<<

buildings

Article Keeping Cool in the Desert: Using Wind Catchers for Improved and at Half the

Jamal Saif 1, Andrew Wright 2 , Sanober Khattak 2,* and Kasem Elfadli 3

1 Independent Researcher, Leicester LE1 4PF, UK; [email protected] 2 Faculty of Computing, Engineering and Media, De Montfort University, Leicester LEI 9BH, UK; [email protected] 3 Environmental Health Department, College of Health Sciences, The Public Authority for Applied Education and Training (PAAET), Shuwaikh, Kuwait; [email protected] * Correspondence: [email protected]

Abstract: In hot arid climates, in the summer dominates energy use in buildings. In Kuwait, energy demand in buildings is dominated by , which also determines the national peak demand. Schools contribute significantly to cooling demand, but also suffer from poor ventilation. This paper presents analysis of a ventilation and cooling system for school classrooms using a wind catcher for natural ventilation and evaporative cooling. A school classroom in Kuwait with single-sided ventilation was modelled using the DesignBuilder V5.4/EnergyPlus V9.1 software and calibrated using field data. The model was used to analyse the performance of a wind catcher, with and without evaporative cooling, in terms of energy use, thermal comfort and indoor air quality. Compared to the baseline of using air-conditioning only, a wind catcher with evaporative cooling

 was found to reduce energy use by 52% during the summer months while increasing the comfortable  hours from 76% to 100% without any supplementary air conditioning. While the time below the

Citation: Saif, J.; Wright, A.; Khattak, ASHRAE CO2 limit also improved from 11% to 24% with the wind catcher, the indoor air quality was S.; Elfadli, K. Keeping Cool in the still poor. These improvements came at the cost of a 14% increase in relative . As the wind Desert: Using Wind Catchers for catcher solution appears to have potential with further development; several avenues for further Improved Thermal Comfort and research are proposed. Indoor Air Quality at Half the Energy. Buildings 2021, 11, 100. https:// Keywords: energy efficiency; thermal comfort; natural ventilation; cooling load; air-conditioning; doi.org/10.3390/buildings11030100 school; wind catcher; carbon dioxide

Academic Editor: Sukumar Natarajan

Received: 30 December 2020 1. Introduction Accepted: 26 February 2021 Published: 6 March 2021 Buildings are responsible for about 40% of global energy use, and usage is predicted to continuously grow further [1]. For countries in which fossil fuels dominate energy supply, use in buildings directly leads to carbon emissions. In Kuwait, primary energy is almost Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in entirely sourced from oil and reserves [2]. With a hot desert climate, the energy demand published maps and institutional affil- for cooling dominates the country’s energy requirements due to extreme in iations. summer [3]. Air conditioning (AC) accounts for more than 60% residential energy use and more than 85% of peak load [4]. Kuwait’s per capita is among the highest globally; in 2014 for instance, the country’s per capita energy consumption was 15,591 kWh [5], with buildings accounting for a massive 90% of the country’s electricity demand. has also grown rapidly, and approximately doubled since 2000, to Copyright: © 2021 by the authors. over 14 GW in 2020 [6,7]. Thus, it becomes very important to reduce energy consumption Licensee MDPI, Basel, Switzerland. This article is an open access article in buildings whilst providing comfortable and healthy indoor conditions. For this purpose, distributed under the terms and the Kuwaiti government has set a target to reduce buildings energy demand by 15% by conditions of the Creative Commons 2030 [8]. Attribution (CC BY) license (https:// According to the Kuwaiti Ministry of Energy, in 2017 Kuwait had approximately creativecommons.org/licenses/by/ 382,817 school students and 949 schools, which is the building type modelled in this 4.0/). paper [9]. The average classroom is occupied by approximately 45 students. The classrooms

Buildings 2021, 11, 100. https://doi.org/10.3390/buildings11030100 https://www.mdpi.com/journal/buildings Buildings 2021, 11, 100 2 of 18

are cooled by split systems, which provide cooling but no fresh air, relying on infiltration and windows for ventilation. This results in poor indoor air quality and high CO2 levels [10]. If the air change rate is increased by opening windows, then the air-conditioning system will consume considerably more electricity during peak summer conditions—an undesired consequence. A review of literature reveals that such a space conditioning strategy may be detrimental to the children’s health and educational performance. A study by Myhrvold and Olesen [11] investigated the ability of students to concen- trate in 35 classrooms in Norway by measuring the students’ reaction times under various rates of ventilation. The study showed that by lowering the rate of ventilation per person from 12 to 4 L/s, students’ reaction times slowed by 5.4%. In , it was established that by raising the rate of ventilation from 0.6 to 6 L/s, the students’ performance was enhanced by 5.5% [12]. Furthermore, Wargocki et al. [13] and Wargocki et al. [14] investigated how the rate of ventilation affects the performance of ten-year-old school children carrying out similar tasks. They established that by raising the ventilation rate to 10 L/s from 5 L/s, there was a 15% improvement in the school’s work performance and an identifiable improvement in the learning and performance of individual children. While there have been several studies on classrooms in hot climates, almost all of these have been in hot humid (tropical and subtropical) climates, which are not particularly relevant [15] with few exceptions; for instance Al-Rashidi et al., [16] found discrepancies between various comfort model predictions and actual sensations in mixed-mode classrooms with cooling. Achieving high levels of comfort, energy efficiency and adequate ventilation in such climates is challenging, and these objectives are often compromised in practice [17]. A study of different cooling approaches [18] found that night ventilation could be effective, but had limitations compared to mechanical systems even in European climates. This study focuses on thermal comfort, energy efficiency and indoor air quality (in terms of CO2) in Kuwaiti classrooms. Specifically, a wind solution is investigated in this work using simulation, with and without evaporative cooling and compared with the existing system for a case study classroom.

2. Wind Catchers Natural ventilation designs can increase internal air speeds to improve thermal com- fort in warm conditions, whilst also improving indoor air quality. Additionally, natural ventilation is passive with no direct energy demand. For centuries, traditional wind catchers (also called wind , or badgirs in ) have been employed in hot areas of Eastern Asia and Middle East [19–21]. It is called a wind catcher since it catches wind-driven air from outside a building from a higher elevation and forces it downwards into an indoor space. In this strategy a vertical shaft of height ranging between 2 and 20 m above the roof level of a building is utilized with openings inside the building level and at the top of the shaft [22]. Traditional wind tower systems used both stack and wind forces to capture fresher air with minimal dust at a high level. This strategy is proposed for hot and arid climatic regions that experience large daily variation; high temperatures during the day and low temperatures at night [23]. There are many designs and configurations, which have evolved over centuries, as a result of local climate and needs. Larger buildings and even some houses have multiple wind catchers. In one configuration, a downward current is created in the morning when the walls of the catchers are still cool (reverse ), so the air moves down and into the building (see Figure1a). Air is then expelled via the building outlet openings that may be found in the tower or may be positioned at the building level to promote air circulation [23,24]. At night-time, the tower and the now warm walls the indoor air, which rises by buoyancy [25] and is expelled via the top openings in the tower [23]; this is illustrated in Figure1b. Some wind catchers draw air through an underground tunnel, and include evaporative cooling [21]. Buildings 2021, 11, 100 3 of 18 Buildings 2021, 11, x 3 of 19

FigureFigure 1.1. Wind tower system principles: ( (aa)) daytime daytime down-draught down-draught operating operating principles principles and and (b ()b ) night-timenight-time up-draughtup-draught reverse-upreverse-up [ 26[26].].

AccordingAccording to to previous previous studies, studies, factors factors that that influence influence the the performance performance of windof wind catchers catch- include:ers include: (i) wind(i) wind angle angle of incidenceof incidence at at the the openings openings [24 [24];]; (ii) (ii) location location and and size size of of thethe openingsopenings [[11]11] and finally finally (iii) (iii) the the geometry geometry of of the the tower; tower; its itsheight, height, shape shape and and cross-sec- cross- sectionaltional area area [27,28]. [27,28 ].For For example, example, Elmualim Elmualim et et al. al. [29] [29] and and Kolokotroni Kolokotroni etet al.al. [[30]30] showedshowed thatthat thethe performanceperformance of of a a windwind catchercatcher system system is is dependent dependent on on the the direction direction and and speed speed of of thethe wind.wind. TheyThey alsoalso showedshowed thatthat toto achieveachieve aa maximummaximum raterate ofof airair flow,flow, thethe windwind catchercatcher designdesign thatthat hashas aa singlesingle openingopening facingfacing thethe directiondirection ofof thethe windwind was was most most effective. effective. AA computercomputer simulation simulation study study was was made made for for a a house house in in Dubai Dubai with with wind wind catchers catchers [ 31[31].]. DubaiDubai isis aboutabout 890890 kmkm south-eastsouth-east ofof Kuwait;Kuwait; itit hashas slightlyslightly lowerlower summer summer temperatures,temperatures, butbut muchmuch higherhigher humidity.humidity. ThisThis foundfound thatthat thethe heightheight andandcross-sectional cross-sectional areaareaof ofthe the towers towers significantlysignificantly affected affected air air flows flows but but had had a a smallsmall effecteffect on on internalinternal temperatures.temperatures. The The authors authors foundfound thatthat adaptiveadaptive comfortcomfort couldcould almostalmost bebe achieved,achieved, andand notednoted “Each“Each ofof thethe [three][three] towerstowers works works in in at at least least six six modes modes that that provide provid moree more or lessor less air inair orin outor out of the of basesthe bases of the of wind tower shafts ... ”, which illustrates the complexity involved. For Kuwait, the annual the wind tower shafts…”, which illustrates the complexity involved. For Kuwait, the an- Windrose diagram is shown in Figure 2 (right). Clearly wind speeds in excess of 10 mph nual Windrose diagram is shown in Figure 2 (right). Clearly wind speeds in excess of 10 are observed in a consistent direction—indicating that wind driven ventilation designs mph are observed in a consistent direction—indicating that wind driven ventilation de- (such as the wind catcher) may be employed in this part of the world. signs (such as the wind catcher) may be employed in this part of the world. Additionally, several technological improvements to the wind catcher can be made Additionally, several technological improvements to the wind catcher can be made to provide improved thermal comfort [24]. For instance, modern advanced wind catchers to provide improved thermal comfort [24]. For instance, modern advanced wind catchers may include; (i) evaporative coolers like pads at the tower top, wetted may include; (i) evaporative coolers like evaporative cooler pads at the tower top, wetted surfaces and columns in the tower [22,32] and at the bottom a pool [27] intended to lower surfaces and columns in the tower [22,32] and at the bottom a pool [27] intended to lower the temperature of indoor air and to raise the relative humidity of indoor air especially the temperature of indoor air and to raise the relative humidity of indoor air especially in in hot areas; (ii) solar chimneys or collectors [33], which enhance ventilation due to stack effecthot areas; during (ii) periods solar chimneys of low winds or collectors and (iii) additional [33], which devices enhance to increase ventilation airflow due and to hence stack aireffect velocity during in theperiods space; of for low example winds fansand powered(iii) additional by photovoltaic devices to modules increase [ 33airflow]. Several and experimentalhence air velocity studies in the have space; reviewed for example the effectiveness fans powered of wind-towersby photovoltaic and modules the results [33]. showedSeveral experimental that they were studies effective have at reviewed inducing the indoor effectiveness air movement of wind-towers [34–36]. In and addition, the re- Sadafisults showed et al. [25 that] investigated they were the effective performance at inducing of wind indoor tower air strategy movement using [34–36]. Venturi-shaped In addi- rooftion, in Sadafi Malaysia, et al. a[25] hot investigated and humid climate;the performance they found of thatwind the tower system strategy effectively using inducedVenturi- airshaped change roof rate in andMalaysia, extraction a hot flow and ratehumid in the clim roomate; usedthey found for the that experiment. the system effectively inducedFrom air the change above-mentioned rate and extraction technological flow rate supplements in the room to used the windfor the catcher, experiment. evapora- tive coolingFrom the is perhapsabove-mentioned the most commontechnological that allowssupplements providing to the much wind improved catcher, evapora- thermal comforttive cooling at the is expenseperhaps of the some most additional common electricity.that allows A providing downside much is the improved reduced effective- thermal nesscomfort of evaporative at the expense cooling of some as humidity additional increases. electricity. Additionally, A downside the is water the reduced evaporated effective- may alsoness increase of evaporative humidity cooling that can as cause humidity serious increases. health concerns, Additionally, such as the the water risk of evaporated . Therefore,may also increase for the geographic humidity locationsthat can cause where se humidityrious health is high, concerns, or if the such humidity as the isrisk high of atLegionella. a certain timeTherefore, of the year,for the the geographic evaporative loca coolingtions where process humidity will be ineffective. is high, or However, if the hu- Buildings 2021, 11, 100 4 of 18

Kuwait has a hot and dry climate, thus making evaporative cooling a suitable to be considered. There are numerous applications for direct evaporative cooling. For instance, Wachen- feldt et al. [37] presented a passive downdraught evaporative cooling system with multiple wind catchers equipped with a water/vapour supply at the top of one wind catcher. While maintaining conditions near saturation along its entire length, consistent droplets of water fall down through the tower, allowing cool air to descend the tower. With successive differences in the and within a local thermal imbalance, in this process, the water droplets evaporate. Consequently, the air moves from the top of the tower, from the high- zone where the air is less dense and hot to the bottom of the tower, to a lower pressure zone where the air is denser and colder, with increased humidity. Natural ventilation strategies based on wind force can provide well distributed and controllable indoor air movement with increased speed necessary in creating a cooling effect and hence comfort indoors. Though not widely used in modern buildings or suitable for some types (such as high-rise), wind catchers can provide large volumes of air flow and hence high air changes. This is advantageous in providing safer internal environments with respect to the Covid-19 coronavirus, although the airflow pattern is also important [38]. The next section provides a short background on suitable thermal comfort metric to assess naturally ventilated and air-conditioned buildings.

3. Thermal Comfort How building occupants perceive comfort varies between individuals and how the building is operated. According to ASHRAE 55 2004 [39], “Thermal comfort is the con- dition of mind that expresses satisfaction with the thermal environment and is assessed by subjective evaluation”. The most important parameters determining comfort are air and radiant temperatures, air velocity, metabolic rate and clothing, but there is large vari- ation between individuals. Many different models have been devised to assess thermal comfort [40,41] however the most commonly used ones are the Fanger’s model, and the adaptive ANSI/ASHRAE standard 55 2017, and these were used in this study. The Fanger model [42] has two comfort indices, the predicted mean vote (PMV) and the predicted percentage of dissatisfied occupants (PPD). The PMV is the average vote of a group of occupants predicted by the model, based on the well-known ASHRAE seven-point vote scale from hot (3) through neutral (0) to cold (−3) [39]. While widely used, this model is not applicable to buildings with natural ventilation systems, as in such buildings, the occupants can adapt to their environment [43]. De Dear et al. [44] show that occupants may physiologically adapt to their thermal environment resulting in the development of adaptive models, incorporated into the ANSI/ASHRAE standard 55 in 2004 [43]. The expected indoor thermal comfort temperature that adapts to the outdoor dry bulb temperature is calculated using a linear relationship as follows (Equation (1)),

Tc = aTo + b (1)

where Tc is the predicted indoor thermal comfort temperature, To is the outdoor reference temperature, a is the slope of the function, proportional to the degree of adaptation and b is the y-intercept. The constants “a” and “b”, depend on empirical data gathered within a specific context, and related to the climatic conditions and cultural background, etc. The outdoor reference temperature is defined in the ANSI/ASHRAE 55 2017 standard [45], as “prevailing mean outdoor air temperature”, defined by Equation (2) as:

h 2 3 i To = (1 − α) Te(d−1) + αTe(d−2) + α Te(d−3) + α Te(d−4) + ··· (2)

where α is a constant (<1) and Te(d−1), Te(d−2), etc. are the daily mean external temperatures for yesterday, the day before, and so on. Since α < 1, this series puts greater weight on the temperature for days closer to the current day (a value of 0 produces just yesterday’s Buildings 2021, 11, x 5 of 19 Buildings 2021, 11, 100 5 of 18

where α is a constant (<1) and Te(d−1), Te(d−2), etc. are the daily mean external temperatures temperature,for yesterday, the the “history” day before, increases and so withon. Sinceα). Aα < value 1, this of series 0.8 is puts often greater used weight based onon empiricalthe studies,temperature but the for appropriate days closer to value the current depends day on (a value the variability of 0 produces of the just climate. yesterday’s Lower tem- values areperature, used with the more“history” variable increases climate with (correspondingα). A value of 0.8 tois often a more used rapidly based varyingon empirical weighted studies, but the appropriate value depends on the variability of the climate. Lower values mean), according to ASHRAE 55 Informative Appendix J, although this is not formally are used with more variable climate (corresponding to a more rapidly varying weighted partmean), of the according standard. to ASHRAE As Kuwait 55 Informative has a consistent Appendix summer J, although climate this with is not little formally day to day variation,part of the a higher standard. value As ofKuwaitα would has a be cons moreistent appropriate. summer climate with little day to day variation,Within a Kuwait, higher value the above of α would equation be more can appropriate. be used to calculate the variation in prevailing mean outdoorWithin Kuwait, air temperature. the above equation This iscan important be used to ascalculate it would the variation provide in information prevail- on whethering mean the outdoor ASHRAE air temperature. standard is This applicable is important for these as it would weather provide conditions. information Figure on2 (left) showswhether the the daily ASHRAE average standard maximum is applicable and minimum for these temperatures weather conditions. by month Figure in Kuwait2 (left) City, Kuwait.shows the The daily monthly average mean maximum outdoor and minimum air temperatures temperatures range by month from 14in Kuwait◦C in JanuaryCity, to 38.7Kuwait.◦C in The July. monthly Therefore, mean any outdoor adaptive air temperatur model usedes shouldrange from have 14 a°C prevailing in January mean to 38.7 temper- ature°C in that July. covers Therefore, this range. any adaptive In case model of the used ASHRAE should adaptive have a prevailing model, the mean upper tempera- limit for the prevailingture that covers outdoor this temperature range. In case limit of th ise ASHRAE 33.5 ◦C. However,adaptive model, in Kuwait, the upper from limit June for to the Septem- prevailing outdoor temperature limit is 33.5 °C. However, in Kuwait, from June to Sep- ber the outdoor reference temperature is above this limit making the ASHRAE standard tember the outdoor reference temperature is above this limit making the ASHRAE stand- unsuitable for application in these hot months. Principally, for natural ventilation-based ard unsuitable for application in these hot months. Principally,◦ for natural ventilation- systemsbased systems where thewhere running the running mean mean temperature temperature exceeds exceeds 33.5 33.5C, °C, neither neither thethe Fanger PMV model,PMV normodel, the nor ASHRAE the ASHRAE adaptive adaptive model model is eligible is eligible for application.for application. Advisory Advisory Appendix Ap- J ofpendix the Standard J of the statesStandard that states “no specificthat “no guidancespecific guidance for such for conditions such conditions is included is included in this stan- dard”.in this The standard”. adaptive The model adaptive is used model here is forused the here natural for the ventilation-based natural ventilation-based scenarios sce- despite violationnarios despite of the violation 33.5 ◦C limit.of the This33.5 °C is limit. because This there is because is evidence there is fromevidence field from visits field in other similarvisits hotin other climates, similar which hot climates, the comfortable which the comfortable indoor temperature indoor temperature may have may a much have larger acceptablea much larger range acceptable than what range is acceptable than what is according acceptable to according the Fanger’s to the model. Fanger’s An model. example of thisAn is example the Indian of this IMAC is the model Indian forIMAC adaptive model for comfort, adaptive which comfort, predicts which comfortable predicts com- indoor conditionsfortable indoor even whenconditions Fanger’s even PPD%when Fanger is as high’s PPD% as 75% is as [46 high]. For as these 75% [46]. reasons, For these andfor the reasons, and for the lack of a better choice, the adaptive model is used. Therefore, the lack of a better choice, the adaptive model is used. Therefore, the results of this work must results of this work must be considered with this limitation in mind. This does indeed be considered with this limitation in mind. This does indeed highlight a knowledge gap highlight a knowledge gap that needs to be addressed for good in hot thatclimates, needs toespecially be addressed considering for good that buildingour world design would inbe hot hotter climates, towards especially the end of considering this thatcentury. our world would be hotter towards the end of this century.

FigureFigure 2. Left 2. :Left Climatic: Climatic average average outdoor outdoor monthly monthly maximummaximum and and minimum minimum temperature temperature for Kuwait for Kuwait City, Kuwait; City, Kuwait; Right: Right: The annual Windrose diagram for Kuwait showing the consistency in wind direction [47]. The annual Windrose diagram for Kuwait showing the consistency in wind direction [47].

4. Methodology The performance of various systems is measured in terms of thermal comfort and energy requirements. This is done using hourly building energy simulation with the De- signBuilder and EnergyPlus software, versions 5.4 and 9.1 respectively [48]. The following scenarios are compared: Buildings 2021, 11, x 6 of 19

4. Methodology The performance of various systems is measured in terms of thermal comfort and energy requirements. This is done using hourly building energy simulation with the Buildings 2021, 11, 100 DesignBuilder and EnergyPlus software, versions 5.4 and 9.1 respectively [48]. The6 of 18fol- lowing scenarios are compared: 1. Scenario 1: Baseline, cooling with split unit, fresh air from windows only (typical 1. Scenariocurrent 1:setup). Baseline, cooling with split unit, fresh air from windows only (typical 2. currentScenario setup). 2: Wind catcher based natural ventilation only, no cooling. 2. 3. ScenarioScenario 2: 3: Wind Wind catcher catcher based with naturalevaporative ventilation cooling. only, no cooling. 3. ScenarioIn the above 3: Wind scenarios, catcher withthe baseline evaporative captures cooling. the real-world typical conditions cur- rentlyIn the found above in scenarios,Kuwaiti classrooms. the baseline Scenario captures 2 the replaces real-world the AC typical with conditions the wind catcher, currently but foundas it is in not Kuwaiti expected classrooms. to fulfil the Scenario thermal 2 replaces comfort the requirements AC with the in windthe extreme catcher, hot but climate as it isof not Kuwait, expected Scenario to fulfil 3 theincludes thermal evaporative comfort requirements cooling as well. in the It should extreme be hot noted climate that of the Kuwait,scope of Scenario this study 3 includes is limited evaporative to climatically cooling similar as well. locations It should as be Kuwait. noted thatThus, the the scope engi- ofneering this study designs is limited presented to climatically in this paper similar are locationsapplicable as within Kuwait. this Thus, climatic the engineeringscope, i.e., hot designsclimate, presented varying inhumidity this paper at different are applicable times withinof the thisyear, climatic high winds scope, speeds i.e., hot throughout climate, varyingthe year, humidity with extreme at different hot temperatures times of the during year, high the windssummer speeds season. throughout the year, with extreme hot temperatures during the summer season. 4.1. Baseline Modelling 4.1. Baseline Modelling The school studied is representative of schools in Kuwait and located in Ahmadi provinceThe school in the studiedFahad-Alahmad is representative Area, approximat of schoolsely in 2.7 Kuwait km east and of the located coast in in Ahmadithe south- provinceern part in of the Kuwait Fahad-Alahmad City. The Area,building approximately consists of 2.724 kmclassrooms, east of the 4 coast teaching in the department southern partoffices of Kuwait and the City. principal’s The building office, consists with a oftotal 24 area classrooms, of approximately 4 teaching 2500 department m2. Due offices to con- 2 andfidentiality, the principal’s the school office, withplans a totalwere area not ofavai approximatelylable for the 2500research. m . Due However, to confidentiality, access was theprovided school plans to a single were notclassroom, available which for the was research. used for However, modelling access and simulation. was provided The toclass- a singleroom classroom, was 5.5 m which wide wasand used6 m forlong, modelling and had and single-sided simulation. ventilation The classroom (Figure was 3). 5.5 It mwas wide and 6 m long, and had single-sided ventilation (Figure3). It was noted during field noted during field visits that the windows were partially opened at certain times depend- visits that the windows were partially opened at certain times depending on the teacher’s ing on the teacher’s view of maintaining comfortable and healthy indoor conditions. view of maintaining comfortable and healthy indoor conditions.

(a) (b)

FigureFigure 3. 3.The The school school classroom classroom modelled modelled in in this this study, study, viewed viewed from from outside outside (a) ( anda) and inside inside (b ).(b).

TheThe modelling modelling of of a buildinga building requires requires the the knowledge knowledge of of the the building building characteristics, characteristics, operationaloperational profiles, profiles, occupancy occupancy profiles, profiles, and and weather weather data. data. The The building building characteristics, characteristics, lightinglighting and and HVAC HVAC information information was was acquired acquired through through a fielda field visit visit and and are are provided provided in in TableTable1. 1.

Table 1. List of the classroom materials and modelling settings—(source: Department of Maintenance, Ministry of Education, field visit).

Elements Layers (Outside to Inside) External wall materials Render 20 mm, limestone tile 50 mm, autoclaved aerated concrete (ACC) block 200 mm, plaster 13 mm Internal partition walls Plaster 13 mm, ACC Block 200 mm, plaster 13 mm. materials Cement 20 mm, tiles 25 mm Building roof Ceramic tiles 25 mm, bitumen 20 mm, concrete slab 200 mm, plasterboard 13 mm. Ceiling material Gypsum Board (15 mm thickness) no insulation External glazing Single glazed 6 mm Buildings 2021, 11, x 7 of 19

Table 1. List of the classroom materials and modelling settings—(source: Department of Maintenance, Ministry of Educa- tion, field visit).

Elements Layers (Outside to Inside) Render 20 mm, limestone tile 50 mm, autoclaved aerated concrete (ACC) block 200 mm, plaster External wall materials 13 mm Internal partition walls Plaster 13 mm, ACC Block 200 mm, plaster 13 mm. Floor materials Cement 20 mm, Ceramic tiles 25 mm Building roof Ceramic tiles 25 mm, bitumen 20 mm, concrete slab 200 mm, plasterboard 13 mm. Buildings 2021Ceiling, 11, 100 material Gypsum Board (15 mm thickness) no insulation 7 of 18 External glazing Single glazed 6 mm

The classroom had two single glazed windows on the longer side of 1.5 m height and 2 mThe length classroom each with had a total two singlearea of glazed 3 m2, and windows one entrance on the door longer (see side Figure of 1.5 4). m The height win- 2 anddows 2 m had length aluminium each with frames a total with area single of 3 m6 mm, and glazing. one entrance door (see Figure4). The windows had aluminium frames with single 6 mm glazing.

(a) (b)

FigureFigure 4. 4.(a ()a Three-dimensional) Three-dimensional axonometric axonometric view view for for the the classroom classroom showing showing the twothe two windows window ands and door door openings openings and (andb) external(b) external elevation elevation showing showing the size the and size position and position of the of windows. the windows.

TheThe classroom classroom was was typically typically occupied occupied by by 29 29 students students plus plus the the teacher teacher and and was was fur- fur- nishednished with with wood wood and and aluminium aluminium tables tables and and chairs. chairs. Due Due to to short short and and mild mild winters, winters, no no heatingheating is is required. required. ForFor cooling, the classroom classroom had had a a 5.28 5.28 kW kW AC AC split split unit unit supplying supplying the thecooling cooling effect effect for for the the occupants occupants with with recirculat recirculateded air; air; it did it did not notsupply supply any any fresh fresh air. air.The TheAC AC setpoint setpoint was was 28 28 °C,◦C, the the operating operating schedu schedulele was was created created in thethe modelmodel basedbased on on the the teacher’steacher’s actions actions for for the the daily daily usage usage as as these these reflect reflect the the actual actual use. use. The The lighting lighting schedule schedule reflectedreflected actual actual daily daily usage, usage, aligned aligned with with the the school school opening opening hours hours (building (building occupancy occupancy duringduring 7 7 am am to to 4 4 pm). pm). The The lighting lighting was was on on 50% 50% 07–09.00, 07–09.00, 100% 100% 09–16.00 09–16.00 and and weekdays weekdays onlyonly in in term-time term-time (September–December, (September–December, January–June). January–June). The The modelled modelled windows windows were were usuallyusually closed closed in in AC AC operation operation but but opened opened periodically periodically to to 20% 20% of of their their area area as as this this was was observedobserved in in field field visits.visits. The handheld handheld anemom anemometereter GM8910 GM8910 [49] [49 ]was was used used to tomeasure measure the Buildings 2021, 11, x the wind speed at different points in the room (Figure5, left), and the building8 structureof 19 wind speed at different points in the room (Figure 5, left), and the building structure was wasinspected inspected based based on which on which an average an average infiltration rate rate of 0.9 of 0.9air changes air changes per perhour hour was was cho- chosen,sen, suggesting suggesting a leaky a leaky structure structure by by modern modern standards. standards. The baseline model was verified against data collected from field visits. Eight HOBO loggers [50] were placed at different locations in the classroom to collect temperature data at 30-min intervals for the hottest summer period (June–July) (Figure 5, right). Addition- ally, the yearly electricity use data for the facility was collected (1,105,160 kWh/year). It can be assumed that about 60% of this electricity is used for cooling [51,52], which would be 663,096 per year, or 265 kWh/m2/year (2500 m2 facility), which is high in comparison with similar schools reported in literature [53].

(a) (b)

FigureFigure 5. (a) Benetch 5. (a) Benetch anemometer anemometer for recording for recording indoor classroom indoor classroom air speed air and speed (b) temperature and (b) temperature measurementmeasurement with Hobo with Hobologgers. loggers.

The simulation was done using Design Builder V5.4 [48]. A modified DesignBuilder weather file for Kuwait International Airport was used with its corresponding latitude and longitude (29° 14 N, 47° 59 E), approximately 18 km north-west of the school. The elevation above sea level was 55 m while the square classroom building was oriented 36 degrees east of north. The dry bulb temperature, wind speed and solar radiation data in the weather file were replaced with real data available from [54,55], for the year 2017 (the year in which data was recorded). Figure 6 depicts the perspective view of the modelled classroom within the whole school, showing the orientation and the sun path.

Figure 6. School building orientation with the sun path timing—classroom shown in white colour (from the DesignBuilder model).

4.2. Scenario 1—Baseline Validation In this baseline scenario, the school classroom is cooled using air conditioning only, which was simulated for a year. To validate the model, the recorded indoor temperature for 16 days in June is compared with the simulated data (see Figure 7). This timeframe was chosen because (i) it is representative of peak summer conditions and (ii) data was collected for this period. The root mean square error (RMSE) between the two data was Buildings 2021, 11, x 8 of 19

Buildings 2021, 11, 100 8 of 18

The baseline model was verified against data collected from field visits. Eight HOBO loggers [50] were placed at different locations in the classroom to collect temperature data

at 30-min intervals for the hottest summer period (June–July) (Figure5, right). Additionally, the yearly electricity(a use) data for the facility was collected (1,105,160(b) kWh/year). It can beFigure assumed 5. (a) Benetch that about anemometer 60% of this for recording electricity indoor is used classroom for cooling air speed [51,52 and], which(b) temperature would be 2 2 663,096measurement per year, with or Hobo 265 kWh/mloggers. /year (2500 m facility), which is high in comparison with similar schools reported in literature [53]. TheThe simulationsimulation waswas donedone usingusing DesignDesign BuilderBuilder V5.4V5.4 [48[48].]. AA modifiedmodified DesignBuilderDesignBuilder weatherweather filefile forfor KuwaitKuwait InternationalInternational AirportAirport waswas usedused withwithits its corresponding corresponding latitudelatitude ◦ ◦ andand longitudelongitude (29(29° 1414 N,N, 4747° 5959 E),E), approximatelyapproximately 1818 kmkm north-westnorth-west ofof the the school. school. TheThe elevationelevation aboveabove sea level was was 55 55 m m while while the the square square classroom classroom building building was was oriented oriented 36 36degrees degrees east east of of north. north. The The dry dry bulb bulb temperat temperature,ure, wind wind speed speed and solar radiationradiation datadata inin thethe weatherweather filefile werewere replaced replaced with with real real data data available available from from [ 54[54,55],,55], for for the the year year 2017 2017 (the (the yearyear inin whichwhich datadata waswas recorded).recorded). FigureFigure6 6depicts depicts the the perspective perspective view view of of the the modelled modelled classroomclassroom withinwithin thethe wholewhole school, school, showing showing the the orientation orientation and and the the sun sun path. path.

FigureFigure 6.6.School School buildingbuilding orientationorientation withwith the sun pathpath timing—classroom shown in white colour colour (from the DesignBuilder model). (from the DesignBuilder model).

4.2.4.2. ScenarioScenario 1—Baseline1—Baseline ValidationValidation InIn thisthis baselinebaseline scenario,scenario, thethe schoolschool classroomclassroom isis cooledcooled usingusing airair conditioningconditioning only,only, whichwhich waswas simulatedsimulated forfor aa year.year. ToTo validate validate the the model, model, the the recorded recorded indoor indoor temperature temperature forfor 1616 daysdays inin JuneJune is is compared compared with with the the simulated simulated data data (see (see Figure Figure7 ).7). This This timeframe timeframe waswas chosenchosen becausebecause (i)(i) itit isis representativerepresentative ofof peakpeak summersummer conditionsconditions andand (ii)(ii) datadata waswas collectedcollected forfor thisthis period.period. TheThe rootroot meanmean squaresquare errorerror (RMSE)(RMSE) betweenbetween thethe twotwo datadata waswas 1.1 and the correlation coefficient (R) was 0.75. Energy data could not be collected, but the simulated annual energy demand of 117 kW/m2/year was comparable to what has been reported for similar schools in Kuwait (69–149 kW/m2/year as reported by [53]). Figure7 shows that without exception, the classroom air temperature goes beyond 28 ◦C every afternoon. Therefore, it is expected that the indoor thermal comfort will be poor in this baseline scenario, which represents the current situation in practice. To address this issue in an energy efficient manner, the following scenarios introduce natural ventilation-based designs to solve this problem. Buildings 2021, 11, x 9 of 19

Buildings 2021, 11, 100 9 of 18 1.1 and the correlation coefficient (R) was 0.75. Energy data could not be collected, but the simulated annual energy demand of 117 kW/m2/year was comparable to what has been reported for similar schools in Kuwait (69–149 kW/m2/year as reported by [53]).

Figure 7. The simulated and recorded indoor temperature profiles for the classroom over 14–30 June. Figure 7. The simulated and recorded indoor temperature profiles for the classroom over 14–30 June. Figure 7 shows that without exception, the classroom air temperature goes beyond 4.3. Scenario28 °C every Two: afternoon. Wind Catcher Therefore, Based it is Naturalexpected Ventilationthat the indoor Only thermal comfort will be poor in this baseline scenario, which represents the current situation in practice. To ad- Thisdress scenario this issue includesin an energy an efficient integrated manner, wind the catcher following system, scenarios with introduce a wind natural supply terminal and anventilation-based air extract that designs uses to natural solve this draught. problem. The wind catcher system is simulated with clay conduits mounted inside the device to enhance heat and mass transfer. This design is based4.3. on Scenario the results Two: Wind of several Catcher Based studies Natural from Ventilation reviewed Only literature, which suggests the wind catcher heightThis scenario needs includes to be at an least integrated 2 m in wind addition catcher system, to the roofwith a height wind supply [27,28 termi-]. For this work, nal and an air extract that uses natural draught. The wind catcher system is simulated the windwith catcherclay conduits design mounted is shown inside inthe Figuredevice 8to, enhance which hasheat aand height mass transfer. of 3 m aboveThis the roof (2 m shaftdesign and is based 1 m on head). the results It is of rectangular several studies in from cross-section reviewed literature, and has which four suggests openings to allow the inflowthe wind of aircatcher from height any needs direction. to be at Theleast wind2 m in addition catcher to head the roof measures height [27,28]. 1 m ×For1 m with the vents dimensionedthis work, the wind as 0.7catcher m × design0.8 mis shown in area. in Figure In DesignBuilder, 8, which has a height the wind-driven of 3 m above ventilation is modelledthe roof as(2 m bulk shaft air and flow 1 m head). [56], drivenIt is rectangular by the in outdoor cross-section wind and speed has four data openings (based on actual to allow the inflow of air from any direction. The wind catcher head measures 1 m × 1 m KISR metrologicalwith the vents dimensioned data). The as vents 0.7 m × on 0.8 the m in catcher area. In wereDesignBuilder, open all the throughout wind-driven the cooling period,ventilation while the is modelled classroom as bulk windows air flow [56], modulated driven by correspondingthe outdoor wind speed to the data occupancy (based schedule Buildings 2021, 11, x 10 of 19 with aon 20% actual free KISR open metrological aperture. data). The vents on the catcher were open all throughout the cooling period, while the classroom windows modulated corresponding to the occupancy schedule with a 20% free open aperture.

Figure 8. Modified classroom with a wind catcher. Figure 8. Modified classroom with a wind catcher. 4.4. Scenario Three: Wind Catcher with Evaporative Cooling Included The direct evaporative cooling system was modelled by adding water pads to cool the air coming from the outside environment to the inside of the wind catcher, to pass it to the classroom. The wind catcher is linked to the classroom through the vents and a convector unit with wetted clay walls and water spray for cooling air. Incoming air first passes through the convector unit and is cooled before flowing to occupied indoor spaces. In Table 2 the specifications of the evaporative pad are provided, chosen with respect to the size and outline of the wind catcher integrated to the classroom. Figure 9 illustrates the HVAC detailed system modelled in Design-Builder to act as the wind catcher plus evaporative cooling system. It consists of direct evaporative cooling with water pads. The in the system operates in natural ventilation mode using the outside wind speed-based inflow through the wind catcher as supply air. The vents on the wind catcher head and the windows in the classroom operate similarly to scenario two.

Table 2. Evaporative cooler specifications used.

Evaporative Cooler Specifications Pad area (m2) 0.6 Pad depth (m) 0.2 Cooler effectiveness 0.7 Coil maximum efficiency 0.8 Coil flow ratio 0.16 Dewpoint effectiveness 0.9 Recirculating water power (W) 200 Buildings 2021, 11, 100 10 of 18

4.4. Scenario Three: Wind Catcher with Evaporative Cooling Included The direct evaporative cooling system was modelled by adding water pads to cool the air coming from the outside environment to the inside of the wind catcher, to pass it to the classroom. The wind catcher is linked to the classroom through the vents and a convector unit with wetted clay walls and water spray for cooling air. Incoming air first passes through the convector unit and is cooled before flowing to occupied indoor spaces. In Table2 the specifications of the evaporative pad are provided, chosen with respect to the size and outline of the wind catcher integrated to the classroom. Figure9 illustrates the HVAC detailed system modelled in Design-Builder to act as the wind catcher plus evaporative cooling system. It consists of direct evaporative cooling with water pads. The fan in the system operates in natural ventilation mode using the outside wind speed-based inflow through the wind catcher as supply air. The vents on the wind catcher head and the windows in the classroom operate similarly to scenario two.

Table 2. Evaporative cooler specifications used.

Evaporative Cooler Specifications Pad area (m2) 0.6 Pad depth (m) 0.2 Cooler effectiveness 0.7 Coil maximum efficiency 0.8 Coil flow ratio 0.16 Dewpoint effectiveness 0.9 Buildings 2021, 11, x 11 of 19 Recirculating water pump power (W) 200

FigureFigure 9.9. HVACHVAC design design in in DesignBuilder DesignBuilder V5.4 V5.4 for for the the wind wind catcher catcher plus plus evaporative evaporative cooler cooler integrated inte- withgrated the with classroom. the classroom.

5.5. ResultsResults andand DiscussionDiscussion AsAs thethe mainmain objectiveobjective ofof thisthis workwork waswas toto developdevelop anan improvedimproved coolingcooling design,design, April–JuneApril–June waswas selectedselected asas thethe periodperiod ofof analysis.analysis. TheThe buildingbuilding waswas cooledcooled fromfrom AprilApril onwards,onwards, with June being being the the hottest hottest summer summer month month when when the the school school was was open. open. July July and andAugust August were were omitted omitted as the as school the school was wasclosed closed during during this thisperiod. period. In this In section, this section, for each for eachof the of scenarios the scenarios defined, defined, the thermal the thermal comfort, comfort, indoor indoor air quality, air quality, relative relative humidity, humidity, venti- ventilationlation and energy and energy use results use results from fromthe Design the DesignBuilderBuilder V5.4/EnergyPlus V5.4/EnergyPlus V9.1 are V9.1 presented. are pre- sented.A comparison A comparison of these of results these resultsbetween between the considered the considered scenarios scenarios is then ispresented then presented in Sec- intion Section 5.4. 5.4.

5.1. Scenario 1: Baseilne—AC Based Cooling Only As the baseline scenario is an AC cooled operation, without any kind of natural ven- tilation intervention, Fanger’s PMV is a suitable thermal comfort indicator. The PMV is calculated within the software, which has internal values of radiant temperature, etc., to calculate PMV. For example, the clo summer value was 0.5, which is representative of light summer clothing. Figure 10 (left) shows the comfort curve over the three months. The ASHRAE 80% comfort criteria correspond to a PMV of ±0.85. While most points lie within this range, significant hours lie in the overheating region (PMV > 0.85). While there are some overcooled hours, these are relatively few. The PMV box plot in Figure 10 (right) shows that the overcooled hours (PMV < −0.85) were outliers within the dataset. A tem- poral analysis of the data revealed that these overcooling hours occurred in either early morning or late afternoon. This is because (i) the outdoor conditions were cooler during these times and (ii) the AC was kept ON 24/7 from April onwards, which was the actual practice at the school. Specifically, 204 h had PPD% greater than 20%, which corresponded to 26% of the total occupied hours. The lower and upper quartiles of the PMV were 0.17 and 0.63 re- spectively, from which one might say that most of the time the occupants were comforta- ble. For air quality, only 11% of the occupied hours (88 h) had a CO2 concentration below the 1100 ppm threshold (ASHRAE stipulated that CO2 concentration should be at most 700 ppm above the outdoor). Here, the CO2 concentration was based on the carbon dioxide generation rate per person as calculated by the software using the number of occupants, their schedule and activity had a fixed CO2 generation rate of 3.82 × 10−8 m3/s-W (obtained from ASHRAE standard 62.1-2007 value at 0.0084 cfm/met/person over the general adult population). Buildings 2021, 11, 100 11 of 18

5.1. Scenario 1: Baseilne—AC Based Cooling Only As the baseline scenario is an AC cooled operation, without any kind of natural ventilation intervention, Fanger’s PMV is a suitable thermal comfort indicator. The PMV is calculated within the software, which has internal values of radiant temperature, etc., Buildings 2021, 11, x 12 of 19 to calculate PMV. For example, the clo summer value was 0.5, which is representative of light summer clothing. Figure 10 (left) shows the comfort curve over the three months. The ASHRAE 80% comfort criteria correspond to a PMV of ±0.85. While most points lie withinThe thismedian range, relative significant humidity hours (RH) lie inwithin the overheating the classroom region within (PMV the occupied > 0.85). While period therewas are60%, some with overcooled the interquartile hours, RH% these ranging are relatively from 53 few. to The71%. PMV The median box plot air in change Figure 10rate (right)during shows occupied that the hours overcooled was 0.56, hours with (PMV the inte < −rquartile0.85) were values outliers ranging within from the dataset.0.41 to 0.65. A temporalFinally, analysisthe energy of theuse data for these revealed three that summer these overcooling months was hours 38 kWh/m occurred2. in either early morningIn summary, or late afternoon. the baseline This scenario is because had (i) some the outdoorwhat comfortable conditions conditions were cooler with during about thesea quarter times of and the (ii) time the exceeding AC was kept the ON ASHRAE 24/7 from 80% April comfort onwards, criteria which but had was unacceptable the actual practiceCO2 concentration at the school. levels.

(a) (b)

FigureFigure 10. 10.(a )(a Predicted) Predicted mean mean vote vote (PMV) (PMV) vs. vs. predicted predicted percentage percentage of dissatisfied of dissatisfied occupants occupants (PPD%) (PPD%) comfort comfort curve curve and ( band) box(b) plot box for plot the for PMV the PMV data. data.

5.2.Specifically, Scenario Two: 204 Wind h had Catcher PPD% Based greater Natural than 20%,Ventilation which Only corresponded to 26% of the total occupiedAs hours.the building The lower is naturally and upper ventilated quartiles in of this the case, PMV the were thermal 0.17and comfort 0.63 respectively,was analysed fromusing which the ASHRAE one might adaptive say that thermal most of comfort the time model the occupants (with the were caveat comfortable. of the 33.5 For°C limit air quality,as already only 11%discussed). of the occupied hours (88 h) had a CO2 concentration below the 1100 ppm thresholdThe (ASHRAE air change stipulated rate was higher that CO than2 concentration the baseline shouldas expected be at from most this 700 natural ppm above venti- thelation-based outdoor). Here, design, the COwith2 concentration a median 2.35 was ac basedh for the on theoccupied carbon dioxidehours. The generation interquartile rate per person as calculated by the software using the number of occupants, their schedule and range was between 1.29 and 3.29 ach, indicating a −much8 3 greater amount of fresh air flow activity had a fixed CO2 generation rate of 3.82 × 10 m /s-W (obtained from ASHRAE into the classroom. This translated into improved air quality, but the median CO2 concen- standard 62.1-2007 value at 0.0084 cfm/met/person over the general adult population). tration was 1190 ppm, still above the 1100 ppm stipulated threshold for good indoor air The median relative humidity (RH) within the classroom within the occupied period quality. The energy use was only a fraction of the baseline, at 7.6 kWh/m2, only 20% of the was 60%, with the interquartile RH% ranging from 53 to 71%. The median air change rate baseline. On the downside, the indoor conditions were not thermally comfortable, as 44% during occupied hours was 0.56, with the interquartile values ranging from 0.41 to 0.65. occupied hours were uncomfortable according to the ASHRAE 55 adaptive thermal com- Finally, the energy use for these three summer months was 38 kWh/m2. fort metric. In summary, the baseline scenario had somewhat comfortable conditions with about a In summary, with the wind catcher operating in only the ventilation mode, thermally quarter of the time exceeding the ASHRAE 80% comfort criteria but had unacceptable CO comfortable conditions could not be reached in the hot desert summer, although large2 concentration levels. energy reductions and IAQ (indoor air quality) improvements were achieved.

5.3. Scenario Three: Wind Catcher with Evaporative Cooling Included In this scenario, an evaporative cooler was added to the wind catcher to improve thermal comfort performance. As this approach also employs natural ventilation, thermal comfort was assessed through the ASHRAE 55 adaptive thermal comfort model. The evaporative cooler certainly made an improvement in this regard, as no hours were pre- dicted to be uncomfortable. The energy use was 18.1 kWh/m2, which was less than half (47.6%) of the baseline energy consumption. The air change rate was also better than the baseline, averaging at 0.87 ach during occupied hours. Compared to the baseline, this also Buildings 2021, 11, 100 12 of 18

5.2. Scenario Two: Wind Catcher Based Natural Ventilation Only As the building is naturally ventilated in this case, the thermal comfort was analysed using the ASHRAE adaptive thermal comfort model (with the caveat of the 33.5 ◦C limit as already discussed). The air change rate was higher than the baseline as expected from this natural ventilation-based design, with a median 2.35 ach for the occupied hours. The interquartile range was between 1.29 and 3.29 ach, indicating a much greater amount of fresh air flow into the classroom. This translated into improved air quality, but the median CO2 concen- tration was 1190 ppm, still above the 1100 ppm stipulated threshold for good indoor air quality. The energy use was only a fraction of the baseline, at 7.6 kWh/m2, only 20% of the baseline. On the downside, the indoor conditions were not thermally comfortable, as 44% occupied hours were uncomfortable according to the ASHRAE 55 adaptive thermal comfort metric. In summary, with the wind catcher operating in only the ventilation mode, thermally comfortable conditions could not be reached in the hot desert summer, although large energy reductions and IAQ (indoor air quality) improvements were achieved.

5.3. Scenario Three: Wind Catcher with Evaporative Cooling Included In this scenario, an evaporative cooler was added to the wind catcher to improve thermal comfort performance. As this approach also employs natural ventilation, thermal comfort was assessed through the ASHRAE 55 adaptive thermal comfort model. The evap- orative cooler certainly made an improvement in this regard, as no hours were predicted to be uncomfortable. The energy use was 18.1 kWh/m2, which was less than half (47.6%) of the baseline energy consumption. The air change rate was also better than the baseline, averaging at 0.87 ach during occupied hours. Compared to the baseline, this also improved the indoor air quality, as the median CO2 concentration was simulated to be 2836 ppm, which was unfortunately still much above the 1100 ppm threshold. These improvements upon the baseline came at the cost of using 0.12 m3 of water in the evaporative cooler, leading to higher humidity levels. The median relative humidity in the classroom was simulated to be 74%, with the interquartile values ranging from 52% to 92%. Despite this higher humidity, the conditions were predicted to be comfortable for all occupied hours. In summary, this scenario resulted in a drastic improvement in energy use and thermal comfort, at the cost of higher relative humidity, but could not sufficiently improve the CO2 concentration levels. Now, the three scenarios were compared as follows.

5.4. Scenarios Comparison Figure 11 depicts the indoor air temperature for two weeks in June (the hottest month of analysis), from which the cooling effect of scenario 3 was clearly evident. In addition to lower daytime temperature peak, the operation of the wind catcher and evaporative cooling purges heat from the building at nighttime, as evident from the troughs in the temperature profile. A comparison of the temperature distributions over the analysis period (April–June) is presented in Figure 12. The effect of evaporative cooling on the for improved indoor air temperature is evident from the figure, as the temperature distribution for Scenario 3 is markedly more to the left than that of Scenario 2. The mean values are 28.1 ◦C, 30.7 ◦C and 28.4 ◦C for the Scenarios 1, 2 and 3 respectively. The utilization of evaporative cooling together with the wind catcher not only brings the average indoor temperature much closer to the baseline, but is also a natural ventilation scenario, thus allowing the building occupants to adapt to their surroundings, and to achieve thermal comfort at higher indoor air temperatures as compared to mechanical air-conditioning only. The result is a completely thermally comfortable environment, as already discussed in Sections 5.1–5.3. Buildings 2021, 11, x 13 of 19

improved the indoor air quality, as the median CO2 concentration was simulated to be 2836 ppm, which was unfortunately still much above the 1100 ppm threshold. These im- provements upon the baseline came at the cost of using 0.12 m3 of water in the evaporative cooler, leading to higher humidity levels. The median relative humidity in the classroom was simulated to be 74%, with the interquartile values ranging from 52% to 92%. Despite this higher humidity, the conditions were predicted to be comfortable for all occupied hours. In summary, this scenario resulted in a drastic improvement in energy use and ther- mal comfort, at the cost of higher relative humidity, but could not sufficiently improve the CO2 concentration levels. Now, the three scenarios were compared as follows.

5.4. Scenarios Comparison Figure 11 depicts the indoor air temperature for two weeks in June (the hottest month of analysis), from which the cooling effect of scenario 3 was clearly evident. In addition to Buildings 2021, 11, 100 lower daytime temperature peak, the operation of the wind catcher and evaporative cool-13 of 18 ing purges heat from the building at nighttime, as evident from the troughs in the tem- perature profile.

Buildings 2021, 11, x 14 of 19 FigureFigure 11. 11.Indoor Indoor temperature temperature comparisoncomparison across the the three three scenario scenarioss over over two two weeks weeks in inJune. June.

A comparison of the temperature distributions over the analysis period (April–June) is presented in Figure 12. The effect of evaporative cooling on the windcatcher for im- proved indoor air temperature is evident from the figure, as the temperature distribution for Scenario 3 is markedly more to the left than that of Scenario 2. The mean values are 28.1 °C, 30.7 °C and 28.4 °C for the Scenarios 1, 2 and 3 respectively. The utilization of evaporative cooling together with the wind catcher not only brings the average indoor temperature much closer to the baseline, but is also a natural ventilation scenario, thus allowing the building occupants to adapt to their surroundings, and to achieve thermal comfort at higher indoor air temperatures as compared to mechanical air-conditioning only. The result is a completely thermally comfortable environment, as already discussed in Sections 5.1, 5.2 and 5.3.

Figure 12. HistogramsFigure 12. ofHistograms indoor air of temper indoorature air temperature for the three for thescenarios. three scenarios.

As mentioned Aspreviously, mentioned this previously, improvement this improvement in thermal incomfort thermal comes comfort at comesthe cost at theof cost of increased humidityincreased as presented humidity in as presentedFigure 13. in The Figure box 13 plots. The clearly box plots show clearly this, show as both this, the as both the median and the spread of relative humidity results were the highest in Scenario 3. This was median and the spread of relative humidity results were the highest in Scenario 3. This expected as evaporative cooling directly adds moisture to the classroom environment, thus was expected asincreasing evaporative humidity. cooling However, directly this adds did notmoisture affect the to comfortthe classroom as the ASHRAE environ- adaptive ment, thus increasingcomfort humidity indicator.results However, in a predictionthis did not of 100%affect comfortable the comfort occupied as the ASHRAE hours. Here, the adaptive comfortlimited indicator applicability results of in this a prediction adaptive comfort of 100% metric comfortable had already occupied been discussed, hours. and that Here, the limitedthis applicability comfort analysis of this should adaptive be understood comfort metric with thishad limitationalready been in mind. discussed, Figure 14 is a and that this comfortsimilar analysis plot for carbon should dioxide be unde concentration;rstood with while this thelimitation wind catcher in mind. achieved Figure the lowest 14 is a similar plotvalues for here, carbon thermal dioxide comfort concen wastration; very poor. while the wind catcher achieved the lowest values here, thermal comfort was very poor.

Buildings 2021, 11, x 14 of 19

Figure 12. Histograms of indoor air temperature for the three scenarios.

As mentioned previously, this improvement in thermal comfort comes at the cost of increased humidity as presented in Figure 13. The box plots clearly show this, as both the median and the spread of relative humidity results were the highest in Scenario 3. This was expected as evaporative cooling directly adds moisture to the classroom environ- ment, thus increasing humidity. However, this did not affect the comfort as the ASHRAE adaptive comfort indicator results in a prediction of 100% comfortable occupied hours. Here, the limited applicability of this adaptive comfort metric had already been discussed, Buildings 2021, 11, 100 and that this comfort analysis should be understood with this limitation in mind. 14Figure of 18 14 is a similar plot for carbon dioxide concentration; while the wind catcher achieved the lowest values here, thermal comfort was very poor.

Buildings 2021, 11, x 15 of 19

Figure 13. Relative humidity comparison across the three scenarios.

It is interesting that none of the scenarios could deliver satisfactory indoor air quality. Even in the complete natural ventilation case, the wind catcher without evaporative cool- ing that delivers unsatisfactory thermal comfort, also had a median CO2 concentration above the 1100 ppm ASHRAE stipulated threshold. Clearly, the issue of indoor air quality Figureis a challenge, 13. Relative which humidity is in agreement comparison acrosswith similar the three studies scenarios. on schools in literature [57].

Figure 14. CO2 concentration comparison across the three scenarios. Figure 14. CO2 concentration comparison across the three scenarios.

ItThe is interestingsummary thattable none to conclude of the scenarios this analysis could is deliver presented satisfactory in Table indoor 3. The air baseline quality. Evenoperates in the at completethe highest natural energy ventilation use amongst case, the the three wind scenarios, catcher without but also evaporative suffers from cooling poor thatair quality delivers and unsatisfactory mediocre thermal thermal comfort. comfort, The also wind had catcher a median only CO design2 concentration uses a fifth above of the theAC’s 1100 energy, ppm somewhat ASHRAE stipulatedimproves the threshold. air qualit Clearly,y but leads the issueto a prediction of indoor of air unacceptable quality is a challenge,thermal comfort which isresult. in agreement The addition with similarof the evaporative studies on schools cooler into literaturethe wind [catcher57]. was simulatedThe summary to deliver table 100% to comfortable conclude this hours, analysis at 47.6% is presented energy use in Tableof the3 .baseline, The baseline but at operateshigher humidity at the highest levels energyin the classroom use amongst and the a small three water scenarios, use amount. but also suffers from poor air quality and mediocre thermal comfort. The wind catcher only design uses a fifth of the Table 3. ResultsAC’s summary energy, table somewhat comparing improves the different the scenarios air quality for butthe time leadsframe to a April prediction to June. of unacceptable thermal comfort result. The addition of the evaporative cooler to the wind catcher was Scenario 3 Baseline Scenario 2 (Wind Catcher with (AC Cooling) (Wind Catcher) Evaporative Cooling) Energy use (kWh/m2) 38 7.6 18.1 Air quality (% occupied hours < 1100 ppm CO2) 88 (11.1%) 240 (30.3%) 191 (24.1%) Discomfort hours (> 20% PPD/adaptive comfort = 0) 204 (25.8%) 347 (43.8%) 0 (0%) Median relative humidity(%) 60 41 74 Water Usage (m3) N/A N/A 0.12

Costs were not considered here. Clearly, installing a wind catcher involves cost; add- ing evaporative cooling adds further capital and maintenance costs; the cost of water is small. While it would be possible to retrofit to existing schools, it would be easier and cheaper to include in new build or major refurbishment projects. Costs will be offset by much reduced energy cost, and replacement and maintenance of mechanical cooling sys- tems. A much greater benefit however will come from the improvement in comfort and Buildings 2021, 11, 100 15 of 18

simulated to deliver 100% comfortable hours, at 47.6% energy use of the baseline, but at higher humidity levels in the classroom and a small water use amount.

Table 3. Results summary table comparing the different scenarios for the timeframe April to June.

Scenario 3 Baseline Scenario 2 (Wind Catcher with (AC Cooling) (Wind Catcher) Evaporative Cooling) Energy use (kWh/m2) 38 7.6 18.1 Air quality (% occupied hours < 1100 ppm CO2) 88 (11.1%) 240 (30.3%) 191 (24.1%) Discomfort hours (>20% PPD/adaptive comfort = 0) 204 (25.8%) 347 (43.8%) 0 (0%) Median relative humidity(%) 60 41 74 Water Usage (m3) N/A N/A 0.12

Costs were not considered here. Clearly, installing a wind catcher involves cost; adding evaporative cooling adds further capital and maintenance costs; the cost of water is small. While it would be possible to retrofit to existing schools, it would be easier and cheaper to include in new build or major refurbishment projects. Costs will be offset by much reduced energy cost, and replacement and maintenance of mechanical cooling systems. A much greater benefit however will come from the improvement in comfort and IAQ and—according to the literature—better educational outcomes. These are very hard to quantify, but likely to far outweigh system costs. A detailed cost analysis, preferably on a real building, would be useful exercise.

6. Conclusions In this paper, a natural ventilation design, the wind catcher was assessed that could provide thermal comfort in educational buildings in Kuwait, whilst reducing the cooling energy demand and indoor CO2 levels. Compared to air-conditioning only, the wind catcher with evaporative cooling was found to be the best option that resulted in a reduction of energy use by 52.4%, and improved thermal comfort with the percentage comfortable hours increasing from 74% to 100%. While the indoor CO2 levels improved as well, in all three scenarios the CO2 concentration was above the ASHRAE stipulated limit for a large portion of the occupied hours. In summary, this study established that within the climatic scope of this work, the recommended strategy of the wind catcher with evaporative cooling is a highly energy efficient option that can successfully provide thermal comfort, but slightly improved indoor air quality. The key findings from this work were as follows: • Using only a split room cooling system with single sided window ventilation to provide thermal comfort in Kuwaiti classrooms led to high energy use, considerable discomfort and poor indoor air quality. • In this case, the wind catcher supplemented by the evaporative cooler was the best design solution, resulting in highly comfortable conditions in the summer (zero un- comfortable hours) accompanied by a drastic reduction in energy use (52.4% reduction) but a slight improvement in indoor air quality, at the cost of increased humidity levels. While the energy savings and improved thermal comfort is promising, the challenge of improving indoor air quality in schools still remains—at least with this design. These results are subject to the limitations in the modelling work and the unavailability of a suitable thermal comfort metric for naturally ventilated buildings in such hot climatic conditions. For the lack of a better choice and because developing a suitable adaptive thermal model was beyond the scope of this paper, the ASHRAE adaptive model was used here, despite the fact that the outdoor running mean prevailing temperature exceeded the 33.5 ◦C limit for significant parts of the summer. Additionally, costs were not analysed, although they were briefly discussed. In view of these limitations and the previously presented conclusions, several avenues for future work are suggested as follows, Buildings 2021, 11, 100 16 of 18

• The airflow modelling in this paper was based on wind pressure coefficients (Cp) in lookup tables using the DesignBuilder V5.4 software, having limited accuracy for natural ventilation-based designs such as wind catchers. Future investigations can utilize computational fluid dynamics (CFD) where more accurate wind pressure coefficients (Cp) can be calculated for more reliable simulations. • The sizing of the wind catcher system in this work was based on recommendations from the literature [58]. However, this work can be extended to conduct an optimiza- tion of the wind catcher design for the buildings considered, within the considered climates. • The scope of application of this wind catcher based design can be expanded to more humid climates by considering desiccant evaporative cooling. • To build on the predicted improvement potential using the wind catcher plus evapora- tive cooler design, a practical demonstration activity for different building archetypes is suggested. This would help highlight any unforeseen inefficiencies in the proposed design while demonstrating its utility in practice and provide data for the validation of future models. It should be noted that such a demonstration activity in Kuwait has not been documented in literature to date. • In the hot Kuwaiti summer, to promote energy efficiency, buildings may by subject to low air change rates, which can lead to adverse health impacts with an associated economic cost. The proposed wind catcher based design may help address these issues, but it has not been explored in this work and may be worthy of investigation. • Review of thermal comfort indicators within the context of hot desert climates such as Kuwait (where prevailing mean temperature go beyond 33.5 ◦C, the ASHRAE 55 upper limit) highlighted the limited applicability of currently available international adaptive comfort models. The applicability of the widely used thermal comfort models for extreme hot climates should be investigated—especially as our world is predicted to be hotter by the end of the century. • Building a fully instrumented classroom with wind catcher to test out the system in practice.

Author Contributions: Conceptualisation and fieldwork, J.S., A.W. and K.E.; modelling and analysis, J.S. and S.K.; writing, J.S., S.K., A.W. and K.E.; editing, S.K. and A.W. All authors have read and agreed to the published version of the manuscript. Funding: The original research was funded by Jamal Saif as part of his PhD studies. Institutional Review Board Statement: Not applicable. Informed Consent Statement: Not applicable. Data Availability Statement: Data are contained within the article. Acknowledgments: The authors would like to thank the Public Authority for Applied Education and Training (PAAET) for access to the school and data provision. Conflicts of Interest: The funders had no role in the design of the study; in the collection, analyses, or interpretation of data; in the writing of the manuscript, or in the decision to publish the results. The authors declare no conflict of interest.

References 1. Xing, Y.; Hewitt, N.; Griffiths, P. Zero carbon buildings refurbishment—A Hierarchical pathway. Renew. Sustain. Energy Rev. 2011, 15, 3229–3236. [CrossRef] 2. Kuwait Institute for Scientific Research. Kuwait Energy Outlook. Available online: http://www.kisr.edu.kw/en/facilities/energy- building/?research=1;Resourcestab (accessed on 20 December 2020). 3. Nasrallah, H.A.; Nieplova, E.; Ramadan, E. Warm season extreme temperature events in Kuwait. J. Arid Environ. 2004, 56, 357–371. [CrossRef] 4. Al-ajmi, F.F.; Al-azmi, A.S.; Alrashidi, F.A. Indoor Environmental Quality in Air-conditioned Buildings in Kuwait. Am. J. Civ. Eng. Archit. 2017, 5, 167–173. [CrossRef] Buildings 2021, 11, 100 17 of 18

5. Bank, T.W. Electric Power Consumption (kWh Per Capita)—Kuwait. Available online: https://data.worldbank.org/indicator/ EG.USE.ELEC.KH.PC?locations=KW (accessed on 20 January 2021). 6. Krarti, M.; Hajiah, A. Analysis of impact of daylight time savings on energy use of buildings in Kuwait. Energy Policy 2011, 39, 2319–2329. [CrossRef] 7. Alhajeri, H.M.; Almutairi, A.; Alenezi, A.; Alshammari, F. Energy Demand in the State of Kuwait during the Covid-19 Pandemic: Technical, Economic, and Environmental Perspectives. 2020, 13, 4370. [CrossRef] 8. Cerezo, C.; Sokol, J.; Alkhaled, S.; Reinhart, C.; Al-mumin, A.; Hajiah, A. Comparison of four building archetype characterization methods in urban building energy modeling (UBEM): A residential case study in Kuwait City. Energy Build. 2017, 154, 321–334. [CrossRef] 9. CEIC Kuwait Education Statistics. Available online: https://www.ceicdata.com/en/kuwait/education-statistics (accessed on 1 February 2021). 10. Clements, C.J.; Awbi, H.B.; Bakó-Biró, Z.; Kochhar, N.; Williams, M. Ventilation rates in schools. Build. Environ. 2008, 43, 362–367. [CrossRef] 11. Myhrvold, A. Pupils health and performance due to renovation of schools. In Proceedings of the Healthy Buildings/IAQ, Washington, DC, USA, 27 September 1997. 12. Wargocki, P.; Wyon, D.P. Research report on effects of HVAC on student performance. ASHRAE J. 2006, 48, 22. 13. Wargocki, P.; Wyon, D.P. The effects of moderately raised classroom temperatures and classroom ventilation rate on the performance of schoolwork by children (RP-1257). HVACR Res. 2007, 13, 193–220. [CrossRef] 14. Wargocki, P.; Wyon, D.P.; Lynge-Jensen, K.; Bornehag, C.G. The effects of electrostatic particle filtration and supply-air filter condition in classrooms on the performance of schoolwork by children (RP-1257). HVACR Res. 2008, 14, 327–344. [CrossRef] 15. Jindal, A. Thermal comfort study in naturally ventilated school classrooms in composite climate of India. Build. Environ. 2018, 142, 34–46. [CrossRef] 16. Al-Rashidi, K.E.; Loveday, D.L.; Al-Mutawa, N.K. Investigating the Applicability of Different Thermal Comfort Models in Kuwait Classrooms Operated in Hybrid Air-Conditioning Mode. In Proceedings of the in Energy and Buildings; Howlett, R.J., Jain, L.C., Lee, S.H., Eds.; Springer: Berlin/Heidelberg, Germany, 2009; pp. 347–355. 17. Anand, P.; Sekhar, C.; Cheong, D.; Santamouris, M.; Kondepudi, S. Occupancy-based zone-level VAV system control implications on thermal comfort, ventilation, indoor air quality and building energy efficiency. Energy Build. 2019, 204, 109473. [CrossRef] 18. Engelmann, P.; Kalz, D.; Salvalai, G. Cooling concepts for non-residential buildings: A comparison of cooling concepts in different climate zones. Energy Build. 2014, 82, 447–456. [CrossRef] 19. Ghiaus, C.; Allard, F. Natural Ventilation in the Urban Environment; Routledge: Abingdon-on-Thames, UK, 2016; ISBN 9781138994393. 20. Da Silva, J.J.C. Passive downdraught evaporative cooling applied to an auditorium. Int. Conf. Passiv. Low Energy Cool. Built Environ. Greece 2005, 555–560. Available online: https://citeseerx.ist.psu.edu/viewdoc/download?doi=10.1.1.526.9413&rep=rep1 &type=pdf (accessed on 20 December 2020). 21. Roaf, S. Air-conditioning avoidance: Lessons from the of Iran. In Proceedings of the International Conference “Passive and Low Energy Cooling for the Built Environment, Santorini, Greece, 19–21 May 2005; pp. 1053–1057. 22. Bahadori, M.N. Viability of wind towers in achieving summer comfort in the hot arid regions of the Middle East. Renew. Energy 1994, 5, 879–892. [CrossRef] 23. Bansal, N.; Hauser, G.; Minke, G. Passive Building Design: A Handbook of Natural Climate Control; Elsevier Science B.V.: Amsterdam, The Netherlands, 1994. 24. Khan, N.; Su, Y.; Riffat, S. A review on wind driven ventilation techniques. Energy Build. 2008, 40, 1586–1604. [CrossRef] 25. Allard, F. Natural Ventilation in Buildings: A Design Handbook; James & James (Science Publishers) Ltd.: , UK, 1998. 26. Gonzelez-Trevizo, M.E.; Gonzelez-Licon, H.J.; Gomez-amador, A.; Pozo, C.E.D.; Lopez, C.J. Exhaust ventilation through a wind tower as response to high hermeticity in welfare housing. In Proceedings of the PLEA2013—29th Conference, for a Renewable Future, Minich, Germany, 10–12 September 2013. 27. Bouchahm, T.; Bourbia, F.; Balhamri, A. Performance analysis and improvement of the use of wind tower in hot dry climate. Renew. Energy 2011, 36, 898–906. [CrossRef] 28. Ghadiri, M.H.; Ibrahim, N.L.N.; Mohamed, M.F. Applying computational fluid dynamic to evaluate the performance of four-sided rectangular wind catcher with different height. Res. J. Appl. Sci. Eng. Technol. 2014, 7, 502–509. [CrossRef] 29. Elmualim, A.; Awbi, H. Evaluating the performance of a windcatcher system using wind tunnel testing. In Proceedings of the 22nd Annual AIVC Conference, Bath, UK, 11–14 September 2001. 30. Kolokotroni, M.; Ayiomamitis, A.; Ge, Y. The suitability of wind driven natural ventilation towers for modern offices in the UK: A case-study. In Proceedings of the World Congress VII (WREC), Cologne, Germany, 29 June–5 July 2002. 31. McCabe, C.; Roaf, S. The wind towers of Bastakiya: Assessing the role of the towers in the whole house ventilation system using dynamic thermal modelling. Archit. Sci. Rev. 2013, 56, 183–194. [CrossRef] 32. Bahadori, M.N.; Mazidi, M.; Dehghani, A.R. Experimental investigation of new designs of wind towers. Renew. Energy 2008, 33, 2273–2281. [CrossRef] 33. Hughes, B.R.; Calautit, J.K.; Ghani, S.A. The development of commercial wind towers for natural ventilation: A review. Appl. Energy 2012, 92, 606–627. [CrossRef] Buildings 2021, 11, 100 18 of 18

34. Van Hooff, T.; Blocken, B.; Aanen, L.; Bronsema, B. A venturi-shaped roof for wind-induced natural ventilation of buildings: Wind tunnel and CFD evaluation of different design configurations. Build. Environ. 2011, 46, 1797–1807. [CrossRef] 35. Blocken, B.; van Hooff, T.; Aanen, L.; Bronsema, B. Computational analysis of the performance of a venturi-shaped roof for natural ventilation: Venturi-effect versus wind-blocking effect. Comput. Fluids 2011, 48, 202–213. [CrossRef] 36. Sadafi, N.; Salleh, E.; Haw, L.C.; Jaafar, Z. Evaluating thermal effects of internal in a tropical terrace house by computational simulation. Energy Build. 2011, 43, 887–893. [CrossRef] 37. Wachenfeldt, B.J.; Dagfinn, B. Building Integrated Energy Systems in Smart Energy Efficient Buildings—A State-of-the-Art; Project Report; SINTEF Civil and Environmental Engineering: Trondheim, Norway, 2003. 38. Bhagat, R.K.; Davies Wykes, M.S.; Dalziel, S.B.; Linden, P.F. Effects of ventilation on the indoor spread of COVID-19. J. Fluid Mech. 2020, 903.[CrossRef] 39. Turner, S.C.; Paliaga, G.; Lynch, B.M.; Arens, E.A.; Aynsley, R.M.; Brager, G.S.; Deringer, J.J.; Ferguson, J.M.; Filler, J.M.; Hogeling, J.J.; et al. ASHRAE STANDARD Thermal Environmental Conditions for Human Occupancy; ASHRAE: Peachtree Corners, GA, USA, 2010. 40. Winslow, C.E.A.; Herrington, L.P.; Gagge, A.P. Relations between Atmospheric Conditions, Physiological Reactions and Sensations of Pleasantness. Am. J. Hyg. 1937, 26, 103–115. 41. Vellei, M.; Le Dréau, J. A novel model for evaluating dynamic thermal comfort under events. Build. Environ. 2019, 160, 106215. [CrossRef] 42. BSI BS EN ISO 7730. Ergonomics of the Thermal Environment. Analytical Determination and Interpretation of Thermal Comfort Using Calculation of the PMV and PPD Indices and Local Thermal Comfort Criteria; ISO: Geneva, Switzerland, 2005. 43. Carlucci, S.; Bai, L.; de Dear, R.; Yang, L. Review of adaptive thermal comfort models in built environmental regulatory documents. Build. Environ. 2018, 137, 73–89. [CrossRef] 44. De Dear, R.J.; Brager, G.S. Developing an adaptive model of thermal comfort and preference. ASHRAE Trans. 1998, 104, 145–167. 45. ANSI/ASHRAE ANSI/ASHRAE Standard 55-2017: Thermal Environmental Conditions for Human Occupancy; ASHRAE Inc.: Atlanta, GA, USA, 2017; Volume 2017, p. 66. ISSN 1041-2336. 46. Khattak, S.H.; Natarajan, S.; Chung, W.J. Out with the power outages: Peak load reduction in the developing world. In Proceedings of the Windsor 2020 Resilient Comfort, Windsor, UK, 16–19 April 2020; pp. 904–922. 47. Atlas, W. Average Temperature: Kuwait City, Kuwait. Available online: https://www.weather-atlas.com/en/kuwait/kuwait- city-climate#temperature (accessed on 20 February 2020). 48. Designbuilder Software Limited Design Builder. Available online: http://www.designbuilder.co.uk/ (accessed on 3 Febru- ary 2021). 49. BENETECH GM8910 Eng Brochure.pdf. Available online: www.ponpe.com (accessed on 20 February 2021). 50. ONSET HOBO® UX100 Series and UX120-014M Data Loggers. Available online: https://tmseurope.co.uk/datasheets/hobo_ux1 00_ux120-014m_data-loggers-datasheet.pdf (accessed on 20 February 2020). 51. Katramiz, E.; Al Jebaei, H.; Alotaibi, S.; Chakroun, W.; Ghaddar, N.; Ghali, K. Sustainable cooling system for Kuwait hot climate combining diurnal radiative cooling and indirect evaporative cooling system. Energy 2020, 213, 119045. [CrossRef] 52. Alajmi, T.; Phelan, P. Modeling and forecasting end-use energy consumption for residential buildings in Kuwait using a bottom-up approach. Energies 2020, 13, 1981. [CrossRef] 53. Al-Otaibi, A.; Al-Qattan, A.; Fairouz, F.; Al-Mulla, A. Performance evaluation of photovoltaic systems on Kuwaiti schools’ rooftop. Energy Convers. Manag. 2015, 95, 110–119. [CrossRef] 54. University, I.S. Iowa Environmental Mesonet. Available online: https://mesonet.agron.iastate.edu/request/download.phtml? network=KW__ASOS (accessed on 1 February 2021). 55. NREL NSRDB: National Solar Radiation Database. Available online: https://nsrdb.nrel.gov/ (accessed on 1 February 2021). 56. Gu, L. Airflow network modeling in energyplus. IBPSA 2007—Int. Build. Perform. Simul. Assoc. 2007, 10, 964–971. 57. Al-rashidi, K.; Loveday, D.; Al-mutawa, N. Impact of ventilation modes on carbon dioxide concentration levels in Kuwait classrooms. Energy Build. 2012, 47, 540–549. [CrossRef] 58. Awbi, H. Ventilation Systems Design and Performance; Taylor & Francis: New York, NY, USA, 2013; Volume 53.