 counts/mL Final Total Coliforms (counts) 0 Final

Report created on 02/03/2017 10:09:13AM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: water Treatment Center Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: water temp: 11C Sampled: 01/30/2017 09:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: water temp: 10C Sampled: 01/30/2017 08:31

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 1 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 02/03/2017 10:09:13AM page 2 of 2 4235 Upper Passmore Road Winlaw, B.C. V0G2J0 Report number: 202CC118 250-226-7339 [email protected]

Client: City of Castlegar Attn: Jesse Reel

Date: February 4, 2017

We have tested the sample of water submitted by you and report as follows:

Method of Testing: Tests were performed in accordance with methods outlined in the "Standard Methods for the Examination of Water and Wastewater", 21st Edition, 2005 published by the American Public Health Association.

Sample Information: #1 Sample Site: Works Yard Recheck Date/time collected Feb 3, 2017 @ 15:00 Date/time on test Feb 3, 2017 @ 16:00 Temperature on arrival: 7 Matrix: DW

Results of Testing: Total Coliforms cfu per 100ml Less than 1 Fecal (Thermotolerant) Coliforms cfu per 100ml Less than 1 Verified E.coli cfu per 100ml Less than 1

DW=Drinking water cfu= colony forming units

Passmore Laboratory Ltd. complies with methods and certification through the Province of British Columbia Enhanced Water Quality Assurance (EWQA) Program and the Clinical Microbiology Proficiency Testing (CMPT) Program.

Analyst: Jennifer Yeow Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 02/07/2017 19:11 Report ID: 206CC119 Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: temp 11 degrees celsius Sampled: 02/06/2017 09:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: temp 11 degrees celsius Sampled: 02/06/2017 08:15

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Temp 11 degrees celsius Sampled: 02/06/2017 07:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 02/07/2017 7:11:27PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: temp 10 degrees celsius Sampled: 02/06/2017 10:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Temp 11 degrees celsius Sampled: 02/06/2017 11:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 02/07/2017 7:11:27PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 02/17/2017 16:47 Report ID: 214CC120 Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Temp. 10 degrees celsius Sampled: 02/14/2017 09:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 1 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Temp. 10 degrees celsius Sampled: 02/14/2017 09:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Temp. 11 degrees celsius Sampled: 02/14/2017 07:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 02/17/2017 4:46:45PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Temp. 9 degrees celsius Sampled: 02/14/2017 10:15

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Temp. 10 degrees celsius Sampled: 02/14/2017 07:15

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 02/17/2017 4:46:45PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 02/24/2017 11:50 Report ID: 220CC121 Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Temp. 10 degrees celsius Sampled: 02/20/2017 11:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 4 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Temp. 9 degrees celsius Sampled: 02/20/2017 09:10

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Temp. 8 degrees celsius Sampled: 02/20/2017 08:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 02/24/2017 11:50:20AM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Temp. 9 degrees celsius Sampled: 02/20/2017 11:20

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Northwell Water System: Castlegar Special System Source: North Well Facility: North Well - Raw Water Sampling Pt: Hydrant at North Well _ Raw Water (2-1-SR, 1EE7E) Comment: Temp.8 degrees celsius Sampled: 02/20/2017 09:40

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/mL Final Fecal Coliforms (counts) 0 counts/mL Final Total Coliforms (counts) 0 Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Temp. 10 degrees celsius note: sediment Sampled: 02/20/2017 11:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 02/24/2017 11:50:20AM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 03/02/2017 17:32 Report ID: 227CC122 Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Temp. 7 degrees celsius Sampled: 02/27/2017 09:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 9 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Temp. 6 degrees celsius Sampled: 02/27/2017 08:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Temp. 7 degrees celsius Sampled: 02/27/2017 07:20

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 03/02/2017 5:32:47PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Temp. 5 degrees celsius Sampled: 02/27/2017 10:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Temp. 7 degrees celsius Sampled: 02/27/2017 11:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 03/02/2017 5:32:47PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 03/10/2017 12:10 Report ID: 306CC123 Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Temp. 7 degrees celsius Sampled: 03/06/2017 09:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 15 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Temp. 5 degrees celsius Sampled: 03/06/2017 08:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Temp. 7 degrees celsius Sampled: 03/06/2017 07:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 03/10/2017 12:10:19PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Temp. 5 degrees celsius Sampled: 03/06/2017 10:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Temp. 6 degrees celsius Sampled: 03/06/2017 11:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 03/10/2017 12:10:19PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 03/17/2017 13:22 Report ID: 314CC124 Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: water temp: 7C Sampled: 03/13/2017 10:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 6 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: water temp: 8C Sampled: 03/13/2017 09:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: water temp: 8C Sampled: 03/13/2017 08:15

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 03/17/2017 1:22:39PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: water temp: 8C Sampled: 03/13/2017 10:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: water temp: 9C Sampled: 03/13/2017 11:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 03/17/2017 1:22:39PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 03/23/2017 19:37 Report ID: 320CC125 Report Name: Drinking Water Report

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: temp. 10 degrees celsius Sampled: 03/20/2017 08:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: temp. 11 degrees celsius Sampled: 03/20/2017 10:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 2 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: temp. 10 degrees celsius Sampled: 03/20/2017 09:18

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 03/23/2017 7:37:49PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: temp. 11 degrees celsius Sampled: 03/20/2017 09:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: temp. 10 degrees celsius Sampled: 03/20/2017 11:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 03/23/2017 7:37:49PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 03/29/2017 19:04 Report ID: 327CC126 Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Temp. 10 degrees celsius Sampled: 03/27/2017 10:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 6 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Temp. 10 degrees celsius Sampled: 03/27/2017 08:40

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Temp. 9 degrees celsius Sampled: 03/27/2017 08:16

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 03/29/2017 7:04:39PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Temp. 10 degrees celsius Sampled: 03/27/2017 10:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Temp. 9 degrees celsius Sampled: 03/27/2017 07:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 03/29/2017 7:04:39PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 04/05/2017 15:01 Report ID: 403CC127 Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: temp. 9 degrees celsius Sampled: 04/03/2017 09:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: temp. 8 degrees celsius Sampled: 04/03/2017 10:50

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: temp. 10 degrees celsius Sampled: 04/03/2017 07:40

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 04/05/2017 5:49:04PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: temp. 9 degrees celsius Sampled: 04/03/2017 08:20

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: temp. 8 degrees celsius Sampled: 04/03/2017 07:28

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 04/05/2017 5:49:04PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 04/11/2017 18:26 Report ID: 410CC130 Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Temp. 10 degrees celsius Sampled: 04/10/2017 09:15

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Temp. 10 degrees celsius Sampled: 04/10/2017 08:25

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Temp. 9 degrees celsius Sampled: 04/10/2017 11:10

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 04/11/2017 6:26:53PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Temp. 8 degrees celsius Sampled: 04/10/2017 07:40

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 04/11/2017 6:26:53PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 04/20/2017 17:06 Report ID: 418CC131 Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Water temperature 8 Sampled: 04/18/2017 11:01

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Water temperature 8 Sampled: 04/18/2017 08:07

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Water temperature 8 Sampled: 04/18/2017 08:54

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 04/20/2017 5:06:33PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Water temperature 8 Sampled: 04/18/2017 07:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: WTC Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Water temperature 8 Sampled: 04/18/2017 09:22

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 04/20/2017 5:06:33PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 04/26/2017 21:12 Report ID: 424CC132 Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Temp. 11 degrees celsius Sampled: 04/24/2017 10:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Temp. 11 degrees celsius Sampled: 04/24/2017 11:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Temp. 11 degrees celsius Sampled: 04/24/2017 09:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 04/26/2017 9:14:22PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Temp. 10 degrees celsius Sampled: 04/24/2017 09:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Temp. 11 degrees celsius Sampled: 04/24/2017 08:35

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 04/26/2017 9:14:22PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 05/06/2017 11:56 Report ID: 501CC133 Report Name: Drinking Water Report

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: temp. 13 degrees celsius Sampled: 05/01/2017 10:44

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: temp. 12 degrees celsius heavy presence of coliform bacteria Sampled: 05/01/2017 09:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) P counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: temp. 12 degrees celsius Sampled: 05/01/2017 10:25

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 05/06/2017 11:56:06AM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: temp. 13 degrees celsius Sampled: 05/01/2017 10:11

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: temp. 14 degrees celsius Sampled: 05/01/2017 08:28

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 05/06/2017 11:56:06AM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 05/11/2017 14:16 Report ID: 508CC134 Report Name: Drinking Water Report

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: temp. 13 degrees celsius Sampled: 05/08/2017 08:08

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: temp. 13 degrees celsius Sampled: 05/08/2017 10:20

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 1 counts/100mL Final Fecal Coliforms (counts) 1 counts/100mL Final Total Coliforms (counts) 4 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: temp. 13 degrees celsius Sampled: 05/08/2017 11:28

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 05/11/2017 2:16:20PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: temp. 14 degrees celsius Sampled: 05/08/2017 08:36

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: temp. 14 degrees celsius Sampled: 05/08/2017 09:23

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 05/11/2017 2:16:20PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 05/19/2017 10:25 Report ID: 515CC135 Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: water temp: 11C Sampled: 05/19/2017 08:09

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 1 counts/100mL Final Total Coliforms (counts) 3 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: water temp: 11C Sampled: 05/15/2017 08:09

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: water temp: 12C Sampled: 05/15/2017 08:27

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 05/19/2017 10:25:53AM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: water temp: 11C Sampled: 05/15/2017 09:35

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: water temp: 12C Sampled: 05/15/2017 08:09

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 05/19/2017 10:25:53AM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 05/26/2017 11:15 Report ID: 523CC136 Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: water temperature: 16C Sampled: 05/23/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: water temperature: 17C Sampled: 05/23/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: water temperature: 14C Sampled: 05/23/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 05/26/2017 11:16:01AM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Water Treatment Center Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: water temperature: 13C Background growth Sampled: 05/23/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: water temperature: 16C Sampled: 05/23/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 05/26/2017 11:16:01AM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 05/31/2017 15:42 Report ID: 529CC137 Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: temp. 15 degrees celsius Sampled: 05/29/2017 10:50

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 1 counts/100mL Final Fecal Coliforms (counts) 1 counts/100mL Final Total Coliforms (counts) 1 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: temp. 14 degrees celsius Sampled: 05/29/2017 11:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: temp. 14 degrees celsius Sampled: 05/29/2017 08:25

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 05/31/2017 3:42:46PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: temp. 15 degrees celsius Sampled: 05/29/2017 09:20

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: temp. 15 degrees celsius Sampled: 05/29/2017 08:10

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 05/31/2017 3:42:46PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 06/10/2017 15:08 Report ID: 605CC138 Report Name: Drinking Water Report

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Temp. 13 degrees celsius Sampled: 06/05/2017 08:36

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Temp. 11 degrees celsius Sampled: 06/05/2017 08:15

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Temp. 12 degrees celsius Sampled: 06/05/2017 10:20

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 06/10/2017 3:08:44PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Temp. 14 degrees celsius Sampled: 06/05/2017 11:50

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Temp. 12 degrees celsius Sampled: 06/05/2017 09:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 06/10/2017 3:08:44PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 06/15/2017 13:37 Report ID: 612CC139 Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: water temp: 13C Sampled: 06/12/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: water temp: 14C Sampled: 06/12/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: water temp: 14C Sampled: 06/12/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 06/15/2017 1:37:54PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Water Treatment Centre Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: water temp: 12C Sampled: 06/12/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 8 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: water temp: 13C Sampled: 06/12/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 06/15/2017 1:37:54PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 06/22/2017 14:22 Report ID: 619CC140 Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: water temp: 12 Sampled: 06/19/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: water temp: 13C Sampled: 06/19/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: water temp: 13C Sampled: 06/19/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 06/22/2017 2:22:12PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Water Treatment Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: water temp: 11 Light Background Growth Sampled: 06/19/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 1 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: water temp: 11C Sampled: 06/19/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 06/22/2017 2:22:12PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 06/29/2017 15:29 Report ID: 626CC143 Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: water temp: 17C Sampled: 06/26/2017 08:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: water temp: 17C Sampled: 06/26/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: water temp: 16C Sampled: 06/26/2017 08:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 06/29/2017 3:29:05PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: water temp: 16C Sampled: 06/26/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: WTC Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: water temp: 16C Sampled: 06/26/2017 08:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 8 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 06/29/2017 3:29:05PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 07/07/2017 15:04 Report ID: 170704CC Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: water temp: 10C Sampled: 07/07/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: water temp: 10C Sampled: 07/07/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: water temp: 10C Sampled: 07/07/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 07/07/2017 3:04:54PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: water treatment centre Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: water temp: 10 Sampled: 07/07/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: water temp: 12C Sampled: 07/07/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 07/07/2017 3:04:54PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 07/13/2017 12:45 Report ID: 170710CC Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Temp 16C Sampled: 07/10/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Temp 18C Sampled: 07/10/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Temp 16C Sampled: 07/10/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 07/13/2017 12:45:19PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Temp 18C Background Growth Sampled: 07/10/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Temp 16C Sampled: 07/10/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 07/13/2017 12:45:19PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 07/20/2017 15:41 Report ID: 170717CC Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Sample temp 14 Sampled: 07/17/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Sample temp 16 Sampled: 07/17/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Sample temp 15 Sampled: 07/17/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 07/20/2017 3:40:39PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Sample temp 14 Sampled: 07/20/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 19 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Water temp 15 Sampled: 07/17/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 07/20/2017 3:40:39PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 07/28/2017 11:46 Report ID: 170724CC Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Sample temperature 13 Sampled: 07/24/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Sample temperature 10 Sampled: 07/24/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Sample temperature 14 Sampled: 07/24/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 07/28/2017 11:47:17AM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Sample temperature 14 Sampled: 07/24/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 48 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Sample temperature 12 Sampled: 07/24/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 07/28/2017 11:47:17AM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 08/03/2017 13:30 Report ID: 170731CC Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Sample temperature 10 Sampled: 07/31/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Sample temperature 7 Sampled: 07/31/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Sample temperature 10 Sampled: 07/31/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 08/03/2017 1:31:03PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Sample temperature 7 Sampled: 07/31/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 2 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Sample temperature 8 Sampled: 07/31/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 08/03/2017 1:31:03PM page 2 of 2 4240 Passmore Upper Road, Winlaw BC, V0G2J0 Method of Testing: Tests were performed in 250-226-7339 accordance with methods outlined in the [email protected] "Standard Methods for the Examination of passmorelaboratory.ca Water and Wastewater", 22st Edition, 2012 published by the American Public Health Client City of Castlegar Association. Attention Jesse Reel Date 2017-08-03 Report # 170731CCD

Sample Site Dog Park Sample Date/Time 2017-08-31 9:30 AM Date/Time on test 2017-08-31 5:00 PM Matrix** Raw Water Total Coliforms* ***Overgrown plate Temperature on arrival 9 Verified E.coli* ***Overgrown plate Fecal (Thermotolerant) Coliforms* 215 Comments ***Cannot accurately count Ecoli or Total coliforms due to heavy background growth Analyst Jennifer Yeow Passmore Laboratory Ltd. complies with methods and certification through the Province of British Columbia Enhanced Water Quality Assurance (EWQA) Program and the Clinical *Colony forming units per 100ml Microbiology Proficiency Testing (CMPT) Program. **SW = Surface water, TW =Treated water, DW= Distribution water, UGW = Untreated Ground water

August 3, 2017 Page 1 of 1 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 08/14/2017 11:09 Report ID: 170808CC Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Sampled: 08/08/2017 09:20

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 115 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Sampled: 08/08/2017 08:20

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Sampled: 08/08/2017 07:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 08/14/2017 11:10:09AM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Sampled: 08/08/2017 08:23

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Sampled: 08/08/2017 07:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 08/14/2017 11:10:09AM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 08/18/2017 13:39 Report ID: 170814CC Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: water temp: 10C Sampled: 08/14/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 4 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: water temp: 12C Sampled: 08/14/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: water temp: 12C Sampled: 08/14/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 08/18/2017 1:39:40PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: water temp: 10C Sampled: 08/14/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: water temp: 12C Sampled: 08/14/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 08/18/2017 1:39:40PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 08/23/2017 13:56 Report ID: 170821CC Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: temp. 13 degrees celsius Sampled: 08/21/2017 10:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: temp. 12 degrees celsius Sampled: 08/21/2017 11:40

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: temp. 13 degrees celsius Sampled: 08/21/2017 08:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 08/23/2017 1:56:45PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: temp. 12 degrees celsius Sampled: 08/21/2017 09:15

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: temp. 13 degrees celsius Sampled: 08/21/2017 08:10

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 1 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 08/23/2017 1:56:45PM page 2 of 2 4240 Passmore Upper Road, Winlaw BC, V0G2J0 Method of Testing: Tests were performed in 250-226-7339 accordance with methods outlined in the [email protected] "Standard Methods for the Examination of passmorelaboratory.ca Water and Wastewater", 22st Edition, 2012 published by the American Public Health Client City of Castlegar Association. Attention Jesse Reel Date 2017-08-26 Report # 170824CC

Sample # 1 Sample Site Works Yard Sample Date/Time 2017-08-24 7:57 AM Date/Time on test 2017-08-24 1:00 PM Matrix** TW Total Coliforms* less than 1 Temperature on arrival 13 Verified E.coli* less than 1 Fecal (Thermotolerant) Coliforms* less than 1

Analyst Jennifer Yeow Passmore Laboratory Ltd. complies with methods and certification through the Province of British Columbia Enhanced Water Quality Assurance (EWQA) Program and the Clinical *Colony forming units per 100ml Microbiology Proficiency Testing (CMPT) Program. **SW = Surface water, TW =Treated water, DW= Distribution water, UGW = Untreated Ground water

August 26, 2017 Page 1 of 1 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 08/30/2017 18:08 Report ID: 170828CC Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: temp. 12 degrees celsius Sampled: 08/28/2017 10:20

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 73 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: temp. 16 degrees celsius Sampled: 08/28/2017 11:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: temp. 12 degrees celsius Sampled: 08/28/2017 07:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 08/30/2017 6:08:14PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: temp. 12 degrees celsius Sampled: 08/28/2017 08:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: temp. 14 degrees celsius Sampled: 08/28/2017 07:35

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 08/30/2017 6:08:14PM page 2 of 2 9/7/2017 View Report

Home | Sign Out | Passmore Laboratory Ltd / Jennifer Yeow

Home Lab Reports View Report Lab Report

Report ID: 170905CC, Drinking Water Report Submitted As: Original Client ID: 4121 Client Name: City of Castlegar Last Updated: 09/07/2017 11:20:06 PM

Sample ID: Airport Collected: 09/05/2017 (mm/dd/yyyy hh:mm:ss) Water System: Castlegar Water System Lab Group ID: Sampling Point: Airport Comments: Water temp 13 Sampling Point Locator:29020

Detection Reporting Lab Analytical Analysis Start Analysis End Analyte Result Limit/MDL Limit(RL) Status Field Result Method Date/Time Date/Time Comment Escherichia coli / E. coli (counts) 0 Final APHA counts/100mL Fecal Coliforms (counts) 0 Final APHA counts/100mL Total Coliforms (counts) 0 Final APHA counts/100mL

Sample ID: Blueberry Collected: 09/05/2017 (mm/dd/yyyy hh:mm:ss) Water System: Castlegar Water System Lab Group ID: Sampling Point: Blueberry Comments: Water temp 11 Sampling Point Locator:90D1

Detection Reporting Lab Analytical Analysis Start Analysis End Analyte Result Limit/MDL Limit(RL) Status Field Result Method Date/Time Date/Time Comment Escherichia coli / E. coli (counts) 0 Final APHA counts/100mL Fecal Coliforms (counts) 0 Final APHA counts/100mL Total Coliforms (counts) 0 Final APHA counts/100mL

Sample ID: Meadowlark Collected: 09/05/2017 (mm/dd/yyyy hh:mm:ss) Water System: Castlegar Water System Lab Group ID: Sampling Point: Meadowlark Comments: Water temp 13 Sampling Point Locator:483F https://lab.watertrax.com/LabDataInbox/ViewReport.aspx?pg=0&LabID=17784&ReportID=170905CC&FileID=1372605&source=lab 1/2 9/7/2017 View Report Analyte Result Detection Reporting Status Field Result Lab Analytical Analysis Start Analysis End Comment Limit/MDL Limit(RL) Method Date/Time Date/Time Escherichia coli / E. coli (counts) 0 Final APHA counts/100mL Fecal Coliforms (counts) 0 Final APHA counts/100mL Total Coliforms (counts) 0 Final APHA counts/100mL

Sample ID: Raw Water Tap Collected: 09/05/2017 (mm/dd/yyyy hh:mm:ss) Water System: Castlegar Water System Lab Group ID: Sampling Point: 1. Raw Water Tap Comments: Water temp 14 Sampling Point Locator:481E

Detection Reporting Lab Analytical Analysis Start Analysis End Analyte Result Limit/MDL Limit(RL) Status Field Result Method Date/Time Date/Time Comment Escherichia coli / E. coli (counts) 0 Final APHA counts/100mL Fecal Coliforms (counts) 0 Final APHA counts/100mL Total Coliforms (counts) 82 Final APHA counts/100mL

Sample ID: Works Yard Collected: 09/05/2017 (mm/dd/yyyy hh:mm:ss) Water System: Castlegar Water System Lab Group ID: Sampling Point: Works Yard Comments: Water Temp 12 Sampling Point Locator:484D

Detection Reporting Lab Analytical Analysis Start Analysis End Analyte Result Limit/MDL Limit(RL) Status Field Result Method Date/Time Date/Time Comment Escherichia coli / E. coli (counts) 0 Final APHA counts/100mL Fecal Coliforms (counts) 0 Final APHA counts/100mL Total Coliforms (counts) 0 Final APHA counts/100mL

Cancel

Copyright © 2000-2017 WaterTrax Inc. All rights reserved. Version 1703.0.855.1

https://lab.watertrax.com/LabDataInbox/ViewReport.aspx?pg=0&LabID=17784&ReportID=170905CC&FileID=1372605&source=lab 2/2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 09/14/2017 13:15 Report ID: 170912CC Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Water temp 12 Sampled: 09/11/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Water temp 8 Sampled: 09/11/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Water temp 9 Sampled: 09/11/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 09/14/2017 1:15:20PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Water temp 11 Sampled: 09/11/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 101 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Water temp 8 Sampled: 09/11/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, Y=yes, N=no, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 09/14/2017 1:15:20PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 09/28/2017 12:45 Report ID: 170925CC Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: temp. 8 degrees celsius Sampled: 09/25/2017 09:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 11 counts/100mL Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: temp. 9 degrees celsius Sampled: 09/25/2017 11:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: temp. 10 degrees celsius Sampled: 09/25/2017 08:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 09/28/2017 12:45:59PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: temp. 10 degrees celsius Sampled: 09/25/2017 08:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: temp. 8 degrees celsius Sampled: 09/25/2017 07:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, Y=yes, N=no, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 09/28/2017 12:45:59PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 09/21/2017 16:01 Report ID: 170918CC Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Sample temp 10 Sampled: 09/18/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Sample temp 13 Sampled: 09/18/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Sample temp 10 Sampled: 09/18/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 09/21/2017 4:01:10PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Sample temp 10 Sampled: 09/18/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 7 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Sample temp 13 Sampled: 09/18/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, Y=yes, N=no, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 09/21/2017 4:01:10PM page 2 of 2 10/5/2017 View Report

Home | Sign Out | Passmore Laboratory Ltd / Jennifer Yeow

Home Lab Reports View Report Lab Report

Report ID: 171002CC, Drinking Water Report Submitted As: Original Client ID: 4121 Client Name: City of Castlegar Last Updated: 10/05/2017 4:04:41 PM

Sample ID: Airport Collected: 10/02/2017 (mm/dd/yyyy hh:mm:ss) Water System: Castlegar Water System Lab Group ID: Sampling Point: Airport Comments: Sample temperature 12 Sampling Point Locator:29020

Detection Reporting Lab Analytical Analysis Start Analysis End Analyte Result Limit/MDL Limit(RL) Status Field Result Method Date/Time Date/Time Comment Escherichia coli / E. coli (counts) 0 Final APHA counts/100mL Fecal Coliforms (counts) 0 Final APHA counts/100mL Total Coliforms (counts) 0 Final APHA counts/100mL

Sample ID: Blueberry Collected: 10/02/2017 (mm/dd/yyyy hh:mm:ss) Water System: Castlegar Water System Lab Group ID: Sampling Point: Blueberry Comments: Sample temperature 13 Sampling Point Locator:90D1

Detection Reporting Lab Analytical Analysis Start Analysis End Analyte Result Limit/MDL Limit(RL) Status Field Result Method Date/Time Date/Time Comment Escherichia coli / E. coli (counts) 0 Final APHA counts/100mL Fecal Coliforms (counts) 0 Final APHA counts/100mL Total Coliforms (counts) 0 Final APHA counts/100mL

Sample ID: Meadowlark Collected: 10/02/2017 (mm/dd/yyyy hh:mm:ss) Water System: Castlegar Water System Lab Group ID: Sampling Point: Meadowlark Comments: Sample temperature 11 Sampling Point Locator:483F https://lab.watertrax.com/LabDataInbox/ViewReport.aspx?pg=0&LabID=17784&ReportID=171002CC&FileID=1381651&source=lab 1/2 10/5/2017 View Report Analyte Result Detection Reporting Status Field Result Lab Analytical Analysis Start Analysis End Comment Limit/MDL Limit(RL) Method Date/Time Date/Time Escherichia coli / E. coli (counts) 0 Final APHA counts/100mL Fecal Coliforms (counts) 0 Final APHA counts/100mL Total Coliforms (counts) 0 Final APHA counts/100mL

Sample ID: Raw Water Tap Collected: 10/02/2017 (mm/dd/yyyy hh:mm:ss) Water System: Castlegar Water System Lab Group ID: Sampling Point: 1. Raw Water Tap Comments: Sample temperature 11 Sampling Point Locator:481E

Detection Reporting Lab Analytical Analysis Start Analysis End Analyte Result Limit/MDL Limit(RL) Status Field Result Method Date/Time Date/Time Comment Escherichia coli / E. coli (counts) 0 Final APHA counts/100mL Fecal Coliforms (counts) 0 Final APHA counts/100mL Total Coliforms (counts) 14 Final APHA counts/100mL

Sample ID: Works Yard Collected: 10/02/2017 (mm/dd/yyyy hh:mm:ss) Water System: Castlegar Water System Lab Group ID: Sampling Point: Works Yard Comments: Sample temperature 11 Sampling Point Locator:484D

Detection Reporting Lab Analytical Analysis Start Analysis End Analyte Result Limit/MDL Limit(RL) Status Field Result Method Date/Time Date/Time Comment Escherichia coli / E. coli (counts) 0 Final APHA counts/100mL Fecal Coliforms (counts) 0 Final APHA counts/100mL Total Coliforms (counts) 0 Final APHA counts/100mL

Cancel

Copyright © 2000-2017 WaterTrax Inc. All rights reserved. Version 1704.0.922.3

https://lab.watertrax.com/LabDataInbox/ViewReport.aspx?pg=0&LabID=17784&ReportID=171002CC&FileID=1381651&source=lab 2/2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 10/14/2017 11:34 Report ID: 171010CC Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: water temp: 12C Sampled: 10/10/2017 09:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: water temp: 12C Sampled: 10/10/2017 08:50

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: water temp: 12C Sampled: 10/10/2017 09:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 10/14/2017 11:36:03AM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Water Treatment Centre Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: water temp: 12C Sampled: 10/10/2017 10:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 15 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: water temp: 12C Sampled: 10/10/2017 08:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, Y=yes, N=no, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 10/14/2017 11:36:03AM page 2 of 2 10/17/2017 View Report

Home | Sign Out | Passmore Laboratory Ltd / Jennifer Yeow

Home Lab Reports View Report Lab Report

Report ID: 171016CC, Drinking Water Report Submitted As: Original Client ID: 4121 Client Name: City of Castlegar Last Updated: 10/17/2017 9:37:48 PM

Sample ID: Airport Collected: 10/16/2017 (mm/dd/yyyy hh:mm:ss) Water System: Castlegar Water System Lab Group ID: Sampling Point: Airport Comments: Sample temperature 13 Sampling Point Locator:29020

Detection Reporting Lab Analytical Analysis Start Analysis End Analyte Result Limit/MDL Limit(RL) Status Field Result Method Date/Time Date/Time Comment Escherichia coli / E. coli (counts) 0 Final APHA counts/100mL Fecal Coliforms (counts) 0 Final APHA counts/100mL Total Coliforms (counts) 0 Final APHA counts/100mL

Sample ID: Blueberry Collected: 10/16/2017 (mm/dd/yyyy hh:mm:ss) Water System: Castlegar Water System Lab Group ID: Sampling Point: Blueberry Comments: Sample temperature 11 Sampling Point Locator:90D1

Detection Reporting Lab Analytical Analysis Start Analysis End Analyte Result Limit/MDL Limit(RL) Status Field Result Method Date/Time Date/Time Comment Escherichia coli / E. coli (counts) 0 Final APHA counts/100mL Fecal Coliforms (counts) 0 Final APHA counts/100mL Total Coliforms (counts) 0 Final APHA counts/100mL

Sample ID: Meadowlark Collected: 10/16/2017 (mm/dd/yyyy hh:mm:ss) Water System: Castlegar Water System Lab Group ID: Sampling Point: Meadowlark Comments: Sample temperature 11 Sampling Point Locator:483F https://lab.watertrax.com/LabDataInbox/ViewReport.aspx?pg=0&LabID=17784&ReportID=171016CC&FileID=1385061&source=lab 1/2 10/17/2017 View Report Analyte Result Detection Reporting Status Field Result Lab Analytical Analysis Start Analysis End Comment Limit/MDL Limit(RL) Method Date/Time Date/Time Escherichia coli / E. coli (counts) 0 Final APHA counts/100mL Fecal Coliforms (counts) 0 Final APHA counts/100mL Total Coliforms (counts) 0 Final APHA counts/100mL

Sample ID: Raw Water Tap Collected: 10/16/2017 (mm/dd/yyyy hh:mm:ss) Water System: Castlegar Water System Lab Group ID: Sampling Point: 1. Raw Water Tap Comments: Sample temperature 11 Sampling Point Locator:481E

Detection Reporting Lab Analytical Analysis Start Analysis End Analyte Result Limit/MDL Limit(RL) Status Field Result Method Date/Time Date/Time Comment Escherichia coli / E. coli (counts) 0 Final APHA counts/100mL Fecal Coliforms (counts) 0 Final APHA counts/100mL Total Coliforms (counts) 0 Final APHA counts/100mL

Sample ID: Works Yard Collected: 10/16/2017 (mm/dd/yyyy hh:mm:ss) Water System: Castlegar Water System Lab Group ID: Sampling Point: Works Yard Comments: Sample temperature 13 Sampling Point Locator:484D

Detection Reporting Lab Analytical Analysis Start Analysis End Analyte Result Limit/MDL Limit(RL) Status Field Result Method Date/Time Date/Time Comment Escherichia coli / E. coli (counts) 0 Final APHA counts/100mL Fecal Coliforms (counts) 0 Final APHA counts/100mL Total Coliforms (counts) 0 Final APHA counts/100mL

Cancel

Copyright © 2000-2017 WaterTrax Inc. All rights reserved. Version 1704.0.922.3

https://lab.watertrax.com/LabDataInbox/ViewReport.aspx?pg=0&LabID=17784&ReportID=171016CC&FileID=1385061&source=lab 2/2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 10/20/2017 14:58 Report ID: 171019CC Report Name:

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Reservoir sample Sampled: 10/19/2017 08:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, Y=yes, N=no, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 10/20/2017 2:58:56PM page 1 of 1 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 10/27/2017 15:04 Report ID: 171023CC Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: temp 10 degrees celsius Sampled: 10/23/2017 09:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: temp 11 degrees celsius Sampled: 10/23/2017 08:22

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: temp 10 degrees celsius Sampled: 10/23/2017 07:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Report created on 10/27/2017 3:04:22PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: temp 10 degrees celsius Sampled: 10/23/2017 04:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Sample ID: Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: temp 12 degrees celsius Sampled: 10/23/2017 08:42

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100mL Final Fecal Coliforms (counts) 0 counts/100mL Final Total Coliforms (counts) 0 counts/100mL Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, Y=yes, N=no, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 10/27/2017 3:04:22PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 11/02/2017 15:53 Report ID: 171030CC Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: sample temperature 11 Sampled: 10/30/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: sample temperature 12 Sampled: 10/30/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: sample temperature 12 Sampled: 10/30/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Report created on 11/02/2017 3:54:08PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Water Treatment Center Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: sample temperature 12 Sampled: 10/30/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 72 counts/100ml Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: sample temperature 11 Sampled: 10/30/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, Y=yes, N=no, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 11/02/2017 3:54:08PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 11/10/2017 22:37 Report ID: 171106CC:00 Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Temp. 13 degrees celsius Sampled: 11/06/2017 11:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 55 counts/100ml Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Temp. 12 degrees celsius Sampled: 11/06/2017 08:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Temp. 12 degrees celsius Sampled: 11/06/2017 10:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Report created on 11/10/2017 10:37:20PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Temp. 11 degrees celsius Sampled: 11/06/2017 08:15

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Temp. 13 degrees celsius Sampled: 11/06/2017 08:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, Y=yes, N=no, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 11/10/2017 10:37:20PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 11/17/2017 15:09 Report ID: 171114CC Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: TEMP. 10 DEGREES CELSIUS Sampled: 11/14/2017 10:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: TEMP. 12 DEGREES CELSIUS Sampled: 11/14/2017 07:40

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: TEMP. 12 DEGREES CELSIUS Sampled: 11/14/2017 08:50

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Report created on 11/17/2017 3:10:05PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: TEMP. 9 DEGREES CELSIUS Sampled: 11/14/2017 09:40

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 1 counts/100ml Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: TEMP. 10 DEGREES CELSIUS Sampled: 11/14/2017 07:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, Y=yes, N=no, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 11/17/2017 3:10:05PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 11/23/2017 16:43 Report ID: 171120CC Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Sample temperature 14 Sampled: 11/20/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Sample temperature 14 Sampled: 11/20/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Sample temperature 13 Sampled: 11/20/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Report created on 11/23/2017 4:43:38PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Sample temperature 11 Sampled: 11/20/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 7 counts/100ml Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Sample temperature 14 Sampled: 11/20/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, Y=yes, N=no, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 11/23/2017 4:43:38PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 11/29/2017 19:01 Report ID: 171127CC Report Name: Drinking Water Report

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Temp. 11 degrees celsius Sampled: 11/27/2017 07:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Temp. 9 degrees celsius Sampled: 11/27/2017 08:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Temp. 8 degrees celsius Sampled: 11/27/2017 08:00

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Report created on 11/29/2017 7:01:47PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Temp. 10 degrees celsius Sampled: 11/27/2017 11:20

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Temp. 8 degrees celsius Sampled: 11/27/2017 10:20

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 1 counts/100ml Final Fecal Coliforms (counts) 1 counts/100ml Final Total Coliforms (counts) 48 counts/100ml Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, Y=yes, N=no, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 11/29/2017 7:01:47PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 12/07/2017 14:36 Report ID: 171204CC Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: water temp: 10C Sampled: 12/04/2017 11:20

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: water temp: 11C Sampled: 12/04/2017 07:45

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: water temp: 10C Sampled: 12/04/2017 09:55

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Report created on 12/07/2017 2:37:02PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Water Treatment Centre Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: water temp: 11C Sampled: 12/04/2017 10:10

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 104 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: water temp: 12C Sampled: 12/04/2017 07:30

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, Y=yes, N=no, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 12/07/2017 2:37:02PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 12/15/2017 14:55 Report ID: 171211CC Report Name: Drinking Water Report

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Water temperature 6 Sampled: 12/11/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Water temperature 7 Sampled: 12/11/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Water temperature 6 Sampled: 12/11/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Report created on 12/15/2017 2:55:17PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: North Well Raw Water Water System: Castlegar Water System Facility: North Well Sampling Pt: North Well (Emergency Water Supply) (8-1-EP, 1D214) Comment: Water temperature 6 Sampled: 12/15/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Water temperature 6 Sampled: 12/11/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 119 counts/100ml Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Water temperature 6 Sampled: 12/11/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, Y=yes, N=no, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 12/15/2017 2:55:17PM page 2 of 2 Laboratory Report Passmore Laboratory Ltd

Report For: City of Castlegar Received: 12/20/2017 21:27 Report ID: 171218CC Report Name: Drinking Water Report

Sample ID: 1. Raw Water Tap Water System: Castlegar Water System Source: Lower Arrow Lake Facility: Water Treatment Centre Sampling Pt: 1. Raw Water Tap (2-1-SR, 481E) Comment: Sample temperature 9 Sampled: 12/18/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 183 counts/100ml Final

Sample ID: Airport Water System: Castlegar Water System Facility: Distribution Sampling Pt: Airport (9-2-MD, 29020) Comment: Sample temperature 9 Sampled: 12/18/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Blueberry Water System: Castlegar Water System Facility: Distribution Sampling Pt: Blueberry (9-6-MR, 90D1) Comment: Sample temperature 9 Sampled: 12/18/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Report created on 12/20/2017 9:28:09PM page 1 of 2 Laboratory Report Passmore Laboratory Ltd Report Name: Drinking Water Report

Sample ID: Meadowlark Water System: Castlegar Water System Facility: Distribution Sampling Pt: Meadowlark (9-3-MD, 483F) Comment: Sample temperature 9 Sampled: 12/18/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Sample ID: Works Yard Water System: Castlegar Water System Facility: Distribution Sampling Pt: Works Yard (9-7-LD, 484D) Comment: Sample temperature 9 Sampled: 12/18/2017

MICROORGANISMS Criteria & Type Status Escherichia coli / E. coli (counts) 0 counts/100ml Final Fecal Coliforms (counts) 0 counts/100ml Final Total Coliforms (counts) 0 counts/100ml Final

Result Legend P=present, A=absent, PR=presumptive, ND=non-detect, U=non-detect, OR=over-range, OG=overgrown, Y=yes, N=no, TNTC=too numerous to count, NR=no result, NT=not tested, IG=ignore, ER=external report, SC=see comment < means less than lower detection limit shown > means greater than upper detection limit shown « means detected & less than number shown » means detected & greater than number shown * Indicates Criteria is exceeded

Report created on 12/20/2017 9:28:09PM page 2 of 2

APPENDIX C

APPENDIX C

ANNUAL LABORATORY TEST RESULTS

AND VALIDATION LOGS OF FLOW METERS AND SENSORS

CERTIFICATE OF ANALYSIS

REPORTED TO Castlegar, City of 460 Columbia Avenue TEL (250) 365-5979 CASTLEGAR, BC V1N 1G7 FAX (250) 365-0594

ATTENTION Chris Barlow WORK ORDER 7010435

PO NUMBER 502 RECEIVED / TEMP 2017-01-10 09:30 / 4°C PROJECT THM & HAA REPORTED 2017-01-19 PROJECT INFO COC NUMBER No Number

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: Kristin McKeown Client Service Representative

If you have any questions or concerns, please contact me at [email protected]

Locations: #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

CARO Analytical Services Page 1 of 3 Rev 2017-01-05 Page 1 of 3 ANALYSIS INFORMATION

REPORTED TO Castlegar, City of WORK ORDER 7010435 PROJECT THM & HAA REPORTED 2017-01-19

Analysis Description Method Reference Technique Location

Haloacetic Acids in Water EPA 552.3* Liquid-Liquid Microextraction, Derivatization and Richmond GC-ECD Trihalomethanes in Water EPA 5030B / APHA Purge&Trap / Purge and Trap Capillary Column Richmond 6200 B GC-MSD Note: An asterisk in the Method Reference indicates that the CARO method has been modified from the reference method

Method Reference Descriptions: EPA United States Environmental Protection Agency Test Methods

Glossary of Terms: MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) mg/L Milligrams per litre

Standards / Guidelines Referenced in this Report: Guidelines for Canadian Drinking Water Quality (Oct 2014) Website: http://www.hc-sc.gc.ca/ewh-semt/alt_formats/pdf/pubs/water-eau/sum_guide-res_recom/sum_guide-res_recom-e ng.pdf Note: In some cases, the values displayed on the report represent the lowest guideline and are to be verified by the end user

CARO Analytical Services Page 2 of 3 Rev 2017-01-05 Page 2 of 3 SAMPLE ANALYTICAL DATA

REPORTED TO Castlegar, City of WORK ORDER 7010435 PROJECT THM & HAA REPORTED 2017-01-19

Analyte Result / Standard / MRL / Units Prepared Analyzed Notes Recovery Guideline Limits

Sample ID: WT# 90D1 - Blueberry (7010435-01) [Water] Sampled: 2017-01-09 00:00

Calculated Parameters Total Trihalomethanes 0.023 MAC = 0.1 0.004 mg/L N/A N/A

Volatile Organic Compounds (VOC) Bromodichloromethane < 0.001 N/A 0.001 mg/L N/A 2017-01-15 Bromoform < 0.001 N/A 0.001 mg/L N/A 2017-01-15 Chloroform 0.023 N/A 0.001 mg/L N/A 2017-01-15 Dibromochloromethane < 0.001 N/A 0.001 mg/L N/A 2017-01-15 Surrogate: Toluene-d8 109 70-130 % N/A 2017-01-15 Surrogate: 4-Bromofluorobenzene 103 70-130 % N/A 2017-01-15

Sample ID: WT# 29020 - Airport (7010435-02) [Water] Sampled: 2017-01-09 00:00

Calculated Parameters Total Trihalomethanes 0.021 MAC = 0.1 0.004 mg/L N/A N/A

Volatile Organic Compounds (VOC) Bromodichloromethane < 0.001 N/A 0.001 mg/L N/A 2017-01-15 Bromoform < 0.001 N/A 0.001 mg/L N/A 2017-01-15 Chloroform 0.021 N/A 0.001 mg/L N/A 2017-01-15 Dibromochloromethane < 0.001 N/A 0.001 mg/L N/A 2017-01-15 Surrogate: Toluene-d8 106 70-130 % N/A 2017-01-15 Surrogate: 4-Bromofluorobenzene 100 70-130 % N/A 2017-01-15

Sample ID: WT# 4849 - Park Pumphouse (7010435-03) [Water] Sampled: 2017-01-09 11:30

Calculated Parameters Total Haloacetic Acids (HAA5) 0.0190 MAC = 0.08 0.0020 mg/L N/A N/A

Haloacetic Acids Monochloroacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-01-16 2017-01-19 Monobromoacetic Acid 0.0042 N/A 0.0020 mg/L 2017-01-16 2017-01-19 Dichloroacetic Acid 0.0058 N/A 0.0020 mg/L 2017-01-16 2017-01-19 Trichloroacetic Acid 0.0089 N/A 0.0020 mg/L 2017-01-16 2017-01-19 Dibromoacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-01-16 2017-01-19 Surrogate: 2-Bromopropionic Acid 94 70-130 % 2017-01-16 2017-01-19

CARO Analytical Services Page 3 of 3 Rev 2017-01-05 Page 3 of 3 3ER"*&*3'"E$!&$')'%;<*<

RE !R"E#$"! Castlegar, City of 460 Columbia Avenue "E% (250) 365-5979 CASTLEGAR, BC V1N 1G7 &'( (250) 365-0594

'""E)"*!) Chris Barlow +!R,$!R#ER 7040687

!$)=>?ER 502 RE3E*@E#$A$"E> 2017-04-11 10:00 / 12°C R!BE3" THM & HAA RE !R"E# 2017-04-18 R!BE3"$*)&! 3!3$)=>?ER No Number

-./.012$3455./678

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: ,0:76:/$>9,.4C/ Client Service Representative

If !"# $%&' %(! )#'*+,"(* "- ."(.'-(*/ 01'%*' ."(+%.+ 2' %+ 32.3'"4(5.%-"6.%

%4916:4/78 #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

3'R!$'/12H6:912$<.0I:9.7 1D.$E$4F$G Rev 2017-01-05 Page 1 of 3 ')'%;<*<$*)&!R>'"*!)

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7040687 R!BE3" THM & HAA RE !R"E# 2017-04-18

'/12H7:7$#.790:M6:4/ >.6J4N$R.F.0./9. ".9J/:KL. %4916:4/

Haloacetic Acids in Water EPA 552.3* Liquid-Liquid Microextraction, Derivatization and Richmond GC-ECD Trihalomethanes in Water EPA 5030B / APHA Purge&Trap / Purge and Trap Capillary Column Richmond 6200 B GC-MSD 7"+'8 9( %*+'-,*3 ,( +$' :'+$"; <'f'-'(.' ,(;,.%+'* +$%+ +$' =9<> 2'+$"; $%* ?''( 2";,f,'; f-"2 +$' -'f'-'(.' 2'+$";

>.6J4N$R.F.0./9.$#.790:M6:4/78 EPA United States Environmental Protection Agency Test Methods

-247710H$4F$".0578 MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) mg/L Milligrams per litre

<61/N10N7$A$-L:N.2:/.7$R.F.0./9.N$:/$6J:7$R.M4068 Guidelines for Canadian Drinking Water Quality (Feb 2017) Website: http://www.hc-sc.gc.ca/ewh-semt/alt_formats/pdf/pubs/water-eau/sum_guide-res_recom/sum_guide-res_recom-e ng.pdf 7"+'8 I( *"2' .%*'*/ +$' &%1#'* ;,*01%!'; "( +$' -'0"-+ -'0-'*'(+ +$' 1"4'*+ @#,;'1,(' %(; %-' +" ?' &'-,f,'; ?! +$' '(; #*'-

3'R!$'/12H6:912$<.0I:9.7 1D.$O$4F$G Rev 2017-01-05 Page 2 of 3 <'> %E$')'%;"*3'%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7040687 R!BE3" THM & HAA RE !R"E# 2017-04-18

$'/12H6. R.7L26$A$ <61/N10N$A$ >R%$A$ =/:67 0.M10.N '/12HP.N )46.7 <'."&'-! -L:N.2:/. A,2,+*$

<15M2.$*#8$+"Q$RS#E$T$?2L.U.00H$$VWSXSYZWTSE[$$\+16.0]$$<15M2.N8$OSEWTSXTES$SS8SS

=%1.#1%+'; B%-%2'+'-* Total Trihalomethanes S^SOZG MAC = 0.1 0.00400 mg/L N/A N/A

C"1%+,1' >-@%(,. ="20"#(;* DC>=E CT2 Bromodichloromethane < 0.001 N/A 0.001 mg/L N/A 2017-04-14 Bromoform < 0.001 N/A 0.001 mg/L N/A 2017-04-14 Chloroform S^SOZ N/A 0.001 mg/L N/A 2017-04-14 Dibromochloromethane < 0.001 N/A 0.001 mg/L N/A 2017-04-14 &'(()*+,-./0)1'-2-"34 !$ !0" %0 % 567 20 !"0#" # &'(()*+,-./#"8()9):1')();-2<-2- 0 !0" %0 % 567 20 !"0#" #

<15M2.$*#8$+"Q$ORSOS$T$':0M406$$VWSXSYZWTSO[$$\+16.0]$$<15M2.N8$OSEWTSXTES$SS8SS

=%1.#1%+'; B%-%2'+'-* Total Trihalomethanes S^SOZX MAC = 0.1 0.00400 mg/L N/A N/A

C"1%+,1' >-@%(,. ="20"#(;* DC>=E CT2 Bromodichloromethane < 0.001 N/A 0.001 mg/L N/A 2017-04-14 Bromoform < 0.001 N/A 0.001 mg/L N/A 2017-04-14 Chloroform S^SOZ N/A 0.001 mg/L N/A 2017-04-14 Dibromochloromethane < 0.001 N/A 0.001 mg/L N/A 2017-04-14 &'(()*+,-./0)1'-2-"34 42 !0" %0 % 567 20 !"0#" # &'(()*+,-./#"8()9):1')();-2<-2- 2 !0" %0 % 567 20 !"0#" #

<15M2.$*#8$+"Q$XZXR$T$ 10_$ L5MJ4L7.$$VWSXSYZWTSG[$$\+16.0]$$<15M2.N8$OSEWTSXTES$SS8SS

=%1.#1%+'; B%-%2'+'-* Total Haloacetic Acids (HAA5) S^SEWS MAC = 0.08 0.00200 mg/L N/A N/A

F%1"%.'+,. 9.,;* Monochloroacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-04-16 2017-04-17 Monobromoacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-04-16 2017-04-17 Dichloroacetic Acid S^SSYR N/A 0.0020 mg/L 2017-04-16 2017-04-17 Trichloroacetic Acid S^SESE N/A 0.0020 mg/L 2017-04-16 2017-04-17 Dibromoacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-04-16 2017-04-17 &'(()*+,-./2"8()9)=()=>)2>?/7?>3 0# !0" %0 % 20 !"0#" @ 20 !"0#" !

<15M2.$A$'/12H7:7$`L12:F:.078 CT2 Excessive headspace in sample container - VOC results may be compromised.

3'R!$'/12H6:912$<.0I:9.7 1D.$G$4F$G Rev 2017-01-05 Page 3 of 3 3ER"*&*3'"E$!&$')'%;<*<

RE !R"E#$"! Castlegar, City of 460 Columbia Avenue "E% (250) 365-5979 CASTLEGAR, BC V1N 1G7 &'( (250) 365-0594

'""E)"*!) Chris Barlow +!R,$!R#ER 7070350

!$)=>?ER 502 RE3E*@E#$A$"E> 2017-07-06 09:00 / 16°C R!BE3" THM & HAA RE !R"E# 2017-07-13 R!BE3"$*)&! 3!3$)=>?ER No Number

-./.012$3455./678

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: ,0:76:/$>9,.4C/ Account Manager

If !"# $%&' %(! )#'*+,"(* "- ."(.'-(*/ 01'%*' ."(+%.+ 2' %+ 32.3'"4(5.%-"6.%

%4916:4/78 #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

3'R!$'/12H6:912$<.0I:9.7 1D.$E$4F$G Rev 2017-01-05 Page 1 of 3 ')'%;<*<$*)&!R>'"*!)

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7070350 R!BE3" THM & HAA RE !R"E# 2017-07-13

'/12H7:7$#.790:M6:4/ >.6J4N$R.F.0./9. ".9J/:KL. %4916:4/

Haloacetic Acids in Water EPA 552.3* Liquid-Liquid Microextraction, Derivatization and Richmond GC-ECD Trihalomethanes in Water EPA 5030B / APHA Purge&Trap / Purge and Trap Capillary Column Richmond 6200 B GC-MSD 7"+'8 9( %*+'-,*3 ,( +$' :'+$"; <'f'-'(.' ,(;,.%+'* +$%+ +$' =9<> 2'+$"; $%* ?''( 2";,f,'; f-"2 +$' -'f'-'(.' 2'+$";

>.6J4N$R.F.0./9.$#.790:M6:4/78 EPA United States Environmental Protection Agency Test Methods

-247710H$4F$".0578 MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) mg/L Milligrams per litre

<61/N10N7$A$-L:N.2:/.7$R.F.0./9.N$:/$6J:7$R.M4068 Guidelines for Canadian Drinking Water Quality (Feb 2017) Website: http://www.hc-sc.gc.ca/ewh-semt/alt_formats/pdf/pubs/water-eau/sum_guide-res_recom/sum_guide-res_recom-e ng.pdf 7"+'8 I( *"2' .%*'*/ +$' &%1#'* ;,*01%!'; "( +$' -'0"-+ -'0-'*'(+ +$' 1"4'*+ @#,;'1,(' %(; %-' +" ?' &'-,f,'; ?! +$' '(; #*'-

3'R!$'/12H6:912$<.0I:9.7 1D.$O$4F$G Rev 2017-01-05 Page 2 of 3 <'> %E$')'%;"*3'%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7070350 R!BE3" THM & HAA RE !R"E# 2017-07-13

$'/12H6. R.7L26$A$ <61/N10N$A$ >R%$A$ =/:67 0.M10.N '/12HP.N )46.7 <'."&'-! -L:N.2:/. A,2,+*$

<15M2.$*#8$+"Q$RS#E$T$?2L.U.00H$$VWSWSGXSTSEY$$Z+16.0[$$<15M2.N8$OSEWTSWTSX$SW8\S

=%1.#1%+'; B%-%2'+'-* Total Trihalomethanes S]SGSG MAC = 0.1 0.00400 mg/L N/A N/A

C"1%+,1' >-@%(,. ="20"#(;* DC>=E Bromodichloromethane < 0.0010 N/A 0.0010 mg/L 2017-07-07 2017-07-07 Bromoform < 0.0010 N/A 0.0010 mg/L 2017-07-07 2017-07-07 Chloroform S]SGSG N/A 0.0010 mg/L 2017-07-07 2017-07-07 Dibromochloromethane < 0.0010 N/A 0.0010 mg/L 2017-07-07 2017-07-07 $%&&'()*+,-.'/%+0+"12 00 !0" #0 % 20 !"0!"0! 20 !"0!"0! $%&&'()*+,-5"6&'7'8/%'&'9+0:+0+ 34 !0" #0 % 20 !"0!"0! 20 !"0!"0!

<15M2.$*#8$+"Q$ORSOS$T$':0M406$$VWSWSGXSTSOY$$Z+16.0[$$<15M2.N8$OSEWTSWTSX$EE8OX

=%1.#1%+'; B%-%2'+'-* Total Trihalomethanes S]SGG^ MAC = 0.1 0.00400 mg/L N/A N/A

C"1%+,1' >-@%(,. ="20"#(;* DC>=E Bromodichloromethane < 0.0010 N/A 0.0010 mg/L 2017-07-07 2017-07-07 Bromoform < 0.0010 N/A 0.0010 mg/L 2017-07-07 2017-07-07 Chloroform S]SGG^ N/A 0.0010 mg/L 2017-07-07 2017-07-07 Dibromochloromethane < 0.0010 N/A 0.0010 mg/L 2017-07-07 2017-07-07 $%&&'()*+,-.'/%+0+"12 32 !0" #0 % 20 !"0!"0! 20 !"0!"0! $%&&'()*+,-5"6&'7'8/%'&'9+0:+0+ 35 !0" #0 % 20 !"0!"0! 20 !"0!"0!

<15M2.$*#8$+"Q$\_\R$T$ 10`$ L5MJ4L7.$$VWSWSGXSTSGY$$Z+16.0[$$<15M2.N8$OSEWTSWTSX$S_8SS

=%1.#1%+'; B%-%2'+'-* Total Haloacetic Acids (HAA5) S]SOSO MAC = 0.08 0.00200 mg/L N/A N/A

F%1"%.'+,. 9.,;* Monochloroacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-07-07 2017-07-09 Monobromoacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-07-07 2017-07-09 Dichloroacetic Acid S]SS_S N/A 0.0020 mg/L 2017-07-07 2017-07-09 Trichloroacetic Acid S]SEOO N/A 0.0020 mg/L 2017-07-07 2017-07-09 Dibromoacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-07-07 2017-07-09 $%&&'()*+,-2"6&'7';&';<'0<=->=<1 20 !0" #0 % 20 !"0!"0! 20 !"0!"03

3'R!$'/12H6:912$<.0I:9.7 1D.$G$4F$G Rev 2017-01-05 Page 3 of 3 3ER"*&*3'"E$!&$')'%;<*<

RE !R"E#$"! Castlegar, City of 460 Columbia Avenue "E% (250) 365-5979 CASTLEGAR, BC V1N 1G7 &'( (250) 365-0594

'""E)"*!) Chris Barlow +!R,$!R#ER 7100132

!$)=>?ER 502 RE3E*@E#$A$"E> 2017-10-03 09:30 / 9°C R!BE3" THM & HAA RE !R"E# 2017-10-11 R!BE3"$*)&! 3!3$)=>?ER no number

-./.012$3455./678

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: ,0:76:/$>9,.4C/ Account Manager

If !"# $%&' %(! )#'*+,"(* "- ."(.'-(*/ 01'%*' ."(+%.+ 2' %+ 32.3'"4(5.%-"6.%

%4916:4/78 #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

3'R!$'/12H6:912$<.0I:9.7 1D.$E$4F$G Rev 2017-01-05 Page 1 of 3 ')'%;<*<$*)&!R>'"*!)

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7100132 R!BE3" THM & HAA RE !R"E# 2017-10-11

'/12H7:7$#.790:M6:4/ >.6J4N$R.F.0./9. ".9J/:KL. %4916:4/

Haloacetic Acids in Water EPA 552.3* Liquid-Liquid Microextraction, Derivatization and Richmond GC-ECD Trihalomethanes in Water EPA 5030B / SM 6200 Purge&Trap / Purge and Trap Capillary Column Richmond B (2011) GC-MSD 7"+'8 9( %*+'-,*3 ,( +$' :'+$"; <'f'-'(.' ,(;,.%+'* +$%+ +$' =9<> 2'+$"; $%* ?''( 2";,f,'; f-"2 +$' -'f'-'(.' 2'+$";

>.6J4N$R.F.0./9.$#.790:M6:4/78 EPA United States Environmental Protection Agency Test Methods

-247710H$4F$".0578 MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) mg/L Milligrams per litre

<61/N10N7$A$-L:N.2:/.7$R.F.0./9.N$:/$6J:7$R.M4068 Guidelines for Canadian Drinking Water Quality (Feb 2017) Website: http://www.hc-sc.gc.ca/ewh-semt/alt_formats/pdf/pubs/water-eau/sum_guide-res_recom/sum_guide-res_recom-e ng.pdf 7"+'8 I( *"2' .%*'*/ +$' &%1#'* ;,*01%!'; "( +$' -'0"-+ -'0-'*'(+ +$' 1"4'*+ @#,;'1,(' %(; %-' +" ?' &'-,f,'; ?! +$' '(; #*'-

3'R!$'/12H6:912$<.0I:9.7 1D.$O$4F$G Rev 2017-01-05 Page 2 of 3 <'> %E$')'%;"*3'%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7100132 R!BE3" THM & HAA RE !R"E# 2017-10-11

$'/12H6. R.7L26$A$ <61/N10N$A$ >R%$A$ =/:67 0.M10.N '/12HP.N )46.7 <'."&'-! -L:N.2:/. A,2,+*$

<15M2.$*#8$+"Q$RS#E$T$?2L.U.00H$$VWESSEGOTSEX$$Y+16.0Z$$<15M2.N8$OSEWTESTSO$S[8OS

=%1.#1%+'; B%-%2'+'-* Total Trihalomethanes S\SGGW MAC = 0.1 0.00400 mg/L N/A N/A

C"1%+,1' >-@%(,. ="20"#(;* DC>=E Bromodichloromethane < 0.0010 N/A 0.0010 mg/L N/A 2017-10-10 Bromoform < 0.0010 N/A 0.0010 mg/L N/A 2017-10-10 Chloroform S\SGGW N/A 0.0010 mg/L N/A 2017-10-10 Dibromochloromethane < 0.0010 N/A 0.0010 mg/L N/A 2017-10-10 $%&&'()*+,-.'/%+0+"12 0 !0" #0 % 345 20 !" 0" 0 $%&&'()*+,-6"7&'8'9/%'&':+0;+0+ 02 !0" #0 % 345 20 !" 0" 0

<15M2.$*#8$+"Q$ORSOS$T$':0M406$$VWESSEGOTSOX$$Y+16.0Z$$<15M2.N8$OSEWTESTSO$ES8GW

=%1.#1%+'; B%-%2'+'-* Total Trihalomethanes S\SG]O MAC = 0.1 0.00400 mg/L N/A N/A

C"1%+,1' >-@%(,. ="20"#(;* DC>=E Bromodichloromethane < 0.0010 N/A 0.0010 mg/L N/A 2017-10-05 Bromoform < 0.0010 N/A 0.0010 mg/L N/A 2017-10-05 Chloroform S\SG]O N/A 0.0010 mg/L N/A 2017-10-05 Dibromochloromethane < 0.0010 N/A 0.0010 mg/L N/A 2017-10-05 $%&&'()*+,-.'/%+0+"12 0 !0" #0 % 345 20 !" 0"0< $%&&'()*+,-6"7&'8'9/%'&':+0;+0+ 02 !0" #0 % 345 20 !" 0"0<

<15M2.$*#8$+"Q$][]R$T$ 10^$ L5MJ4L7.$$VWESSEGOTSGX$$Y+16.0Z$$<15M2.N8$OSEWTESTSO$S[8]_

=%1.#1%+'; B%-%2'+'-* Total Haloacetic Acids (HAA5) S\SO`] MAC = 0.08 0.00200 mg/L N/A N/A

F%1"%.'+,. 9.,;* Monochloroacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-10-05 2017-10-06 Monobromoacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-10-05 2017-10-06 Dichloroacetic Acid S\SESO N/A 0.0020 mg/L 2017-10-05 2017-10-06 Trichloroacetic Acid S\SE`O N/A 0.0020 mg/L 2017-10-05 2017-10-06 Dibromoacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-10-05 2017-10-06 $%&&'()*+,-2"7&'8'>&'>?'0?@-5@?1 2< !0" #0 % 20 !" 0"0< 20 !" 0"0=

3'R!$'/12H6:912$<.0I:9.7 1D.$G$4F$G Rev 2017-01-05 Page 3 of 3 Giardia and Cryptosporidium Analysis Report Sheet Confidential Report

Hyperion Research Ltd. 1008 Allowance Ave. SE, Medicine Hat, AB T1A 3G8 Telephone (888) 529-0847 Fax (403) 5290852 [email protected]

To: Jesse Reel Sample Date: 12-Jun-17 Project #: City of Castlegar Sample Type: Raw Upload to DB?: 4500 Minto RD LIMS: Field pH: 7.80 Castlegar BC o Volume Filtered (L): 96.5 Field Temp C: 9.0 250-365-5979 Rec'd within 96h?: Yes Field Turb (NTU): 0.6 [email protected] Arrival Temp <20 o C?: Yes Sample Location: Water Treatment Centre

The methodology used to produce this report conforms to USEPA Method 1623 unless indicated otherwise below. Based on the validation data, the method is fit for its intended use Hyperion Research Ltd. is accredited for this analysis by CALA under the ISO/IEC 17025 standard. Raw Counts in Sample Equivalent Volume Processing Data # CYSTS/OOCYSTS Giardia Crypto. Date/Time Received: 6/14/2017 10:45:00 AM Sample Temp. on arrival o C: 8.25 DAPI+/empty: Probably Dead 0 0 Lab ID: 57172 DAPI-/Probably Alive 0 0 Filter Type: Filta-Max Detection Limit: 1.04 cysts or oocysts/100L Date/Time Conc: 6/14/2017 1:30:00 PM The detection limit is calculated assuming a minimum of 1 Concentration Analyst: CS cyst or oocyst observed in the Sample Equivalent Volume IMS System: DynaBeads GC Combo IMS Lot No: 00458402 RESULTS Pellet Vol (mL): 0.4 Resusp Vol (uL): 100 Giardia 0.0 cysts/100 L MAb Conjugate: Giardi-a-Glo; Crypt-a-Glo Cryptosporidium 0.0 oocysts/100 L Monoclonal Antibody Lot No: G33, C35 Control G: 4 - A value of '0' really means below the detection limit - These results apply to this sample only. Control C: 4 Date/Time Stained: 6/15/2017 10:30:00 AM Staining Analyst: CS Comments: Microscope Analyst: KW/PW Vol Used (uL): 100 Sample Equivalent Volume (L): 96.5

Method 1623 Quality Control Data Lab Water Spike 2016 Matrix Spike 2017 % Recovery RSD % Recovery RSD Analyst: Giardia 49.3 22.9 69.0 6.9 Cryptosporidium 46.8 37.2 62.7 2.9 Peter M. Wallis, Ph.D. These data indicate ongoing precision and recovery from monthly spiked water samples.

Effective Date: 6 Feb. 2002 Revision Date: 22 January 2016 Version 1.2 Document # HR0008 Report Date: 6/19/2017 3:32:37 PM Page 1 of 1 Giardia and Cryptosporidium Analysis Report Sheet Confidential Report

Hyperion Research Ltd. 1008 Allowance Ave. SE, Medicine Hat, AB T1A 3G8 Telephone (888) 529-0847 Fax (403) 5290852 [email protected]

To: Jesse Reel Sample Date: 26-Sep-17 Project #: City of Castlegar Sample Type: Raw Upload to DB?: 4500 Minto RD LIMS: Field pH: 7.85 Castlegar BC o Volume Filtered (L): 114 Field Temp C: 10.6 250-365-5979 Rec'd within 96h?: Yes Field Turb (NTU): 0.73 [email protected] Arrival Temp <20 o C?: Yes Sample Location: WTP-Raw

The methodology used to produce this report conforms to USEPA Method 1623 unless indicated otherwise below. Based on the validation data, the method is fit for its intended use Hyperion Research Ltd. is accredited for this analysis by CALA under the ISO/IEC 17025 standard. Raw Counts in Sample Equivalent Volume Processing Data # CYSTS/OOCYSTS Giardia Crypto. Date/Time Received: 9/28/2017 12:15:00 PM Sample Temp. on arrival o C: 13.2 DAPI+/empty: Probably Dead 0 0 Lab ID: 57255 DAPI-/Probably Alive 0 0 Filter Type: Filta-Max Detection Limit: 0.44 cysts or oocysts/100L Date/Time Conc: 10/29/2017 10:45:00 AM The detection limit is calculated assuming a minimum of 1 Concentration Analyst: CW cyst or oocyst observed in the Sample Equivalent Volume IMS System: DynaBeads GC Combo IMS Lot No: 00491857 RESULTS Pellet Vol (mL): 1 Resusp Vol (uL): 100 Giardia 0.0 cysts/100 L MAb Conjugate: Giardi-a-Glo; Crypt-a-Glo Cryptosporidium 0.0 oocysts/100 L Monoclonal Antibody Lot No: C35 G33 Control G: 4 - A value of '0' really means below the detection limit - These results apply to this sample only. Control C: 4 Date/Time Stained: 10/2/2017 1:00:00 PM Staining Analyst: PW Comments: Microscope Analyst: KW Vol Used (uL): 50 Sample Equivalent Volume (L): 57.0

Method 1623 Quality Control Data Lab Water Spike 2016 Matrix Spike 2017 % Recovery RSD % Recovery RSD Analyst: Giardia 49.3 22.9 69.0 6.9 Cryptosporidium 46.8 37.2 62.7 2.9 Peter M. Wallis, Ph.D. These data indicate ongoing precision and recovery from monthly spiked water samples.

Effective Date: 6 Feb. 2002 Revision Date: 22 January 2016 Version 1.2 Document # HR0008 Report Date: 10/3/2017 1:15:22 PM Page 1 of 1 CERTIFICATE OF ANALYSIS

REPORTED TO Castlegar, City of 460 Columbia Avenue TEL 1-250-365-9482 CASTLEGAR, BC V1N 1G7 FAX (250) 365-0594

ATTENTION Jesse Reel WORK ORDER 7010430

PO NUMBER RECEIVED / TEMP 2017-01-10 09:30 / 4°C PROJECT General Potability REPORTED 2017-01-17 PROJECT INFO COC NUMBER No Number

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: Kristin McKeown Client Service Representative

If you have any questions or concerns, please contact me at [email protected]

Locations: #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

CARO Analytical Services Page 1 of 10 Rev 2017-01-05 Page 1 of 10 ANALYSIS INFORMATION

REPORTED TO Castlegar, City of WORK ORDER 7010430 PROJECT General Potability REPORTED 2017-01-17

Analysis Description Method Reference Technique Location

Alkalinity in Water APHA 2320 B* Titration with H2SO4 Kelowna Anions by IC in Water APHA 4110 B Ion Chromatography with Chemical Suppression of Kelowna Eluent Conductivity Coliforms, Total (MF-CCA) in Water APHA 9222* Membrane Filtration / Incubation on Chromocult Agar Kelowna Coliforms, Total (MF-Endo) in Water APHA 9222 B Membrane Filtration / Incubation on m-Endo Agar Kelowna Colour, True in Water APHA 2120 C Spectrophotometry (456 nm) Kelowna Conductivity in Water APHA 2510 B Conductivity Meter Kelowna Cyanide, SAD in Water ASTM D7511-12 Flow Injection Analysis with In-Line Ultraviolet Kelowna Digestion and Amperometric Detection E. coli (MF-CCA) in Water APHA 9222* Membrane Filtration / Incubation on Chromocult Agar Kelowna E. coli (MF-NA+MUG) in Water APHA 9222 G Membrane Filtration / Nutrient Agar with MUG Kelowna Hardness (as CaCO3) in Water APHA 2340 B* Calculation: 2.497 [total Ca] + 4.118 [total Mg] N/A (Estimated) Langelier Index in Water APHA 2330 B Calculation N/A Mercury, total by CVAFS in Water EPA 245.7* BrCl2 Oxidation / Cold Vapor Atomic Fluorescence Richmond Spectrometry (CVAFS) pH in Water APHA 4500-H+ B Electrometry Kelowna Solids, Total Dissolved (calc) in APHA 1030 E Calculation: 100 x ([Cations]-[Anions])/ N/A Water ([Cations]+[Anions]) Temperature (lab) in Water APHA 2550 B Thermometer Kelowna Total Metals by ICPMS in Water APHA 3030E* / APHA HNO3+HCl Hot Block Digestion / Inductively Coupled Richmond 3125 B Plasma Mass Spectrometry (ICP-MS) Turbidity in Water APHA 2130 B Nephelometry Kelowna

Note: An asterisk in the Method Reference indicates that the CARO method has been modified from the reference method

Method Reference Descriptions: APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health Association/American Water Works Association/Water Environment Federation ASTM ASTM International Test Methods EPA United States Environmental Protection Agency Test Methods

Glossary of Terms: MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) °C Degrees Celcius CFU/100 mL Colony Forming Units per 100 millilitres CU Colour Units (referenced against a platinum cobalt standard) mg/L Milligrams per litre NTU Nephelometric Turbidity Units pH units pH < 7 = acidic, ph > 7 = basic µS/cm Microsiemens per centimetre

CARO Analytical Services Page 2 of 10 Rev 2017-01-05 Page 2 of 10 SAMPLE ANALYTICAL DATA

REPORTED TO Castlegar, City of WORK ORDER 7010430 PROJECT General Potability REPORTED 2017-01-17

Analyte Result / MRL / Units Prepared Analyzed Notes Recovery Limits

Sample ID: WTC - Raw Water (7010430-01) [Water] Sampled: 2017-01-09 09:30

Anions Chloride 0.25 0.10 mg/L N/A 2017-01-10 Fluoride < 0.10 0.10 mg/L N/A 2017-01-10 Nitrate (as N) 0.134 0.010 mg/L N/A 2017-01-10 Nitrite (as N) < 0.010 0.010 mg/L N/A 2017-01-10 Sulfate 10.0 1.0 mg/L N/A 2017-01-10

General Parameters Alkalinity, Total (as CaCO3) 54 2 mg/L N/A 2017-01-11 Alkalinity, Phenolphthalein (as CaCO3) < 1 2 mg/L N/A 2017-01-11 Alkalinity, Bicarbonate (as CaCO3) 54 2 mg/L N/A 2017-01-11 Alkalinity, Carbonate (as CaCO3) < 1 2 mg/L N/A 2017-01-11 Alkalinity, Hydroxide (as CaCO3) < 1 2 mg/L N/A 2017-01-11 Colour, True < 5 5 CU N/A 2017-01-11 Conductivity (EC) 124 2 µS/cm N/A 2017-01-11 Cyanide, Total < 0.0020 0.0020 mg/L N/A 2017-01-11 pH 7.59 0.01 pH units N/A 2017-01-11 HT2 Temperature 20 °C N/A 2017-01-11 HT2 Turbidity 0.29 0.10 NTU N/A 2017-01-10

Calculated Parameters Hardness, Total (as CaCO3) 65.0 0.50 mg/L N/A N/A Langelier Index -0.9 -5.0 - N/A 2017-01-17 Solids, Total Dissolved (calc) 68.2 1.00 mg/L N/A N/A

Total Metals Aluminum, total 0.012 0.005 mg/L 2017-01-11 2017-01-11 Antimony, total < 0.0001 0.0001 mg/L 2017-01-11 2017-01-11 Arsenic, total < 0.0005 0.0005 mg/L 2017-01-11 2017-01-11 Barium, total 0.017 0.005 mg/L 2017-01-11 2017-01-11 Boron, total < 0.004 0.004 mg/L 2017-01-11 2017-01-11 Cadmium, total < 0.00001 0.00001 mg/L 2017-01-11 2017-01-11 Calcium, total 18.6 0.2 mg/L 2017-01-11 2017-01-11 Chromium, total 0.0005 0.0005 mg/L 2017-01-11 2017-01-11 Cobalt, total < 0.00005 0.00005 mg/L 2017-01-11 2017-01-11 Copper, total 0.0248 0.0002 mg/L 2017-01-11 2017-01-11 Iron, total 0.01 0.01 mg/L 2017-01-11 2017-01-11 Lead, total 0.0005 0.0001 mg/L 2017-01-11 2017-01-11 Magnesium, total 4.51 0.01 mg/L 2017-01-11 2017-01-11 Manganese, total 0.0010 0.0002 mg/L 2017-01-11 2017-01-11 Mercury, total < 0.00002 0.00002 mg/L 2017-01-11 2017-01-11 Molybdenum, total 0.0006 0.0001 mg/L 2017-01-11 2017-01-11 Nickel, total 0.0008 0.0002 mg/L 2017-01-11 2017-01-11 Potassium, total 0.65 0.02 mg/L 2017-01-11 2017-01-11 Selenium, total < 0.0005 0.0005 mg/L 2017-01-11 2017-01-11 Sodium, total 0.91 0.02 mg/L 2017-01-11 2017-01-11 Uranium, total 0.00041 0.00002 mg/L 2017-01-11 2017-01-11 Zinc, total 0.006 0.004 mg/L 2017-01-11 2017-01-11

CARO Analytical Services Page 3 of 10 Rev 2017-01-05 Page 3 of 10 SAMPLE ANALYTICAL DATA

REPORTED TO Castlegar, City of WORK ORDER 7010430 PROJECT General Potability REPORTED 2017-01-17

Analyte Result / MRL / Units Prepared Analyzed Notes Recovery Limits

Sample ID: WTC - Raw Water (7010430-01) [Water] Sampled: 2017-01-09 09:30, Continued

Microbiological Parameters Coliforms, Total < 1 1 CFU/100 mL N/A 2017-01-10 Background Colonies > 200 200 CFU/100 mL N/A 2017-01-10 E. coli < 1 1 CFU/100 mL N/A 2017-01-10

Sample ID: North Well (7010430-02) [Water] Sampled: 2017-01-09 11:00

Anions Chloride 28.1 0.10 mg/L N/A 2017-01-10 Fluoride < 0.10 0.10 mg/L N/A 2017-01-10 Nitrate (as N) 1.44 0.010 mg/L N/A 2017-01-10 Nitrite (as N) < 0.010 0.010 mg/L N/A 2017-01-10 Sulfate 52.2 1.0 mg/L N/A 2017-01-10

General Parameters Alkalinity, Total (as CaCO3) 161 2 mg/L N/A 2017-01-11 Alkalinity, Phenolphthalein (as CaCO3) < 1 2 mg/L N/A 2017-01-11 Alkalinity, Bicarbonate (as CaCO3) 161 2 mg/L N/A 2017-01-11 Alkalinity, Carbonate (as CaCO3) < 1 2 mg/L N/A 2017-01-11 Alkalinity, Hydroxide (as CaCO3) < 1 2 mg/L N/A 2017-01-11 Colour, True < 5 5 CU N/A 2017-01-11 Conductivity (EC) 488 2 µS/cm N/A 2017-01-11 Cyanide, Total < 0.0020 0.0020 mg/L N/A 2017-01-11 pH 7.95 0.01 pH units N/A 2017-01-11 HT2 Temperature 20 °C N/A 2017-01-11 HT2 Turbidity 1.25 0.10 NTU N/A 2017-01-10

Calculated Parameters Hardness, Total (as CaCO3) 219 0.50 mg/L N/A N/A Langelier Index 0.5 -5.0 - N/A 2017-01-17 Solids, Total Dissolved (calc) 290 1.00 mg/L N/A N/A

Total Metals Aluminum, total 0.035 0.005 mg/L 2017-01-11 2017-01-11 Antimony, total < 0.0001 0.0001 mg/L 2017-01-11 2017-01-11 Arsenic, total < 0.0005 0.0005 mg/L 2017-01-11 2017-01-11 Barium, total 0.100 0.005 mg/L 2017-01-11 2017-01-11 Boron, total 0.025 0.004 mg/L 2017-01-11 2017-01-11 Cadmium, total 0.00006 0.00001 mg/L 2017-01-11 2017-01-11 Calcium, total 68.4 0.2 mg/L 2017-01-11 2017-01-11 Chromium, total 0.0013 0.0005 mg/L 2017-01-11 2017-01-11 Cobalt, total 0.00009 0.00005 mg/L 2017-01-11 2017-01-11 Copper, total 0.0521 0.0002 mg/L 2017-01-11 2017-01-11 Iron, total 0.15 0.01 mg/L 2017-01-11 2017-01-11 Lead, total 0.0106 0.0001 mg/L 2017-01-11 2017-01-11 Magnesium, total 11.7 0.01 mg/L 2017-01-11 2017-01-11 Manganese, total 0.0040 0.0002 mg/L 2017-01-11 2017-01-11 Mercury, total < 0.00002 0.00002 mg/L 2017-01-12 2017-01-12

CARO Analytical Services Page 4 of 10 Rev 2017-01-05 Page 4 of 10 SAMPLE ANALYTICAL DATA

REPORTED TO Castlegar, City of WORK ORDER 7010430 PROJECT General Potability REPORTED 2017-01-17

Analyte Result / MRL / Units Prepared Analyzed Notes Recovery Limits

Sample ID: North Well (7010430-02) [Water] Sampled: 2017-01-09 11:00, Continued

Total Metals, Continued Molybdenum, total 0.0033 0.0001 mg/L 2017-01-11 2017-01-11 Nickel, total 0.0037 0.0002 mg/L 2017-01-11 2017-01-11 Potassium, total 3.58 0.02 mg/L 2017-01-11 2017-01-11 Selenium, total 0.0019 0.0005 mg/L 2017-01-11 2017-01-11 Sodium, total 21.4 0.02 mg/L 2017-01-11 2017-01-11 Uranium, total 0.00544 0.00002 mg/L 2017-01-11 2017-01-11 Zinc, total 0.075 0.004 mg/L 2017-01-11 2017-01-11

Microbiological Parameters Coliforms, Total < 1 1 CFU/100 mL N/A 2017-01-10 E. coli < 1 1 CFU/100 mL N/A 2017-01-10

Sample / Analysis Qualifiers: HT2 The 15 minute recommended holding time (from sampling to analysis) has been exceeded - field analysis is recommended.

CARO Analytical Services Page 5 of 10 Rev 2017-01-05 Page 5 of 10 APPENDIX 1: QUALITY CONTROL DATA

REPORTED TO Castlegar, City of WORK ORDER 7010430 PROJECT General Potability REPORTED 2017-01-17

The following section displays the quality control (QC) data that is associated with your sample data. Groups of samples are prepared in fibatchesfl and analyzed in conjunction with QC samples that ensure your data is of the highest quality. Common QC types include:

Ł Method Blank (Blk): Laboratory reagent water is carried through sample preparation and analysis steps. Method Blanks indicate that results are free from contamination, i.e. not biased high from sources such as the sample container or the laboratory environment Ł Duplicate (Dup): Preparation and analysis of a replicate aliquot of a sample. Duplicates provide a measure of the analytical method™s precision, i.e. how reproducible a result is. Duplicates are only reported if they are associated with your sample data. Ł Blank Spike (BS): A known amount of standard is carried through sample preparation and analysis steps. Blank Spikes, also known as laboratory control samples (LCS), are prepared from a different source of standard than used for the calibration. They ensure that the calibration is acceptable (i.e. not biased high or low) and also provide a measure of the analytical method™s accuracy (i.e. closeness of the result to a target value). Ł Standard Reference Material (SRM): A material of similar matrix to the samples, externally certified for the parameter(s) listed. Standard Reference Materials ensure that the preparation steps in the method are adequate to achieve acceptable recoveries of the parameter(s) tested.

Each QC type is analyzed at a 5-10% frequency, i.e. one blank/duplicate/spike for every 10 samples. For all types of QC, the specified recovery (% Rec) and relative percent difference (RPD) limits are derived from long-term method performance averages and/or prescribed by the reference method.

Spike Source REC RPD Analyte Result MRL Units % REC % RPD Notes Level Result Limit Limit

Anions, Batch B7A0411

Blank (B7A0411-BLK1) Prepared: 2017-01-10, Analyzed: 2017-01-10 Chloride < 0.10 0.10 mg/L Fluoride < 0.10 0.10 mg/L Nitrate (as N) < 0.010 0.010 mg/L Nitrite (as N) < 0.010 0.010 mg/L Sulfate < 1.0 1.0 mg/L LCS (B7A0411-BS1) Prepared: 2017-01-10, Analyzed: 2017-01-10 Chloride 16.0 0.10 mg/L 16.0 100 90-110 Fluoride 3.68 0.10 mg/L 4.00 92 88-108 Nitrate (as N) 4.00 0.010 mg/L 4.00 100 93-108 Nitrite (as N) 1.97 0.010 mg/L 2.00 99 83-110 Sulfate 15.4 1.0 mg/L 16.0 96 91-109

General Parameters, Batch B7A0382

Blank (B7A0382-BLK1) Prepared: 2017-01-10, Analyzed: 2017-01-10 Turbidity < 0.10 0.10 NTU LCS (B7A0382-BS1) Prepared: 2017-01-10, Analyzed: 2017-01-10 Turbidity 39.1 0.10 NTU 40.0 98 90-110 Duplicate (B7A0382-DUP1) Source: 7010430-01 Prepared: 2017-01-10, Analyzed: 2017-01-10 Turbidity 0.31 0.10 NTU 0.29 15

General Parameters, Batch B7A0430

Blank (B7A0430-BLK1) Prepared: 2017-01-11, Analyzed: 2017-01-11 Alkalinity, Total (as CaCO3) < 1 2 mg/L Alkalinity, Phenolphthalein (as CaCO3) < 1 2 mg/L Alkalinity, Bicarbonate (as CaCO3) < 1 2 mg/L Alkalinity, Carbonate (as CaCO3) < 1 2 mg/L Alkalinity, Hydroxide (as CaCO3) < 1 2 mg/L

CARO Analytical Services Page 6 of 10 Rev 2017-01-05 Page 6 of 10 APPENDIX 1: QUALITY CONTROL DATA

REPORTED TO Castlegar, City of WORK ORDER 7010430 PROJECT General Potability REPORTED 2017-01-17

Spike Source REC RPD Analyte Result MRL Units % REC % RPD Notes Level Result Limit Limit

General Parameters, Batch B7A0430, Continued

Blank (B7A0430-BLK1), Continued Prepared: 2017-01-11, Analyzed: 2017-01-11 Conductivity (EC) < 2 2 µS/cm LCS (B7A0430-BS1) Prepared: 2017-01-11, Analyzed: 2017-01-11 Alkalinity, Total (as CaCO3) 99 2 mg/L 100 99 92-106 LCS (B7A0430-BS2) Prepared: 2017-01-11, Analyzed: 2017-01-11 Conductivity (EC) 1390 2 µS/cm 1410 99 95-104 Reference (B7A0430-SRM1) Prepared: 2017-01-11, Analyzed: 2017-01-11 pH 7.01 0.01 pH units 7.00 100 98-102

General Parameters, Batch B7A0460

Blank (B7A0460-BLK1) Prepared: 2017-01-11, Analyzed: 2017-01-11 Colour, True < 5 5 CU LCS (B7A0460-BS1) Prepared: 2017-01-11, Analyzed: 2017-01-11 Colour, True 10 5 CU 10.0 100 85-115 Duplicate (B7A0460-DUP1) Source: 7010430-02 Prepared: 2017-01-11, Analyzed: 2017-01-11 Colour, True < 5 5 CU < 5 5

General Parameters, Batch B7A0467

Blank (B7A0467-BLK1) Prepared: 2017-01-11, Analyzed: 2017-01-11 Cyanide, Total < 0.0020 0.0020 mg/L LCS (B7A0467-BS1) Prepared: 2017-01-11, Analyzed: 2017-01-11 Cyanide, Total 0.0187 0.0020 mg/L 0.0200 94 85-115 LCS Dup (B7A0467-BSD1) Prepared: 2017-01-11, Analyzed: 2017-01-11 Cyanide, Total 0.0192 0.0020 mg/L 0.0200 96 85-115 2 10

Microbiological Parameters, Batch B7A0358

Blank (B7A0358-BLK1) Prepared: 2017-01-10, Analyzed: 2017-01-10 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL Blank (B7A0358-BLK2) Prepared: 2017-01-10, Analyzed: 2017-01-10 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL Blank (B7A0358-BLK3) Prepared: 2017-01-10, Analyzed: 2017-01-10 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL Blank (B7A0358-BLK4) Prepared: 2017-01-10, Analyzed: 2017-01-10 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL Blank (B7A0358-BLK5) Prepared: 2017-01-10, Analyzed: 2017-01-10 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL

CARO Analytical Services Page 7 of 10 Rev 2017-01-05 Page 7 of 10 APPENDIX 1: QUALITY CONTROL DATA

REPORTED TO Castlegar, City of WORK ORDER 7010430 PROJECT General Potability REPORTED 2017-01-17

Spike Source REC RPD Analyte Result MRL Units % REC % RPD Notes Level Result Limit Limit

Microbiological Parameters, Batch B7A0358, Continued

Blank (B7A0358-BLK6) Prepared: 2017-01-10, Analyzed: 2017-01-10 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL Blank (B7A0358-BLK7) Prepared: 2017-01-10, Analyzed: 2017-01-10 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL Blank (B7A0358-BLK8) Prepared: 2017-01-10, Analyzed: 2017-01-10 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL Blank (B7A0358-BLK9) Prepared: 2017-01-10, Analyzed: 2017-01-10 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL Blank (B7A0358-BLKA) Prepared: 2017-01-10, Analyzed: 2017-01-10 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL Blank (B7A0358-BLKB) Prepared: 2017-01-10, Analyzed: 2017-01-10 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL Blank (B7A0358-BLKC) Prepared: 2017-01-10, Analyzed: 2017-01-10 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL Blank (B7A0358-BLKD) Prepared: 2017-01-10, Analyzed: 2017-01-10 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL Blank (B7A0358-BLKE) Prepared: 2017-01-10, Analyzed: 2017-01-10 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL

Microbiological Parameters, Batch B7A0360

Blank (B7A0360-BLK1) Prepared: 2017-01-10, Analyzed: 2017-01-10 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL Blank (B7A0360-BLK2) Prepared: 2017-01-10, Analyzed: 2017-01-10 E. coli < 1 1 CFU/100 mL Blank (B7A0360-BLK3) Prepared: 2017-01-10, Analyzed: 2017-01-10 E. coli < 1 1 CFU/100 mL Blank (B7A0360-BLK4) Prepared: 2017-01-10, Analyzed: 2017-01-10 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL

Total Metals, Batch B7A0440

Blank (B7A0440-BLK1) Prepared: 2017-01-11, Analyzed: 2017-01-11 Aluminum, total < 0.005 0.005 mg/L Antimony, total < 0.0001 0.0001 mg/L Arsenic, total < 0.0005 0.0005 mg/L

CARO Analytical Services Page 8 of 10 Rev 2017-01-05 Page 8 of 10 APPENDIX 1: QUALITY CONTROL DATA

REPORTED TO Castlegar, City of WORK ORDER 7010430 PROJECT General Potability REPORTED 2017-01-17

Spike Source REC RPD Analyte Result MRL Units % REC % RPD Notes Level Result Limit Limit

Total Metals, Batch B7A0440, Continued

Blank (B7A0440-BLK1), Continued Prepared: 2017-01-11, Analyzed: 2017-01-11 Barium, total < 0.005 0.005 mg/L Boron, total < 0.004 0.004 mg/L Cadmium, total < 0.00001 0.00001 mg/L Calcium, total < 0.2 0.2 mg/L Chromium, total < 0.0005 0.0005 mg/L Cobalt, total < 0.00005 0.00005 mg/L Copper, total < 0.0002 0.0002 mg/L Iron, total < 0.01 0.01 mg/L Lead, total < 0.0001 0.0001 mg/L Magnesium, total < 0.01 0.01 mg/L Manganese, total < 0.0002 0.0002 mg/L Molybdenum, total < 0.0001 0.0001 mg/L Nickel, total < 0.0002 0.0002 mg/L Potassium, total < 0.02 0.02 mg/L Selenium, total < 0.0005 0.0005 mg/L Sodium, total < 0.02 0.02 mg/L Uranium, total < 0.00002 0.00002 mg/L Zinc, total < 0.004 0.004 mg/L Reference (B7A0440-SRM1) Prepared: 2017-01-11, Analyzed: 2017-01-11 Aluminum, total 0.295 0.005 mg/L 0.303 98 81-129 Antimony, total 0.0505 0.0001 mg/L 0.0511 99 88-114 Arsenic, total 0.117 0.0005 mg/L 0.118 99 88-114 Barium, total 0.799 0.005 mg/L 0.823 97 72-104 Boron, total 3.86 0.004 mg/L 3.45 112 75-121 Cadmium, total 0.0509 0.00001 mg/L 0.0495 103 89-111 Calcium, total 11.4 0.2 mg/L 11.6 98 86-121 Chromium, total 0.263 0.0005 mg/L 0.250 105 89-114 Cobalt, total 0.0419 0.00005 mg/L 0.0377 111 91-113 Copper, total 0.553 0.0002 mg/L 0.486 114 91-115 Iron, total 0.52 0.01 mg/L 0.488 107 77-124 Lead, total 0.200 0.0001 mg/L 0.204 98 92-113 Magnesium, total 3.98 0.01 mg/L 3.79 105 78-120 Manganese, total 0.109 0.0002 mg/L 0.109 100 90-114 Molybdenum, total 0.195 0.0001 mg/L 0.198 99 90-111 Nickel, total 0.270 0.0002 mg/L 0.249 109 90-111 Potassium, total 7.46 0.02 mg/L 7.21 104 84-113 Selenium, total 0.139 0.0005 mg/L 0.121 115 85-115 Sodium, total 7.98 0.02 mg/L 7.54 106 82-123 Uranium, total 0.0287 0.00002 mg/L 0.0306 94 85-120 Zinc, total 2.58 0.004 mg/L 2.49 104 85-111

Total Metals, Batch B7A0469

Blank (B7A0469-BLK1) Prepared: 2017-01-11, Analyzed: 2017-01-11 Mercury, total < 0.00002 0.00002 mg/L Reference (B7A0469-SRM1) Prepared: 2017-01-11, Analyzed: 2017-01-11 Mercury, total 0.00519 0.00002 mg/L 0.00489 106 50-150

Total Metals, Batch B7A0528

Blank (B7A0528-BLK1) Prepared: 2017-01-12, Analyzed: 2017-01-12 Mercury, total < 0.00002 0.00002 mg/L

CARO Analytical Services Page 9 of 10 Rev 2017-01-05 Page 9 of 10 APPENDIX 1: QUALITY CONTROL DATA

REPORTED TO Castlegar, City of WORK ORDER 7010430 PROJECT General Potability REPORTED 2017-01-17

Spike Source REC RPD Analyte Result MRL Units % REC % RPD Notes Level Result Limit Limit

Total Metals, Batch B7A0528, Continued

Blank (B7A0528-BLK2) Prepared: 2017-01-12, Analyzed: 2017-01-12 Mercury, total < 0.00002 0.00002 mg/L Reference (B7A0528-SRM1) Prepared: 2017-01-12, Analyzed: 2017-01-12 Mercury, total 0.00500 0.00002 mg/L 0.00489 102 50-150 Reference (B7A0528-SRM2) Prepared: 2017-01-12, Analyzed: 2017-01-12 Mercury, total 0.00441 0.00002 mg/L 0.00489 90 50-150

CARO Analytical Services Page 10 of 10 Rev 2017-01-05 Page 10 of 10 CERTIFICATE OF ANALYSIS

REPORTED TO Castlegar, City of 460 Columbia Avenue TEL (250) 365-5979 CASTLEGAR, BC V1N 1G7 FAX (250) 365-0594

ATTENTION Chris Barlow WORK ORDER 7010435

PO NUMBER 502 RECEIVED / TEMP 2017-01-10 09:30 / 4°C PROJECT THM & HAA REPORTED 2017-01-19 PROJECT INFO COC NUMBER No Number

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: Kristin McKeown Client Service Representative

If you have any questions or concerns, please contact me at [email protected]

Locations: #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

CARO Analytical Services Page 1 of 3 Rev 2017-01-05 Page 1 of 3 ANALYSIS INFORMATION

REPORTED TO Castlegar, City of WORK ORDER 7010435 PROJECT THM & HAA REPORTED 2017-01-19

Analysis Description Method Reference Technique Location

Haloacetic Acids in Water EPA 552.3* Liquid-Liquid Microextraction, Derivatization and Richmond GC-ECD Trihalomethanes in Water EPA 5030B / APHA Purge&Trap / Purge and Trap Capillary Column Richmond 6200 B GC-MSD Note: An asterisk in the Method Reference indicates that the CARO method has been modified from the reference method

Method Reference Descriptions: EPA United States Environmental Protection Agency Test Methods

Glossary of Terms: MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) mg/L Milligrams per litre

Standards / Guidelines Referenced in this Report: Guidelines for Canadian Drinking Water Quality (Oct 2014) Website: http://www.hc-sc.gc.ca/ewh-semt/alt_formats/pdf/pubs/water-eau/sum_guide-res_recom/sum_guide-res_recom-e ng.pdf Note: In some cases, the values displayed on the report represent the lowest guideline and are to be verified by the end user

CARO Analytical Services Page 2 of 3 Rev 2017-01-05 Page 2 of 3 SAMPLE ANALYTICAL DATA

REPORTED TO Castlegar, City of WORK ORDER 7010435 PROJECT THM & HAA REPORTED 2017-01-19

Analyte Result / Standard / MRL / Units Prepared Analyzed Notes Recovery Guideline Limits

Sample ID: WT# 90D1 - Blueberry (7010435-01) [Water] Sampled: 2017-01-09 00:00

Calculated Parameters Total Trihalomethanes 0.023 MAC = 0.1 0.004 mg/L N/A N/A

Volatile Organic Compounds (VOC) Bromodichloromethane < 0.001 N/A 0.001 mg/L N/A 2017-01-15 Bromoform < 0.001 N/A 0.001 mg/L N/A 2017-01-15 Chloroform 0.023 N/A 0.001 mg/L N/A 2017-01-15 Dibromochloromethane < 0.001 N/A 0.001 mg/L N/A 2017-01-15 Surrogate: Toluene-d8 109 70-130 % N/A 2017-01-15 Surrogate: 4-Bromofluorobenzene 103 70-130 % N/A 2017-01-15

Sample ID: WT# 29020 - Airport (7010435-02) [Water] Sampled: 2017-01-09 00:00

Calculated Parameters Total Trihalomethanes 0.021 MAC = 0.1 0.004 mg/L N/A N/A

Volatile Organic Compounds (VOC) Bromodichloromethane < 0.001 N/A 0.001 mg/L N/A 2017-01-15 Bromoform < 0.001 N/A 0.001 mg/L N/A 2017-01-15 Chloroform 0.021 N/A 0.001 mg/L N/A 2017-01-15 Dibromochloromethane < 0.001 N/A 0.001 mg/L N/A 2017-01-15 Surrogate: Toluene-d8 106 70-130 % N/A 2017-01-15 Surrogate: 4-Bromofluorobenzene 100 70-130 % N/A 2017-01-15

Sample ID: WT# 4849 - Park Pumphouse (7010435-03) [Water] Sampled: 2017-01-09 11:30

Calculated Parameters Total Haloacetic Acids (HAA5) 0.0190 MAC = 0.08 0.0020 mg/L N/A N/A

Haloacetic Acids Monochloroacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-01-16 2017-01-19 Monobromoacetic Acid 0.0042 N/A 0.0020 mg/L 2017-01-16 2017-01-19 Dichloroacetic Acid 0.0058 N/A 0.0020 mg/L 2017-01-16 2017-01-19 Trichloroacetic Acid 0.0089 N/A 0.0020 mg/L 2017-01-16 2017-01-19 Dibromoacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-01-16 2017-01-19 Surrogate: 2-Bromopropionic Acid 94 70-130 % 2017-01-16 2017-01-19

CARO Analytical Services Page 3 of 3 Rev 2017-01-05 Page 3 of 3 3ER"*&*3'"E$!&$')'%;<*<

RE !R"E#$"! Castlegar, City of 460 Columbia Avenue "E% 1-250-365-9482 CASTLEGAR, BC V1N 1G7 &'( (250) 365-0594

'""E)"*!) Jesse Reel +!R,$!R#ER 7040683

!$)=>?ER 502 RE3E*@E#$A$"E> 2017-04-11 10:00 / 12°C R!BE3" General Potability RE !R"E# 2017-04-20 R!BE3"$*)&! 3!3$)=>?ER No Number

-./.012$3455./678

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: ,0:76:/$>9,.4C/ Client Service Representative

If !"# $%&' %(! )#'*+,"(* "- ."(.'-(*/ 01'%*' ."(+%.+ 2' %+ 32.3'"4(5.%-"6.%

%4916:4/78 #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

3'R!$'/12H6:912$<.0I:9.7 1D.$E$4F$G Rev 2017-01-05 Page 1 of 8 ')'%;<*<$*)&!R>'"*!)

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7040683 R!BE3" General Potability RE !R"E# 2017-04-20

'/12H7:7$#.790:M6:4/ >.6J4N$R.F.0./9. ".9J/:KL. %4916:4/

Alkalinity in Water APHA 2320 B* Titration with H2SO4 Kelowna Anions by IC in Water APHA 4110 B Ion Chromatography with Chemical Suppression of Kelowna Eluent Conductivity Coliforms, Total (MF-Endo) in Water APHA 9222 B Membrane Filtration / Incubation on m-Endo Agar Kelowna Colour, True in Water APHA 2120 C Spectrophotometry (456 nm) Kelowna Conductivity in Water APHA 2510 B Conductivity Meter Kelowna Cyanide, SAD in Water ASTM D7511-12 Flow Injection Analysis with In-Line Ultraviolet Kelowna Digestion and Amperometric Detection E. coli (MF-NA+MUG) in Water APHA 9222 G Membrane Filtration / Nutrient Agar with MUG Kelowna Hardness (as CaCO3) in Water APHA 2340 B* Calculation: 2.497 [total Ca] + 4.118 [total Mg] N/A (Estimated) Langelier Index in Water APHA 2330 B Calculation N/A Mercury, total by CVAFS in Water EPA 245.7* BrCl2 Oxidation / Cold Vapor Atomic Fluorescence Richmond Spectrometry (CVAFS) pH in Water APHA 4500-H+ B Electrometry Kelowna Solids, Total Dissolved (calc) in APHA 1030 E Calculation: 100 x ([Cations]-[Anions])/ N/A Water ([Cations]+[Anions]) Temperature (lab) in Water APHA 2550 B Thermometer Kelowna Total Metals by ICPMS in Water APHA 3030 E* / APHA HNO3+HCl Hot Block Digestion / Inductively Coupled Richmond 3125 B Plasma Mass Spectrometry (ICP-MS) Turbidity in Water APHA 2130 B Nephelometry Kelowna

7"+'8 9( %*+'-,*3 ,( +$' :'+$"; <'f'-'(.' ,(;,.%+'* +$%+ +$' =9<> 2'+$"; $%* ?''( 2";,f,'; f-"2 +$' -'f'-'(.' 2'+$";

>.6J4N$R.F.0./9.$#.790:M6:4/78 APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health Association/American Water Works Association/Water Environment Federation ASTM ASTM International Test Methods EPA United States Environmental Protection Agency Test Methods

-247710H$4F$".0578 MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) °C Degrees Celcius CFU/100 mL Colony Forming Units per 100 millilitres CU Colour Units (referenced against a platinum cobalt standard) mg/L Milligrams per litre NTU Nephelometric Turbidity Units pH units pH < 7 = acidic, ph > 7 = basic µS/cm Microsiemens per centimetre

3'R!$'/12H6:912$<.0I:9.7 1D.$O$4F$G Rev 2017-01-05 Page 2 of 8 <'> %E$')'%;"*3'%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7040683 R!BE3" General Potability RE !R"E# 2017-04-20

$'/12H6. R.7L26$A$ >R%$A$ =/:67 0.M10.N '/12HP.N )46.7 <'."&'-! @,2,+*$

<15M2.$*#8$+"Q$RGEE$S$+"3$S$R1C$+16.0$$TUVRVWGXSVEY$$Z+16.0[$$<15M2.N8$OVEUSVRSEV$EV8EV

9(,"(* Chloride V\XV 0.10 mg/L N/A 2017-04-12 Fluoride < 0.10 0.10 mg/L N/A 2017-04-12 Nitrate (as N) V\EEV 0.010 mg/L N/A 2017-04-12 Nitrite (as N) < 0.010 0.010 mg/L N/A 2017-04-12 Sulfate EE\O 1.0 mg/L N/A 2017-04-12

A'('-%1 B%-%2'+'-* Alkalinity, Total (as CaCO3) ]W\V 2.0 mg/L N/A 2017-04-20 Alkalinity, Phenolphthalein (as CaCO3) < 1.0 2.0 mg/L N/A 2017-04-20 Alkalinity, Bicarbonate (as CaCO3) ]W\V 2.0 mg/L N/A 2017-04-20 Alkalinity, Carbonate (as CaCO3) < 1.0 2.0 mg/L N/A 2017-04-20 Alkalinity, Hydroxide (as CaCO3) < 1.0 2.0 mg/L N/A 2017-04-20 Colour, True < 5.0 5.0 CU N/A 2017-04-12 Conductivity (EC) EXO 2.0 µS/cm N/A 2017-04-20 Cyanide, Total < 0.0020 0.0020 mg/L N/A 2017-04-13 pH U\UX 0.01 pH units N/A 2017-04-20 HT2 Temperature, at pH OX °C N/A 2017-04-20 HT2 Turbidity V\XR 0.10 NTU N/A 2017-04-12

=%1.#1%+'; B%-%2'+'-* Hardness, Total (as CaCO3) WE\W 0.500 mg/L N/A N/A Langelier Index SV\U -5.0 - N/A 2017-04-20 Solids, Total Dissolved (calc) W^\] 1.00 mg/L N/A N/A

C"+%1 :'+%1* Aluminum, total V\VE] 0.005 mg/L 2017-04-13 2017-04-13 Antimony, total < 0.0001 0.0001 mg/L 2017-04-13 2017-04-13 Arsenic, total < 0.0005 0.0005 mg/L 2017-04-13 2017-04-13 Barium, total V\VEU 0.005 mg/L 2017-04-13 2017-04-13 Boron, total V\VVU 0.004 mg/L 2017-04-13 2017-04-13 Cadmium, total V\VVVV] 0.00001 mg/L 2017-04-13 2017-04-13 Calcium, total EU\U 0.2 mg/L 2017-04-13 2017-04-13 Chromium, total V\VVVU 0.0005 mg/L 2017-04-13 2017-04-13 Cobalt, total < 0.00005 0.00005 mg/L 2017-04-13 2017-04-13 Copper, total V\VVGU 0.0002 mg/L 2017-04-13 2017-04-13 Iron, total V\VE 0.01 mg/L 2017-04-13 2017-04-13 Lead, total V\VVVX 0.0001 mg/L 2017-04-13 2017-04-13 Magnesium, total R\OR 0.01 mg/L 2017-04-13 2017-04-13 Manganese, total V\VVER 0.0002 mg/L 2017-04-13 2017-04-13 Mercury, total < 0.00002 0.00002 mg/L 2017-04-19 2017-04-19 Molybdenum, total V\VVVW 0.0001 mg/L 2017-04-13 2017-04-13 Nickel, total V\VVV] 0.0002 mg/L 2017-04-13 2017-04-13 Potassium, total V\WU 0.02 mg/L 2017-04-13 2017-04-13 Selenium, total < 0.0005 0.0005 mg/L 2017-04-13 2017-04-13 Sodium, total V\GO 0.02 mg/L 2017-04-13 2017-04-13 Uranium, total V\VVVRR 0.00002 mg/L 2017-04-13 2017-04-13 Zinc, total V\VXU 0.004 mg/L 2017-04-13 2017-04-13

3'R!$'/12H6:912$<.0I:9.7 1D.$X$4F$G Rev 2017-01-05 Page 3 of 8 <'> %E$')'%;"*3'%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7040683 R!BE3" General Potability RE !R"E# 2017-04-20

$'/12H6. R.7L26$A$ >R%$A$ =/:67 0.M10.N '/12HP.N )46.7 <'."&'-! @,2,+*$

<15M2.$*#8$+"Q$RGEE$S$+"3$S$R1C$+16.0$$TUVRVWGXSVEY$$Z+16.0[$$<15M2.N8$OVEUSVRSEV$EV8EV_$34/6:/L.N

:,.-"?,"1"D,.%1 B%-%2'+'-* Coliforms, Total W 1 CFU/100 mL N/A 2017-04-11 Background Colonies `$OVV 200 CFU/100 mL N/A 2017-04-11 E. coli < 1 1 CFU/100 mL N/A 2017-04-11

<15M2.$A$'/12H7:7$aL12:F:.078 HT2 The 15 minute recommended holding time (from sampling to analysis) has been exceeded - field analysis is recommended.

3'R!$'/12H6:912$<.0I:9.7 1D.$R$4F$G Rev 2017-01-05 Page 4 of 8 ' E)#*($E8$a='%*";$3!)"R!%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7040683 R!BE3" General Potability RE !R"E# 2017-04-20

The following section displays the quality control (QC) data that is associated with your sample data. Groups of samples are prepared (9'mBa!:># n'a9?'a9a")D#?'(9':*9bA9:!(*9'@(!>'lC' a<="# '!>a!'#9 A%#')*A%'?a!a'( '*+'!>#'>($># !'EAa"(!)G'C*<<*9'lC'!)=# '(9:"A?#J o' >.6J4N$ ?21/b$ T?2bY: Laboratory reagent water is carried through sample preparation and analysis steps. Method Blanks indicate that results are free from contamination, i.e. not biased high from sources such as the sample container or the laboratory environment o' #LM2:916.$ T#LMY: Preparation and analysis of a replicate aliquot of a sample. Duplicates provide a measure of the analytical methodps precision, i.e. how reproducible a result is. Duplicates are only reported if they are associated with your sample data. o' ?21/b$ 16.0:12$ TY: A material of similar matrix to the samples, externally certified for the parameter(s) listed. Standard Reference Materials ensure that the preparation steps in the method are adequate to achieve acceptable recoveries of the parameter(s) tested.

Each QC type is analyzed at a 5-10% frequency, i.e. one blank/duplicate/spike for every 10 samples. For all types of QC, the specified recovery (% Rec) and relative percent difference (RPD) limits are derived from long-term method performance averages and/or prescribed by the reference method.

R% =/:67 c$RE3 c$R # )46.7$ %.I.2 R.7L26 %:5:6 %:5:6

9(,"(*/ E%+.$ EFGHIHJ

?21/b$T?U#VWVXS?%,EY Prepared: 2017-04-12, Analyzed: 2017-04-12 Chloride < 0.10 0.10 mg/L Fluoride < 0.10 0.10 mg/L Nitrate (as N) < 0.010 0.010 mg/L Nitrite (as N) < 0.010 0.010 mg/L Sulfate < 1.0 1.0 mg/L ?21/b$T?U#VWVXS?%,OY Prepared: 2017-04-12, Analyzed: 2017-04-12 Chloride < 0.10 0.10 mg/L Fluoride < 0.10 0.10 mg/L Nitrate (as N) < 0.010 0.010 mg/L Nitrite (as N) < 0.010 0.010 mg/L Sulfate < 1.0 1.0 mg/L %3<$T?U#VWVXS?

A'('-%1 B%-%2'+'-*/ E%+.$ EFGHIJK

?21/b$T?U#VWXRS?%,EY Prepared: 2017-04-12, Analyzed: 2017-04-12 Turbidity < 0.10 0.10 NTU

3'R!$'/12H6:912$<.0I:9.7 1D.$]$4F$G Rev 2017-01-05 Page 5 of 8 ' E)#*($E8$a='%*";$3!)"R!%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7040683 R!BE3" General Potability RE !R"E# 2017-04-20

R% =/:67 c$RE3 c$R # )46.7$ %.I.2 R.7L26 %:5:6 %:5:6

A'('-%1 B%-%2'+'-*/ E%+.$ EFGHIJK/ ="(+,(#';

%3<$T?U#VWXRS?

A'('-%1 B%-%2'+'-*/ E%+.$ EFGHIFL

?21/b$T?U#VWUGS?%,EY Prepared: 2017-04-12, Analyzed: 2017-04-12 Colour, True < 5.0 5.0 CU %3<$T?U#VWUGS?

A'('-%1 B%-%2'+'-*/ E%+.$ EFGHFMK

?21/b$T?U#VU]RS?%,EY Prepared: 2017-04-13, Analyzed: 2017-04-13 Cyanide, Total < 0.0020 0.0020 mg/L ?21/b$T?U#VU]RS?%,OY Prepared: 2017-04-13, Analyzed: 2017-04-13 Cyanide, Total < 0.0020 0.0020 mg/L %3<$T?U#VU]RS?

A'('-%1 B%-%2'+'-*/ E%+.$ EFGHLIK

?21/b$T?U#VGWRS?%,EY Prepared: 2017-04-20, Analyzed: 2017-04-20 Alkalinity, Total (as CaCO3) < 1.0 2.0 mg/L Alkalinity, Phenolphthalein (as CaCO3) < 1.0 2.0 mg/L Alkalinity, Bicarbonate (as CaCO3) < 1.0 2.0 mg/L Alkalinity, Carbonate (as CaCO3) < 1.0 2.0 mg/L Alkalinity, Hydroxide (as CaCO3) < 1.0 2.0 mg/L Conductivity (EC) < 2.0 2.0 µS/cm %3<$T?U#VGWRS?

3'R!$'/12H6:912$<.0I:9.7 1D.$W$4F$G Rev 2017-01-05 Page 6 of 8 ' E)#*($E8$a='%*";$3!)"R!%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7040683 R!BE3" General Potability RE !R"E# 2017-04-20

R% =/:67 c$RE3 c$R # )46.7$ %.I.2 R.7L26 %:5:6 %:5:6

A'('-%1 B%-%2'+'-*/ E%+.$ EFGHLIK/ ="(+,(#';

#LM2:916.$T?U#VGWRS#= EY_$34/6:/L.N <4L09.8$UVRVWGXSVE Prepared: 2017-04-20, Analyzed: 2017-04-20 pH 7.74 0.01 pH units 7.73 < 1 4 HT2 R.F.0./9.$T?U#VGWRSEY Prepared: 2017-04-20, Analyzed: 2017-04-20 pH 6.99 0.01 pH units 7.00 100 98-102 HT2

:,.-"?,"1"D,.%1 B%-%2'+'-*/ E%+.$ EFGHMLN

?21/b$T?U#V]GOS?%,EY Prepared: 2017-04-11, Analyzed: 2017-04-11 E. coli < 1 1 CFU/100 mL ?21/b$T?U#V]GOS?%,OY Prepared: 2017-04-11, Analyzed: 2017-04-11 E. coli < 1 1 CFU/100 mL ?21/b$T?U#V]GOS?%,XY Prepared: 2017-04-11, Analyzed: 2017-04-11 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL

C"+%1 :'+%1*/ E%+.$ EFGHFJL

?21/b$T?U#VUXGS?%,EY Prepared: 2017-04-13, Analyzed: 2017-04-13 Aluminum, total < 0.005 0.005 mg/L Antimony, total < 0.0001 0.0001 mg/L Arsenic, total < 0.0005 0.0005 mg/L Barium, total < 0.005 0.005 mg/L Boron, total < 0.004 0.004 mg/L Cadmium, total < 0.00001 0.00001 mg/L Calcium, total < 0.2 0.2 mg/L Chromium, total < 0.0005 0.0005 mg/L Cobalt, total < 0.00005 0.00005 mg/L Copper, total < 0.0002 0.0002 mg/L Iron, total < 0.01 0.01 mg/L Lead, total < 0.0001 0.0001 mg/L Magnesium, total < 0.01 0.01 mg/L Manganese, total < 0.0002 0.0002 mg/L Molybdenum, total < 0.0001 0.0001 mg/L Nickel, total < 0.0002 0.0002 mg/L Potassium, total < 0.02 0.02 mg/L Selenium, total < 0.0005 0.0005 mg/L Sodium, total < 0.02 0.02 mg/L Uranium, total < 0.00002 0.00002 mg/L Zinc, total < 0.004 0.004 mg/L R.F.0./9.$T?U#VUXGSEY Prepared: 2017-04-13, Analyzed: 2017-04-13 Aluminum, total 0.294 0.005 mg/L 0.303 97 81-129 Antimony, total 0.0488 0.0001 mg/L 0.0511 96 88-114 Arsenic, total 0.116 0.0005 mg/L 0.118 99 88-114 Barium, total 0.786 0.005 mg/L 0.823 96 72-104 Boron, total 3.70 0.004 mg/L 3.45 107 75-121 Cadmium, total 0.0493 0.00001 mg/L 0.0495 100 89-111 Calcium, total 12.1 0.2 mg/L 11.6 104 86-121 Chromium, total 0.239 0.0005 mg/L 0.250 95 89-114 Cobalt, total 0.0382 0.00005 mg/L 0.0377 101 91-113 Copper, total 0.493 0.0002 mg/L 0.486 101 91-115 Iron, total 0.48 0.01 mg/L 0.488 99 77-124 Lead, total 0.218 0.0001 mg/L 0.204 107 92-113 Magnesium, total 3.73 0.01 mg/L 3.79 98 78-120

3'R!$'/12H6:912$<.0I:9.7 1D.$U$4F$G Rev 2017-01-05 Page 7 of 8 ' E)#*($E8$a='%*";$3!)"R!%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7040683 R!BE3" General Potability RE !R"E# 2017-04-20

R% =/:67 c$RE3 c$R # )46.7$ %.I.2 R.7L26 %:5:6 %:5:6

C"+%1 :'+%1*/ E%+.$ EFGHFJL/ ="(+,(#';

R.F.0./9.$T?U#VUXGSEY_$34/6:/L.N Prepared: 2017-04-13, Analyzed: 2017-04-13 Manganese, total 0.104 0.0002 mg/L 0.109 96 90-114 Molybdenum, total 0.191 0.0001 mg/L 0.198 97 90-111 Nickel, total 0.244 0.0002 mg/L 0.249 98 90-111 Potassium, total 7.34 0.02 mg/L 7.21 102 84-113 Selenium, total 0.127 0.0005 mg/L 0.121 105 85-115 Sodium, total 7.47 0.02 mg/L 7.54 99 82-123 Uranium, total 0.0324 0.00002 mg/L 0.0306 106 85-120 Zinc, total 2.50 0.004 mg/L 2.49 100 85-111

C"+%1 :'+%1*/ E%+.$ EFGHOMM

?21/b$T?U#V^]]S?%,EY Prepared: 2017-04-19, Analyzed: 2017-04-19 Mercury, total < 0.00002 0.00002 mg/L ?21/b$T?U#V^]]S?%,OY Prepared: 2017-04-19, Analyzed: 2017-04-19 Mercury, total < 0.00002 0.00002 mg/L >160:d$EY Prepared: 2017-04-19, Analyzed: 2017-04-19 Mercury, total 0.00448 0.00002 mg/L 0.00489 92 50-150 R.F.0./9.$T?U#V^]]SOY Prepared: 2017-04-19, Analyzed: 2017-04-19 Mercury, total 0.00429 0.00002 mg/L 0.00489 88 50-150

a3$aL12:F:.078 HT2 The 15 minute recommended holding time (from sampling to analysis) has been exceeded - field analysis is recommended.

3'R!$'/12H6:912$<.0I:9.7 1D.$G$4F$G Rev 2017-01-05 Page 8 of 8 3ER"*&*3'"E$!&$')'%;<*<

RE !R"E#$"! Castlegar, City of 460 Columbia Avenue "E% (250) 365-5979 CASTLEGAR, BC V1N 1G7 &'( (250) 365-0594

'""E)"*!) Chris Barlow +!R,$!R#ER 7040687

!$)=>?ER 502 RE3E*@E#$A$"E> 2017-04-11 10:00 / 12°C R!BE3" THM & HAA RE !R"E# 2017-04-18 R!BE3"$*)&! 3!3$)=>?ER No Number

-./.012$3455./678

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: ,0:76:/$>9,.4C/ Client Service Representative

If !"# $%&' %(! )#'*+,"(* "- ."(.'-(*/ 01'%*' ."(+%.+ 2' %+ 32.3'"4(5.%-"6.%

%4916:4/78 #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

3'R!$'/12H6:912$<.0I:9.7 1D.$E$4F$G Rev 2017-01-05 Page 1 of 3 ')'%;<*<$*)&!R>'"*!)

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7040687 R!BE3" THM & HAA RE !R"E# 2017-04-18

'/12H7:7$#.790:M6:4/ >.6J4N$R.F.0./9. ".9J/:KL. %4916:4/

Haloacetic Acids in Water EPA 552.3* Liquid-Liquid Microextraction, Derivatization and Richmond GC-ECD Trihalomethanes in Water EPA 5030B / APHA Purge&Trap / Purge and Trap Capillary Column Richmond 6200 B GC-MSD 7"+'8 9( %*+'-,*3 ,( +$' :'+$"; <'f'-'(.' ,(;,.%+'* +$%+ +$' =9<> 2'+$"; $%* ?''( 2";,f,'; f-"2 +$' -'f'-'(.' 2'+$";

>.6J4N$R.F.0./9.$#.790:M6:4/78 EPA United States Environmental Protection Agency Test Methods

-247710H$4F$".0578 MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) mg/L Milligrams per litre

<61/N10N7$A$-L:N.2:/.7$R.F.0./9.N$:/$6J:7$R.M4068 Guidelines for Canadian Drinking Water Quality (Feb 2017) Website: http://www.hc-sc.gc.ca/ewh-semt/alt_formats/pdf/pubs/water-eau/sum_guide-res_recom/sum_guide-res_recom-e ng.pdf 7"+'8 I( *"2' .%*'*/ +$' &%1#'* ;,*01%!'; "( +$' -'0"-+ -'0-'*'(+ +$' 1"4'*+ @#,;'1,(' %(; %-' +" ?' &'-,f,'; ?! +$' '(; #*'-

3'R!$'/12H6:912$<.0I:9.7 1D.$O$4F$G Rev 2017-01-05 Page 2 of 3 <'> %E$')'%;"*3'%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7040687 R!BE3" THM & HAA RE !R"E# 2017-04-18

$'/12H6. R.7L26$A$ <61/N10N$A$ >R%$A$ =/:67 0.M10.N '/12HP.N )46.7 <'."&'-! -L:N.2:/. A,2,+*$

<15M2.$*#8$+"Q$RS#E$T$?2L.U.00H$$VWSXSYZWTSE[$$\+16.0]$$<15M2.N8$OSEWTSXTES$SS8SS

=%1.#1%+'; B%-%2'+'-* Total Trihalomethanes S^SOZG MAC = 0.1 0.00400 mg/L N/A N/A

C"1%+,1' >-@%(,. ="20"#(;* DC>=E CT2 Bromodichloromethane < 0.001 N/A 0.001 mg/L N/A 2017-04-14 Bromoform < 0.001 N/A 0.001 mg/L N/A 2017-04-14 Chloroform S^SOZ N/A 0.001 mg/L N/A 2017-04-14 Dibromochloromethane < 0.001 N/A 0.001 mg/L N/A 2017-04-14 &'(()*+,-./0)1'-2-"34 !$ !0" %0 % 567 20 !"0#" # &'(()*+,-./#"8()9):1')();-2<-2- 0 !0" %0 % 567 20 !"0#" #

<15M2.$*#8$+"Q$ORSOS$T$':0M406$$VWSXSYZWTSO[$$\+16.0]$$<15M2.N8$OSEWTSXTES$SS8SS

=%1.#1%+'; B%-%2'+'-* Total Trihalomethanes S^SOZX MAC = 0.1 0.00400 mg/L N/A N/A

C"1%+,1' >-@%(,. ="20"#(;* DC>=E CT2 Bromodichloromethane < 0.001 N/A 0.001 mg/L N/A 2017-04-14 Bromoform < 0.001 N/A 0.001 mg/L N/A 2017-04-14 Chloroform S^SOZ N/A 0.001 mg/L N/A 2017-04-14 Dibromochloromethane < 0.001 N/A 0.001 mg/L N/A 2017-04-14 &'(()*+,-./0)1'-2-"34 42 !0" %0 % 567 20 !"0#" # &'(()*+,-./#"8()9):1')();-2<-2- 2 !0" %0 % 567 20 !"0#" #

<15M2.$*#8$+"Q$XZXR$T$ 10_$ L5MJ4L7.$$VWSXSYZWTSG[$$\+16.0]$$<15M2.N8$OSEWTSXTES$SS8SS

=%1.#1%+'; B%-%2'+'-* Total Haloacetic Acids (HAA5) S^SEWS MAC = 0.08 0.00200 mg/L N/A N/A

F%1"%.'+,. 9.,;* Monochloroacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-04-16 2017-04-17 Monobromoacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-04-16 2017-04-17 Dichloroacetic Acid S^SSYR N/A 0.0020 mg/L 2017-04-16 2017-04-17 Trichloroacetic Acid S^SESE N/A 0.0020 mg/L 2017-04-16 2017-04-17 Dibromoacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-04-16 2017-04-17 &'(()*+,-./2"8()9)=()=>)2>?/7?>3 0# !0" %0 % 20 !"0#" @ 20 !"0#" !

<15M2.$A$'/12H7:7$`L12:F:.078 CT2 Excessive headspace in sample container - VOC results may be compromised.

3'R!$'/12H6:912$<.0I:9.7 1D.$G$4F$G Rev 2017-01-05 Page 3 of 3 3ER"*&*3'"E$!&$')'%;<*<

RE !R"E#$"! Castlegar, City of 460 Columbia Avenue "E% (250) 365-5979 CASTLEGAR, BC V1N 1G7 &'( (250) 365-0594

'""E)"*!) Chris Barlow +!R,$!R#ER 7040698

!$)=>?ER 502 RE3E*@E#$A$"E> 2017-04-11 10:00 / 12°C R!BE3" Water Treatment Centre RE !R"E# 2017-04-12 R!BE3"$*)&! 2-1-SR 3!3$)=>?ER 41981.31143

-./.012$3455./678

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: ,0:76:/$>9,.4C/ Client Service Representative

If !"# $%&' %(! )#'*+,"(* "- ."(.'-(*/ 01'%*' ."(+%.+ 2' %+ 32.3'"4(5.%-"6.%

%4916:4/78 #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

3'R!$'/12H6:912$<.0I:9.7 1D.$E$4F$G Rev 2017-01-05 Page 1 of 3 ')'%;<*<$*)&!R>'"*!)

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7040698 R!BE3" Water Treatment Centre RE !R"E# 2017-04-12

'/12H7:7$#.790:M6:4/ >.6J4N$R.F.0./9. ".9J/:KL. %4916:4/

Coliforms, Total (MF-Endo) in Water APHA 9222 B Membrane Filtration / Incubation on m-Endo Agar Kelowna E. coli (MF-NA+MUG) in Water APHA 9222 G Membrane Filtration / Nutrient Agar with MUG Kelowna

>.6J4N$R.F.0./9.$#.790:M6:4/78 APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health Association/American Water Works Association/Water Environment Federation

-247710H$4F$".0578 MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) CFU/100 mL Colony Forming Units per 100 millilitres

<61/N10N7$A$-L:N.2:/.7$R.F.0./9.N$:/$6J:7$R.M4068 Guidelines for Canadian Drinking Water Quality (Feb 2017) Website: http://www.hc-sc.gc.ca/ewh-semt/alt_formats/pdf/pubs/water-eau/sum_guide-res_recom/sum_guide-res_recom-e ng.pdf 7"+'8 I( *"2' .%*'*/ +$' &%1#'* 9,*01%!'9 "( +$' -'0"-+ -'0-'*'(+ +$' 1"4'*+ :#,9'1,(' %(9 %-' +" ;' &'-,f,'9 ;! +$' '(9 #*'-

3'R!$'/12H6:912$<.0I:9.7 1D.$O$4F$G Rev 2017-01-05 Page 2 of 3 <'> %E$')'%;"*3'%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7040698 R!BE3" Water Treatment Centre RE !R"E# 2017-04-12

$'/12H6. R.7L26$A$ <61/N10N$A$ >R%$A$ =/:67 0.M10.N '/12HP.N )46.7 <'."&'-! -L:N.2:/. =,2,+*$

<15M2.$*#8$+"Q$RSEE$T$+"3$T$R1C$+16.0$$UVWRWXYSTWEZ$$[+16.0\$$<15M2.N8$OWEVTWRTEW$WW8WW

>,.-";,"1":,.%1 ?%-%2'+'-* Coliforms, Total X MAC = None 1 CFU/100 mL N/A 2017-04-11 Detected Background Colonies ]$OWW N/A 200 CFU/100 mL N/A 2017-04-11 E. coli < 1 MAC = None 1 CFU/100 mL N/A 2017-04-11 Detected

3'R!$'/12H6:912$<.0I:9.7 1D.$G$4F$G Rev 2017-01-05 Page 3 of 3 CERTIFICATE OF ANALYSIS

REPORTED TO Castlegar, City of 460 Columbia Avenue TEL (250) 365-5979 CASTLEGAR, BC V1N 1G7 FAX (250) 365-0594

ATTENTION Chris Barlow WORK ORDER 7070346

PO NUMBER 502 RECEIVED / TEMP 2017-07-06 09:00 / 16°C PROJECT Drinking Water REPORTED 2017-07-07 PROJECT INFO COC NUMBER 41981.31143

General Comments:

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: Kristin McKeown Account Manager

If you have any questions or concerns, please contact me at [email protected]

Locations: #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

CARO Analytical Services Page 1 of 3 Rev 2017-01-05 Page 1 of 3 ANALYSIS INFORMATION

REPORTED TO Castlegar, City of WORK ORDER 7070346 PROJECT Drinking Water REPORTED 2017-07-07

Analysis Description Method Reference Technique Location

Coliforms, Total (MF-CCA) in Water APHA 9222* Membrane Filtration / Incubation on Chromocult Agar Kelowna Coliforms, Total (MF-Endo) in Water APHA 9222 B Membrane Filtration / Incubation on m-Endo Agar Kelowna E. coli (MF-CCA) in Water APHA 9222* Membrane Filtration / Incubation on Chromocult Agar Kelowna E. coli (MF-NA+MUG) in Water APHA 9222 G Membrane Filtration / Nutrient Agar with MUG Kelowna

Note: An asterisk in the Method Reference indicates that the CARO method has been modified from the reference method

Method Reference Descriptions: APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health Association/American Water Works Association/Water Environment Federation

Glossary of Terms: MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) CFU/100 mL Colony Forming Units per 100 millilitres

Standards / Guidelines Referenced in this Report: Guidelines for Canadian Drinking Water Quality (Feb 2017) Website: http://www.hc-sc.gc.ca/ewh-semt/alt_formats/pdf/pubs/water-eau/sum_guide-res_recom/sum_guide-res_recom-e ng.pdf Note: In some cases, the values displayed on the report represent the lowest guideline and are to be verified by the end user

CARO Analytical Services Page 2 of 3 Rev 2017-01-05 Page 2 of 3 SAMPLE ANALYTICAL DATA

REPORTED TO Castlegar, City of WORK ORDER 7070346 PROJECT Drinking Water REPORTED 2017-07-07

Analyte Result / Standard / MRL / Units Prepared Analyzed Notes Recovery Guideline Limits

Sample ID: WT# 1D214 - North Well (7070346-01) [Water] Sampled: 2017-07-05 09:30

Microbiological Parameters Coliforms, Total < 1 MAC = None 1 CFU/100 mL N/A 2017-07-06 Detected E. coli < 1 MAC = None 1 CFU/100 mL N/A 2017-07-06 Detected

Sample ID: WT# 481E - WTC - Raw Water Tap (7070346-02) [Water] Sampled: 2017-07-05 10:40

Microbiological Parameters Coliforms, Total 4 MAC = None 1 CFU/100 mL N/A 2017-07-06 Detected Background Colonies > 200 N/A 200 CFU/100 mL N/A 2017-07-06 E. coli < 1 MAC = None 1 CFU/100 mL N/A 2017-07-06 Detected

CARO Analytical Services Page 3 of 3 Rev 2017-01-05 Page 3 of 3 3ER"*&*3'"E$!&$')'%;<*<

RE !R"E#$"! Castlegar, City of 460 Columbia Avenue "E% 1-250-365-9482 CASTLEGAR, BC V1N 1G7 &'( (250) 365-0594

'""E)"*!) Jesse Reel +!R,$!R#ER 7070348

!$)=>?ER 502 RE3E*@E#$A$"E> 2017-07-06 09:00 / 16°C R!BE3" General Potability RE !R"E# 2017-07-13 R!BE3"$*)&! 3!3$)=>?ER No Number

-./.012$3455./678

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: ,0:76:/$>9,.4C/ Account Manager

If !"# $%&' %(! )#'*+,"(* "- ."(.'-(*/ 01'%*' ."(+%.+ 2' %+ 32.3'"4(5.%-"6.%

%4916:4/78 #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

3'R!$'/12H6:912$<.0I:9.7 1D.$E$4F$G Rev 2017-01-05 Page 1 of 9 ')'%;<*<$*)&!R>'"*!)

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7070348 R!BE3" General Potability RE !R"E# 2017-07-13

'/12H7:7$#.790:M6:4/ >.6J4N$R.F.0./9. ".9J/:KL. %4916:4/

Alkalinity in Water APHA 2320 B* Titration with H2SO4 Kelowna Anions by IC in Water APHA 4110 B Ion Chromatography with Chemical Suppression of Kelowna Eluent Conductivity Coliforms, Total (MF-Endo) in Water APHA 9222 B Membrane Filtration / Incubation on m-Endo Agar Kelowna Colour, True in Water APHA 2120 C Spectrophotometry (456 nm) Kelowna Conductivity in Water APHA 2510 B Conductivity Meter Kelowna Cyanide, SAD in Water ASTM D7511-12 Flow Injection Analysis with In-Line Ultraviolet Kelowna Digestion and Amperometric Detection E. coli (MF-NA+MUG) in Water APHA 9222 G Membrane Filtration / Nutrient Agar with MUG Kelowna Hardness (as CaCO3) in Water APHA 2340 B* Calculation: 2.497 [total Ca] + 4.118 [total Mg] N/A (Estimated) Langelier Index in Water APHA 2330 B Calculation N/A pH in Water APHA 4500-H+ B Electrometry Kelowna Solids, Total Dissolved (calc) in APHA 1030 E Calculation: 100 x ([Cations]-[Anions])/ N/A Water ([Cations]+[Anions]) Temperature (lab) in Water APHA 2550 B Thermometer Kelowna Total Metals by ICPMS in Water APHA 3030 E* / APHA HNO3+HCl Hot Block Digestion / Inductively Coupled Richmond 3125 B Plasma Mass Spectrometry (ICP-MS) Turbidity in Water APHA 2130 B Nephelometry Kelowna

7"+'8 9( %*+'-,*3 ,( +$' :'+$"; <'f'-'(.' ,(;,.%+'* +$%+ +$' =9<> 2'+$"; $%* ?''( 2";,f,'; f-"2 +$' -'f'-'(.' 2'+$";

>.6J4N$R.F.0./9.$#.790:M6:4/78 APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health Association/American Water Works Association/Water Environment Federation ASTM ASTM International Test Methods

-247710H$4F$".0578 MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) °C Degrees Celcius CFU/100 mL Colony Forming Units per 100 millilitres CU Colour Units (referenced against a platinum cobalt standard) mg/L Milligrams per litre NTU Nephelometric Turbidity Units pH units pH < 7 = acidic, ph > 7 = basic µS/cm Microsiemens per centimetre

3'R!$'/12H6:912$<.0I:9.7 1D.$O$4F$G Rev 2017-01-05 Page 2 of 9 <'> %E$')'%;"*3'%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7070348 R!BE3" General Potability RE !R"E# 2017-07-13

$'/12H6. R.7L26$A$ >R%$A$ =/:67 0.M10.N '/12HP.N )46.7 <'."&'-! @,2,+*$

<15M2.$*#8$+"Q$RSEE$T$+"3$T$R1C$+16.0$$UVWVWXRSTWEY$$Z+16.0[$$<15M2.N8$OWEVTWVTW\$EW8RW

9(,"(* Chloride W]OR 0.10 mg/L N/A 2017-07-07 Fluoride < 0.10 0.10 mg/L N/A 2017-07-07 Nitrate (as N) W]WGX 0.010 mg/L N/A 2017-07-07 Nitrite (as N) < 0.010 0.010 mg/L N/A 2017-07-07 Sulfate EW]^ 1.0 mg/L N/A 2017-07-07

A'('-%1 B%-%2'+'-* Alkalinity, Total (as CaCO3) RG]V 1.0 mg/L N/A 2017-07-09 Alkalinity, Phenolphthalein (as CaCO3) < 1.0 1.0 mg/L N/A 2017-07-09 Alkalinity, Bicarbonate (as CaCO3) RG]V 1.0 mg/L N/A 2017-07-09 Alkalinity, Carbonate (as CaCO3) < 1.0 1.0 mg/L N/A 2017-07-09 Alkalinity, Hydroxide (as CaCO3) < 1.0 1.0 mg/L N/A 2017-07-09 Colour, True < 5.0 5.0 CU N/A 2017-07-07 Conductivity (EC) EOR 2.0 µS/cm N/A 2017-07-09 Cyanide, Total < 0.0020 0.0020 mg/L N/A 2017-07-07 pH V]SG 0.01 pH units N/A 2017-07-09 HT2 Temperature, at pH OO °C N/A 2017-07-09 HT2 Turbidity W]XV 0.10 NTU N/A 2017-07-06

=%1.#1%+'; B%-%2'+'-* Hardness, Total (as CaCO3) \V]O 0.500 mg/L N/A N/A Langelier Index TW]V -5.0 - N/A 2017-07-13 Solids, Total Dissolved (calc) ^X]R 1.00 mg/L N/A N/A

C"+%1 :'+%1* Aluminum, total W]WOGS 0.0050 mg/L 2017-07-11 2017-07-11 Antimony, total < 0.00010 0.00010 mg/L 2017-07-11 2017-07-11 Arsenic, total < 0.00050 0.00050 mg/L 2017-07-11 2017-07-11 Barium, total W]WE\S 0.0050 mg/L 2017-07-11 2017-07-11 Boron, total W]WWG^ 0.0050 mg/L 2017-07-11 2017-07-11 Cadmium, total W]WWWWEO 0.000010 mg/L 2017-07-11 2017-07-11 Calcium, total E^]X 0.20 mg/L 2017-07-11 2017-07-11 Chromium, total < 0.00050 0.00050 mg/L 2017-07-11 2017-07-11 Cobalt, total W]WWWES 0.00010 mg/L 2017-07-11 2017-07-11 Copper, total W]WEEW 0.00020 mg/L 2017-07-11 2017-07-11 Iron, total W]WOX 0.010 mg/L 2017-07-11 2017-07-11 Lead, total W]WWW\V 0.00010 mg/L 2017-07-11 2017-07-11 Magnesium, total R]WW 0.010 mg/L 2017-07-11 2017-07-11 Manganese, total W]WWERV 0.00020 mg/L 2017-07-11 2017-07-11 Mercury, total W]WWWWOE 0.000020 mg/L 2017-07-11 2017-07-11 Molybdenum, total W]WWWRG 0.00010 mg/L 2017-07-11 2017-07-11 Nickel, total W]WWW\E 0.00020 mg/L 2017-07-11 2017-07-11 Potassium, total W]^O 0.10 mg/L 2017-07-11 2017-07-11 Selenium, total < 0.00050 0.00050 mg/L 2017-07-11 2017-07-11 Sodium, total W]GO 0.10 mg/L 2017-07-11 2017-07-11 Uranium, total W]WWWROG 0.000020 mg/L 2017-07-11 2017-07-11 Zinc, total W]WWRW 0.0040 mg/L 2017-07-11 2017-07-11

3'R!$'/12H6:912$<.0I:9.7 1D.$X$4F$G Rev 2017-01-05 Page 3 of 9 <'> %E$')'%;"*3'%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7070348 R!BE3" General Potability RE !R"E# 2017-07-13

$'/12H6. R.7L26$A$ >R%$A$ =/:67 0.M10.N '/12HP.N )46.7 <'."&'-! @,2,+*$

<15M2.$*#8$+"Q$RSEE$T$+"3$T$R1C$+16.0$$UVWVWXRSTWEY$$Z+16.0[$$<15M2.N8$OWEVTWVTW\$EW8RW_$34/6:/L.N

:,.-"?,"1"D,.%1 B%-%2'+'-* Coliforms, Total X 1 CFU/100 mL N/A 2017-07-06 Background Colonies `$OWW 200 CFU/100 mL N/A 2017-07-06 E. coli < 1 1 CFU/100 mL N/A 2017-07-06

<15M2.$A$'/12H7:7$aL12:F:.078 HT2 The 15 minute recommended holding time (from sampling to analysis) has been exceeded - field analysis is recommended.

3'R!$'/12H6:912$<.0I:9.7 1D.$R$4F$G Rev 2017-01-05 Page 4 of 9 ' E)#*($E8$a='%*";$3!)"R!%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7070348 R!BE3" General Potability RE !R"E# 2017-07-13

The following section displays the quality control (QC) data that is associated with your sample data. Groups of samples are prepared (9'mBa!:># n'a9?'a9a")D#?'(9':*9bA9:!(*9'@(!>'lC' a<="# '!>a!'#9 A%#')*A%'?a!a'( '*+'!>#'>($># !'EAa"(!)G'C*<<*9'lC'!)=# '(9:"A?#J o' >.6J4N$ ?21/b$ U?2bY: Laboratory reagent water is carried through sample preparation and analysis steps. Method Blanks indicate that results are free from contamination, i.e. not biased high from sources such as the sample container or the laboratory environment o' #LM2:916.$ U#LMY: Preparation and analysis of a replicate aliquot of a sample. Duplicates provide a measure of the analytical methodps precision, i.e. how reproducible a result is. Duplicates are only reported if they are associated with your sample data. o' ?21/b$ 16.0:12$ UY: A material of similar matrix to the samples, externally certified for the parameter(s) listed. Standard Reference Materials ensure that the preparation steps in the method are adequate to achieve acceptable recoveries of the parameter(s) tested.

Each QC type is analyzed at a 5-10% frequency, i.e. one blank/duplicate/spike for every 10 samples. For all types of QC, the specified recovery (% Rec) and relative percent difference (RPD) limits are derived from long-term method performance averages and/or prescribed by the reference method.

R% =/:67 c$RE3 c$R # )46.7$ %.I.2 R.7L26 %:5:6 %:5:6

9(,"(*/ E%+.$ EFAGHII

?21/b$U?V-WOSST?%,EY Prepared: 2017-07-07, Analyzed: 2017-07-07 Chloride < 0.10 0.10 mg/L Fluoride < 0.10 0.10 mg/L Nitrate (as N) < 0.010 0.010 mg/L Nitrite (as N) < 0.010 0.010 mg/L Sulfate < 1.0 1.0 mg/L ?21/b$U?V-WOSST?%,OY Prepared: 2017-07-07, Analyzed: 2017-07-07 Chloride < 0.10 0.10 mg/L Fluoride < 0.10 0.10 mg/L Nitrate (as N) < 0.010 0.010 mg/L Nitrite (as N) < 0.010 0.010 mg/L Sulfate < 1.0 1.0 mg/L %3<$U?V-WOSST?

A'('-%1 B%-%2'+'-*/ E%+.$ EFAGHFI

?21/b$U?V-WOVST?%,EY Prepared: 2017-07-06, Analyzed: 2017-07-06 Turbidity < 0.10 0.10 NTU

3'R!$'/12H6:912$<.0I:9.7 1D.$\$4F$G Rev 2017-01-05 Page 5 of 9 ' E)#*($E8$a='%*";$3!)"R!%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7070348 R!BE3" General Potability RE !R"E# 2017-07-13

R% =/:67 c$RE3 c$R # )46.7$ %.I.2 R.7L26 %:5:6 %:5:6

A'('-%1 B%-%2'+'-*/ E%+.$ EFAGHFI/ ="(+,(#';

%3<$U?V-WOVST?

A'('-%1 B%-%2'+'-*/ E%+.$ EFAGJHK

?21/b$U?V-WXO^T?%,EY Prepared: 2017-07-07, Analyzed: 2017-07-07 Cyanide, Total < 0.0020 0.0020 mg/L %3<$U?V-WXO^T?

A'('-%1 B%-%2'+'-*/ E%+.$ EFAGJLH

?21/b$U?V-WX\OT?%,EY Prepared: 2017-07-07, Analyzed: 2017-07-07 Colour, True < 5.0 5.0 CU %3<$U?V-WX\OT?

A'('-%1 B%-%2'+'-*/ E%+.$ EFAGMJH

?21/b$U?V-WRXOT?%,EY Prepared: 2017-07-09, Analyzed: 2017-07-09 Alkalinity, Total (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Phenolphthalein (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Bicarbonate (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Carbonate (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Hydroxide (as CaCO3) < 1.0 1.0 mg/L Conductivity (EC) < 2.0 2.0 µS/cm ?21/b$U?V-WRXOT?%,OY Prepared: 2017-07-09, Analyzed: 2017-07-09 Alkalinity, Total (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Phenolphthalein (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Bicarbonate (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Carbonate (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Hydroxide (as CaCO3) < 1.0 1.0 mg/L Conductivity (EC) < 2.0 2.0 µS/cm ?21/b$U?V-WRXOT?%,XY Prepared: 2017-07-09, Analyzed: 2017-07-09 Alkalinity, Total (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Phenolphthalein (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Bicarbonate (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Carbonate (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Hydroxide (as CaCO3) < 1.0 1.0 mg/L Conductivity (EC) < 2.0 2.0 µS/cm ?21/b$U?V-WRXOT?%,RY Prepared: 2017-07-09, Analyzed: 2017-07-09 Alkalinity, Total (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Phenolphthalein (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Bicarbonate (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Carbonate (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Hydroxide (as CaCO3) < 1.0 1.0 mg/L Conductivity (EC) < 2.0 2.0 µS/cm

3'R!$'/12H6:912$<.0I:9.7 1D.$^$4F$G Rev 2017-01-05 Page 6 of 9 ' E)#*($E8$a='%*";$3!)"R!%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7070348 R!BE3" General Potability RE !R"E# 2017-07-13

R% =/:67 c$RE3 c$R # )46.7$ %.I.2 R.7L26 %:5:6 %:5:6

A'('-%1 B%-%2'+'-*/ E%+.$ EFAGMJH/ ="(+,(#';

%3<$U?V-WRXOT?EY Prepared: 2017-07-09, Analyzed: 2017-07-09 pH 7.00 0.01 pH units 7.00 100 98-102 HT2 R.F.0./9.$U?V-WRXOTOY Prepared: 2017-07-09, Analyzed: 2017-07-09 pH 7.00 0.01 pH units 7.00 100 98-102 HT2 R.F.0./9.$U?V-WRXOTXY Prepared: 2017-07-09, Analyzed: 2017-07-09 pH 7.00 0.01 pH units 7.00 100 98-102 HT2 R.F.0./9.$U?V-WRXOTRY Prepared: 2017-07-09, Analyzed: 2017-07-09 pH 7.00 0.01 pH units 7.00 100 98-102 HT2

:,.-"?,"1"D,.%1 B%-%2'+'-*/ E%+.$ EFAGHJN

?21/b$U?V-WOXET?%,EY Prepared: 2017-07-06, Analyzed: 2017-07-06 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL ?21/b$U?V-WOXET?%,OY Prepared: 2017-07-06, Analyzed: 2017-07-06 Coliforms, Total < 1 1 CFU/100 mL ?21/b$U?V-WOXET?%,XY Prepared: 2017-07-06, Analyzed: 2017-07-06 E. coli < 1 1 CFU/100 mL

C"+%1 :'+%1*/ E%+.$ EFAGLMJ

?21/b$U?V-W\RXT?%,EY Prepared: 2017-07-11, Analyzed: 2017-07-11 Aluminum, total < 0.0050 0.0050 mg/L Antimony, total < 0.00010 0.00010 mg/L Arsenic, total < 0.00050 0.00050 mg/L Barium, total < 0.0050 0.0050 mg/L Boron, total < 0.0040 0.0050 mg/L Cadmium, total < 0.000010 0.000010 mg/L Calcium, total < 0.20 0.20 mg/L

3'R!$'/12H6:912$<.0I:9.7 1D.$V$4F$G Rev 2017-01-05 Page 7 of 9 ' E)#*($E8$a='%*";$3!)"R!%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7070348 R!BE3" General Potability RE !R"E# 2017-07-13

R% =/:67 c$RE3 c$R # )46.7$ %.I.2 R.7L26 %:5:6 %:5:6

C"+%1 :'+%1*/ E%+.$ EFAGLMJ/ ="(+,(#';

?21/b$U?V-W\RXT?%,EY_$34/6:/L.N Prepared: 2017-07-11, Analyzed: 2017-07-11 Chromium, total < 0.00050 0.00050 mg/L Cobalt, total < 0.00010 0.00010 mg/L Copper, total < 0.00020 0.00020 mg/L Iron, total < 0.010 0.010 mg/L Lead, total < 0.00010 0.00010 mg/L Magnesium, total < 0.010 0.010 mg/L Manganese, total < 0.00020 0.00020 mg/L Mercury, total < 0.000020 0.000020 mg/L Molybdenum, total < 0.00010 0.00010 mg/L Nickel, total < 0.00020 0.00020 mg/L Potassium, total < 0.10 0.10 mg/L Selenium, total < 0.00050 0.00050 mg/L Sodium, total < 0.10 0.10 mg/L Uranium, total < 0.000020 0.000020 mg/L Zinc, total < 0.0040 0.0040 mg/L %3<$U?V-W\RXT?EY Prepared: 2017-07-11, Analyzed: 2017-07-11 Aluminum, total 0.300 0.0050 mg/L 0.303 99 81-129 Antimony, total 0.0515 0.00010 mg/L 0.0511 101 88-114 Arsenic, total 0.120 0.00050 mg/L 0.118 101 88-114 Barium, total 0.764 0.0050 mg/L 0.823 93 72-104 Boron, total 3.55 0.0050 mg/L 3.45 103 75-121 Cadmium, total 0.0496 0.000010 mg/L 0.0495 100 89-111 Calcium, total 11.1 0.20 mg/L 11.6 96 86-121 Chromium, total 0.248 0.00050 mg/L 0.250 99 89-114 Cobalt, total 0.0389 0.00010 mg/L 0.0377 103 91-113 Copper, total 0.516 0.00020 mg/L 0.486 106 91-115 Iron, total 0.495 0.010 mg/L 0.488 101 77-124 Lead, total 0.207 0.00010 mg/L 0.204 101 92-113 Magnesium, total 3.86 0.010 mg/L 3.79 102 78-120 Manganese, total 0.107 0.00020 mg/L 0.109 98 90-114 Mercury, total 0.00564 0.000020 mg/L 0.00489 115 50-150 Molybdenum, total 0.193 0.00010 mg/L 0.198 97 90-111

3'R!$'/12H6:912$<.0I:9.7 1D.$S$4F$G Rev 2017-01-05 Page 8 of 9 ' E)#*($E8$a='%*";$3!)"R!%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7070348 R!BE3" General Potability RE !R"E# 2017-07-13

R% =/:67 c$RE3 c$R # )46.7$ %.I.2 R.7L26 %:5:6 %:5:6

C"+%1 :'+%1*/ E%+.$ EFAGLMJ/ ="(+,(#';

R.F.0./9.$U?V-W\RXTEY_$34/6:/L.N Prepared: 2017-07-11, Analyzed: 2017-07-11 Nickel, total 0.256 0.00020 mg/L 0.249 103 90-111 Potassium, total 7.29 0.10 mg/L 7.21 101 84-113 Selenium, total 0.133 0.00050 mg/L 0.121 110 85-115 Sodium, total 7.60 0.10 mg/L 7.54 101 82-123 Uranium, total 0.0306 0.000020 mg/L 0.0306 100 85-120 Zinc, total 2.56 0.0040 mg/L 2.49 103 85-111

a3$aL12:F:.078 HT2 The 15 minute recommended holding time (from sampling to analysis) has been exceeded - field analysis is recommended.

3'R!$'/12H6:912$<.0I:9.7 1D.$G$4F$G Rev 2017-01-05 Page 9 of 9 3ER"*&*3'"E$!&$')'%;<*<

RE !R"E#$"! Castlegar, City of 460 Columbia Avenue "E% (250) 365-5979 CASTLEGAR, BC V1N 1G7 &'( (250) 365-0594

'""E)"*!) Chris Barlow +!R,$!R#ER 7070350

!$)=>?ER 502 RE3E*@E#$A$"E> 2017-07-06 09:00 / 16°C R!BE3" THM & HAA RE !R"E# 2017-07-13 R!BE3"$*)&! 3!3$)=>?ER No Number

-./.012$3455./678

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: ,0:76:/$>9,.4C/ Account Manager

If !"# $%&' %(! )#'*+,"(* "- ."(.'-(*/ 01'%*' ."(+%.+ 2' %+ 32.3'"4(5.%-"6.%

%4916:4/78 #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

3'R!$'/12H6:912$<.0I:9.7 1D.$E$4F$G Rev 2017-01-05 Page 1 of 3 ')'%;<*<$*)&!R>'"*!)

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7070350 R!BE3" THM & HAA RE !R"E# 2017-07-13

'/12H7:7$#.790:M6:4/ >.6J4N$R.F.0./9. ".9J/:KL. %4916:4/

Haloacetic Acids in Water EPA 552.3* Liquid-Liquid Microextraction, Derivatization and Richmond GC-ECD Trihalomethanes in Water EPA 5030B / APHA Purge&Trap / Purge and Trap Capillary Column Richmond 6200 B GC-MSD 7"+'8 9( %*+'-,*3 ,( +$' :'+$"; <'f'-'(.' ,(;,.%+'* +$%+ +$' =9<> 2'+$"; $%* ?''( 2";,f,'; f-"2 +$' -'f'-'(.' 2'+$";

>.6J4N$R.F.0./9.$#.790:M6:4/78 EPA United States Environmental Protection Agency Test Methods

-247710H$4F$".0578 MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) mg/L Milligrams per litre

<61/N10N7$A$-L:N.2:/.7$R.F.0./9.N$:/$6J:7$R.M4068 Guidelines for Canadian Drinking Water Quality (Feb 2017) Website: http://www.hc-sc.gc.ca/ewh-semt/alt_formats/pdf/pubs/water-eau/sum_guide-res_recom/sum_guide-res_recom-e ng.pdf 7"+'8 I( *"2' .%*'*/ +$' &%1#'* ;,*01%!'; "( +$' -'0"-+ -'0-'*'(+ +$' 1"4'*+ @#,;'1,(' %(; %-' +" ?' &'-,f,'; ?! +$' '(; #*'-

3'R!$'/12H6:912$<.0I:9.7 1D.$O$4F$G Rev 2017-01-05 Page 2 of 3 <'> %E$')'%;"*3'%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7070350 R!BE3" THM & HAA RE !R"E# 2017-07-13

$'/12H6. R.7L26$A$ <61/N10N$A$ >R%$A$ =/:67 0.M10.N '/12HP.N )46.7 <'."&'-! -L:N.2:/. A,2,+*$

<15M2.$*#8$+"Q$RS#E$T$?2L.U.00H$$VWSWSGXSTSEY$$Z+16.0[$$<15M2.N8$OSEWTSWTSX$SW8\S

=%1.#1%+'; B%-%2'+'-* Total Trihalomethanes S]SGSG MAC = 0.1 0.00400 mg/L N/A N/A

C"1%+,1' >-@%(,. ="20"#(;* DC>=E Bromodichloromethane < 0.0010 N/A 0.0010 mg/L 2017-07-07 2017-07-07 Bromoform < 0.0010 N/A 0.0010 mg/L 2017-07-07 2017-07-07 Chloroform S]SGSG N/A 0.0010 mg/L 2017-07-07 2017-07-07 Dibromochloromethane < 0.0010 N/A 0.0010 mg/L 2017-07-07 2017-07-07 $%&&'()*+,-.'/%+0+"12 00 !0" #0 % 20 !"0!"0! 20 !"0!"0! $%&&'()*+,-5"6&'7'8/%'&'9+0:+0+ 34 !0" #0 % 20 !"0!"0! 20 !"0!"0!

<15M2.$*#8$+"Q$ORSOS$T$':0M406$$VWSWSGXSTSOY$$Z+16.0[$$<15M2.N8$OSEWTSWTSX$EE8OX

=%1.#1%+'; B%-%2'+'-* Total Trihalomethanes S]SGG^ MAC = 0.1 0.00400 mg/L N/A N/A

C"1%+,1' >-@%(,. ="20"#(;* DC>=E Bromodichloromethane < 0.0010 N/A 0.0010 mg/L 2017-07-07 2017-07-07 Bromoform < 0.0010 N/A 0.0010 mg/L 2017-07-07 2017-07-07 Chloroform S]SGG^ N/A 0.0010 mg/L 2017-07-07 2017-07-07 Dibromochloromethane < 0.0010 N/A 0.0010 mg/L 2017-07-07 2017-07-07 $%&&'()*+,-.'/%+0+"12 32 !0" #0 % 20 !"0!"0! 20 !"0!"0! $%&&'()*+,-5"6&'7'8/%'&'9+0:+0+ 35 !0" #0 % 20 !"0!"0! 20 !"0!"0!

<15M2.$*#8$+"Q$\_\R$T$ 10`$ L5MJ4L7.$$VWSWSGXSTSGY$$Z+16.0[$$<15M2.N8$OSEWTSWTSX$S_8SS

=%1.#1%+'; B%-%2'+'-* Total Haloacetic Acids (HAA5) S]SOSO MAC = 0.08 0.00200 mg/L N/A N/A

F%1"%.'+,. 9.,;* Monochloroacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-07-07 2017-07-09 Monobromoacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-07-07 2017-07-09 Dichloroacetic Acid S]SS_S N/A 0.0020 mg/L 2017-07-07 2017-07-09 Trichloroacetic Acid S]SEOO N/A 0.0020 mg/L 2017-07-07 2017-07-09 Dibromoacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-07-07 2017-07-09 $%&&'()*+,-2"6&'7';&';<'0<=->=<1 20 !0" #0 % 20 !"0!"0! 20 !"0!"03

3'R!$'/12H6:912$<.0I:9.7 1D.$G$4F$G Rev 2017-01-05 Page 3 of 3 3ER"*&*3'"E$!&$')'%;<*<

RE !R"E#$"! Castlegar, City of 460 Columbia Avenue "E% (250) 365-5979 CASTLEGAR, BC V1N 1G7 &'( (250) 365-0594

'""E)"*!) Chris Barlow +!R,$!R#ER 7091612

!$)=>?ER 502 RE3E*@E#$A$"E> 2017-09-19 09:30 / 14°C R!BE3" Water Treatment Centre RE !R"E# 2017-09-26 R!BE3"$*)&! 2-1-SR 3!3$)=>?ER no number

-./.012$3455./678

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: ,0:76:/$>9,.4C/ Account Manager

If !"# $%&' %(! )#'*+,"(* "- ."(.'-(*/ 01'%*' ."(+%.+ 2' %+ 32.3'"4(5.%-"6.%

%4916:4/78 #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

3'R!$'/12H6:912$<.0I:9.7 1D.$E$4F$G Rev 2017-01-05 Page 1 of 3 ')'%;<*<$*)&!R>'"*!)

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7091612 R!BE3" Water Treatment Centre RE !R"E# 2017-09-26

'/12H7:7$#.790:M6:4/ >.6J4N$R.F.0./9. ".9J/:KL. %4916:4/

Chlorophyll-A in Water APHA 10200 H Spectrophotometry Kelowna

>.6J4N$R.F.0./9.$#.790:M6:4/78 APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health Association/American Water Works Association/Water Environment Federation

-247710H$4F$".0578 MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) µg/L Micrograms per litre

<61/N10N7$A$-L:N.2:/.7$R.F.0./9.N$:/$6J:7$R.M4068 Guidelines for Canadian Drinking Water Quality (Feb 2017) Website: http://www.hc-sc.gc.ca/ewh-semt/alt_formats/pdf/pubs/water-eau/sum_guide-res_recom/sum_guide-res_recom-e ng.pdf 7"+'8 I( *"2' .%*'*/ +$' &%1#'* 9,*01%!'9 "( +$' -'0"-+ -'0-'*'(+ +$' 1"4'*+ :#,9'1,(' %(9 %-' +" ;' &'-,f,'9 ;! +$' '(9 #*'-

3'R!$'/12H6:912$<.0I:9.7 1D.$O$4F$G Rev 2017-01-05 Page 2 of 3 <'> %E$')'%;"*3'%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7091612 R!BE3" Water Treatment Centre RE !R"E# 2017-09-26

$'/12H6. R.7L26$A$ <61/N10N$A$ >R%$A$ =/:67 0.M10.N '/12HP.N )46.7 <'."&'-! -L:N.2:/. =,2,+*$

<15M2.$*#8$+"Q$RSEE$T$+"3$T$R1C$+16.0$$UVWXEYEOTWEZ$$[+16.0\$$<15M2.N8$OWEVTWXTES$EE8WW

>'('-%1 ?%-%2'+'-* Chlorophyll a W]XV N/A 0.10 µg/L 2017-09-19 2017-09-25

3'R!$'/12H6:912$<.0I:9.7 1D.$G$4F$G Rev 2017-01-05 Page 3 of 3 3ER"*&*3'"E$!&$')'%;<*<

RE !R"E#$"! Castlegar, City of 460 Columbia Avenue "E% (250) 365-5979 CASTLEGAR, BC V1N 1G7 &'( (250) 365-0594

'""E)"*!) Chris Barlow +!R,$!R#ER 7092522

!$)=>?ER 502 RE3E*@E#$A$"E> 2017-09-26 08:00 / 8°C R!BE3" Water Treatment Centre RE !R"E# 2017-10-02 R!BE3"$*)&! 2-1-SR 3!3$)=>?ER No Number

-./.012$3455./678

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: ,0:76:/$>9,.4C/ Account Manager

If !"# $%&' %(! )#'*+,"(* "- ."(.'-(*/ 01'%*' ."(+%.+ 2' %+ 32.3'"4(5.%-"6.%

%4916:4/78 #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

3'R!$'/12H6:912$<.0I:9.7 1D.$E$4F$G Rev 2017-01-05 Page 1 of 3 ')'%;<*<$*)&!R>'"*!)

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7092522 R!BE3" Water Treatment Centre RE !R"E# 2017-10-02

'/12H7:7$#.790:M6:4/ >.6J4N$R.F.0./9. ".9J/:KL. %4916:4/

Chlorophyll-A in Water APHA 10200 H Spectrophotometry Kelowna

>.6J4N$R.F.0./9.$#.790:M6:4/78 APHA Standard Methods for the Examination of Water and Wastewater, 22nd Edition, American Public Health Association/American Water Works Association/Water Environment Federation

-247710H$4F$".0578 MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) µg/L Micrograms per litre

<61/N10N7$A$-L:N.2:/.7$R.F.0./9.N$:/$6J:7$R.M4068 Guidelines for Canadian Drinking Water Quality (Feb 2017) Website: http://www.hc-sc.gc.ca/ewh-semt/alt_formats/pdf/pubs/water-eau/sum_guide-res_recom/sum_guide-res_recom-e ng.pdf 7"+'8 I( *"2' .%*'*/ +$' &%1#'* 9,*01%!'9 "( +$' -'0"-+ -'0-'*'(+ +$' 1"4'*+ :#,9'1,(' %(9 %-' +" ;' &'-,f,'9 ;! +$' '(9 #*'-

3'R!$'/12H6:912$<.0I:9.7 1D.$O$4F$G Rev 2017-01-05 Page 2 of 3 <'> %E$')'%;"*3'%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7092522 R!BE3" Water Treatment Centre RE !R"E# 2017-10-02

$'/12H6. R.7L26$A$ <61/N10N$A$ >R%$A$ =/:67 0.M10.N '/12HP.N )46.7 <'."&'-! -L:N.2:/. =,2,+*$

<15M2.$*#8$+"Q$RSEE$T$+"3$T$R1C$+16.0$$UVWXOYOOTWEZ$$[+16.0\$$<15M2.N8$OWEVTWXTOY$WX8GW

>'('-%1 ?%-%2'+'-* Chlorophyll a E]EE N/A 0.10 µg/L 2017-09-26 2017-09-28

3'R!$'/12H6:912$<.0I:9.7 1D.$G$4F$G Rev 2017-01-05 Page 3 of 3 3ER"*&*3'"E$!&$')'%;<*<

RE !R"E#$"! Castlegar, City of 460 Columbia Avenue "E% 1-250-365-9482 CASTLEGAR, BC V1N 1G7 &'( (250) 365-0594

'""E)"*!) Jesse Reel +!R,$!R#ER 7100128

!$)=>?ER 502 RE3E*@E#$A$"E> 2017-10-03 09:30 / 9°C R!BE3" General Potability RE !R"E# 2017-10-11 R!BE3"$*)&! 3!3$)=>?ER no number

-./.012$3455./678

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: ,0:76:/$>9,.4C/ Account Manager

If !"# $%&' %(! )#'*+,"(* "- ."(.'-(*/ 01'%*' ."(+%.+ 2' %+ 32.3'"4(5.%-"6.%

%4916:4/78 #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

3'R!$'/12H6:912$<.0I:9.7 1D.$E$4F$G Rev 2017-01-05 Page 1 of 8 ')'%;<*<$*)&!R>'"*!)

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7100128 R!BE3" General Potability RE !R"E# 2017-10-11

'/12H7:7$#.790:M6:4/ >.6J4N$R.F.0./9. ".9J/:KL. %4916:4/

Alkalinity in Water SM 2320 B* (2011) Titration with H2SO4 Kelowna Anions by IC in Water SM 4110 B (2011) Ion Chromatography with Chemical Suppression of Kelowna Eluent Conductivity Coliforms, Total (MF-Endo) in Water SM 9222 B (2006) Membrane Filtration / Incubation on m-Endo Agar Kelowna Colour, True in Water SM 2120 C (2011) Spectrophotometry (456 nm) Kelowna Conductivity in Water SM 2510 B (2011) Conductivity Meter Kelowna Cyanide, SAD in Water ASTM D7511-12 Flow Injection Analysis with In-Line Ultraviolet Kelowna Digestion and Amperometric Detection E. coli (MF-NA+MUG) in Water SM 9222 G (2006) Membrane Filtration / Nutrient Agar with MUG Kelowna Hardness (as CaCO3) in Water SM 2340 B* (2011) Calculation: 2.497 [total Ca] + 4.118 [total Mg] N/A (Estimated) Langelier Index in Water SM 2330 B (2010) Calculation N/A Mercury, total by CVAFS in Water EPA 245.7* BrCl2 Oxidation / Cold Vapor Atomic Fluorescence Richmond Spectrometry (CVAFS) pH in Water SM 4500-H+ B (2011) Electrometry Kelowna Solids, Total Dissolved (calc) in SM 1030 E (2011) Calculation: 100 x ([Cations]-[Anions])/ N/A Water ([Cations]+[Anions]) Temperature (lab) in Water SM 2550 B (2010) Thermometer Kelowna Total Metals by ICPMS in Water APHA 3030 E* / EPA HNO3+HCl Hot Block Digestion / Inductively Coupled Richmond 6020B Plasma-Mass Spectroscopy (ICP-MS) Turbidity in Water SM 2130 B (2011) Nephelometry Kelowna

7"+'8 9( %*+'-,*3 ,( +$' :'+$"; <'f'-'(.' ,(;,.%+'* +$%+ +$' =9<> 2'+$"; $%* ?''( 2";,f,'; f-"2 +$' -'f'-'(.' 2'+$";

>.6J4N$R.F.0./9.$#.790:M6:4/78 ASTM ASTM International Test Methods EPA United States Environmental Protection Agency Test Methods

-247710H$4F$".0578 MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) °C Degrees Celcius CFU/100 mL Colony Forming Units per 100 millilitres CU Colour Units (referenced against a platinum cobalt standard) mg/L Milligrams per litre NTU Nephelometric Turbidity Units pH units pH < 7 = acidic, ph > 7 = basic µS/cm Microsiemens per centimetre

3'R!$'/12H6:912$<.0I:9.7 1D.$O$4F$G Rev 2017-01-05 Page 2 of 8 <'> %E$')'%;"*3'%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7100128 R!BE3" General Potability RE !R"E# 2017-10-11

$'/12H6. R.7L26$A$ >R%$A$ =/:67 0.M10.N '/12HP.N )46.7 <'."&'-! @,2,+*$

<15M2.$*#8$+"Q$RGEE$S$+"3$S$R1C$+16.0$$TUEVVEOGSVEW$$X+16.0Y$$<15M2.N8$OVEUSEVSVO$VZ8[\

9(,"(* Chloride V]RE 0.10 mg/L N/A 2017-10-03 Fluoride < 0.10 0.10 mg/L N/A 2017-10-03 Nitrate (as N) V]VZE 0.010 mg/L N/A 2017-10-03 Nitrite (as N) < 0.010 0.010 mg/L N/A 2017-10-03 Sulfate EV]O 1.0 mg/L N/A 2017-10-03

A'('-%1 B%-%2'+'-* Alkalinity, Total (as CaCO3) \R][ 1.0 mg/L N/A 2017-10-05 Alkalinity, Phenolphthalein (as CaCO3) < 1.0 1.0 mg/L N/A 2017-10-05 Alkalinity, Bicarbonate (as CaCO3) \R][ 1.0 mg/L N/A 2017-10-05 Alkalinity, Carbonate (as CaCO3) < 1.0 1.0 mg/L N/A 2017-10-05 Alkalinity, Hydroxide (as CaCO3) < 1.0 1.0 mg/L N/A 2017-10-05 Colour, True < 5.0 5.0 CU N/A 2017-10-05 Conductivity (EC) EER 2.0 µS/cm N/A 2017-10-05 Cyanide, Total < 0.0020 0.0020 mg/L N/A 2017-10-04 pH U]O^ 0.10 pH units N/A 2017-10-05 HT2 Temperature, at pH OE °C N/A 2017-10-05 HT2 Turbidity V]RZ 0.10 NTU N/A 2017-10-03

=%1.#1%+'; B%-%2'+'-* Hardness, Total (as CaCO3) \U]U 0.500 mg/L N/A N/A Langelier Index SE]O -5.0 - N/A 2017-10-11 Solids, Total Dissolved (calc) ^^]E 1.00 mg/L N/A N/A

C"+%1 :'+%1* Aluminum, total V]VEGV 0.0050 mg/L 2017-10-05 2017-10-06 Antimony, total < 0.00020 0.00020 mg/L 2017-10-05 2017-10-06 Arsenic, total < 0.00050 0.00050 mg/L 2017-10-05 2017-10-06 Barium, total V]VE[G 0.0050 mg/L 2017-10-05 2017-10-06 Boron, total V]VVUV 0.0050 mg/L 2017-10-05 2017-10-06 Cadmium, total < 0.000010 0.000010 mg/L 2017-10-05 2017-10-06 Calcium, total E^]U 0.20 mg/L 2017-10-05 2017-10-06 Chromium, total < 0.00050 0.00050 mg/L 2017-10-05 2017-10-06 Cobalt, total < 0.00010 0.00010 mg/L 2017-10-05 2017-10-06 Copper, total V]VEUR 0.00040 mg/L 2017-10-05 2017-10-06 Iron, total V]VE[ 0.010 mg/L 2017-10-05 2017-10-06 Lead, total V]VVV\^ 0.00020 mg/L 2017-10-05 2017-10-06 Magnesium, total []GU 0.010 mg/L 2017-10-05 2017-10-06 Manganese, total V]VVE[^ 0.00020 mg/L 2017-10-05 2017-10-06 Mercury, total < 0.000010 0.000010 mg/L 2017-10-10 2017-10-11 Molybdenum, total V]VVVRZ 0.00010 mg/L 2017-10-05 2017-10-06 Nickel, total V]VVV\G 0.00040 mg/L 2017-10-05 2017-10-06 Potassium, total V]^[ 0.10 mg/L 2017-10-05 2017-10-06 Selenium, total < 0.00050 0.00050 mg/L 2017-10-05 2017-10-06 Sodium, total V]U^ 0.10 mg/L 2017-10-05 2017-10-06 Uranium, total V]VVV[\G 0.000020 mg/L 2017-10-05 2017-10-06 Zinc, total < 0.0040 0.0040 mg/L 2017-10-05 2017-10-06

3'R!$'/12H6:912$<.0I:9.7 1D.$[$4F$G Rev 2017-01-05 Page 3 of 8 <'> %E$')'%;"*3'%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7100128 R!BE3" General Potability RE !R"E# 2017-10-11

$'/12H6. R.7L26$A$ >R%$A$ =/:67 0.M10.N '/12HP.N )46.7 <'."&'-! @,2,+*$

<15M2.$*#8$+"Q$RGEE$S$+"3$S$R1C$+16.0$$TUEVVEOGSVEW$$X+16.0Y$$<15M2.N8$OVEUSEVSVO$VZ8[\_$34/6:/L.N

:,.-"?,"1"D,.%1 B%-%2'+'-* Coliforms, Total [ 1 CFU/100 mL N/A 2017-10-03 Background Colonies `$OVV 200 CFU/100 mL N/A 2017-10-03 E. coli E 1 CFU/100 mL N/A 2017-10-03

<15M2.$A$'/12H7:7$aL12:F:.078 HT2 The 15 minute recommended holding time (from sampling to analysis) has been exceeded - field analysis is recommended.

3'R!$'/12H6:912$<.0I:9.7 1D.$R$4F$G Rev 2017-01-05 Page 4 of 8 ' E)#*($E8$a='%*";$3!)"R!%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7100128 R!BE3" General Potability RE !R"E# 2017-10-11

The following section displays the quality control (QC) data that is associated with your sample data. Groups of samples are prepared (9'mBa!:># n'a9?'a9a")D#?'(9':*9bA9:!(*9'@(!>'lC' a<="# '!>a!'#9 A%#')*A%'?a!a'( '*+'!>#'>($># !'EAa"(!)G'C*<<*9'lC'!)=# '(9:"A?#J o' >.6J4N$ ?21/b$ T?2bW: Laboratory reagent water is carried through sample preparation and analysis steps. Method Blanks indicate that results are free from contamination, i.e. not biased high from sources such as the sample container or the laboratory environment o' #LM2:916.$ T#LMW: Preparation and analysis of a replicate aliquot of a sample. Duplicates provide a measure of the analytical methodps precision, i.e. how reproducible a result is. Duplicates are only reported if they are associated with your sample data. o' ?21/b$ 16.0:12$ TW: A material of similar matrix to the samples, externally certified for the parameter(s) listed. Standard Reference Materials ensure that the preparation steps in the method are adequate to achieve acceptable recoveries of the parameter(s) tested.

Each QC type is analyzed at a 5-10% frequency, i.e. one blank/duplicate/spike for every 10 samples. For all types of QC, the specified recovery (% Rec) and relative percent difference (RPD) limits are derived from long-term method performance averages and/or prescribed by the reference method.

R% =/:67 c$RE3 c$R # )46.7$ %.I.2 R.7L26 %:5:6 %:5:6

9(,"(*/ E%+.$ EFGHIJK

?21/b$T?UBVEGRS?%,EW Prepared: 2017-10-03, Analyzed: 2017-10-03 Chloride < 0.10 0.10 mg/L Fluoride < 0.10 0.10 mg/L Nitrate (as N) < 0.010 0.010 mg/L Nitrite (as N) < 0.010 0.010 mg/L Sulfate < 1.0 1.0 mg/L %3<$T?UBVEGRS?

A'('-%1 B%-%2'+'-*/ E%+.$ EFGHHJL

?21/b$T?UBVVGOS?%,EW Prepared: 2017-10-03, Analyzed: 2017-10-03 Turbidity < 0.10 0.10 NTU %3<$T?UBVVGOS?

A'('-%1 B%-%2'+'-*/ E%+.$ EFGHLKM

?21/b$T?UBVORZS?%,EW Prepared: 2017-10-04, Analyzed: 2017-10-04 Cyanide, Total < 0.0020 0.0020 mg/L ?21/b$T?UBVORZS?%,OW Prepared: 2017-10-04, Analyzed: 2017-10-04 Cyanide, Total < 0.0020 0.0020 mg/L %3<$T?UBVORZS?

3'R!$'/12H6:912$<.0I:9.7 1D.$\$4F$G Rev 2017-01-05 Page 5 of 8 ' E)#*($E8$a='%*";$3!)"R!%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7100128 R!BE3" General Potability RE !R"E# 2017-10-11

R% =/:67 c$RE3 c$R # )46.7$ %.I.2 R.7L26 %:5:6 %:5:6

A'('-%1 B%-%2'+'-*/ E%+.$ EFGHLKM/ ="(+,(#';

%3<$T?UBVORZS?

A'('-%1 B%-%2'+'-*/ E%+.$ EFGHNKN

?21/b$T?UBV[R[S?%,EW Prepared: 2017-10-05, Analyzed: 2017-10-05 Alkalinity, Total (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Phenolphthalein (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Bicarbonate (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Carbonate (as CaCO3) < 1.0 1.0 mg/L Alkalinity, Hydroxide (as CaCO3) < 1.0 1.0 mg/L Conductivity (EC) < 2.0 2.0 µS/cm %3<$T?UBV[R[S?EW Prepared: 2017-10-05, Analyzed: 2017-10-05 pH 6.99 0.10 pH units 7.00 100 98-102 HT2

A'('-%1 B%-%2'+'-*/ E%+.$ EFGHNOO

?21/b$T?UBV[^^S?%,EW Prepared: 2017-10-05, Analyzed: 2017-10-05 Colour, True < 5.0 5.0 CU %3<$T?UBV[^^S?

:,.-"?,"1"D,.%1 B%-%2'+'-*/ E%+.$ EFGHINM

?21/b$T?UBVE[ZS?%,EW Prepared: 2017-10-03, Analyzed: 2017-10-03 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL ?21/b$T?UBVE[ZS?%,OW Prepared: 2017-10-03, Analyzed: 2017-10-03 E. coli < 1 1 CFU/100 mL ?21/b$T?UBVE[ZS?%,[W Prepared: 2017-10-03, Analyzed: 2017-10-03 E. coli < 1 1 CFU/100 mL ?21/b$T?UBVE[ZS?%,RW Prepared: 2017-10-03, Analyzed: 2017-10-03 Coliforms, Total < 1 1 CFU/100 mL E. coli < 1 1 CFU/100 mL

C"+%1 :'+%1*/ E%+.$ EFGHKKK

?21/b$T?UBVRRRS?%,EW Prepared: 2017-10-05, Analyzed: 2017-10-06 Aluminum, total < 0.0050 0.0050 mg/L Antimony, total < 0.00020 0.00020 mg/L

3'R!$'/12H6:912$<.0I:9.7 1D.$^$4F$G Rev 2017-01-05 Page 6 of 8 ' E)#*($E8$a='%*";$3!)"R!%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7100128 R!BE3" General Potability RE !R"E# 2017-10-11

R% =/:67 c$RE3 c$R # )46.7$ %.I.2 R.7L26 %:5:6 %:5:6

C"+%1 :'+%1*/ E%+.$ EFGHKKK/ ="(+,(#';

?21/b$T?UBVRRRS?%,EW_$34/6:/L.N Prepared: 2017-10-05, Analyzed: 2017-10-06 Arsenic, total < 0.00050 0.00050 mg/L Barium, total < 0.0050 0.0050 mg/L Boron, total < 0.0050 0.0050 mg/L Cadmium, total < 0.000010 0.000010 mg/L Calcium, total < 0.20 0.20 mg/L Chromium, total < 0.00050 0.00050 mg/L Cobalt, total < 0.00010 0.00010 mg/L Copper, total < 0.00040 0.00040 mg/L Iron, total < 0.010 0.010 mg/L Lead, total < 0.00020 0.00020 mg/L Magnesium, total < 0.010 0.010 mg/L Manganese, total < 0.00020 0.00020 mg/L Molybdenum, total < 0.00010 0.00010 mg/L Nickel, total < 0.00040 0.00040 mg/L Potassium, total < 0.10 0.10 mg/L Selenium, total < 0.00050 0.00050 mg/L Sodium, total < 0.10 0.10 mg/L Uranium, total < 0.000020 0.000020 mg/L Zinc, total < 0.0040 0.0040 mg/L %3<$T?UBVRRRS?EW Prepared: 2017-10-05, Analyzed: 2017-10-06 Aluminum, total 0.287 0.0050 mg/L 0.303 95 82-114 Antimony, total 0.0489 0.00020 mg/L 0.0511 96 88-115 Arsenic, total 0.112 0.00050 mg/L 0.118 95 88-111 Barium, total 0.742 0.0050 mg/L 0.823 90 83-110 Boron, total 3.44 0.0050 mg/L 3.45 100 80-118 Cadmium, total 0.0478 0.000010 mg/L 0.0495 96 90-110 Calcium, total 11.7 0.20 mg/L 11.6 101 85-113 Chromium, total 0.237 0.00050 mg/L 0.250 95 88-111 Cobalt, total 0.0369 0.00010 mg/L 0.0377 98 90-114 Copper, total 0.478 0.00040 mg/L 0.486 98 90-117 Iron, total 0.508 0.010 mg/L 0.488 104 90-116 Lead, total 0.193 0.00020 mg/L 0.204 95 90-110 Magnesium, total 4.11 0.010 mg/L 3.79 108 88-116

3'R!$'/12H6:912$<.0I:9.7 1D.$U$4F$G Rev 2017-01-05 Page 7 of 8 ' E)#*($E8$a='%*";$3!)"R!%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7100128 R!BE3" General Potability RE !R"E# 2017-10-11

R% =/:67 c$RE3 c$R # )46.7$ %.I.2 R.7L26 %:5:6 %:5:6

C"+%1 :'+%1*/ E%+.$ EFGHKKK/ ="(+,(#';

R.F.0./9.$T?UBVRRRSEW_$34/6:/L.N Prepared: 2017-10-05, Analyzed: 2017-10-06 Manganese, total 0.106 0.00020 mg/L 0.109 97 88-108 Molybdenum, total 0.192 0.00010 mg/L 0.198 97 88-110 Nickel, total 0.240 0.00040 mg/L 0.249 96 90-112 Potassium, total 7.73 0.10 mg/L 7.21 107 87-116 Selenium, total 0.122 0.00050 mg/L 0.121 101 90-122 Sodium, total 8.04 0.10 mg/L 7.54 107 86-118 Uranium, total 0.0291 0.000020 mg/L 0.0306 95 88-112 Zinc, total 2.42 0.0040 mg/L 2.49 97 90-113

C"+%1 :'+%1*/ E%+.$ EFGHOFN

?21/b$T?UBV^U[S?%,EW Prepared: 2017-10-10, Analyzed: 2017-10-11 Mercury, total < 0.000010 0.000010 mg/L ?21/b$T?UBV^U[S?%,OW Prepared: 2017-10-10, Analyzed: 2017-10-11 Mercury, total < 0.000010 0.000010 mg/L >160:d$EW Prepared: 2017-10-10, Analyzed: 2017-10-11 Mercury, total 0.00473 0.000010 mg/L 0.00489 97 80-120 R.F.0./9.$T?UBV^U[SOW Prepared: 2017-10-10, Analyzed: 2017-10-11 Mercury, total 0.00462 0.000010 mg/L 0.00489 94 80-120

a3$aL12:F:.078 HT2 The 15 minute recommended holding time (from sampling to analysis) has been exceeded - field analysis is recommended.

3'R!$'/12H6:912$<.0I:9.7 1D.$G$4F$G Rev 2017-01-05 Page 8 of 8 3ER"*&*3'"E$!&$')'%;<*<

RE !R"E#$"! Castlegar, City of 460 Columbia Avenue "E% (250) 365-5979 CASTLEGAR, BC V1N 1G7 &'( (250) 365-0594

'""E)"*!) Chris Barlow +!R,$!R#ER 7100132

!$)=>?ER 502 RE3E*@E#$A$"E> 2017-10-03 09:30 / 9°C R!BE3" THM & HAA RE !R"E# 2017-10-11 R!BE3"$*)&! 3!3$)=>?ER no number

-./.012$3455./678

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: ,0:76:/$>9,.4C/ Account Manager

If !"# $%&' %(! )#'*+,"(* "- ."(.'-(*/ 01'%*' ."(+%.+ 2' %+ 32.3'"4(5.%-"6.%

%4916:4/78 #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

3'R!$'/12H6:912$<.0I:9.7 1D.$E$4F$G Rev 2017-01-05 Page 1 of 3 ')'%;<*<$*)&!R>'"*!)

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7100132 R!BE3" THM & HAA RE !R"E# 2017-10-11

'/12H7:7$#.790:M6:4/ >.6J4N$R.F.0./9. ".9J/:KL. %4916:4/

Haloacetic Acids in Water EPA 552.3* Liquid-Liquid Microextraction, Derivatization and Richmond GC-ECD Trihalomethanes in Water EPA 5030B / SM 6200 Purge&Trap / Purge and Trap Capillary Column Richmond B (2011) GC-MSD 7"+'8 9( %*+'-,*3 ,( +$' :'+$"; <'f'-'(.' ,(;,.%+'* +$%+ +$' =9<> 2'+$"; $%* ?''( 2";,f,'; f-"2 +$' -'f'-'(.' 2'+$";

>.6J4N$R.F.0./9.$#.790:M6:4/78 EPA United States Environmental Protection Agency Test Methods

-247710H$4F$".0578 MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) mg/L Milligrams per litre

<61/N10N7$A$-L:N.2:/.7$R.F.0./9.N$:/$6J:7$R.M4068 Guidelines for Canadian Drinking Water Quality (Feb 2017) Website: http://www.hc-sc.gc.ca/ewh-semt/alt_formats/pdf/pubs/water-eau/sum_guide-res_recom/sum_guide-res_recom-e ng.pdf 7"+'8 I( *"2' .%*'*/ +$' &%1#'* ;,*01%!'; "( +$' -'0"-+ -'0-'*'(+ +$' 1"4'*+ @#,;'1,(' %(; %-' +" ?' &'-,f,'; ?! +$' '(; #*'-

3'R!$'/12H6:912$<.0I:9.7 1D.$O$4F$G Rev 2017-01-05 Page 2 of 3 <'> %E$')'%;"*3'%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7100132 R!BE3" THM & HAA RE !R"E# 2017-10-11

$'/12H6. R.7L26$A$ <61/N10N$A$ >R%$A$ =/:67 0.M10.N '/12HP.N )46.7 <'."&'-! -L:N.2:/. A,2,+*$

<15M2.$*#8$+"Q$RS#E$T$?2L.U.00H$$VWESSEGOTSEX$$Y+16.0Z$$<15M2.N8$OSEWTESTSO$S[8OS

=%1.#1%+'; B%-%2'+'-* Total Trihalomethanes S\SGGW MAC = 0.1 0.00400 mg/L N/A N/A

C"1%+,1' >-@%(,. ="20"#(;* DC>=E Bromodichloromethane < 0.0010 N/A 0.0010 mg/L N/A 2017-10-10 Bromoform < 0.0010 N/A 0.0010 mg/L N/A 2017-10-10 Chloroform S\SGGW N/A 0.0010 mg/L N/A 2017-10-10 Dibromochloromethane < 0.0010 N/A 0.0010 mg/L N/A 2017-10-10 $%&&'()*+,-.'/%+0+"12 0 !0" #0 % 345 20 !" 0" 0 $%&&'()*+,-6"7&'8'9/%'&':+0;+0+ 02 !0" #0 % 345 20 !" 0" 0

<15M2.$*#8$+"Q$ORSOS$T$':0M406$$VWESSEGOTSOX$$Y+16.0Z$$<15M2.N8$OSEWTESTSO$ES8GW

=%1.#1%+'; B%-%2'+'-* Total Trihalomethanes S\SG]O MAC = 0.1 0.00400 mg/L N/A N/A

C"1%+,1' >-@%(,. ="20"#(;* DC>=E Bromodichloromethane < 0.0010 N/A 0.0010 mg/L N/A 2017-10-05 Bromoform < 0.0010 N/A 0.0010 mg/L N/A 2017-10-05 Chloroform S\SG]O N/A 0.0010 mg/L N/A 2017-10-05 Dibromochloromethane < 0.0010 N/A 0.0010 mg/L N/A 2017-10-05 $%&&'()*+,-.'/%+0+"12 0 !0" #0 % 345 20 !" 0"0< $%&&'()*+,-6"7&'8'9/%'&':+0;+0+ 02 !0" #0 % 345 20 !" 0"0<

<15M2.$*#8$+"Q$][]R$T$ 10^$ L5MJ4L7.$$VWESSEGOTSGX$$Y+16.0Z$$<15M2.N8$OSEWTESTSO$S[8]_

=%1.#1%+'; B%-%2'+'-* Total Haloacetic Acids (HAA5) S\SO`] MAC = 0.08 0.00200 mg/L N/A N/A

F%1"%.'+,. 9.,;* Monochloroacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-10-05 2017-10-06 Monobromoacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-10-05 2017-10-06 Dichloroacetic Acid S\SESO N/A 0.0020 mg/L 2017-10-05 2017-10-06 Trichloroacetic Acid S\SE`O N/A 0.0020 mg/L 2017-10-05 2017-10-06 Dibromoacetic Acid < 0.0020 N/A 0.0020 mg/L 2017-10-05 2017-10-06 $%&&'()*+,-2"7&'8'>&'>?'0?@-5@?1 2< !0" #0 % 20 !" 0"0< 20 !" 0"0=

3'R!$'/12H6:912$<.0I:9.7 1D.$G$4F$G Rev 2017-01-05 Page 3 of 3 3ER"*&*3'"E$!&$')'%;<*<

RE !R"E#$"! Castlegar, City of 460 Columbia Avenue "E% (250) 365-5979 CASTLEGAR, BC V1N 1G7 &'( (250) 365-0594

'""E)"*!) Chris Barlow +!R,$!R#ER 7100493

!$)=>?ER 502 RE3E*@E#$A$"E> 2017-10-05 10:15 / 6°C R!BE3" Water Treatment Centre RE !R"E# 2017-10-12 R!BE3"$*)&! 2-1-SR 3!3$)=>?ER no number

-./.012$3455./678

CARO Analytical Services employs methods which are conducted according to procedures accepted by appropriate regulatory agencies, and/or are conducted in accordance with recognized professional standards using accepted testing methodologies and quality control efforts, except where otherwise agreed to by the client.

The results in this report apply to the samples analyzed in accordance with the Chain of Custody or Sample Requisition document. This analytical report must be reproduced in its entirety. CARO is not responsible for any loss or damage resulting directly or indirectly from error or omission in the conduct of testing. Liability is limited to the cost of analysis . Samples will be disposed of 30 days after the test report has been issued unless otherwise agreed to in writing.

Authorized By: ,0:76:/$>9,.4C/ Account Manager

If !"# $%&' %(! )#'*+,"(* "- ."(.'-(*/ 01'%*' ."(+%.+ 2' %+ 32.3'"4(5.%-"6.%

%4916:4/78 #110 4011 Viking Way #102 3677 Highway 97N 17225 109 Avenue Richmond, BC V6V 2K9 Kelowna, BC V1X 5C3 Edmonton, AB T5S 1H7 Tel: 604-279-1499 Tel: 250-765-9646 Tel: 780-489-9100 www.caro.ca

3'R!$'/12H6:912$<.0I:9.7 1D.$E$4F$G Rev 2017-01-05 Page 1 of 3 ')'%;<*<$*)&!R>'"*!)

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7100493 R!BE3" Water Treatment Centre RE !R"E# 2017-10-12

'/12H7:7$#.790:M6:4/ >.6J4N$R.F.0./9. ".9J/:KL. %4916:4/

Chlorophyll-A in Water SM 10200 H (2011) Spectrophotometry Kelowna

>.6J4N$R.F.0./9.$#.790:M6:4/78

-247710H$4F$".0578 MRL Method Reporting Limit < Less than the Reported Detection Limit (RDL) - the RDL may be higher than the MRL due to various factors such as dilutions, limited sample volume, high moisture, or interferences AO Aesthetic objective MAC Maximum acceptable concentration (health based) OG Operational guideline (treated water) µg/L Micrograms per litre

<61/N10N7$A$-L:N.2:/.7$R.F.0./9.N$:/$6J:7$R.M4068 Guidelines for Canadian Drinking Water Quality (Feb 2017) Website: http://www.hc-sc.gc.ca/ewh-semt/alt_formats/pdf/pubs/water-eau/sum_guide-res_recom/sum_guide-res_recom-e ng.pdf 7"+'8 I( *"2' .%*'*/ +$' &%1#'* 9,*01%!'9 "( +$' -'0"-+ -'0-'*'(+ +$' 1"4'*+ :#,9'1,(' %(9 %-' +" ;' &'-,f,'9 ;! +$' '(9 #*'-

3'R!$'/12H6:912$<.0I:9.7 1D.$O$4F$G Rev 2017-01-05 Page 2 of 3 <'> %E$')'%;"*3'%$#'"'

RE !R"E#$"! Castlegar, City of +!R,$!R#ER 7100493 R!BE3" Water Treatment Centre RE !R"E# 2017-10-12

$'/12H6. R.7L26$A$ <61/N10N$A$ >R%$A$ =/:67 0.M10.N '/12HP.N )46.7 <'."&'-! -L:N.2:/. =,2,+*$

<15M2.$*#8$+"Q$RSEE$T$+"3$T$R1C$+16.0$$UVEWWRXGTWEY$$Z+16.0[$$<15M2.N8$OWEVTEWTWR$WX8WW

>'('-%1 ?%-%2'+'-* Chlorophyll a W\SX N/A 0.10 µg/L 2017-10-05 2017-10-12

3'R!$'/12H6:912$<.0I:9.7 1D.$G$4F$G Rev 2017-01-05 Page 3 of 3

APPENDIX D

APPENDIX D

SECTION 6 – FROM ARROW RESERVOIR SOURCE ASSESSMENT: RECOMMENDATIONS FOR THE CITY

37

6.0 Recommendations to Improve Drinking Water Source Protection and Sustainability (Module 8)

 FLNRO should continue making improvements to its nutrient program as recommended by Dr. Stockner to reduce future algae problems at the intake.

 The City should collaborate with Celgar to construct a security fence around the intake and treatment works at Arrow Lake.

 The City should meet with the booming ground lease holder to confirm that workers are aware of the location of the City’s drinking water intake and that adequate safety measures are in place to protect the water quality. A log boom exclusion zone should be created at the intake to reduce the risk of decomposition by-products from decaying bark and wood debris reaching the intake.

 Sediment from natural sources (landslides, erosion and shoreline erosion): where imminent threats exist (UV and/or chlorination no long effective) create and implement a deviation response plan that warns the public and/or relies on treated water storage or another source until the threat has passed.

 Sediment from roads and forestry activity: work with FLNRO / Forest Management on a sediment source plan/sediment source inventory for zone1/2. Where possible deactivate roads. Where possible road drainage should be directed away from tributary streams. Where possible use settling ponds.

 Cattle: water systems representative to contact FLNRO range algologist and take part in annual tenure meetings. FLNRO to implement BMP’s and audit BMP’s (suggest annually) for effectiveness. If BMP’s (off stream watering, stubble height minimums or cattle movement plans) are not effective use adaptive management to adjust BMP’s.

 Recreational Vehicles: contact FLNRO to address specific issues under the mud bogging regulation, and/or section 46 and/or new recreation vehicle licensing registration.

 Wildfire: develop fuel management plans with FLNRO in areas thought to be of significance to the intake (most likely zones 1/2).

 Recreation (general): review the Land and Resource Management Plan (LRMP) for areas in question. Ensure Recreation is consistent with the plan. All recreation planning must consider appropriate BMP’s within zones 1 and 2 or on tributaries that are within the two zones.

o Castlegar may consider applying to the province to designate zone 1 as (non-commercial) restricted motorized boating. (note: reduces fuel and shoreline sediment loading)

o Refueling at the boat launch and marinas to be restricted to dry land refuelling.

City of Castlegar | Castlegar Source Assessment Report | urbansystems.ca 38

 Celgar: hazards for this site include fuel storage, refuelling on the water, log boom debris, and sediment loading. I suggest that both the City of Castlegar and Celgar work together to develop a plan for the log storage site as well as secondary fuel containment for the storage. A communication plan for spillage and spill cleanup / prevention measures apply. Sediment and log debris BMP’s will be site specific and can be worked on by both parties.

 Industrial Activities: identify owner of the industrial site (Photo 2, Appendix E) located in the general proximity of the intake. Identify potential contaminants which may be stored within the industrial area. Develop a plan for secondary fuel containment, a communication plan for spillage and spill cleanup and prevention measures.

 Ongoing source water monitoring: Ongoing source water assessments should be part of routine vulnerability assessments. Develop a water quality sampling schedule, including sampling frequencies, to provide information on changes in water quality conditions and to identify possible threats to the source water quality.

 The City, IHA and FLNRO should collaborate in developing and implementing a coordinated public education program focused on the importance of protecting the water quality in the lake.

City of Castlegar | Castlegar Source Assessment Report | urbansystems.ca

APPENDIX E

APPENDIX E

OPERATING PERMIT & INTERIOR HEALTH PERMITS

January 23, 2015

Chris Barlow Director of Transportation and Civic Works City of Castlegar 480 Columbia Ave. Castlegar, BC V1N 1G7

Re: IH Review-City of Castlegar Exclusion of Filtration Application and Supporting Documents Urban Systems-Arrow Reservoir Source Assessment Report-September 2014 Urban Systems-Process Review Summary and Design Objective Memo-April 5, 2011 City of Castlegar-Turbidity data 2014 City of Castlegar Bacteriological testing results 2013-2014

Interior Health has reviewed your application for exclusion of filtration along with the supporting documents noted above within the context of the Province’s Drinking Water Treatment Objectives (Microbiological) for Surface Water Supplies in British Columbia (BC SWTO).

I am satisfied that the surface water source for the City of Castlegar is currently meeting the exclusion criteria for inactivation of viruses and protozoa, the number of E.coli in raw water, average daily turbidity levels, and watershed control planning.

Excerpt from Drinking Water Treatment objectives (Microbiological) for Surface Water Supplies in British Columbia, March 2012 A water supply system may be permitted to operate without filtration if the following conditions for exclusion of filtration are met, or a timetable to implement filtration has been agreed to by the drinking water officer:

1. Overall inactivation is met using a minimum of two disinfections, providing 4-log reduction of viruses and 3-log reduction of Cryptosporidium and Giardia. 2. The number of E. coli in raw water does not exceed 20/100 mL (or if E. coli data are not available less than 100/100 mL of total coliform) in at least 90% of the weekly samples from the previous six months. The treatment target for all water systems is to contain no detectable E. coli or fecal coliform per 100 ml. Total coliform objectives are also zero based on one sample in a 30-day period. For more than one sample in a 30-day period, at least 90% of the samples should have no detectable total coliform bacteria per 100 ml and no sample should have more than 10 total coliform bacteria per 100 ml. 3. Average daily turbidity levels measured at equal intervals (at least every four hours) immediately before the disinfectant is applied are around 1 NTU, but do not exceed 5 NTU for more than two days in a 12-month period. 4. A watershed control program is maintained that minimizes the potential for fecal contamination in the source water. (Health Canada, 2003)

Bus: (250)364-6202 INTERIOR HEALTH Fax: (250)364-6218 Health Protection Email: [email protected] Suite 2-1500 Columbia Avenue Web: interiorhealth.ca Trail, BC, V1R 1J9

The City of Castlegar is currently utilizing chlorination to achieve the 4 log reduction of viruses and UV disinfection to achieve the 3 log reduction of protozoa.

The results reported for E.coli in 2013/2014 met the exclusion criteria.

The results reported for total coliforms in 2013/2014 met the exclusion criteria.

Reported average daily turbidity levels from 2011-2014 met the exclusion criteria.

A source protection plan for the Arrow Lake Reservoir has been developed using the BC Comprehensive Drinking Water Source-to-Tap Assessment Guideline.

As stated in the BC SWTO, applying the exclusion of filtration criteria does not mean filtration will never be needed at some point in the future. A consistent supply of good source water quality is critical to the approach, but source quality can change. Therefore, the exclusion of filtration must be supported by continuous assessment of water supply conditions.

It is expected that an annual report be submitted by July 1st of each year, which demonstrates that the City of Castlegar is meeting the conditions for exclusion of filtration on an ongoing basis.

I would like to acknowledge the City of Castlegar for their efforts in source water protection planning and success in meeting the filtration exclusion criteria under the British Columbia Surface Water Treatment Objectives.

Sincerely,

Juliana Gola Specialist- Environmental Health Officer

cc: Marianne Crowe, Public Health Engineer, Interior Health Dan Byron, Team Leader Large Water Program, Interior Health

Bus: (250)364-6202 INTERIOR HEALTH Fax: (250)364-6218 Health Protection Email: [email protected] Suite 2-1500 Columbia Avenue Web: interiorhealth.ca Trail, BC, V1R 1J9