Section 26 05 19 Insulated Wires and Cables

Total Page:16

File Type:pdf, Size:1020Kb

Section 26 05 19 Insulated Wires and Cables Regional Connector Transit Corridor Project SECTION 26 05 19 INSULATED WIRES AND CABLES PART 1 - GENERAL 1.1 DESCRIPTION The Work specified in this Section consists of furnishing and installing wires and cables as specified and as indicated. 1.2 QUALITY CONTROL Comply with Section 01 43 10, Project Quality Program Requirements - Design/Build. 1.3 REFERENCE STANDARDS Comply with the latest issuance of each referenced standard and code. A. American National Standards Institute (ANSI) ANSI MC96.1 Temperature Measurement Thermocouples B. American Society for Testing and Materials (ASTM) ASTM B3 Soft or Annealed Copper Wire C. Institute of Electrical and Electronics Engineers (IEEE) IEEE 383 Type Test of Class 1E Electric Cables, Field Splices, and Connections for Nuclear Power Generating Stations D. International Cable Engineers Association (ICEA) E. National Electrical Manufacturers Association (NEMA) ANSI/ICEA S-95-658 / NEMA WC 70 Non-shielded 0-2kV Cables ANSI/ICEAS-96-659 / NEMA WC 71 Non-shielded 2001-5kV Cables ANSI/ICEA S-93-639 / NEMA WC 74 Shielded Power Cable 5-46 kV F. National Fire Protection Association (NFPA) NFPA 70 National Electrical Code (NEC) NFPA 130 Standard for the Design of Fixed Guideway Transit Systems INSULATED WIRES AND CABLES ISSUED: 08/02/13 METRO C0980 26 05 19 - 1 Regional Connector Transit Corridor Project G. Underwriters Laboratories Inc. (UL) UL 62 Flexible Cord and Fixture Wire 1.4 SUBMITTALS Refer to Section 01 33 00, Submittals, for submittal procedures. A. Manufacturer Product Data - Before installation of wire and cable, submit a list of proposed wires and cables to be provided for the electrical installation, identifying the typical application, usage and location of each submitted wire and cable data sheet. Submit the following information for each type and size of wire and cable: 1. Manufacturer of wire and cable. 2. Number and size of strands composing each conductor. 3. Conductor insulation composition and thickness in mils. 4. Average overall diameter of finished wire and cable. 5. Minimum insulation resistance in megohms per 1000 feet at 20°C ambient. 6. Jacket composition and thickness in mils. 7. Total number of conductors per cable. 8. Shield materials and thickness. 9. Conductor resistance and reactance in ohms per 1000 feet at 20°C ambient. 10. Conductor ampacity at 20°C ambient. 11. Bending radius of cable sizes larger than 1/0. 12. Cable weight per linear foot. PART 2 - PRODUCTS 2.1 GENERAL REQUIREMENTS A. Furnish cables, conduits, cable assemblies and support hardwares for feeders and branch circuits, as described in the following articles 2.2 to 2.11, as required to comply with Metro Design Criteria, the National Electrical Code (NEC) and the following requirements: 1. NFPA 130 rating, UL equipment listing and ASTM E136 non-combustible material requirements. 2. All conductors shall be insulated and shall be listed for wet locations. Insulation INSULATED WIRES AND CABLES ISSUED: 08/02/13 METRO C0980 26 05 19 - 2 Regional Connector Transit Corridor Project shall be moisture and heat-resistive type and shall conform to NFPA 70 cable insulation requirements. 3. Listed for resistance to the spread of fire and reduced smoke emissions per FT4/IEEE 1202 exposure requirements and peak release rate requirements of ANSI/UL 1685. 4. Branch circuit rating and listing requirements shall be based on the location of branch circuits and the type of loads supported as either life safety system related or non-life safety system related, as defined in Metro’s Life Safety Design Criteria, and applying the requirements of items 1 through 3 listed above. In general, life safety system equipment loads and associated branch circuiting are those supporting the operation of systems that provide the safe egress of patrons from stations and tunnels during a fire or other life safety related event. These systems typically include: 1) Emergency egress lighting. 2) Emergency ventilation. 3) Fire detection and protection systems. 4) Gas detection systems. 5) Emergency communications. 6) Emergency control systems. 2.2 CONDUCTORS A. Type - ICEA stranded copper, soft drawn. B. Insulation Rating: 600 volts. 2.3 CABLES A. Non-Life Safety System Branch Circuit Cables: 1. Size 1/0 AWG and Smaller - NFPA 70 Type XHHW, cross-linked-thermosetting- polyethylene-insulated in accordance with NEMA WC70, WC71 and WC74 or NFPA 70 Type RHW, ethylene-propylene-rubber-insulated neoprene, Hypalon or CPE jacketed in accordance with NEMA WC 70. Compliant with NFPA 130 -5.4 and -6.33 Wiring Requirements. 2. Size 2/0 AWG and Larger - NFPA 70 Type RHW, ethylene-propylene-rubber- insulated, neoprene, Hypalon or Type CPE jacket and has better abrasion resistance when pulled through uncleaned conduits. Jacketing in accordance with NEMA WC 70. Compliant with NFPA 130 -5.4 and -6.33 Wiring Requirements. 3. Temperature ratings of cables - Not less than 90°C. INSULATED WIRES AND CABLES ISSUED: 08/02/13 METRO C0980 26 05 19 - 3 Regional Connector Transit Corridor Project 4. Use multiple conductor cable for power applications, except receptacles and when otherwise indicated, and when installed in cable tray for sizes up to 4/0. 5. Control wires: Provide multi-conductor type cables, minimum size No. 14 AWG stranded copper, except wiring between CIC compartments, where a minimum of No. 16 stranded copper can be used. 6. Jacketed over insulation suitable for installation in cable tray. B. Life Safety Branch Circuit Cables: 1. Compliant with NFPA 130 branch circuit rating and UL listing requirements. 2. 1 hour rated cables UL 2196 listed, or conductors included as part of a listed UL 2196 assembly, meeting the following requirements: a. NFPA 70 Type RHW-2, copper conductor with cross-linked polyethylene (XLP) Insulation, jacketing NEMA WC 70 and RoHS/REACH compliant, or equivalent conductor, provided as part of an assembly tested and listed per UL 2196 listing requirements. b. Pass flame propagating criteria of IEEE 383 and with minimum circuit time of five minutes in flame test of IEEE 383. Type test certificate is required with every shipment of cables. c. Temperature ratings of cables - Not less than 90°C. d. Cable assemblies capable of withstanding a sustained fire with a temperature of 250°C (482°F) for a minimum of one hour. 3. 2 hour rated cables UL 2196 listed, or conductors included as part of UL 2196 assembly, meeting the following requirements: a. NFPA 70 type RHW-2, copper conductor with cross-linked polyethylene (XLP) insulation, jacketing NEMA WC 70 and RoHS/REACH compliant, or equivalent conductor, provided as part of an assembly tested and listed per UL 2196 listing requirements. b. Pass flame propagating criteria of IEEE 383 and with minimum circuit time of five minutes in flame test of IEEE 383. Type test certificate is required with every shipment of cables. c. Temperature ratings of cables - Not less than 90°C. d. Cable assemblies capable of withstanding a sustained fire with a temperature of 250°C (482°F) for a minimum of two hours. 2.4 METAL CLAD CABLE A. Metal clad cable with single or multiconductor configuration with ground wire compliant with NFPA 70 metal clad cable requirements. INSULATED WIRES AND CABLES ISSUED: 08/02/13 METRO C0980 26 05 19 - 4 Regional Connector Transit Corridor Project B. Conductor: Annealed copper Class B strand per ASTM B-3 & B-8. C. Insulation Material: low smoke zero halogen polymer meeting listing requirements. D. Armor: Continuously welded and corrugated copper. E. 1 hour fire rated power cable. F. Listed per UL 2196 requirements. G. UL listed in accordance with NFPA 70 Type MC UL standard 1569. H. UL listed for CT (cable tray) use. 2.5 MINERAL INSULATED CABLE A. NFPA 70 Mineral Insulated (MI) cable type with single or multi-conductor configurations with ground wire compliant with NFPA 70 Article 332 requirements. B. Conductor: Solid high conductivity copper C. Insulation Material: Magnesium Oxide D. Insulation Voltage Rating: 600 Volts E. Cabling Rating: 90°C F. Cable Sheath/Armor: Seamless soft-drawn copper G. Listing: UL 2196 2 hour listed cable 2.6 FIXTURE WIRE UL 62 with following additional requirements: A. Type - SF-2 silicone rubber insulated. B. Conductor - Stranded copper conductor 16 or larger as indicated. 2.7 BARE CONDUCTOR ASTM B3, Class B stranded annealed soft-drawn copper conductor unless otherwise indicated, size as indicated. Bare conductor - Use for internal equipment ground connections only. Feeders and branch circuit ground conductors provided with insulation per article 2.2 and 2.3 with green colored jacket. 2.8 THERMOCOUPLE CABLE Provide thermocouple cable with solid conductors meeting requirements of ANSI MC96.1 and of type compatible with thermocouple leads furnished with motor or temperature sensor. Thermocouple cable - Flame-retardant insulation, pair assembled with left-hand lay, flame-retardant outer jacket, with overall shield and UL listed as Type INSULATED WIRES AND CABLES ISSUED: 08/02/13 METRO C0980 26 05 19 - 5 Regional Connector Transit Corridor Project PLTC. 2.9 COLOR CODING OF CONDUCTORS A. Color code of multiple conductor, 120 VAC control cables - Conform to NEMA WC 57 or as indicated. B. Color code power supply cables and branch circuit conductors throughout secondary alternating current wiring system as follows: CONDUCTOR 208/120 VOLTS 480/277 VOLTS A Black Brown B Red Orange C Blue Yellow Neutral White White Ground (Communication) Green Green Ground (Power) Bare/Green Bare/Green C. Branch circuit phase conductors No. 10 and smaller, neutral and equipment ground conductors - Solid color insulation or solid color coating. D. Phase conductors having colored tracers - Background color other than white or green. E. Solid color coatings and tracers - A strongly adherent paint or dye non damaging to the insulation, will not fade, and which will not be obliterated by pulling into a conduit or raceway.
Recommended publications
  • 2020 National Electrical Code® Style Manual
    2020 NATIONAL ELECTRICAL CODE® STYLE MANUAL 1 FOREWORD August 2020 The National Electrical Code® is used nationally and internationally as the basis for safeguarding persons, buildings, and their contents from hazards arising from the use of electricity. It is vitally important that the text be as explicit as possible, and that maximum consistency be achieved in the language used in the text. The Code contains those provisions considered necessary for safety and thus is widely used as a basis for legal enforcement in the installation of electrical conductors and equipment in buildings and certain other premises (as detailed in the Code itself); this places a major responsibility on those involved in the preparation of document text to use forms of expression that promote uniform interpretation. The National Electrical Code Correlating Committee has recognized these responsibilities and has issued this manual. Preparation and Date of Adoption. This manual was originally prepared by the Editorial Task Group of the National Electrical Code Committee and adopted by the National Electrical Code Correlating Committee on May 13, 1969. It was amended September 22, 1975, October 11, 1984, October 12, 1989, and May 9, 1994. In January 1999, the Correlating Committee Task Group on the Usability of the NEC rewrote the manual. It was adopted by the National Electrical Code Correlating Committee on March 19, 1999 and by the Standards Council on April 15, 1999. It was amended March 1, 2001, January 15, 2003, and August 9, 2011, August 2015, and December 2020. 2 TABLE OF CONTENTS Foreword ........................................................................................................ 2 Chapter 1 General 4 1.1 Purpose ............................................................................................
    [Show full text]
  • 90 INTRODUCTION to the National Electrical Code
    ARTICLE INTRODUCTION TO THE 90 NATIONAL ELECTRICAL CODE Introduction to Article 90—Introduction to the National Electrical Code Many NEC violations and misunderstandings wouldn’t occur if people doing the work simply understood Article 90. For exam- ple, many people see Code requirements as performance standards. In fact, the NEC requirements are bare minimums for safety. This is exactly the stance electrical inspectors, insurance companies, and courts take when making a decision regard- ing electrical design or installation. Article 90 opens by saying the NEC isn’t intended as a design specification or instruction manual. The National Electrical Code has one purpose only, and that’s the “practical safeguarding of persons and property from hazards arising from the use of electricity.” The necessity of carefully studying the NEC rules can’t be overemphasized, and the role of textbooks such as this one is to help in that undertaking. Understanding where to find the rules in theCode that apply to the installation is invaluable. Rules in several different articles often apply to even a simple installation. Article 90 then describes the scope and arrangement of the NEC. The balance of this article provides the reader with informa- tion essential to understanding the Code rules. Typically, electrical work requires you to understand the first four chapters of theNEC which apply generally, plus have a working knowledge of the Chapter 9 tables. That understanding begins with Article 90. Chapters 5, 6, and 7 make up a large portion of the Code, but they apply to special occupancies, special equipment, or other special conditions.
    [Show full text]
  • Industrial MI Wiring Cable
    Industrial MI Wiring Cable Installation Manual for Alloy 825 Sheath Cable Wiring Systems Important Safeguards and Warnings WARNING: FIRE AND SHOCK HAZARD. nVent PYROTENAX mineral insulated (MI) industrial wiring cables must be installed in accordance with the requirements of national and local codes and standards, the installation instructions in this manual, and the customer’s specification. Read these important safeguards and carefully follow the installation instructions. • Ensure the cable has been stored properly and is in good condition prior to commencing installation. • Always use safe working practices when installing cables, observing OSHA and other national safety rules. • Store cables indoors in a clean, dry, covered area, if possible. • During the time that the cables are exposed and during cable pulling activities, protect cables from nearby or overhead work to prevent damage to the cable sheath. • Do not pull cables around corners that have sharp edges, such as corners in cable trays, or other obstructions. • Prevent damage to cables by removing any abrasions or sharp edges from surface of support system. • Damage to cables or components can cause sustained electrical arcing or fire. Do not energize cables that have been damaged. Damaged cable or terminations may need to be repaired or replaced. Damaged cable should be repaired by a qualified person. • When installing cables which may be exposed to hydrocarbon flash fires, use only steel or stainless steel in the support system. ii | nVent.com Table of Contents General Information
    [Show full text]
  • 2011 National Electrical Code Amendments
    541 DeKalb Avenue Sycamore, IL 60178 Building (815) 895-4434 Building & Engineering Department Engineering (815) 895-4557 Fax (815) 895-7572 2011 NATIONAL ELECTRICAL CODE AMENDMENTS The 2011 National Electrical Code (NEC), adopted in Section 9-4-1, Subsection A of the Sycamore City Code as the electrical code of the City, is amended and revised in the following respects: 1. Service Equipment – Disconnecting Means: Means shall be provided to disconnect all conductors in a building from the service entrance conductors. The service disconnecting means shall be installed at a readily accessible location either outside the building or inside the building nearest the point of entrance of the service conductors. The maximum distance from the point of entrance of service conductors to a readily accessible service disconnecting means shall be six (6) feet. 2. All residential, commercial and industrial electrical services shall be installed with rigid metal conduit (RMC) or intermediate metal conduit (IMC). PVC and service entrance cable is not allowed. Electrical metallic tubing (EMT) is permitted between the meter enclosure and the electrical panel only if compression fittings are used and provided the EMT exits the back of the meter enclosure and is not exposed to weather. 3. When additional grounding is required for hot tubs, spas or similar equipment, the grounding conductor is allowed to be located at the cold water pipe of that piece of equipment provided the ground clamp is accessible. If the ground clamp is not accessible, a minimum #8 insulated copper conductor shall be run from the motor or pump back to the electrical panel.
    [Show full text]
  • Electrical Safety in the Workplace® ARTICLE 90 Introduction
    ARTICLE 90 — INTRODUCTION 90.2 NOTE: The following draft shows how the draft of the proposed 2012 edition of NFPA 70E looks based on NFPA ARTICLE 90 staff’s reading of the Committee Actions contained in the Introduction NFPA 70E Technical Committee Report of the Technical Committees on Electrical Safety in the Workplace (i.e., the Committee Actions in the Report on Proposals). NFPA Staff 90.1 Purpose. The purpose of this standard is to provide a frequently prepare and make available drafts such as this as practical safe working area for employees relative to the an aid to participants in reviewing Technical Committee hazards arising from the use of electricity. Reports. Participants are encouraged to review this Report on Proposals and to raise any issues they believe need reso- 90.2 Scope. lution through the making of appropriate comments. Please (A) Covered. This standard addresses electrical safety re- submit your public comments on the proposals, not on the quirements for employee workplaces that are necessary for draft. As mentioned previously, the draft is only an aid for the practical safeguarding of employees during activities reviewing the document, incorporating the proposals. such as the installation, inspection, operation, maintenance, For further information on NFPA codes and standards and demolition of electric conductors, electric equipment, development rules or on how to participate in the NFPA signaling and communications conductors and equipment, codes and standards development process, check the NFPA and raceways for
    [Show full text]
  • International Electrical Standards & Regulations
    International electrical standards & regulations AN OVERVIEW OF ELECTRICAL INSTALLATIONS Introduction to the installations world he world of electrical installations knowledge of the wiring suited to your specific Tis not always straightforward. regulations and standards requirements in terms of Working on an international project which are applicable in electrical installations and electrical engineers are often bewildered the specific country. communication networks. by the extensive amount of electrical This document compares Continuous innovation standards and wiring regulations which the basic framework No less than 1 800 determines their decisions. of the standards. people are dedicated Therefore, it is essential full-time to research and Rely on the world’s Detailed knowledge for the design engineer development. On average, leading specialist of the wiring rules to obtain more detailed Legrand invests 5% of its As one of the world The purpose of this information by contacting sales each year in R&D. leading specialists document is to clearly the appropriate standards in wiring accessories, present the most and building regulations Sustainable Legrand actively participate frequently encountered organisations. Development: a priority to the elaboration of the sets of wiring rules, For many years, installation standards showing the main One of the most complete the Legrand Group at international (IEC), technical characteristics offer of the market has drawn strength regional (NEC) and local of each set of installation 130 000 catalogue items! from its values to ensure levels. Thus, the technical and main accessories For you, the wealth profitable, sustainable expertise of the Legrand standards. Obviously, on of the Legrand Group’s and responsible growth people makes it possible any given project, it is catalogue offer is the in its business.
    [Show full text]
  • Supply Circuit Disconnecting Means with Rotary Handles in Compliance with NFPA 79 and UL 508A
    www.eaton.com www.moeller.net Supply circuit disconnecting means with rotary handles in compliance with NFPA 79 and UL 508A Technical Paper Dipl.-Ing. Wolfgang Esser Supply circuit disconnecting means with rotary handles in compliance with NFPA 79 and UL 508A – Fulfilling key requirements of relevant North American standards – Abstract Introduction machinery, particularly those involving IEC style door mounted rotary handles, Differences between IEC and North In the IEC world the rotary handle is the its primary goal naturally is not to make American standards already become popular choice, and it’s by far the most component design more difficult, but apparent when discussing even the most widely encountered type of operating rather to provide industry floor person- basic of component accessories, such as handle for main disconnect switches in nel with an extra measure of protection the operating handle of a supply circuit these various countries. In the US and from electric shock through the use of disconnecting switch. For example, main Canada, the situation is markedly differ- suitable enclosures, specifically the disconnect switches equipped with door ent, and the use of similar rotary handles need for adequate interlocking provi- mounted rotary handles, and installed in for main disconnect switch applications sions with the supply disconnecting industrial control panels for industrial is not nearly as prevalent, chiefly due to means whenever there is the potential machinery applications, essentially the fact that the conventionally door for exposure to live equipment. require the use of an additional internally mounted operating handle separates The new supplementary handles Type mounted supplemetary handle in order to from the switch when the door is NZM…-XHB-DA(R)-NA from Eaton meet all of the requirements found in the opened, and this feature is considered Moeller fulfill all of the more stringent relevant North American standards deal- less than desirable.
    [Show full text]
  • IS 12640-1 (2008): Residual Current Operated
    इंटरनेट मानक Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information under the control of public authorities, in order to promote transparency and accountability in the working of every public authority, and whereas the attached publication of the Bureau of Indian Standards is of particular interest to the public, particularly disadvantaged communities and those engaged in the pursuit of education and knowledge, the attached public safety standard is made available to promote the timely dissemination of this information in an accurate manner to the public. “जान का अधकार, जी का अधकार” “परा को छोड न 5 तरफ” Mazdoor Kisan Shakti Sangathan Jawaharlal Nehru “The Right to Information, The Right to Live” “Step Out From the Old to the New” IS 12640-1 (2008): Residual Current Operated Circuit - Breakers for Household and Similar Uses, Part 1: Circuit-Breakers Without Integral Overcurrent Protection (RCCBs) [ETD 7: Low Voltage Switchgear and Controlgear] “ान $ एक न भारत का नमण” Satyanarayan Gangaram Pitroda “Invent a New India Using Knowledge” “ान एक ऐसा खजाना > जो कभी चराया नह जा सकताह ै”ै Bhartṛhari—Nītiśatakam “Knowledge is such a treasure which cannot be stolen” IS 12640 (Part 1) :2008 IEC 61008-1:1996 Indian Standard RESIDUAL CURRENT OPERATED CIRCUIT- BREAKERS FOR HOUSEHOLD AND SIMILAR USES PART 1 CIRCUIT-BREAKERS WITHOUT INTEGRAL OVERCURRENT PROTECTION (RCCBS) (First Revision ) ICS 29.120.50 @ 61S 2008 BUREAU OF INDIAN STANDARDS MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG NEW DELHI 110002 Apti 2008 Price Rs.
    [Show full text]
  • Electrician's Exam Preparation Guide to the 2017
    Buy this title complete here: http://bit.ly/2yP4hOJ $67.99 ELECTRICIAN’S EXAM PREPARATION GUIDE Tenth Edition Based on the 2017 NEC® by John E. Traister Revised and Updated by Rob Adair IncludesOnline inside the backPreview cover: Inside the back cover of this book you’ll find a software download certificate. To access the download, follow the instructions printed there. Contains all the questions in the book in interactive self-test software that makes studying almost fun. Each answer is explained, and shows the pertinent NEC® section at the click of the mouse. Use the study mode to get an immediate response on each answer. Use the exam mode for a timed exam — just like the real one, and see your grade when finished. ® Craftsman Book Company 6058 Corte del Cedro, Carlsbad, CA 92011 Buy similar Craftsman Book Co. titles here: https://www.Craftsman-Book.com Buy this title complete here: http://bit.ly/2yP4hOJ Acknowledgments We are indebted to several individuals and organizations who helped in the preparation of this book. One group is the electrical examining boards throughout the United States. A list of these organiza- tions appears in Appendix I of this book. The following were especially helpful in furnishing refer- ence materials or else helping with the production. National Fire Protection Association® (NFPA®) C. Keeler Chapman, Artwork John D. Lee, Sr., Question Verification & Code Consultant Portions of this publication are reprinted with permission from NFPA 70®-2017 National Electrical Code®, Copyright® 2016 National Fire Protection Association, Quincy, MA 02169. This reprinted material is not the complete and official position of the National Fire Protection Association on the referenced subject, which is represented only by the standard in its entirety.
    [Show full text]
  • Conductor Sizing and the National Electrical Code
    Conductor Sizing and the National Electrical Code The National Electrical Code requirements for conductor sizing and overcurrent protection have always been confusing and complex. Factors that must be consider include: 1. Continuous loads 2. Terminal temperature ratings 3. Conductor insulation 4. Conductor ampacity 5. Special application 6. System voltage NEC Section 240-3 requires the branch circuit, feeder, and service conductors to be protected against overcurrent in accordance with their ampacities as specified in Table 310-16. However, Section 240-3 contains twelve rules that modify the general requirement and permit the conductors not to be protected in accordance with their ampacities, they include: 1. Power Loss Hazard 2. Devices Rated 800 Amperes or Less 3. Tap Conductors 4. Motor-Operated Appliance Circuit Conductors 5. Motor and Motor-Control Circuit Conductors 6. Phase Converter Supply Conductors 7. Air-Conditioning and Refrigeration Equipment Circuit Conductors 8. Transformer Secondary Conductors 9. Capacitor Circuit Conductors 10. Electric Welder Circuit Conductors 11. Remote-Control, Signaling, and Power-Limited Circuit Conductors 12. Fire Alarm System Circuit Conductors With so many different Code rules that modify the general requirements, it does become overwhelming to a circuits conductor and overcurrent protection device. However the following steps and examples should help you understand the basic rules of conductor sizing and protection. Step 1 - Size the overcurrent protection device in accordance with Sections 210-20(a), 215-3, and 384-16(d). These three NEC rules required the overcurrent protection device (breaker or fuse) be sized no less than 100% of the noncontinuous load, plus 125% of the continuous load.
    [Show full text]
  • Arc Fault Circuit Interrupter Explained
    What is an Arc Fault Circuit Interrupter? Courtesy of Wikipedia, the free encyclopedia An Arc Fault Circuit Interrupter (AFCI ) is a circuit breaker designed to prevent fires by detecting a non-working (i.e., non-intended/non-useful) electrical arc and disconnect power before the arc starts a fire. An AFCI should, but does not always, distinguish between a working arc that may occur in the brushes of a vacuum cleaner, light switch, or other household devices and a non-working arc that can occur, for instance, in a lamp cord that has a broken conductor in the cord from overuse. Arc faults in a home are one of the leading causes for household fires.[1] AFCI’s resemble a GFCI/RCD (Ground- Fault Circuit Interrupt/Residual-Current Device) in that they both have a test button, although it is important to distinguish between the two. GFCIs are designed to protect against electrical shock, while AFCIs are primarily designed to protect against arcing and/or fire. Electrical Code Requirements Starting with the 1999 version of the National Electrical Code (NEC, also called NFPA 70) in the United States and the 2002 version of the Canadian Electrical Code in Canada (CSA Standard C22.1), the national codes require AFCIs in all circuits that feed receptacles in bedrooms of dwelling units. This requirement is typically accomplished by using a kind of circuit-breaker (defined by UL 1699) in the breaker panel that provides combined arc-fault and over current protection. Not all U.S.A. jurisdictions have adopted the AFCI requirements of the NEC as written.
    [Show full text]
  • Chapter 10 TEMPLE ELECTRICAL CODE
    Chapter 10 TEMPLE ELECTRICAL CODE ARTICLE I - GENERAL PROVISIONS Section 10-1. Short Title. Section 10-2. Purpose. Section 10-3. Electrical Code Adoption. Section 10-4. Definitions. ARTICLE II – ELECTRICAL OFFICIAL Section 10-5. Designated officials. Section 10-6. Qualifications and appointment of the electrical official. Section 10-7. Authority of electrical official. ARTICLE III – ADMINISTRATION OF CODE Section 10-8. Application of code. Section 10-9. Standards and requirements. Section 10-10. Electrical inspectors. Section 10-11. Authority to inspect. Section 10-12. Appeals; Interpretation of code. ARTICLE IV – AMENDMENTS TO NATIONAL ELECTRICAL CODE 2008 Section 10-13. Conductors. Section 10-14. Wiring methods. Section 10-15. Receptacles and switches. Section 10-16. Fireplaces with electric blowers. Section 10-17. Grounding electrode system. Section 10-18. Grounding. Section 10-19. Service requirements Section 10-20. Lighting and appliance panel boards Section 10-21. Fusible disconnects. Section 10-22. Swimming pools, fountains and similar installations. ARTICLE V - LICENSES Section 10-23. Licenses required. ARTICLE VI – TYPES OF LICENSES AND REQUIREMENTS Section 10-24. Electrical contractor. Section 10-25. Electrical sign contractor. Section 10-26. Master electrician. Section 10-27. Master sign electrician. Section 10-28. Journeyman electrician. Section 10-29. Journeyman sign electrician. Section 10-30. Residential wireman. Section 10-31. Apprentice electrician. Section 10-32. Maintenance electrician. ARTICLE VII – PERMITS AND INSPECTIONS Section 10-33. Permits Required. Section 10-34. Application requirements. Section 10-35. Cancellation of permit. Section 10-36. Permits not transferable. Section 10-37. Revocation of permit. Section 10-38. Duration of permit. Section 10-39.
    [Show full text]