KALAMAZOO, MICHIGAN 710 AVIS DRIVE ANN ARBOR, MICHIGAN 48108 WATER RECLAMATION PLANT PHONE: (734) 665-6000 FAX: (734) 213-3003

ELECTRICAL UPGRADES SWITCHGEAR www.tetratech.com

ELECTRICAL PROJECT LOCATION: CLIENT INFORMATION: E-001 ELECTRICAL LEGEND KALAMAZOO, MICHIGAN

E-002 ELECTRICAL LEGEND, NOTES KALAMAZOO, MICHIGAN

E-003 ELECTRICAL KALAMAZOO WATER RECLAMATION PLANT SITE

E-004 ELECTRICAL SITE PLAN DEMOLITION E-005 ELECTRICAL ONE-LINE PROPOSED DEMOLITION Tt PROJECT No.: CLIENT PROJECT No.: E-006 ELECTRICAL ONE-LINE PROPOSED WORK 200-19743-19002 E-007 ELECTRICAL SWITCHGEAR FRONT ELEVATION

E-008 ELECTRICAL ONE-LINE PROPOSED WORK E-009 ELECTRICAL ONE-LINE PROPOSED WORK PROJECT DESCRIPTION / NOTES: E-010 ELECTRICAL SYSTEM CONFIGURATION

E-011 BACKGROUND PLAN PROPOSED WORK

E-012 ELECTRICAL DEMOLITION, PROPOSED WORK

E-013 PROPOSED ROOF PLAN

E-014 PROPOSED ROOF PLAN MVUS NO.1

E-015 ELECTRICAL DETAILS

E-016 ELECTRICAL DETAILS ISSUED: OWNER REVIEW 7-12-19 OWNER REVIEW 50% 7-25-19 OWNER REVIEW 100% 8-22-19 OWNER REVIEW FINAL 9-12-19 OWNER REVIEW FINAL 10-17-19 FOR BIDDING AND CONSTRUCTION 11-30-20

VICINITY MAP:

PROJECT LOCATION 1 2 3 4 5 6 7 710 AVIS DRIVE www.tetratech.com

F ANN ARBOR, MI 48108

BACKGROUND PLAN AND ONE LINE SYMBOLS I.S.A. STANDARD LETTER FUNCTIONS SYMBOL DESCRIPTION SYMBOL DESCRIPTION CONTROL (SEL. OR P.B.) SYMBOL FIRST LETTER SUCCEEDING LETTERS PHONE: (734) 665-6000 FAX: 213-3003 SEE CIRCUITS FOR SPECIFIC TYPE FT TAG NO. (BALLOON) FOR DEVICE 10 INDICATED A ANALYSIS, ANALOG ALARM SEE CIRCUITS FOR SPECIFIC TYPE F FL B BURNER, FLAME BATCH - FLOW SWITCH CONTROL CIRCUIT & PILOT DEVICE LEGEND C CONDUCTIVITY, COMMAND CONTROL (FEEDBACK TYPE) TEMPERATURE - SWITCH FT FOR POWER (SEE NOTE 2 ON D DENSITY, SPECIFIC GRAVITY T M (SUBSCRIPT=NO. OF STAGES) 10 STANDARD NOTE SHEET) SYMBOL DESCRIPTION SYMBOL DESCRIPTION 3/4"C(2/C#18SH) SELECTOR SWITCH - NORMALLY E VOLTAGE PRIMARY ELEMENT LIMIT (PROXIMITY TYPE) L P V CONDUIT AND WIRE RUN FROM PRESS. ACTUATED SWITCH OPEN F FLOW RATE RATIO PRESSURE - VACUUM SWITCH A-3 DEVICE INDICATED TO LOCATION G GAGING GLASS ELECTRICAL OR MECHANICAL MCP OR ALT INDICATED FLOAT ACTUATED SWITCH H HAND, MANUAL HIGH ALTERNATOR (SEE WIRING) CP-1 FLOW ACTUATED SWITCH CAPACITOR, 3 PHASE, SIZE AS I CURRENT INDICATE OS OVERLOAD SWITCH OR DEVICE INDICATED J POWER SCAN TEMP. ACTUATED SWITCH TIME, TIME SCHEDULE CONTROL (NO FEEDBACK) DISCONNECT SWITCH (F) = FUSED, - NORMALLY OPEN K TB TERMINAL BOX F C (C) = CIRCUIT BREAKER L LEVEL, LIGHT LOW E LIMIT SWITCH - NORMALLY M MOISTURE, HUMIDITY MIDDLE, MODULATE LIMIT SWITCH - NORMALLY SOLENOID VALVE (BACKGROUND DRAWINGS ONLY) CLOSED N CLOSED - HELD OPEN O OVERLOAD ORIFICE COMBINATION MAGNETIC LIMIT SWITCH - NORMALLY OPEN - PC PHOTOCELL LINE VOLTAGE STARTER FUSED UNLESS NOTED P PRESSURE, VACUUM POINT LATCHING CABLE SWITCH HELD CLOSED SIZE 2 (CIRCUIT BREAKER) Q QUANTITY TOTALIZE, INTEGRATE AS NOTED (LIGHTING PANEL, R RADIOACTIVITY RECORD, PRINT, RECEIVE CONTROL PANEL, DISTRIBUTION COMBINATION LIGHTING MOMENTARY PUSHBUTTON TIME DELAY FUSE S SPEED, FREQUENCY, SOLENOID SWITCH PANEL, ETC.) WALL MOUNTED CONTACTOR WITH LC OPERATOR-NORMALLY CLOSED TEMPERATURE, TURBIDITY TRANSMIT, TRANSFORM HAND-OFF-AUTO SWITCH T PUSHBUTTON OPERATOR U MULTIVARIABLE MULTIFUNCTION JB JUNCTION BOX MANUAL STARTER (R) = MOMENTARY PUSHBUTTON R WITH MUSHROOM HEAD V VIBRATION, VISCOSITY VALVE, DAMPER, LOUVER REVERSING OPERATOR-NORMALLY OPEN TRANSFORMER W WEIGHT, FORCE CP CONTROL PANEL CONTROL RELAY CONTACT - FIELD LOCATED STOP BUTTON X CONDUIT WITH CONDUIT SEAL NORMALLY OPEN (F) Y RELAY, COMPUTE FITTING Z POSITION DRIVE, ACTUATE 1 CONTROL RELAY CONTACT - CONDUIT EXPOSED UNIT HEATER, 1/8 HORSEPOWER TIMING RELAY INSTANTANEOUS 8 UH-19 NORMALLY CLOSED INST. CONTACT CONDUIT CONCEALED TIMING RELAY CR E DIRECT BURIED CONDUIT LIGHTING ARRESTOR CONTROL RELAY COIL INST. INSTANTANEOUS CONTACT UG DIRECT BURIED CABLE O LOW VOLTAGE HOME RUNS D H C OH OVERHEAD LINE A-3 120/208V, 120/240V (SEE NOTE 2 CR L ON STANDARD NOTE SHEET) SELECTOR SWITCH OPERATOR DB UNDERGROUND DUCT BANK TWO COIL LATCHING RELAY WITH FUNCTION SHOWN PROTECTIVE RELAY LEGEND EXISTING UNDERGROUND DUCT NEMA 4 WATERTIGHT EDB WATERTIGHT AND CORROSION BANK NEMA 4X CR DEVICE NO. DESCRIPTION

PROOF BY CONCRETE ENCASED DUCT BANK U 2 SYNC. TIMER 0-5 MIN. 1 2 3 EXPLOSION PROOF - CLASS I, WITH CABLE LOCATIONS, AND SPARE NEMA 7 4 5 6 DUCTS AS INDICATED ON DRAWINGS DIVISION 1, GROUP D TIMED OPEN CONTACT ON 25 SYNCHRONIZING EXPLOSION PROOF - CLASS II, TIMED CLOSED CONTACT ON NEMA 9 ENERGIZATION 27 SHORT TIME UNDERVOLTAGE CABLE REEL DIVISION 1 ENERGIZATION 32 REVERSE POWER RELAY K KEYLOCK TIMED CLOSED CONTACT ON TIMED OPEN CONTACT ON L L L L MULTI-STACK ALARM LIGHTS DE-ENERGIZATION 38 TEMPERATURE DE-ENERGIZATION SD SMOKE DETECTOR 40 LOSS OF EXCITATION SELECTOR SWITCH / R PUSH-TO-TEST INDICATING PUSHBUTTON. FUNCTIONS AS ZERO SPEED OR LIGHT 43 SELECTOR SWITCH 1 SHOWN IN WIRING DIAGRAMS E EXIT LIGHT ANTI-PLUGGING SWITCH 47 PHASE SEQUENCE & UNDERVOLTAGE LOW VOLTAGE DISCONNECT MAINTAINED STOP - MOMENTARY FLUORESCENT LUMINAIRE 49 THERMAL SWITCH MAINTAINED STOP-START START PUSHBUTTON (JOG) LOW VOLTAGE FUSE PUSHBUTTON OPERATOR 50/51 INSTANTANEOUS AND VERY INVERSE

SHANK, JASON INCANDESCENT LUMINAIRE (BELOW 600V) - 51 VERY INVERSE HIGH VOLTAGE FUSE SOLENOID OR CLUTCH C (ABOVE 600V) HIGH INTENSITY DISCHARGE 51G INVERSE GROUND FAULT LIGHT MAINTAINED PUSH - PULL ALL STARTERS SHALL BE FULL 51N NEUTRAL OVERCURRENT OPERATOR 1 VOLTAGE, NON-REVERSING UNLESS ETI ELAPSED TIME INDICATOR RV 51V OVERCURRENT RELAY WITH VOLTAGE RESTRAINT OTHERWISE INDICATED. EMERGENCY BATTERY PACK DESCRIPTION 2 EM FVR (FVR) FULL VOLTAGE REVERSING 52/CS CONTROL SWITCH (RV) REDUCED VOLTAGE X1 X2 3 DS DESK INTERCOM SET LOCAL TERMINALS WITH 120VAC TRANSFORMER 2S,2W (2S, 2W) TWO SPEED, TWO WINDING 59 INSTANTANEOUS OVERVOLTAGE

EXTERNAL WIRING DATE 60 VOLTAGE BALANCE 600V, 3 POLE MOLDED CASE CAMERA PUSHBUTTON OPERATOR WITH CIRCUIT BREAKER, FRAME & T MUSHROOM HEAD 62 TIME DELAY RATING AS SHOWN PTZ TIMING RELAY COIL DOME CAMERA (PAN, TILT, ZOOM) SOLENOID OR CLUTCH 64 SHORT TIME LOW PICK UP OVERVOLTAGE MARK SINGLE PHASE, FRACTIONAL HP 67 DIRECTIONAL OVERCURRENT T 1 MOTOR TO LOCATION INDICATED 1 TIMING RELAY COIL (OFF DELAY) THERMAL OVERLOAD A-3 69 LOCKOUT CONTROL SWITCH 2 (SEE NOTE 2 ON STANDARD NOTE 52 DRAW OUT CIRCUIT BREAKER SHEET) (ABOVE 600 VOLT) (F) FIELD LOCATED 78 OUT OF STEP G INDICATING LIGHT 81 OVER/UNDER FREQUENCY RELAY DEVICE SYMBOL WITH TYPE CIRCUIT BREAKER WITH STAB TERMINAL POINT 86 83 MULTI-CONTACT AUXILIARY DEVICE CONNECTION PUSH-TO-TEST INDICATING LIGHT 86/HR MULTI-CONTACT AUX. HAND RESET CURRENT TRANSFORMER, AND TERMINAL (3) 87 DIFFERENTIAL OVERCURRENT THREE PHASE LOAD WITH RATIO (WITH NUMBER REQUIRED A 50/5 X1 X2 SECONDARY LOW VOLTAGE FUSE B 1 IDENTIFICATION SHOWN) TRANSFORMER FUSIBLE TERMINAL BLOCK MOLDED CASE CIRCUIT BREAKER CONTROL POWER TRANSFORMER MOMENTARY PUSHBUTTON OPERATOR - NORMALLY CLOSED MOMENTARY PUSHBUTTON RECEPTACLE OPERATOR - NORMALLY OPEN SYMBOL LEGEND LEGEND GENERAL DISCONNECT SWITCH WIRING DEVICE SCHEDULE SYMBOL DESCRIPTION SYMBOL DESCRIPTION ELECTRICAL NOTE: THE PLC I/O ADDRESS SHALL BE USED AS THE WIRING TAG SCHEME FOR ALL PANEL AND FIELD PT POTENTIAL TRANSFORMER W WATTMETER SYMBOL DESCRIPTION NEMA TYPE WATER RECLAMATION PLANT CONTROL WIRING. COORDINATE WITH ELECTRICAL CONTRACTOR. CT CURRENT TRANSFORMER AP ALARM POINT

125V, 2P, DUPLEX, 3W 5-20 R CITY OF KALAMAZOO, MICHIGAN A AMMETER CPT CONTROL POWER TRANSFORMER ELECTRICAL UPGRADES SWITCHGEAR SIMPLEX RECEPTACLE V VOLTMETER (2) (3) NUMBER OF DEVICES REQUIRED QUAD RECEPTACLE PF POWER FACTOR METER ETI ELAPSED TIME METER 20A, 120/277V SWITCH SPST

A Project No.: 200-19743-19002 Designed By: GCJ \TT.LOCAL\IER ROJECTS\ANN ARBOR\IER\19743\200-19743-19002\CAD\SHEETFILES\E-001_ELECTRICAL LEGEND.DWG

- Drawn By: JLS Checked By: WAP/MSJ E-001 OF 16 Copyright: Tetra Tech 9/15/2020 9:32:53 AM Bar Measures 1 inch 1 2 3 4 5 6 7

NOTES: GENERAL NOTES: 710 AVIS DRIVE www.tetratech.com 1. FIELD VERIFY CONDUIT ROUTING AT THE KWRP WITH OWNER. CORE HOLES AS REQUIRED TO SUIT 1. PRIOR TO SUBMITTING A BID FOR THE WORK DETAILED UNDER THIS CONTRACT, BIDDER SHALL VISIT THE

INSTALLATION OF THE CONDUITS SHOWN. PATCH WITH NON-SHRINK GROUT. KWRP. THE BIDDER SHALL FULLY ACQUAINT ONESELF WITH EXISTING FIELD CONDITIONS AT EACH SITE. NO ANN ARBOR, MI 48108 F BULLETINS WILL BE WRITTEN FOR WORK DUE TO LACK OF VERIFICATION OF EXISTING SITE CONDITIONS 2. TURN OVER TO OWNER AT PROJECT COMPLETION OPERATION AND MAINTENANCE MANUALS (QUANTITY AS AND WIRING. SPECIFIED) TO OWNER. 2. NO WIRES SHALL BE TERMINATED TO TERMINAL STRIPS, OR OTHER EQUIPMENT WITHOUT FIRST VERIFYING 3. IN ADDITION TO PATCH CABLES SUPPLIED FOR THE PROJECT, FURNISH 30-10FT LONG SINGLEMODE DUPLEX SIGNAL TYPE. DAMAGES RESULTING IN LACK OF VERIFICATION SHALL BE BORNE BY THE CONTRACTOR. FIBER OPTIC PATCH CABLES (ST-ST) CONNECTORS, AND 30-10FT CAT-5E PATCH CABLES FOR OWNERS USE. CONTRACTOR SHALL COORDINATE SIGNAL TYPE AND VOLTAGE WITH I/O CARDS SHOWN. TURN OVER CABLES TO OWNER. 3. WITHIN CONTROL PANELS, NAMEPLATES SHALL BE PROVIDED TO INDICATE DIFFERENT VOLTAGE LEVELS

4. MULTIMODE FIBER OPTIC PATCH CABLES, AND ETHERNET PATCH CABLES SUPPLIED IN THE PROJECT SHALL WITHIN PANELS. ALSO, A NAME TAG (YELLOW BACKGROUND, RED LETTERING) SHALL BE LOCATED ON THE H N PHONE: (734) 665-6000 FAX: 213-3003 BE COLORED PURPLE. FRONT OF EVERY PANEL INDICATING THAT WHEN MAIN PANEL DISCONNECTED 120V IS STILL PRESENT LP-A(12) FROM FIELD DEVICES (YELLOW WIRING/ISOLATED INPUT CARDS.) 5. FIBER OPTIC PATCH PANELS SHALL BE THE PRODUCT OF CORNING CABLE SYSTEMS. (RACK OR SURFACE MOUNTED AS SHOWN", ST STYLE CONNECTORS, WITH QUANTITY OF BULKHEADS AS SHOWN. 4. PHENOLIC TAGS ON FACE OF CONTROL PANELS TO HAVE WHITE BACKGROUND AND BLACK LETTERING (EXCEPT WARNING TAGS; YELLOW BACKGROUND RED LETTERING). C R GENERAL CONSTRUCTION NOTES: 5. PROVIDE SAFETY COVERS ON ALL 480V MOLDED CASE MAIN CIRCUIT BREAKERS TO INSULATE THE 1. ELECTRICAL MATERIALS AND EQUIPMENT ITEMS SHOWN IN LIGHT LINE WEIGHTS ON THE DRAWINGS ARE INCOMING CABLES AND SIDE CONDUCTORS FROM CONTACT. (TYP. FOR CONTROL PANELS.) PROVIDE H EXISTING ITEMS TO REMAIN. ELECTRICAL MATERIALS AND EQUIPMENT ITEMS SHOWN IN HEAVY LINE BREAKER LOCKS FOR PUMP CIRCUIT BREAKERS (MCP)AND MAIN PANEL BREAKERS. OFF ON WEIGHTS ARE NEW THIS CONTRACT. C 6. REFER TO WIRING DIAGRAMS FOR ADDITIONAL INFORMATION ON ISOLATED I/O. A COMMON NEUTRAL MAY 2. ITEMS SHOWN OR NOTED TO BE DEMOLISHED ON THE DRAWINGS ARE EXISTING ITEMS TO BE REMOVED BE USED FOR SEVERAL ISOLATED INPUTS FROM THE SAME STARTER. PROVIDE NEUTRAL JUMPERS WIRES FROM SITE BY CONTRACTOR UNLESS NOTED TO BE TURNED OVER TO OWNER. WITHIN THE PANEL AS REQUIRED. E 3. FOR ITEMS INDICATED AS "FIELD LOCATE", THE CONTRACTOR SHALL FIELD VERIFY FOR INTERFERENCE 7. ELECTRICAL MATERIALS AND EQUIPMENT ITEMS SHOWN IN LIGHT LINE WEIGHTS ON THE DRAWINGS ARE AND FOR LOCATIONS OF MOUNTING FLANGES, CONNECTION POINTS, ETC. EXISTING ITEMS TO REMAIN. ELECTRICAL MATERIALS AND EQUIPMENT ITEMS SHOWN IN HEAVY LINE (F) WEIGHTS ARE NEW THIS CONTRACT. 4. CONDUIT ROUTINGS SHOWN ON BACKGROUND PLANS ARE INTENDED ROUTINGS ONLY. EXACT CONDUIT 8. ITEMS SHOWN CROSSHATCHED (OR NOTED TO BE DEMOLISHED) ON THE DRAWINGS ARE EXISTING ITEMS 1 PHASE LOAD ROUTINGS FOR CONDUITS, AND LENGTH SHALL BE FIELD LOCATED AND VERIFIED BY THE CONTRACTOR. TO BE REMOVED, FROM SITE BY CONTRACTOR. LP-A(14) COORDINATE CONDUIT ROUTING IN FINISHED AREAS WITH OWNER. CONDUIT TO BE CONCEALED IN THESE AREAS. 9. INSTALL A SINGLE CONDUCTOR INSULATED (RHW, THHN, OR XHHW) COPPER GROUND WIRE IN EACH (F) CONDUIT, SIZE AS SHOWN ON DRAWINGS, OR AS A MINIMUM PER THE NATIONAL ELECTRICAL CODE. THIS 5. REFER TO THE CABLE MANUFACTURER'S RECOMMENDATIONS FOR MINIMUM BEND RADIUS FOR FIBER GROUND WIRE SHALL BE CONNECTED AT EACH END TO THE EQUIPMENT GROUND. THIS ALSO INCLUDES OPTIC CABLES. INSTALL NEW PULL BOXES (PB) AS REQUIRED FOR CONDUITS. SIZE PULL BOXES AS INSTRUMENTATION DEVICES SUCH AS LEVEL, PRESSURE, FLOW TRANSMITTERS, LIMIT , LP-A(16) REQUIRED PER FIBER OPTIC CABLE MANUFACTURERS RECOMMENDATIONS. CONDUITS, NETWORK AND I/O CABLES. (F) (F)

6. CONDUITS/RACEWAYS, PULL BOXES AND JUNCTION BOXES TO BE INSTALLED WITH 316 STAINLESS STEEL 10. THE FOLLOWING EXAMPLE COMPONENT IDENTIFICATION SHALL BE USED AS APPROPRIATE: TYPICAL LOCAL DISC. W/O.L. WHERE REQUIRED CHANNEL STRUT. MINIMUM STRUT LENGTH TO BE 12 INCHES, WHERE POSSIBLE. (F) FIELD MOUNTED, NOT AT STARTER OR OTHER CONTROL PANELS 7. PANELS SHALL BE MOUNTED OFF WALLS WITH STRUT, CONDUITS SHALL BE MOUNTED ON STRUT (S) STARTER PANEL MOUNTED INCLUDING SINGLE RUNS. (MCP)AT MAIN CONTROL PANEL TYPICAL 120V 3 POLE CONTACTOR (1) AT CONTROL PANEL NO.1 (EXAMPLE CIRCUIT) 8. CONDUIT ENTERING CONTROL PANELS AND ELECTRICAL EQUIPMENT ENCLOSURES SHALL BE FILLED WITH (2) AT CONTROL PANEL NO.2 DUCT SEAL, INCLUDING OPENINGS IN BOTTOM OF PANELS, AND EQUIPMENT. (TCP) AT TEMPERATURE CONTROL PANEL SEAL-IN CONTACT FROM 9. REPAIR SIDEWALKS AND ROADWAYS DUE TO SITE WORK ADDITIONS, THE EXTENT OF THE REPAIR D 11. REFER TO DETAIL SHEETS. CONTRACTOR SHALL FURNISH AND INSTALL HARDWARE AND APPURTENANCES STARTER CONTACTOR A1 REQUIRED SHALL BE FIELD VERIFIED PRIOR TO BIDS IN CONJUNCTION WITH THE WORK SHOWN IN THE (I.E. PIPE TAPS, WETWELL BUBBLER TUBES, VALVES, COPPER TUBING, BALL VALVES, PNEUMATIC PIPING, CONTRACT DOCUMENTS. PRIOR TO TRENCHING, FIELD LOCATE EXISTING GAS LINES, TELEPHONE LINES, SPOOL PIECES, ETC.) FOR FIELD DEVICES SHOWN (FLOWMETERS, PRESSURE TRANSMITTERS, LEVEL STARTER CONTROL TRANSFORMER SPRINKLER LINES, ETC. COORDINATE WITH OWNER TRANSMITTERS, ETC.). WORK SHALL BE COORDINATED WITH OTHER TRADES (MECHANICAL INSTRUMENTATION, ETC.) CONTRACTOR SHALL BE RESPONSIBLE FOR SYSTEM COORDINATION AND X1 X2 10. PULL CORDS SHALL BE INSTALLED IN CONDUITS CONTAINING NETWORK CABLES, AND FIBER OPTIC CABLES. INSTALLATION. 120V BY 11. CORE HOLES AS REQUIRED TO SUIT INSTALLATION OF CONDUIT AND WIRING/CABLING AS SHOWN. FIELD 12. ETHERNET AND FIBER OPTIC TERMINATIONS SHALL BE PERFORMED BY A QUALIFIED REPRESENTATIVE OF PLC-I/O POINT/ADDRESS (TYP.) STARTER LIGHT VERIFY EXACT EXTENT OF WORK REQUIRED. CABLE MANUFACTURER, THE CABLES SHALL BE TESTED. NO SPLICING SHALL BE PERMITTED OF FIBER A-1 A-1 "RUNNING" PUSHBUTTON FIELD MOUNTED OPTIC CABLES, BETWEEN PANELS. FIBERS SHALL BE TERMINATED AT PATCH PANELS, INCLUDING SPARES. R 12. FURNISH PULL BOXES FOR FIBER OPTIC CABLE. COORDINATE EXACT BENDING RADIUS WITH TAG THIS WIRE MANUFACTURER. 1 13. REFER TO THE CABLE MANUFACTURER'S RECOMMENDATIONS FOR MINIMUM BEND RADIUS FOR FIBER A1-1A (TYP.) OFF OPTIC CABLES. INSTALL NEW PULL BOXES (PB) AS REQUIRED FOR CONDUITS. SIZE PULLBOXES AS HAND AUTO 3-OL'S 13. NEW CONDUITS INSTALLED THIS CONTRACT WITH FIBER OPTIC CABLES ARE TO BE LABELED WITH 1 STOP REQUIRED PER FIBER OPTIC CABLE MANUFACTURERS RECOMMENDATIONS. A PHENOLIC TAGS (AT BEGINNING TO END) TO INDICATE THE NUMBER OF STRANDS, ORIGINATION AND 1 DESTINATION. TAGS TO BE COLOR CODED ORANGE FOR MULTIMODE. 14. CONDUIT ENTERING CONTROL PANELS AND ELECTRICAL EQUIPMENT ENCLOSURES SHALL BE FILLED WITH PUSHBUTTON (F) (F) DUCT SEAL, INCLUDING OPENINGS IN BOTTOM OF PANEL. FIELD MOUNTED 14. WHERE NEW CONDUITS SHOWN TO BE INSTALLED PASS UNDER ROADWAYS, CONDUITS SHALL BE SHANK, JASON A-1 STARTER CONTACTOR - CONCRETE ENCASED. 15. CABLES (INCLUDING FIBER, ETHERNET, CONTROL WIRE, ETC.) WHERE PASSING THROUGH A PULLBOX SWITCH LOCATED AT COIL FOR MOTOR A1. SHALL BE LABELED AND COMPLETELY IDENTIFIED WITH IDENTIFICATION NUMBERS AND STARTER CUBICLE TO MCP 15. PRIOR TO EXCAVATION, FIELD LOCATE EXISTING UTILITIES. COORDINATE WITH OWNER. ORIGINATION/DESTINATION. THIS ALSO INCLUDES ALL CABLE BUNDLES ENTERING CONTROL PANELS, A-1 7I-0101 PULLBOXES, ETC. 16. AREAS WHERE CAMERAS ARE SHOWN TO BE INSTALLED SHALL BE CLASSIFIED AS NEMA 4, UNLESS CALLED STARTER CUBICLE C OUT OTHERWISE. ISOLATED PLC I/O POINT (TYP.) TO MCP 16. CONTROL WIRES SHALL BE TAGGED WITH THE PLC I/O ADDRESS IN THE FIELD AND AT THE PANEL. TERMINAL STRIP RELAY INTERLOCK FROM AUX. STARTER CONTACT 17. THE ASSOCIATED INSTRUMENTATION DRAWINGS SHOW EXISTING WIRES AND TERMINAL NUMBERS 17. THE FIELD DEVICES SHOWN ON THE P&ID'S, ELECTRICAL BACKGROUNDS, AND DETAILS SHEETS MAKEUP MAIN CONTROL PANEL TO MAIN CONTROL PANEL NON-ISOLATED INPUT REQUIRED TO PROPERLY INTERFACE WITH NEW EQUIPMENT. THIS INFORMATION WAS COLLECTED FROM THE FIELD DEVICE EQUIPMENT REQUIREMENTS. NOT ALL FIELD DEVICES REQUIRED ARE SHOWN ON THE DESCRIPTION AS-BUILT DRAWINGS AND EXTENSIVE FIELD VERIFICATION. THE INFORMATION SHALL BE USED AS A GUIDE P&ID'S. IN RE-TERMINATION. IT SHALL REMAIN THE CONTRACTOR'S RESPONSIBILITY TO EXAMINE THE WIRING AND TO REVISE TO SUIT AS REQUIRED. CHANGES IN THE CONTRACT OR COST WILL NOT BE GRANTED FOR THIS 18. UPS SELECTED SHALL BE COMPATIBLE WITH ISOLATION TRANSFORMERS. (TYP.) A EXAMPLE PUMP DATE COORDINATION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO EXAMINE PROPOSED WORK SHOWN. STARTER NAMEPLATE 19. REFER TO I/O DRAWING LAYOUT FOR ADDITIONAL SIGNALS NOT SHOWN ON P&ID FLOW DIAGRAMS. 1 (TAG A1) 18. CONDUIT ROUTINGS SHOWN ON BACKGROUND PLANS ARE PROPOSED ROUTINGS ONLY. EXACT CONDUIT (EXAMPLE CIRCUIT)

ROUTINGS AND LENGTH SHALL BE FIELD LOCATED AND VERIFIED BY THE CONTRACTOR. COORDINATE MARK CONDUIT ROUTING IN FINISHED AREAS WITH OWNER. CONDUIT TO BE CONCEALED IN THESE AREAS.

19. RACEWAYS, PULL BOXES AND JUNCTION BOXES TO BE INSTALLED WITH 316 STAINLESS STEEL FASTENERS SUPPORTS, AND THREADED ROD, ETC. (CHANNEL STRUT TO ALSO BE STAINLESS STEEL). MINIMUM STRUT LENGTH TO BE 12 INCHES, WHERE POSSIBLE. TYPICAL FOR NEMA 12, 4, AND 7 AREAS. WIRES TO CONTROL NO.1 FIELD MOUNTED PILOT DEVICES 20. WIRING FOR STARTERS SHALL BE IN ACCORDANCE WITH NEMA CLASS II B STANDARDS. SUBMIT 3/4"C(4#14) ENGINEERED SHOP DRAWINGS FOR ALL STARTERS SHOWN TO BE WIRED. FUSE SIZE 2#14 21. WIRE NUMBERS (1, 3, 5, ETC.) SHALL BE PREFIXED WITH STARTER TAG NUMBERS. THE WIRE NUMBER AFTER 3/4"C(4#12) (1) THE PREFIX SHALL BE THE MANUFACTURER'S WIRE NUMBERING SYSTEM. WIRE MARKERS SHALL BE USED 3 KVAR B AT EACH WIRE TERMINATION POINT. 60A 20A 3/4"C(4#10, 4#14) 2 A 10HP SAMPLE PUMP 22. IN AREAS WHERE EQUIPMENT AND CONDUIT IS REMOVED, REPAIR WALL AND FLOOR SURFACES AS 1 60A REQUIRED TO MATCH SURROUNDING AREA. WHERE DEVICES ARE REMOVED FROM CONCEALED BOXES, SWITCH, AND SIZE FURNISH AND INSTALL A BLANK COVER ON THE BOX. CONDUIT SIZE, AND FILL DISCONNECT LOAD SIZE IDENTIFICATION PLATE INFORMATION SWITCH LOAD 23. FIBER OPTIC CABLE SHALL BE AS CALLED OUT ON SYSTEM CONFIGURATION DRAWINGS, SINGLE MODE, ALL IDENT. DIELECTRIC, SUITABLE FOR INSTALLATION UNDERGROUND IN WET CONDUIT. STARTER, AND TYPE A OR A THESE ITEMS SHOWN ON PLAN VIEW AS 1 1 ELECTRICAL LEGEND, NOTES MCC LEGEND EXAMPLE WATER RECLAMATION PLANT CITY OF KALAMAZOO, MICHIGAN ELECTRICAL UPGRADES SWITCHGEAR

A Project No.: 200-19743-19002 Designed By: GCJ \TT.LOCAL\IER ROJECTS\ANN ARBOR\IER\19743\200-19743-19002\CAD\SHEETFILES\E-002_ELECTRICAL LEGEND-NOTES.DWG

- Drawn By: JLS Checked By: WAP/MSJ E-002 OF 16 Copyright: Tetra Tech 9/15/2020 9:34:38 AM Bar Measures 1 inch 1 2 3 4 5 6 7 710 AVIS DRIVE www.tetratech.com

F ANN ARBOR, MI 48108 PHONE: (734) 665-6000 FAX: 213-3003

E

EXISTING NETWORK ROOM INSTALL THREE MULTIPOINT RADIOS ON EXISTING POLE. MOUNT AT 100' +/- ABOVE GRADE ONTO EXISTING POLE. 1 - 12-STRAND F.O. CABLE D ROUTE CABLES INTO RADIO BUILDING TO RADIO CONCENTRATOR PANEL.

EXISTING RADIO BUILDING INSTALL NEW FIBEROPTIC CABLE IN EXISTING CONDUIT BETWEEN RADIO PANEL, AND RCS RADIO CONCENTRATION PANEL BY EXISTING 130' POLE PANEL IN ADMINISTRATION BUILDING. TERMINATE 12-STRANDS AT EACH END.

ADMINISTRATION BUILDING RCS PANEL

SEAL HOLE(S) AT BUILDING WALL WITH PLIABLE CAULK

EXISTING STAINLESS EXISTING 130' POLE STEEL MESSENGER CABLE EXISTING STAINLESS STEEL MESSENGER CABLE SHANK, JASON

- SEAL HOLE(S) AT BUIILDING WALL WITH PLIABLE CAULK C

PORTABLE GENERATOR/TRANSFORMER/CABLES. STAGING AREA. DESCRIPTION COORDINATE WITH OWNER, AND CONSUMERS ENERGY. DATE MARK

B PLANT SITE ELECTRICAL EXISTING CONSUMERS ENERGY SUBSTATION. WATER RECLAMATION PLANT CITY OF KALAMAZOO, MICHIGAN ELECTRICAL UPGRADES SWITCHGEAR KALAMAZOO WATER RECLAMATION

EXISTING SWITCHGEAR SHALL BE DEMOLISHED. SEE SHEET E-004 FOR ADDITIONAL INFORMATION. A PLANT SITE 0 30' 60' 120' Project No.: 200-19743-19002 \TT.LOCAL\IER ROJECTS\ANN ARBOR\IER\19743\200-19743-19002\CAD\SHEETFILES\E-003_SITE PLAN_DEMO.DWG Designed By: GCJ N

- SCALE: 1"=60' SCALE: 1"=60' Drawn By: JLS EXISTING DRAWING FROM PREVIOUS PROJECT. Checked By: WAP/MSJ PROPOSED WORK SHOWN BOLD, CROSSHATCHED, AND/OR CIRCLED. E-003 OF 16 Copyright: Tetra Tech 9/15/2020 12:46:05 PM Bar Measures 1 inch 1 2 3 4 5 6 7 710 AVIS DRIVE www.tetratech.com

F ANN ARBOR, MI 48108 PHONE: (734) 665-6000 FAX: 213-3003

E

14

D BY

REMOVE WIRES, AND CAP EXISTING SERVICE CONDUITS IN EXISTING SWITCHES NO LONGER IN USE. (TYP.).

C SHANK, JASON - DESCRIPTION DATE

SWITCH ID NUMBER. SEE PICS. (TYP.) MARK

DEMOLISH EXISTING CONCRETE DUCTBANK, CONDUIT/WIRE.

B DEMOLISH EXISTING CONCRETE DUCTBANK, CONDUIT/WIRE FOR EACH SERVICE. RACK/BUS STRUCTURE TO BE REPLACED. SEE SHEET E-006, AND E-015 FOR ADDITIONAL INFORMATION. ELECTRICAL N WATER RECLAMATION PLANT CITY OF KALAMAZOO, MICHIGAN ELECTRICAL UPGRADES SWITCHGEAR SITE PLAN SITE PLAN DEMOLITION SCALE: 3/16"=1'-0"

A Project No.: 200-19743-19002 Designed By: GCJ \TT.LOCAL\IER ROJECTS\ANN ARBOR\IER\19743\200-19743-19002\CAD\SHEETFILES\E-004_SITE_DEMO.DWG

- Drawn By: JLS EXISTING DRAWING FROM PREVIOUS PROJECT. Checked By: WAP/MSJ PROPOSED WORK SHOWN BOLD, CROSSHATCHED, AND/OR CIRCLED. E-004 OF 16 Copyright: Tetra Tech 9/15/2020 9:51:04 AM Bar Measures 1 inch 1 2 3 4 5 6 7 710 AVIS DRIVE www.tetratech.com

F LOCATED AT CPCO TRANSFORMER YARD. ANN ARBOR, MI 48108 PHONE: (734) 665-6000 FAX: 213-3003

E

D BY SHANK, JASON

- C DESCRIPTION DATE MARK

B ELECTRICAL WATER RECLAMATION PLANT CITY OF KALAMAZOO, MICHIGAN ELECTRICAL UPGRADES SWITCHGEAR ONE-LINE PROPOSED DEMOLITION

A Project No.: 200-19743-19002

\TT.LOCAL\IER ROJECTS\ANN ARBOR\IER\19743\200-19743-19002\CAD\SHEETFILES\E-005_ONE-LINE_DEMO.DWG Designed By: GCJ - Drawn By: JLS EXISTING DRAWING FROM PREVIOUS PROJECT. Checked By: WAP/MSJ PROPOSED WORK SHOWN BOLD, CROSSHATCHED, AND/OR CIRCLED. E-005 OF 16 Copyright: Tetra Tech 9/15/2020 10:05:48 AM Bar Measures 1 inch 1 2 3 4 5 6 7

PROVIDE 2000A COPPER JUMPERS AT SWITCH. FROM BUS TO SWITCH. (TYP.) METERING BY CPCO. 4800V, 3 PH, 3W, 2000A COPPER BUS. CT'S 166 4800V, 3 PH, 3W, 2000A COPPER BUS. 266 CT'S SOUTH FEED 46,000V. 5 - 5"C(3#500 KCMIL, 133% 15 KV RATED, 1#250 KCMIL) EACH. NORTH FEED 46,000V. 299 1 - 5"C(PULL CORD) SPARE. CABLE TO CONFORM TO CPCO STANDARDS. (TYP.) 299 CONSUMERS ENERGY TRANSFORMER YARD PT'S 5 - 5"C(3#500 KCMIL, 133% 15 PT'S M 10,000 KVA 10,000 KVA M

KV RATED, 1#250 KCMIL) EACH. 710 AVIS DRIVE METERING BY CPCO. INSTALL NEW CONDUIT, WIRE, RISER RACK, BUS, ETC. (TO MATCH EXISTING) AND 1 - 5"C(PULL CORD) SPARE. DUCTBANKS FROM NEW SWITCHGEAR TO EXISTING CPCO TRANSFORMERS. COORDINATE www.tetratech.com CABLE TO CONFORM TO CPCO SECONDARY CONNECTION AT TRANSFORMERS WITH CONSUMERS ENERGY. SEE NOTES, (CONSUMERS ENERGY) ANN ARBOR, MI 48108 F STANDARDS. (TYP.) AND DETAILS ON SHEET E-015. (TYP. OF 2 TRANSFORMERS/SERVICES.) PROVIDE 2000A COPPER JUMPERS AT SWITCH. FROM BUS TO SWITCH. (TYP.) COORDINATE EXACT TYPE, AND CONSTRUCTION WITH CONSUMERS ENERGY. (TYP.)

(KWRP) 6 - 5"C(3#500 KCMIL 15KV, GROUNDED WYE GROUNDED WYE (133%), 1#250 KCMIL) EACH. CONTROL LOGIX BROKEN FURNISH LOADING RESISTOR AS REQUIRED. (TYP.) BROKEN PLC-L72 CABLE TO CONFORM TO DELTA DELTA 6 - 5"C(3#500 KCMIL 15KV, (133%), 1#250 KCMIL) EACH. PROVIDE BREAKERS WITH IR WINDOWS. (TYP.) WITH I/O CARDS AS REQUIRED CPCO STANDARDS. (TYP.) 3-PTS 3-PTS TRANSFER SCHEME SEQUENCE 59 ALARM 59 CABLE TO CONFORM TO CPCO STANDARDS. (TYP.) G TO PLC G 4800/120V 4800/120V PHONE: (734) 665-6000 FAX: 213-3003 OF OPERATION - (MVUS NO.1) STACKING STRATIX 5700 GE MODEL PQMII-A (2 UNITS) TO 1. TRANSFER: WITH THE MAIN AND TIE BREAKERS IN THE CABLE SWITCH I/O SWITCH MB-1 MB-2 INCLUDE POWER QUALITY, AND AUTOMATIC TRANSFER GE MODEL PQMII-A (2 UNITS) AUTOMATIC MODE AND UPON THE LOSS OF VOLTAGE ON SCHEME - (PLC) MVUS NO.1 15 KV, 95 KVBIL, 500 MVA RATED WAVE FORM CAPTURE ANALYSIS. TO INCLUDE POWER EITHER SOURCE, THE RESPECTIVE MAIN SHALL OPEN AFTER A LIGHTNING OPEN TRANSITION METAL CLAD SWITCHGEAR, NEMA 3R SUITABLE TIME DELAY AND THE TIE SHALL THEN CLOSE IF NO ARRESTORS 6 KV. 27 86 E-NET E-NET QUALITY, AND WAVE FORM ENCLOSURE. PAINT NEMA 3R ENCLOSURE WHITE. LOCKOUT CONDITION EXISTS. IF THE REMAINING SOURCE HAS STRATIX 5700 CAPTURE ANALYSIS. SWITCH I/O SWITCH LIGHTNING ARRESTORS 6 KV. A LOSS OF VOLTAGE ITS RESPECTIVE MAIN BREAKER SHALL 47 51 27/ A A 27/ 47X 47X OPEN. THE TIE REMAINS CLOSED. CONTACTS TO PLC. (TYP. FOR EACH BREAKER.) A 59G TO TO 2. RETRANSFER: UPON RETURN OF THE LOST VOLTAGE AND STRATIX 5700 PF MB-1 MB-2 PF AFTER A SUITABLE TIME DELAY THE TIE BREAKER SHALL OPEN. SWITCH LAN SWITCH 27/ BREAKER BREAKER 27/ B 43A IF NO LOCKOUT CONDITION EXISTS, THE MAIN SHALL THEN 47 TO 47 SEQUENCE OF CONSTRUCTION CLOSE AFTER A SUITABLE TIME DELAY THE MAIN MUST BE IN FURNISH SEPARATE TOP V V ENCLOSURE IF REQUIRED TIE THE PLANT SHALL REMAIN OPERATIONAL DURING THE ENTIRE E AUTOMATIC FOR THE MAIN TO CLOSE ON RETRANSFER AND BREKER PANELVIEW PLUS BY MANUFACTURER. (TYP.) SWITCHOVER. THE CONTRACTOR SHALL SUPPLY PORTABLE THE TIE BREAKER MUST BE IN AUTOMATIC OR OFF AND OPEN. 3-PTS GE PQMII-A WITH MULTINET-FE 3-PTS IF SIMULTANEOUS RESTORATION OF BOTH SOURCES SHOULD 1500 SERIES 7 CPT W W CPT GENERATOR(S), STEP UP TRANSFORMER CABLING, PERFORMANCE PLUS (L-L) (SERIAL TO ETHERNET CONVERTER (L-L) 3 KVA MIN. SWITCHES, ETC, AS REQUIRED TO MAINTAIN PLANT OCCUR, THE TIE SHALL OPEN AND THEN BOTH MAINS SHALL MODULE) COMMUNICATION 3 KVA MIN. 4800V-120V OPERATION DURING ENTIRE CONSTRUCTION PERIOD. CLOSE. HEATERS, BREAKER MODULE WITH KEYPAD. FURNISH 4800V-120V HEATERS, BREAKER CONTROLS, AND 83 4800V-120V 4800V-120V CONTROLS, AND 83 ETHERNET SWITCH TO CONNECT HALF OF THE EXISTING MAIN SWITCHGEAR SHALL BE 3. LOCKOUT: PROTECTIVE TRIPPING OF EITHER MAIN CONTROL RELAYS. PM TO NETWORK. PROVIDE ONLINE CONTROL RELAYS. 3 CT'S 3 CT'S SWITCHED OUT AT A TIME. BREAKER, AS CAUSED BY 51 OR 51G RELAYS, SHALL CAUSE PROVIDE ONE LICENSED UPS FOR EACH PM. (TYP.) THE HAND RESET LOCKOUT RELAY, 86, TO OPERATE. THIS COPY TO OWNER OF 2000/5 51 51 2000/5 E-NET E-NET COORDINATE SHUTDOWN AND DISCONNECTION OF EACH SHALL PREVENT THE OPERATION OF THE TRANSFER SCHEME FACTORYTALK VIEW BREAKERS SHALL BE CAPABLE OF CAT-6 TO SWITCH. (TYP.) BEING REMOTELY RACKED VIA PRIMARY SERVICE WITH CONSUMERS ENERGY AND PAY ANY OR RECLOSING OF THE RESPECTIVE BREAKERS UNTIL SUCH 2 KVA ONLINE UPS STUDIO 4 MACHINE INTERNAL RACKING MECHANISM. (TYP.) FEES ASSOCIATED WITH THIS COORDINATION AS PART OF TIME AS THE LOCKOUT HAS BEEN RESET. ADDITION. MULTILIN SR850 (TYP.) MULTILIN SR850 THE CONTRACTORS BASE BID. SEE NOTE BELOW. 9701-VWSTMENE. 4. MANUAL: WITH THE AUTOMATIC-MANUAL SWITCHES, 43, IN MB-1 MB-2 MANUAL MODE THE MAINS AND TIE BREAKERS ARE UNDER CS 86 2000A, 15 KV, 95 KVBIL, CS 86 2000A, 15 KV, 95 KVBIL, NOTE: FROM PLC 52 52 CONTROL OF THEIR RESPECTIVE CONTROL SWITCHES 52CS, 43 50 KA RMS SYM. FROM PLC 43 50 KA RMS SYM. CONTRACTOR SHALL INCLUDE IN BID AN ALLOWANCE IN THE THESE BREAKERS SHALL BE INTERLOCKED SO THAT BOTH N.C. N.C. AMOUNT OF $35,000 FOR PAYMENT TO CONSUMERS ENERGY 2000A BUS, 15 KV, 95 KVBIL, 3 CT'S PLC/TIE MAINS CANNOT BE CLOSED WITH THE TIE BREAKER CLOSED. PLC/TIE TIE FOR SHUT OFF/RE-ENERGIZATION OF THE TWO ELECTRIC 50 KA RMS SYM. BRACING 2000/5 2000A BUS, 15 KV, 95 KVBIL, 50 KA RMS SYM. BRACING 52 SERVICES, IN THE CONSUMERS ENERGY TRANSFORMER 5. SYMBOLS WITHOUT QUANTITY NUMBERS ASSUMED TO BE E-NET YARD, DURING THE SWITCHOVER. ANY UNUSED MONIES ONE. SHALL BE CREDITED BACK TO OWNER. NO MARKUPS SHALL 50 KA RMS SYM. BRACING. 2000A 15 KV, 95 KVBIL, FROM CS FROM CS FROM CS (TYP. ALL BREAKERS.) 51 FROM CS FROM CS FROM CS BE ALLOWED ON THE ALLOWANCE MONIES 6. TRANSFER SCHEME LOGIC SHALL BE IMPLEMENTED WITHIN PLC 43 PLC 43 PLC 43 50 KA RMS SYM. PLC 43 PLC 43 PLC 43 D N.O. ROCKWELL CONTROL LOGIX PLC. SEE SHEET E-010 FOR MULTILIN SR850 A ADDITIONAL INFORMATION, AND REQUIREMENTS. 52 52 52 CS 86 52 52 52 86 1200A 86 1200A 86 1200A FROM PLC 43 86 1200A 86 1200A 86 1200A 7. FEEDER BREAKERS SHALL BE CAPABLE OF BEING FB1 FB2 FB3 B FB4 FB5 FB6 CONTROLLED MANUALLY FROM PV-1500/PLC WHEN NOT IN

43A BY AUTOMATIC OPERATION. TO PLC I/O. (TYP. FOR EACH FEEDER BREAKER.) SWITCHGEAR TO BE PROVIDED WITH REMOTE 8. SEMI-AUTOMATIC TRANSFER: IN THIS MODE, WHEN POWER 86 CONTROL MECHANISM TO OPERATE BREAKERS IS TRANSFERRED AND TIE BREAKER IS CLOSED, THE 3 CT'S 3 CT'S 3 CT'S 3 CT'S 3 CT'S 3 CT'S REMOTELY. PROVIDE WITH 25 FT. OF CABLE MINIMUM. RE-TRANSFER SHALL BE SOFTWARE SELECTABLE TO BE 1000/5 51 50 1000/5 51 50 1000/5 51 50 51 1000/5 51 50 1000/5 51 50 1000/5 51 50 MANUALLY INITIATED VERSUS AUTOMATICALLY TRANSFER BACK TO BOTH MAIN SOURCES AND THE TIE BREAKER OPEN. E-NET E-NET E-NET E-NET E-NET E-NET

FIREWRAP CABLES IN BREAKER COMPARTMENT, AND FUSE COMPARTMENT. (TYP.) (C) (J) (K) (C1) (J1) (K1) SWITCHGEAR SHALL BE LOCATED ON 4" THICK CONCRETE HOUSEKEEPING PAD. MULITLIN SR850. (TYP.) FEEDER IDENTIFICATION (TYP.) (4" THICK PAD IS ON TOP OF NEW CONCRETE PAD.) SHANK, JASON - PROVIDE THERMOSTATICALLY CONTROLLED STRIP C BOTTOM EXIT. (TYP. OF 6) CONTRACTOR/MANUFACTURER TO HEATERS FOR EACH BREAKER SECTION. (TYP.) PROVIDE WEATHERPROOF SEALS, BOXES, HUBS, ETC. (TYP.) PROVIDE RED, AND BLUE PHENOLIC TAGS WITH LARGE WHITE LETTERS TO INDICATE. (TYP. FOR FEEDER BREAKERS, AND LOAD INTERRUPTER SWITCHES.) DESCRIPTION 2 - 5"C(3#500 KCMIL, 15 KV, 133%, 1#4/0) 2 - 5"C(3#500 KCMIL, 15 KV, 133%, 1#4/0) 2 - 5"C(3#500 KCMIL, 15 KV, 133%, 1#4/0)

15 KV, 1200A BUS, 3 PH, 3W, 60 HZ, 95 KVBIL, TOP ENTRY. (TYP. OF 15.) DATE 2 - 5"C(3#500 KCMIL, 15 KV, 133%, 1#4/0) 50 KA RMS SYM. BRACING. CONTRACTOR/MANUFACTURER TO PROVIDE 3 - 5"C(3#500 KCMIL, 15 KV, 133%, 1#4/0 OR NEMA 3R/4 BUS DUCT) SEE SHEET WEATHER PROOF SEALS, BOXES, HUBS, ETC. (TYP.) 2 - 5"C(3#500 KCMIL, 15 KV, 133%, 1#4/0) 2 - 5"C(3#500 KCMIL, 15 KV, 133%, 1#4/0) E-007, AND SHEET E-011 FOR DISTANCE ≈90'± FIELD VERIFY EXACT LENGTH.

LOAD INTERRUPTOR SWITCHES SHALL MARK 15 KV, 1200A BUS, 3 PH, 3W, 60 HZ, 95 KVBIL, 15 KV, 1200A BUS, 3 PH, 3W, 60 HZ, EACH BE RATED 15KV, 38 KA RMS. SYM 95 KVBIL, 50 KA RMS SYM. BRACING. BRACING. (MIN.) 95 KVBIL. (TYP.) K1 K1 1200A 50 KA RMS SYM. BRACING. 3 - K1 LOCKS CONTRACTOR TO 2 - K1 KEYS N.C. FIELD VERIFY N.C. (25) EXISTING ID NUMBER. (TYP.) (31) EXISTING ID (38) NUMBERS. (TYP.) (35)(34) 800E 800E K2 1200A K2 1200A K3 1200A K3 1200A (30) (32) (33) 1200A (36) (37) (39) N.C. N.C. 3 - K3 LOCKS N.C. N.C. 15 KV, 1200A BUS, 3 PH, 3W, 60 HZ, 3 - K2 LOCKS B (1), (2) (15), (16) 2 - K3 KEYS (18) (22) 95 KVBIL, 50 KA RMS SYM. BRACING. K1 2 - K2 KEYS (9)(8) (24) (23) N.O. 800E 800E 720E 720E 600A 600A 600A 600A 600A 600A NEW SWITCH CONSTRUCTION, AND (3) (4) (5) (6) (7) 1200A (10) (11) (12) (13) (14) (17) (19) (20) 1200A (21) SIZE CPT AS ORIENTATION TO MATCH EXISTING. REQUIRED. (TYP.) CONTRACTOR/MANUFACTURER TO K2 K3 FIELD VERIFY. (TYP.) NEW SWITCHES TO BE SUPPLIED WITH 200E 200E 100E 200E 150E 200E N.O. N.O. IR WINDOWS. (TYP. ALL SWITCHES.) CPT 600A 600A 600A 600A 600A 600A 600A 600A 600A 600A 600A 600A 600A 600A 600A ELECTRICAL WATER RECLAMATION PLANT (C) (B) (A) (A1) (B1) (C1) COORDINATE LUG, AND

400E 125E 250E 100E 200E 200E 100E 125E 200E 400E 400E 400E 400E 400E 400E CITY OF KALAMAZOO, MICHIGAN

CABLE LANDING ELECTRICAL UPGRADES SWITCHGEAR LOCATION TO SUIT RECONNECTION OF ONE-LINE PROPOSED WORK EXISTING WIRES. (TYP.) (H1) (G1) (F1) (E1) (D1) (D) (E) (F) (G) (H) (L) (M) (L1) (M) (J)

A NEMA 3R/4 Project No.: 200-19743-19002 PROVIDE STRIP RATED. (TYP.) Designed By: GCJ

\TT.LOCAL\IER ROJECTS\ANN ARBOR\IER\19743\200-19743-19002\CAD\SHEETFILES\E-006__ONE-LINE_PROPOSED.DWG HEATER (TYP. FOR

- EACH SWITCH) Drawn By: JLS Checked By: WAP/MSJ EXISTING 5 KV WIRING TO PLANT TRANSFORMERS. EXISTING 5 KV WIRING TO PLANT TRANSFORMERS. EXISTING 5 KV WIRING TO PLANT TRANSFORMERS. TO BE RECONNECTED. (TYP.) TO BE RECONNECTED. (TYP.) TO BE RECONNECTED. (TYP.) WEST BANK (FACING WEST) EAST BANK-1 (FACING EAST) EAST BANK-2 (FACING EAST) E-006 OF 16 Copyright: Tetra Tech 11/9/2020 5:29:48 PM Bar Measures 1 inch 1 2 3 4 5 6 7

FB-1 FB-2 FB-3 INCOMING TIE INCOMING FB-4 FB-5 FB-6 (C) (J) (K) MB-1 BREAKER MB-2 (C1) (J1) (K1)

PQM 59 PQM 59 II G II G

43 SR 43 SR 43 SR 27 43 SR 43 SR 27 43 SR 43 SR 43 SR 43 SR 710 AVIS DRIVE www.tetratech.com 850 850 850 850 850 850 850 850 850

F 86 86 86 47 86 86 47 86 86 86 86 ANN ARBOR, MI 48108 39 38 37 36 35 34 33 32 31 30 (MAIN) (TIE) (MAIN) 115"± PHONE: (734) 665-6000 FAX: 213-3003 96"±

E 38"± 38"± 38"± 38"± 22"± 38"± 38"± 38"± 38"± 38"± 3'± 3'± 3'± 3'± 3'± 3'± 3'± 3'± 3'±

62"± DEPTH 27'±

PROPOSED WEST BANK SWITCHES MB-1 BOTTOM MB-2 BOTTOM FEEDER BREAKERS BOTTOM EXIT (FACING WEST) ENTRY ENTRY FEEDER BREAKERS BOTTOM EXIT NEMA 3R ENCLOSURE. (NOT SHOWN) NOT TO SCALE PROPOSED MAIN SWITCHGEAR FRONT ELEVATION (MVUS NO.1) SET MVUS NO.1 ON 4" THICK CONCRETE NOT TO SCALE. PAD ON TOP OF NEW CONCRETE PAD. DIMENSIONS ARE APPROXIMATE. CONTRACTOR TO FIELD FURNISH ON THE FACE OF EACH BREAKER, MEASURE, AND MATCH EXISTING SO THAT EXISTING LOAD, AND SWITCH RED, AND BLUE PHENOLIC NOT ALL DOOR DEVICES ARE SHOWN. CONDUITS, AND ASSOCIATED WIRING CAN BE REUSED. CONTRACTOR TO FIELD MEASURE EXISTING SWITCHES AND TRANSITION SECTIONS NAMETAGS WITH WHITE LETTERS TO AND PROVIDE NEW SWITCHES AND TRANSITION SECTIONS THAT ARE IDENTICAL IN DIFFERENTIATE THE TWO POWER SOURCES. COORDINATE EXACT DIMENSIONS WITH SWITCHGEAR MANUFACTURER. PHYSICAL SIZE SO THAT EXISTING CONDUIT/WIRE CAN BE REUSED/RECONNECTED TRANSITION SECTION TO FEED EXISTING LOADS FROM THE NEW LOAD INTERRUPTER SWITCHES. SEE NOTES. AS REQUIRED.

CONTRACTOR RESPONSIBLE FOR PROPER SITING TO MEET CODE REQUIREMENTS. FURNISH ON THE FACE OF EACH BREAKER, AND SWITCH RED, AND BLUE PHENOLIC NAMETAGS WITH WHITE LETTERS TO DIFFERENTIATE THE TWO POWER SOURCES. D

MATCH EXISTING SWITCH DEPTH IN ORDER 24 23 22 21 1 2 3 4 5 6 7 8 9 TO MAINTAIN PROPER CLEARANCES IN (TIE) (MAIN) (MAIN) (TIE) FRONT, AND BACK, AND TO RE-USE EXISTING LOAD CONDUITS/CONDUCTORS. (TYP.) EAST-2 EAST-2 EAST-1 EAST-1 BY 96"± SHANK, JASON -

C

36"± 36"± 20"± 36"± 33"± 38"± 38"± 36"± 38"± 38"± 38"± 38"± 22"± 38"± 62"± DEPTH (EAST BANK-2) - PROPOSED (EAST BANK-1) - PROPOSED DESCRIPTION DIMENSIONS SHOWN ARE FROM SWITCHES (21-24) (FACING EAST) SWITCHES (1-16) (FACING EAST)

EXISTING SWITCHES. NEW SWITCHES TO DATE NOT TO SCALE. NOT TO SCALE. MATCH EXISTING DIMENSIONS. (TYP.) EAST BANK-1 CONTINUED BELOW. SEE BELOW LINEUP SEE BELOW LINEUP

FURNISH ON THE FACE OF EACH BREAKER, MARK AND SWITCH RED, AND BLUE PHENOLIC CONTRACTOR TO FIELD LOCATE EXISTING NAMETAGS WITH WHITE LETTERS TO SWITCHES AND TRANSITION SECTIONS AND DIFFERENTIATE THE TWO POWER SOURCES. PROVIDE NEW SWITCHES AND TRANSITION SECTIONS THAT ARE IDENTICAL IN PHYSICAL SIZE SO THAT EXISTING CONDUIT/WIRE CAN BE REUSED/RECONNECTED TO EXISTING LOADS

B NOTES: 1. COORDINATE EXACT DIMENSIONS WITH SWITCHGEAR MANUFACTURER. 10 11 12 13 14 15 16 17 18 19 20 25 2. NOT ALL DEVICES REQUIRED ARE SHOWN IN THE FRONT ELEVATIONS. REFER TO THE WIRING (MAIN) (MAIN) DIAGRAMS FOR CONTROL/PILOT DEVICES TO BE LOCATED ON THE FACE OF EACH STARTER. EAST-1 EAST-2

3. THE NEW SWITCHGEAR SHALL BE FURNISHED WITH A ROCKWELL CONTROL LOGIX L72 SERIES PROCESSOR, MEMORY MODULE, ETHERNET BRIDGE CARDS, RACK, IO CARDS, AND POWER SUPPLY AS REQUIRED FOR CONTROLLING THE MAIN-TIE-MAIN BREAKERS. IN ADDITION, FURNISH A STRATIX ELECTRICAL SWITCH, PANELVIEW PERFORMANCE PLUS SERIES 7 SERIES 1500. SEE THE SYSTEM CONFIGURATION DRAWING FOR ADDITIONAL INFORMATION. WATER RECLAMATION PLANT 96"±

4. THE CONTROL OF THE BREAKERS SHALL BE PROGRAMMED BY THE SWITCHGEAR MANUFACTURER. CITY OF KALAMAZOO, MICHIGAN INTEGRATION OF THIS PLC TO THE OWNERS EXISTING SCADA SYSTEM IS BY OWNER. ELECTRICAL UPGRADES SWITCHGEAR

5. OBTAIN IP ADDRESSES FOR THE PLC/BRIDGE CARD, POWER MONITORS, MULTILIN RELAYS, AND PANELVIEW FROM OWNER/TETRA TECH. SWITCHGEAR FRONT ELEVATION 6. TURN OVER DOCUMENTED COPIES OF PLC PROGRAMS AND PANELVIEW PLUS APPLICATIONS TO OWNER/TETRA TECH.

A 7. CONTRACTOR RESPONSIBLE FOR PROPER SITING TO MEET CODE REQUIREMENTS. Project No.: 200-19743-19002 Designed By: GCJ \TT.LOCAL\IER ROJECTS\ANN ARBOR\IER\19743\200-19743-19002\CAD\SHEETFILES\E-007_SWITCHGEAR FRONT EL_PR.DWG

- 38"± 38"± 38"± 38"± 38"± 38"± 38"± 33"± 36"± 20"± 33"± 33"± 35 1/2"± Drawn By: JLS 62"± DEPTH (EAST BANK-1) - PROPOSED (EAST BANK-2) - PROPOSED Checked By: WAP/MSJ SWITCHES (1-16 CONTINUED) (FACING EAST) SWITCHES (17-20, AND 25) (FACING EAST) NOT TO SCALE. NOT TO SCALE. E-007 SEE ABOVE. SEE ABOVE. OF 16 Copyright: Tetra Tech 9/17/2020 2:21:47 PM Bar Measures 1 inch 1 2 3 4 5 6 7 710 AVIS DRIVE www.tetratech.com

F ANN ARBOR, MI 48108 1 H

CLOSE OUTPUT OPEN OUTPUT T C CS FROM PLC CS FROM PLC 86-1 B A 59G 86-1 A M M TOC PHONE: (734) 665-6000 FAX: 213-3003 43-1 83-2 83-1 43-1 43-1 SIZE CPT'S AS A H H 43-1 REQUIRED. 51

120V AC

83-1 B B TIE

120V AC FROM CPT 83-1 83-2 120V AC FROM CPT CONTROL MB-2 INCOMING SOURCE NO.1 INCOMING SOURCE NO.2 POWER FROM RELAY CONTROL TRANSFER N N LOGIC 86-1 LATCHING RELAYS

E 83-1 83-1 A LS BB 86-1 120V AC 120V AC 83-1 83-1 B B R G Y M TC 86-1 CLOSED OPENED LOCKOUT GROUND FAULT 1 1 1 1 Y A LS PS BB PS

H N 86-1

N TO BREAKERS CONTROL POWER (MB-1, MB-2, TIE, FEEDER BREAKERS, EXISTING ROOF EXTERIOR LIGHTS, EXISTING SWITCHGEAR YARD FLOOD LIGHT, CONVENIENCE OUTLET, RADIO CAPACITOR TRIP PANEL, NEW SWITCHGEAR ROOF LIGHTS) PROVIDE BRANCH CIRCUIT BREAKERS AS REQUIRED 43-1A 52A 83-1 51 52B 83-2 TO SWITCHGEAR PLC - I/O TO PLC 86 D

MAIN TIE MAIN BREAKER CONTROL POWER TRANSFER DIAGRAM MAIN BREAKER MB-1 PARTIAL WIRING DIAGRAM BY (MB-1, MB-2, TIE) (NOT ALL 52 BREAKER DEVICES ARE SHOWN.)

1 1 H H

CLOSE OUTPUT OPEN OUTPUT CLOSE OUTPUT OPEN OUTPUT T T C C CS CS FROM PLC CS FROM PLC FROM PLC CS FROM PLC 86-1 86-2 86-2 86-T SHANK, JASON - B A B A 59G 86-2 C 86-T A A M M M TOC TOC 43-2 43-2 43-2 43-T 43-T 43-M A A 43-2 43-T 51 51 DESCRIPTION

120V AC 120V AC B B B B TIE

CONTROL MB-1 MB-2 CONTROL MB-1 POWER FROM POWER FROM DATE RELAY RELAY CONTROL CONTROL 86-1

TRANSFER TRANSFER MARK LOGIC LOGIC 86-2 86-2 A 86-T A LS LS BB BB 86-2 86-T TC B B B R R G G Y Y M M TC 86-2 86-T CLOSED CLOSED OPENED OPENED

B LOCKOUT LOCKOUT A GROUND FAULT 1 1 1 1 1 1 1 Y Y A LS LS PS BB PS PS BB PS 86-2 86-T

N N CAPACITOR TRIP CAPACITOR TRIP (TYP.) 43-TA 52A 43-2A 52A ELECTRICAL 51 52B 51 52B WATER RECLAMATION PLANT TO PLC TO PLC CITY OF KALAMAZOO, MICHIGAN

86 86 ELECTRICAL UPGRADES SWITCHGEAR ONE-LINE PROPOSED WORK

TIE BREAKER PARTIAL WIRING DIAGRAM MAIN BREAKER MB-2 PARTIAL WIRING DIAGRAM A (NOT ALL 52 BREAKER DEVICES ARE SHOWN.) (NOT ALL 52 BREAKER DEVICES ARE SHOWN.) Project No.: 200-19743-19002

\TT.LOCAL\IER ROJECTS\ANN ARBOR\IER\19743\200-19743-19002\CAD\SHEETFILES\E-008_BREAKER WIR DIA.DWG Designed By: GCJ - Drawn By: JLS Checked By: WAP/MSJ E-008 OF 16 Copyright: Tetra Tech 9/15/2020 10:39:41 AM Bar Measures 1 inch 1 2 3 4 5 6 7 710 AVIS DRIVE www.tetratech.com

F ANN ARBOR, MI 48108 1 H

CLOSE OUTPUT OPEN OUTPUT T C 86 CS FROM PLC CS FROM PLC B A 86 A M TOC PHONE: (734) 665-6000 FAX: 213-3003 43-T 43-T 43-M A 43-T 50/51 120V AC CONTROL POWER FROM RELAY CONTROL TRANSFER LOGIC

E A 86 LS BB 86 TC B R G Y M 86 CLOSED OPENED LOCKOUT A 1 1 1 Y 86 LS PS BB PS

N CAPACITOR TRIP 43-TA 52A

51 52B TO PLC 86 D

FEEDER BREAKER PARTIAL WIRING DIAGRAM BY (NOT ALL 52 BREAKER DEVICES ARE SHOWN.) (TYP. OF 6) SHANK, JASON -

C DESCRIPTION DATE MARK

B ELECTRICAL WATER RECLAMATION PLANT CITY OF KALAMAZOO, MICHIGAN ELECTRICAL UPGRADES SWITCHGEAR ONE-LINE PROPOSED WORK

A Project No.: 200-19743-19002

\TT.LOCAL\IER ROJECTS\ANN ARBOR\IER\19743\200-19743-19002\CAD\SHEETFILES\E-009_BREAKER WIR DIA_II.DWG Designed By: GCJ - Drawn By: JLS Checked By: WAP/MSJ E-009 OF 16 Copyright: Tetra Tech 9/15/2020 10:41:14 AM Bar Measures 1 inch 1 2 3 4 5 6 7

TO MULTIPOINT RADIO(S) MOUNT ON POLE 9 FEET ABOVE GRADE CONTRACTOR SHALL PROGRAM, AND DISPLAY ON PANELVIEW PLUS 1500 UP TO 30 PARAMETERS FOR EACH SR-850, AND PQM-IIA. (TYP.) FURNISH EACH WITH MULTINET-FE SERIAL TO ETHERNET MODULE. RADIO PANEL NO.1

5.8 GHZ 710 AVIS DRIVE

RADIO www.tetratech.com OUTDOOR 15 KV SWITCHGEAR

F 1783-BMS10CGA WITH 1783-SPF1GSX. ANN ARBOR, MI 48108 CAT-5E JUMPER PROSOFT PLX31-EIP-MBTCP SOURCE SOURCE MB-1 NO.1 TIE NO.2 MB-2 FB-1 FB-2 FB-3 FB-4 FB-5 FB-6 BRIDGE FOR MULTILIN RELAYS LC-LC CONNECTORS TVSS SR PQM SR PQM SR SR SR SR SR SR SR 850 II-A 850 II-A 850 850 850 850 850 850 850 50 MICRON DUPLEX MULTIMODE TO UPS FIBER ZIP CORDS. (2) IN 1" CONDUIT.

E-NET POE E-NET STRATIX 5700 SWITCH E-FO PHONE: (734) 665-6000 FAX: 213-3003 CAT-5E CAT-6 PATCH CABLES

E-NET E-NET E-NET E-NET TVSS

L72 E E E E-NET E-NET E-NET E-NET

P/S RACK 0 N N N E-NET E-NET

13-SLOT 2 2 2 E-NET E-NET E-NET E-NET E-NET E-NET 1 KVA ON-LINE RACK T T T APC UPS PM E-FO E-NET E-NET E-NET E-NET KEYPAD E-NET E-NET 1783-BMS20CA. I/O SWITCH I/O SWITCH E E-NET STRATIX 5700 SWITCH STRATIX 5700 SWITCH PM E-NET FIBER PATCH CABLE KEYPAD 1783-BMS20CA. RADIO PANEL NO.1 E-NET E-NET E-FO E-FO E-FO GIGABIT SFP'S. (TYP.) 1.5 KVA 27IIP-T15C21D8S E-FO E-NET PANELVIEW PLUS ON-LINE UPS STRATIX 5700 SWITCH 1500 SERIES 7 LAN SWITCH E-NET PERFORMANCE PLUS MULTIMODE GIGABIT SFP'S. (TYP.) E-FO E-FO E-FO E-FO E-FO FOPP E-FO E-FO E-FO E-FO E-FO E-FO E-FO E-FO MULTIMODE 100 MB SFP'S. FIBER ZIP CORDS ST-LC CONNECTORS.

1783-BMS10CGA WITH SFP - 1783-SFP1GSX. (1GB MULTIMODE) MAIN OUTDOOR 15 KV SWITCHGEAR MVUS NO.1

MOUNT ON EXISTING MOUNT ON EXISTING MOUNT ON EXISTING 130' POLE. MOUNT AT 130' POLE. MOUNT AT 130' POLE. MOUNT AT D ELEV 100' ± ELEV 100' ± ELEV 100' ± 5.8 GHZ INTREPID/RAD MULTI POINT RADIO 5.8 GHZ 5.8 GHZ RADIO AIRMUX 5000I. (TYP. OF 3) RADIO RADIO SEE 5.8 GHZ BILL OF MATERIAL. (TYP.)

NO.6 GREEN ISOLATED AWG GROUND WIRE. (TYP.) NO.6 GREEN ISOLATED AWG GROUND WIRE. (TYP.) NO.6 GREEN ISOLATED AWG GROUND WIRE. (TYP.) EXISTING RADIO BY PANEL AT BASE OF RADIO POLE TVSS TVSS TVSS

FOC/SWITCH POWER AS REQUIRED. FROM EXISTING UPS. TVSS TO UPS

E-NET POE E-NET RAD SWITCH E-FO CAT-5E CAT-6 SHANK, JASON

- TVSS TO UPS E-NET E-NET POE E-NET C CAT-5E CAT-6 E-NET

TVSS TO UPS DESCRIPTION E-NET POE E-NET CAT-5E CAT-6 DATE INSTALL 1-12 PORT BULKHEAD IN EXISTING FOPP. (TYP. EACH END)

FOPP MARK E-FO TO EXISTING FOPP. PROVIDE E-FO E-FO E-FO 20 FT PATCH CABLE ST-LC QUANTITY PART NO. DESCRIPTION 12-STRANDS, ST-ST CONNECTORS. HBS 750 ODU, WITH A SMART BEAMFORMING INTEGRATED ANT WITH EMBEDDED GPS, SUPPORTING MULTI FREQ BANDS AT 5.X EXISTING RADIO CONCENTRATOR PANEL 3 AIRMUX-5000I/BS/F58F/750 M/INT LOCATED IN RADIO BUILDING AT BASE OF POLE GHZ, FACT DEFAULT 5.8 GHZ FCC/IC E-FO

B 2 AIRMUX-IDUH/2ETH/HP IDU-H, 2 X ETHERNET PORTS, 1000 BASET INTERFACE AND 2 X SFP INSTALL EQUIPMENT WITHIN EXISTING PANEL PORTS IN ADMINISTRATION BUILDING SERVER ROOM. 2 AIRMUX-PS-H-AC/ACUS IDU-H AC POWER ADAPTOR (90-240VAC TO 48VDC) FOR IDU-H, US AC PROSOFT CARD MODEL PLX51-DFI-ENI. PLUG PROVIDE POWER SUPPLY AS REQUIRED. 3 CBL-AIRMUX-UTP/100 AIRMUX CAT5E, ODU-IDU CABLE, 100M, ASSEMBLED W/RJ45 CONNECTORS

KIT OF 10 OUTDOOR LIGHTNING PROTECTION UNITS FOR E-FO FOC/SWITCH POWER 10/100/1000BASE-T POE SURGE PROTECTOR (INCLUDING 0.5M RS-232 TO ABB AS REQUIRED. 1 AIRMUX-OUTDOOR-LPU-KIT FOPP CAT5E CABLE AND WALL/POLE MOUNTING KIT) E-FO E-FO CONTROLLER (15 FT SERIAL CABLE) PROVIDE CONNECTORS ELECTRICAL SU-PRO 100 ODU, WITH AN INTEGRATED ANTENNA, SUPPORTING AS REQUIRED. MULTI FREQUENCY BANDS AT 5.X GHZ, FACTORY DEFAULT 5.8 EXISTING PLC PANEL IN ADMINISTRATION BUILDING SERVER ROOM. FROM EXISTING FOPP IN PLC WATER RECLAMATION PLANT 3 AIRMUX-5000/SU-PRO/F58F/100M/EMB E-NET FOC E-FO GHZ FCC NOTES: COMMUNICATION PANEL

CAT-6 PATCH CABLE. CITY OF KALAMAZOO, MICHIGAN PROSOFT 1. PLC HARDWARE SHALL BE ALLEN-BRADLEY CONTROL LOGIX, AS SHOWN. ELECTRICAL UPGRADES SWITCHGEAR 10 FT. IN LENGTH. AIRMUX CAT5E, ODU-IDU CABLE, 50M, ASSEMBLED W/RJ45 4 CBL-AIRMUX-UTP/50 SYSTEM CONFIGURATION CONNECTORS 2. PROVIDE 1756-TBE EXTENDED TERMINAL BLOCK HOUSINGS FOR CONTROL LOGIX I/O. 75 FT. PATCH CABLE ST-LC. PATCH THROUGH MULTIMODE SFP-GIG WITH LC CONNECTOR FOR IDU-HP RAISED FLOOR TO EXISTING PLC COMMUNICATIONS 2 SFP-50 3. PROVIDE 1756-PA-75 POWER SUPPLIES FOR CONTROL LOGIX RACKS. PANEL LOCATED IN CONTROL/SERVER ROOM, NEAR CONTROL/SERVER PANEL. 4. MOUNT PLC HARDWARE WITHIN SWITCHGEAR.

A 5. CONTRACTOR/SWITCHGEAR MANUFACTURER SHALL CONFIGURE THE SETTINGS IN EACH Project No.: 200-19743-19002 5.8 GHZ HIGH SPEED RADIO LINK - BILL OF MATERIAL PROTECTIVE RELAY, AND PLC SHOWN FOR PROTECTION. CONFIGURE THE SETTINGS IN Designed By: GCJ

\TT.LOCAL\IER ROJECTS\ANN ARBOR\IER\19743\200-19743-19002\CAD\SHEETFILES\E-010_SYSTEM CONFIGURATION.DWG THE MAIN-TIE-MAIN BREAKER PROTECTION RELAYS (PER THE COORDINATION STUDY), AND ADMINISTRATION BUILDING SERVER ROOM - THE TWO POWER MONITORS (PM-5000) DOWNLOAD CONFIGURATION FILES, AND EXISTING CONTROL/SERVER PANEL Drawn By: JLS DOCUMENT SETTINGS ON PDF, AND TURN OVER TO OWNER ELECTRONIC COPIES OF FILES. Checked By: WAP/MSJ ALSO ASSUME FOR 30 PARAMETERS TO BE CONFIGURED PER MULTILIN RELAY, POWER MONITOR, AND DISPLAYED AT PV-1500 BY CONTRACTOR/SWITCHGEAR MANUFACTURER.

SYSTEM CONFIGURATION DRAWING E-010 OF 16 Copyright: Tetra Tech 11/9/2020 5:38:02 PM Bar Measures 1 inch 1 2 3 4 5 6 7 NOTES: 1. DIMENSIONS ARE APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY EXISTING, AND PROPOSED 7. CONDUITS TO SWITCHES. ROUTE CONDUITS OVER (CONCRETE ENCASED), AND UP (EXPOSED) DIMENSIONS. TO NEW SWITCHES. SUPPORT CONDUITS AS REQUIRED.

2. COORDINATE EXACT DIMENSIONS WITH EQUIPMENT MANUFACTURER. 8. NEW TRUSSES TO BE PROVIDED. TO SUIT SPACE SHOWN, AND TO MAINTAIN PROPER CLEARANCES FOR CONSUMERS ENERGY TRANSFORMER YARD. 3. CONTRACTOR RESPONSIBLE FOR PROPER SITING TO MEET NEC, AND LOCAL CODE 710 AVIS DRIVE

REQUIREMENTS. www.tetratech.com

F 4. CONDUITS SHALL BE ROUTED FROM FEEDER BREAKERS BELOW GRADE UP SIDE OF MVUS NO.1. ANN ARBOR, MI 48108 DO NOT EXCEED MANUFACTURER CABLE BOND RADIUS REQUIREMENTS.

5. SAW CUT THIS PORTION OF EXISTING PAD TO SUIT NEW CONDUITS SHOWN. POUR BACK TO ORIGINAL CONDITION. DOWEL, AND BOND NEW CONCRETE TO EXISTING CONCRETE PAD.

6. CONDUITS UP SIDE OF MVUS NO.1 TO SWITCHES. (TYP.) CONDUITS SHALL BE PVC-RMC FROM EACH BREAKER TO SWITCHES. (TYP.) PHONE: (734) 665-6000 FAX: 213-3003

MOUNT RADIO ON THIS POST, 9 FEET ABOVE GRADE. ORIENT TO 130' POLE BEHIND ADMINISTRATION BUILDING. SEE SHEET E-003, FOR ADDITIONAL INFORMATION. SECURE CAT-5E CABLING AS REQUIRED INSTALL NEW LANDSCAPING. STONES 24" TO RADIO PANEL. PROVIDE CORD GRIPS AT RADIO PANEL. EXISTING CONCRETE PAD WIDE X 3" DEEP, ENTIRE LENGTH, ALL THE WAY AROUND SWITCHGEAR PAD. TO MATCH MAINTAIN 3 FT. OF CLEARANCE MINIMUM TO EXISTING STONES IN SWITCHGEAR YARD. 86' - 10"± MATCH EXISTING CLEARANCE. THIS SIDE. 4' - 1 1/4"± (TIE) EAST BANK-2 (MAIN) EAST BANK-2 (MAIN) EAST BANK-1 (TIE) EAST BANK-1 ROUTE CONDUITS OVERHEAD. SUPPORT AS REQUIRED. (MAIN) EAST BANK-1 (MAIN) EAST BANK-2 REAR MVUS NO.1 MVUS NO.1 1"C(2 - FIBER ZIP CORDS)

RADIO PANEL NO.1 E 24 23 22 21 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 25 EAST BANK-1

MOUNT RADIO PANEL ON STRUT 1"C(3#12) EAST BANK-2 5' - 6"± SUPPORT RACK. SECURE TO EXISTING CONCRETE PAD. 2'-6" 36"± 36"± 20"± 36"± 33"± 38"± \A1;38"%%P38"± 38"± 38"± 38"± 38"± 38"± 22"± 38"± 38"± 38"± 38"± 38"± \A1;2'-3/4"%%P38"± 38"± 38"± 33"± 36"± 20"± 33"± 33"± 35 1/2"± 13' - 11"± 2 - 5"C(POWER) (TYP. OF 15 OVERHEAD CONDUITS) ROUTE OVERHEAD. TO FB-6 TO FB-5 ROUTE PVC COATED STEEL CONDUITS OVERHEAD TO FB-3

TO FB-2 17'+/- SUPPORT AS REQUIRED. TO 20 FROM FEEDER BREAKERS TO LOAD INTERRUPTER PAD AT NO.25 IS UNEVEN. LEVEL PAD AS 3 - 5"C(3#500 KCMIL,15 KV,1#4/0 OR BUS DUCT) SWITCH LINEUPS EAST BANK-1, EAST BANK-2, AND INSTALL SIX (6) NEMA 4, FRONT REQUIRED TO SUIT NEW SWITCHES. (TYP.) WEST BANK. (TYP. OF 15 CONDUITS) STAINLESS STEEL PULL ROUTE CONDUITS OVERHEAD SUPPORT CONDUITS AS REQUIRED. (TYP.) BOXES THIS SIDE, ABOVE TO NEW SWITCHES. (TYP.) (TIE) WEST BANK GRADE. SIZE AS REQUIRED. TO FB-4 (MAIN) WEST BANK TO FB-1 5' - 3 1/4"±

39 38 37 36 35 34 33 32 31 30 EXISTING 4'X3' COMBO DUCT. WEST BANK 16' - 10 3/4'±

EXISTING 4'X4' MANHOLE 5' - 6"± MAIN WEST BANK D FIELD LOCATE EXISTING DUCT BANK. HAND DIG THIS AREA. EXISTING 2'X2' DUCT. 38"± 38"± 38"± 38"± 22"± 38"± 38"± 38"± 38"± 38"± CAP EMPTY CONDUITS NO LONGER IN USE. (TYP.) BARE 4/0 - BOND TO STEEL ROOF. GROUND NEW, AND EXISTING STEEL ROOF WITH BARE 4/0. 6' - 1/2"± POUR CONCRETE SIDEWALK TO (TYP. OF 4 PLACES EACH ROOF) REAR BY 4' - 9"± CONNECT TO EXISTING SIDEWALK AT MAINTENANCE BUILDING ENTRANCE. BARE 4/0 - TO FENCE BARE 4/0 - TO MVUS NO.1 \A1;4'%%PBARE 4/0 - BOND TO STEEL ROOF. ROOF PAD

EXISTING STEEL ROOF 3' - 9"± FIELD LOCATE EXISTING UTILITIES. HAND DIG THIS IN THIS AREA. (TYP.) x x x

x 2'-3/4"± x x 1'± x x x x x x x x x x x x SET SWITCHGEAR ON 4" THICK HOUSEKEEPING x x x x ADD CONCRETE STEPS AT 1'± 1'± PAD ON TOP OF NEW CONCRETE PAD. 15' - 7 1/2"± 6' - 4"± 13' - 8 1/4"±

x INSTALL NEW LANDSCAPING. STONES 24"

EACH END OF PAD. (TYP.) x ROOF 22'± WIDE X 3" DEEP, ENTIRE LENGTH, ALL THE BARE 4/0 - TO EAST SWITCH LINEUP DEMOLISH EXISTING DUCTBANKS/CONDUITS/WIRES CONTRACTOR TO HAND DIG ANYWHERE WORK WAY AROUND SWITCHGEAR PAD. TO MATCH PROVIDE CHANNEL SEE NOTE TO ALLOW INSTALLATION OF NEW IS BEING DONE INSIDE SUBSTATION FENCE. EXISTING STONES IN SWITCHGEAR YARD. SILLS IF REQUIRED INSTALL NEW GROUND MAT x

NO.7 x DUCTBANKS/CONDUITS/WIRES SHOWN. COORDINATE EXTEND NEW SIDEWALK TO EXISTING 7'-6"± BY SWITCHGEAR WORK IN THIS AREA WITH CONSUMERS ENERGY. C SIDEWALK. APPROXIMATELY 20'± FROM NEW MANUFACTURER. 6 - 5"C(POWER) NEW ROOF COORDINATE EXACT METERING SHANK, JASON PAD TO EXISTING SIDEWALK. EACH END. 8'-8"± 3'± REQUIREMENTS WITH CONSUMERS

- TO 31 FIELD LOCATE, AND TURN CONDUITS UP - EXTEND x

x ENERGY. (TYP. EACH SOURCE) TO 15 12 FT. MIN. (PVC-RMC) SUPPORT AS REQUIRED. (TYP.) DB TO 18 FIELD LOCATE EXISTING UTILITIES. DESCRIPTION BARE 4/0 - TO WEST SWITCH LINEUP. HAND DIG IN THIS AREA. (TYP.) DB DB x 3'± EXISTING (C) DB FB-1 DB MAINTENANCE 5 - 5"C(3#500 KCMIL, 133%, 15 KV RATED, 1#250 KCMIL) DATE BUILDING 1 - 5"C(PULL CORD) SPARE DB DB

x

x

7'-6"± LOCATE MVUS NO.1 ON (J) 3'± MARK

FB-2 DB 4" THICK CONCRETE HOUSE KEEPING PAD. HAND DIG THIS AREA. FIELD x x DB LOCATE EXISTING PHONE LINE FOR 3'± (K) CONSUMERS ENERGY METERING. FB-3 DB DB

x BAREx 4/0 - TO EXISTING FENCE. MVUS EXISTING CONSUMERS (TYP. OF 4 PLACES.) DB NO.1 DB ENERGY SWITCHGEAR YARD. FRONT

x MB-1 3'± x DB 7'-6"±

B ROOF 40'± DB

x PAD 38'±

x FILL THIS AREA WITH 3'± TIE LANDSCAPING SEE NOTE 5 - 5"C(3#500 KCMIL, 133%, 15 KV RATED, 1#250 KCMIL) STONES. TO MATCH DB TYP. OF WEST PUSH WEST SWITCH LINEUP 16" WEST TO NO.7 MVUS NO.1 1 - 5"C(PULL CORD) SPARE

EXISTING STONES. BANK LOAD ACHIEVE 36" FREE SPACE FROM REAR OFx

x ENTIRE LENGTH OF 6 - 5"C(POWER) DB SWITCHES. NEW SWITCHES TO EXISTING WOOD POSTS.

PAD. (40'±) EACH SIDE. MB-2 3'± CONTRACTOR TO FIELD LOCATE DB REAR MVUS NO.1 TO FACILITATE GETTING x TO 38 x THE CONDUITS INTO, AND OUT OF TO 1 ELECTRICAL 7'-6"± CPCO FENCE THE BREAKERS AT MVUS NO.1. WORK COORDINATE WITH SWITCH 3'± (C1) TO 22 FB-4 TO AVOID EXISTING DUCTBANK. LOWER BUS/LANDING LUGS TO MANUFACTURER TO ADJUST DB

x

x SUIT RECONNECTION OF DOOR OPENING TO WATER RECLAMATION PLANT ACCOMMODATE NEW BOX. PROPOSED WORK EXISTING LOAD CONDUCTORS. BACKGROUND PLAN DB CITY OF KALAMAZOO, MICHIGAN ELECTRICAL UPGRADES SWITCHGEAR 3'± (J1)

x FB-5

x GROUND ROD. (TYP.) 5" FLEX EXISTING NEMA 3R/4 HINGED PULL FIELD LOCATE EXISTING DUCTBANK. POUR NEW PAD OVER TOP OF CONCRETE PAD BOX. SIZE AS REQUIRED. DUCTBANK. SUPPORT EXISTING DUCTBANK AS REQUIRED. PROVIDE x

x 3'± (K1) FB-6 A BOND BREAK (INSULATION BOARD, OR CHEMICAL COATING) BETWEEN THE EXISTING DUCT BANK, AND NEW CONCRETE SLAB. EXISTING 7'-6"±

A MANHOLE 2'± x Project No.: 200-19743-19002

NEW POSTS.x CONCRETE ENCASED. TO REMAIN. EXISTING CONSUMERS \TT.LOCAL\IER ROJECTS\ANN ARBOR\IER\19743\200-19743-19002\CAD\SHEETFILES\E-011_BCKGND_PR.DWG 4'-6"± FROM CPCO FENCE. COORDINATE DISCONNECTION, AND Designed By: GCJ

- FIELD LOCATE EXISTING CONDUIT(S)/WIRES. 3'-6"± ENERGY SWITCHGEAR YARD. RELOCATION WITH CONSUMERS EXISTING DUCT. Drawn By: JLS

ENERGY. (TYP. EACH SERVICE.) x x BACKGROUND PLAN WEST SWITCH - LINEUP Checked By: WAP/MSJ PROPOSED WORK 0 2' 4' 8' PARTIAL DETAIL 1'-4"± N SCALE: 1/4"=1'-0" x 1'± 6'± SEE NOTE NO.8 4'± x DIMENSIONS ARE APPROXIMATE. CONTRACTOR SCALE: 1/4" = 1'-0'' NO SCALE TO FIELD MEASURE/FIELD VERIFY PRIOR TO BIDS. E-011 4'± PAD 16'-8"± 1'± SLOPE GRADE TOWARDS PARKING LOT Copyright: Tetra Tech OF 16

x 9/15/2020 11:30:23 AM

x Bar Measures 1 inch 1 2 3 4 5 6 7 710 AVIS DRIVE www.tetratech.com

F ANN ARBOR, MI 48108

DEMOLISH EXISTING CONDUITS ON BACK PHONE: (734) 665-6000 FAX: 213-3003 SIDE OF SWITCHGEAR, NEAR PAD. (TYP.)

RE-CIRCUIT THESE LIGHTS AND MVUS NO.1 CONNECT TO NEW 120V CIRCUIT BREAKER AT MVUS NO.1. 1"C(3#12) 1"C(6#12) E MVUS NO.1

RE-POWER THE EXISTING , OUTLET AND FLOOD LIGHT TO NEW MVUS NO.1.

D BY

C SHANK, JASON - DESCRIPTION DATE MARK

RE-CIRCUIT TO NEW CIRCUIT MVUS NO.1 BREAKER AT NEW MVUS NO.1. 1"C(3#12)

B ELECTRICAL WATER RECLAMATION PLANT CITY OF KALAMAZOO, MICHIGAN ELECTRICAL UPGRADES SWITCHGEAR DEMOLITION, PROPOSED WORK

A Project No.: 200-19743-19002

\TT.LOCAL\IER ROJECTS\ANN ARBOR\IER\19743\200-19743-19002\CAD\SHEETFILES\E-012_DEMO PICS.DWG Designed By: GCJ - Drawn By: JLS Checked By: WAP/MSJ SITE PHOTOS - DEMOLITION, PROPOSED WORK NO SCALE E-012 OF 16 Copyright: Tetra Tech 9/15/2020 11:39:57 AM Bar Measures 1 inch 1 2 3 4 5 6 7 710 AVIS DRIVE www.tetratech.com

F ANN ARBOR, MI 48108

LITHONIA LED STRIP LIGHT - 120V AC, NEMA 4 RATED IN-LINE FUSING, ASYMETRIC LITHONIA - VAP LED, 114 A - WATTS, WET LOCATION, WITH SURFACE MOUNT BRACKETS, COVER, AND GUARD AS REQUIRED. PHONE: (734) 665-6000 FAX: 213-3003

E 22'± EDGE OF ROOF. CONTINUOUS 2 X 6 FASCIA. GABLE END TRUSS WITH METAL SIDING. (TYP.) NEMA 4 WEATHERPROOF SWITCH. MOUNT ON WOOD POST/COLUMN. 1'± 1'±

1'± 3'± 1'± 7'-6"± 7'-6"±

4'± MVUS NO.1 120V AC A A BREAKER.

1"C(3#10) RIDGE 4'±

D 7'-6"± 7'-6"± 6" X 8" POST. (TYP.) 4'± A A BY

24"Ø CONCRETE

4'± FOOTING. (TYP.) 40'± 7'-6"± 7'-6"± MOUNT ON TREATED BOARD. 4'± A A

SHANK, JASON 2" X 12" BEAM. -

4'± (TYP. OF 2 EACH SIDE)

C 7'-6"± 7'-6"± DESCRIPTION 4'± DATE

CONCRETE SLAB A A 4'± \A1;40'%%P MARK 7'-6"± 7'-6"± 3'± \A1;4'%%P

1'± 1'± B \A1;7'-6"%%P PRE-FABRICATED TRUSSES AT 4' O.C. UNLESS NOTED OTHERWISE

2 X 4 HORIZONTAL, AND VERTICAL DIAGONAL BRACING. (TYP. 3 LOCATIONS.)

PLAN VIEW - STRUCTURAL PLAN VIEW - LIGHTING 0 2' 4' 8'

NEW ROOF (OVER MVUS NO.1) NEW ROOF (OVER MVUS NO.1) WATER RECLAMATION PLANT SCALE: 1/4"=1'-0" N SCALE: 1/4"=1'-0"

SCALE: 1/4" = 1'-0'' CITY OF KALAMAZOO, MICHIGAN

SEE SHEET E-014 FOR MATERIALS, AND CONSTRUCTION ELECTRICAL UPGRADES SWITCHGEAR PROPOSED ROOF PLAN REQUIREMENTS. MATCH ROOF CONSTRUCTION METHODS FOR EXISTING ROOF.

A Project No.: 200-19743-19002

\TT.LOCAL\IER ROJECTS\ANN ARBOR\IER\19743\200-19743-19002\CAD\SHEETFILES\E-013_ENCLOSURE_PR_PLAN.DWG Designed By: GCJ - Drawn By: JLS EXISTING DRAWING FROM PREVIOUS PROJECT. Checked By: WAP/MSJ PROPOSED WORK SHOWN BOLD, CROSSHATCHED, AND/OR CIRCLED. E-013 OF 16 Copyright: Tetra Tech 9/15/2020 11:45:25 AM Bar Measures 1 inch 1 2 3 4 5 6 7

FOUNDATION NOTES 710 AVIS DRIVE

1. FOUNDATIONS ARE DESIGNED BASED ON SOIL BEARING OF 1500 PSF. IF SOIL OF THIS www.tetratech.com

CAPACITY IS NOT FOUND AT THE ELEVATION NOTED, ENLARGE OR LOWER FOOTINGS. ANN ARBOR, MI 48108 F 2. HAND EXCAVATION IS REQUIRED FOR ALL FOUNDATIONS AND CARE MUST BE TAKEN NEAR EXISTING CONCRETE SLAB AND BURIED ELECTRICAL CONDUITS. COORDINATE WITH OWNER.

3. MINIMIZE UNDERMINING OF EXISTING CONCRETE SLAB DURING EXCAVATION.

4. BACKFILL AROUND BELOW GRADE PORTIONS OF POST FOUNDATIONS WITH A CEMENT/SAND MIXTURE. PHONE: (734) 665-6000 FAX: 213-3003

ROOF SYSTEM

1. 26 GAUGE MINIMUM PAINTED GALVALUME ROOFING AND TRIM TO HAVE 30 YEAR PAINT AND 25 YEAR CORROSION WARRANTY. COLOR PER OWNER. CONTINUOUS 2. PANEL WIDTH OF 36 INCH COVERAGE, EXPOSED FASTENERS, AND 1 1/2 INCH MAXIMUM RIBBED TREATED 2 X 12 FOR TEXTURE. MOUNTING LIGHTS. CONTINUOUS 3. TRIM COMPONENTS TO INCLUDE VENTED RIDGE CAP, GABLE TRIM, EAVE TRIM, J-CHANNEL, AND TREATED 2 X 12 FOR MOUNTING LIGHTS. E CLOSURES WITH BUTYL SEALANT.

4. FASTENERS SHALL BE THE EXPOSED FASTENER TYPE WITH SEALED WASHERS ON THE EXTERIOR SIDE OF THE COVERING TO WATERPROOF THE FASTENERS PENETRATION. FASTENERS TO MEET TO UPLIFT LOADING AND MANUFACTURER'S RECOMMENDATION.

CEILING SYSTEM 10'-3" 1. 29 GAUGE MINIMUM PAINTED GALVALUME ROOFING AND TRIM TO HAVE 30 YEAR PAINT AND 25 YEAR CORROSION WARRANTY. COLOR PER OWNER.

2. PANEL WIDTH OF 36 INCH COVERAGE, EXPOSED FASTENERS, AND 5/8 INCH MAXIMUM RIBBED TEXTURE.

3. TRIM COMPONENTS TO INCLUDE VENTED RIDGE CAP, GABLE TRIM, EAVE TRIM, J-CHANNEL, AND CLOSURES WITH BUTYL SEALANT. NEW CONCRETE PAD FOR MVUS NO.1. 4. FASTENERS SHALL BE THE EXPOSED FASTENER TYPE WITH SEALED WASHERS ON THE EXTERIOR SIDE OF THE COVERING TO WATERPROOF THE FASTENERS PENETRATION. D FASTENERS TO MEET TO UPLIFT LOADING AND MANUFACTURER'S RECOMMENDATION.

MISCELLANEOUS COMPONENTS

1. COMPONENTS SHALL BE COMPATIBLE WITH THE ROOF CEILING PANEL FURNISHED. BY 2. COMPONENTS TO INCLUDE VENTED SOFFIT, FLAT STOCK, J CHANNEL SHANK, JASON -

C NEW ROOF, POSTS, AND FOUNDATIONS. (TYP.) DESCRIPTION

22'-0" DATE

DESIGN CRITERIA: MATERIAL: MARK

PERFORMANCE SPEC: TRUSSES SHALL BE DESIGNED PER TRUSS PLATE INSTITUTE SPECIFICATIONS. STRUCTURAL LUMBER SHALL BE DETAILED, FABRICATED AND ERECTED IN ACCORDANCE WITH THE LATEST EDITIONS OF THE TIMBER CONSTRUCTION MANUAL BY THE AMERICAN INSTITUTE OF TIMBER ALL NEW TRUSSES, POSTS, BEAMS, BRACING AND FOUNDATION SHALL BE DESIGNED BY A TRUSS MFR IS RESPONSIBLE FOR TEMPORARY AND PERMANENT BRACING DESIGN. CONSTRUCTION (AITC) AND THE NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION BY PROFESSIONAL ENGINEER, LICENSED IN THE STATE OF MICHIGAN SIGNED AND SEALED DRAWINGS THE AMERICAN FOREST & PAPER ASSOCIATION (ANSI/ NDS). AND CALCULATIONS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL. TRUSS PLATES SHALL BE GALVANIZED STEEL AND SHALL BE APPLIED TO BOTH FACES OF THE MEMBERS BEING CONNECTED. BOLTS, LAG SCREWS, NAILS AND OTHER WOOD FASTENINGS, UNLESS OTHERWISE NOTED, SHALL BE 1. ICC INTERNATIONAL BUILDING CODE, 2015 EDITION MINIMUM LUMBER SIZE FOR TOP AND BOTTOM CHORD MEMBERS SHALL BE 2”X 6” (NOMINAL). WEB HOT DIP GALVANIZED AND CONFORM TO THE LATEST EDITION OF THE NATIONAL DESIGN 2. STATE BUILDING CODE: 2015 MICHIGAN BUILDING CODE MEMBER SIZE AND CONFIGURATION SHALL BE THE OPTION OF THE FABRICATOR. SPECIFICATION FOR WOOD CONSTRUCTION. STANDARD CUT WASHERS SHALL BE USED BETWEEN B 3. ASCE/SEI 7-10 - MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES THE WOOD AND BOLT HEAD AND THE WOOD AND NUT. PRESERVATIVES FOR PRESSURE TREATED (P.T.) WOOD SHALL BE WATERBORNE AND COPPER OR LOADING: BORATE-BASED. AMMONIA SHALL NOT BE USED AS A CHEMICAL CARRIER IN THE TREATMENT WOOD CONSTRUCTION CONNECTORS PLATES SHALL BE AS MANUFACTURED BY SIMPSON PROCESS. WHERE PRESERVATIVE RETENTION LEVELS EXCEED 0.31 FOR CA, OR 0.60 FOR CCA/ACQ, STRONG-TIE COMPANY, INC. OR APPROVED EQUIVALENT. TOP CHORD DEAD LOAD ROOFING 10 PSF STAINLESS STEEL CONNECTORS AND HARDWARE ARE REQUIRED. GENERALLY, CONNECTOR TOP CHORD LIVE 20 PSF MATERIAL SHALL BE AS FOLLOWS (MINIMUM): CAST IN PLACE STRUCTURAL CONCRETE F'C = 4500 PSI BOTTOM CHORD DEAD LOAD 5PSF P.T. WOOD MEMBER CONDITION EMBEDDED IN GROUND (UC4B/C): GROUND CONTACT (UC4A): REINFORCING BARS: ASTM A615, GRADE 60 BOTTOM CHORD LIVE LOAD 10 PSF NON -CONCURRENT WITH TOP CHORD LIVE LOAD ABOVE GROUND EXTERIOR (UC3B): INTERIOR DRY (UC1/UC2):

METAL CONNECTOR MATERIAL (U.N.O.) FOUNDATIONS: MVUS NO.1 ROOF SNOW LOAD: STAINLESS STEEL FOUNDATIONS SHALL BE DESIGNED BASED ON SOIL BEARING OF 1500 PSF. IF SOIL OF THIS CAPACITY

HOT-DIP GALVANIZED (HDG) OR G185 GALVANIZED IS NOT FOUND AT THE ELEVATION NOTED, ENLARGE OR LOWER FOOTINGS. WATER RECLAMATION PLANT GROUND SNOW LOAD, PG = 35 PSF HOT-DIP GALVANIZED (HDG) OR G185 GALVANIZED CITY OF KALAMAZOO, MICHIGAN

SNOW EXPOSURE FACTOR, CE = 1.0 ZINC-COATED G90 AT SAWN LUMBER IN CONTACT WITH THE GROUND, MASONRY OR CONCRETE, OR EXPOSED TO ELECTRICAL UPGRADES SWITCHGEAR PROPOSED ROOF PLAN SNOW LOAD IMPORTANCE FACTOR, I = .8 MOISTURE SHALL BE SOUTHERN YELLOW PINE PRESSURE TREATED IN ACCORDANCE WITH THERMAL FACTOR, CT = 1.00 PLYWOOD AND PERFORMANCE RATED PANELS (ORIENTED STRAND BOARD) SHALL BE DETAILED, AMERICAN WOOD PROTECTION ASSOCIATION (AWPA "STANDARD U1") FOR THE APPROPRIATE USE FABRICATED AND ERECTED IN ACCORDANCE WITH THE LATEST CRITERIA ESTABLISHED BY THE CATEGORY (UC) BASED ON WOOD MEMBER EXPOSURE & LOCATION. WIND LOAD: AMERICAN PLYWOOD ASSOCIATION (APA) INCLUDING THEIR LATEST EDITION OF THE PLYWOOD RISK CATEGORY = I DESIGN SPECIFICATION (AND ITS SUPPLEMENTS). ULTIMATE DESIGN WIND SPEED, VULT = 105 MPH A WIND EXPOSURE CATEGORY = C Project No.: 200-19743-19002

\TT.LOCAL\IER ROJECTS\ANN ARBOR\IER\19743\200-19743-19002\CAD\SHEETFILES\E-014_ENCLOSURE_SECTION.DWG DIRECTIONALITY FACTOR, KD = 0.85 Designed By: GCJ - TOPOGRAPHY = 1.0 Drawn By: JLS Checked By: WAP/MSJ SEISMIC DESIGN DATA: RISK CATEGORY = I 0 1' 2' 4' IMPORTANCE FACTOR = 1.0 SECTIONAL VIEW - STRUCTURAL SITE CLASS = 'D' STIFF SOIL SCALE: 1/2"=1'-0" N E-014 SCALE: 1/2" = 1'-0'' OF 16 Copyright: Tetra Tech 9/15/2020 11:48:18 AM Bar Measures 1 inch 1 2 3 4 5 6 7 710 AVIS DRIVE www.tetratech.com

F ANN ARBOR, MI 48108 PHONE: (734) 665-6000 FAX: 213-3003

E

D BY

C SHANK, JASON - DESCRIPTION

FOR NEW CONDUITS, FILL WITH DUCT SEAL - EACH END. FIRE DATE WRAP CABLES AT EACH END WITHIN BREAKER COMPARTMENTS, AND WITHIN SWITCH COMPARTMENTS. (TYP.) SEE NOTES FOR WORK REQUIRED. (TYP. OF TWO (2) SERVICE ENTRANCE RACKS.) MARK

NOTES: CONTRACTOR SHALL OBTAIN THE SERVICES OF THE HYDAKER-WHEATLAKE CO.(AUTHORIZED CONSUMERS ENERGY SUBSTATION CONTRACTOR) TO PERFORM THE FOLLOWING AS PART OF THIS CONTRACT:

B 1. FURNISH AND INSTALL MATERIALS INCLUDING STEEL RACKS, STEEL RACK SUPPORTS, PLATES, BASES, BOLTS, NUTS, WASHERS, COPPER BUS(2000A), INSULATORS, STANDOFFS, TERMINATIONS, COPPER CONDUCTORS TO CONSUMERS ENERGY SWITCHES, ETC TO MATCH THE TWO EXISTING CONDUIT SUPPORT AND CONNECTION RACKS.

2. CONSTRUCTION FOR EACH OF THE TWO RACKS SHALL MATCH EXISTING CONSTRUCTION AND SHALL BE COORDINATED WITH CONSUMERS ENERGY. DETAILS ELECTRICAL 3. REMOVE EXISTING FENCING AS REQUIRED TO SUIT NEW CONSTRUCTION. REINSTALL EXISTING FENCE BACK TO ORIGINAL WATER RECLAMATION PLANT CONDITION FOLLOWING COMPLETION OF THE WORK. CITY OF KALAMAZOO, MICHIGAN 4. GROUND THE RACKS AS REQUIRED TO THE EXISTING GROUND ELECTRICAL UPGRADES SWITCHGEAR MAT. BOND TO NEW MAT AROUND NEW SWITCHGEAR.

5. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO SUPPORT THE NEW CONDUITS AND WIRES SHOWN FOR EACH NEW SERVICE.

6. REFER TO THE ATTACHED PICTURES FOR INFORMATION ON THE EXISTING RISER RACK CONSTRUCTION. A Project No.: 200-19743-19002

\TT.LOCAL\IER ROJECTS\ANN ARBOR\IER\19743\200-19743-19002\CAD\SHEETFILES\E-015_E-DETAILS.DWG Designed By: GCJ - NOTE: Drawn By: JLS TRANSFORMER CONDUITS/BUS SUPPORT RISER RACK EXISTING PHOTOS ARE SHOWN OF THE TWO EXISTING RISER RACKS. (TYP. OF 2 SERVICE ENTRANCE RACKS.) FOR INFORMATION SEE NOTES THIS SHEET FOR WORK REQUIRED. Checked By: WAP/MSJ NO SCALE E-015 OF 16 Copyright: Tetra Tech 9/15/2020 11:51:36 AM Bar Measures 1 inch 1 2 3 4 5 6 7 710 AVIS DRIVE www.tetratech.com

F ANN ARBOR, MI 48108 PVC WATERSTOP. (TYP.) ALL SIDES, APPLY EPOXY BONDING AGENT BETWEEN NEW, A AND HARDENED CONCRETE. WALL OPENING = DUCT DIM. + 2" (TYP. EACH DIRECTION.) INSIDE WALL FACE. FIBERGLASS REINFORCMENT, PVC, OR PVC COATED RGS CONDUITS. FIBER OR ASBESTOS CEMENT DUCTS. PHONE: (734) 665-6000 FAX: 213-3003 2'-0" MIN. FINISH GRADE.

#4/0 BARE 7-STRAND COPPER CABLE. (TYP.) PROVIDE STANDARD END BELL FOR EACH DUCT. 3/4" X 20' - 0" MIN. CONNECTION TO BE MADE WITH COPPER CLAD HEAVY DUTY EXOTHERMIC STEEL RODS. PROCESS OR ENGINEERS APPROVED COMPRESSION TYPE CONNECTORS. REBAR TIE. (TYP.)

E STANDARD CONSTRUCTION JOINT. CONCRETE, OR MASONRY. CONCRETE, OR MASONRY. 24" 'Z' TYPE FITTING. 18" 36" MIN. DEPTH BELOW GRADE. STAIN CONCRETE DUCTBANKS RED COLOR. 3" SEPARATION LEAD, OR MALLEABLE IRON EQUIPMENT GROUND #4/0 BARE GROUND WIRE. EXPANSION CASE. (TYP.) BUS LUGS. WOOD THE BUILT-UP OR MONOLITHIC METHOD OF INSTALLING DUCTS IN DOUBLE NUT GENERATOR CONCRETE AS OUTLINED BY DUCT MFR'S SHALL BE USED IN UNSTABLE PIPE CLAMPS GALVANIZED BOLT, SOIL. ELECTRICAL CONDUITS, AND WASHER, AND NUT. DUCTS ENCASED IN CONCRETE SHALL STRUT *

18" (IF LOADING REQ'S.) BE REINFORCED WITH #4 REINFORCING BARS, AND #3 REBAR TIES ON 18" GALVANIZED, OR BEAM ATTACHMENT. (TYP.) 3" SEPARATION CTRS. LOCATED AS SHOWN ON THE PLATED LAG SCREWS. UNDERGROUND DUCT SECTIONS. NOTE: * = STRUT SHALL HAVE A MIN. THICKNESS OF .105 INCH, OR 12 GA. ALL WIRE #4/0 BARE INTERMEDIATE SPACER. WOOD 7-STRAND COPPER. (TYP.) 3" STRUT * D BASE SPACER - NO. REQ'D. AND 5000 PSI STRENGTH CONCRETE PIPE CLAMPS TYPICAL ALL DUCT BANKS SECTION A LOCATION PER CONDUIT MFR'S RECOMMENDATIONS. BEAM CLAMP

GROUND MAT THREADED ROD

DUCT DETAILS BEAM CLAMP BY NO SCALE NO SCALE BUILDING STEEL

STRUT * BEAM CLAMPS BUILDING STEEL BEAM CLAMP

1/2" HEX NUT. 1/2" SQ. WASHER. (TYP.)

PIPE CLAMP BUILDING 17'± STAIN CONCRETE PAD RED. STEEL 10" (TYP.) 1/2" THREADED ROD. (TYP.)

C TYPE "WSK" OR "WDP" COMPRESSION NEOPRENE GROMMET SEAL FITTING WATERTIGHT EYD TYPE SEAL, STRUT *

SHANK, JASON WITH 316 STAINLESS STEEL SLEEVE. SEALING HUB. SEALING BUSHING TYPE "CSBI". AND DRAIN. PIPE CLAMPS

- STRUT *

SEALER. (EXT. ONLY.) DESCRIPTION OPENING LOCATION, SEAL VERTICALLY RACKED HORIZONTAL RACKED SEALING BUSHING TYPE. "CSMI". AND SIZE COORDINATE AND VERTICAL RUNS SUSPENDED RUN WITH SWITCHGEAR CORE OUT OPENING IN EXISTING WALL, DATE NO SCALE NO SCALE MANUFACTURER. AND INSERT COMPRESSION SEALS. ADD 3#5 BOTT. AT OPENING. 38'± MARK

CONDUIT BODY TYPE FITTING. FOR WIRE SIZE SMALLER THAN CONDUIT CONDUIT NO.4 ONLY.

PULL BOX. (SEE SPECS.) FOR B 5000 PSI STRENGTH CONCRETE. (TYP.) PLAN WIRE SIZE NO.4, AND LARGER. #4 AT 12" EW, BOTT. SCALE: 1/4" = 1'-0" PROVIDE DRAIN. FIELD VERIFY EXACT DIMENSIONS. #4 AT 12" EW, MIDDLE. 3'-0" MIN. SUPPORT FRAME. #12 GA. SEALING BUSHING OR .105 INCH MIN. THICK. TYPE. "CSMC".

#4 AT 18" EW, TOP. 12" SEALER. (EXT. ONLY.) BUILDING WALL. FIN. GR. DETAILS

#4 AT 12" EW, EF. ELECTRICAL EXISTING CONSTRUCTION NEW CONSTRUCTION PROVIDE UNION HERE

WHEN NECESSARY. WATER RECLAMATION PLANT 2' - 4" CITY OF KALAMAZOO, MICHIGAN

BELOW GRADE CONDUIT ENTRANCE DETAIL ELECTRICAL UPGRADES SWITCHGEAR 12" 3#4 (TYP.) NO SCALE NOTE: ALL CONDUIT ENTRANCES SHALL HAVE SEAL, AND DRAIN. 2' - 0" 7" (TYP.)

SECTION SCALE: 1/4" = 1'-0" A SWITCHGEAR PAD - ADDITION Project No.: 200-19743-19002

\TT.LOCAL\IER ROJECTS\ANN ARBOR\IER\19743\200-19743-19002\CAD\SHEETFILES\E-016_E-DETAILS.DWG Designed By: GCJ - Drawn By: JLS Checked By: WAP/MSJ E-016 OF 16 Copyright: Tetra Tech 9/15/2020 11:56:36 AM Bar Measures 1 inch