S S 1 1/2" HC14 SILICONE SPLICE SLEEVE (FIELD INSTALL) HC14

1H97 STB1 STB1 1 7/16"

SPZ1 1/8"

WA02 M173/MTZ0 M173/MTZ0 3" 1/4" 111 S.S.G. HEAD 17V3 LC45

SERIES: 8750XD - 7 1/2" CAPTURED HN09

STB1 ROUGH OPENING 1 7/16" 7/8" 17T6

17T5 KV20 UNIT DIM. ??

WC18 H12A FRAME GASKET OVERALL FRAME DIM. D.L.O.

FM70 SPLIT CLIP SEE ELEVATION 1" FOR LOCATION 7 1/2" D.L.O.

M173 ERECTOR NOTE: E11 = TO INSURE A WATERTIGHT SEAL, BACK BED WITH SEALANT BEFORE THE STACK JOINTS IS FACTORY ORDER NOTE: INSTALLED. S MTZ0 S S1 = GLASS UNIT ARE TO BE SHOP GLAZED BY EFCO. SEE SHEET 1.02 FOR COLOR AND SEALANT TYPE SHOP DRAWER GLAZING NOTE: FM41 E12 FOR ALL SHOP SHOP GLAZED UNITS. IF GLASS UNITS ARE TO BE SUPPLIED AND

ERECTOR NOTE: ERECTOR NOTE: STB1 ERECTOR NOTE: GLAZED BY EFCO THE DETAIL WILL NEED TO ERECTOR NOTE: M173 FIELD APPLY KV39 SILICONE SHEET TO THE SET HC14 SILICONE SPLICE IN A BED OF SET HC09 SILICONE SPLICE IN A BED OF FIELD APPLY KV39 SILICONE SHEET TO THE SHOW "S1" WITH THE S1 FACTORY ORDER NOTE. E10 = SEALANT SLEEVE ABOVE VERTICAL MULLION E12 = TOP OF LOWER UNIT AT STACK JOINT. AFTER SEALANT SLEEVE ABOVE VERTICAL MULLION MTZ0 TOP OF LOWER UNIT AT STACK JOINT. AFTER MTZ0 MTZ0 MTZ0 MTZ0 MTZ0 MTZ0 E9 = SETTING IN BOTH THE LOWER AND UPPER AT HORIZONTAL STACK JOINT. AT HORIZONTAL STACK JOINT. HC09 (SILICONE SPLICE) E9 = SETTING IN BOTH THE LOWER AND UPPER ERECTOR NOTE: IF GLASS UNITS ARE TO BE SUPPLIED AND M173 M173 UNITS INTO THE OPENING APPLY KV39 M173 M173 UNITS INTO THE OPENING APPLY KV39 M173 M173 GLASS UNIT ARE TO BE SHOP GLAZED BY GLAZED BY CUSTOMER THE DETAIL WILL NEED FM41 TO SHOW "E1" WITH THE E1 ERECTOR NOTE FM41 FM41 SILICONE SHEET TO THE UPPER UNIT BY FM41 FM41 SILICONE SHEET TO THE UPPER UNIT BY FM41 FM41 (CUSTOMER NAME). IT WILL BE THE MTZ0 PLACING IN A BED OF SEALANT. ERECTOR NOTE: PLACING IN A BED OF SEALANT. E1 = RESPONSIBILITY OF (CUSTOMER NAME) TO STB1 STB1 STB1 STB1 M173 VERIFY COLOR AND SEALANT TYPE FOR ALL TO INSURE A WATERTIGHT SEAL, BACK BED UNIT DIMENSION ERASE NOTE AFTER READING E11 = WITH SEALANT BEFORE THE STACK JOINTS IS SHOP SHOP GLAZED UNITS. ERECTOR NOTE: INSTALLED. ERECTOR NOTE: FM40 SPLIT CLIP STB1 MTZ0 SET HC14 SILICONE SPLICE IN A BED OF STB1 SET HC14 SILICONE SPLICE IN A BED OF OVERALL FRAME DIMENSION E10 = SEALANT SLEEVE ABOVE VERTICAL MULLION SEE ELEVATION KV49 CORNER ALIGNMENT CLIP E10 = SEALANT SLEEVE ABOVE VERTICAL MULLION M173 E9 M173 M173 M173 STC7 M173 E9 M173 AT HORIZONTAL STACK JOINT. FOR LOCATION ERASE NOTE AFTER READING 17W9 HD25 (MULL PLUG) WORK POINT TO ROUGH OPENING AT HORIZONTAL STACK JOINT. 8" LONG CAULK BACKER 8" LONG CAULK BACKER 8" LONG CAULK BACKER 8" LONG CAULK BACKER AT VERTICAL STACK JOINTS MTZ0 MTZ0 AT VERTICAL STACK JOINTS MTZ0 MTZ0 AT VERTICAL STACK JOINTS AT VERTICAL STACK JOINTS MTZ0 MTZ0

SHOP DRAWER NOTE: M173 IF EFCO FABRICATING AND ASSEMBLING CURTAIN WALL UNITS THE DETAIL WILL NEED TO SHOW "S4" WITH THE S4 FACTORY ORDER NOTE. WC21 WC18 ??

KV39 (SILICONE END DAM) IF THE CUSTOMER ASSEMBLING CURTAIN WALL KV39 (SILICONE END DAM) ERASE NOTE AFTER READING ERASE NOTE AFTER READING UNITS THE DETAIL WILL NEED TO SHOW "E7" ERASE NOTE AFTER READING 17T3 17T7 WC21 17T8 STC7 17T3 SHOP DRAWER NOTE: SHOP DRAWER NOTE: WITH THE E7 ERECTOR NOTE 17W8 SHOP DRAWER NOTE: STB1 STB1 E11 STB1 HC14 STB1 E6 ?? IF EFCO FABRICATING AND ASSEMBLING IF EFCO FABRICATING AND ASSEMBLING STB1 E11 IF EFCO FABRICATING AND ASSEMBLING ?? E6 CURTAIN WALL UNITS THE DETAIL WILL NEED TO ?? CURTAIN WALL UNITS THE DETAIL WILL NEED TO ?? CURTAIN WALL UNITS THE DETAIL WILL NEED TO E10 SHOW "S4" WITH THE S4 FACTORY ORDER NOTE. SHOW "S4" WITH THE S4 FACTORY ORDER NOTE. SHOW "S4" WITH THE S4 FACTORY ORDER NOTE. E10 WA02 1 31/32" STC7 STC7 LC45 IM04 STC7 IF THE CUSTOMER ASSEMBLING CURTAIN WALL IF THE CUSTOMER ASSEMBLING CURTAIN WALL FACTORY ORDER NOTE: IF THE CUSTOMER ASSEMBLING CURTAIN WALL STC7 IM04 UNITS THE DETAIL WILL NEED TO SHOW "E7" E10 UNITS THE DETAIL WILL NEED TO SHOW "E7" STC7 1/4" UNITS THE DETAIL WILL NEED TO SHOW "E7" HC14 (SILICONE SPLICE) PLACE STC7 FASTENER 1/8" FROM BOTTOM END LC45 WA02 WITH THE E7 ERECTOR NOTE WITH THE E7 ERECTOR NOTE S4 = WITH THE E7 ERECTOR NOTE HC14 (SILICONE SPLICE) OF MULLION TO KEEP DURACAST CLIP FROM FALLING OUT THE END OF UNITS. WC18 SPZ1 WC18 WC18 WC18 WC18 SPZ1 4 3/8" HN09 HN09 HN09 HN09 S LC45 LC45 LC45 ERECTOR NOTE: LC45 S 15H3 - 3" LONG 15Y8 - 3" LONG FACTORY ORDER NOTE: WA02 FACTORY ORDER NOTE: E7 = PLACE STC7 FASTENER 1/8" FROM BOTTOM END FACTORY ORDER NOTE: 15Y7 - 3" LONG 1835 - 3" LONG ?? ?? OF MULLION TO KEEP DURACAST CLIP FROM ?? ?? PLACE STC7 FASTENER 1/8" FROM BOTTOM END PLACE STC7 FASTENER 1/8" FROM BOTTOM END 17W3 PLACE STC7 FASTENER 1/8" FROM BOTTOM END 3/8" FASTENER SLEEVE 1/2" FASTENER SLEEVE 1/4" FASTENER SLEEVE 1/4" FASTENER SLEEVE 1H97 1H97 S4 = S4 = OF MULLION TO KEEP DURACAST CLIP FROM FALLING OUT THE END OF UNITS. S4 = WNC1 (MULL PLUG) OF MULLION TO KEEP DURACAST CLIP FROM WNC1 (MULL PLUG) WNC1 (MULL PLUG) HD25 (MULL PLUG) OF MULLION TO KEEP DURACAST CLIP FROM WNC1 (MULL PLUG) FALLING OUT THE END OF UNITS. FALLING OUT THE END OF UNITS. 17W3 FALLING OUT THE END OF UNITS.

WA02 17V4 17V4 2 5/32" WA02 ERECTOR NOTE: ERECTOR NOTE: ERECTOR NOTE: PLACE STC7 FASTENER 1/8" FROM BOTTOM END 1/8" PLACE STC7 FASTENER 1/8" FROM BOTTOM END PLACE STC7 FASTENER 1/8" FROM BOTTOM END 17V3 E7 = OF MULLION TO KEEP DURACAST CLIP FROM E7 = OF MULLION TO KEEP DURACAST CLIP FROM E7 = OF MULLION TO KEEP DURACAST CLIP FROM 17V3 FALLING OUT THE END OF UNITS. FALLING OUT THE END OF UNITS. ERASE NOTE AFTER READING FALLING OUT THE END OF UNITS.

1/8" SHOP DRAWER GLAZING NOTE: 1/8" 1/4" IF GLASS UNITS ARE TO BE SUPPLIED AND ERASE NOTE AFTER READING ERASE NOTE AFTER READING GLAZED BY EFCO THE DETAIL WILL NEED TO ERASE NOTE AFTER READING 511 S.S.G. HORIZONTAL 1/4" 7/8" 7/8" 1/4" 7/8" SHOW "S1" WITH THE S1 FACTORY ORDER NOTE. 1/4" 7/8" 1/4" SHOP DRAWER GLAZING NOTE: SHOP DRAWER GLAZING NOTE: SHOP DRAWER GLAZING NOTE: SERIES:8750XD - 7 1/2" STRUCTURAL GLAZED IF GLASS UNITS ARE TO BE SUPPLIED AND IF GLASS UNITS ARE TO BE SUPPLIED AND IF GLASS UNITS ARE TO BE SUPPLIED AND IF GLASS UNITS ARE TO BE SUPPLIED AND 1 7/16" 1 7/16" GLAZED BY EFCO THE DETAIL WILL NEED TO 1 7/16" 1 7/16" GLAZED BY EFCO THE DETAIL WILL NEED TO GLAZED BY CUSTOMER THE DETAIL WILL NEED 1 31/32" 2 5/32" GLAZED BY EFCO THE DETAIL WILL NEED TO 1 7/16" 1 7/16" 7 1/2" SHOW "S1" WITH THE S1 FACTORY ORDER NOTE. SHOW "S1" WITH THE S1 FACTORY ORDER NOTE. TO SHOW "E1" WITH THE E1 ERECTOR NOTE SHOW "S1" WITH THE S1 FACTORY ORDER NOTE.

IF GLASS UNITS ARE TO BE SUPPLIED AND IF GLASS UNITS ARE TO BE SUPPLIED AND IF GLASS UNITS ARE TO BE SUPPLIED AND 3" D.L.O. GLAZED BY CUSTOMER THE DETAIL WILL NEED D.L.O. 3" D.L.O. GLAZED BY CUSTOMER THE DETAIL WILL NEED D.L.O. 4 3/8" GLAZED BY CUSTOMER THE DETAIL WILL NEED D.L.O. 3" 1" TO SHOW "E1" WITH THE E1 ERECTOR NOTE TO SHOW "E1" WITH THE E1 ERECTOR NOTE TO SHOW "E1" WITH THE E1 ERECTOR NOTE UNIT DIMENSION UNIT DIMENSION UNIT DIMENSION UNIT DIMENSION UNIT DIMENSION FACTORY ORDER NOTE: CL S1 = GLASS UNIT ARE TO BE SHOP GLAZED BY EFCO. OVERALL FRAME DIMENSION OVERALL FRAME DIMENSION SEE SHEET 1.02 FOR COLOR AND SEALANT TYPE OVERALL FRAME DIMENSION OVERALL FRAME DIMENSION 1" FOR ALL SHOP SHOP GLAZED UNITS. 1" FACTORY ORDER NOTE: FACTORY ORDER NOTE: FACTORY ORDER NOTE: S1 = GLASS UNIT ARE TO BE SHOP GLAZED BY EFCO. S1 = GLASS UNIT ARE TO BE SHOP GLAZED BY EFCO. S1 = GLASS UNIT ARE TO BE SHOP GLAZED BY EFCO. ROUGH OPENING SEE SHEET 1.02 FOR COLOR AND SEALANT TYPE ROUGH OPENING SEE SHEET 1.02 FOR COLOR AND SEALANT TYPE ROUGH OPENING TO WORK POINT SEE SHEET 1.02 FOR COLOR AND SEALANT TYPE ROUGH OPENING FOR ALL SHOP SHOP GLAZED UNITS. FOR ALL SHOP SHOP GLAZED UNITS. ERECTOR NOTE: FOR ALL SHOP SHOP GLAZED UNITS. D.L.O. GLASS UNIT ARE TO BE SHOP GLAZED BY (CUSTOMER NAME). IT WILL BE THE E1 = RESPONSIBILITY OF (CUSTOMER NAME) TO 432 S.S.G. STACK JOINT JAMB ERECTOR NOTE: 631 S.S.G. STACK JOINT VERTICAL ERECTOR NOTE: VERIFY COLOR AND SEALANT TYPE FOR ALL 731 S.S.G. STACK JOINT 90° OUTSIDE CORNER ERECTOR NOTE: 433 S.S.G. STACK JOINT JAMB WC18 SERIES: 8750XD - 7 1/2" STRUCTURAL GLAZED GLASS UNIT ARE TO BE SHOP GLAZED BY SERIES:8750XD - 7 1/2" STRUCTURAL GLAZED GLASS UNIT ARE TO BE SHOP GLAZED BY SHOP SHOP GLAZED UNITS. SERIES:8750XD - 7 1/2" STRUCTURAL GLAZED GLASS UNIT ARE TO BE SHOP GLAZED BY SERIES: 8750XD - 7 1/2" STRUCTURAL GLAZED E1 = (CUSTOMER NAME). IT WILL BE THE E1 = (CUSTOMER NAME). IT WILL BE THE E1 = (CUSTOMER NAME). IT WILL BE THE 17U3 RESPONSIBILITY OF (CUSTOMER NAME) TO RESPONSIBILITY OF (CUSTOMER NAME) TO RESPONSIBILITY OF (CUSTOMER NAME) TO VERIFY COLOR AND SEALANT TYPE FOR ALL VERIFY COLOR AND SEALANT TYPE FOR ALL VERIFY COLOR AND SEALANT TYPE FOR ALL SHOP SHOP GLAZED UNITS. SHOP SHOP GLAZED UNITS. SHOP SHOP GLAZED UNITS. STB1 STB1 1 3/32" 1/4"

HN09 H12A FRAME GASKET

3" LC45 17V4

13/16" HN09 UNIT DIM. ROUGH OPENING

OVERALL FRAME DIM. 1/4" STB1 STB1 1 3/32" E1 WC18 D.L.O.

FACTORY ORDER NOTE: S1 = GLASS UNIT ARE TO BE SHOP GLAZED BY EFCO. SEE SHEET 1.02 FOR COLOR AND SEALANT TYPE SHOP DRAWER GLAZING NOTE: FOR ALL SHOP SHOP GLAZED UNITS. IF GLASS UNITS ARE TO BE SUPPLIED AND GLAZED BY EFCO THE DETAIL WILL NEED TO SHOW "S1" WITH THE S1 FACTORY ORDER NOTE.

ERECTOR NOTE: IF GLASS UNITS ARE TO BE SUPPLIED AND GLASS UNIT ARE TO BE SHOP GLAZED BY GLAZED BY CUSTOMER THE DETAIL WILL NEED E1 = (CUSTOMER NAME). IT WILL BE THE TO SHOW "E1" WITH THE E1 ERECTOR NOTE RESPONSIBILITY OF (CUSTOMER NAME) TO VERIFY COLOR AND SEALANT TYPE FOR ALL ERASE NOTE AFTER READING SHOP SHOP GLAZED UNITS.

311 S.S.G. HORIZONTAL STACKS SERIES:8750XD - 7 1/2" STRUCTURAL GLAZED

7 1/2"

1"

FM70 SPLIT CLIP ?? SEE ELEVATION FOR LOCATION D.L.O.

H12B FRAME D.L.O. GASKET STB1 ERECTOR NOTE: WC18 STB1 TO INSURE A WATERTIGHT SEAL, BACK BED ?? 17U0 E11 = STB1

WITH SEALANT BEFORE THE STACK JOINTS IS UNIT DIM. FACTORY ORDER NOTE: INSTALLED. STACK JOINT LOADING CLIPS WILL NEED TO BE S S 7/8" STB1 HC05 S2 = MOUNTED TO THE CURTAIN WALL UNIT BY THE SHOP DRAWER NOTE: BOTTOM TWO ATTACHMENT HOLES AT THIS IF EFCO FABRICATING AND ASSEMBLING HN09 DETAIL LOCATION. CURTAIN WALL UNITS THE DETAIL WILL NEED TO STB1 STB1 WEA2 KV26 (LOADING CLIP) KV25 (LOADING CLIP) KV28 (LOADING CLIP) SHOW "S2" WITH THE S2 FACTORY ORDER NOTE. 1 15/16" LC45 STB1

17V1 IF THE CUSTOMER ASSEMBLING CURTAIN WALL STB1 ERECTOR NOTE:

W07V (TAPE) LC23 1/4" LC54 STACK JOINT LOADING CLIPS WILL NEED TO BE UNITS THE DETAIL WILL NEED TO SHOW "E4" STB1 STB1 STB1 STB1 STB1 STB1 HC14 E4 = MOUNTED TO THE CURTAIN WALL UNIT BY THE WITH THE E4 ERECTOR NOTE ERECTOR NOTE: C BOTTOM TWO ATTACHMENT HOLES AT THIS STB1 STB1 STB1 TO INSURE A WATERTIGHT SEAL, BACK BED STB1 L HC14 SILICONE SPLICE KV30 (LOADING CLIP) STB1 E3 E11 = STB1 3 7/8" DETAIL LOCATION. WITH SEALANT BEFORE THE STACK JOINTS IS UNIT DIMENSION SLEEVE (FIELD INSTALL) 17T9 ERASE NOTE AFTER READING STB1 STB1 STB1 STB1 INSTALLED. STB1 STB1 1/4"

KV49 CORNER ALIGNMENT CLIP LC45 17V6

FM40 SPLIT CLIP STB1 17V4 OVERALL FRAME DIMENSION STB1 STB1 STB1 STB1 SEE ELEVATION STB1 STB1 STC7 ROUGH OPENING HN09 FOR LOCATION ERASE NOTE AFTER READING STB1 17W9 WORK POINT TO ROUGH OPENING 8" LONG CAULK BACKER 8" LONG CAULK BACKER 8" LONG CAULK BACKER 8" LONG CAULK BACKER OVERALL FRAME DIM. 1 15/16" AT VERTICAL STACK JOINTS AT VERTICAL STACK JOINTS AT VERTICAL STACK JOINTS AT VERTICAL STACK JOINTS STB1 E2 STB1 SHOP DRAWER NOTE: H12G MULLION IF EFCO FABRICATING AND ASSEMBLING ?? 7/8" CAP GASKET M173/MTZ0 M173/MTZ0 CURTAIN WALL UNITS THE DETAIL WILL NEED TO ?? 17U1 17T5 ERECTOR NOTE: APPLY H12G MULLION CAP IN A BED SEALANT AT SHOW "S4" WITH THE S4 FACTORY ORDER NOTE. WC21 WC18 E2 = VERTICAL STACK PRIOR TO INSTALLATION 17T9 STACK JOINT NECK IN PLACE. SPZ1 ERASE NOTE AFTER READING ERASE NOTE AFTER READING IF THE CUSTOMER ASSEMBLING CURTAIN WALL ERASE NOTE AFTER READING SPZ1 WC18 17T3 WC21 17T8 UNITS THE DETAIL WILL NEED TO SHOW "E7" H12C FRAME 17T7 WITH THE E7 ERECTOR NOTE 17W8 STC7 17T3 UNIT DIM. KV32 (END DAM) SHOP DRAWER NOTE: SHOP DRAWER NOTE: SHOP DRAWER NOTE: KV32 (END DAM) GASKET ERECTOR NOTE: STB1 E11 STB1 ?? STB1 IF EFCO FABRICATING AND ASSEMBLING IF EFCO FABRICATING AND ASSEMBLING E11 IF EFCO FABRICATING AND ASSEMBLING STB1 ?? KV19 APPLY CONTINUOUS BEAD OF SEALANT E6 CURTAIN WALL UNITS THE DETAIL WILL NEED TO ?? CURTAIN WALL UNITS THE DETAIL WILL NEED TO STB1 ?? CURTAIN WALL UNITS THE DETAIL WILL NEED TO E6 E3 = HORIZONTAL STACK JOINT GUTTER TRACK PRIOR SHOW "S4" WITH THE S4 FACTORY ORDER NOTE. SHOW "S4" WITH THE S4 FACTORY ORDER NOTE. SHOW "S4" WITH THE S4 FACTORY ORDER NOTE. WA02 1 31/32" TO SETTING 17T9 STACK JOINT NECK IN PLACE. D.L.O. STC7 STC7 LC45 IM04 STC7 IF THE CUSTOMER ASSEMBLING CURTAIN WALL IF THE CUSTOMER ASSEMBLING CURTAIN WALL FACTORY ORDER NOTE: IF THE CUSTOMER ASSEMBLING CURTAIN WALL STC7 IM04

UNITS THE DETAIL WILL NEED TO SHOW "E7" UNITS THE DETAIL WILL NEED TO SHOW "E7" STC7 1/4" UNITS THE DETAIL WILL NEED TO SHOW "E7" WITH THE E7 ERECTOR NOTE WITH THE E7 ERECTOR NOTE PLACE STC7 FASTENER 1/8" FROM BOTTOM END LC45 WA02 WITH THE E7 ERECTOR NOTE S4 = OF MULLION TO KEEP DURACAST CLIP FROM FALLING OUT THE END OF UNITS. WC18 SPZ1 WC18 WC18 WC18 WC18 SPZ1 4 3/8" HN09 HN09 HN09 HN09

S LC45 LC45 LC45 ERECTOR NOTE: LC45 S FACTORY ORDER NOTE: WA02 FACTORY ORDER NOTE: E7 = PLACE STC7 FASTENER 1/8" FROM BOTTOM END FACTORY ORDER NOTE: ?? ?? OF MULLION TO KEEP DURACAST CLIP FROM ?? ?? PLACE STC7 FASTENER 1/8" FROM BOTTOM END PLACE STC7 FASTENER 1/8" FROM BOTTOM END 17W3 PLACE STC7 FASTENER 1/8" FROM BOTTOM END SPZ1 1H97 S4 = S4 = FALLING OUT THE END OF UNITS. S4 = 1H97 OF MULLION TO KEEP DURACAST CLIP FROM OF MULLION TO KEEP DURACAST CLIP FROM OF MULLION TO KEEP DURACAST CLIP FROM FALLING OUT THE END OF UNITS. FALLING OUT THE END OF UNITS. 17W3 FALLING OUT THE END OF UNITS. SPZ1

WA02 17V4 17V4 2 5/32" WA02

ERECTOR NOTE: ERECTOR NOTE: ERECTOR NOTE: FACTORY ORDER NOTE: PLACE STC7 FASTENER 1/8" FROM BOTTOM END 1/8" PLACE STC7 FASTENER 1/8" FROM BOTTOM END PLACE STC7 FASTENER 1/8" FROM BOTTOM END

17V3 E7 = E7 = E7 = 17V3 GLASS UNIT ARE TO BE SHOP GLAZED BY EFCO. OF MULLION TO KEEP DURACAST CLIP FROM OF MULLION TO KEEP DURACAST CLIP FROM OF MULLION TO KEEP DURACAST CLIP FROM S1 = SHOP DRAWER GLAZING NOTE: ERASE NOTE AFTER READING SEE SHEET 1.02 FOR COLOR AND SEALANT TYPE FALLING OUT THE END OF UNITS. FALLING OUT THE END OF UNITS. FALLING OUT THE END OF UNITS. FOR ALL SHOP SHOP GLAZED UNITS. IF GLASS UNITS ARE TO BE SUPPLIED AND GLAZED BY EFCO THE DETAIL WILL NEED TO 1/8" SHOP DRAWER GLAZING NOTE: 1/8" SHOW "S1" WITH THE S1 FACTORY ORDER NOTE. 1/4" IF GLASS UNITS ARE TO BE SUPPLIED AND ERASE NOTE AFTER READING ERASE NOTE AFTER READING GLAZED BY EFCO THE DETAIL WILL NEED TO ERASE NOTE AFTER READING ERECTOR NOTE: IF GLASS UNITS ARE TO BE SUPPLIED AND 1/4" 7/8" SHOD DRAWER GLAZING NOTE: 7/8" 1/4" 7/8" SHOP DRAWER GLAZING NOTE: SHOW "S1" WITH THE S1 FACTORY ORDER NOTE. 1/4" SHOP DRAWER GLAZING NOTE: 7/8" 1/4" GLASS UNIT ARE TO BE SHOP GLAZED BY GLAZED BY CUSTOMER THE DETAIL WILL NEED TO SHOW "E1" WITH THE E1 ERECTOR NOTE IF GLASS UNITS ARE TO BE SUPPLIED AND IF GLASS UNITS ARE TO BE SUPPLIED AND IF GLASS UNITS ARE TO BE SUPPLIED AND IF GLASS UNITS ARE TO BE SUPPLIED AND (CUSTOMER NAME). IT WILL BE THE E1 = RESPONSIBILITY OF (CUSTOMER NAME) TO GLAZED BY EFCO THE DETAIL WILL NEED TO GLAZED BY EFCO THE DETAIL WILL NEED TO GLAZED BY CUSTOMER THE DETAIL WILL NEED GLAZED BY EFCO THE DETAIL WILL NEED TO 1 7/16" 1 7/16" 1 7/16" 1 7/16" SHOW "S1" WITH THE S1 FACTORY ORDER NOTE. 1 31/32" 2 5/32" 1 7/16" 1 7/16" VERIFY COLOR AND SEALANT TYPE FOR ALL ERASE NOTE AFTER READING SHOW "S1" WITH THE S1 FACTORY ORDER NOTE. TO SHOW "E1" WITH THE E1 ERECTOR NOTE SHOW "S1" WITH THE S1 FACTORY ORDER NOTE. SHOP SHOP GLAZED UNITS. IF GLASS UNITS ARE TO BE SUPPLIED AND IF GLASS UNITS ARE TO BE SUPPLIED AND IF GLASS UNITS ARE TO BE SUPPLIED AND 3" D.L.O. GLAZED BY CUSTOMER THE DETAIL WILL NEED D.L.O. 3" D.L.O. GLAZED BY CUSTOMER THE DETAIL WILL NEED D.L.O. 4 3/8" GLAZED BY CUSTOMER THE DETAIL WILL NEED D.L.O. 3" TO SHOW "E1" WITH THE E1 ERECTOR NOTE TO SHOW "E1" WITH THE E1 ERECTOR NOTE TO SHOW "E1" WITH THE E1 ERECTOR NOTE 3/8" UNIT DIMENSION UNIT DIMENSION UNIT DIMENSION UNIT DIMENSION UNIT DIMENSION 3/8" FACTORY ORDER NOTE: C GLASS UNIT ARE TO BE SHOP GLAZED BY EFCO. L S1 = SEE SHEET 1.02 FOR COLOR AND SEALANT TYPE OVERALL FRAME DIMENSION 1" OVERALL FRAME DIMENSION OVERALL FRAME DIMENSION FOR ALL SHOP SHOP GLAZED UNITS. OVERALL FRAME DIMENSION 1" FACTORY ORDER NOTE: FACTORY ORDER NOTE: FACTORY ORDER NOTE: S1 = GLASS UNIT ARE TO BE SHOP GLAZED BY EFCO. S1 = GLASS UNIT ARE TO BE SHOP GLAZED BY EFCO. S1 = GLASS UNIT ARE TO BE SHOP GLAZED BY EFCO. ROUGH OPENING SEE SHEET 1.02 FOR COLOR AND SEALANT TYPE ROUGH OPENING SEE SHEET 1.02 FOR COLOR AND SEALANT TYPE ROUGH OPENING TO WORK POINT SEE SHEET 1.02 FOR COLOR AND SEALANT TYPE ROUGH OPENING FOR ALL SHOP SHOP GLAZED UNITS. FOR ALL SHOP SHOP GLAZED UNITS. ERECTOR NOTE: FOR ALL SHOP SHOP GLAZED UNITS. GLASS UNIT ARE TO BE SHOP GLAZED BY (CUSTOMER NAME). IT WILL BE THE E1 = RESPONSIBILITY OF (CUSTOMER NAME) TO 422 S.S.G. DYNAMIC JAMB ERECTOR NOTE: 621 S.S.G. DYNAMIC VERTICAL ERECTOR NOTE: VERIFY COLOR AND SEALANT TYPE FOR ALL 721 S.S.G. DYNAMIC 90° OUTSIDE CORNER ERECTOR NOTE: 423 S.S.G. DYNAMIC JAMB SERIES: 8750XD - 7 1/2" STRUCTURAL GLAZED GLASS UNIT ARE TO BE SHOP GLAZED BY SERIES:8750XD - 7 1/2" STRUCTURAL GLAZED GLASS UNIT ARE TO BE SHOP GLAZED BY SHOP SHOP GLAZED UNITS. SERIES:8750XD - 7 1/2" STRUCTURAL GLAZED GLASS UNIT ARE TO BE SHOP GLAZED BY SERIES: 8750XD - 7 1/2" STRUCTURAL GLAZED (CUSTOMER NAME). IT WILL BE THE E1 = (CUSTOMER NAME). IT WILL BE THE (CUSTOMER NAME). IT WILL BE THE E1 = RESPONSIBILITY OF (CUSTOMER NAME) TO RESPONSIBILITY OF (CUSTOMER NAME) TO E1 = RESPONSIBILITY OF (CUSTOMER NAME) TO VERIFY COLOR AND SEALANT TYPE FOR ALL VERIFY COLOR AND SEALANT TYPE FOR ALL VERIFY COLOR AND SEALANT TYPE FOR ALL SHOP SHOP GLAZED UNITS. SHOP SHOP GLAZED UNITS. SHOP SHOP GLAZED UNITS.

221 S.S.G. DYNAMIC STARTER SILL SERIES: 8750XD - 7 1/2" STRUCTURAL GLAZED

7 1/2"

1" D.L.O.

H12B FRAME GASKET WC18 UNIT DIM.

?? 17U0

7/8" STB1 HC05 STB1 1/4"

HN09 LC23 KV31 BRAKE METAL END STB1 WEA2 DAM AT JAMBS 1 11/16"

OVERALL FRAME DIM. LC45 ROUGH OPENING 17V1

9/16" W07V (TAPE) LC54 3 1/4" HC13 HC13 SILICONE SPLICE MULLION DYAMIC LOADING CLIP 3/4" SLEEVE (FIELD INSTALL) STB1 STB1 STB1 1 9/16" 1H92 13/16"

S S 1/2"

FACTORY ORDER NOTE: 1/4" FASTENER WASHER GLASS UNIT ARE TO BE SHOP GLAZED BY EFCO. 1/4" FASTENER WASHER U17D3-001 (WASHER) S1 = SEE SHEET 1.02 FOR COLOR AND SEALANT TYPE SHOP DRAWER GLAZING NOTE: FOR ALL SHOP SHOP GLAZED UNITS. IF GLASS UNITS ARE TO BE SUPPLIED AND GLAZED BY EFCO THE DETAIL WILL NEED TO 3/8" FASTENER WASHER FM59 (WASHER) SHOW "S1" WITH THE S1 FACTORY ORDER NOTE.

ERECTOR NOTE: IF GLASS UNITS ARE TO BE SUPPLIED AND 1/2" FASTENER WASHER FM60 (WASHER) FM68 GLASS UNIT ARE TO BE SHOP GLAZED BY GLAZED BY CUSTOMER THE DETAIL WILL NEED (CUSTOMER NAME). IT WILL BE THE TO SHOW "E1" WITH THE E1 ERECTOR NOTE E1 = RESPONSIBILITY OF (CUSTOMER NAME) TO VERIFY COLOR AND SEALANT TYPE FOR ALL ERASE NOTE AFTER READING U17D3-001 SHOP SHOP GLAZED UNITS.

3/8" FASTENER WASHER

SEE ELEVATION 12 1/4" SEE ELEVATION FOR SPACING FOR SPACING CL FM59 6 1/8" 6 1/8"

925 6" 6" 8.?? 1/2" FASTENER WASHER

KV25 MULLION DYAMIC LOADING CLIP

LC46 DURACAST CAPTURED THERMAL SPACER 17V4 S.S.G. COVER 17V4 S.S.G. COVER FM60 1" FM49 FM66 WC19 STRUCTURAL SILICONE WC19 STRUCTURAL SILICONE SPACER GASKET BEHIND GLASS SPACER GASKET BEHIND GLASS STB1 FM48 STB1 ANCHOR BOLT (SIZED AS REQ'D) STRUCTURAL LC45 DURACAST S.S.G. STRUCTURAL GLAZED SEAL THERMAL SPACER GLAZED SEAL STB1 STB1 FIELD CONDITION EDGE OF VERTICAL EDGE OF VERTICAL (N.B.E.) MULLION BEHIND GLASS MULLION BEHIND GLASS VERTICAL CURTAIN WALL PER EMBED DWG. 1 1/2" PLACE STC7 FASTENER 1/8" FROM BOTTOM STB1 STB1 MULLION ABOVE EDGE OF GLASS END OF MULLION TO KEEP DURACAST CLIP EDGE OF GLASS OR ARCHITECTURAL DWG MIN. FROM FALLING OUT THE END OF UNITS 17T2 CAPTURED 17T2 CAPTURED 1H97 CAPTURED HALF COVER HALF COVER HALF COVER

LC45 DURACAST S.S.G. THERMAL SPACER LC46 DURACAST CAPTURED LC46 DURACAST CAPTURED THERMAL SPACER THERMAL SPACER PLACE STC7 FASTENER 1/8" FROM BOTTOM END OF MULLION TO KEEP DURACAST CLIP FM66 FROM FALLING OUT THE END OF UNITS .562" X .882" SLOTS AT EACH 17D3 EXTRUDED ALUM. W07V DOUBLE W07V DOUBLE ANCHOR BOLT LOCATION SERRATED WASHERS SHOR DRAWER NOTE: STC7 STC7 SIDED TAPE STC7 STC7 SIDED TAPE (SLOT WIDTH PER BOLT SIZE) NEED TO VERIFY WITH STRUCTURAL DEPARTMENT IF THE STANDARD LOAD 11" OR THE HIGH LOAD 16" SLAB ANCHOR WILL BE FIELD APPLY KV39 SILICONE SHEET IN BED OF REQUIRED ON YOUR PROJECT. SEALANT TO THE TOP OF LOWER UNIT AT STACK JOINT. AFTER SETTING IN BOTH THE LOWER AND ERASE NOTE AFTER READING UPPER UNITS INTO THE OPENING APPLY HC13 STACK SWEEP STACK SWEEP 5 1/2" 5 1/2" SILICONE SHEET THEN APPLY HC13 SILICONE HIGH LOAD SLAB ANCHOR HIGH LOAD SLAB ANCHOR HIGH LOAD SLAB ANCHOR HC13 HC13 REF. REF. SHEET TO THE UPPER UNIT BY PLACING IT IN A SET HC13 SILICONE SPLICE BED OF SEALANT. IN A BED OF SEALANT SLEEVE APPLY A CONTINUOUS LINE SEALANT KV39 SET HC13 SILICONE SPLICE IN A BED OF WNC1 MULL PLUG WNC1 MULL PLUG (FIELD INSTALL) AT THE THERMAL STRUT JOINT SEALANT SLEEVE ABOVE VERTICAL MULLION AT HORIZONTAL STACK JOINT (FIELD INSTALL) LC46 DURACAST CAPTURED LC46 DURACAST CAPTURED THERMAL SPACER THERMAL SPACER LC45 DURACAST S.S.G. APPLY AND TOOL A LINE OF THERMAL SPACER SEALANT BETWEEN STARTER EMBED T-BOLT & NUT (N.B.E.) SILL SPLICE JOINT SIZED PER EMBED DWG. SET HC13 SILICONE SPLICE IN A BED OF 17T2 CAPTURED 17T2 CAPTURED ANCHOR BOLT HALF COVER HALF COVER SEALANT SLEEVE ABOVE VERTICAL MULLION AT HORIZONTAL STACK JOINT (SIZED AS REQ'D) EDGE OF GLASS EDGE OF GLASS (FIELD INSTALL) FOR SPACING SEE ELEVATION EDGE OF VERTICAL EDGE OF VERTICAL 1H97 CAPTURED MULLION BEHIND GLASS MULLION BEHIND GLASS PLUG END OF THE SILL STARTER HALF COVER WITH BACKER ROD AT JAMBS AND SLICE JOINTS (BY INSTALLER) STRUCTURAL STRUCTURAL WC19 STRUCTURAL SILICONE GLAZED SEAL GLAZED SEAL SPACER GASKET BEHIND GLASS

WC19 STRUCTURAL SILICONE 1/4" LC46 DURACAST CAPTURED SPACER GASKET BEHIND GLASS 17V4 S.S.G. COVER 17V4 S.S.G. COVER THERMAL SPACER STARTER SILL LENGTH STARTER SILL LENGTH .562" X .882" SLOTS AT EACH ANCHOR BOLT LOCATION (SLOT WIDTH PER BOLT SIZE)

SECTION CUT FM53 SECTION CUT 902 SECTION CUT 901 STACK JOINT END DAM STACK JOINT END DAM 922 DYNAMIC STARTER SILL INTERMEDIATE SPLICE

FM67

6 3/4" PER EMBED DWG. 8" SEE ELEVATION SEE ELEVATION 12" SEE ELEVATION REF.

FOR SPACING FOR SPACING FOR SPACING OR ARCHITECTURAL DWG C 6" L 6" 1/4" FASTENER WASHER U17D3-001 (WASHER) 925 925 925 8.?? 8.?? 8.?? 3/8" FASTENER WASHER FM59 (WASHER) FM66 FM66 FM66 M171

1/2" FASTENER WASHER FM60 (WASHER)

KV30 MULLION DYAMIC STARTER SILL LENGTH SHOR DRAWER NOTE: LOADING CLIP MULLION DYAMIC LOADING CLIP KV25 MULLION DYAMIC NEED TO VERIFY WITH STRUCTURAL STB1 FM61 KV26 AT LEFT JAMB LOADING CLIP DEPARTMENT IF THE STANDARD LOAD 12 3/4" OR KV28 AT RIGHT JAMB 930 DEAD-LOAD ANCHOR THE HIGH LOAD 17 3/4" SLAB ANCHOR WILL BE REQUIRED ON YOUR PROJECT. SERIES: 8750XD - 7 1/2" ERASE NOTE AFTER READING CONC. EMBED (N.B.E.) STB1 EDGE OF CONC. FM48 SIZED PER EMBED DWG. FM64 OR FM65 FM49 FM52 FLOOR SLAB (N.B.E.) M169/IHQ1 SHOR DRAWER NOTE: SHOR DRAWER NOTE: SHOR DRAWER NOTE: FM63 MIN. STB1 1 1/2" 13 29/32" STB1 NEED TO VERIFY WITH STRUCTURAL NEED TO VERIFY WITH STRUCTURAL NEED TO VERIFY WITH STRUCTURAL LC46 DURACAST CAPTURED FM48 STB1 STB1 ANCHOR BOLT STB1 STB1 ANCHOR BOLT DEPARTMENT IF THE STANDARD LOAD 11" OR DEPARTMENT IF THE STANDARD LOAD 11" OR DEPARTMENT IF THE STANDARD LOAD 11" OR FM05 THERMAL SPACER FM48 (SIZED AS REQ'D) (SIZED AS REQ'D) THE HIGH LOAD 16" SLAB ANCHOR WILL BE THE HIGH LOAD 16" SLAB ANCHOR WILL BE THE HIGH LOAD 16" SLAB ANCHOR WILL BE REQUIRED ON YOUR PROJECT. REQUIRED ON YOUR PROJECT. REQUIRED ON YOUR PROJECT. 1" STB1

FM44 17V4 S.S.G. COVER STB1 STB1 STB1 STB1 ERASE NOTE AFTER READING ERASE NOTE AFTER READING ERASE NOTE AFTER READING

3/8" VERTICAL CURTAIN WALL VERTICAL CURTAIN WALL WC19 STRUCTURAL SILICONE STB1 STB1 STB1 STB1 MULLION ABOVE MULLION ABOVE SPACER GASKET BEHIND GLASS STB1 IHQ2 M169 STRUCTURAL

GLAZED SEAL INSIDE CORNER DETAIL OUTSIDE CORNER DETAIL RIGHT JAMB DETAIL LEFT JAMB DETAIL INTERMEDIATE DETAIL FM61 KV31 (END DAM) FIELD CONDITION EDGE OF VERTICAL (N.B.E.) MULLION BEHIND GLASS 5 1/2" 5 1/2" 5 1/2" 5 1/2" 5 1/2" 5 1/2" M141 EDGE OF GLASS 935 934 933 932 931 SPZ1 REF. REF. REF. REF. REF. REF. FM17 8.?? 8.?? 8.?? 8.?? 8.?? M174 17T2 CAPTURED 1H97 CAPTURED .562" X .882" SLOTS AT EACH .562" X .882" SLOTS AT EACH 17D3 EXTRUDED ALUM. 17D3 EXTRUDED ALUM. HALF COVER APPLY AND TOOL A LINE OF ANCHOR BOLT LOCATION ANCHOR BOLT LOCATION HALF COVER SEALANT BETWEEN THE SERRATED WASHERS SERRATED WASHERS SET HC09 SILICONE SPLICE M169/IHQ1 (SLOT WIDTH PER BOLT SIZE) (SLOT WIDTH PER BOLT SIZE) FM44 CURTAIN WALL SYSTEM AND IN A BED OF SEALANT SLEEVE 1/4" FASTENER WASHER 1/4" FASTENER WASHER 1/4" FASTENER WASHER END DAM 17D3 EXTRUDED ALUM. (FIELD INSTALL) IHQ1 LC45 DURACAST S.S.G. VERTICAL CURTAIN WALL SERRATED WASHERS THERMAL SPACER LC46 DURACAST CAPTURED MULLION ABOVE THERMAL SPACER

PLACE STC7 FASTENER 1/8" FROM BOTTOM FM11 FM17 6 3/4" REF.

M174 M171 END OF MULLION TO KEEP DURACAST CLIP EMBED T-BOLT & NUT (N.B.E.) EMBED T-BOLT & NUT (N.B.E.) EMBED T-BOLT & NUT (N.B.E.) EMBED T-BOLT & NUT (N.B.E.) FROM FALLING OUT THE END OF UNITS SIZED PER EMBED DWG. SIZED PER EMBED DWG. SIZED PER EMBED DWG. SIZED PER EMBED DWG. IHQ2 W07V DOUBLE IHQ2/M174/M141 CONC. EMBED (N.B.E.) CONC. EMBED (N.B.E.) CONC. EMBED (N.B.E.) 1/4" FASTENER WASHER FM06 REF. APPLY AND TOOL A LINE OF STC7 STC7 MARRY LINE OF SEALANT AT 5 1/2" SIDED TAPE APPLY AND TOOL A LINE OF SIZED PER EMBED DWG. SIZED PER EMBED DWG. SIZED PER EMBED DWG. SEALANT BETWEEN THE STARTER SILL INTO THE APPLY A BED BED OF SEALANT APPLY A CONTINUOUS LINE SEALANT APPLY A CONTINUOUS LINE SEALANT APPLY A CONTINUOUS LINE SEALANT SEALANT BETWEEN STARTER CURTAIN WALL SYSTEM AND CURTAIN WALL PERIMETER TO THE END OF STARTER SILL AT THE THERMAL STRUT JOINT AT THE THERMAL STRUT JOINT AT THE THERMAL STRUT JOINT SILL SPLICE JOINT END DAM SPZ1 AT THE JAMB CONDIDTION BEFORE ATTACHING END DAM M141 U17D3-001 U17D3-001 U17D3-001

KV31 OR KV32 (END DAM) STACK SWEEP SPZ1 APPLY A BED BED OF SEALANT 3/8" FASTENER WASHER 3/8" FASTENER WASHER 3/8" FASTENER WASHER TO THE END OF STARTER SILL PLUG END OF THE SILL STARTER BEFORE ATTACHING END DAM WITH BACKER ROD AT JAMBS FM05/FM06 STARTER SILL AND SLICE JOINTS (BY INSTALLER) U17D3-001 SPZ1

MARRY LINE OF SEALANT AT STARTER SILL INTO THE CURTAIN WALL PERIMETER 3/8" FASTENER WASHER SECTION CUT AT THE JAMB CONDIDTION FIELD JAMB CONDITION PLUG END OF THE SILL STARTER

1/4" 935 WITH BACKER ROD AT JAMBS INSIDE CORNER DEAD-LOAD DETAIL AND SLICE JOINTS (BY INSTALLER) IHQ2/M174/M141 900 EMBED T-BOLT & NUT (N.B.E.) SEE ELEVATION 13 29/32" SIZED PER EMBED DWG. FM59 FM59 FM59 8.?? PLUG END OF THE SILL STARTER FOR SPACING 3/8" EMBED T-BOLT & NUT (N.B.E.) WITH BACKER ROD AT JAMBS SECTION CUT GENERAL NOTE: SIZED PER EMBED DWG. AND SLICE JOINTS (BY INSTALLER) 900 STARTER SILL LENGTH 1/4" CONC. EMBED (N.B.E.) STARTER SILL END DAM M171 THE PRIMARY LINE OF SEALANT (NOT SHOWN HERE SHIMS BY INSTALLER 1/2" FASTENER WASHER 1/2" FASTENER WASHER 1/2" FASTENER WASHER SIZED PER EMBED DWG. FOR CLARITY) IS AT THE FACE OF THE MULLION, IT IS

AT THE FACE OF THE COVER (NOT SHOWN FOR 5/8" STARTER SILL LENGTH STARTER SILL LENGTH FM59 CLARITY) ONLY AT THE STARTER SILL AND WILL FOLLOW THE LINE OF THE END CAP TO MARRY INTO SECTION CUT THE PRIMARY LINE. 923 SECTION CUT SECTION CUT DYNAMIC STARTER SILL CORNER SPLICE 1/2" FASTENER WASHER 920 DYNAMIC STARTER SILL JAMB 921 DYNAMIC STARTER SILL INTERMEDIATE 4" 4" PER EMBED DWG. PER EMBED DWG. PER EMBED DWG. PER EMBED DWG. 5 1/2" REF.

FM60 REF. FM60 FM60 REF. FM06 OR ARCHITECTURAL DWG OR ARCHITECTURAL DWG OR ARCHITECTURAL DWG OR ARCHITECTURAL DWG IHQ2/M174/M141 M171

CONC. FLOOR M171 M171 M171 M171 FM60 M171 SLAB (N.B.E.)

FM43 M170 M169/IHQ1 FM61 FM61 FM61 FM62

EDGE OF CONC. EDGE OF CONC. EDGE OF CONC. EDGE OF CONC. M169/IHQ1 M169/IHQ1 FLOOR SLAB (N.B.E.) M169/IHQ1 FLOOR SLAB (N.B.E.) FLOOR SLAB (N.B.E.) M169/IHQ1 FLOOR SLAB (N.B.E.) M169/IHQ1 MIN. MIN. MIN. MIN. 1 1/2"

1 1/2" 1 1/2" 1 1/2" M141

FM06 FM05 FM05 FM06 FM05

IHQ2 FM43 FM11 FM11 FM11 FM11 IHQ2 IHQ2 IHQ2 IHQ2 M174

CONC. EMBED SIZE FM17 PER EMBED DWG. M174 M174 M174 M174 (N.B.E.) FM17 FM17 FM17 FM17 SECTION CUT

M141 M141 M141 M141 934 OUTSIDE CORNER DEAD-LOAD DETAIL 1 1/2" PER EMBED DWG. MIN. OR ARCHITECTURAL DWG M174 1 1/2" PER EMBED DWG. MIN. OR ARCHITECTURAL DWG FM17 IHQ2

M141

SECTION CUT SECTION CUT SECTION CUT 931 INTERMEDIATE DEAD-LOAD DETAIL 932 LEFT JAMB DEAD-LOAD DETAIL 933 RIGHT JAMB DEAD-LOAD DETAIL