Thermodynamic Properties of R-502

Total Page:16

File Type:pdf, Size:1020Kb

Thermodynamic Properties of R-502 National Refrigerants, Inc. TABLE OF CONTENTS SECTION I — REFRIGERANTS: TECHNICAL DATA 4 Product Part Numbers 7 Refrigerant Property Summary 9 Application Summary 11 Product Data Summary and Thermodynamic Tables 12 R-11 and R-12 15 R-13 17 R-22 19 R-23 21 R-32 23 R-123 and R-124 26 R-134a 28 R-401A and R-401B 31 R-402A and R-402B 34 R-403B 36 R-404A 38 R-407A 40 R-407C 42 R-408A 44 R-409A 46 R-410A 48 R-414B 50 R-417C 52 R-422C 54 R-422B and R-422D 57 R-500 and R-502 60 R-503 62 R-507 64 R-508B 66 Ultra-Low Temperature Refrigeration 68 AHRI Chemical Names and Color Codes SECTION II — RETROFITS AND CONVERSIONS 70 Introduction to Retrofitting: Blends Tutorial 71 Fractionation 79 Temperature Glide 87 Application Property Match 90 Retrofitting Guidelines and Procedures 90 Checklist and Data Sheet 92 R-22 Alternative Retrofit Guidelines 94 General Retrofit Procedures 96 Sizing Thermostatic Expansion Devices (TXV) 6th Edition 2016 Refrigerant Reference Guide National Refrigerants, Inc. SECTION III — REFRIGERANT MANAGEMENT SERVICES 100 Analytical Testing Service 101 Request for Refrigerant Analysis 103 Request for Oil Analysis 105 Recovery Cylinder Hydrostatic Test & Refurbish Program 106 Refrigerant Recovery Containers 107 Instructions for Participating in NRI’s Refrigerant Reclamation Program 109 EZ One-Shot™ Recovery Cylinder 111 Refrigerant Banking Program 112 Guidelines for Maximum Shipping Weights for Recovered Refrigerant Containers SECTION IV — ADDITIONAL TECHNICAL LITERATURE 114 Glossary of Terms 118 Lubricant Cross Reference Guide 122 Lubricants 126 Propylene Glycol SECTION V — REGULATORY & LEGISLATIVE ISSUES 130 Complying with Section 608 Regulations 138 The Refrigerant Sales Restriction 141 Leak Repair 143 Changing Refrigerant Oil 144 Overlap between Section 608 and Section 609 146 EPA HCFC Allocation and Pre-charged Equipment Rules Refrigerant Reference Guide 6th Edition 2016 National Refrigerants, Inc. REFRIGERANTS: TECHNICAL DATA PG: 4-10 NRI PRODUCTS 4 NRI Product Part Numbers 7 Refrigerant Property Summary 9 Application Summary I PG: 11-64 PRODUCT DATA SUMMARY & THERMODYNAMIC TABLES 12 R-11 and R-12 15 R-13 17 R-22 19 R-23 21 R-32 23 R-123 and R-124 26 R-134a 28 R-401A and R-401B 31 R-402A and R-402B 34 R-403B 36 R-404A 38 R-407A 40 R-407C 42 R-408A 44 R-409A 46 R-410A 48 R-414B 50 R-417C 52 R-422C 54 R-422B and R-422D 57 R-500 and R-502 60 R-503 62 R-507 64 R-508B PG: 66 ULTRA-LOW TEMPERATURE REFRIGERATION PG: 68 AHRI CHEMICAL NAMES & COLOR CODES 6th Edition 2016 Refrigerant Reference Guide National Refrigerants, Inc. Product Part Numbers Refrigerants REFRIGERANTS PART NO. TYPE SIZE REFRIGERANTS PART NO. TYPE SIZE R-11 100R11 Drum 100 lb. 27R402A Cylinder 27 lb. R-402A R-12 30R12 Cylinder 30 lb. 110R402A Cylinder 110 lb.* R-13 5R13 Cylinder 5 lb. R-402B 13R402B Cylinder 13 lb. R-13B1 5R13B1 Cylinder 5 lb. R-403B 25R403B Cylinder 25 lb. 30R22 Cylinder 30 lb. 24R404A Cylinder 24 lb. R-22 R-404A 50R22 Cylinder 50 lb. 100R404A Cylinder 100 lb.* 125R22 Cylinder 125 lb.* 800R404A Cylinder 800 lb.* 1000R22 Cylinder 1,000 lb.* 1300R404A Cylinder 1,300 lb.* 25R407A Cylinder 25 lb. 1750R22 Cylinder 1,750 lb.* R-407A 5R23 Cylinder 5 lb. 100R407A Cylinder 100 lb.* R-23 9R23 Cylinder 9 lb.* 925R407A Cylinder 925 lb.* 20R23 Cylinder 20 lb.* 1550R407A Cylinder 1,550 lb.* 70R23 Cylinder 70 lb.* R-407C 25R407C Cylinder 25 lb. R-113 100R113 Drum 100 lb. 115R407C Cylinder 115 lb.* 925R407C Cylinder 925 lb.* R-114 30R114 Cylinder 30 lb. 1550R407C Cylinder 1,550 lb.* 100R123 Drum 100 lb. R-123 24R408A Cylinder 24 lb. 200R123 Drum 200 lb. R-408A 100R408A Cylinder 100 lb.* 650R123 Drum 650 lb. 30R409A Cylinder 30 lb. 30R124 Cylinder 30 lb. R-409A R-124 125R409A Cylinder 125 lb.* 145R124 Cylinder 145 lb.* R-410A 25R410A Cylinder 25 lb. 012R134a Can 12 oz. R-134a 100R410A Cylinder 100 lb.* 30R134a Cylinder 30 lb. 850R410A Cylinder 850 lb.* A30R134a Cylinder 30 lb. Automotive Valve 1450R410A Cylinder 1,450 lb.* 125R134a Cylinder 125 lb.* R-414B 25R414B Cylinder 25 lb. 1000R134a Cylinder 1,000 lb.* 25R417C Cylinder 25 lb. 1750R134a Cylinder 1,750 lb.* R-417C 30R401A Cylinder 30 lb. 25R422B Cylinder 25 lb. R-401A R-422B 125R401A Cylinder 125 lb.* 110R422B Cylinder 110 lb.* 30R401B Cylinder 30 lb. R-422C 24R422C Cylinder 24 lb. R-401B 125R401B Cylinder 125 lb.* 100R422C Cylinder 100 lb.* 25R422D Cylinder 25 lb. R-422D 110R422D Cylinder 110 lb.* 30R500 Cylinder 30 lb. R-500 125R500 Cylinder 125 lb.* 30R502 Cylinder 30 lb. R-502 125R502 Cylinder 125 lb.* R-503 5R503 Cylinder 5 lb. 9R503 Cylinder 9 lb.* 20R503 Cylinder 20 lb.* * RETURNABLE / DEPOSIT 80R503 Cylinder 80 lb.* 4 Refrigerant Reference Guide 6th Edition 2016 National Refrigerants, Inc. Product Part Numbers Refrigerants, Analytical Testing, Lubricants REFRIGERANTS PART NO. TYPE SIZE ALKYLBENZENE OIL PART NO. VISCOSITY SIZE R-507 25R507 Cylinder 25 lb. 150AKB1G 1 Gallon 100R507 Cylinder 100 lb.* NL AKB150 150AKB5G 150 SUS / 32 ISO 5 Gallon 800R507 Cylinder 800 lb.* 150AKB55G 55 Gallon 1400R507 Cylinder 1,400 lb.* 200AKB1G 1 Gallon R-508B 5R508B Cylinder 5 lb. NL AKB200R 200AKB5G 200 SUS / 46 ISO 5 Gallon 10R508B Cylinder 10 lb.* 200AKB55G 55 Gallon 20R508B Cylinder 20 lb.* 300AKB1G 1 Gallon 70R508B Cylinder 70 lb.* NL AKB300 300AKB5G 300 SUS / 68 ISO 5 Gallon 3R170 Cylinder 3 lb. 300AKB55G 55 Gallon R-170 AKB500E1G 1 Gallon (Ethane) 004R170 Cylinder 4 oz. NL AKB500 AKB500E5G 500 SUS / 100 ISO 5 Gallon R-1150 004R1150 Cylinder 4 oz. (Ethylene) AKB500E55G 55 Gallon R-600 016R600 Cylinder 16 oz. (Butane) POLYOLESTER R-600a (Isobutane) 016R600a Cylinder 16 oz. PE321P 1 Pint R-290 (Propane) 014R290 Cylinder 14 oz. NL PE32 PE321Q 150 SUS / 32 ISO 1 Quart PENTANE PE321G 1 Gallon (Liquid) 016RPENTANE Metal Can 16 oz. PE681P 1 Pint NL PE68 PE681Q 300 SUS / 68 ISO 1 Quart PE681G 1 Gallon MINERAL OIL PART NO. VISCOSITY SIZE VACUUM PUMP OIL 1501G 1 Gallon VPO1P 1 Pint NL 150 1505G 150 SUS / 32 ISO 5 Gallon NL VPO VPO1Q 200 SUS / 46 ISO 1 Quart 15055G 55 Gallon VPO1G 1 Gallon 3001G 1 Gallon NL 300 3005G 300 SUS / 68 ISO 5 Gallon 30055G 55 Gallon 5001G 1 Gallon 5005G 500 SUS / 100 ISO 5 Gallon ANALYTICAL NL 500 DESCRIPTION 50055G 55 Gallon TESTING WF32 1 Gallon NRIHPN High Pressure Liquid Refrigerant Test Kit NL WF32 WF325G 150 SUS / 32 ISO 5 Gallon NRILP Low Pressure Liquid Refrigerant Test Kit WF3255G 55 Gallon NRINCN Non-Condensible Vapor Refrigerant Test Kit 1TD 1 Gallon NRIOA Oil Analysis Test Kit NL WF68 5TD 300 SUS / 68 ISO 5 Gallon 55TD 55 Gallon NRIHALON Halon Analysis * RETURNABLE / DEPOSIT 6th Edition 2016 Refrigerant Reference Guide 5 National Refrigerants, Inc. Product Part Numbers Solest®, Chemicals, Recovery Containers, Cylinder Refurbishing SOLEST PART NO. VISCOSITY SIZE** RECOVERY CONTAINERS PART NO. SIZE Solest LT32 SolestLT321G 150 SUS / 32 ISO 1 Gallon EZ One Shot DC30 30 lb. Solest 46 Solest461G 200 SUS / 46 ISO 1 Gallon 100RC30 30 lb. Solest 68 Solest681G 300 SUS / 68 ISO 1 Gallon Recovery Cylinder 100RC40 40 lb. Solest 100 Solest1001G 500 SUS / 100 ISO 1 Gallon 100RC50 50 lb. Solest 120 Solest1201G 600 SUS / 120 ISO 1 Gallon Recovery Cylinder with Float 125RC50F 50 lb. Solest 150 Solest1501G 700 SUS / 150 ISO 1 Gallon Recovery Cylinder 125RC50HP 50 lb. CP4214-150 CP4214-1505G 700 SUS / 150 ISO 5 Gallon Rated 400 PSI Solest 170 Solest1701G 800 SUS / 170 ISO 1 Gallon 200RC125 125 lb. Solest 220 Solest2201G 1000 SUS/220 ISO 1 Gallon Recovery Cylinder 1500RC1000 1,000 lb. CP4214-320 CP4214-3201G 1500 SUS / 320 ISO 1 Gallon 4500RC2000 2,000 lb. Solest 370 Solest3701G 1700 SUS / 370 ISO 1 Gallon 130RC9 9 lb. **Also available in 5 Gallon and 55 Gallon containers Recovery Cylinder Very High Pressure 150RC23 23 lb. 200RC80 80 lb. CHEMICALS PART NO. SIZE Propylene Glycol C100DRUM 100 lb. 96% Inhibited 5PG96 5 Gallon Propylene Glycol (No dye) 55PG96 55 Gallon Recovery Drums C200DRUM 200 lb. 1PG70 1 Gallon C650DRUM 650 lb. 70% Inhibited 5PG70 5 Gallon Propylene Glycol (blue dye) 55PG70 55 Gallon CYLINDER REFURBISHING % Inhibited 5PG40 5 Gallon 40 Disposal of Empty CYLDISP Cylinder Propylene Glycol (blue dye) 55PG40 55 Gallon Non-Refillable DRUMDISP Drum 35% Inhibited 55PG35D 55 Gallon Propylene Glycol (blue dye) HST 30 /40 /50 lb. Cylinder 125HST 125 lb. Cylinder 45% Inhibited 55PG45 55 Gallon Propylene Glycol (blue dye) Hydrostatic Testing 240HST 240 lb. Cylinder 1/2TONHST 1/2 Ton Cylinder 99.9% Uninhibited PROPYL55G 55 Gallon Propylene Glycol (No dye) TONHST 1 Ton Cylinder HSTR 30 /40 /50 lb. Cylinder 125HSTR 125 lb. Cylinder Refurbishing & Hydrostatic Testing 240HSTR 240 lb. Cylinder 1/2TONHSTR 1/2 Ton Cylinder TONHSTR 1 Ton Cylinder 6 Refrigerant Reference Guide 6th Edition 2016 National Refrigerants, Inc. Technical Guidelines Refrigerant Property Summary COMPONENTS TEMP. (Weight %) TYPE GLIDE (˚F) LUBRICANTS COMMENTS Mineral Oil or Refrigeration systems, commercial refrigeration, R-22 100% HCFC 0 Alkylbenzene air conditioning, chillers. Very low temperature refrigeration. R-23 100% HFC 0 Polyolester Properties similar to R-13; can also retrofit R-503. Mineral Oil or Low pressure centrifugal chillers. R-123 100% HCFC 0 Alkylbenzene Can retrofit R-11 equipment with modifications. Mineral Oil or High ambient air conditioning. R-124 100% HCFC 0 Alkylbenzene Can retrofit R-114 equipment with modifications.
Recommended publications
  • AHRI Project 8018 Final Report
    AHRI Project 8018 Final Report Review of Refrigerant Management Programs Prepared for: Navigant Consulting, Inc. 77 South Bedford St. Suite 400 Burlington, MA 01803 781.270.0101 navigant.com Reference No.: 180019 January 2016 © 2016 AHRI. Table of Contents Acronyms, Abbreviations, and Definitions ....................................................................... vii Executive Summary ................................................................................................................... 1 Research Summary ........................................................................................................................................ 1 Program Effectiveness ................................................................................................................................... 4 Best Practices .................................................................................................................................................. 5 Recommendations ......................................................................................................................................... 7 1. Introduction .......................................................................................................................... 10 1.1 Background ............................................................................................................................................. 10 1.2 Objective .................................................................................................................................................
    [Show full text]
  • GEF Impact Evaluation of the Phase-Out of Ozone-Depleting Substances in Countries with Economies in Transition
    65338 v2 GEF Evaluation Office GEF IMPACT EVALUATION Public Disclosure Authorized GEF IMPACT EVALUATION Public Disclosure Authorized Impact Evaluation Information Document No. 18 GEF Impact Evaluation of the Phase-Out of Ozone-Depleting Substances in Countries with Economies in Transition. Volume Two: Country Reports Public Disclosure Authorized October 2009 Public Disclosure Authorized This paper is an input into the GEF Evaluation Office (GEF EO) program of Impact Evaluation. The findings, interpretations, and conclusions expressed herein are those of the authors and do not necessarily represent the views of GEF Evaluation Office, the GEF Council, or the Governments they represent. The papers in the Impact Evaluation information document series are: 1. Approach Paper to GEF Impact Evaluation – Brann and Todd 2. Final Report on Proposed Approach to GEF Impact Evaluation - Foundations of Success 3. GEF Biodiversity Policy Review - Foundations of Success 4. Methodological Challenges in Impact Evaluation: The Case of the Global Environment Facility – Todd and Vaessen 5. Priorities and indicators for Global Environment Benefits from Biodiversity: The current international architecture – Nair 6. Case Study Methodology – Conservation Development Centre 7. Case Study: Bwindi Impenetrable National Park and Mgahinga Gorilla National Park Conservation Project - Conservation Development Centre 8. Case Study: Lewa Wildlife Conservancy – Conservation Development Centre 9. Case Study: Reducing Biodiversity Loss at Cross-Border Sites in East Africa Conservation Development Centre 10. Impacts of Creation and Implementation of National Parks and of Support to Batwa on their Livelihoods, Well-Being and Use of Forest Products – Namara 11. Protected Areas and Avoided Deforestation: A Statistical Evaluation – Andam, Ferraro, Pfaff and Sanchez-Azofeifa 12.
    [Show full text]
  • Refrigerant Management Program
    BY ORDER OF THE AIR FORCE MANUAL 32-7089 SECRETARY OF THE AIR FORCE 4 NOVEMBER 2016 Civil Engineering REFRIGERANT MANAGEMENT PROGRAM COMPLIANCE WITH THIS PUBLICATION IS MANDATORY ACCESSIBILITY: Publications and forms are available for downloading or ordering on the e-Publishing website at www.e-Publishing.af.mil. RELEASABILITY: There are no releasability restrictions on this publication. OPR: AF/A4CF Certified by: HQ USAF/A4C (Maj Gen Timothy Green) Supersedes: AFPAM 32-7089, 14 June 2013 Pages: 51 This manual implements Air Force Policy Directive (AFPD) 32-10, Installations and Facilities, and Title 40, Code of Federal Regulations (CFR), Part 82, Protection of Stratospheric Ozone. It describes the Air Force policy for managing refrigerants used in real property equipment and does not apply to refrigerants used in motor vehicle air conditioning (MVAC) or aircraft refrigeration systems. This manual applies to all Air Force Active, Reserve, Guard, civilian and contractor personnel who develop, acquire, deliver, use, operate, or manage refrigerants used in Air Force real property equipment. Direct questions, comments, recommended changes, or conflicts to this manual through command channels, using the AF Form 847, Recommendation for Change of Publication, through the appropriate functional chain of command. The authorities to waive wing/unit level requirements in this publication are identified with a Tier (“T-0, T-1, T- 2, T-3”) number following the compliance statement. See AFI 33-360, Publications and Forms Management, Table 1.1, for a description of the authorities associated with the Tier numbers. Submit requests for waivers through the chain of command to the appropriate Tier waiver approval authority, or alternately, to the publication OPR for non-tiered compliance items.
    [Show full text]
  • IN the UNITED STATES COURT of APPEALS for the DISTRICT of COLUMBIA CIRCUIT NATURAL RESOURCES DEFENSE COUNCIL, INC., Petitioner
    IN THE UNITED STATES COURT OF APPEALS FOR THE DISTRICT OF COLUMBIA CIRCUIT NATURAL RESOURCES DEFENSE COUNCIL, INC., Petitioner, v. Case No. _______ ANDREW WHEELER, Administrator, U.S. Environmental Protection Agency, and UNITED STATES ENVIRONMENTAL PROTECTION AGENCY, Respondents. PETITION FOR REVIEW of a final rule of the U.S. Environmental Protection Agency Pursuant to Clean Air Act § 307(b)(1), 42 U.S.C. § 7607(b)(1), Rule 15 of the Federal Rules of Appellate Procedure, and D.C. Circuit Rule 15, the Natural Resources Defense Council hereby petitions the Court for review of the final rule of Respondents Andrew Wheeler, Administrator, U.S. Environmental Protection Agency (EPA), and EPA, titled “Protection of Stratospheric Ozone: Revisions to the Refrigerant Management Program’s Extension to Substitutes.” This rule was published in the Federal Register at 85 Fed. Reg. 14,150 on March 11, 2020. A copy of the rule is attached as Exhibit A. Dated: May 11, 2020 Respectfully submitted, /s/ Melissa J. Lynch Melissa J. Lynch David D. Doniger Natural Resources Defense Council 1152 15th Street NW, Ste. 300 Washington, DC 20005 Telephone: (202) 289-6868 [email protected] [email protected] Sarah C. Tallman Natural Resources Defense Council 20 N. Wacker Dr., Ste. 1600 Chicago, IL 60606 Telephone: (312) 651-7918 [email protected] Counsel for Petitioner Natural Resources Defense Council, Inc. 2 IN THE UNITED STATES COURT OF APPEALS FOR THE DISTRICT OF COLUMBIA CIRCUIT NATURAL RESOURCES DEFENSE COUNCIL, INC., Petitioner, v. Case No. _______ ANDREW WHEELER, Administrator, U.S. Environmental Protection Agency, and UNITED STATES ENVIRONMENTAL PROTECTION AGENCY, Respondents.
    [Show full text]
  • Mergers, Acquisitions, Name Changes
    MERGERS, ACQUISITIONS, NAME CHANGES 575 Mergers, Acquisitions, Name Changes Looking for a manufacturing company that doesn’t seem to be listed in this 2009 Directory Issue? If you can’t find it in the Manufacturers Alphabetic Listings, then one of several things may have happened. The company could have dropped out of the hvacr industry — ceased to operate altogether, or just stopped making hvacr products; or the company may have changed owners and it is now a part of another corpo- rate identity. In either case, this listing may help. Following are the names of hundreds of manufacturers and their brand names that were found in previous editions of the Directory Issue. Many of these companies continue to exist, but are now known under different names. To find the new identity, just look up the old name in this alphabetic listing. If no information is available, we simply provide the last year the company was listed in the Directory Issue. This listing represents our best efforts at tracking the manufacturer-members of the hvacr community. If we have erred or provided incomplete information, we apologize and hope that you will set us straight. Contact The News Editorial Department at P.O. Box 2600, Troy, Mich. 48007. A Adelta Mfg Co., Inc., Philadelphia AAF-McQuay Inc., Dallas Last listed in 1971. As part of a corporate reorganization in 1994, SnyderGeneral Corp. was given this new name and Advance Systems Inc., Lewiston, Maine was divided into two major companies — McQuay The company was sold to Erie Manufacturing Co. International and AAF International.
    [Show full text]
  • Proposed Rule: Protection of Stratospheric Ozone
    The EPA Administrator, Gina McCarthy, signed the following proposed rule on October 15, 2015, and EPA is submitting it for publication in the Federal Register (FR). While we have taken steps to ensure the accuracy of this Internet version of the rule, it is not the official version of the rule for purposes of public comment. Please refer to the official version in a forthcoming FR publication, which will appear on the Government Printing Office's FDsys website (http://www.gpo.gov/fdsys/search/home.action) and on Regulations.gov (http://www.regulations.gov) in Docket No. EPA-HQ-OAR-2015-0453. Once the official version of this document is published in the FR, this version will be removed from the Internet and replaced with a link to the official version. This document is a prepublication version, signed by the EPA Administrator, Gina McCarthy, on October 15, 2015. We have taken steps to ensure the accuracy of this version, but it is not the official version. 6560-50-P ENVIRONMENTAL PROTECTION AGENCY 40 CFR Part 82 [EPA-HQ-OAR-2015-0453; FRL-9933-48-OAR] RIN: 2060-AS51 Protection of Stratospheric Ozone: Update to the Refrigerant Management Requirements under the Clean Air Act AGENCY: Environmental Protection Agency (EPA). ACTION: Proposed rule. SUMMARY: The Clean Air Act prohibits the knowing release of ozone-depleting and substitute refrigerants during the course of maintaining, servicing, repairing, or disposing of appliances or industrial process refrigeration. The existing regulations require that persons servicing or disposing of air-conditioning and refrigeration equipment observe certain service practices that reduce emissions of ozone-depleting refrigerant.
    [Show full text]
  • Geyser C-Series 2019
    Geyser C-Series 2019 The Nyle Systems Geyser C-Series product line is a High Efficiency Air-to-Water or Water-to Water Heat Pump Water Heating System. Heat Pump Water Heaters provide the most efficient way to heat water , drawing energy from the ambient air or available source water and thereby saving up to 75% in costs when compared to electric water heaters. Upon using the air source models, air surrounding the C-Series is cooled and dehumidified, which can be ducted to an alternate location, while heating potable water. In utilizing the water source models, we are cooling source water on one side while heating potable water on the other. We are reducing air conditioning load as well as reducing heating costs. The C-Series are designed and manufactured in our state How does the GEYSER C-Series work? of the art facility located in Brewer, Maine. These units use various options to meet your application needs. They are The Geyser Heat Pump Water Heater captures heat and suitable for drinking water applications with the standard humidity from the surrounding air, or heat from source double wall heat exchanger. water, and transfers that heat energy into a storage tank. In basic terms, Heat Pump Water Heaters move Energy Efficiency heat from where it is not needed, to where it is desired. Performance is expressed in Coefficient of Performance The Geyser C-Series provides low cost water heating (COP). In typical installations, the Geyser C-Series and supplemental cooling that can be directed where achieve COP’s ranging from 3-5.
    [Show full text]
  • The Economics of Reclamation
    VISITVISIT USUS ONON THETHE WEB!WEB! FindFind more more inspiring spotlights stories at at greenhvacrmag.comgreenhvacrmag.com Up Close Behind the Scenes with the Industry’s Leading Innovators The best replacement for R-22 is reclai m ed R-22, according to the experts at Hudson Technologies Co m p any. over Antarctica) and allowing harmful ultra- U.S. and most other developed countries in Rogers Supply Company in Illinois. She The process Zugibe developed a quar- violet radiation to reach humans and other 2020. So where does that leave owners of shares that the per-pound prices have ranged ter-century ago is fundamentally the same life back on the ground. legacy coolers, those designed to run with the from $5.50 in 2015 to $11 in 2016–2017, as what’s used today, and it’s still the fast- The phasing out of CFCs is widely cred- greatest energy efficiency on R-22? then back down to $7 in 2018. “Some people est, most efficient reclamation equipment ited as an effective global effort to repair the The economic and environmental equation worry that R-22 will run out in the future. in the world, able to reclaim every type of ozone hole. In place of CFCs came other is not lost on Hudson. The company’s tech- But we tell them if their equipment is in good refrigerant on the market. And with mil- technologies (HCFCs and HFCs), and in nologies and services—as delivered through shape to stick with the reclaimed product.” lions poured into further research and de- particular HCFC-22, otherwise referred to wholesalers and HVAC contractors—enable People like Lampton are on the front lines velopment, Hudson Technologies can also as R-22.
    [Show full text]
  • Freon™ 123 PUSH Bulletin
    Freon™ 123 Refrigerant (R-123) Properties, Uses, Storage, and Handling Freon™ 123 Refrigerant Table of Contents Shipping, Storage, and Handling ......................................16 Shipping Containers in the United States ..............................16 Introduction ...........................................................................3 Bulk Storage Systems ..........................................................................16 Background .......................................................................................................... 3 Storage, Handling, and Use Recommendations .................16 Freon™ 123—An Environmentally Acceptable Prohibited Uses ...................................................................................16 Alternative ....................................................................................................... 3 Personal Protective Equipment ................................................17 Uses .......................................................................................3 Storage ......................................................................................................17 Refrigerant ...................................................................................................... 4 Handling ....................................................................................................17 Heat-Transfer Fluid ....................................................................................4 Charging, Maintenance, and Sampling .................................18
    [Show full text]
  • HFC Proposed Second 15-Day Changes Notice
    State of California Air Resources Board Second Notice of Public Availability of Modified Text and Availability of Additional Documents Proposed Amendments to the Prohibitions on Use of Certain Hydrofluorocarbons in Stationary Refrigeration, Chillers, Aerosols-Propellants, and Foam End-Uses Regulation Public Hearing Date: December 10, 2020 Public Availability Date: August 3, 2021 Deadline for Public Comment: August 18, 2021 At its December 10, 2020, public hearing, the California Air Resources Board (CARB or Board) approved for adoption the proposed amendments to sections 95371, 95372, 95373, 95374, 95375, 95376, 95377, 95378, and added section 95379 Article 4, Subarticle 5, Chapter 1, Division 3, Title 17, California Code of Regulations, which prohibits certain substances in refrigeration, air-conditioning (AC), chillers, cold storage, aerosols-propellants, and foam end-uses to reduce high-global warming hydrofluorocarbon (HFC) emissions and support California’s greenhouse gas (GHG) emission reduction goals. In Resolution 20-37, the Board recognized the importance of near-term actions to reduce GHGs, including HFCs, by ensuring successful and orderly transition to lower global warming potential (GWP) refrigerants, which is necessary to reduce the impacts of climate change, and meet California’s legal mandate to reduce HFC emissions by 40 percent below 2013 levels by 2030, as identified in section 39730.5 of the Health and Safety Code. The Board, therefore, approved the adoption of the proposed amendments and found that an additional compliance pathway for AC manufacturers was appropriate.1 The Board directed the Executive Officer to determine if additional conforming modifications to the regulation were appropriate and to make any proposed modified regulatory language available for public comment, with any additional supporting 1 See State of California, Air Resources Board, Board Hearing Transcript, December 10, 2020.
    [Show full text]
  • Freon™ 407C and 407A Properties, Uses, Storage, and Handling
    Freon™ 407C and 407A Refrigerants (R-407C and R-407A) Properties, Uses, Storage, and Handling Freon™ Refrigerants Table of Contents Introduction ...........................................................................4 Air Monitors and Leak Detection ...................................... 16 Freon™ 407C and Freon™ 407A Refrigerant Types of Detectors .................................................................................16 Descriptions ................................................................................................... 4 Nonselective Detectors .................................................................16 Uses ......................................................................................4 Halogen-Selective Detectors ....................................................16 Physical Properties ...............................................................4 Compound-Specific Detectors .................................................16 Fluorescent Additives .....................................................................16 Chemical/Thermal Stability .............................................. 10 Stability with Metals .............................................................................10 Storage and Handling ........................................................ 17 Thermal Decomposition......................................................................11 Shipping Containers in the United States ..............................17 Compatibility Concerns If HCFC-22 and Freon™ Bulk Storage
    [Show full text]
  • Low Pressure Refrigerant Reclamation Systems
    http://www.siqinc.com/hvacr-manufacturing/refrigerant-reclamation/low-pressure-refrigerant-reclamation-systems/ PG 1 of 1 Low Pressure Refrigerant Reclamation Systems This system addresses the needs of commercial system manufacturers looking to reclaim the large volume, low pressure refrigerant charges from their chillers and roof top products. Our turnkey system initiates the process with an inlet tank to consolidate and convert refrigerant into vapor phase. Refrigerant then flows to the automatic processing station that removes particulates, oil, non condensible gasses and moisture. Refrigerant is processed to reclaimed quality specifications before being pumped to the storage tank for testing and re-use. The world’s largest chiller and commercial HVAC system manufacturers depend on this system to reclaim their low pressure refrigerant charges from repair areas, test areas, and laboratory units. Low Pressure Reclaimed Inlet Evaporator Tank Product Detail Refrigerant Holding Tank STANDARD FEATURES: PRODUCT OPTIONS: DIMENSIONS: • Automatic operation • Back-up compressor 74″H x 60”W x 72”D • Refrigerant reclamation to ARI-700 • Air cooled or water cooled condensing unit UTILITY REQUIREMENTS: • Pressure blower for compression of refrigerant • Process R-11, HCFO-1233ZD, or other Electric: 480V, 3Ø, 60A low pressure refrigerants • Oil separation and automatic drain Air: 100 psig shop air • Scalable for various recovery rates • High capacity desiccant driers Water: City water or chilled water supply • Reclaimed refrigerant moisture indicator (water-cooled systems only) • Automatic air/non-condensable removal • Onboard, electric transfer pump • Allen Bradley PLC control and Operator Interface • Warning light fault indicator • Panel mounted hour meter • Reclaimed refrigerant totalizing meter Serv-I-Quip, Inc.
    [Show full text]