<<

Water Treatment Terminology Operation & Maintenance  GPM= gallons per minute  MGD= million gallons per day  TTHM= total trihalomethane Exam Review  PSI= pounds per square inch  NTU= Nephelometric Turbidity Unit  mg/L= milligrams per litre or ppm= parts per million  Feet of Head

Purpose of Treatment Process Pathogenic  Screens  Remove debris  Disease causing organisms  Pre-chlorination  Kills pathogens, controls  Includes Viruses, Protozoa, or taste and odors. Possible Bacteria problems with DBP’s  Causes diseases such as  Use UV or Ozone instead typhoid, cholera and dysentery  Chemicals  Organisms that don’t cause  Assist with the process disease are non-pathogenic  Flash mixer  Mixes chemicals with water  Coagulation/flocculation  Slowly mixes the chemical and particles together.

Intakes & Screens Thermocline  Multiple inlet intake structures allows operators to pull from  Epilimnion- upper layer that depth of better quality circulates warm water where dissolved oxygen  Should prevent large debris & fish from entering treatment plant concentrations are moderate to high  Should be designed to handle  Thermocline - separates flows upper an lower layers  Manually cleaning screens for  Hypolimnion , a cold, deep- small amounts of debris water, non-circulating layer  Turnover cause mainly by change in which oxygen is low or in water temperature & density absent

1 Pre-sedimentation Aeration

 Removal of debris  Removes dissolved  Helps control impact of changing raw water gases  Removes dissolved  Impoundments are types of pre-sedimentation metals such as iron systems  Releases volatile chemicals

Coagulation/Flocculation Primary Coagulants  Zeta Potential  The repelling force that keeps particles separated  Aluminum sulfate  Coagulation  Ferrous sulfate  Is the adding & rapid mixing of chemical coagulants in water to reduce turbidity prior to filtration  Ferric sulfate  Is a chemical reaction between coagulant, turbidity, & alkalinity.  Cationic polymer  Neutralizes negative (-) charges  hydroxide  Flocculation is a process that form floc to settle out impurities in the  water & reduce turbidity prior to filtration  Floc grows with the collision of the particles  Sodium aluminates  Troubleshooting  Paddle speed- slow speed floc will settle prematurely  Velocity through basin  Short circuiting

Coagulant Aids Sedimentation  Allows solids to settle out before filtration  Sedimentation - With Settling Tubes  Calcium hydroxide  As required by drinking water rules  Calcium oxide  Sedimentation - Without Settling Tubes  2 hours detention time  Sodium aluminates  WLR (weir loading rate) <20,000 g/d/ft  Bentonite weir length  Head on rectangular weir is measured  Calcium carbonate from crest to top of water on weir plate  Sodium silicate  0.5 fpm velocity  8 to 12 ft depth  Anionic polymer  Nonionic polymer

2 Sedimentation Tube Settler  Sedimentation Troubleshooting  Short circuiting  Temperature  Working properly determined by the measurement of turbidity in compared to turbidity out.  Wind currents  Velocity  Increase in flow  Floating materials  Sludge removal  Sludge accumulation  Noisy drive chain

Filtration Systems Filtration Systems

Conventional – Pressure Filters Conventional Treatment Non-conventional Screens Screens  Direct filtration Pre-chlorination Pre-chlorination *No sedimentation Chemicals Chemicals Flash mixer Flash mixer  Slow sand filter Coagulation/ *Coagulation, Flocculation, *No: Chemicals flocculation Sedimentation, & Filtration Flash mixing Sedimentation Post chlorination Coagulation Filtration Flocculation Chemicals Post chlorination Sedimentation Clear well Chemicals Clear well

Filtration Filtration Rates

 Removes small contaminants  Terminal Head Loss water can no longer be

 Bacteria- Salmonella, E. Coli filtered  Protozoan- Giardia, Cryptosporidium  Recommended flow rates are 15 to 20 GPM per  Virus- Hepatitus A, Rotavirus square foot  Types  Closing inlet valve & measure drop in the water  Mechanical filter level over time you can determine flow thru filter  Absorption filter  Too large of floc can cause the filter to clog at a  Slow sand rapid rate  Rapid sand  Mixed media  Filter Loading rates are defined as gallons of  Highest rate of flow water applied to each square foot of filter surface  Water flows through the filter by percolation area  Head loss gauge measures pressure drop as water passes thru the filter

3 Multimedia Filter - Sand Filter Media Types - Garnet - Coal  Sand  Anthracite  Garnet  Granular Activated Carbon  Green Sand  Measured by sieve analysis to determine size

Filtration FILTRATION

 Removes small contaminants  Trouble shooting  Bacteria  Method of determining flow through a filter  Protozoan without a meter.  Virus  Measure the rise or fall of the water in the filter  Types over time  Mechanical filter  Used for removal of Giardia & Cryptosporidium  Absorption filter  Aeration  Slow sand  Dissolves gases  Rapid sand  Dissolves metals  Mixed media  Removes volatile chemicals  Highest rate of flow  Water flows through the filter by percolation

FILTRATION Disinfection

 Process to kill or inactivate most pathogens in water.  Trouble shooting  There are several ways to  Mud balls disinfect  Improper surface washing or backwashing  is most popular  Air binding method because of cost and it leaves a residual throughout  Cold water the system  Negative pressure head in lower filter  UV  Cracking  Ozone- doesn’t leave a  Septic smell measurable residual in system

4 Breakpoint Chlorination Graph Disinfection By-products

 Chlorine smell would indicate you need to add more  TTHM- Total Trihalomethanes to reach breakpoint  Adsorption where molecules collect & adhere to a surface of an adsorbent solid (GAC) would help reduce TTHM’s  Combination of chlorine and organics  Warmer temperatures and pH form THM’s faster  THM precursors would indicate THM forming throughout the system  Aeration & Clarification can remove THM precursors

Organic Matter Under Drains  TTHM  Total trihalomethanes  Used for backwashing  MCL = 80 ppb (0.080 mg/l)  Collects the filtered  HAA5 water  Haloacetic acids  Keeps the media bed in  MCL = 60 ppb (0.060 mg/l) the filter.  Reduction and removal through:  Absorption  Aeration  Oxidation  Clarification

Backwash Filter Head Loss Gauge

 Open backwash valve slowly  Used to measure drop  Backwash is based on: in pressure thru filter  Increase in Effluent Turbidity  Terminal head loss =  Head Loss No water flowing  Filter Run Times determined by plant (many use 36 hrs)  Backwash duration depends on amounts of sludge & debris in filter  Typical Backwash Rate: 15 to 20 gpm/sq.ft .

5 Surface Washer Sludge Collectors

 Mudballs and surface mats are reduced  Fix noisy drive chains by tightening and aligning the chain & casing

3 Most Important Monitoring Parameters For Safe Drinking Water Jar Testing

 Bacteria  Duplicates the treatment plant  Turbidity- operator has processes such as detention most control over time, mixing conditions & settling conditions  Chlorine residual  Helps provide optimal dosages  Helps optimize coagulation process  Floc remaining longer than 15 to 20 minutes probably won’t settle out

Water Hardness Water Hardness & Corrosion  Caused by salts of calcium & magnesium (bicarbonate,  Objectionable tastes carbonate, sulfate, chloride &  Magnesium leaves black stains nitrate)  Galvanic Corrosion cause by  Causes formation of soap dissimilar metals in a drinking water curds system  Increased use of soap  Hardness test uses EDTA titrant  Deposits in boilers & fixtures  Expressed as mg/L CaCO3  Soft water considered as 0 to 50  Damages industrial processes mg/L of CaCO3  High dissolved CO2 would increase corrosion

6 Corrosion C-Factor

 Electrochemical phenomenon observed as red water  Indicates the smoothness pipe  Calcium carbonate saturation used for corrosion control material  Measurements:  The higher the C value, the  Langelier index smoother the pipe.  Positive number: Deposit  To calculate measure flow, pipe  Negative number: Corrosive diameter, distance between two  Metal coupons used to measure corrosiveness of pressure gauges, and the water – determined by weight loss of coupon friction losses between the gauges.  Adjustments can be accomplished by:  Chemicals which increase or decrease the depositing,  Tuberculation reduces C value or  Sequester the problem with the use of polyphosphates PVC has higher C- factor than concrete

Head Loss FRICTIONAL HEADLOSS

 Friction head loss: caused by valves, bends, pipe  Energy used up by water movement roughness, etc.  Two Conditions that affect head loss:  Water hardness caused by calcium & magnesium 1. Roughness  Coefficient tests can indicate 2. Velocity whether or not friction losses are increasing . Two Conditions that affect Roughness:  Galvanic corrosion can 1. Age – Condition happen when connecting brass to steel 2. Type of pipe Materials

Iron  Consumer complaints Turbidity- NTU’s  Can cause stains on laundry & fixtures  The following is the most  Formation of iron bacteria that form slick frequent method used to slimes on pipe walls water quality & the  Taste and odor problems cloudiness of the water  Reacts with chlorine increasing use  Uses light to measure  Removed thru aeration and filtration  The higher the NTU, the  Iron & manganese react with dissolved dirtier the water, the more oxygen forming insoluble compounds possibility of micro- biological contamination  Polyphosphates & flushing reduce iron deposits  NTU= Nephelometric Turbidity Unit

7 Turbidity Particle Counter

 Physical characteristic of water making it appear cloudy.  The method used to  Caused by suspended matter. measure the cloudiness of the water – the amount of  The most monitored treatment of water for quality. particles and the size of particles.  The greatest control factor in treatment of water.  The dirtier the water, the  Increased influent turbidity means an increase greater the possibility of in chemicals microbiological  Masks pathogens from disinfections . contamination.

pH  Alkalinity  pH: expression that refers to the basic or acidic conditions of the water  A measurement of the water’s capacity to  pH is measured on a scale from 0 to 14. neutralize an acid  Less than 7 is more acidic, greater than 7 is more basic or higher alkalinity. 7 is  Alkalinity is determined by titrating to an end neutral. point with a pH meter or the use of the methyl  PVC pipe is least affected by acidic water  Reinforced concrete pipe would most likely orange test corrode in acidic water  Corrosiveness on pipes can be detected by  Use sulfuric acid to perform test plotting Baylis Curve or Langlier Index  Affects the coagulation process  Weight of metal coupons used to determine corrosiveness  The higher the alkalinity, the better the floc  A negative number on Langlier Index would formation be corrosive

pH Temperature  Characteristics of Temperature  The colder the water, the more dense.  Any substance that releases HYDROGEN (H+) when  The colder the water, the less activity. mixed with water is acidic (0-6)  Higher disinfection concentration is required  Any substance that releases HYDROXYL IONS (OH-) is a base (8-14) in cold water.  Low temps decrease the rate of floc settling  Alkalinity changes will affect the coagulation process  F (Fahrenheit) C (Celsius)  pH is measured by use of a PROBE OR A COLORIMETRIC METHOD.  SIGNIFICANCE:  Main impacts  Affects chlorination, coagulation, softening, and  Affect to speed of biological and chemical corrosion reactions  Affect to rate of biological decomposition  CO 2 – Carbon dioxide reduces the pH  Changes to chlorine demand

8 Chemicals Temperature

 Low temperatures the bacteria kill rate is lower  Chemical Storage  Chlorine residual will remain  Cool, dry place longer in cold water  Away from general traffic  Warm water will cause bacteria  Non-treatment chemicals to bloom  Spillage control – clean plan  Calcium Carbonate will form more rapidly in hot water  Empty drum disposal  Temperature drops would  According to manufacturer’s recommendation cause carryover in sed. basins

Aluminum Sulfate (Alum) Chemical Compounds  Part of coagulation/flocculation process & creates the floc  Aluminum sulfate  An anhydrous acid  Ferrous sulfate  Affects skin and mucous tissues  Need goggles, face shields, dust mask, gloves,  Ferric sulfate boots, rubber apron, clothing to protect skin & proper ventilation  Cationic polymer  MCL for atmosphere  Calcium hydroxide  15 mg/cm for 8 hours  When added to water:  Calcium oxide  Dissolved Sulfate increases  Sodium aluminates  Alkalinity decreases  Calcium Carbonate  pH decreases  MCL in finished water is 450 mg/l

Alum Ferric Chloride

 Alum is a mild  Is a very corrosive material corrosive  Should prevent splashing  Never use the same conveyor system for  Use eye protection, rubber alum and quicklime gloves, and protective clothing  Potential for explosion  When spilled on skin, flush  pH below 5 floc won’t with large amounts of water form properly

9 Chemicals Chlorine  Corrosion Control  Fluoridation  Gas is heavier than air  Calcium hydroxide  Sodium fluorosilicate  Have eyewash/shower available  Most leaks occur around control valve  Hydrated -  Sodium fluoride increases pH  Cylinder liquid form expands 460 times  Fluorosilicic acid  Sodium hydroxide  When changing cylinders, shut gas off at  Hydrofluoric acid  Caustic soda cylinder first, evacuate lines  SPADNS test for fluoride  Softening  Produces hydrochloric acid mixed with moisture  Calcium oxide  Use rubber gloves & ventilate  Quicklime  Should practice response once per year  Sodium carbonate  Inspect daily for leaks in system  Soda ash  Higher alkaline = more chlorine

Chlorine Leaks Three Forms of Chlorine

 POWDER 65%- HTH (High Test  Put on SCBA )  Turn on ventilation fan  LIQUID-  Have help standing by * 5% *T-Chlor 15%  GAS 99.9% *extremely corrosive with water/humidity *compressible *changes to liquid at 82 psi *68 deg. F *2.5 times heavier than air *greenish-yellow color * Must meet NSF approval

Calcium Hypochlorite & Quicklime Chloramines

 Calcium Hypochlorite  Quicklime  Can create heat & oxygen  Extremely caustic material  Formation of chloramines is a chemical to start a fire  Reacts violently with water reaction  HTH- High Test  Reaction can cause fire or Hypochlorite explosion  The reaction is between hypochlorous  Store totally dry area acid (or aqueous chlorine) with  Do not allow to mix with ammonia . alum  Formation of chloramines weakens the disinfecting strength of chlorine

10 Chloramination DPD

 Method of measuring chlorine residual in  Cloramines are a reaction the water between applied chlorine  Testing agent turns and ammonia chlorinated water a  When done intentionally it pink color. More can reduce tastes and intense color, higher odors residual.  Chloramines are a weaker  DPD= N,N-diethyl-p- disinfection than chlorine phenylene-diamine

Fluoride Over Feeding Fluoride

 Victims exposed to large  Can Mottle Teeth amounts should me removed from area  Operators should know the hazards contained in MSDS  Can cause dental stains & mottling of teeth  SPADNS test to analyze fluoride levels

Caustic Soda Safety Chemical Safety for Acids

 Chemicals cause visible  Strong caustic alkali and very hazardous destruction or irreversible damage to skin tissue at the  Very reactive point of contact  Dissolves human skin  Swallowing can damage  Generates heat with when esophagus & stomach . mixed with water  Wear personal protective  Reacts with amphoteric equipment metals generating  Flush affected area with clean hydrogen gas which is water flammable or explosive  Use sodium bicarbonate to  Use special precautions neutralize acids when handling  Add acid to the water

11 Polymers Polymers

 Used as coagulant and  Filtration aid filter aids  Not enough:  Keep polymer dust off  Rapid turbidity break through floors  Too much:  Will create very slippery  Rapid increase in head loss surfaces when on floors  Use inert, absorbent material such as sand to clean up spills

Potassium Permanganate Explosions  Strong oxidizing agent , use caution  Turns water pink  Will react easily with organic  Don’t use sawdust to materials absorb liquids  Will ignite when in contact with antifreeze, sawdust compounds and  Powder activated many other materials carbon is the most  All lubricants & fuels are potential fire hazards volatile powder  Store separately from other  Methane is the most chemicals in a cool dry location common combustible  Use dust masks and rubber gloves when handling & for cleaning up gas  Used for taste & odor, TTHM control, reduces Iron, Hydrogen (rotten egg smell) & Manganese

Activated Carbon Taste & Odor  Used for taste & odor problems  Is considered the most volatile powder  Activated Carbon & KMNO4 are chemicals  Keep away from Cl2 compounds and KMnO4, possible spontaneous combustions used  The main problems are dust and fire control  Will burn with intense heat , and without  Threshold Odor Number (TON) is a unit of smoke or visible flame measure for odors in water & should be  Keep electrical equipment clean  Carbon dust can cause short-circuit fires conducted at 60 deg. Celsius  Use explosion-proof electrical equipment  Water devoid of oxygen produces odor and  Used prior to chlorination because they react with each other anaerobic bacteria growth  Sludge accumulations could cause problems

12 Algae Control Chemical Nitrite – Cause & Effect

 Cause  Large concentration of fertilizers.  Copper Sulfate  Effect  Indicators that affect  Blue-baby syndrome copper sulfate:  High Nitrate Levels  Alkalinity  MCL 10 mg/1  Type of algae  Temperature  5 mg/1 – quarterly monitoring  Nitrate turns in nitrite and replaces oxygen in blood. Thus babies and immuno-deficient individuals are affected.

Sampling Fusible Plug

 Grab samples taken in 150 lb. Cylinder Valve Composite Sample  Safety Device instantaneous  Made out of lead conditions at certain  Melts between 160 to times & locations 165 degrees

Bacteriological Sampling Bacteriological Sampling Procedures Procedures

 If sample is OK, this only  Should allow sample tap water to run several minutes or as long as necessary indicates that water was safe at Not smooth nosed point of sample to clear service line  Coliform is an indicator of  Sampling bottle/bag should be filled to bacteria presence just above fill line or 1 inch from top  Sample should be transported  Results are meaningless if sample is as soon as possible in a cool contaminated container with ice pack  Sample identification cards need to filled  Routine bacti’s should be taken out completely at the customers tap at various  Should be sterilized by lab points that represent the entire  Sodium Thiosulfate system  Dechlorination agent in bacteriological sample container

13 Coliform GWR

 Coliform= a group of bacteria  December 1, 2009 found in the intestines of warm blooded animals & also plants,  TC+ bacterial Samples soil, air and water  Requires Triggered Source Water sample (TSW)  Total Coliform = a measurement  Of all sources that were in operation at time of that shows if coliform bacteria is present in a water system & are +TC sample an indicator organism  Email on sources not sampled – not running  Fecal Coliform = a specific class  Test for fecal coliform of bacteria coming from animal intestines. If sample is coliform positive, a fecal coliform test is performed.

Sanitary Surveys Performed GWR continued By

 Executive Secretary shall ensure a sanitary  5 addition samples if first TSW is Fecal+ survey is conducted at least every 3 years  2 or more sources requires you to submit  Division of Drinking Water new sample site plan  DEQ District Engineers  Correct significant deficiencies within 120  Local Health Departments days  Forest Service Engineers  Utah Rural Water Association staff  Consulting Engineers  Others authorized by Executive Secretary

Aesthetics Electrical Motor

 Clean dust from a motor with compressed air.  Means attractive or appealing.  Measure speed with  With respect to water it means tachometer taste, odor, or coloration of the  Auxiliary motors can be water. used in emergencies  Things that affect this are extreme  Brake HP is amount of hardness or high total dissolved HP supplied by the solids motor to the pump  Effects range from bad smell and poor taste to causing stains on laundry and/or fixtures

14 Circuit Breaker Electric Motors  Opens or closes the electrical circuit to motors

 Function as overload device  Upon start up an electric motor will develop a load to turn the  Opens automatically when an overload occurs to pump shaft and impeller protect circuit  Torque causes motor to draw a high amperage  To change rotation on 3 phase, switch any 2 leads  Voltage imbalances cause 3 phase motors to overheat & burn out the insulation  Tachometer used to determine speed of motor/pump

Volt – Ohm Meter Transformer

 Volts  Measure of the force of electrons  The purpose of the  Set the volt meter at a transformer is to higher setting than the voltage being measured. increase (step up) or decrease (step  Ohms down) voltage.  Measurement of resistance  Amps  Measurement of the flow of electrons

Confined Spaces Security

 Carbon dioxide will  Deter settle near floor  Detect  Blowers are the most effective means to  Delay reduce atmospheric  Respond hazards  Ventilate until proper oxygen levels are reached (minimum19.5%)

15 Safety Security Distribution Systems

 Looped systems have continuous  Reservoir sites flow & less water quality problems  Water quality problems could indicate a closed valve or partially  Sources open  Main Offices  Leak surveys done at night  Water mains   10 Feet horizontal distance from Vehicles sewer main  Water main and sewer mains must  Vaults cross at least 18” of separation  Water line is on top  Water & sewer not installed in the same trench.  Leaks will get worse not better

Maintenance Records Ground Water - Wells

 Water bearing  Why keep maintenance records? formation called an  Develop preventative maintenance program aquifer  Prolong life of equipment  Maps  Maintain backup equipment  Reduce liabilities  Improve customer service

New & Repaired Water Mains Water Distribution Systems

 Operation and Maintenance  Pressure test  Water main design  Disinfected in accordance with  Distribution system pressures AWWA standard C651  20 psi at all times  Must be disinfected with some  Peak instantaneous flows type of chlorine  Minimum Water main size  Tablet or a solution are typically  8 inch with fire hydrants used  Unless you have an engineer signature to buy off on  Chlorine must be flushed with it potable water  4 inch without fire hydrants  Take chlorine residuals  Must take bacteria samples

16 New Minimum PSI Standards Thrust Blocking

 Thrust Block - a concrete mass cast in place between a fitting and  Maintain minimum of 20 psi at all times the undisturbed soil at the side or  For Construction after 3/1/06 bottom of the pipe trench.  Purpose is to keep fittings from *20 psi during fire flow moving & either coming loose or apart from the force of the water *30 psi during peak instantaneous demand pressure in the pipe. *40 psi during peak day demand  Needs to be centered on the thrust force

Water Storage Reservoir Storage Reservoirs

 Provides a volume of water to the water system during  2 categories of paint- long life and short life average and peak demands  Frequent pumping & changing depth can  Provides adequate pressures reduce freezing throughout the water systems  Sandblasting is recommended to prepare  Covered to prevent bacti & inside for painting, inspect every 3 to 5 years algae growth  Stagnant water causes quality problems  Reserve storage   Fire protection They’re most susceptible to water quality degradation from external sources

Parts of a Well Parts of a Well

 Pumps from a geologic formation called an aquifer  Well Screen – unrestricted water flow and  When water passes through porous layers of soil it’s small enough to stop sand from entering called percolation  Gravel pack – aids screen in filtering sand.  Sanitary seal – prevents contamination from entering  Well casing – pipe placed inside well to keep it open  Grout – mixture of cement, water and sand pumped between the casing & the drilling hole (annulus)

17 Wire to Water Efficiency Cavitation

 Energy required to overcome pump inefficiencies  Main cause of losing pump suction  Sounds like pumping rocks or pinging  The combined efficiency of the pump and  Vibration & popping noises caused by low the motor together. Also called the over all pressure in volute efficiency.  Generally caused by vapor bubbles  Water HP HPx100 = % Wire to Water Efficiency  Vapor bubbles implode causing damage to pump Motor HP  Volute case needs to be full of water  (Flow, gpm) (Total Dynamic Head, ft) (0.746 kw/hp) (100) = % WWE  Prevented by having adequate suction (3,960) (Electrical Demand, kilowatts) pressure and proper bowl depths

Cross Connections Air Gap- Safest Method  Cross connection: a connection between a potable & an unapproved source.  A physical break between the  Caused most disease outbreaks end of a pipe and an open  Two Types of Backflow vessel flood rim *Backsiphonage : backflow caused by a negative or • Minimum of 1” or two times the below atmospheric pressure in a water system where diameter of the pipe. a vacuum exists such as draining as system (fire  Backflow protection fighting can cause) • Backsiphonage *Backpressure : when users pressure is higher than  Hazard the system pressure • High degree or health risk  Approved assemblies are used to keep contaminants  Required on all sewer, out the drinking water system wastewater or sludge  Protection established by degree of hazard connections

Meter Sizing Considerations AWWA C651 – Water Mains

 Pressure at the service connection  Methods  Highest fixture in the building being served  Any back flow prevention device  Tablet or granular – 25 mg/l – 24 hours  A 5/8 inch meter should be tested every 5 to 10  Continuous Feed – 10 mg/l after 24 hours years.  Fill main with water  Meter should not have more than 20 psi of head  Flush out debris loss.  Fill with chlorinated water  In absence of a flow meter on a filter you can close the inlet valve and measure the drop over time.

18 AWWA C651 Water Mains AWWA C651-05 Continued

 Final flushing  Slug method  Clearing main of heavily chlorinated water  3 hour exposure of not less than 50 mg/l  Disposing chlorinated water  Start with 100 mg/L and test at intervals on pipe  Discharge can cause damage to the environment  If residual drops below 100 mg/L move equipment  Neutralizing agents  Sulfur dioxide, sodium biosulfates, sodium sulfide, sodium thiosulfates, ascobic acid  Flushing at 2.5 fps  Scour the insides of the pipe.

Procedure existing water mains Bacteriological Testing

 Positive pressure during repairs  Standard Conditions  Swabbing  AWWA C651-05  2 samples - 24 hours apart  Flushing  One set collected every 1200 feet  Slug chlorination  Plus one set from ends of main  300 mg/l – 15 minutes  At least one on each branch  Sampling – to prove procedure effectiveness

Bacteriological Testing Pressure Testing New Water Main

 Special Conditions  Pipe should sit idle for at least 24 hours  Trench water entered  Should be done at 150 psi  Excessive quantities of dirt  Water stand for 16 hours before 1 st test  Or 1.5 times the normal pressures  Sampling procedures  Duration 4 Hours  No hose  No fire hydrant  What does your ordinance say about testing  Orem’s Ordinance

19 Valves Gate Valves - Isolation

 Gate Valve: Isolation, should be either all the way open or all the way closed (least amount of head loss)  Air and vacuum relief: allows air in and air to escape.  Altitude valve: opens when system psi drops below a certain pressure and closes when the reservoir reaches a predetermined level.  Glove valves used for flow & pressure regulating

Altitude Valve – good for regulating tanks Pump Control Valves

 Minimizes water hammer  Starts & stops on a closed valve

Valves Butterfly Valves -

 Pressure Sustaining/Reducing:  Higher resistance to maintain either upstream flow or downstream  Operates easily & pressures depending on quickly the position of the pilot screw.  They cost less than gate valves  Need periodic service & maintenance  Used for flow control

20 Ball & Plug Valves Sluice Gate & Sleeve Valves

Check Valves Water Hammer

 Occurs when a valve is closed quickly or  Permit flow in one pump shuts down and causes the water direction pressures to rise and fall rapidly.  Swing Checks  Sounds like some hammering on pipe.  Spring loaded silent checks  Can damage pipes, causing them burst.

Meter Sizing Considerations Meter Accuracy

 Worn meters under register &  Pressure at the service connection give the customer free water  Highest fixture in the building being served  Over time a worn meter will  Any back flow prevention device cost the water system revenue.  A 5/8 inch meter should be tested every 5 to 10  Formula: Meter Accuracy= years. (Meter,GPM)(100%)/Volume,GPM  Meters should not have more than 20 psi of head  Compound meters are used loss. for low to intermediate flows  Meters one inch and smaller shouldn’t have more & occasionally for high flows than 15 psi of head loss  Venturi meter is not a prime mover

21 Positive Displacement Meter Piston Meter

 Nutating disk : nutating means nodding. When the water flows the disk rotates.  Displacement type  Water flows into a chamber and displaces piston  Oscillating circular motion moves meter  Higher head loss than nutating disk

Air Release Valves Velocity Meter (Air Vac) – air in & out

 Should be placed at high points in the water system.

 Propeller, Venturi, insertion  Outlet should be screened about 12” min. above type, and most electronic ground types  Rotors or propellers are turned be velocity of meter

Air Vacuum Air Release Combination

HYDROPNEUMATIC TANKS Line Collapse

 Frequent on/off cycling indicates water logged tank  Caused by not opening a downstream valve  Operate by applying air pressure to tank before they began  Tank levels controlled by pressure switches to pumps sucking water from the  Air leaks can cause pumps to run continuously other end  1/3 to 2/3 air to water ratio limiting storage capacity  A vacuum developed

before they realized PUMP CONTROL

what happened and the AIR RELIEF pipe pancaked PSI AIR BLADDER OR  The pipe is the main DIAPHRAGM

transmission line to COMPRESSOR OPERATING LEVEL

supply water for the City PUMP PSI WATER LEVEL WATER AT MINIMUM of Folsom OPERATING PSI

22 Acronyms Acronyms

 Forms of expressing a flow of water over a  PSI = pounds per square inch period of time:  The pounds of force on a given area. The area is expressed in a square inch.  GPM 1 inch  Gallons per minute  MGD  Million gallons per day 60 pounds 1 inch  CFS  Cubic feet per second 60 pounds per square inch, or 60 PSI

Acronyms Acronyms

 Methods for measuring chemicals or other  PVC, PE, ABS- refer to chemical composition of pipe constituents in drinking water  Methods for measuring chemicals or other constituents in drinking water  ppb  ppm  Parts per billion  The measure of 1 gallon or lb. of a chemical in 1 billion gallons or  Parts per million lbs. of water  Refers to 1 gallon or lb. of a chemical in 1 million  ug/l gallons or lbs. of water  Microgram per liter  The same measurement as ppb expressed in metric  mg/l measurements  Milligrams per liter  1000 ppb or ug/l = 1 ppm or mg/l  Example: 80 ppb is the same as 0.080 mg/l  The same measurement as ppm expressed in metric measurements

Definitions Fire Hydrants  Toxic  A substance that is poisonous to a living organism.

 Potable  Dry barrel hydrant used in areas  Water that does not contain objectionable pollution, susceptible to freezing. contamination, minerals, or infective agents and is satisfactory to  Drain hole allows water to drain from barrel drink. so water won’t freeze and crack the  Culinary hydrant.  Fit for human consumption.  Hydrant bury is the distance below the  Action Level : ground to the main connection.  Required actions if lead and copper standards are exceeded:  Because of increased population growth  MCL and scaling of pipes, hydrant flow tests  Lead – 15 ppb, or 0.015 ppm should be performed periodically.  Copper – 1300 ppb, or 1.3 ppm

23 If the cut stake for a fire hydrant is marked AC- 4.25 @ and the hydrant is 7 ft. 6 in. tall, how high Thrust Blocking will the top be above the finished grade?  Thrust Block - a concrete mass between a elbows, crosses & tees in undisturbed soil at the side or bottom of the pipe trench .  Keeps fittings from moving & either coming loose or apart  7’ 6” convert to decimal from the force of the water C - 4.25 pressure in the pipe.  7.5 – 4.25 = 3.25  Thrust anchors – used when ? ft.  3.25 is the answer thrust blocks cannot be used  Restrained fitting – use of clamps or anchor screws on fittings 7’6”  Tie rods – used on mechanical 4.25’ joint fittings that a located close together  Should be calculated & designed properly

Thrust Blocks Water Loss

 Affected by: leaks, pressures, efficiency of the meter maintenance, attention given to leak reduction, & unauthorized use of water  Some systems 10% of the water produced  Other systems not until 20%

Lightning Arrestor Screen Sizes

 Becomes a low resistance  #14 mesh for air vents conductor to ground when and air vacuum release the line voltage exceeds a valve #14 predetermined amount  Air vac vent pipe above the flood line  Used to protect equipment  #4 mesh for overflow and from lightning strikes. drain lines  No device made to protect  #14 mesh = 14 squares against a direct hit. per inch #4  #4 mesh = 4 squares per inch

24 Electrolysis Tanks – Cathodic Protection

 Decomposition of material by an outside electric current  Electric current caused by movement of water in the line  Cathodic protection installed to prevent

25