Hot Generation – Flooded Heat Exchangers

Steam equipment emerges from the 20th century… Space saving, GREEN design by Advanced Technology

The Advanced Steam Technology XE that were installed over the last 40 to 50 Technology XE Thermal unit for steam Thermal unit is a new, patented form years are at the end of their useful life. to water heating. It squeezes every of vertical steam to water exchanger for Many times the facility is built up practical BTU out of the steam and building heat. around these failing units. The only condensate. way to get a new unit in would entail Two key factors have led to the growth major demolition. Normally when a system is energy of this style of for efficient, it’s not the lowest cost to building heat. First, the new design is Vertical packages can be wheeled install. The Advanced Steam vertical, and much smaller than old- through a doorway. They can be piped Technology XE Thermal unit is fashioned conventional steam heaters up with the existing unit in place, different. It does not require a pressure (convertors). Secondly, testing and causing minimal downtime. Sometimes reducing valve station, or a dedicated research has enabled these units to the existing unit is encapsulated and condensate . This can save up to eliminate flash steam, usable for LEED left in place, or it can be drained and 40% of the installed cost on a new job. calculations and GREEN building cut into pieces for removal. certification, (not to mention saving To explain how the dramatic energy energy and money). conservation and cost savings are possible, let’s start at the beginning, Size is a frequent consideration. Floor with water… space is at a premium in modern mechanical rooms. The difference in Steam fundamentals footprint between a 16 square foot When make-up water enters the vertical skid and trying to stack regular room or power plant, its first stop after horizontal exchangers can be worth treatment is the deaerator. Here it is thousands of dollars. sprayed over heated trays to drive out dissolved gases. The water is usually heated from 40F to 205F by adding . It takes about 1 BTU to raise a pound (or pint) of water by 1F. These BTU’s are supplied by steam in Fig 2 Advanced Steam Technology the trays. XE Thermal Unit Smaller package might not Conventional piping components are utilize a deaerator, in which case, the utilized in every critical valve or pump. boiler provides this same sensible heat A facility can even specify and demand.

valves for which they already stock Fig. 1 Vertical steam piping layout parts. Here is one place where the Advanced

Steam Technology XE Thermal unit

Energy conservation is unparalleled. system makes a difference. Why is Retrofit applications are perfect for There is no unit on the market more make-up water needed in the first vertical units. Large, bulky exchangers energy efficient than a Advanced Steam place? Some losses are due to boiler

Bulletin TB-202 Advanced Steam Technology Company LLC – www.advancedsteam.com blow-down and some to make up for Pressure Temperature Volume to 60 psig return systems, which then leaks. The other loss is from “flash 0 psig 212 F 27 ft3 “cascade” down into a 0 psig system. steam”. That’s the steam puffing out of 15 psig 250 F 14 ft3 vent pipes all around the condensate 60 psig 308 F 6 ft3 Conventional Heaters return system. 100 psig 338 F 4 ft3 When heating air or water, the 150 psig 366 F 3 ft3 conventional control method is to use a 600 psig 486 F 1 ft3 modulating valve on the steam inlet. Its Fig 5 Steam pressure compared to job is to throttle the steam pressure volume feeding the heat exchanger. By raising and lowering the pressure, the steam High pressure distribution is used to temperature changes in response to the minimize pipe sizes, and reduce the sensor which controls the valve. A drop in pressure experienced by person could even do it manually. Just flowing steam. watch a thermometer in the leaving fluid. If the temperature is too high, Intermediate pressure steam is then start closing the inlet steam valve. normally 60 or 80 psig. It is used for If it’s too low, open the valve. sterilizers, autoclaves, wash mixers, Fig 3 Flash steam puffing from vents and pumping stations. This steam is This is called the “feedback” method. usually generated from distribution In a storage tank or service water The steam boiler takes water from the pressure by a pressure reducing station. application it works well from a deaerator, heats it to the boiling point temperature control standpoint. From by adding more sensible heat, and then Low pressure steam is normally 10 to the steam management side, it’s adds to vaporize the water 15 psig. It is used for heating air and complicated. Also, it does not work into steam. How much sensible and water. The water heating systems are well for domestic water heating without latent heat are needed? That depends on either “service” or “domestic”. a storage tank. the steam pressure desired. Domestic water is for the hot side of sinks and showers. Service water is first What’s the problem with conventional Pressure Temperature Sensible Heat Latent Heat heated by the steam, then it circulates “feedback” control? For one thing, its 0 psig 212 F 180 Btu 970 Btu through coils and baseboard to heat air. very nature is “after the fact”. The 15 psig 250 F 218 Btu 945 Btu It’s usually mixed with glycol to avoid modulating valve only reacts after it 60 psig 308 F 277 Btu 905 Btu 100 psig 338 F 308 Btu 880 Btu freezing. Between building heat and sees a variation in outlet temperature. If 150 psig 366 F 338 Btu 857 Btu domestic, most facilities use at least that leaving water is too hot, that’s too 600 psig 486 F 472 Btu 732 Btu 50% of their steam for heating water. bad; it’s out into the system already.

Fig 4 Pressure compared to heat The other problems can be summed up content in condensate in one word… vacuum. The inlet modulating valve typically has 15 psig A sophisticated system for a university, steam supplied to it. We often forget food processor, or chemical plant will that this is really 30 psia steam. The generate steam at 600 psig or higher, modulating valve doesn’t know that because steam is used to generate 14.7 psia is what we call 0 psig. It will power before distribution. The steam is throttle the steam pressure to whatever normally distributed at 100 or 150 psig. satisfies the temperature sensor. If it Some industrial plants (usually with needs 200F steam to satisfy the sensor, turbine drives) will distribute steam up Fig 6 Typical building heat system it’s no problem. It will throttle the to 600 psig. with “conventional” control pressure down into vacuum, and “presto!” there is 200F steam. (See Systems are designed around higher Condensate system pressure is following appendix VACUUM) pressure distribution because of the normally 0 psig. Industrial process steam volume. dryers sometimes use intermediate 30 That’s where the problems start. Because the condensate return system

Bulletin TB-202 Advanced Steam Technology Company LLC – www.advancedsteam.com is at 14.7 psia, the heat exchanger can’t conventional control method with the like it’s full of gravel, and the internals drain. Water hammer, valve hunting, inherent design problems. will wear out quickly. and uneven control result. The solution is simple, fortunately, but the Advanced Steam Technology design becomes much more XE Thermal Operation complicated. The Advanced Steam Technology XE Thermal unit system uses a control The solution is to install a vacuum valve on the condensate side for breaker. It sucks air into the exchanger, temperature control. This difference breaking the vacuum. The system can allows two advantages. First, high then drain by gravity. pressure steam can be used. A pressure Fig 9 Worn impeller from condensate reducing station is not needed, and pump That solves the problem, but three steam piping is smaller and lighter. factors make the system design Second, the heater utilizes the latent In addition, the unbalanced impeller complicated. and sensible heat of the steam. wobbles and causes the shaft seals to  There is now air in the heat leak. exchanger The Advanced Steam Technology XE  The pressure is very low (0 psig) Thermal unit eliminates the need for a and condensate is still being dedicated condensate pump. The 200F created condensate has high pressure behind it,  An overhead return line can’t be so it does not need a pump. This piping used without a pump is sized like a water line, so smaller and lighter pipe can again be used.

In order to deliver these benefits, the control valve on the condensate side is a vital component. Every precaution is Fig 8 Advanced Steam Technology taken to be sure it does not leak. The XE Thermal Skids system is normally furnished with a temperature controlled steam regulator At full load, a Advanced Steam to prevent high water temperatures Technology XE Thermal unit style is should the control valve leak. A steam designed to discharge condensate at or trap is also provided to prevent a even below 200F. Compared to a leaking control valve from discharging Fig 7 Complicated steam and conventional or a blending heater at live steam. drainage piping 250F, this saves 50 BTU’s for every Between larger steam trap selection, air pound of steam consumed. Furthermore vent placement, and adding a because the condensate is less than In summary, the Advanced Steam condensate pump, the design gets 212F, it will not create flash steam. Technology XE Thermal unit steam expensive. heater has many advantages: When flash steam is formed, it flows up • Lower installed cost than other fluid Lifting condensate to an overhead through the vent on the condensate heaters return is not recommended, so a return station. It’s lost in the • Utilize steam that is wasted by other condensate pump may be needed. Hot atmosphere through the vent pipe. In heaters (Save 20%of energy usage at water can potentially work its way back the deaerator discussion above, 125 psig steam, save 5% of energy into the supply, so thermal “U loops” remember that make-up must be added, usage at 15 psig steam. are needed on the water side. treated, and heated when flash steam is • Smaller footprint lost. • A dedicated condensate pump is not Advanced Steam Technology XE required Thermal Vertical Design The condensate pump station behaves • No dedicated PRV station required This is a new twist on a proven design. better with the cooler condensate. Hot • No vacuum breaker required Vertical exchangers were called condensate cavitates as the pump pulls “Calorifiers” years ago. They used the it into the volute. The pump will sound

Bulletin TB-202 Advanced Steam Technology Company LLC – www.advancedsteam.com

• Control liquid leaving temperature at +- 3F

Figure 10 Hotel Domestic Heaters

You can use the Advanced Steam Technology XE Thermal units for: • Domestic Hot Water • Heating Water/Glycol for Building Heat • Hot Oil or other Heat Transfer Fluids • Wash Stations • Emergency Showers

Bulletin TB-202 Advanced Steam Technology Company LLC – www.advancedsteam.com