CMP-400 Indeks: WMGBCMP400 Digital Clamp-On Multimeter

Description

Measure a wide range of electrical parameters with the CMP- 400 Clamp Meter

The Sonel CMP-400 digital clamp meter was developed for direct measurement of AC current up to 400 A. The device allows also to measure and AC voltages up to 600 V (using leads). Further useful functions of the instrument are resistance measurement, continuity of connections measurement with acoustic signalling, and temperature measurement using the probe included in the standard equipment of the meter. With its high precision and speed of measurement, the instrument will meet the expectations of any electrician.

The Sonel CMP-400 meter is a device perfectly prepared for hard work even in unfavourable measurement conditions. The casing of the meter has a protection level of IP 40 and is additionally covered with elastomer, provides the device with higher protection against drops and mechanical damage.

Surprisingly versatile, and the same small and easy to use, the CMP-400 meter is a professional instrument which is perfect for the work of electricians, e.g. in residential, commercial or industrial facilities. The extended functions of this meter will also be appreciated by maintenance workers, electrical installation technicians, electrical fitters, as well as HVACR specialists (heating, ventilation, air conditioning). An unquestionable advantage of the CMP-400 is its pocket size, which allows it to be easily stored in a toolbox or bag. In addition, the instrument is characterised by its exceptionally easy operation, which even beginners can master in no time. The interface combined with the handy form of the meter ensures ease and comfort.

Measure wide range of electrical parameters with the CMP- 400 Clamp Meter

Measurement functions

AC current measurement up to 400 A DC and AC voltage measurement up to 600 V resistance measurement continuity test with acoustic signalling (beeper) for resistance below 50 Ω temperature measurement (Fahrenheit or Celsius) frequency measurement diode test

Overview

Sonel CMP-400 Clamp Meter is designed to hard work in arduous measuring conditions. A special housing, covered with an elastomer coating, provides protection against drops and mechanical damages. CMP-400 is the first choice for those expect the device to be reliable at work in industrial and residential environments.

Designed for specialists

industrial and commercial electricians plant maintenance facility maintenance electrical contractors utility technicians HVACR specialists

Special features

non-contact neon lamp safe, insulated measurement clamp reinforced, impact resistant enclosure automatic selection of ranges with the capability of switching over to the manual selection mode HOLD function, allowing for freezing the result on the display large and easy to read LCD display with backlit relative measurement function indication of range overflow

Faciliating the measurements

The AC-16 adapter expands the application of the clamp meter. With the ratio x1 and x10, 230 V AC of voltage and max 16 A of current, the adapter can be applied with any of clamp meter. Technical Specification

Temperature measurement

Range -20,0...760°C

Accuracy ±(3% m.v. + 5°C)

Range -4,0...1400°F

Accuracy ±(3% m.v. + 9°F)

*probe (K type) accuracy not included

Frequency measurement

Range -10 Hz

Accuracy ±(1,5% m.v. + 2 dgt)

» sensitivity: 100 V (<50 Hz), 50 V (50…400 Hz); 15 V (401 Hz…10 kHz)

AC current measurement

Range 4,000 A

Resolution 0,001 A

Accuracy ±(2,5% m.v. + 12 dgt)

Range 40,00 A

Resolution 0,01 A

Accuracy ±(2,5% m.v. + 8 dgt)

Range 400,0 A

Resolution 0,1 A

Accuracy ±(2,8% m.v. + 8 dgt)

» frequency range: 50...60 Hz.

AC voltage measurement

Range 400,0

Resolution 0,1 mV

Accuracy ±(1,5% m.v. + 30 dgt)

Range 4,000 V

Resolution 0,001 V

Accuracy ±(1,8% m.v. + 8 dgt)

Range 40,00 V

Resolution 0,01 V

Accuracy ±(1,8% m.v. + 8 dgt) Range 400,0 V

Resolution 0,1 V

Accuracy ±(1,8% m.v. + 8 dgt)

Range 600 V

Resolution 1 V

Accuracy ±(2,5% m.v. + 8 dgt)

» frequency range: 50 Hz...400 Hz

DC voltage measurement

Range 400,0 mV

Resolution 0,1 mV

Accuracy ±(0,8% m.v. + 2 dgt)

Range 4,000 V

Resolution 0,001 V

Accuracy ±(1,5% m.v. + 2 dgt)

Range 40,00 V

Resolution 0,01 V

Accuracy ±(1,5% m.v. + 2 dgt)

Range 400,0 V

Resolution 0,1 V

Accuracy ±(1,5% m.v. + 2 dgt)

Range 600 V

Resolution 1 V

Accuracy ±(2% m.v. + 2 dgt)

Resistance measurement

Range 400,0 Ω

Resolution 0,1 Ω

Accuracy ±(1,0% m.v + 4 dgt)

Range 4,000 kΩ

Resolution 0,001 kΩ

Accuracy ±(1,5% m.v. + 2 dgt)

Range 40,00 kΩ

Resolution 0,01 kΩ

Accuracy ±(1,5% m.v. + 2 dgt)

Range 400,0 kΩ

Resolution 0,1 kΩ

Accuracy ±(1,5% m.v. + 2 dgt)

Range 4,000 MΩ

Resolution 0,001 MΩ

Accuracy ±(2,5% m.v. + 3 dgt)

Range 40,00 MΩ

Resolution 0,01 MΩ

Accuracy ±(3,5% m.v. + 5 dgt)

„m.v.”- measured value

Electric security: - measurement category: III 600 V acc. to EN 61010 - 1:2004 - protection class acc. to EN 60529: IP40

Other technical data: - power supply: 9 V battery type 6LR61 - display: 4000 counts, backlit LCD - continuity test: I<0,5 mA, sound signal for R<50 Ω - diode test: I = 0,3 mA, U0 = 1,5 V DC - over range indication: 0L displayed - sampling rate: 2 times per second - input impedance: 10 MΩ (V DC and V AC) - clamp size: opening 30 mm (1,2”) - auto power OFF: approx. 30 min. - dimensions: 197 x 70 x 40 mm - weight: 183 g - accordance with following standards: EN 61010 - 1:2004, EN 61010 - 2 - 032 - quality standard ISO 9001

Rated operational conditions: - operating temperature: 0...+40°C - storage temperature: -20...+60°C - operating humidity: max 80% up to 31°C decreasing linearly to 50% at 40°C - operating altitude: max 2000 m