Extract from the Proceedings of Building Simulation and Optimization 2012

Total Page:16

File Type:pdf, Size:1020Kb

Extract from the Proceedings of Building Simulation and Optimization 2012 First Building Simulation and Optimization Conference Loughborough, UK BSO12 10-11 September 2012 MODELING AND SIMULATION OF BUILDING ECONOMIZER AND ENERGY RECOVERY SYSTEMS FOR OPTIMUM PERFORMANCE Stephen Treado, Xing Liu Pennsylvania State University University Park, PA appropriate to provide “free cooling”, the rough ABSTRACT equivalent of opening the windows on a nice day This paper describes how building economizer and rather than using mechanical cooling. The former energy/enthalpy recovery system control and study has demonstrated that the energy savings operation can be modelled and simulated to evaluate associated with economizer could be very significant and optimize their performance. A improved method (Brandemuehl et al., 1999). The energy saving of the to determine optimum temperature setpoints and robust control strategy on cooling coil energy outdoor air fractions is discussed and demonstrated. consumption which was evaluated by over one year’s Through the simulation, the new strategy based on comparison tests on two air-handling units in a total system energy use is shown to be able to save building was 88.47% in contrast to the energy up to 11% of energy under certain conditions and to consumption using the conventional control (damper be most useful for dry climates. at fixed position) in Hong Kong (Wang et al., 2004). Energy recovery systems exploit the “free heating or INTRODUCTION cooling” provided by exchanging energy between the exhaust and outdoor airstreams. In both of these Buildings are constructed to serve a purpose, namely systems, some control logic must be implemented to to provide a comfortable, safe, healthy and determine how and when the systems should be productive environment for human endeavours. operated to obtain the most favourable outcome. They require the investment of scarce resources and substantial time and effort to design, build and This paper examines the current methods used for operate, so efficiency and cost effectiveness are controlling building economizer and energy recovery always considerations. In particular, energy efficient systems, and related methods for modeling and performance, and the means to achieve it, is of simulating their performance. It identifies some critical interest to building designers and owners. A inconsistencies in approaches and suggests some tension exists, however, between building energy improved models and simulation methods to more efficiency, thermal performance and occupant health accurately evaluate energy performance and increase and comfort, whereby the means employed to the energy savings potential from the use of these minimize energy usage may negatively impact technologies. thermal and air quality within the building’s conditioned space. This is a constant challenge faced SIMULATION by building designers and operators, and the focus of There are several important aspects related to the many design codes, standards and tools. In addition control, modeling and simulation of building HVAC to requiring building envelope components to reduce economizer and energy recovery systems. The or control unwanted heat transfer, building codes discussion will commence with economizer control, impose minimum requirements for ventilation air, and then extend to the analysis of energy recovery sometimes known as fresh air, to control the buildup systems. The actual implementation of the of contaminants in the indoor air. Ventilation economizer control, for example, can be done in standards are based on a combination of factors, different ways depending on the installed sensors and usually including building use, size and occupancy, actuators. The basic strategies (ASHRAE Standard and inadequate ventilation has been linked to 90.1-2010) employed include the following problems with moisture, allergens and generally conditions, under which the outdoor air intake unhealthy conditions. damper would be opened beyond the minimum It is within this context that building economizer required for ventilation: cycles and energy recovery systems have evolved. • fixed dry bulb-outdoor air dry bulb The introduction of ventilation air from the outside temperature less than a set value may impact heating or cooling loads since the • differential dry bulb- outdoor air dry bulb outdoor air needs to be conditioned to maintain the temperature less than return air temperature indoor comfort conditions. This means that in • fixed enthalpy- outdoor air enthalpy less extreme climate conditions (winter, summer) than a set value additional energy may be required to heat or cool the • differential enthalpy- outdoor air enthalpy ventilation air as compared to a sealed building. An less than return air enthalpy economizer cycle utilizes outdoor air when © Copyright IBPSA-England, 2012 - 433 - • combination- some combination of the effect is described more fully below. Second, above outdoor air conditions in region C, being warmer but • optimal- a combined strategy that dryer than the return air, may provide reduced maximizes energy savings cooling loads with partial economizer operation. The differential modes require at least two sensors, This can be a substantial benefit in certain climate and the enthalpy-based strategies require the regions. A method for optimal control in this region measurement of relative humidity or some other will be outlined below. Third, the optimal control moisture content indicator, while the combination logic in Figure 1 is based on minimizing cooling coil strategies require multiple temperature and enthalpy loads, but the energy is actually expended to operate sensors. Lacking these sensors limits the control a chiller and pump to provide chilled water to the strategies that can be implemented. Even when the coil, and a fan to provide conditioned air to the space. sensors are installed, sensor errors and other The energy inputs to these components depend on a measurement problems can seriously compromise number of factors, including chilled water supply performance, particularly for enthalpy measurements, temperature, part load ratio and condenser entering which are notoriously unreliable (Zhou et al., 2008). temperature. Optimizing economizer operation to Several studies have illustrated the potential minimize energy input by adjusting setpoints without degradation of economizer energy performance due diminishing comfort will be demonstrated. to sensor uncertainty (Seem et al., 2010). That said, A typical air handling unit (AHU) has hydronic this paper will not explore that issue any further, but heating and cooling coils, a supply fan, and ducts, will focus on the theoretical basis for economizer dampers and control valves. For the sake of control assuming properly functioning and simplicity, the system is assumed to control the air reasonably accurate sensors. temperature within a single zone, although that assumption can readily be extended to a multi-zone A schematic representation of optimum economizer case without loss of applicability. A source of hot control logic based on (Taylor, 2010) is shown in and chilled water is further assumed to provide the Figure 1 in the form of a psychrometric chart, which heating and cooling functions to the room air by way is formatted to show a wide range of air temperature of the respective heating and cooling coils. Outdoor and moisture conditions. Note that lines of constant air can be drawn in to the system through the outdoor dry bulb temperature are nearly vertical on a air damper, and similarly exhausted through the psychrometric chart, increasing from left to right on exhaust air damper. These two dampers work in the horizontal axis, while moisture content increases conjunction with the return air damper to admit the on the vertical axis, and lines of constant enthalpy desired quantity of outdoor air to meet ventilation, slant diagonally downward from left to right. Two pressurization and economizer requirements for the air condition points define the boundaries for building zone. The two basic modes of fan operation optimum economizer control, one being the return air are constant air volume (CAV) or variable air volume temperature Tr (which is assumed to be equal to the (VAV), with the latter being preferred for its energy zone air temperature) and the supply air temperature saving potential. Ts (which is assumed to be saturated). If the condition of the air entering the cooling coil is above In either CAV or VAV operation, the zone heating the moisture content defined by the supply air and cooling loads are met by supplying conditioned temperature intersection with the saturation curve, air to the zone such that the product of the mass flow condensation will occur on the coil (wet coil) while if rate of the supply air, the specific heat of air and the the moisture content is below the line, the temperature change of the air from supply (Ts) to condensation will not occur (dry coil). Thus, it will return (Tr) are equal to the zone thermal load: be advantageous to use 100% outdoor air if the outdoor air condition lies in region A, based on lower ̇ ̇ (1) enthalpy for the wet coil, or region B, based on lower dry bulb temperature for the dry coil. In regions D The difference between the CAV and VAV modes is and E, the use of outdoor air is not advantageous, that as loads vary, supply air temperature is varied by while in region F, some fraction of outdoor air may the control system for CAV, and airflow rate is be beneficial. varied for VAV. Thus, supply air temperature is held at a setpoint (although
Recommended publications
  • VAV Systems, on the Other Hand, Are Designed to Simultaneously Meet a Variety of Cooling and Heating Loads in a Relatively Efficient Manner
    PDHonline Course M252 (4 PDH) HVAC Design Overview of Variable Air Volume Systems Instructor: A. Bhatia, B.E. 2012 PDH Online | PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.PDHonline.org www.PDHcenter.com An Approved Continuing Education Provider www.PDHcenter.com PDH Course M252 www.PDHonline.org HVAC Design Overview of Variable Air Volume Systems A. Bhatia, B.E. VARIABLE AIR VOLUME SYSTEMS In central air conditioning systems there are two basic methods for delivering air to the conditioned space 1) the constant air volume (CAV) systems and 2) the variable air volume (VAV) systems. As the name implies, constant volume systems deliver a constant air volume to the conditioned space irrespective of the load with the air conditioner cycling on and off as the load varies. The fan may or may not continue to run during the off cycle. VAV systems, on the other hand, are designed to simultaneously meet a variety of cooling and heating loads in a relatively efficient manner. The system achieves this by varying the distribution of air depending on the cooling or heating loads of each area. The air flow variation allows for adjusting the temperature in a single zone without changing the temperature of air in the whole system, minimizing any instances of overcooling or overheating. This flexibility has made this one of the most popular HVAC systems for large buildings with varying conditioning needs such as office buildings, schools, or apartments. How a VAV system works? What distinguishes a variable air volume system from other types of air delivery systems is the use of a variable air volume box in the ductwork.
    [Show full text]
  • Controlling Airflow in Class II Biosafety Cabinets
    Controlling Airfl ow in Class II Biosafety Cabinets by Jim Hunter, Senior Project Engineer, Mark Meinders, Product Manager, and Brian Garrett, Product Specialist, Labconco Corporation Introduction Class II biosafety cabinets are defi ned by the National Sanitation Founda- tion (NSF International) as: “A ventilated cabinet for personnel, product, and environmental protec- tion having an open front with inward airfl ow for personnel protection, downward HEPA fi ltered laminar airfl ow for product protection, and HEPA fi ltered exhausted air for environmental protection.”1 In order to maintain proper containment, NSF stipulates that recircu- lating and exhausted airfl ow volumes, and therefore velocities, must be maintained within a tolerance of +/- 5 feet per minute (FPM).2 HEPA fi lter loading can compromise a biological safety cabinet’s ability to maintain proper airfl ow. This paper will review the current technologies used by various biosafety cabinet manufacturers to monitor and maintain proper airfl ows as HEPA fi lters load. Manually Controlling Airfl ow Differential Pressure Gauges When biosafety cabinets were originally developed in the 1960s and 70s, ® ® built-in electronic technologies for measuring and displaying airfl ow were The Purifi er Logic Biosafety Cabinet is one example of a biologi- cal safety cabinet that uses sensorless airfl ow control. prohibitively expensive. To indicate that the cabinet was running prop- erly, most manufacturers opted to equip their cabinets with differential pressure gauges. The differential pressure gauge simply reports the pres- readings may not be intuitive and since most gauges do not have an sure change between points. The most commonly used gauge is known by alarm to indicate a performance failure, there is potential for users to be the trade name Magnehelic™, manufactured by Dwyer Instruments Incor- exposed to unsafe conditions before performance is restored.
    [Show full text]
  • Reverse Flow Fan Filter Units Models: 92Ffu-Rf and 92Ffum-Rf
    MEETING THE NEED FOR COVID-19 PATIENT ISOLATION ROOMS WITH REVERSE FLOW FAN FILTER UNITS MODELS: 92FFU-RF AND 92FFUM-RF According to the ASHRAE Standard 170, all Airborne Infection Isolation (AII) Our Reverse Flow FFU’s create negative pressure environments that remove rooms should be kept at a negative static pressure at all times to prevent the air from an isolation room and clean it via the unit’s built-in HEPA filter, the spread of infected air to the rest of the building. To accomplish this, the which keeps airborne contaminants from escaping the room. These units are exhaust air should be filtered and exceed the supply air. However, in most the most powerful available, featuring... cases, the central exhaust will not be able to accommodate HEPA filtration. • The industry’s highest output, up to 1125 CFM Therefore, using a Reverse Flow Fan Filter Unit (FFU) with HEPA filter can keep the • Energy efficiency (only 65 watts at 90 FPM velocity/450 CFM) room at negative pressure and decontaminate the exhaust air at the same time. • Quiet performance (only 45 DBA at 90 FPM, 58 DBA at 1100 CFM) Nailor has played an important role in helping hospitals provide critical • Ceiling-mount version has the industry’s lowest plenum height – just 16” environment patient isolation care – from the Ebola outbreak of 2014 to the for easier retrofits current COVID-19 pandemic – with our Critical Environment products. • Standard and High Flow HEPA and ULPA filter options Nailor’s Reverse Flow - Fan Filter Units are available in both ceiling-mounted • Ducted and non-ducted versions are available and portable models, making it easier to quickly convert existing spaces into patient isolation rooms.
    [Show full text]
  • BALDWIN HALL (0050) Baldwin Hall Was Originally Constructed in 1937 with Additions Constructed in 1942 and 2018
    BALDWIN HALL (0050) Baldwin Hall was originally constructed in 1937 with additions constructed in 1942 and 2018. The 2018 addition also included modifications to the existing air conditioning systems serving the balance of the building to convert them from constant air volume to variable air volume systems. The building is predominantly served by variable volume Air Handling Units (AHUs) serving duct mounted variable air volume terminal units with hot water reheat coils. There are Fan Coil Units that provide heating and cooling within data rooms on each floor and the new annex stairwell. VARIABLE VOLUME AIR HANDLING UNITS The Air Handling Units deliver a variable volume of conditioned air consisting of a mixture of recirculated building air and fresh air from outside of the building. The building return air is mixed with outdoor air, passed through a bank of filters and cooled with chilled water coils in the building’s air handling unit before being supplied to rooms throughout the building through above ceiling ductwork. The Variable Air Volume terminal units (VAVs) are equipped with an air damper to regulate the volume of air delivered from the central AHU to the space based on the current space temperatures. Most of the VAVs also include a fan, a hot water coil and a filter combination that will mix in air from the above ceiling plenum with the conditioned air from the central AHU when the space requires heating. Air is recirculated from the spaces back to the air handling unit through ceiling mounted air return registers located in each space. Return air is pulled from a plenum space above the ceiling, in lieu of ductwork.
    [Show full text]
  • February 10, 2021 From: Chief Facilities Officer To: All District Administrators and Supervisors Subject: Heating, Ventilation
    February 10, 2021 From: Chief Facilities Officer To: All District Administrators and Supervisors Subject: Heating, Ventilation, and Air Conditioning (HVAC) in Preparation for Limited In-Person Instruction (LIPI) Phase 2 and Hybrid Learning 1. This memorandum provides a summary of HVAC operations and modifications (as needed) in preparation for LIPI Phase 2 and hybrid learning. The memorandum gives district leaders a resource that can be shared with all staff and school communities on the steps being taken to reduce the risk of COVID-19 transmission. 2. This memorandum is organized into seven (7) areas: ● References ● HVAC Guidance for COVID-19 ● Target Operating Conditions for All District Facilities ● Summary of District HVAC Operations and Systems ● Summary of HVAC Systems at District Facilities ● Standard Operating Procedures in the Event of HVAC System Maintenance or Failure ● Frequently Asked Questions (FAQ) ● Glossary of Acronyms 3. Following the guidance from The Oregon Health Authority (OHA), The Centers for Disease Control and Prevention (CDC), The American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE), and Healthy Buildings, the district will improve indoor air quality and reduce the risk of COVID-19 transmission for LIPI Phase 2 and hybrid learning by doing the following: ● Introduce more outside air (OSA) in most buildings. ● Extend operation run times (in general 6 am - 6 pm). ● The district will upgrade all Minimum Efficiency Reporting Value (MERV) 8 filters to MERV 13. ● The district will use portable High Efficiency Particulate Air (HEPA) air cleaners in areas that ​ need them. ​ ● The district will make some areas off limits for LIPI Phase 2 and hybrid learning 4.
    [Show full text]
  • Air Conditioning Today’S Technology Rooms Require Precise, Stable Environments in Order for Sensitive Electronics to Operate Optimally
    Dening Quality. Building Comfort. Precision Air Conditioning Today’s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard In addition, technology rooms may reduce comfort air conditioning is poorly suited for computing capacity as a protective measure, technology rooms, leading to system shut- if environmental conditions are not properly downs and component failures. Because controlled. This protective response results in precision air conditioning maintains reduced computational capacity for the owner. temperature and humidity within a very Standard comfort air conditioning is not designed narrow range, it provides the environmental to handle the heat load profile of critical purpose stability required by sensitive electronic areas, nor is it designed to provide the precise equipment, allowing your business to avoid temperature and humidity set point required expensive downtime. for these applications. Precision air conditioning systems are designed for close temperature and humidity control. They provide high reliability for PreciSion Air condiTioning year-round operation, with the ease of service, APPlicationS system flexibility and redundancy necessary to keep critical applications running 24 hours a day. TemPerature And humidiTy deSign Precision environmental control requirements condiTionS reach far beyond the confines of the traditional data center or computer room to encompass a larger suite of applications. Maintaining temperature and humidity design conditions is critical to the smooth operation of Typical1. applications that benefit from precision a data center or other technology room. Design air conditioning include: conditions% should be 68-77°F (20-25°C) and 40- 2. Medical equipment suites (MRI, CAT scan) 55 relative humidity. As damaging as the wrong Hospital facilities (operating, isolation ambient conditions can be, rapid temperature 3.
    [Show full text]
  • Staff Report #21-006-EQC
    AGENDA ITEM D-2 City Manager's Office STAFF REPORT Environmental Quality Commission Meeting Date: 8/18/2021 Staff Report Number: 21-006-EQC Regular Business: Review and discuss cost effectiveness and policy options report to electrify existing buildings (CAP No.1 strategy) Recommendation City Council requested the commission’s review and feedback on cost effectiveness and policy options to electrify existing buildings as envisioned under Climate Action Plan goal No.1: Electrify 95% of existing building by 2030. Policy Issues In 2019, the City Council declared a climate emergency (Resolution No. 6535) committing to catalyze accelerated climate action implementation. In July 2020, the City adopted a new CAP with the bold goal to reach carbon neutrality (zero emissions) by 2030 that included a goal to electrify 95% of existing buildings by 2030. Converting 95% of existing buildings from using natural gas to electric equipment is a top priority for the City Council as identified in their 2021 work plan. Background The City Council included a top priority in their 2021 work plan to begin work in electrifying 95% of Menlo Park’s existing buildings by 2030. Electricity consumed in Menlo Park is greenhouse gas free as almost all residents and businesses are subscribed to Peninsula Clean Energy. This provides an opportunity to eliminate the use of natural gas (a fossil fuel) in existing buildings by changing natural gas equipment (such as water heaters and space heating) to electric. In 2020, new building reach codes were implemented that require all new buildings to be electric. In order to achieve carbon neutrality, eliminating natural gas in existing buildings through electrification will be crucial.
    [Show full text]
  • Supply Fan Control for Constant Air Volume Air Handling Units
    Supply Fan Control for Constant Air Volume Air Handling Units YoungHum Cho Gang Wang Mingsheng Liu Professor of Architectural Graduate Student Research Associate Professor Engineering, PhD, PE Energy Systems Laboratory, University of Nebraska-Lincoln 1110 So. 67th St, Omaha, NE 68182 Abstract required design size when the HVAC systems design. Since terminal boxes do not have a modulation This results in major fan power waste. damper in constant volume (CV) air handling unit The following is the possible solution for how to (AHU) systems, zone reheat coils have to be solve these issues and control supply fan in the current modulated to maintain the space temperature with CV systems. The best way to control supply fan is an constant supply airflow. This conventional control installation of terminal box and modulate airflow with sequence causes a significant amount of reheat and VFDs on AHUs. In this way, the system should be constant fan power under partial load conditions. changed from CV system to VAV system. This method Variable Frequency Drives (VFDs) can be installed on will be able to control adequate supply fan speed under these constant air volume systems. The fan speed can partial load conditions. However, this method needs be modulated based on the maximum zone load. This high installation and labor fees. Another way is an paper presents the procedure to control the supply fan installation of the VFD on CV system and set the fan speed and analyzes the thermal performance and major speed. In this method, the system will not change and fan energy and thermal energy savings without does not need high installation and labor fees.
    [Show full text]
  • Comparison of Temperature and Enthalpy Controlled Economizer Cycle for All-Air Air-Conditioning Systems in the Mediterranean
    Isı Bilimi ve Tekniği Dergisi, 32, 2, 19-30, 2012 J. of Thermal Science and Technology ©2012 TIBTD Printed in Turkey ISSN 1300-3615 PERFORMANCE EVALUATION OF DIFFERENT AIR-SIDE ECONOMIZER CONTROL METHODS FOR ENERGY EFFICIENT BUILDING Mehmet Azmi AKTACİR Harran University, Department of Mechanical Engineering, Osmanbey Campus, Şanlıurfa, [email protected] (Geliş Tarihi :22.10.2010 Kabul Tarihi:14.02.2011) Abstract Energy saving in all-air air-conditioning systems can be significantly improved by using free cooling application. This application, commonly known economizer cycle, is used when outside conditions are suitable, being cool enough to be used as a cooling medium. The most important and characteristic parameter for free cooling is local climatic features. However, detailed analysis of weather data determines the free cooling potential of a region. In this study, energy analysis of the free cooling applications with the outdoor air temperature and enthalpy controls are carried out for a commercial building conditioned by all-air air conditioning system in Antalya. The results obtained from the sample building analysis show that for all working modes the highest energy saving ratio is obtained by enthalpy control strategy. Keywords: Energy saving; Free cooling; Air-Conditioning; Economizer cycle; Bin number; Antalya. ENERJİ VERİMLİ BİNALARDA FARKLI EKONOMİZER KONTROL YÖNTEMLERİNİN PERFORMANS DEGERLENDİRİLMESİ Özet Tam havalı iklimlendirme sistemlerinde serbest soğutma uygulaması ile önemli ölçüde enerji tasarrufu sağlanabilir. Ekonomizer çevrim olarak da bilinen bu uygulamada, uygun koşullardaki dış hava soğutucu olarak kullanılır. Serbest soğutma için en önemli parametre yerel iklim özelliğidir. Ancak, meteorolojik verilerin detaylı analizi ile bir bölgenin serbest soğutma potansiyeli belirlenir.
    [Show full text]
  • Heat Transfer Performance and Piping Strategy Study for Chilled Water
    HEAT TRANSFER PERFORMANCE AND PIPING STRATEGY STUDY FOR CHILLED WATER SYSTEMS AT LOW COOLING LOADS A Thesis by NANXI LI Submitted to the Office of Graduate Studies of Texas A&M University in partial fulfillment of the requirements for the degree of MASTER OF SCIENCE Chair of Committee, David E. Claridge Committee Members, Charles H. Culp Michael B. Pate Head of Department, Jerald A. Caton December 2012 Major Subject: Mechanical Engineering Copyright 2012 Nanxi Li ABSTRACT The temperature differential of chilled water is an important factor used for evaluating the performance of a chilled water system. A low delta-T may increase the pumping energy consumption and increase the chiller energy consumption. The system studied in this thesis is the chilled water system at the Dallas/Fort Worth International Airport (DFW Airport). This system has the problem of low delta-T under low cooling loads. When the chilled water flow is much lower than the design conditions at low cooling loads, it may lead to the laminar flow of the chilled water in the cooling coils. The main objective of this thesis is to explain the heat transfer performance of the cooling coils under low cooling loads. The water side and air side heat transfer coefficients at different water and air flow rates are calculated. The coefficients are used to analyze the heat transfer performance of the cooling coils at conditions ranging from very low loads to design conditions. The effectiveness-number of transfer units (NTU) method is utilized to analyze the cooling coil performance under different flow conditions, which also helps to obtain the cooling coil chilled water temperature differential under full load and partial load conditions.
    [Show full text]
  • Air Volume Control Systems Air Volume Control Systems Air Volume
    AIR VOLUME CONTROL SYSTEMS AIR VOLUME CONTROL SYSTEMS VENTSVENTS reservesreserves the rightsrights to modifymodify anyany of itsits products’products’ features,features, designs,designs, componentscomponents andand spspecificationsecifications aatt ananyy titimeme aandnd wwithoutithout noticnoticee to maimaintainntain ththee developmdevelopmentent anandd ququalityality of mmanufacturedanufactured ggoods.oods. 08/201511/2016 2016 WWW.VENTILATION-SYSTEM.COM CONTENT General information 4 General concepts of variable air volume terminals 5 VAV terminal construction 7 Terminal units KPR series 8 Accessories 18 Terminal units KPR I20 series 20 Accessories 32 Standard solutions 34 3 VENTS. AIR VOLUME CONTROL SYSTEMS AIR VOLUME CONTROL SYSTEMS GENERAL INFORMATION Usually, some of the most important elements of climate control systems go unnoticed. This is because they are ment to. The main goal of any ventilation system is to make people feel comfortable without any interruptions into ther comfort. The air distribution system in a building is responsible for maintaining appropriate levels of comfort in air quality, temperature, and moisture level consuming the least possible amount of energy at the same time. An example of such a system is a variable air volume, or VAV, system. A VAV system is a type of air distribution sys- tem that supplies one specific temperature of air to each space in a building but controls the temperatures within the building by changing the amount of air supplied to each space. In other words it compensates heat losses in a way, sufficient to maintain the set temperature. The different parts of this system include the air handling unit, the supply ductwork system, air distribution units and the return/exhaust ductwork system.
    [Show full text]
  • Cryocooler Fundamentals and Space Applications
    Cryocooler Fundamentals and Space Applications Ray Radebaugh R. G. Ross, Jr. National Institute of Standards and Technology Jet Propulsion Laboratory Boulder, Colorado 80305 California Institute of Technology (303) 497-3710; [email protected] Pasadena, California 91109 [email protected] Sponsored by Short Course Lecturers: Cryogenic Engineering Conference Ray Radebaugh, NIST Tucson, Arizona R. G. Ross, Jr., JPL June 28, 2015 CSA-CEC2015.ppt Cryocooler Fundamentals and Space Applications Contents Morning (8:00 – 12:00): One 15 min. break Session 1: Information sources, definitions, history, applications, thermodynamics, cryocooler types, Joule-Thomson (JT) coolers, Brayton cryocoolers, Claude systems, heat exchangers Session 2: Regenerative cycles, Stirling cryocoolers, Gifford-McMahon (GM) cryocoolers, 4 K regenerators, pulse tube cryocoolers, types, examples, modeling, cryocooler comparisons, new research Afternoon (1:00 – 5:00): One 15 min. break Session 3: Space cryocoolers, history, applications, long life, Stirling coolers, Ron Ross pulse tube coolers, JT systems, Brayton coolers, system design, qualification, vacuum, conduction and radiation thermal loads Session 4: Performance requirements, thermal measurements, orientation, Ron Ross generated vibration and supression, launch vibration, EMI, AIRS example, sizing, temperature stability, integration 6/28/2015 CSA Short Course, Cryocoolers and Space Applications 2 Course Goals • Provide information to a variety of students • Learn about various types of cryocoolers •
    [Show full text]