Optimizing Your Heating, Ventilating and Air Conditioning Systems

Total Page:16

File Type:pdf, Size:1020Kb

Optimizing Your Heating, Ventilating and Air Conditioning Systems Optimizing Your Heating, Ventilating and Air Conditioning Systems Many modern buildings are designed with a forced-air heating, ventilating and air conditioning (HVAC) systems. While different types of designs may be found, the HVAC system has two critical functions: Hartford Steam Boiler One State Street − Control temperature and humidity for occupant comfort P.O. Box 5024 − Control indoor air quality for a healthy environment Hartford, CT 06102-5024 Tel.: (800) 472-1866 www.hsb.com One type of modern HVAC system achieves this by delivering a variable air volume (VAV) to a space. A VAV system provides many separate units, usually hung above the ceiling, to controls the various space conditions in defined zones of the building. Each zone has its own control sensor mounted in the individual space being controlled. This helps control energy costs by allowing the users to customize the space condition depending on the hours or use. In some systems this can be done for every room in the building. Most modern HVAC systems have a distributed control system that is accessible through the internet for setpoint adjustments or for remote monitoring. Many older systems still use room-unit ventilators. These are units that are installed against an outside wall of the room and are able to pull in fresh ventilation air through a small duct installed through the outside wall of each room. The heating function controls the space temperature in the winter but also preheats the cold outside ventilation air in the cold days of winter. Most of these systems are “heating only” units, but still provide uncomfortably warm, but ventilated rooms, during the warmer seasons. Many older control systems use pneumatic controls. A pneumatic control system uses air pressure signals rather than electrical signals to relay control messages from the rooms to the HVAC equipment. Pneumatic control systems require a noisy air compressor usually in the equipment room. Other larger area spaces are designed with constant air volume HVAC systems. Limited control capabilities contribute to energy waste. This occurs when large horsepower motors run while rooms are unoccupied. Any HVAC system that operates when it is not needed wastes energy. Hartford Steam Boiler Page 2/4 Optimizing Your Heating, Ventilating and Air Conditioning Systems While heating and cooling are ductboard to fall off allowing the to overflow and damage ceiling or seasonal, the ventilation systems seams to discharge air out of the floor tiles. Keeping condensate need to function whenever the ducts. Good integrity of the drains open and clean will reduce the building is occupied. Enforceable insulation and vapor barrier are chance for unhealthy microbiological building and mechanical codes especially important for ducts growth in the dark, damp air specify the ventilation options supplying cold air. Cold air ducts handling units. available for HVAC systems operating in an unconditioned air designers. Ventilation systems, like space will sweat and condense water Inspect for aging or deteriorated all HVAC systems, require frequent out of the hot muggy air. This coils in units and replace if maintenance to keep the system moisture can cause mold problems necessary. Rusting coil frames and working efficiently and effectively. in concealed locations above false flaking aluminum fins on the coils Failing to keep ventilation systems ceilings. will be hard to keep clean due to the maintained and controlled properly corroded surfaces. Steel that has lost has the potential to waste huge its protective galvanizing coating amounts of energy. Bringing in too could promote unhealthy mold or much cold air in the winter, or too slime growth within the air handling much hot, muggy air in the summer, units. forces a great energy load on the boiler or the air conditioning Inspect and maintain fans and systems. A disproportionately high blowers amount of energy is needed to temper hot or cold ventilation air Establish a periodic or seasonal requirements for the rooms while maintenance plan for all fans and occupied. Remove any cardboard or “stuffing” blowers. Document the many types installed by the occupants due to and location of the fans. Be sure to There are many ways that facilities annoying or drafty air discharges on include all lavatory exhaust fans. personnel can help to reduce energy people. Blocking off the intended air These are typically overlooked and waste and redirect saved energy flow by uncomfortable occupants can create unhealthy air in the dollars. Some of the best, simplest forces more air to be delivered to the lavatories. Keep the blower wheel or and lowest cost options for remaining rooms on the system. fan blades clean to maximize the increasing the efficiency of the Verify that the duct systems are open efficiency of the equipment. HVAC systems are: to all the original design rooms and Centrifugal blower wheels frequently properly balanced to prevent collect enough dirt on the bladed to Inspect and maintain all air duct occupants from taking matters into reverse the designed curvature of the systems their own hands. blade. Periodically inspect supply and Clean heating and cooling coils Establish a documented service plan return ducts for air leaking into or out for any kitchen and food services of the duct seams. Also look for open Dirt and dust are great insulators on fans and blowers. Fans used in ducts that may be disconnected and coil surfaces. Even a fine coating of cooking hoods are critical to keep open above false ceilings. Seal all dust on a coil can result in a reduced cleaned of grease residue to prevent leaking duct seams with seam sealer heat exchange, causing the system a fire in the kitchen or the exhaust and cap or repair unused or to run longer to meet heating or duct. The kitchen hoods and fans abandoned branch taps dumping air cooling needs. Keep the coils clean should be serviced by a professional into the ceiling cavities. By repairing throughout the changing seasons. cleaning company familiar with the leaks the air will go where it was fire codes related to proper and safe designed to go and energy will not be During the cooling season, moisture system functioning. wasted. collecting on the cooling coils is collected by drain pans and drained Inspect and replace worn or loose Verify the integrity of the insulation out of the air handler. Drain lines can V-belts on belt driven fans and on insulated ducts. This is especially accumulate dirt or become plugged, blowers. A loose belt on a blower can true for ducts that are made out of causing moisture carryover into the slip, squeal and waste motor rigid insulation board. It is common discharge side of the coil. Plugged horsepower in addition to burning up for duct sealing tape on rigid drains can also cause the drain pan the belts. Friction between the loose Hartford Steam Boiler Page 3/4 Optimizing Your Heating, Ventilating and Air Conditioning Systems belt and the sheave can generate If a motor requires replacement, Verify that the number of belt enough heat to burn the belt and trip consider replacing it with a premium grooves in the sheaves match the the fire alarm causing a building efficiency rated motor. It can save up number of V-belts installed. Multiple evacuation. Make sure the belts are to 8 percent energy compared to a grooved sheaves require the same properly aligned and tracking standard efficiency motor. Also, number of belts to transfer the properly to prevent premature belt check with the HVAC service required horsepower from the motor and bearing wear. Keep all motor provider to see if any motors in the shaft to the driven equipment shaft. bearings and driven equipment shaft building could be retrofitted with bearings lubricated at the scheduled variable frequency drives for energy Establish an air filters maintenance frequency provided by the savings. Make sure all motors are program manufacturer. only operated when performing a needed task. Motors are typically Apply a consistently executed filter Maintain and properly control all large loads and can quickly waste a maintenance program to help motors lot of money if left on when everyone minimize dirt and dust deposits on goes home for the night. Invest in a fans and coils. In addition, keeping Verify that all fractional horsepower simple, economically installed the filters changed at the proper motors are functioning properly. controller for the largest uncontrolled frequencies will help to improve the Although they do not consume a motors in the building. indoor air quality. large amount of energy when they run, they all perform a necessary Maintain all belts and sheaves Determine the optimal frequency for HVAC function. The smaller motors changing the filters based on regular used in small room unit ventilators, Inspect the motor and driven inspections of the filter material. Not heat pumps or stand-alone room air- equipment pulleys or sheaves to all filters need to be replaced at the conditioners have a shorter rated life make sure the V-grove sides are not same frequency. For example, for a than a large equipment room motor. worn into a concave shape. A worn ventilator unit with an outside air These smaller motors usually fail sheave will not transmit the rated filter and a recirculated-air filter, the from seized motor bearings and then mechanical horsepower from the outside air filter many need to be the motor shaft locks up. When this motor to the driven equipment. Worn replaced half as many times as the happens, the motor will continue to sheaves will cause new belts to be recirculated-air filter. Filter change draw energy but do no useful work. If noisy, wear out quickly and perform frequencies are a function of many left unchecked, these motors can get poorly.
Recommended publications
  • VAV Systems, on the Other Hand, Are Designed to Simultaneously Meet a Variety of Cooling and Heating Loads in a Relatively Efficient Manner
    PDHonline Course M252 (4 PDH) HVAC Design Overview of Variable Air Volume Systems Instructor: A. Bhatia, B.E. 2012 PDH Online | PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.PDHonline.org www.PDHcenter.com An Approved Continuing Education Provider www.PDHcenter.com PDH Course M252 www.PDHonline.org HVAC Design Overview of Variable Air Volume Systems A. Bhatia, B.E. VARIABLE AIR VOLUME SYSTEMS In central air conditioning systems there are two basic methods for delivering air to the conditioned space 1) the constant air volume (CAV) systems and 2) the variable air volume (VAV) systems. As the name implies, constant volume systems deliver a constant air volume to the conditioned space irrespective of the load with the air conditioner cycling on and off as the load varies. The fan may or may not continue to run during the off cycle. VAV systems, on the other hand, are designed to simultaneously meet a variety of cooling and heating loads in a relatively efficient manner. The system achieves this by varying the distribution of air depending on the cooling or heating loads of each area. The air flow variation allows for adjusting the temperature in a single zone without changing the temperature of air in the whole system, minimizing any instances of overcooling or overheating. This flexibility has made this one of the most popular HVAC systems for large buildings with varying conditioning needs such as office buildings, schools, or apartments. How a VAV system works? What distinguishes a variable air volume system from other types of air delivery systems is the use of a variable air volume box in the ductwork.
    [Show full text]
  • Controlling Airflow in Class II Biosafety Cabinets
    Controlling Airfl ow in Class II Biosafety Cabinets by Jim Hunter, Senior Project Engineer, Mark Meinders, Product Manager, and Brian Garrett, Product Specialist, Labconco Corporation Introduction Class II biosafety cabinets are defi ned by the National Sanitation Founda- tion (NSF International) as: “A ventilated cabinet for personnel, product, and environmental protec- tion having an open front with inward airfl ow for personnel protection, downward HEPA fi ltered laminar airfl ow for product protection, and HEPA fi ltered exhausted air for environmental protection.”1 In order to maintain proper containment, NSF stipulates that recircu- lating and exhausted airfl ow volumes, and therefore velocities, must be maintained within a tolerance of +/- 5 feet per minute (FPM).2 HEPA fi lter loading can compromise a biological safety cabinet’s ability to maintain proper airfl ow. This paper will review the current technologies used by various biosafety cabinet manufacturers to monitor and maintain proper airfl ows as HEPA fi lters load. Manually Controlling Airfl ow Differential Pressure Gauges When biosafety cabinets were originally developed in the 1960s and 70s, ® ® built-in electronic technologies for measuring and displaying airfl ow were The Purifi er Logic Biosafety Cabinet is one example of a biologi- cal safety cabinet that uses sensorless airfl ow control. prohibitively expensive. To indicate that the cabinet was running prop- erly, most manufacturers opted to equip their cabinets with differential pressure gauges. The differential pressure gauge simply reports the pres- readings may not be intuitive and since most gauges do not have an sure change between points. The most commonly used gauge is known by alarm to indicate a performance failure, there is potential for users to be the trade name Magnehelic™, manufactured by Dwyer Instruments Incor- exposed to unsafe conditions before performance is restored.
    [Show full text]
  • Extract from the Proceedings of Building Simulation and Optimization 2012
    First Building Simulation and Optimization Conference Loughborough, UK BSO12 10-11 September 2012 MODELING AND SIMULATION OF BUILDING ECONOMIZER AND ENERGY RECOVERY SYSTEMS FOR OPTIMUM PERFORMANCE Stephen Treado, Xing Liu Pennsylvania State University University Park, PA appropriate to provide “free cooling”, the rough ABSTRACT equivalent of opening the windows on a nice day This paper describes how building economizer and rather than using mechanical cooling. The former energy/enthalpy recovery system control and study has demonstrated that the energy savings operation can be modelled and simulated to evaluate associated with economizer could be very significant and optimize their performance. A improved method (Brandemuehl et al., 1999). The energy saving of the to determine optimum temperature setpoints and robust control strategy on cooling coil energy outdoor air fractions is discussed and demonstrated. consumption which was evaluated by over one year’s Through the simulation, the new strategy based on comparison tests on two air-handling units in a total system energy use is shown to be able to save building was 88.47% in contrast to the energy up to 11% of energy under certain conditions and to consumption using the conventional control (damper be most useful for dry climates. at fixed position) in Hong Kong (Wang et al., 2004). Energy recovery systems exploit the “free heating or INTRODUCTION cooling” provided by exchanging energy between the exhaust and outdoor airstreams. In both of these Buildings are constructed to serve a purpose, namely systems, some control logic must be implemented to to provide a comfortable, safe, healthy and determine how and when the systems should be productive environment for human endeavours.
    [Show full text]
  • Reverse Flow Fan Filter Units Models: 92Ffu-Rf and 92Ffum-Rf
    MEETING THE NEED FOR COVID-19 PATIENT ISOLATION ROOMS WITH REVERSE FLOW FAN FILTER UNITS MODELS: 92FFU-RF AND 92FFUM-RF According to the ASHRAE Standard 170, all Airborne Infection Isolation (AII) Our Reverse Flow FFU’s create negative pressure environments that remove rooms should be kept at a negative static pressure at all times to prevent the air from an isolation room and clean it via the unit’s built-in HEPA filter, the spread of infected air to the rest of the building. To accomplish this, the which keeps airborne contaminants from escaping the room. These units are exhaust air should be filtered and exceed the supply air. However, in most the most powerful available, featuring... cases, the central exhaust will not be able to accommodate HEPA filtration. • The industry’s highest output, up to 1125 CFM Therefore, using a Reverse Flow Fan Filter Unit (FFU) with HEPA filter can keep the • Energy efficiency (only 65 watts at 90 FPM velocity/450 CFM) room at negative pressure and decontaminate the exhaust air at the same time. • Quiet performance (only 45 DBA at 90 FPM, 58 DBA at 1100 CFM) Nailor has played an important role in helping hospitals provide critical • Ceiling-mount version has the industry’s lowest plenum height – just 16” environment patient isolation care – from the Ebola outbreak of 2014 to the for easier retrofits current COVID-19 pandemic – with our Critical Environment products. • Standard and High Flow HEPA and ULPA filter options Nailor’s Reverse Flow - Fan Filter Units are available in both ceiling-mounted • Ducted and non-ducted versions are available and portable models, making it easier to quickly convert existing spaces into patient isolation rooms.
    [Show full text]
  • BALDWIN HALL (0050) Baldwin Hall Was Originally Constructed in 1937 with Additions Constructed in 1942 and 2018
    BALDWIN HALL (0050) Baldwin Hall was originally constructed in 1937 with additions constructed in 1942 and 2018. The 2018 addition also included modifications to the existing air conditioning systems serving the balance of the building to convert them from constant air volume to variable air volume systems. The building is predominantly served by variable volume Air Handling Units (AHUs) serving duct mounted variable air volume terminal units with hot water reheat coils. There are Fan Coil Units that provide heating and cooling within data rooms on each floor and the new annex stairwell. VARIABLE VOLUME AIR HANDLING UNITS The Air Handling Units deliver a variable volume of conditioned air consisting of a mixture of recirculated building air and fresh air from outside of the building. The building return air is mixed with outdoor air, passed through a bank of filters and cooled with chilled water coils in the building’s air handling unit before being supplied to rooms throughout the building through above ceiling ductwork. The Variable Air Volume terminal units (VAVs) are equipped with an air damper to regulate the volume of air delivered from the central AHU to the space based on the current space temperatures. Most of the VAVs also include a fan, a hot water coil and a filter combination that will mix in air from the above ceiling plenum with the conditioned air from the central AHU when the space requires heating. Air is recirculated from the spaces back to the air handling unit through ceiling mounted air return registers located in each space. Return air is pulled from a plenum space above the ceiling, in lieu of ductwork.
    [Show full text]
  • February 10, 2021 From: Chief Facilities Officer To: All District Administrators and Supervisors Subject: Heating, Ventilation
    February 10, 2021 From: Chief Facilities Officer To: All District Administrators and Supervisors Subject: Heating, Ventilation, and Air Conditioning (HVAC) in Preparation for Limited In-Person Instruction (LIPI) Phase 2 and Hybrid Learning 1. This memorandum provides a summary of HVAC operations and modifications (as needed) in preparation for LIPI Phase 2 and hybrid learning. The memorandum gives district leaders a resource that can be shared with all staff and school communities on the steps being taken to reduce the risk of COVID-19 transmission. 2. This memorandum is organized into seven (7) areas: ● References ● HVAC Guidance for COVID-19 ● Target Operating Conditions for All District Facilities ● Summary of District HVAC Operations and Systems ● Summary of HVAC Systems at District Facilities ● Standard Operating Procedures in the Event of HVAC System Maintenance or Failure ● Frequently Asked Questions (FAQ) ● Glossary of Acronyms 3. Following the guidance from The Oregon Health Authority (OHA), The Centers for Disease Control and Prevention (CDC), The American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE), and Healthy Buildings, the district will improve indoor air quality and reduce the risk of COVID-19 transmission for LIPI Phase 2 and hybrid learning by doing the following: ● Introduce more outside air (OSA) in most buildings. ● Extend operation run times (in general 6 am - 6 pm). ● The district will upgrade all Minimum Efficiency Reporting Value (MERV) 8 filters to MERV 13. ● The district will use portable High Efficiency Particulate Air (HEPA) air cleaners in areas that ​ need them. ​ ● The district will make some areas off limits for LIPI Phase 2 and hybrid learning 4.
    [Show full text]
  • Air Conditioning Today’S Technology Rooms Require Precise, Stable Environments in Order for Sensitive Electronics to Operate Optimally
    Dening Quality. Building Comfort. Precision Air Conditioning Today’s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard In addition, technology rooms may reduce comfort air conditioning is poorly suited for computing capacity as a protective measure, technology rooms, leading to system shut- if environmental conditions are not properly downs and component failures. Because controlled. This protective response results in precision air conditioning maintains reduced computational capacity for the owner. temperature and humidity within a very Standard comfort air conditioning is not designed narrow range, it provides the environmental to handle the heat load profile of critical purpose stability required by sensitive electronic areas, nor is it designed to provide the precise equipment, allowing your business to avoid temperature and humidity set point required expensive downtime. for these applications. Precision air conditioning systems are designed for close temperature and humidity control. They provide high reliability for PreciSion Air condiTioning year-round operation, with the ease of service, APPlicationS system flexibility and redundancy necessary to keep critical applications running 24 hours a day. TemPerature And humidiTy deSign Precision environmental control requirements condiTionS reach far beyond the confines of the traditional data center or computer room to encompass a larger suite of applications. Maintaining temperature and humidity design conditions is critical to the smooth operation of Typical1. applications that benefit from precision a data center or other technology room. Design air conditioning include: conditions% should be 68-77°F (20-25°C) and 40- 2. Medical equipment suites (MRI, CAT scan) 55 relative humidity. As damaging as the wrong Hospital facilities (operating, isolation ambient conditions can be, rapid temperature 3.
    [Show full text]
  • Staff Report #21-006-EQC
    AGENDA ITEM D-2 City Manager's Office STAFF REPORT Environmental Quality Commission Meeting Date: 8/18/2021 Staff Report Number: 21-006-EQC Regular Business: Review and discuss cost effectiveness and policy options report to electrify existing buildings (CAP No.1 strategy) Recommendation City Council requested the commission’s review and feedback on cost effectiveness and policy options to electrify existing buildings as envisioned under Climate Action Plan goal No.1: Electrify 95% of existing building by 2030. Policy Issues In 2019, the City Council declared a climate emergency (Resolution No. 6535) committing to catalyze accelerated climate action implementation. In July 2020, the City adopted a new CAP with the bold goal to reach carbon neutrality (zero emissions) by 2030 that included a goal to electrify 95% of existing buildings by 2030. Converting 95% of existing buildings from using natural gas to electric equipment is a top priority for the City Council as identified in their 2021 work plan. Background The City Council included a top priority in their 2021 work plan to begin work in electrifying 95% of Menlo Park’s existing buildings by 2030. Electricity consumed in Menlo Park is greenhouse gas free as almost all residents and businesses are subscribed to Peninsula Clean Energy. This provides an opportunity to eliminate the use of natural gas (a fossil fuel) in existing buildings by changing natural gas equipment (such as water heaters and space heating) to electric. In 2020, new building reach codes were implemented that require all new buildings to be electric. In order to achieve carbon neutrality, eliminating natural gas in existing buildings through electrification will be crucial.
    [Show full text]
  • Supply Fan Control for Constant Air Volume Air Handling Units
    Supply Fan Control for Constant Air Volume Air Handling Units YoungHum Cho Gang Wang Mingsheng Liu Professor of Architectural Graduate Student Research Associate Professor Engineering, PhD, PE Energy Systems Laboratory, University of Nebraska-Lincoln 1110 So. 67th St, Omaha, NE 68182 Abstract required design size when the HVAC systems design. Since terminal boxes do not have a modulation This results in major fan power waste. damper in constant volume (CV) air handling unit The following is the possible solution for how to (AHU) systems, zone reheat coils have to be solve these issues and control supply fan in the current modulated to maintain the space temperature with CV systems. The best way to control supply fan is an constant supply airflow. This conventional control installation of terminal box and modulate airflow with sequence causes a significant amount of reheat and VFDs on AHUs. In this way, the system should be constant fan power under partial load conditions. changed from CV system to VAV system. This method Variable Frequency Drives (VFDs) can be installed on will be able to control adequate supply fan speed under these constant air volume systems. The fan speed can partial load conditions. However, this method needs be modulated based on the maximum zone load. This high installation and labor fees. Another way is an paper presents the procedure to control the supply fan installation of the VFD on CV system and set the fan speed and analyzes the thermal performance and major speed. In this method, the system will not change and fan energy and thermal energy savings without does not need high installation and labor fees.
    [Show full text]
  • Comparison of Temperature and Enthalpy Controlled Economizer Cycle for All-Air Air-Conditioning Systems in the Mediterranean
    Isı Bilimi ve Tekniği Dergisi, 32, 2, 19-30, 2012 J. of Thermal Science and Technology ©2012 TIBTD Printed in Turkey ISSN 1300-3615 PERFORMANCE EVALUATION OF DIFFERENT AIR-SIDE ECONOMIZER CONTROL METHODS FOR ENERGY EFFICIENT BUILDING Mehmet Azmi AKTACİR Harran University, Department of Mechanical Engineering, Osmanbey Campus, Şanlıurfa, [email protected] (Geliş Tarihi :22.10.2010 Kabul Tarihi:14.02.2011) Abstract Energy saving in all-air air-conditioning systems can be significantly improved by using free cooling application. This application, commonly known economizer cycle, is used when outside conditions are suitable, being cool enough to be used as a cooling medium. The most important and characteristic parameter for free cooling is local climatic features. However, detailed analysis of weather data determines the free cooling potential of a region. In this study, energy analysis of the free cooling applications with the outdoor air temperature and enthalpy controls are carried out for a commercial building conditioned by all-air air conditioning system in Antalya. The results obtained from the sample building analysis show that for all working modes the highest energy saving ratio is obtained by enthalpy control strategy. Keywords: Energy saving; Free cooling; Air-Conditioning; Economizer cycle; Bin number; Antalya. ENERJİ VERİMLİ BİNALARDA FARKLI EKONOMİZER KONTROL YÖNTEMLERİNİN PERFORMANS DEGERLENDİRİLMESİ Özet Tam havalı iklimlendirme sistemlerinde serbest soğutma uygulaması ile önemli ölçüde enerji tasarrufu sağlanabilir. Ekonomizer çevrim olarak da bilinen bu uygulamada, uygun koşullardaki dış hava soğutucu olarak kullanılır. Serbest soğutma için en önemli parametre yerel iklim özelliğidir. Ancak, meteorolojik verilerin detaylı analizi ile bir bölgenin serbest soğutma potansiyeli belirlenir.
    [Show full text]
  • Heat Transfer Performance and Piping Strategy Study for Chilled Water
    HEAT TRANSFER PERFORMANCE AND PIPING STRATEGY STUDY FOR CHILLED WATER SYSTEMS AT LOW COOLING LOADS A Thesis by NANXI LI Submitted to the Office of Graduate Studies of Texas A&M University in partial fulfillment of the requirements for the degree of MASTER OF SCIENCE Chair of Committee, David E. Claridge Committee Members, Charles H. Culp Michael B. Pate Head of Department, Jerald A. Caton December 2012 Major Subject: Mechanical Engineering Copyright 2012 Nanxi Li ABSTRACT The temperature differential of chilled water is an important factor used for evaluating the performance of a chilled water system. A low delta-T may increase the pumping energy consumption and increase the chiller energy consumption. The system studied in this thesis is the chilled water system at the Dallas/Fort Worth International Airport (DFW Airport). This system has the problem of low delta-T under low cooling loads. When the chilled water flow is much lower than the design conditions at low cooling loads, it may lead to the laminar flow of the chilled water in the cooling coils. The main objective of this thesis is to explain the heat transfer performance of the cooling coils under low cooling loads. The water side and air side heat transfer coefficients at different water and air flow rates are calculated. The coefficients are used to analyze the heat transfer performance of the cooling coils at conditions ranging from very low loads to design conditions. The effectiveness-number of transfer units (NTU) method is utilized to analyze the cooling coil performance under different flow conditions, which also helps to obtain the cooling coil chilled water temperature differential under full load and partial load conditions.
    [Show full text]
  • Air Volume Control Systems Air Volume Control Systems Air Volume
    AIR VOLUME CONTROL SYSTEMS AIR VOLUME CONTROL SYSTEMS VENTSVENTS reservesreserves the rightsrights to modifymodify anyany of itsits products’products’ features,features, designs,designs, componentscomponents andand spspecificationsecifications aatt ananyy titimeme aandnd wwithoutithout noticnoticee to maimaintainntain ththee developmdevelopmentent anandd ququalityality of mmanufacturedanufactured ggoods.oods. 08/201511/2016 2016 WWW.VENTILATION-SYSTEM.COM CONTENT General information 4 General concepts of variable air volume terminals 5 VAV terminal construction 7 Terminal units KPR series 8 Accessories 18 Terminal units KPR I20 series 20 Accessories 32 Standard solutions 34 3 VENTS. AIR VOLUME CONTROL SYSTEMS AIR VOLUME CONTROL SYSTEMS GENERAL INFORMATION Usually, some of the most important elements of climate control systems go unnoticed. This is because they are ment to. The main goal of any ventilation system is to make people feel comfortable without any interruptions into ther comfort. The air distribution system in a building is responsible for maintaining appropriate levels of comfort in air quality, temperature, and moisture level consuming the least possible amount of energy at the same time. An example of such a system is a variable air volume, or VAV, system. A VAV system is a type of air distribution sys- tem that supplies one specific temperature of air to each space in a building but controls the temperatures within the building by changing the amount of air supplied to each space. In other words it compensates heat losses in a way, sufficient to maintain the set temperature. The different parts of this system include the air handling unit, the supply ductwork system, air distribution units and the return/exhaust ductwork system.
    [Show full text]