Listed and Certified Gas Detection for Collection Treatment Facilities In Compliance with NFPA 820

Pumping Stations • Wet Wells • Primary Sedimentation • Flow Equalization Tanks • Headworks • Aeration Tanks • Grit Removal • Screening • Disinfection • Clarifiers • Denitrification • De-chlorination • Bar Screen Area • Sludge Storage •Pre- aeration Tanks • Scum Handling Areas • Odor Control Areas • Recovery • Stripping • Sludge Treatment • Digesters In Buildings • Digester Gas Storage / Processing • Underground Tunnels • Co-generation Systems

Detection at every point. Universal Point Gas Monitor Accepting Combustible (Infrared or Catalytic), Toxic, and Oxygen Gas Sensors

Universal 2 or 3-Wire Transmitter Models Accepts All SensAlert Plus Sensors for Toxic or Combustible Gases and Oxygen Deficiency Optional HART and Modbus Communication Protocols

Non-Intrusive User Interface Fully Configurable, Assignable Relays with Time Stamped Calibration-Event Data, Sensor End of Life Data and Warning Test-on-Demand Function for Automated Bump Tests

FM Certified for Hazardous ClassifiedAreas Class I, II and III, Div. 1 or 2 Groups A, B, C, D, E, F and G Performance Tested and Certified Sensors

Intrinsically Safe Sensor Head Simple Remote Sensor or Duct Mount Permits Hot-swap of Sensor for Shop or Field Calibration Hot Work Permit is Not Required

FM Certified Intelligent Sensors Calibration and Application Parameters Stored in Onboard Non-volatile Memory for Auto-recognition and Setup upon Sensor Install

Flexible Installation or Retrofit 2-Wire or 3-Wire Transmitters Remote Sensor / Gassing Configurable Alarms and Fault Currents Conditions

Detection at every point. Listed Gas Detection Sample Draw System The Sensidyne Advantage The Sensidyne SensAlert Plus is FM and CSA approved for unrestricted Hazardous (Classified) Area installation and operation. Plus Series Combustible, Toxic, and Oxygen gas sensors are performance tested and certified to FM and ATEX standards for assured reliability. The sensor head is certified Intrinsically Safe enabling shop calibration and hot-swap without declassifying the area. System components, such as Sample Draw, are also FM approved and Listed as required by NFPA 820. Sensidyne understands wastewater applications and works directly with customers to deliver effective and reliable solutions to their gas detection requirements. Sales and on-site service personnel are knowledgeable and experienced to help resolve application issues and provide local training and ongoing support. Typical Wet Well Gas Detection System with Sample Draw Class 1 Division 2 or Non-Hazardous Area Alarm Contacts 4-20 mA RS-485 PRODUCT SPECIFICATIONS 24 VDC Enclosure AC or DC Power In Material.... NEMA 3R Fiberglass wall mount with two 3/4” conduit entries AC Annunciation Dimensions:...... 11” (H) X 10” (W) X 6.375” (D) (27.9cm X 25.4cm X 16.2cm) Weight:...... 6.6 lbs (3.0 kg) Temperature:...... -4° to 104°F (-20° to 40°C) Air Sample From Class I, Division 1, Humidity: ...... 5-95% RH, non-condensing for Group C or D Area indoor or outdoor locations. Indicators and Controls External: ...... Flowmeter, green power LED and Coalescing red fault/low flow LED Outdoor Vent 3-Way Calibration Filter + Drain Internal: ....On-Off switch, voltage out adjust and Valve Gas Inlet flow rate adjust Outputs: ...... Two 24 VDC power terminals, Gas Formula Density TLV/LEL Span Type Part Number SPDT fault/low flow relay contact Power In/Out: .85–264 VAC, 47-63 Hz, 1.2 Amps; * Ammonia NH3 0.6 25 ppm/15% 100 ppm LI, EC, D 823-0201-21 24 VDC, 1.1 Amp max. Ammonia* NH3 0.6 25 ppm/15% 300 ppm LI, EC, D 823-0201-41 Approvals Hazloc...... FM approved* for Class I, CO2 1.5 0.5%, 3% IDLH 5% vol Infrared 823-0205-52 Division 2, Groups C & D * CO 1.0 50 ppm 100 ppm EC, ND 823-0219-23 location to sample from Class I, Division 2,Groups C & D; Bleach (Use Cl2) NaClO2 2.5 0.5 ppm 5 ppm LI, EC 823-0202-22 DC Supply:...... UL60950-1, UL508, UL1310(3), Chlorine* Cl2 2.5 0.5 ppm 5 ppm LI, EC 823-0202-22 EN60950-1, CE Mark Pump:...... Diaphragm type rated at 1.0 lpm @ * Chlorine Cl2 2.5 0.5 ppm 10 ppm LI, EC 823-0202-21 40” H2O at pressurized leak rate of HC Mixture 2 to 4 1.2% vol 100% LEL Infrared 823-0211-51 < 1.0 inch wc drop in 5 seconds at 25 inches wc * Hydrogen Chloride HCl 1.3 2.0 ppm 20 ppm EC, ND 823-0208-22 Wetted parts:...... Polycarbonate, Neoprene, * H2S 1.2 1.0 ppm 10 ppm EC, ND 823-0206-23 Tygon 2075, Silicone Silastic, 304/316ss, Buna-N, Brass, PVC, Glass, Acrylic Hydrogen Sulfide* H2S 1.2 1.0 ppm 50 ppm EC, ND 823-0206-22 and User Tubing Hydrogen Sulfide* H2S 1.2 1.0 ppm 100 ppm EC, ND 823-0206-21 Cautions Do not use for Acid gases such as Cl2, ClO2, HCl, Methanol CH3OH 1.1 200 ppm/250 ppm STEL 500 ppm EC, ND 823-0253-21 HF, HCN, NH3, NO2, SO2 and others since the Methanol CH3OH 1.1 6.0% vol 100% LEL Infrared 823-0211-51 PPM gases are absorbed by the tubing, moisture and various wetted parts slowing or completely Natural Gas CH4 0.63 3.8-6.5% vol 100% LEL Infrared 823-0211-51 eliminating response to the target gas. Do N2 Monitor O2 Deficiency ------not attempt to use below freezing without heat tracing and a means to keep the system Oxygen O2 ~1.0 19.5%, 18.0% IDLH 25% vol EC, D 823-0240-22 above 32⁰ F (0⁰ C). Excessive condensation will Sewer Gas CO2, CH4 ~1.0 5.3% vol 100% LEL Infrared 823-0211-51 occur when sampling from a higher to a lower temperature. Sludge Gas CH4, CO2 ~0.8 5.0% vol 100% LFL Infrared 823-0211-51

Sulfur Dioxide* SO2 2.3 2.0 ppm 10 ppm EC, ND 823-0218-22 * FM approval pending.

* Additional Ranges Available LI: Low Interference; EC: Electrochemical; D: Depleting with Gas Exposure; ND: Non-depleting with Exposure TLVs from ACGIH or OSHA, IDLH from NIOSH, STEL from ACGIH, LELs from NFPA 325 and NFPA 820 SensAlert Plus Exploded View Waste Treatment Is Big Business Remote Sensor Kits Nearly 16,000 municipal sewage collection and treatment systems in the US, serve over 1 75 percent of the population 1. The facilities have exceptional regulatory2 , environmental and safety requirements 3 with quality of life 3 consequences for everyone. 2 Sewage collection systems operate on gravity 4 flow to central lift or pumping stations which deliver the raw sewage to a treatment plant. Sewage decomposition produces Sewer Gas (Carbon Dioxide, Methane, Hydrogen Sulfide, et al) which presents Oxygen deficiency, toxic gas and the risk of fire or explosion hazards. Remote Calibration Fixture Fuels and industrial solvents might also be in 821-0218-01 the collection system. All of these gases and Run rigid condulet to transmitter. 5 vapors require monitoring to provide early warning of life threatening conditions. Remote mounted gas sensors with remote gassing simplify monitoring Wet Wells and screening difficult access areas for Methane or exposes workers to sewer gas or floating other hazards. Sensors may also be duct mounted in the same manner. 6 7 4 flammables and these areas are Hazardous , The Transmitter is at face level for Class I, Division 1, Group D. Placing electronic ease of routine maintenance. equipment in wet corrosive environments subject to flooding is not practical and Part Numbers 8 821-0207-02 Division 1 seldom done anymore. Listed Sample 823-0207-01 Division 2 Draw or remote mounted Intrinsically Safe 100 Feet Maximum 5 sensors from Sensidyne are a lower-cost Belden 27326AS 9 and minimal maintenance solution for all Cable by others. Bracket, Condulet, Seal, and hazards. Cable Glands Furnished. 10 Treatment plant applications vary widely but 11 have similar conditions to pumping stations. Sensidyne has proven solutions and support 12 13 for all water and waste water treatment gas detection applications.

Footnotes and References 1 US EPA, 832-R-04-001, September 2004, Office of Wastewater Management, Washington DC 20460 2 The Federal Water Pollution Control Act of 1948, 1972 Amendments to Poured Seal Clean Water Act, and continuing Amendments to 2011 14 3 NFPA 820, Standard for Fire Protection in Wastewater Treatment and Required in Collection Facilities, 10 States Recommended Standards for Wastewater Facilities, Great Lakes - Upper Mississippi River Board of Division 1 State and Provincial Public Health 4 NFPA 70, National Electrical Code, Article 500, Hazardous (Classified) Locations. 5 Intrinsically safe equipment and wiring shall not be capable of releasing sufficient electrical or thermal energy under normal or abnormal conditions to cause ignition of a flammable or combustible 1. Enclosure Certified for Hazardous (Classified) Environments atmospheric mixture in its most easily ignitable state. 2. Large Backlit Alphanumeric Display (Backlit on 3-Wire only) 3. HART or Modbus RS-485 Communication (Optional) 4. Alarm Relay Card (Optional) Detection at every point. 5. Intrinsically Safe Sensor Head 6. Test-on-Demand Gas Generator 7. Plus Series Intelligent Sensor 8. O-ring Seal 9. Sensor Retainer 10. Moisture Barrier (Optional) 11. Remote Gassing Fixture (Optional) 12. Sensor Shield 13. Flow Block for Remote Sampling and Cal Plug (Optional) 14. Baffled Rainshield (Optional)

© 2013 Sensidyne, LP — WWTP-Brochure-Rev. B 02.13.13

1000 112th Circle North, Suite 100 • St. Petersburg, Florida 33716 • U.S.A. Tel: 800-451-9444 / +1 727-530-3602 • Fax: +1 727-539-0550 [email protected] • www.SensidyneGasDetection.com