CHAPTER 5
SECONDARY NETWORK SYSTEMS
D. N. REPS
maintaining satisfactory voltage conditions. These I. DEVELOPMENT OF SECONDARY-NETWORK problems were serious obstacles to further development DISTRIBUTION of the d-c distribution system. From the earliest days of electric power usage, the As early as 1915, some forms of alternating current distribution of power in concentrated commercial areas systems patterned after the d-c network system began has been a major concern of electric utilities. Require- to appear in commercial areas. These systems used a ments and limitations generally not found in other grid of conductors operating at utilization voltages and areas have resulted in unique problems in the design energized from a number of step-down transformer and operation of commercial-area distribution systems. banks. Fuses were applied between the transformers and High concentration of commercial electric load, the re- the secondary grid in an attempt to provide some means quirements of this load for interruption-free service, and of isolating faulted cables or transformers. Experience the need for well-regulated utilization voltage have had with these early a-c networks proved to be unsatis- fundamental influence on the design of systems to serve factory because of the operating limitations of fuses. these loads. Flexibility to handle new loads where and This experience showed that detection of power-flow when they occur is another requirement which takes on direction was required to prevent a fault in a trans- added importance in the commercial area. The usual former or primary feeder from interrupting service to physical congestion in the downtown area and the dif- the system loads. Subsequent developments resulted in ficulties in locating heavy equipment and circuits over- an automatic switch and the necessary relays to pro-- head have resulted in the use of underground distribu- vide completely automatic operation of an alternating- tion systems in the downtown areas of most large cities. current network system. Such a scheme assured isola-
1. Early Network Systems From 1884 to about 1922, distribution in heavy load 300 density commercial areas became firmly established as a d-c network system. The very first electric power sys- 280 tems applied to serve the downtown office buildings in (1/ 260 cities such as New York and Chicago were underground d-c systems. Rapid growth and early improvement re- >-co 240 sulted in considerable investment in d-c facilities. While er 220 the pattern was established at an early date for d-c 0 systems in downtown areas of large cities, the develop- - 200 ment of practicable and efficient transformers soon per- ›. 180 mitted the application of the more efficient a-c system to rr urban and residential areas. 2 160 The d-c system in commercial areas was designed to 0 provide interruption-free service from a grid of con- U)hi 140 ductors. The d-c grid or network was energized from 120 multiple sources, usually several a-c to d-c converter stations operating in conjunction with large battery • 100 installations for emergency supply. While providing re- 1-1 liable service, the d-c network presented inherent dis- O 80 U- advantages which grew to serious proportions as expan- 0 60 sion was necessary to keep pace with load growth. rr Among these disadvantages were the following: the cost 2 40 of installing, operating, and maintaining large converter stations and battery installations; the problem of find- 20 ing locations for these installations in the downtown 0 area; the cost of copper conductors and the space re- 1922- 24 28 32 36 40 44 46 52 56 60 quired in underground ducts for the ever increasing YEAR number of circuits necessary to carry the low voltage Fig. 1—Growth in number of cities employing secondary- d-c power throughout the area; and the problem of network systems—including foreign installations. 149
Gridco, Inc. v. Varentec, Inc. IPR2017-01135 GRIDCO 1004 Part 2 of 5 - 157/576 150 Secondary Network Systems tion of a primary-system fault by a means which sensed SUBSTATION BUS • • CIRCUIT BREAKERS a reversal of power flow. In April, 1922, the first multi- NO 3 feed low-voltage a-c network using fully automatic net- PRIMARY FEEDERS work protectors was put in operation in New York City. 11111
SWITCH 2. Growth of Network Applications TRANSFORMER NET WORK The low voltage a-c secondary network has become PROTECTOR well accepted as the standard distribution system ar- SECONDARY rangement in large city commercial areas. Based on re- GRID cent census figures, there are only two cities in the United States with populations greater than 250,000 that do not use secondary network distribution. Appli- LOADS cation has steadily expanded into smaller cities and towns as increasing load density and electrical usage have necessitated improvements in commercial-area distribution. At present there are approximately 260 cities in the United States which use secondary network distribution in some form. While most of these systems Fig. 3—Simplified one-line diagram of a conventional a-c are underground, there are many localities operating secondary network. partially or completely overhead secondary network systems. Growth in the application of networks has been almost uninterrupted over the years. At the same II. ELEMENTS OF THE SYSTEM time, the increasing size and growing electrical load of In its conventional form, the network system, whether most cities have resulted in a continual increase in the underground or overhead, consists of an interconnected number of cities which could reasonably and profitably grid of low-voltage circuits operating at utilization apply network systems in their downtown areas. Esti- voltage and energized from a number of primary feeder mates indicate that networks are applied in only 40 per circuits and step-down transformers. A typical network cent of the total number of cities which could reason- system in which the low-voltage circuits are intercon- ably be considered to have use for this type of system. nected in the form of a grid or mesh is shown in Fig. 3. The system of multiple primary-feeder circuits, each supplying more than one step-down transformer feeding into the common secondary grid, is designed to provide uninterrupted service, except in the case of complete E 0-5000 KVA PEAK LOAD failure of the power supply to the primary feeders. The 5001-10000 KVA design of the system is based on the premise that failure of any one primary feeder circuit or step-down trans- g 10 001-20 000 KVA former causes no service interruption since the load con- 20 001-50 000 KVA tinues to be supplied over the remaining primary feeders and transformers. Automatic isolation of a faulty pri- 50 001-60 000 KVA mary circuit or network transformer is provided by the tripping of the feeder circuit breaker, and the circuit 200 breaker in each of the network protectors located in the
180 secondary leads of the network transformers supplied by the faulted feeder. The automatic network protector 160 was specially developed for this function of interrupting a back feed of power from the network grid to the trans- 140 former or feeder. Segregation of the basic network into 120 three parts facilitates discussion of basic system ele- ments. These major segments are: 100 1. The secondary grid 80 2. The network units—consisting of step-down trans- 60 former and automatic network protector 3. The primary feeder circuits 40
20 3. Underground Networks—The Secondary Grid AL.1 1111 The secondary circuits which are tied together at various points to form the common grid generally sup- 1931 1943 1952 1955 ply all or most of the single-phase and three-phase loads Fig. 2—Evolution of the number of individual network in the network area. The disadvantages of separate systems of various sizes—including foreign installations. power and lighting transformer banks, and duplication
Gridco, Inc. v. Varentec, Inc. IPR2017-01135 GRIDCO 1004 Part 2 of 5 - 158/576 Secondary Network Systems 151
of secondary mains and services, are avoided by the use Table 1—Secondary Cable Miles in Service and of a common three-phase, four-wire system at utilization Failure Rate voltage. The secondary grid operates at a utilization voltage which has varied over the years from 115/199 to Miles of Per Cent of Failures Per 100 Cable Total 125/216 volts. As a nominal system voltage, 120/208 Miles Per Year volts has become most widely accepted. It should be Types of emphasized that 120/208 volts is considered to be a Cable 1955 1952 1955 1952 1955 nominal system voltage, that is, the nominal voltage delivered at the customer's service. This voltage pro- Paper-Lead 4 449 16.68 16.13 3.70 3.84 vides a standard lamp voltage from line to neutral and Rubber- a three-phase line-to-line voltage generally satisfactory Lead 10 726 41.85 38.89 1.64 1.87 for power applications. The transformers supplying this system have a standard voltage rating of 216Y/125 volts. Miscel lane- Secondary Mains The secondary mains forming the ous Lead 272 0.84 0.99 6.95 0.13 grid from which consumers' services are tapped gen- erally follow the geographical pattern of the load area Non-Lead and are located under the streets or alleys, so that the Including 12 132*** 40.63 43.99 3.57 9.79 service route to the consumers can be as short as possi- Neoprene ble. This arrangement facilitates access to the main for Rubber repairs, maintenance, and service connections. These 0.32 circuits are generally carried in duct systems, and the Neoprene 7 298 (18.77) (26 46) 0.42 service connections are made in manholes, vaults, or TOTAL 27 579 100.00 100 00 3.02* 3.36** shallow junction boxes. *Includes 174 Failures, Type Cable Unknown—**Includes 249 Cases Un- Single conductor cables are generally used in the known—***Includes Rubber Neoprene. secondary grid because of the many interconnections Table reproduced from Reference 1. and service taps required. These can be made more easily and less expensively on single conductor cables One of the major factors influencing the design of net- than on multi-conductor cables. Another reason for work secondary grids has been the problem of protect- using single conductor cables is that circuit continuity ing against cable failures in the grid. For many years, can be maintained after a cable fault where parallel network systems were designed on the basis that faults conductors per phase are employed. In the early net- in the secondary cables would be self-clearing. This de- work systems, practically all cable used in the secondary sign was premised on obtaining sufficient fault current grids consisted of rubber-- or paper-insulated, lead at a cable fault to burn the conductor free of the point sheath cable. With the development in recent years of of fault. This is feasible on low-voltage circuits such as ' newer, improved types of non-metallic sheath cable, 120/208-volt secondary network grids, because arcs are there has been an increasing trend toward eliminating not sustained at that voltage. For circuits operating at the problems associated with splicing and terminating lead sheath cables. At the present time, approximately 1.8 43 per cent of network cable in use on underground sys- tems is non-leaded, as shown in Table 1. The size of the conductors in the secondary main de- ON 1.6 TI CURVE NO pends primarily on the required current carrying capac- A
UL $ ity. However, the voltage drop from a transformer to CURVE NO. 2 any load along the mains under normal operating con- REG 1.4 ditions, i.e., with all transformers in operation, should E
not exceed about two per cent. The carrying capacity of ATIV
a secondary network main should be one-half to two- REL 1.2 thirds of the rated capacity of the predominant size of network transformer unit. This relationship is based on the premise that a transformer is connected in the grid to so as to feed in at least two directions; and also that a 100 90 80 70 60 50 40 part of the total current of the transformer supplies load PERCENT POWER FACTOR at the transformer location itself. Fig. 4—Relative voltage regulation per unit length of three- Burning Faults Clear—Conductor sizes commonly used phase circuit at various power factors. in underground secondary networks are No. 4/0, 250, Curve No. 1—Three 500-MCM single-conductor cables 350, and 500 MCM, AWG. However, because of rela- in one duct. tively high voltage drop, difficulty in handling and in Curve No. 2—Two parallel branches of three 4/0 single- burning faults clear, parallel-conductor 4/0 or 250 MCM, conductor cables; one duct per branch. AWG circuit are preferred. Fig. 4 shows the reduction Curve No. 3—Two parallel branches of three 250 MCM in voltage drop obtained by using several parallel con- single-conductor cables; one duct per ductors of smaller size. branch.
Gridco, Inc. v. Varentec, Inc. IPR2017-01135 GRIDCO 1004 Part 2 of 5 - 159/576 152 Secondary Network Systems
higher voltages such as 460 volts, this method of clear- 300 KVA 1" 5%2 ing faults is not always dependable. Use of "limiters" to (co ocan 0011 500 MC M- a0Z1 0101 FAVLY—It overcome this problem is discussed below. Tests and taw 4250 AMP. 05%! calculations have shown that the minimum currents 500 FT. 1 shown in Table 2 are required to burn clear the most 300 KVA 300 KVA L1-115% Z 5%2 severe type of fault. Such a fault is one in which the coon OHM TWO 4(01-0.0352 01431 !Aim 0 0070 OHM current and thermal capacity of the faulting mechanism (b) < AmP.•(1.3.2%) • AuLT-> are greater than that of the conductor itself, so that the
conductor on each side of the fault becomes fused. Such 300 KVA 300 KVA 5% 5%2 a fault might occur when a power shovel digs into a duct 0.001; OHM TWO 4/01-00350 OMM ZACH 0.0072 01131 (C) line. The probability of faults of this type is rather 4 3504. AMA CPT 1%1, F"LT small. Most faults on network grids clear with much smaller currents than those shown in Table 2. Fig. 5—Tying together paralleled conductors in a secondary main assists the burning-off of faults. Table 2—Minimum Current in Amperes Required in Each Conductor on Both Sides of a Solid Fault on Single- Conductor Cables to Burn Off the Fault fault at the end of the 500-foot section of 500-mcm cable will be 4250 amperes, or only 85 per cent of the 5000 Conductor Size Overhead Circuit Underground Circuit amperes necessary to clear a solid fault on that size con- 1 1000 1600 ductor. In Fig. 5(b), two paralleled 4/0 AWG conduc- 1/0 1200 1800 tors are substituted for the 500-mcm cable and the fault 2/0 1400 2100 clearing ability is improved. However, the amount of 3/0 1700 2500 fault current is still only 98.2 per cent of the 2900 4/0 2100 2900 amperes required for this size conductor. If, as in Fig. 250 MCM 2300 3200 5(c), the two paralleled 4/0 conductors are tied together 350 MCM 3000 4000 500 MCM 4000 5000 at the midpoint of the section, the available fault cur- rent is increased to 149.2 per cent of the 2900 amperes required for burn-off. This provides a wide margin of Parallel Conductors per Phase—The problem of burn- safety. The improvement in fault clearing ability is a ing off secondary faults influences design of secondary result of two factors: Both transformers supply energy grids by tending to limit the largest size conductor used, to the fault even after it is burned off on one side; and so as not to require an excessive amount of current for the effective impedance to the fault is less than that of burn-off. Since the load carrying ability needed in each either the single conductor or the two paralleled con- section of the main in the grid is directly related to the ductors without a tie point. The effectiveness of using size of network transformer used in the system, the parallel conductors and tie points is assured by carrying required current-carrying capacity is provided by using each set of three-phase conductors in a separate duct to two or more parallel conductors per phase tied together prevent a fault in one branch from affecting another. at the various junction points and service manholes in Limiters—While satisfactory clearing of secondary the grid. A 500-mcm conductor is about the largest con- cable faults by burn-off is often obtained, other cases ductor that can be expected to burn clear consistently. exist where faults would not burn clear, resulting in ex- Larger conductors require high minimum-fault currents, tensive cable damage, manhole fires, and interruption of which are difficult to obtain in network mains except service. Such cases require a fusible device for installa- where the transformer capacity is highly concentrated. tion at each end of each run of secondary cable. Fre- Also, the large amount of metallic vapor generated when quently there will be a few mains in a secondary net- a large conductor fuses makes it difficult to obtain arc work grid, particularly around the fringe areas, where extinction. With a parallel arrangement of secondary fault current is insufficient to insure clearing a solid main conductors, a fault opens only one of the branch fault. To avoid the possibility of faults failing to clear, conductors. To help maintain the maximum possible and to minimize the amount of cable damage resulting fault current available at the fault point, the parallel from secondary faults, limiters were first developed and circuit may be tied together at relatively short inter- applied. n New York in 1936. These high-capacity fuses vals, such as at the various service manholes between are called limiters because of their function of limiting main junction points. With such a circuit arrangement, damage to cable insulation as a result of carrying fault only a small section of main is affected by a fault, and current. It should be noted that these devices are not the magnitude of fault current at the fault point is designed to limit fault current, and should not be con- generally increased. fused with current-limiting fuses. The limiter is a re- The effects of parallel mains and tie points are illus- stricted copper section installed in the secondary main trated by Fig. 5. The fault location used in this example at each junction point. At the present time, limiters are is usually the most difficult location at which to com- being used to some extent in a majority of network sys- pletely clear the fault, because the current to one side tems. Some of the more recent systems have been in- of the fault is limited by the impedance of the entire stalled with limiters terminating all secondary cables. length of secondary main. In Fig. 5(a), the current to a In other systems, limiters have been installed in sections
Gridco, Inc. v. Varentec, Inc. IPR2017-01135 GRIDCO 1004 Part 2 of 5 - 160/576
Secondary Network Systems 153
where doubt exists as to the availability of sufficient 10000 fault current for clearing secondary cable faults. 0 I INSULATION DAMAGE _ 5000 Since the limiter is designed to burn clear only on CHARACTERISTICS faults of sufficient magnitude to cause damage to the BALANCED CIRCUIT cable insulation, its time-current characteristic is co- %.‘ CONDITIONS 3 PHASES AND ordinated with the insulation-damage characteristic of NEUTRAL IN DUCT the cable. The insulation-damage characteristic has been 1000 %.\ found to be very similar for rubber-covered cable and \ \t"---- 1000 MCM oil-impregnated, paper-insulated cable. Curves giving 500 1:",‘ 750 MCM — \\‘\‘‘\.....--- 50 0 MCM the time-current characteristics of limiters and the in- 40 0 MCM sulation-damage characteristics of the cables ordinarily 350 MCM used in underground networks are shown in Fig. 6. 30 0 MCM \v"•-- 250 MCM 100 4. Network Units 4/0 MCM 0 co 50 The network units which supply power to the net- z 0 — z work secondary grid have been developed over the cra 00 -— 1000 MCM years into a unitized piece of equipment consisting of a w 750 MCM C.) three-phase step-down transformer and associated auto- 500 MCM - - 400 MCM matic network protector. In all early network installa- 1- 1" 10 0 M — 350 MCM tions, the transformers and network protectors were F: -— 300 MCM installed separately and not physically associated with 5 —250 MCM each other. These early installations invariably used — 4/0 MCM LIMITER FUSING banks of single-phase distribution transformers, and the — CHARACTERISTICS network protector was usually mounted on the wall of the network vault. The network protectors were cable- 1 connected to the secondary terminals of the transformer bank. This length of exposed cable in the vault gave an .5 undesirable degree of exposure to this portion of the system. Due to the nature of the network protector pro- tective relaying, the most severe fault condition, from I 1 I 1111 1 1 1 I Ill II 1 1111 the standpoint of network-protector operation, exists 100 500 5000 50000 for a fault between the secondary terminals of the trans- 1000 10000 100000 formers and the network protector itself. Reducing the CURRENT IN AMPERES Fig. 6a
10000 I I I likillk ‘6. CABLE INSULATION DAMAGE CHARACTERISTICS 4 BALANCED CIRCUIT CONDITIONS. 3 )0,181/4‘ 3 PHASES 13 NEUTRAL IN DUCT. 2 NII1‘/4 , N. i600 MCM 1000 -I, 500 MCM 8 400 MCM 6 Il 4 k N. 350 MCM 3 ;.— 300 MCM 2 cr) —.-- 250 MCM Z 100 NIX .....__ 4/0 o 8 6 (I, 4 3 — 2 10 Alk z 8 600 VOLT LIMITER lb.'" FUSING CHARACTERISTICS 4 3 600 MCM 2 500 MCM 400 MCM 350 MCM '4..0.,41%....S44,44 ."441...... 300 MCM A 250 MCM '41%\..,...... s....„ .3 4/0 .2 T_ HIIIIII i II IIIIII III III .1.1,1W .I.I.1,1, ,1.11,1111 t11 111111111 111111111 I It Ill itt III It, 400 500 600 700 900 1000 2000 3000 4000 5000 7000 9000 800 6000 8000 10000 CURRENT IN AMPERES Fig. 6b Fig. 6—Limiter characteristics. Time to fuse versus current in amperes. a—Limiters used in 120/208-volt systems b—Limiters used in 265/460-volt systems
Gridco, Inc. v. Varentec, Inc. IPR2017-01135 GRIDCO 1004 Part 2 of 5 - 161/576 154 Secondary Network Systems fault exposure of this connection was a major factor in bringing about the development of the network unit with the network protector is mounted directly on the transformer. The electrical connection consists of bush- ings completely enclosed by a steel throat. The indi- vidual components of the network unit are more fully treated in the sections following.
5. Network Transformers In addition to providing the basic requirement of voltage transformation, the network transformer has been developed to meet the special and oftentimes severe requirements for underground service. Limita- tions of vault size and ventilation, and requirements of submersibility have all had a strong influence on the design of the network transformer. In most installa- tions, three-phase transformers have replaced the earlier banks of single-phase units because of the decreased vault space required by three-phase units, and the rela- tive ease of installation and connection. Single-phase transformers offer no advantage from the standpoint of service continuity, because the innerconnected second- ary grid maintains the service at a transformer point even though that transformer is out of operation. How- ever, where existing single-phase transformers have Fig. 7—View showing a modern network unit mounted in impedances and voltage rating such that they can be an underground vault. paralleled with network units, they can be used in developing a network system. This often occurs when A recent design of network transformer is shown in an existing distribution system is being converted to a Fig. 8, incorporating a number of improvements over low-voltage secondary network. Single-phase trans- prior designs. Such improvements include reduction in formers sometimes are necessary because of space and overall size and weight, and new design of coolers. A weight limitations of elevators, hallways, doorways, serious problem with prior transformer designs has been manholes, and other means of access to the transformer the difficulty in properly cleaning and painting the tank vault. walls and cooling tubes. The new design overcomes this The publication containing industry standards for problem by providing radiating surfaces in the form of network transformers is entitled EEI-NEMA Standards fins or corrugations rather than tubes. A further step for Secondary Network Transformers'. One of the towards reducing corrosion has been the elimination of principal characteristics of network-transformer classi- many corners and crevices where dirt and moisture fication is the type of cooling. With respect to cooling, lodge. The reduction in size of the transformers permits network transformers are available in three general a reduction in vault volume and cost, or the replace- types. These will be discussed individually. Oil-Filled----The most commonly used network trans- former is the oil-filled type. A typical installation is shown in Fig. 7. These units normally are constructed with cooling devices along both of the long sides of the transformer tank, and with high-voltage cable terminat- ing facilities and a high-voltage switch on one end of the tank. A throat for direct connection of the network protector is provided on the other tank end. Auxiliary devices commonly employed are: a no-load tap-changer available for operation with a special wrench by removal of a pipe plug in the tank; temperature indicator; liquid level indicator; oil sample valve and filter press connec- tions. Tanks are 'constructed of copper bearing steel plate and the cooling tubes or radiators are of a suit- able thickness to resist corrosion. The vault-type trans- former has the thinner tubes and headers and is recom- mended for ordinary conditions of submersibility and corrosion. The thicker tubes and headers are used on Fig. 8—Comparison in physical dimensions between conven- the subway type, where frequent submersion presents a tional and new (space-miser design) network transformers. greater than normal corrosion problem. Both units are 500 kva, 15-kv class primary.
Gridco, Inc. v. Varentec, Inc. IPR2017-01135 GRIDCO 1004 Part 2 of 5 - 162/576 Secondary Network Systems 155
Table 3—Standards for Secondary Network Transformers
Standard Ratings for Three-Phase Transformers
Preferred Transformer High Voltage Standard Kva Ratings Nominal BIL Taps for Low-Voltage Rat- System Rating (Kv) ing of 216Y/125 Volts Voltage Above Below
4,160 (a) None None
4,160Y/2,400 (a)(b) None None 2,400/ 4160Y, 60 4,330 None None 300, 500, 750 4,330Y/2,500 (b) None None
4,800 5,000 60 None 4,875/ 4,750/4,625/4,500 300, 500, 750
7,200 (a) None 7,020/6,840/6,660/6,480 7,200 '75 7,500 None 7,313/7,126/6,939/6,752 300, 500, 750
11,500 95 None 11,213/10,926/10,639/10,352 300, 500, 750, 1,000
12,000 (a) None 11,700/11,400/11,100/10,800 12,000 95 12,500 None 12,190/11,875/11,565/11,250 300, 500, 750, 1,000
7,200/12,470Y 13,000Y/7,500 (b) 95 None 12,675/12,350/12,025/11,700 300, 500, 750, 1,000
13,200 (a) None 12,870/12,540/12,210/11,880 13,200 13,200Y/7,620 (a)(b) None 12,870/12,540/12,210/11,880 or 95 13,750 None 13,406/13,063/12,719/12,375 300, 500, 750, 1,000 7,620/13,200Y 13,750Y/7,940 (b) None 13,406/13,063/12,719/12,375
14,440 14,400 (a) 95 None 14,040/13,680/13,320/12,960 300, 500, 750, 1,000
22,900 (a) 24,100/23,500 22,300/21,700 23,000 150 24,000 25,200/24,600 23,400/22,800 500, 750, 1,000
(a) Preferred ratings which should be used when establishing new ne works. NOTE: All windings are delta connected unless otherwise indicated. (b) High-voltage and low-voltage neutrals are internally connected by Table reproduced from Reference 3. means of a removable link. ment of an existing unit with one of the new type hav- mersibility are not a problem. Fig. 9 shows a photo- ing a higher rating. graph of a ventilated dry-type network unit. These units Askarel-Filled—Oil-filled transformers have been used are directly air-cooled, with the core and coils enclosed in nearly all underground vault applications. But since in a sheet metal housing. Ventilating louvres provide an oil-filled transformer offers the potential hazard of subsequent fire in the event of tank structural failure, transformers are available with a non-flammable liquid ..fi0011111,1011111=1111M1111=811111=LfAMBeem.—A. - used in place of mineral oil. Askarel liquid-filled trans- formers are similar in construction and appearance to the oil-filled units. It is possible, in the field, with one manufacturer's unit, to substitute one liquid for the other in a given transformer by following a prescribed procedure. The Askarel liquid-filled network trans- formers do not completely eliminate the hazards of tank rupture, since an internal winding failure of sufficient severity can generate gas at a sufficiently high rate to cause tank rupture. Because of this, it is desirable to provide Askarel-filled units with a mechanical pressure relief device. The chief advantage of the non-flammable liquid is in eliminating the potential fire hazards of a large volume of transformer oil. Ventilated Dry Type—It is sometimes possible to obtain space for locating network transformers in a building basement or other dry vault location. The ventilated dry-type network transformer finds applica- Fig. 9—Ventilated dry-type network transformer in a net- tion in these locations where dirt accumulation and sub- work unit.
Gridco, Inc. v. Varentec, Inc. IPR2017-01135 GRIDCO 1004 Part 2 of 5 - 163/576 156 Secondary Network Systems for circulation of air over the core and coils. Solid insula- its primary feeder circuit when a network unit must be tion in these transformers consists of such materials as taken out of service for any length of time. The first porcelain, mica glass, or asbestos in combination with a step is the opening of the primary-feeder circuit breaker. sufficient amount of organic materials and binders, gen- With the network transformer disconnected, the feeder erally in form of a thermosetting varnish, to impart the can be re-energized and the other units on it put back in necessary mechanical strength to the insulation struc- service. This procedure is particularly advantageous ture without a detrimental effect to fire-resistant quali- where the primary feeder supplies other radial loads in ties. Combinations of these materials are defined in addition to the secondary network. Should a network American Standards C-57.1 as Class B insulation. The transformer failure occur, or if for some other reason a dry-type transformers are designed for an average transformer must be taken out of service, the affected winding temperature of 80°C. Fans are not required for unit can be isolated without a long-time outage of the normal cooling but may be used to provide increased radial loads supplied from the particular primary- capacity above the self-cooled rating. The use of dry- feeder circuit. The grounding position in the conven- type network transformers has largely been in building tional disconnecting-grounding switch provides a means vault locations. For these locations, such units offer for grounding of points on the high-voltage primary important advantages of maximum safety and mini- feeder circuit. These readily available grounds assure mum installation and maintenance costs. safety to personnel during work done on primary Sealed Dry Type—Another type of network trans- feeders. Another purpose served by the disconnecting former in use is also a dry-type and is made suitable for switch is to allow high potential dielectric testing of the submersible service by enclosing the core and coils in a primary feeder cables. This can be done with the net- hermetically sealed tank. Insulation used in these units work transformers connected to the primary cable in is designated in American Standard C-57.1 as Class H the case of delta-connected transformer primary wind- and consists of such materials as glass tape, glass sili- ings, properly insulated. Star-connected primary wind- cone, plate glass, and porcelain. A small amount of high ings make it practically impossible to test the feeder temperature silicone varnish is used to impregnate the cables without disconnecting the transformer from the insulation of the windings and furnish mechanical cables. In certain large network installations, the dis- strength. The core and coils of the submersible dry-type connecting feature of the primary switch is not re- unit are enclosed by a steel tank which is purged with quired, and only a grounding switch is. applied. dry nitrogen and sealed under a small positive pressure Regardless of type, the primary switch is a manually of this gas. These transformers completely eliminate the operated device equipped with the necessary interlocks hazards of fire or explosion, and the cost of equipment to prevent improper operation. The most commonly and labor for maintaining oil or Askarel. Since sealed used type of primary disconnecting switch is not de- dry-type transformer initial cost is more than that of signed to open load current or transformer exciting cur- either oil or Askarel units, the additional cost must be rent, and is therefore interlocked electrically so that the evaluated in terms of increased safety and decreased switch cannot be moved unless the transformer is de- maintenance. Sealed dry type units are somewhat energized. This type of switch requires that the primary larger in size than equivalent ratings of liquid-filled feeder circuit be de-energized before the switch can be units; the larger size is necessary because the major insu- operated. The three-position disconnecting and ground- lation is air and greater electrical clearances are required. ing switch is designed so that the closed or transformer Another characteristic of dry type transformers, both position is between the open position and the ground ventilated and sealed, which must be considered in some position. This requires that the switch be in the trans- applications is their lower dielectric strength. Since former position just prior to going to the ground posi- these units depend on air for dielectric strength, their tion, which allows the interlock to function to prevent impulse insulation level is substantially lower than cor- grounding a live primary feeder should the feeder be responding liquid-filled units. This factor becomes im- energized. The switch is designed with a forced pause to portant only when dry-type transformers are applied to allow the interlock to pick up. circuits exposed to lightning surges. Though nearly all It is sometimes desirable to be able to disconnect a underground networks are free from such exposure, network transformer from an energized primary feeder. when it is needed, adequate protection can be provided This procedure is desirable where the primary feeders with low ratio, rotating-machine type lightning ar- are not exclusive to the network. For this purpose, a resters installed in the primary leads of the transformer. primary disconnecting switch capable of opening trans- Fig. 10 shows a comparison of approximate weights, former exciting current is used, and is interlocked with dimensions and other application information for the the associated network protector to assure that load is various types of network transformers. removed from the transformer before operating the High-Voltage Switch—An integral part of nearly all switch. network units is the three-position switch provided in the primary leads for disconnecting the primary circuit 6. Network Protectors from the transformer. This standard switch is provided Functions—The network protector is an electrically with a position for grounding the primary circuit. In operated low-voltage air circuit breaker with self-con- small or medium size network systems, it is desirable to tained relays for controlling its operation. The network be able to disconnect an individual network unit from protector performs three basic functions in the system.
Gridco, Inc. v. Varentec, Inc. IPR2017-01135 GRIDCO 1004 Part 2 of 5 - 164/576 Secondary Network Systems 157
Conventional Design Conventional Design Approximate Dimen- n sions in Inches Net L.11::•;), Weight High tector Submers- Voltage Kva ible Pounds * Class Rat- ing A• CEPH Protector B G D. Oil int eeern-
:11%—V 150 600 31 70 46 85 103 61 5400 6500 0 11 225 800 36 73 90 117 6700 7800 — — 48 — 66 300 1200 68 37 65 74 91 11 7700 9000 5 Kv — through 500 1600 75 52 92 119 70 840 9500 15 Kv 44 600 2000 77 53 94 121 71 8700 10500 750 2500 77 45 80 58 104 136 77 11100 12700 65 1000 3000 79 52 89 62 11 145 82 13800 16000 150 600 74 50 89 107 65 7100 8800 68 38 65 225 800 7800 9600 77 52 94 121 70 300 1200 73 60 8700 10300 39 25 Kv 500 1600 78 64 95 122 72 10800 12500 79 65 600 2000 81 56 98 125 74 11501 13500 44 overall dimension with I. v. 750 2500 87 82 60 107 131 84 12700 14800 G 70 protector door open 90° 1000 3000 89 53 91 66 115 147 90 14200 16400 300 1200 73 44 60 87 54 104 131 72 9500 11900 500 1600 48 90 58 107 134 76 11700 14000 79 65 33 Kv. 600 2000 91 60 108 135 78 12500 15000 50 750 2500 87 95 68 119 151 92 14200 16700 Space Miser Design 70 1000 3000 89 53 98 70 122 154 94 16800 19400 Space Miser Design Approximate Dimen- sions in Inches Net High Pro Weignt Voltage Kva tector Submersible Pounds÷ Class Rat- Protector ing A4 C E F H Iner- B G D Oil teen- 300 1200 54 38 68 38 87 111 52 595 6900 44 5 Kv 500 1600 56 43 71 41 90 114 59 7450 8450 through 15 Kv 750 2500 65 44 77 48 104 132 72 9900 11150 46 1000 3000 73 47 85 67 112 140 81 13300 15400 300 1200 37 75 44 94 118 61 720 8200 64 500 1600 42 78 46 97 121 63 8750 10050 25 Kv 56 750 2500 71 44 83 53 110 138 77 11450 13050 1000 3000 81 48 91 63 118 146 87 1490D 17300 NOTE: Above dimensions and weights are based on transformers with an impedance of 5% and a low voltage rating of 216 Y/125 or 480 Y/277 volts. B '"A" dimension does not include relief device. If relief device is required, overall dimension with I.v.. add 3 inches from "A" dimension. G '"A" dimension covers oil-filled units only. Add 3 inches for Inerteen- protector door open.90° filled units and oil-filled units using mechanical relief device. $"D" dimension is height over stud on protector. If other type terminal is used, use "H" dimension and add height from center line of protector throat to top of terminal for correct "D" dimension. Fig. 10—Network-transformer physical characteristics. 'Weight of protector is not included. Weights listed cover transformers of vault-type construction. For weights of subway-type construction, use the (a)—Oil filled following approximate percentage addition: Oil-5.5%. Inerteen-5.0%.
Gridco, Inc. v. Varentec, Inc. IPR2017-01135 GRIDCO 1004 Part 2 of 5 - 165/576 158 Secondary Network Systems
One Triple Conductor F or Three Single Conductor Switch Operating Wiping Sleeve. Mechanism
Network Protector
A
Removable Ponels G • "6 is Overall Dimension With L.V. Protector Door Open 90° Fig. 10—(b)—Ventilated dry-type
Dimensions and Weights Recom- Approximate Dimensions—Inches Net High Kva mended With Submersible With Dust-Proof Weight Voltage Ratin Protector Network Protector Network Protector Class g Rating A C E F —Pounds --Amperes B D G B D G 150 600 75 42 81 86 103 72 120 104 64 120 4000 225 800 75 42 81 95 114 72 140 116 64 140 5000 300 1200 75 42 81 95 114 77 140 116 64 140 5500 15 Kv 114 77 140 116 64 140 6700 and 450 1600 75 42 81 95 114 140 116 64 140 7000 Below 500 1600 75 42 81 95 77 600 2000 80 48 86 104 124 90 149 126 76 149 8500
750 2500 80 48 86 104 132 90 160 132 76 157 9100 1000 3000 80 48 86 104 132 90 160 132 76 157 11100
Above dimensions and weights are based on standard transformers with an impedance of 5 percent and a low voltage of 216Y/125. 450 and 600 kva sizes are special.
The first and most important function is to provide The second function of most network protectors is automatic isolation of faults in the primary feeders or provided by the ability of the reverse-power relay to trip network transformers. This basic tripping function is the protector on relatively small values of reverse power provided by the three-phase power directional relay such as required to magnetize the transformer. This called the master relay. This relay trips the protector sensitive tripping assures proper network protector op- when power flows in a reverse direction from the ener- eration for phase-to-ground fault conditions in a uni- gized secondary grid back towards a fault in the trans- grounded three-wire primary feeder supplying delta- former or primary feeder. A faulty primary cable or connected network transformers. It is also commonly transformer is thus removed from the system automati- used to provide a ready means of checking for proper cally by tripping the substation breaker in the affected network-protector operation. By individually opening primary feeder, and by tripping the network protectors each primary feeder breaker at the substation supplying associated with that feeder. By this means, the network the network, an operator can conveniently check the system makes use of its multiple paths of supply, pro- network protectors for proper tripping. The voltmeter vided by the several primary circuits and by the com- on the load side of each primary feeder breaker will indi- mon secondary grid, to give a high degree of service cate to the operator whether or not all network protec- reliability. tors on that feeder have opened.
Gridco, Inc. v. Varentec, Inc. IPR2017-01135 GRIDCO 1004 Part 2 of 5 - 166/576 Secondary Network Systems 159
0 f 0 0 I ©
A
-4- B overall dimension with protector door open 90.
Fig. 10—(c)—Sealed dry-type
Recom- Approximate Dimensions: Inches High mended Net Kva With Submersible With Dust Proof Voltage Protector Weight: Rating A C E F Network Protector Network Protector Class Rating: Pounds amperes B D G B D G
300 1200 81 47 76 99 117 88 138 119 80 138 11200
500 1600 86 48 76 102 120 93 141 122 85 141 12000
600 2000 ...... 15 kv and 750 2500 95 49 76 108 132 109 160 132 95 156 13250 Below 1000 3000 99 51 76 114 138 113 166 138 99 162 17500
1500m 2500 113 52 76 117 141 111 174 141 97 170 23140
2000 3000 119 52 76 120 144 111 177 141 97 173 24640
Above dimensions and weights are based on standard transformers with a °For a low voltage of 480Y/277. low voltage of 216Y/125. Size 600 kva is special and dimensions can be fur- nished upon request.
A third function of the network protector is to auto- network relays prevent the protector from closing auto- matically close when certain predetermined system con- matically under crossed-phase conditions. ditions are met: When a primary feeder associated with Network-Protector Standards—The National Electrical a given network protector is energized, if the voltage on Manufacturers Association (NEMA) Standards for Net- the transformer side of the open network protector is work Protectors consist of five major parts: Definitions; slightly higher in magnitude, and is in phase with, or General Standards; Rating Standards; Manufacturing leading, the voltage on the secondary grid side of the Standards; Application Standards. protector, the relays cause the protector to automatical- These standards discuss such topics as types of en- ly close and connect the transformer to the grid. The closure, insulation classifications, service conditions, result of the closing function of the network relays is voltage and current ratings, relay operating characteris- such that the protector will close only when voltage tics and adjustments, circuit-breaker interrupting rat- conditions are such as to cause any resultant power flow ings, network protector fuse characteristics, dimensions, to be towards the load. In addition to the operating con- etc. Tables 4 through 10, which are taken from these venience of being able to restore a network feeder to NEMA Standards, are representative of the information service merely by closing the substation breaker, the contained therein. These standards cover what are
Gridco, Inc. v. Varentec, Inc. IPR2017-01135 GRIDCO 1004 Part 2 of 5 - 167/576 160 Secondary Network Systems
Table 4—Network Protectors Table 5—Network Protectors
Classification of Insulating Materials Voltage and Current Ratings The temperature limits on which the rating of network pro- For applications at altitudes greater than 3300 feet (1000 tectors is based are largely determined by the character of the meters), the standard voltage and continuous-current ratings insulating materials used. of network protectors shall be multiplied by the following cor- For the purpose of establishing temperature limits, insulat- rection factors : ing materials shall be classified as follows: Altitude Correction Factors Class of Feet Meters Voltage Current Insulation Description of Material 3300 1000 1.00 1.00 Class A insulation consists of (1) cotton, silk, A 4000 1200 0.98 0.996 paper and similar organic materials when either 5000 1500 0.95 0.99 impregnated* or immersed in a liquid dielectric; 10000 3300 0.80 0.96 (2) molded and laminated materials with cellulose filler, phenolic resins and other resins of similar NEMA Standard 5-17-1953. properties; (3) films and sheets of cellulose acetate and other cellulose derivatives of similar proper- ties; and (4) varnishes (enamel) as applied to con- protector. These are the master relay, phasing relay, ductors. and de-sensitizing relay. B Class B insulation consists of mica, asbestos, Master Relay—The master relay is a three-phase, fiberglass and similar inorganic materials in built- power-directional, induction relay which provides the up form with organic binding substances. A small basic functions of directional tripping and correct-volt- proportion of Class A materials may be used for age closing for the network-protector circuit breaker. structural purposes onlyf. The master relay is pictured in Fig. 11. C Class C insulation consists entirely of mica, por- Adjustments There are only two adjustments to be celain, glass, quartz and similar inorganic ma- made on the Westinghouse Type CN-33 relay, namely, terials. the overvoltage adjustment and the reverse-current ad- H Class H insulation consists of (1) mica, asbestos, justment. When the relay is completely deenergized, the fiberglass and similar inorganic materials in built- moving contact is held firmly against the stationary up form with binding substances composed of sili- closing contact by means of a spiral spring around the cone compounds or materials with equivalent prop- moving element shaft. By adjusting spring tension, a erties and (2) silicone compounds in rubbery or continuous overvoltage adjustment, having a range of resinous forms or materials with equivalent proper- approximately 1.0 to 5 volts 75° leading, or .5 to 2.0 volts ties. A minute proportion of Class A materials may in phase with the network voltage, is obtained. Three be had only where essential for structural purposes flat springs, placed side by side, are carried on the mov- during manufactures. ing contacts. In conjunction with an adjustable thumb O Class 0 insulation consists of cotton, silk, paper screw stop which can be located in any one of three tap- and similar organic materials when neither impreg- ped holes in its mounting block so that it will deflect nated* nor immersed in a liquid dielectric. one, two, or all three of the springs, these springs pro- l'An insulation is considered to be "impregnated" when a suitable substance replaces the air between its fibers, even if this substance does not, completely vide a continuous range of in-phase reverse current ad- fill the spaces between the insulated conductors. Thu impregnating substances, justment from about 0.1 to 10 per cent of the protector in order to be considered suitable, must have good insulating properties• must entirely cover the fibers and render them adherent to each -other and rating in amperes. to the conductor; must not produce interstices within itself es a consequence of evaporation of the solvent or through any other cause; must not Sow during Closing Characteristics Figs. 13, 14, and 15 show the the operation of the machine at full working load or at the temperature limit specified; and must not unduly deteriorate tinder prolonged action of heat. operating characteristics of the Type CN-33 network tTho electrical and mechanical properties of the insulated winding must not be impaired by application of the temperature permitted for Clam B master relay. Curve No. 1 of Fig. 13 shows the closing material. (The word 'impair" is hero used in the sense Of causing any change which could disqualify the insulating material for continuous service.) The characteristics of the relay. Lines drawn to it from the temperature endurance of different Class B insulation assemblies varies over origin at various angles with the network voltage repre- a considerable range in accordance with the percentage of Class A materiide employed and the degree of dependence placed on the organic binder for sent, in both magnitude and phase position, the trans- maintaining the structural integrity of the insulation. rl'he electrical and mechanical properties of the insulated winding must not be impaired by the application of the temperature permitted for Class H material. (The word "impaired" is here used in the senile of causing any change which would disqualify the insulating material for continuous service.) Table 6—Network Protectors NEMA Standard 5-17-1953. Voltage Ratings termed "heavy-duty" and "medium-duty" network pro- The standard voltage ratings shall be: tectors. The "light-duty" unit is discussed below in con- Alternating-current nection with overhead network systems. Standards for 600-volt class network protectors are not yet available. Maximum Design Voltage, Voltage Rating, Volts Volts 7. Network Relaying 125/216 or 240 250 The planning, design, and operating features of the 480 500 a-c secondary network system are made possible by the 575 600 particular type of relays which are a part of the network NEMA Standard 5-17-1953.
Gridco, Inc. v. Varentec, Inc. IPR2017-01135 GRIDCO 1004 Part 2 of 5 - 168/576 Secondary Network Systems 161
Closeup crossection showing gasket re- tainer and highly compressible tubu- lar gasket
Connection Plate, Ammeter Plate, or Type BN Relay Type CNJ Phasing Relay
Type CN-33 Master Relay
Engagement Tongue For Operating Handle (a)—Heavy-duty type network protector. Transformer mounted submersible enclosure. View showing door open and unit rolled out on rails. Circuit breaker is located behind relay panel.
Terminal Screw —Molded Tqrminal' Plate Terminal Screw Molded Terminal Bloch Moving Contacts Stationary Tripping Contact Current and Phasing Mounting Hole _Stationary Closing Coil and Iron Assemb Contact Damping Magnet Overvoltage Adjusting Pinion Drum Current and Phasing Coil Spiral Spring Adjuster Assembly Mounting Screws Trent Bearing Plots Mounting Plate Reverse Current Springs with Insulating Cover Rear Electing Plots — Captive Cover Screw Glass Cover averse Current Stationary Slop ------Adjusting Strew Damping Magnet
Moving Element Slop
(b)—Network master relay. Front view with glass cover (c)—Network master relay. Rear view of relay removed removed. from base. Fig. 11—Network protector and network master relay. former voltages which will produce a torque in the relay will produce a relay torque in the tripping direction just sufficient to cause its closing contacts to make. The which prevents the closing contacts from making and closing contacts will also make and connect the trans- the network protector will remain open. The Curve No. former to the network if the transformer voltage termi- 1-A in the same figure shows a small section of the clos- nates above the closing curve. Any transformer voltage ing curve plotted to a much larger scale, so as to show which does not terminate on or above the closing curve the characteristics of the relay for the values of phasing voltage at which it normally operates. Lines drawn from Table 7—Network Protectors the origin to this curve represent in magnitude and Dielectric Test Voltage phase position the phasing voltage, that is, the voltage The dielectric test voltage shall be an alternating voltage across the open contacts of the network protector neces- having a crest value equal to times the following test volt- sary to produce a torque in the relay just sufficient to age. A sine wave shape is recommended. make its closing contacts. The upper end or line poten- tial end of the network voltage vector is at the origin in A-c Rms Voltage Rating A-c this case. The network voltage vector cannot be shown of Network Protector, Dielectric Test Voltage, in its true relationship to this curve, because of the Volts Volts* large scale to which the curve is plotted. It will be noted 125/216 or"240 1500 by referring to Curve No. 1-A that the relay will just 480 2200 close its closing contacts with approximately 0.8 volt 575 2200 across the phasing circuit in phase with the network *EXCEPTION—The closing motor shall be tested at 900 volts. When the voltage. When the phasing voltage leads the network network protector is tested in the field, the dielectric teat voltage shall be not greater than 75 per cent of the foregoing values. voltage by 75°, about 2.0 volts are required to close the
Gridco, Inc. v. Varentec, Inc. IPR2017-01135 GRIDCO 1004 Part 2 of 5 - 169/576 162 Secondary Network Systems
Table 9—Network Protectors Standard Ratings for 125/216- or 240-volt A-c Network Protectors*
Continuous Maximum Dielectric .Interrupt- Short-time Current Design Test Volt- ing Rating, Rating, Rating, Voltage, age, Except Rms Rms Rms Except Relay Closing Amperes Amperes Amperes and Control Motor
It 2f 3f 4t 5f
300 250 1500 10000 10000 600 250 1500 10000 10000 1200 250 1500 20000 20000 1600 250 1500 30000 30000 2000 250 1500 35000 35000 2500 250 1500 45000 45000 3000 250 1500 60000 60000
*Standards have not yet been developed for 480- and 575-volt network protectors. tFor a further explanation of the column headings, see the following stand- ards: Column 1—see 803.1-3.09. Column 2—see SG3.1-3.03. Column 3—see SG3.1-3.04. Column 4—see 8G3.1-3.15. Column 5—see SG3.1-3.17. NEMA Standard 5-17-1953.
Opening Characteristics—The opening characteristics Fig. 12—Installing a modern network unit for the secondary of the type CN-33 relay are shown by Curve No. 2 in network system in a large city. Fig. 13. Lines drawn from the origin to Curve No. 2 represent in magnitude and phase position the line cur- closing contacts. This voltage at 75° leading, however, rents which will produce a torque in the relay just suffi- means only a small angle between network and trans- cient to cause its tripping contacts to make. The trip- former voltages. This can readily be appreciated by ping contacts will also make and disconnect the trans- observing that 10 volts across the phasing circuit former from the network if the line current terminates leading the network voltage by 90° will throw the net- below the opening curve. If, however, the line current work and transformer voltages less than 5° out of phase. does not cross the opening curve but terminates above
Table 8—Network Protectors Table 10—Network Protectors Limits of Observable Temperature Rise Continuous-current Rating The temperature rise, above the ambient temperature of each A network protector shall have a continuous-current rating at least as great as the maximum load current which it will of the various parts of the network protector, when subjected to temperature tests in accordance with these standards, shall be required to carry. The following table should be used as a guide in applying not exceed the values given in the following table. All tempera- 125/216-volt network protectors to network transformers*. ture determinations shall be made by the thermometer method. Associated Network Transformer Limit of Network Protector Current Rating Temperature Rise, Rated Rated Part Degrees C Per Cent of Full-load 3-phase Secondary Rms Trans- Current Current and potential coils and Kva , Voltag, e Amperes former Rms other insulated parts Volts Class 0 Insulation 60 Full Load Amperes Class A Insulation 65 300 150 75 200 125/216 Class B Insulation 85 600 150 150 400 125/216 Class C Insulation No Limit Specified 1200 150 300 800 125/216 Class H Insulation 140 1600 120 500 1340 125/216 All other parts except thermal 2000 150 500 1340 125/216 elements, heaters, fuses, fuse 2500 125 750 2000 125/216 terminals and resistors 100 3000 150 750 2000 125/216 NOTE—Due to the oxidation of contact surfaces. there is an inherent 3000 112 1000 2680 125/216 decrease in the amount of current which can be carried by contact* in air. The continuous current rating, is, therefore, based on the assumption that main- *Tables have not yet been developed for 240-, 480- or 575-volt network tenance will be sufficient to keep the temperature rise within ecified limits. protectors. NMAE Standard 5-17-1953. NEMA Standard 5-17-1953.
Gridco, Inc. v. Varentec, Inc. IPR2017-01135 GRIDCO 1004 Part 2 of 5 - 170/576 I