50LC Single Package Rooftop Cooling Only with Puronr (R---410A) Refrigerant Sizes: 04, 05, 06

Installation Instructions

NOTE: Read the entire instruction manual before starting the installation TABLE OF CONTENTS SAFETY CONSIDERATIONS...... 2 All Units...... 19 Convenience Outlets...... 20 INSTALLATION...... 6 HACR...... 21 Jobsite Survey...... 6 Factory--Option Thru--Base Connections...... 21 Step 1 --Plan for Unit Location...... 6 Units without Thru--Base Connections...... 22 Roof Mount...... 6 Field Control Wiring...... 22 Step 2 -- Plan for Sequence of Unit Installation...... 6 Thermostat...... 22 Curb--Mount Installation...... 6 Unit without Thru--Base Connection Kit...... 22 Pad--Mount Installation...... 7 Heat Anticipator Settings...... 23 Frame--Mount Installation...... 7 Electric Heaters...... 23 Step 3 --Inspect Unit...... 7 Single Point Boxes & Supplementary Fuses.... 24 Step 4 -- Provide Unit Support...... 7 Single Point Boxes without Fuses...... 24 Roof Curb Mount...... 7 Low--Voltage Control Connections...... 24 Slab Mount (Horizontal Units Only)...... 7 Humidi--MiZerR Control Connections...... 25 Alternate Unit Support (In Lieu of Curb or Slab Mount)...... 7 Humidi--MiZer -- Space RH Controller...... 25 Step 5 --Field Fabricate Ductwork...... 9 EconoMi$er X (Factory Option)...... 27 For Units with Accessory Electric Heaters...... 9 ComfortLINK (Factory Option)...... 27 Step 6 --Rig and Place Unit...... 9 RTU Open Control System...... 29 Positioning on Curb...... 10 Supply Air Temperature (SAT) Sensor...... 32 Step 7 -- Convert to Horizontal and Connect Outdoor Air Temperature (OAT) Sensor...... 33 Ductwork...... 11 EconoMi$er2...... 33 Step 8 --Install Outside Air Hood...... 11 Field Connections...... 33 Economizer Hood Package Removal and Setup — Space Temperature (SPT) Sensors...... 33 Factory Option...... 11 Indoor Air Quality (CO2)Sensor...... 34 Economizer Hood Hood...... 12 Outdoor Air Quality Sensor...... 35 Step 9 -- Units with Hinged Panels Only...... 12 Space Relative Humidity Sensor or ... 35 Step 10 -- Install External Condensate Trap Smoke Detector/Fire Shutdown (FSD)...... 36 and Line...... 13 Connecting Discrete Inputs...... 36 Step 11 --Make Electrical Connections...... 13 Communication Wiring --Protocols...... 37 Field Power Supply...... 13 General...... 37 Units with Factory--Installed Non--Fused Disconnect or HACR...... 18 Local Access...... 38 Units without Factory--Installed Non--Fused RTU Open Troubleshooting...... 38 Disconnect or HACR...... 19 Outdoor Air Enthalpy Control...... 39 Differential Enthalpy Control...... 39 ! WARNING Return Air Enthalpy Sensor...... 39 ELECTRICAL SHOCK HAZARD Smoke Detectors...... 40 Failure to follow this warning could cause personal Step 12 -- Adjust Factory--Installed Options...... 47 injury or death. Step 13 --Install Accessories...... 47 Before performing service or maintenance operations on unit, turn off main power to unit and install APPENDIX -- VFD Operation with Remote Keypad.. 48 lock(s) and lockout tag(s). Ensure electrical service to rooftop unit agrees with voltage and amperage listed START--UP CHECKLIST...... 58 on the unit rating plate. Unit may have more than one power switch. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical ! WARNING shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, UNIT OPERATION AND SAFETY HAZARD service agency, or your distributor or branch for Failure to follow this warning could cause personal information or assistance. The qualified installer or injury, death and/or equipment damage. 50LC agency must use factory--authorized kits or accessories Puronr (R--410A) refrigerant systems operate at when modifying this product. Refer to the individual higher pressures than standard R--22 systems. Do not instructions packaged with the kits or accessories when use R--22 service equipment or components on Puron installing. refrigerant equipment. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to ! WARNING the unit. Consult local building codes and appropriate PERSONAL INJURY AND ENVIRONMENTAL national electrical codes (in USA, ANSI/NFPA 70, HAZARD National Electrical Code (NEC); in Canada, CSA C22.1) Failure to follow this warning could cause personal for special requirements. injury or death. It is important to recognize safety information. This is the Relieve pressure and recover all refrigerant before safety--alert symbol . When you see this symbol on the system repair or final unit disposal. unit and in instructions or manuals, be alert to the Wear safety glasses and gloves when handling potential for personal injury. refrigerants. Keep torches and other ignition sources away from refrigerants and oils. Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or ! CAUTION death. WARNING signifies hazards which could result in CUT HAZARD personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal Failure to follow this caution may result in personal injury or product and property damage. NOTE is used to injury. highlight suggestions which will result in enhanced Sheet metal parts may have sharp edges or burrs. Use installation, reliability, or operation. care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing air conditioning equipment.

2 Position: 12345678910 11 12 13 14 15 16 17 18 Example: 50LCD006A1A5A0A0A 0

Unit Heat Type Packaging 50 - Electric Cooling/Heating 0 = Standard Packaged Rooftop 1 = LTL

Model Series - WeatherExpertTM Electrical Options LC - Ultra High Efficiency A = None B = HACR Circuit Breaker C = Non-Fused Disconnect Heat Options D = Thru-The-Base Connections 0 = Standard, No Electric Heat E = HACR Circuit Breaker D = Low Electric Heat and Thru-The Base Connections E = Medium Electric Heat F = Non-Fused Disconnect and F = High Electric Heat Thru-The-Base Connections

Refrig. Systems Options Service Options 0 = Two stage cooling capacity 0 = None A = Two stage cooling capacity 1 = Unpowered Convenience Outlet with Humidi-MiZer System 2 = Powered Convenience Outlet

3 = Hinged Panels 50LC Cooling Tons 4 = Hinged Panels and 04 - 3 ton Unpowered Convenience Outlet 05 - 4 ton 5 = Hinged Panels and 06 - 5 ton Powered Convenience Outlet

Sensor Options Air Intake / Exhaust Options A = None A = None B = RA Smoke Detector B = Temperature Economizer with Barometric Relief C = SA Smoke Detector E = Enthalpy Economizer with Barometric Relief D = RA + SA Smoke Detector N = Ultra Low Leak Temperature Economizer

E = CO2 with Barometric Relief

F = RA Smoke Detector and CO2 R = Ultra Low Leak Enthalpy Economizer with

G = SA Smoke Detector and CO2 Barometric Relief

H = RA + SA Smoke Detector and CO2 Base Unit Controls Indoor Options 0 = Base Electromechanical Controls 0 = Standard Electrical (Direct) Drive x13 ECM Motor 1 = RTU Open Multi-Protocol Controller 2 = Medium Static Belt Drive with VFD controller 2 = ComfortLink Controls* 3 = High Static Belt Drive with VFD controller Design Revision Coil Options: Fin/Tube (Condenser- Evaporator - Hail Guard) A = Factory Design Revision A = Al/Cu - Al/Cu B = Precoat Al/Cu - Al/Cu Voltage C = E-coat Al/Cu - Al/Cu 1 = 575/3/60 D = E-coat Al/Cu - E-coat Al/Cu 5 = 208-230/3/60 E = Cu/Cu - Al/Cu 6 = 460/3/60 F = Cu/Cu - Cu/Cu M = Al/Cu -Al/Cu — Louvered Hail Guard N = Precoat Al/Cu - Al/Cu — Louvered Hail Guard * Not available for units equipped with Humidi-MiZer P = E-coat Al/Cu - Al/Cu — Louvered Hail Guard Q = E-coat Al/Cu - E-coat Al/Cu — Louvered Hail Guard R = Cu/Cu - Al/Cu — Louvered Hail Guard S = Cu/Cu - Cu/Cu — Louvered Hail Guard

C13385 Fig. 1 -- 50LC 04--06 Model Number Nomenclature (Example)

3 50LC

Vertical Connections / Economizer

Horizontal Connections / Economizer

C12098 Fig. 2 -- Dimensional Drawing 4 50LC C12099 Fig. 2 -- Unit Dimensional Drawing (cont.)

C D

B A

C08337 LOCATION DIMENSION CONDITION 48---in (1219 mm) Unit disconnect is mounted on panel 18---in (457 mm) No disconnect, convenience outlet option A 18---in (457) mm Recommended service clearance 12---in (305 mm) Minimum clearance 40---in (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall) B 36---in (914 mm) Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass) Special Check sources of flue products within 10---ft of unit fresh air intake hood 36---in (914 mm) Side condensate drain is used C 18---in (457 mm) Minimum clearance 48---in (1219 mm) No flue discharge accessory installed, surface is combustible material 42---in (1067 mm) Surface behind servicer is grounded (e.g., metal, masonry wall, another unit) D 36---in (914 mm) Surface behind servicer is electrically non---conductive (e.g., wood, fiberglass) Special Check for adjacent units or building fresh air intakes within 10---ft (3 m) of this unit’s flue outlet NOTE: Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application planning overhead obstruction or for vertical clearances. Fig. 3 -- Service Clearance Dimensional Drawing

5 INSTALLATION requirements. Refer to Step 10 — Install External Condensate Trap and Line – for required trap dimensions. Jobsite Survey Roof Mount — Complete the following checks before installation. Check building codes for weight distribution 1. Consult local building codes and the NEC (National requirements. Unit operating weight is shown in Table 1. Electrical Code) (ANSI/NFPA 70) for special installa- Step 2 — Plan for Sequence of Unit Installation tion requirements. 2. Determine unit location (from project plans) or select The support method used for this unit will dictate different unit location. sequences for the steps of unit installation. For example, 3. Check for possible overhead obstructions which may on curb--mounted units, some accessories must be interfere with unit lifting or rigging. installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for Step 1 — Plan for Unit Location installation steps. Select a location for the unit and its support system (curb Curb--mounted Installation — or other) that provides for minimum clearances required for safety (including clearance to combustible surfaces), Install curb unit performance and service access below and around Install field--fabricated ductwork inside curb unit as specified in Fig. 3. Install accessory thru--base service connection package 50LC NOTE: Consider also the effect of adjacent units. (affects curb and unit) (refer to accessory installation instructions for details) Unit may be installed directly on wood flooring or on Class A, B, or C roof--covering material when roof curb is Prepare bottom condensate drain connection to suit used. planned condensate line routing (refer to Step 10 for details) Do not install unit in an indoor location. Do not locate air Rig and place unit inlets near exhaust vents or other sources of contaminated Install outdoor air hood air. Install condensate line trap and piping Although unit is weatherproof, avoid locations that permit Make electrical connections water from higher level runoff and overhangs to fall onto Install other accessories unit. Select a unit mounting system that provides adequate height to allow installation of condensate trap per

Table 1 – Operating Weights

UNITS LB (KG) 50LC---* 04 05 06 Base Unit 458 (208) 545 (247) 550 (249) Economizer Vertical 50 (23) 50 (23) 50 (23) Horizontal 80 (36) 80 (36) 80 (36) H u m i d i --- M i Z e r R System 50 (23) 55 (25) 55 (25) Cu Fins 25 (11) 43 (20) 56 (25) Powered Outlet 35 (16) 35 (16) 35 (16) Curb 14---in/356 mm 115 (52) 115 (52) 115 (52) 24---in/610 mm 197 (89) 197 (89) 197 (89)

6 Pad--mounted Installation — Step 4 — Provide Unit Support Prepare pad and unit supports Roof Curb Mount — Check and tighten the bottom condensate drain Accessory roof curb details and dimensions are shown in connection plug Fig. 4. Assemble and install accessory roof curb in Rig and place unit accordance with instructions shipped with the curb. Convert unit to side duct connection arrangement Install field--fabricated ductwork at unit duct openings Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are shown in Install outdoor air hood Fig. 5. Refer to Accessory Roof Curb Installation Install condensate line trap and piping Instructions for additional information as required. Make electrical connections Install insulation, cant strips, roofing felt, and counter Install other accessories flashing as shown. Ductwork must be attached to curb and Frame--mounted installation — not to the unit. The accessory thru--the--base power and Frame--mounted applications generally follow the gas connection package must be installed before the unit sequence for a curb installation. Adapt as required to is set on the roof curb. suit specific installation plan. If electric and control wiring is to be routed through the Step 3 — Inspect unit basepan, attach the accessory thru--the--base service

connections to the basepan in accordance with the 50LC Inspect unit for transportation damage. File any claim accessory installation instructions. with transportation agency. NOTE: The gasketing of the unit to the roof curb is Confirm before installation of unit that voltage, amperage critical for a watertight seal. Install gasket supplied with and circuit protection requirements listed on unit data the roof curb as shown in Fig. 4. Improperly applied plate agree with power supply provided. gasket can also result in air leaks and poor unit On units with hinged panel option, check to be sure all performance. latches are snug and in closed position. Slab Mount (Horizontal Units Only) — Locate the carton containing the outside air hood parts; Provide a level concrete slab that extends a minimum of 6 see Fig. 9. Do not remove carton until unit has been in. (150 mm) beyond unit cabinet. Install a gravel apron in rigged and located in final position. front of condenser coil air inlet to prevent grass and foliage from obstructing airflow. NOTE: Horizontal units may be installed on a roof curb if required. Alternate Unit Support (InLieuofCurborSlabMount)— A non--combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4--in. x 4--in. (102 mm x 102 mm) pads on each side.

7 B 1-3/4" [44.4] (004-007) SEE NOTE #2 SHEET 5 OF ACCESSORY CONVENIENCE OUTLET WIRING CONNECTOR 48TC400427 CURB ASY, ROOF [1711.3] 5' 7-3/8" 2-3/8" [61] SIZE DRAWING NUMBER REV D FITTING THIS DOCUMENT AND THE INFORMATION CONTAINED THEREIN IS PROPRIETARY TO CARRIER CORPORATION AND SHALL NOT BE USED OR DISCLOSED TO OTHERS, IN WHOLE PART, WITHOUT THE WRITTEN AUTHORIZATION OF CARRIER CORPORATION. - 1/2" [12.7] NPT 1/2" [12.7] NPT CONTROL WIRING - - FITTING 1041738 RETURN AIR 3/4" [19] NPT TOLERANCES ON: POWER WIRING AUTHORIZATION NUMBER TITLE DIMENSIONS ARE IN INCHES 1-3/4" [44.5] ---- DRAFTER CHECKER 1' 4-13/16" [427] INSIDE UNLESS OTHERWISE SPECIFIED ENGINEERING MANUFACTURING 1 DEC 2 DEC 3 DEC ANG PRODUCTION - MMC 06/17/11 - - CERTIFIED DRAWING 1/2" [12.7] NPT - - - - MATERIAL T-005, Y-002 11 3/4"[298.5] WIDE INSULATED DECK PANELS WEIGHT: - PURCH - N/A MMC 50LC ENGINEERING REQUIREMENTS SURFACE FINISH MFG/PURCH MODEL (INTERNAL USE ONLY) NEXT DRAWING SCALE DISTRIBUTION DRAWING RELEASE LEVEL: THIRD ANGLE PROJECTION SUPPLY AIR

[944.6] 3'-1 3/16" SEE VIEW "B" THRU THE CURB ECN NO. 1067898 8 9/16"[217.5] WIDE INSULATED DECK PANEL GAS SERVICE PLATE THRU THE CURB DRILL HOLE 2" [50.8] @ ASSEMBLY (IF REQUIRED) (SEE NOTE #8) - APP'D 1.00" [25.4] - "A" 1-3/4" [44.4] CHK'D E-E BY MMC SCALE 0.250 CRBTMPWR003A01 THRU THE BOTTOM CRBTMPWR001A01 3/4" [19] NPT 1-3/4" [44.5] CONNECTOR PKG. ACC. GAS CONNECTION TYPE GAS FITTING SECTION DATE 04/22/13 ROOFING MATERIAL (FIELD SUPPLIED) "A" CANT STRIP (FIELD SUPPLIED) ROOFING FELT (FIELD SUPPLIED) COUNTER FLASHING (FIELD SUPPLIED) NAIL (FIELD SUPPLIED) TYPICAL (4) SIDES UNIT 7/16" [11] RIGID INSULATION (FIELD SUPPLIED) REVISION RECORD DUCT VIEW "B" CORNER DETAIL GASKET (FIELD SUPPLIED) OVERALL DIM. 5'-7 3/8" WAS 7/8; 18GA MATERIAL WA 16 GA.; NAIL FIELD SUPPLIED WAS WITH CURB (SUPPLIED WITH CURB) A REV 70.87" [1800.2] 32.19" [817.6] E E 13.78" [350.0] 3.00" [76.2] RETURN AIR OPENING 16.03" [407.2] NOTES: 1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED. 2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY. 3. DIMENSIONS IN [ ] ARE MILLIMETERS. 4. ROOFCURB: 18 GAGE STEEL. 5. ATTACH DUCTWORK TO CURB. (FLANGES OF DUCT REST ON CURB). 6. SERVICE CLEARANCE 4 FEET ON EACH SIDE. 7. DIRECTION OF AIR FLOW. 8. CONNECTOR PACKAGE CRBTMPWR001A01 IS FOR THRU-THE-CURB GAS TYPE PACKAGE CRBTMPWR003A01 IS FOR THRU-THE-BOTTOM TYPE GAS CONNECTIONS. 40.69" [1033.5] 21.84" [554.7] A 20.41" [518.3] 11.96" 14" 24" [303.8] [356] [610] SUPPLY AIR OPENING SUPPLY AIR RETURN AIR 1/3/4"[44.5] 5.42" 3.00" [76.2] [137.7] 1/4" [7.0] 21.74" 1.75" [552.2] [44.5] 4.96" [126.0] 15.19" 14.00" ROOF CURB [385.8] [355.6] [115.5] 4 9/16" ACCESSORY # CRRFCURB001A01 CRRFCURB002A01

C13310 Fig. 4 -- Roof Curb Details 8 ! WARNING

PERSONAL INJURY HAZARD Failure to follow this warning could cause personal injury. For vertical supply and return units, tools or parts MAXIMUM ALLOWABLE could drop into ductwork and cause an injury. Install DIFFERENCE IN. (MM) a 90--degree turn in the return ductwork between the A-B B-C A-C unit and the conditioned space. If a 90--degree elbow 0.5” (13) 1.0” (25) 1.0” (25) cannot be installed, then a grille of sufficient strength C06110 and density should be installed to prevent objects Fig. 5 -- Unit Leveling Tolerances from falling into the conditioned space. Due to electric heater, supply duct will require 90--degree Step 5 — Field Fabricate Ductwork elbow. Cabinet return-air static pressure (a negative condition) shall not exceed 0.35 in. wg (87 Pa) with economizer or Step 6 — Rig and Place Unit 0.45 in. wg (112 Pa) without economizer. Keep unit upright and do not drop. Spreader bars are not

For vertical ducted applications, secure all ducts to roof required if top crating is left on unit. Rollers may be used 50LC curb and building structure. Do not connect ductwork to to move unit across a roof. Level by using unit frame as a unit. reference. See Table 1 and Fig. 6 for additional information. Fabricate supply ductwork so that the cross sectional dimensions are equal to or greater than the unit supply Lifting holes are provided in base rails as shown in Fig. 6. duct opening dimensions for the first 18 in. (458 mm) of Refer to rigging instructions on unit. duct length from the unit basepan. Before setting the unit onto the curb, recheck gasketing on Insulate and weatherproof all external ductwork, joints, curb. and roof openings with counter flashing and mastic in accordance with applicable codes. Rigging materials under unit (cardboard to prevent base pan damage) must be removed PRIOR to placing the unit Ducts passing through unconditioned spaces must be on the roof curb. insulated and covered with a vapor barrier. When using the standard side drain connection, ensure the If a plenum return is used on a vertical unit, the return red plug in the alternate bottom connection is tight. Do this should be ducted through the roof deck to comply with before setting the unit in place. The red drain pan plug can 1 applicable fire codes. be tightened with a /2--in. square socket drive extension. For further details see “Step 10 -- Install External Condensate ! CAUTION Trap and Line” on page 13. PROPERTY DAMAGE HAZARD ! CAUTION Failure to follow this caution may result in damage to roofing materials. UNIT DAMAGE HAZARD Membrane roofs can be cut by sharp sheet metal Failure to follow this caution may result in edges. Be careful when placing any sheet metal parts equipment damage. on such roof. All panels must be in place when rigging. Unit is not designed for handling by fork truck when packaging is removed. For Units with Accessory or Optional Electric Heaters — If using top crate as spreader bar, once unit is set, All installations require a minimum clearance to carefully lower wooden crate off building roof top to combustible surfaces of 1--in (25 mm) from duct for first ground. Ensure that no people or obstructions are 12--in (305 mm) away from unit. below prior to lowering the crate. Outlet grilles must not lie directly below unit discharge. NOTE: A 90--degree elbow must be provided in the ductwork to comply with UL (Underwriters Laboratories) code for use with electric heat.

9 CAUTION - NOTICE TO RIGGERS: AVERTISSEMENT - REMARQUE À L’ATTENTION DES MONTEURS ALL PANELS MUST BE IN PLACE WHEN RIGGING. TOUS LES CAPOTS DOIVENT ÊTRE EN PLACE AVANT LE LEVAGE • Hook rigging shackles through holes in base rail, as shown in Detail “A”. • Use wooden top skid, when rigging, to prevent rigging straps from damaging unit. • Max weight includes base unit plus shipping pallet plus all available FIOP's which could be on that size unit. • "B" dimension is based on base unit (PAC no heat or YAC w/low heat) plus economizer option only. This dimension may vary slightly with units configured with other FIOP options. • Spreader bars required to lift and transport the unit. • Accrocher les manilles des élingues de levages dans les trous situés dans le rail de base comme indiqué au Détail « A ». • Utiliser des cales en bois lors du levage pour éviter que les élingues n’endommagent 50LC le haut de l’appareil. • Le poids maximum inclut la configuration de base, le poids de la palette d'expédition, ainsi que toutes les options pouvant être installées en usine (FIOP) pour la plateforme sélectionnée. • La dimension de "B" provient de la configuration de base (PAC sans chauffage ou YAC chauffage au gaz natufrel) qui inclut l'option economizer seulement. Cette dimension peut varier légèrement en fonction des différentes options sélectionnées, installées en usine (FIOP). • Barres d'écartement requises pour soulever et transporter l'unité.

PLACE ALL SEAL STRIP IN PLACE BEFORE PLACING UNIT ON ROOF CURB. “B” DETAIL A INSTALLER TOUTES LES BANDES REQUIRED 914-1371 D’ISOLATION EN PLACE AVANT DE DÉTAIL « A » SPREADER (36"- 54") PLACER L’APPAREIL SUR LE REBORD BARS DE TOIT. DUCT END PASSAGES CONDUITES “C”

“A” SEE DETAIL “A” VOIR DÉTAIL « A »

MAX WEIGHT AB C MODEL LB KG IN MM IN MM IN MM 50LC_004 700 318 74.5 1890 36.5 925 33.5 850 50LC_005 830 377 74.5 1890 36.5 925 41.5 1055 50LC_006 865 393 74.5 1890 36.0 915 41.5 1055 48LC_004 760 345 74.5 1890 38.0 965 33.5 850 48LC_005 895 407 74.5 1890 38.0 965 41.5 1055 48LC_006 930 423 74.5 1890 37.5 955 41.5 1055 48HC500030 A

C12100 Fig. 6 -- Rigging Label

PositioningonCurb— Position unit on roof curb so that the following clearances Although unit is weatherproof, guard against water from 1 are maintained: /4 in. (6.4 mm) clearance between the higher level runoff and overhangs. roof curb and the base rail inside the front and rear, 0.0 in. clearance between the roof curb and the base rail inside on After unit is in position, remove rigging skids and the duct end of the unit. This will result in the distance shipping materials. between the roof curb and the base rail inside on the 1 condenser end of the unit being approximately /4 in. (6.4 mm).

10 Step 7 — Convert to Horizontal and Connect Step 8 — Install Outside Air Hood Ductwork (when required) Economizer Hood Package Removal and Setup -- Unit is shipped in the vertical duct configuration. Unit Factory Option without factory--installed economizer or return air smoke detector option may be field--converted to horizontal ducted 1. The hood is shipped in knock--down form and must configuration. To convert to horizontal configuration, be field assembled. The indoor coil access panel is remove screws from side duct opening covers and remove used as the hood top while the hood sides, divider and covers. Using the same screws, install covers on vertical filter are packaged together, attached to a metal sup- duct openings with the insulation--side down. Seals around port tray using plastic stretch wrap, and shipped in the duct openings must be tight. See Fig. 7. return air compartment behind the indoor coil access panel. The hood assembly’s metal tray is attached to the basepan and also attached to the damper using two plastic tie--wraps. 2. To gain access to the hood, remove the filter access panel. (See Fig. 8.)

FILTER ACCESS PANEL 50LC

COMPRESSOR ACCESS PANEL OUTDOOR-AIR OPENING AND C06108 INDOOR COIL ACCESS PANEL Fig. 7 -- Horizontal Conversion Panels C06023 Fig. 8 -- Typical Access Panel Locations Field--supplied flanges should be attached to horizontal duct openings and all ductwork should be secured to the 3. Locate the (2) screws holding the metal tray to the flanges. Insulate and weatherproof all external ductwork, basepan and remove. Locate and cut the (2) plastic joints, and roof or building openings with counter flashing tie--wraps securing the assembly to the damper. (See and mastic in accordance with applicable codes. Fig. 9) Be careful to not damage any wiring or cut tie--wraps securing any wiring. Do not cover or obscure visibility to the unit’s informative data plate when insulating horizontal ductwork.

Hood Parts

Plastic Tie Wrap Qty (2)

Screws for Metal Tray Qty (2)

C08639 Fig. 9 -- Economizer Hood Parts Location

11 4. Carefully lift the hood assembly (with metal tray) 3. Remove the shipping tape holding the economizer through the filter access opening and assemble per the barometric relief damper in place (economizer only). steps outlined in Economizer Hood, below. 4. Insert the hood divider between the hood sides. See Economizer Hood — Fig. 11 and Fig. 12. Secure hood divider with 2 screws on each hood side. The hood divider is also NOTE: If the power exhaust accessory is to be installed used as the bottom filter rack for the aluminum filter. on the unit, the hood shipped with the unit will not be 5. Open the filter clips which are located underneath the used and must be discarded. Save the aluminum filter for hood top. Insert the aluminum filter into the bottom use in the power exhaust hood assembly. filter rack (hood divider). Push the filter into position 1. The indoor coil access panel will be used as the top of past the open filter clips. Close the filter clips to lock the hood. Remove the screws along the sides and bot- the filter into place. See Fig. 12. tom of the indoor coil access panel. See Fig. 10. 6. Caulk the ends of the joint between the unit top panel and the hood top. 7. Replace the filter access panel.

TOP PANEL 50LC

DIVIDER OUTSIDE AIR TOP PANEL HOOD CAULK HERE INDOOR INDOOR CLEANABLE COIL COIL ALUMINUM FILTER ACCESS ACCESS FILTER PANEL PANEL

BAROMETRIC C06025 RELIEF Fig. 10 -- Indoor Coil Access Panel Relocation FILTER CLIP C08634 2. Swing out indoor coil access panel and insert the hood Fig. 12 -- Economizer Filter Installation sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use Step 9 — Units with Hinged Panels Only screws provided to attach the hood sides to the unit. See Fig. 11. Relocate latch shipped inside the hinged compressor door to location shown in Fig. 13 after unit installation.

TOP If the unit does not have hinged panels, skip step 9 and PANEL continue at step 10.

INDOOR COIL ACCESS PANEL

LEFT HOOD SCREW SIDE 19 1/16”B (483mm)

33 3/8” (848mm)

HOOD DIVIDER C12101 Fig. 13 -- Compressor Door Latch Location C06026 Fig. 11 -- Economizer Hood Construction

12 Step 10 — Install External Condensate Trap Step 11 — Make Electrical Connections and Line 3 The unit has one /4-in. condensate drain connection on ! WARNING the end of the condensate pan and an alternate connection on the bottom. See Fig. 14. Unit airflow configuration ELECTRICAL SHOCK HAZARD does not determine which drain connection to use. Either Failure to follow this warning could result in personal drain connection can be used with vertical or horizontal injury or death. applications. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC; ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical CONDENSATE PAN (SIDE VIEW) codes. ALTERNATE STANDARD DRAIN PLUG SIDE DRAIN BOTTOM DRAIN (FACTORY-INSTALLED)

C08021 NOTE: Field--supplied wiring shall conform with the 50LC Fig. 14 -- Condensate Drain Pan (Side View) limitations of minimum 63_F(33_C) rise. To use the alternate bottom drain connection, remove the Field Power Supply — red drain plug from the bottom connection (use a 1/ -- i n . 2 If equipped with optional Powered Convenience Outlet: square socket drive extension) and install it in the side The power source leads to the convenience outlet’s drain connection. transformer primary are not factory connected. Installer The piping for the condensate drain and external trap can must connect these leads according to required operation be completed after the unit is in place. See Fig. 15. of the convenience outlet. If an always--energized convenience outlet operation is desired, connect the source leads to the line side of the unit--mounted MINIMUM PITCH disconnect. (Check with local codes to ensure this method 1” (25mm) PER BASE RAIL 10’ (3m) OF LINE is acceptable in your area.) If a de--energize via unit

2˝ (51) MIN disconnect switch operation of the convenience outlet is OPEN VENT desired, connect the source leads to the load side of the unit disconnect. On a unit without a unit--mounted disconnect, connect the source leads to compressor TO ROOF SEE NOTE DRAIN contactor C and indoor fan terminal block (IFTB) pressure lugs with unit field power leads.

ROOF Refer to Fig. 28 for power transformer connections and CURB DRAIN PLUG the discussion on connecting the convenience outlet on NOTE: Trap should be deep enough to offset maximum unit static page 20. difference. A 4” (102) trap is recommended. Field power wires are connected to the unit at line--side C08022 pressure lugs on compressor contactor C and indoor fan Fig. 15 -- Condensate Drain Piping Details terminal block (IFTB) (see wiring diagram label for control box component arrangement) or at factory--installed option All units must have an external trap for condensate non--fused disconnect switch or HACR. Max wire size is drainage. Install a trap at least 4-in. (102 mm) deep and #2ga AWG (copper only) per pole on contactors. #2ga AWG protect against freeze-up. If drain line is installed per pole on optional disconnect or HACR and 4/0 AWG per downstream from the external trap, pitch the line away pole on terminal or fuse block on units with single point from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do box. See Fig. 20 and unit label diagram for field power not use a pipe size smaller than the unit connection wiring connections. 3 ( /4-in.).

13 OFM C TRAN CONTROL BD

CONTROL BD CTB-C HC1 HC2 F CLO1 TERM BD DD IFM C O M TB4 TB4 TB4 COFS C LDR CLO2/ COMP2 -2 3 5 C 12 24V WHT GRA

YEL BLK BLU

BRN GRN/ BRN BRN GRA

BRN BRN 48HC500007 CKT 1 CKT CKT 2 CKT YEL BRN BRN WHT RED BRN BRN BRN BRN BRN BRN BRN

C PNK ALARM FOR FIELD USE SMOKE UNIT LPS YEL LPS1 LPS2 LAS HC1 HC2 BLU BLU BLU SHUTDOWN HIGH BLU (SEE NOTE 3) VOLTAGE WHT SF WHT BLK BRN

BLK VIO VIO

ELECTRIC HEAT (ACCESSORY) NOTE 6 C LDR BLK BRN YEL SEE DETAIL A FOR 5 TON HPS BRN

COFS (FIOP)

HPS1 HPS2 24V OUT 24V VIO ORN BLK FPT BRN RED BLU BRN

BLK

BRN

SHUTDOWN BLK

BLU

10 SMOKE

RED JMP3 10 BLU

TB4

DDC NOTE 7

ORN BLU 9

ORN 9

4

ORN 4

SHUTDOWN

VIO 8

BLU BRN BRN 8

REMOTE YEL

BLK

BRN 3 BRN

JMP4 VIO

BRN 2 6 3 1 3 4 5

PMR 7

7 VIO

2

VIO

24V 2

CONT 2 5 6 1 3 4 7 2 4 5 6 1 3 COM 6

FIOP/ACCY PMR BRN 6

SAT/OAT PNK CLO1/ COMP1 CLO2/ COMP2

GRN/YEL

COFS(FIOP) 1

PNK 1 VIO 1 ORN

BRN

BRN RED

LOGIC 2 ECON

PNK

10

3 JMP1 10 RED

24V

BRN DDC

RED 9

BRN BRN 9

BRN C

8

BRN PNK 8

DDC

5

5 RED PNK

CB R 7

7

RED GRA

TRAN FROM POWER SCHEMATIC 3.2 AMPS 4

4 RED GRA

6

OCCUPANCY

6 GRA

24V 3

JMP2

3

SEE NOTE 5 GRA 5

5 BLK

BRN 2 RED

2

RED

4 BRN 12

4 12 YEL

1

LSM 1

BLU RED

RED 11

3

11

3

ORN

RED 10

10

2

2 GRA 9 RED

9

1

8 RED

1 BLU 8

7 GRA

7

6 BLK

6

5 BRN

5

4 BRN

4

3 50LC ORN

ORN 3 CTB

2 VIO

VIO 2

YEL BLU (SEE NOTE 1) PNK BRN RED GRA GRA ORN WHT

1 GRA

4 3 8 9 1 2 6 7 5

BLK 1 BOARD

PL19- CONTL R X C G Y1 Y2 W1 W2 YEL BLU PNK RED BRN GRA ORN GRN WHT CCHTS STAT THERMO- 9 6 3 5 4 17 10 16 14 BLK JMP5 JMP7 NC NO 460/575V ONLY NO MODULE NC CCHR ALARM 8 2 4 5 6 3 7 1 TROUBLE JMP6 7 2 3 6 4 5 1 POWER 24 VAC SMOKE CONTROL RJ-45 RJ-45 FIOP/ACCESSORY DDC T'STAT BRN REHEAT 4 1 2 3 5 6 7 GRA FIOP/ SMOKE SMOKE SUPPLY SENSOR SENSOR RETURN YEL BLU GRA PNK BRN GRN ORN WHT ACCESSORY DDC ONLY FIELD WIRING CONTROL ESL GRA GRA DDC OPTIONS ONLY LOGIC YEL BLU PNK BRN GRN ORN WHT 7 4 2 6 5 3 1 I C R R NC NO SPT IFM TDR CONTROL 5 7 6 4 3 2 1 DDC RED HARNESS BLK RED BRN GRA CTB HC1 12 TB4 YEL BLK BLU BRN RED GRA GRA ORN ORN BRN VIO PNK 2 7 10 1 5 6 4 3 9 8 2 3 4 1 HC1 BRN YEL ECONOMIZER (FIOP/ ACCESSORY) RED BRN L5 BRN 8 5 6 4 9 10 2 3 7 1 3 1 2 4 BRN PNK/BLK (NOT USED) DETAIL A PL18-1 PL18-2 GRA YEL BRN ORN HCR1 HCR2 RED ELECTRIC HEAT FIOP/ACCY STD UNIT CTB ECON 3 1 2 4 5 GRA GRA ORN BRN VIO PNK BRN J1 5 TON 575V "C" HEAT ONLY VIO BRN WHT NOTE 6 1 2 3 4 5 RED BRN BLK YEL BLU PNK BRN RED GRA ORN GRA GRA PNK VIO TB4 2 1 NOTE 7 3 10 4 6 8 2 7 1 5 9 12 JW2 JW1 PL6 VFD FAN VIO RED BOARD ORN IAQ

(FIOP/ ACCY)

8 4 1 9 6 3 5 7 2

BLU 12 11 3 2 1 6 5 4 6 YEL 7 PL6-R FOR STD UNIT J2 24V TO TRANS 2 6 3 5 7 8 4 1 6 2 3 9 11 11 10 12 BLK BLU YEL PNK RED -OR- WHT PL6-R R CTB PNK YEL GRA BLU BRN RED BLK GRA ORN HIGH VOLTAGE VIO RED PL18-3 PL18-4 TAN TO "C" COIL GRN GRN GRA BLK BLU (FIOP/ ACCY) YEL BLK BRN OAT GRN/YEL PNK PNK BLK BLU L N C G YEL YEL PNK BLK BLU WHT GRA GRA WHT GRA GRA ORN BRN 2 3 4 2 3 4 6 5 1 5 1 2 HI 4 3 GRN GRN BLK RED GRN WHT ECM PL25 2 PL 1 LO ECONOMIZER (FIOP/ ACCESSORY) YEL BLU PNK PNK BLU PNK WHT 1 3 4 5 2 SENSOR ENTHALPY (ACCY) SAT 4 ENTHALPY SEE NOTE ECONO MOTOR 10 11 13 14 15 16 12 DD IFM CTB T'STAT-W1 VFD YEL WHT 3 PH IFM TAN GRA

1 WHT GRN/YEL BLU RED BLK YEL ORN YEL ORN GRA BRN 4 NOTE 8 NOTE 1 3 4 2 2 1 5 6 3 6 5 4 ACCESSORY TAN TO POWER EXHAUST GRA C R OCC Y2-I Y1-I Y2-O Y1-O EXH 1

E-GND AUX2-I

AUX1-O

GRAY BLUE W1 MAT OAT OAT MAT ACT 2-10 ACT COM ACT 24V+ IAQ COM IAQ 24V+ IAQ 2-10 S-BUS S-BUS W7220 HONEYWELL 2 1 1 2 1 1 1 3 2 2 4 2 3 VIO BLK BLK BLU BLU PNK BRN GRA GRA ORN TO SIMPLIFY CIRCUIT TRACES. DETECTORS, PHASE LOSS RELAY, OCCUPANCY AND REMOTE SHUTDOWN. RECTIFIER TO CONVERT AC DC. RELOCATION OF SIGNALCONNECTION MAY BE REQUIRED WHEN USING FIELD INSTALLED ACCESSORIES - CONSULT INSTALLATION INSTRUCTIONS FOR PROPER SELECTION. AND 8. VIOLET HEATER WIRE FROM TB4-VIOLET TO TB4-ORANGE WIRE. AND WHITE WIRES. DISCONNECT FOR NORMAL OPERATION. NOTES: 1. TERMINAL BOARD SCHEMATIC LAYOUT DOES NOT MATCH ACTUAL 2. ENSURE DESIGNATED JUMPERS ON TERMINAL BOARD ARE CUT WHEN ADDING SMOKE 3. COMPRESSOR LOADER PLUG CONTAINS BRIDGE 4. FACTORY WIRING FOR SIGNAL CONNECTIONS: LO=1 HI=2. 5. WITH DDC OPTION THERE WILL BE WIRES IN PINS 6, 7, 6. FOR SINGLE STAGE ELECTRIC HEAT OPTION, MOVE 7. TB4 LOCATED IN HEAT SECTION. 8. FOR HIGH SPEED BLOWER TESTING, CONNECT YELLOW 50LC CONTROL 208/230V,460V,575V 3-5 TON C13386 Fig. 16 -- 50LC Control Wiring Diagram 14 GRA GRA - BRN 24V CONT COM PMR FIOP/ ACCY OFM RED PNK FOR FIELD USE YEL

RED PNK F BRN C O M TRAN CONTROL BD CONTROL BD HC1 HC2 CLO1 TERM BD DD IFM TB4 TB4 TB4 COFS CTB-C OFR1 LDR C CLO2/ COMP2 -2 LCTB C CLO2/COMP2-2 48HC500324 5 3 C 12 WHT 24V YEL YEL BLK BRN BLU GRN/

BRN

BRN

BRN BRN BLK BRN BRN

BRN 1 CKT BRN CKT 2 CKT WHT SF YEL FPT BRN BRN BRN BRN BRN BRN BRN

C BLU ALARM

BRN YEL BLK GRN/YEL HIGH SMOKE LPS UNIT COFS (FIOP) ORN LPS1 LPS2 GRY VOLTAGE HC1 HC2 24V BLU SHUTDOWN

BLU BLU (SEE NOTE 3) LOGIC WHT BLU BRN

BLK VIO VIO SEE DETAIL A FOR 5 TON NOTE 6

ELECTRIC HEAT (ACCESSORY) C LDR LAS1 VIO HPS

CB

HPS1 BRN HPS2 BRN 24V OUT 24V BLU GRA BRN RED BLK BRN YEL BLU COFS (FIOP) TRAN FROM POWER SCHEMATIC BLK

12 14 12 BRN 3.2 AMPS BLU SHUTDOWN

TB4 NOTE 7 SMOKE OFR2 LAS3 BLU BLU 24V JMP3 OFR1 OFR1 ORN BLU RED BRN OFR2 WHT 11 ORN 11 VIO

RED GRA

SHUTDOWN WHT

YEL VIO BLU BRN REMOTE PNK/BLK BRN BRN BLK VIO 2 5 6 1 3 4 JMP4

2 3 4 5 6 7 1 2 3 4 5 6 1

PMR

YEL 10 BLU PNK BRN RED GRA GRA ORN WHT

RED CLO1/ COMP1 10 CLO2/ COMP2

6 7 1 2 4 3 5 8 9

DDC 1

PL19- 9 BRN ORN 9 2

RED YEL PNK BRN

GRN GRA

ORN BLU WHT

RED

8

BRN 8 3 JMP1

PNK

6 5 4 3 9

10 16 17 14

7

7 VIO

ECON C

BRN 6

10

6

NC PNK NO BRN DDC 10 RED

NO

NC MODULE

RED ALARM R

TROUBLE 9

POWER 24 VAC 4 SMOKE CONTROL RJ-45 RJ-45 RED

FIOP/ACCESSORY BRN 9 ORN 4

RED

DDC

OCCUPANCY

8

PNK 3 PNK 8

BRN

JMP2 3

BRN 7

2

GRA 7

VIO

SMOKE 2 SMOKE BRN SUPPLY

SENSOR SENSOR 24V FIOP/ RETURN

SAT/OAT

12

GRN/YEL BRN

ACCESSORY 6

1

12

6 GRA

PNK 1

CB 5

TRAN2 11

FROM POWER SCHEMATIC RED

5

SEE NOTE 5 PNK BRN 11

5

5 BLK

10 RED

LSM 4

10

4 GRA

4

9 RED 4 YEL

9

RED 3

3

GRA

8 RED

3

3 ORN 8

2

2 7 RED GRA

2

RED BLK YEL 7 BLU

2 GRA

1

6 BLK

1 4 5 6 7 1 2 3 BLU

6

BLK 1

BLU 1 BLU 5 BRN

2 4 5 1 3 5 6 7 J2

4 RDV BRN

4 50LC

3

REHEAT CONTROL ORN

BLK 3

2

CR1 VIO CR2

X R C G 2 W1 W2 Y1 Y2 DHRB2

CLV DHRA DHRB

DHRB2

1 GRA

STAT BRN 1

BRD THERMO-

YEL CNTL JMP5 JMP7 HR1 CR1 CR2 HR1 DHRB DHRA RLV CCHTS BRN BLK J1 1 2 3 6 7 8 9 4 5 10 11 460/575V ONLY 2 3 5 6 4 7 8 1 JMP6 1 2 5 7 3 4 6 8 6 7 9 5 1 2 4 3 11 10 BRN CCHR DDC T'STAT REHEAT 7 6 5 4 1 3 2 BRN RED YEL PNK BRN BRN ORN ORN GRA WHT GRA WHT 1 4 6 2 5 (SEE NOTE 1) CTB ORN BLU BRN WHT GRN PNK YEL ORN ORN GRA GRA (J1-6) (J1-5) (J1-11) (J1-10) WHT WHT YEL YEL PNK BLK PNK/ GRA LTLO HUMID- ISTAT ACCY HU BLK PNK/ DDC ONLY FIELD WIRING CONTROL ESL GRA GRA DDC OPTIONS ONLY LOGIC GRN ORN YEL PNK BLU BRN WHT 1 2 3 4 7 5 6 I R C R NO NC SPT IFM TDR CONTROL 2 5 1 3 7 6 4 DDC RED HARNESS RED GRA BLK BRN CTB HC1 TB4 12 GRA YEL BLU RED ORN BLK BRN GRA ORN BRN VIO PNK 7 10 1 9 8 3 6 2 4 5 2 3 4 HC1 1 BRN YEL ECONOMIZER (FIOP/ ACCESSORY) RED BRN L5 BRN 4 10 2 3 1 5 8 9 7 6 BRN 3 1 2 4 PNK/BLK (NOT USED) DETAIL A PL18-1 PL18-2 YEL BRN GRA ORN HCR1 HCR2 RED ELECTRIC HEAT FIOP/ACCY STD UNIT CTB ECON 2 3 1 4 5 GRA GRA BRN ORN VIO PNK BRN J1 BRN VIO 5TON 575V "C" HEAT ONLY WHT NOTE 6 1 2 3 4 5 RED BRN YEL BLU RED GRA ORN BLK BRN PNK GRA GRA VIO PNK TB4 1 2 NOTE 7 7 6 11 1 5 9 8 2 12 3 4 10 JW1 JW2 PL6 VFD FAN BOARD RED VIO ORN IAQ

(FIOP/ ACCY)

6 7 5 8 2 3 4 1 9

BLU 12 11 3 6 5 2 4 1 6 YEL 7 PL6-R FOR STD UNIT J2 24V TO TRANS 2 6 3 7 6 5 8 2 3 4 1 9 12 11 10 BLK BLU YEL PNK RED -OR- WHT PL6-R R CTB PNK GRA RED ORN YEL GRA BRN BLU BLK HIGH VOLTAGE VIO RED PL18-3 PL18-4 TAN TO "C" COIL GRN GRN GRA BLK BLU (FIOP/ ACCY) YEL BLK BRN OAT GRN/YEL PNK PNK BLK BLU L N C G YEL GRA GRA PNK BLK BLU YEL WHT WHT GRA GRA BRN ORN 4 3 2 2 3 4 5 1 6 5 1 2 HI 4 3 GRN GRN GRN WHT BLK RED PL25 ECM 2 PL 1 LO ECONOMIZER (FIOP/ ACCESSORY) YEL BLU PNK PNK BLU PNK WHT 1 2 5 3 4 SENSOR ENTHALPY (ACCY) SAT 4 ENTHALPY SEE NOTE ECONO MOTOR 11 12 13 14 16 10 15 CTB DD IFM T'STAT-W1 VFD YEL WHT 3 PH IFM TAN GRA

YEL BLU RED BRN GRA

ORN 1 WHT BLK GRN/YEL YEL ORN 4 NOTE 8 NOTE 1 3 4 2 2 1 6 5 3 6 5 4 ACCESSORY TAN GRA TO POWER EXHAUST C R Y2-I Y1-I OCC Y2-O Y1-O EXH 1

E-GND

AUX2-I

AUX1-O BLUE GRAY W1 OAT OAT MAT MAT IAQ 2-10 ACT 2-10 IAQ 24V+ ACT COM ACT 24V+ IAQ COM S-BUS S-BUS 2 1 1 2 1 1 1 3 2 2 4 2 3 HONEYWELL W7220 VIO BLK BLU PNK BLU BLK BRN GRA GRA ORN TO SIMPLIFY CIRCUIT TRACES. DETECTORS, PHASE LOSS RELAY, OCCUPANCY AND REMOTE SHUTDOWN. RECTIFIER TO CONVERT AC DC. RELOCATION OF SIGNALCONNECTION MAY BE REQUIRED WHEN USING FIELD INSTALLED ACCESSORIES - CONSULT INSTALLATION INSTRUCTIONS FOR PROPER SELECTION. AND 8. VIOLET HEATER WIRE FROM TB4-VIOLET TO TB4-ORANGE WIRE. AND WHITE WIRES. DISCONNECT FOR NORMAL OPERATION. NOTES: 1. TERMINAL BOARD SCHEMATIC LAYOUT DOES NOT MATCH ACTUAL 2. ENSURE DESIGNATED JUMPERS ON TERMINAL BOARD ARE CUT WHEN ADDING SMOKE 3. COMPRESSOR LOADER PLUG CONTAINS BRIDGE 4. FACTORY WIRING FOR SIGNAL CONNECTIONS: LO=1 HI=2. 5. WITH DDC OPTION THERE WILL BE WIRES IN PINS 6, 7, 6. FOR SINGLE STAGE ELECTRIC HEAT OPTION, MOVE 7. TB4 LOCATED IN HEAT SECTION. 8. FOR HIGH SPEED BLOWER TESTING, CONNECT YELLOW 50LC CONTROL 208/230V,460V,575V 3-5 TON C13416 Fig. 17 -- 50LC Control Wiring Diagram with Humidi--MiZerR 15 E DIRECT DRIVE IFM OFM OFM 460V 575V FOR FOR COMP TRAN TRAN ONLY ONLY IFM 3 PH OFM GRN/YEL 5 - OR X1 H4 X1 H2 BLK BLK 4 F C O M HI WHT 3 2 X3 X3 H2 LO YEL 2 3 1 GRN/YEL 1 LOW VOLTAGE 48HC500009 575V 230V 230V X2 H3 X2 BLK YEL BLU BLK YEL BLU BRN L N C WHT G 460V T1 T3 T2 NOTE 6 H1 X4 X4 H1 BLU BLU BLK YEL BLU GRN/YEL BLK BRN YEL BLK YEL BLU GRN/YEL LOW BLK BLK BLU BLU VOLTAGE W2 V2 U2 CCH BLK BLU FU FU FU FU 2 AMP 2 AMP VFD 1 AMP 1 AMP PE SEE NOTE #8 SEE NOTE #10 BLK U1 V1 W1 4 BLK BLK SEE NOTE #9 2 BLK BLU YEL BLK BLU BLK TRAN2 6 575V BLK YEL BLU MOV3 MOV2 MOV1 460V ONLY 460V YEL FOR 230V AND 3 1 GRN/YEL BLK RED CCHR 460/575V ONLY 8 42 BLU BLU BLK BLK YEL BLK BLK YEL BLU ONLY FU FU 4 AMP 4 AMP FOR 575V BLU SEE NOTE #7 GRN/YEL BLU BLK C BLK BLU BLK YEL BLK 1113 21 23 BLU IFTB BLK YEL YEL BLK BLK BLK YEL YEL BLK GRN/YEL 24V YEL BRN 230 200 C BLK 24V CCHTS 208/230V ONLY BLK YEL BLU BLK 460 RED TO 24V SCHEMATIC L1 L3 L2 575 BLK BLK PMR (ACCY) TRAN 1 & 2 HEATERS ELECTRIC BLU BLK YEL CCH YEL GRN/YEL 24V BLK 50LC BLK BLU BLK BLU YEL YEL EQUIP GR BRN 230 200 C 24V YEL BLU BLK FB2 FB3 FU FU FU 60 AMP 60 AMP 60 AMP 460 GRN/YEL MAXIMUM WIRE SIZE 4 AWG SEE NOTE#5 FU FU FU RED 60 AMP 60 AMP 60 AMP TO 24V SCHEMATIC 575 USED WITH 208/ 230V ELECTRIC HEAT OPTIONS OVER 17.0 KW USED WITH ALL 460V, 575V ELECTRIC HEAT OPTIONS AND UP TO 17.0 KW 208/230V HEAT OPTIONS TB DEHUMIDIFICATION FIOP TRAN 2 L1,L2,L3 WIRES ARE FACTORY WIRES WITH HACR/DISCONNECT FIOPS YEL BLU BLK YEL BLU YEL BLU BLK BLK SINGLE POINT CONNECTION BOX EQUIP GR EQUIP GR SINGLE POINT CONNECTION BOX

FIOP HACR 1/0 MAX WIRE SIZE SEE NOTE 4 BLU YEL BLK BLK YEL BLU MAXIMUM WIRE SIZE 2 AWG SEE NOTE #5 T2 T1 T3 EQUIP GR MAXIMUM WIRE SIZE 2 AWG SEE NOTE #5 FIOP 1/0 MAX L1 L3 L2 WIRE SIZE DISCONNECT SEE NOTE 5

FIOP OUTLET FIOP HACR FIOP HACR 1/0 MAX 1/0 MAX CONVENIENCE WIRE SIZE NON-POWERED SEE NOTE 4 WIRE SIZE POWER FIELD SEE NOTE 4 SUPPLY BLK T2 T1 T3 EQUIP GR T2 T1 T3 EQUIP GR GR WHT FIOP FIOP 1/0 MAX L1 L3 L2 DISCONNECT 1/0 MAX WIRE SIZE L1 L3 L2 DISCONNECT SEE NOTE 5 WIRE SIZE SEE NOTE 5 115V FIELD SUPPLY

FIELD FIELD

POWER POWER SUPPLY SUPPLY REHEAT BOARD REHEAT LOSS PHASE DEHMIDIFICATION FIOP TRAN 2 IFTB TRAN COMPONENT ARRANGEMENT C BD VFD FAN 575V ONLY IFM 460V & CCHR TDR

OPTION DEHMIDIFICATION FIOP DEHMIDIFICATION

HACR/DISCONNECT

COFS OFR1 (FIOP) OFR2 CTB X C R G Y1 Y2 W1 W2

THERMOSTAT IF ANY OF THE ORIGINAL WIRE FURNISHED MUST BE REPLACED. IT MUST BE REPLACED WITH TYPE 90 C WIRE OR ITS EQUIVALENT. COMPRESSOR AND FAN MOTORS ARE THERMALLY PROTECTED. THREE PHASE MOTORS ARE PROTECTED AGAINST PRIMARY SINGLE PHASING CONDITIONS. ON 208/230V UNITS, TRAN IS WIRED FOR 230V. IF UNIT TO BE RUN WITH 208V POWER SUPPLY, DISCONNECT BLK WIRE FROM 230V TAP AND CONNECT TO 200V TAP. 230V,200V TAPS ON TRAN DO NOT APPEAR ON 575V TRAN AND TAP DOES 208/230/460V TRAN. USE COPPER, COPPER CLAD ALUMINUM OR CONDUCTOR. USE COPPER CONDUCTOR ONLY. DO NOT DISCONNECT POWER PLUG OR SIGNAL WIRE WHILE UNDER LOAD. THESE FUSES ARE MANUFACTURED BY COOPER BUSSMANN, P/N - FNQ-R-4. THESE FUSES ARE MANUFACTURED BY COOPER BUSSMANN, P/N - FNQ-R-1. VFD USER KEYPAD CONNECTED TO THE DRIVE FOR SHIPPING PURPOSES. THESE FUSES ARE MANUFACTURED BY COOPER BUSSMANN, P/N - FNQ-R-2. -OR- 7220 NOTES 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. RTU-OPEN BLOWER COMMON COMMON (TRAN2) CENTRIFUGAL SWITCH FAN LINE 1 THERMOSTAT POWER THERMOSTAT POWER (TRAN2) POWER SUPPLY SPEED SENSOR THERMOSTAT HEAT CALL 1st STAGE OF HEATING 2nd STAGE OF HEATING ALARM OUTPUT 1st STAGE OF COOLING 2nd STAGE OF COOLING THERMOSTAT MARKINGS BM C C-2 CS G L1 R R-2 RT SS W W1 W2 X Y1 Y2 LEGEND ACCESSORY OR OPTIONAL WIRING TERMINAL (MARKED) TERMINAL (UNMARKED) FIELD SPLICE MARKED WIRE SPLICE SPLICE (MARKED) TERMINAL BLOCK FACTORY WIRING FIELD CONTROL WIRING FIELD POWER WIRING CIRCUIT BOARD TRACE TO INDICATE COMMON POTENTIAL ONLY: NOT TO REPRESENT WIRING X CIRCUIT A CIRCUIT B ACCESSORY ALARM RELAY CONTACTOR,COMPRESSOR CAPACITOR CIRCUIT BREAKER CRANKCASE HEATER CARRIER COMFORT NETWORK COMMUNICATION INTERFACE BOARD COOLING LIQUID VALVE CONDENSATE OVERFLOW SWITCH SIGNAL COMMON COMPRESSOR MOTOR CENTRAL TERMINAL BOARD DIRECT DIGITAL CONTROL ENTHALPY CONTROL ECONOMIZER CONTROL BOARD ENTHALPY ENERGY RECOVERY VENTILATOR FUSE BLOCK FACTORY INSTALLED OPTION FIRE SHUT DOWN FREEZE PROTECTION THERMOSTAT FUSE GROUND HIGH PRESSURE SWITCH HUMIDISTAT INDOOR AIR QUALITY SENSORS INDOOR FAN CONTACTOR INDOOR FAN MOTOR INDOOR FAN TERMINAL BLOCK LOW AMBIENT RELAY LOW AMBIENT SWITCH COMPRESSOR LOADER(INTERNAL) LOCAL EQUIPMENT NETWORK CURRENT LOOP POWER LIMIT SWITCH (MANUAL RESET) SCROLLING MARQUEE DISPLAY MAIN BASE BOARD METAL OXIDE VARISTOR OUTDOOR AIR TEMP. SEN OUTDOOR FAN CONTACTOR OUTDOOR FAN MOTOR OUTDOOR FAN RELAY OUTDOOR FAN TERMINAL BLOCK OVERLOAD POWER EXHAUST RELAY PLUG ASSEMBLY PHASE MONITOR RELAY QUADRUPLE TERMINAL RELAY RETURN AIR TEMP. SEN REHEAT DISCHARGE VALVE RELATIVE HUMIDITY REHEAT LIQUID VALVE REMOTE OCCUPANCY SUPPLY AIR TEMP. SENSOR SENSOR SET POINT OFFSET SATURATED CONDENSING TEMP SIGNAL FILTER SPACE RELATIVE HUMIDITY SPACE TEMPERATURE SENSOR SPACE TEMPERATURE OFFSET SATURATED SUCTION PRESSURE SWITCH TERMINAL BLOCK TRANSFORMER UNIVERSAL PROTOCOL CONVERTER VARIABLE FREQUENCY DRIVE X X ___.A ___.B ACCY ALM C CAP CB CCH CCN CIB CLV COFS COM COMP CTB DDC EC ECB ENTH ERV FB FIOP FDWN FPT FU GR (GND) HPS HUM IAQ IFC IFM IFTB LAR LAS LDR LEN LPWR LS LSM MARQ MBB MOV OAT OFC OFM OFR OFTB OL PER PL PMR QT R RAT RDV RH RLV RMOC SAT SEN SET SCT SF SPRH SPT SPTO SSP SW TB TRAN UPC VFD 50LC POWER 208/230V, 460V, 575V 3 PH 3-5 TON

C13417 Fig. 18 -- 50LC Power Wiring Diagram, 208/230V, 460V, 575V 3 Phase 16 50LC

C13418 Fig. 19 -- 50LC ComfortLINK Power Wiring Diagram, 208/230V, 460V, 575V 3 Phase 17 Units Without Single Point Box, Disconnect or HACR Option

Equip ELECTRIC C GR Lug DISCONNECT 11 IFTB SWITCH COPPER WIRE ONLY

ALUMINUM WIRE Disconnect per NEC A93033 Fig. 21 -- Disconnect Switch and Unit L1 L2 L3 Ground 208/230-3-60 (GR) 460-3-60 575-3-60 Units With Factory--Installed Non--Fused Disconnect or HACR — The factory--installed optional non--fused disconnect (NFD) Units With Disconnect or HACR Option or HACR switch is located in a weatherproof enclosure located under the main control box. The manual switch L1 2 1 handle and shaft is shipped in the disconnect or HACR

Optional enclosure. Assemble the shaft and handle to the switch at 50LC L2 4 Disconnect 3 this point. 3 Phase OnlySwitch 3 Phase Only Factory Wiring L3 6 5

Ground (GR) Equip GR Lug

Units With Electric Heat Option with Single Point Box and Without Disconnect or HACR Option

Single Point Box Terminal Block L1

L2 Factory Wiring L3

C12284 Ground (GR) Equip GR Fig. 22 -- Location of Non--Fused Disconnect Enclosure Lug To field install the NFD shaft and handle: — OR — 1. Remove the unit front panel (see Fig. 2). Single Point Box 2. Remove (3) hexagon screws on the front cover -- (2) Fuse/Terminal Block on the face of the cover and (1) on the left side cover. L1 Fuse 3. Remove the front cover of the NFD enclosure. L2 Fuse Factory 4. Make sure the NFD shipped from the factory is at Wiring OFF position (the arrow on the black handle knob is L3 Fuse at OFF). Ground (GR) 5. Insert the shaft with the cross pin on the top of the Equip GR Lug shaft in the horizontal position.

C12104 6. Measure from the tip of the shaft to the top surface of Fig. 20 -- Power Wiring Connections the black pointer; the measurement should be 3.75 -- 3.88 in. (95 -- 99 mm). 7. Tighten the locking screw to secure the shaft to the ! WARNING NFD. 8. Turn the handle to the OFF position with red arrow FIRE HAZARD pointing at OFF. Failure to follow this warning could result in 9. Install the handle on to the painted cover horizontally intermittent operation or performance satisfaction. with the red arrow pointing to the left. Do not connect aluminum wire between disconnect 10. Secure the handle to the painted cover with (2) screws switch and 50LC unit. Use only copper wire. and lock washers supplied. (See Fig. 21.)

18 11. Engaging the shaft into the handle socket, re--install (3) hexagon screws on the front cover. 12. Re--install the unit front panel.

C12281 Fig. 25 -- Handle and Shaft Assembly for HACR

C12279 Units Without Factory--Installed Disconnect or HACR — 50LC Fig. 23 -- Handle and Shaft Assembly for NFD When installing units, provide a disconnect switch per NEC (National Electrical Code) of adequate size. Disconnect sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative plate if mounting the disconnect on the unit cabinet. All Units — All field wiring must comply with NEC and all local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 20 and the unit label diagram for power wiring connections to the unit power terminal blocks and equipment ground. Maximum wire size is #2ga AWG per pole on contactors. #2ga AWG per pole on optional disconnect or HACR and 4/0 AWG per pole on terminal or fuse block on units with single point box. See Fig. 20 and unit label diagram for field C12285 power wiring connections. Fig. 24 -- Location of HACR Enclosure Provide a ground--fault and short--circuit over--current To field install the HACR shaft and handle: protection device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for 1. Remove the unit front panel (see Fig. 2). MOCP (Maximum Over--current Protection) device size. 2. Remove (3) hexagon screws on the front cover -- (2) NOTE: Units ordered with factory installed HACR do on the face of the cover and (1) on the left side cover. not need an additional ground--fault and short--circuit 3. Remove the front cover of the HACR enclosure. over--current protective device unless required by local 4. Make sure the HACR shipped from the factory is at codes. OFF position (the white arrow pointing at OFF). All field wiring must comply with the NEC and local 5. Insert the shaft all the way with the cross pin on the requirements. top of the shaft in the horizontal position. 6. Tighten the locking screw to secure the shaft to the All units except 208/230-v units are factory wired for the HACR. voltage shown on the nameplate. If the 208/230-v unit is 7. Turn the handle to the OFF position with red arrow to be connected to a 208-v power supply, the control transformer must be rewired by moving the black wire pointing at OFF. 1 with the /4-in. female spade connector from the 230--v 8. Install the handle on to the painted cover horizontally 1 connection and moving it to the 200-v /4-in. male with the red arrow pointing to the left. terminal on the primary side of the transformer. Refer to 9. Secure the handle to the painted cover with (2) screws unit label diagram for additional information. and lock washers supplied. NOTE: Check all factory and field electrical connections 10. Engaging the shaft into the handle socket, re--install for tightness. (3) hexagon screws on the front cover. 11. Re--install the unit front panel.

19 Convenience Outlets — and align with the gasket; tighten the two screws until snug (do not over-tighten). ! Mount the weatherproof cover to the backing plate as WARNING shown in Fig. 27. Remove two slot fillers in the bottom of ELECTRICAL OPERATION HAZARD the cover to permit service tool cords to exit the cover. Check for full closing and latching. Failure to follow this warning could result in personal injury or death. COVER – WHILE-IN-USE RECEPTACLE WEATHERPROOF NOT INCLUDED Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and switch to off position. Lock--out and tag--out this switch, if necessary.

Two types of convenience outlets are offered on 50LC models: Non--powered and unit--powered. Both types provide a 125--volt GFCI (ground--fault circuit--interrupter) duplex receptacle rated at 15--A behind a hinged waterproof access cover, located on the 50LC end panel of the unit. See Fig. 26. BASE PLATE FOR NOTE: Unit powered convenience outlets are not GFCI RECEPTACLE available as factory installed options for single phase (--3 C09022 voltage code) models. Fig. 27 -- Weatherproof Cover Installation Pwd-CO Convenience Transformer Outlet Non--powered type: This type requires the field GFCI installation of a general--purpose 125--volt 15--A circuit powered from a source elsewhere in the building. Observe

Pwd-CO national and local codes when selecting wire size, fuse or Fuse breaker requirements and disconnect switch size and Switch location. Route 125--v power supply conductors into the bottom of the utility box containing the duplex receptacle. Unit--powered type: A unit--mounted transformer is factory--installed to stepdown the main power supply voltage to the unit to 115--v at the duplex receptacle. This option also includes a manual switch with fuse, located in Control Box a utility box and mounted on a bracket behind the Access Panel convenience outlet; access is through the unit’s control box access panel. See Fig. 26. C08128 Fig. 26 -- Convenience Outlet Location The primary leads to the convenience outlet transformer are not factory--connected. Selection of primary power source is Installing Weatherproof Cover: A weatherproof a customer--option. If local codes permit, the transformer while-in-use cover for the factory-installed convenience primary leads can be connected at the line--side terminals on outlets is now required by UL standards. This cover the unit--mounted non--fused disconnect or HACR breaker cannot be factory-mounted due its depth; it must be switch; this will provide service power to the unit when the installed at unit installation. For shipment, the unit disconnect switch or HACR switch is open. Other convenience outlet is covered with a blank cover plate. connection methods will result in the convenience outlet circuit being de--energized when the unit disconnect or The weatherproof cover kit is shipped in the unit’s control HACR switch is open. See Fig. 28. box. The kit includes the hinged cover, a backing plate and gasket. Using unit--mounted convenience outlets: Units with DISCONNECT ALL POWER TO UNIT AND unit--mounted convenience outlet circuits will often require CONVENIENCE OUTLET. LOCK--OUT AND TAG--OUT that two disconnects be opened to de--energize all power to ALL POWER. the unit. Treat all units as electrically energized until the Remove the blank cover plate at the convenience outlet; convenience outlet power is also checked and discard the blank cover. de--energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience Loosen the two screws at the GFCI duplex outlet, until 1 outlets. approximately /2-in (13 mm) under screw heads are exposed. Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole slots

20 HACR — The amp rating of the HACR factory installed option is based on the size, voltage, indoor motor and other electrical options of the unit as shipped from the factory. If field installed accessories are added or changed in the field (i.e. electric heat, power exhaust, ERV), the HACR may no longer be of the proper amp rating and therefore will need to be removed from the unit. See unit nameplate and label on factory installed HACR for the amp rating of the HACR that was shipped with the unit from the factory. See unit nameplates for the proper fuse, HACR or maximum over--current protection device required on the unit with field installed accessories.

C08283 UNIT CONNECT PRIMARY TRANSFORMER VOLTAGE AS CONNECTIONS TERMINALS

208, L1: RED +YEL H1 + H3 50LC 240 230 L2: BLU + GRA H2 + H4 L1: RED H1 460 480 Splice BLU + YEL H2 + H3 L2: GRA H4 L1: RED H1 575 600 L2: GRA H2 Fig. 28 -- Powered Convenience Outlet Wiring

Fuse on power type: The factory fuse is a Bussman C12105 “Fusetron” T--15, non--renewable screw--in (Edison base) Fig. 30 -- HACR Caution Label type plug fuse. Factory--Option Thru--Base Connections — 1 NOTICE This service connection kit consists of two /2-- i n 3 electrical bulkhead connectors and a /4--in electrical Convenience Outlet Utilization bulkhead connector, all factory--installed in the embossed (raised) section of the unit basepan in the condenser Maximum Continuous use : 8 Amps 24/7 3 section. The /4--in bulkhead connector enables the

50HJ542739 B low--voltage control wires to pass through the basepan. 1 The /2--in electrical bulkhead connector allows the C13415 high--voltage power wires to pass through the basepan. Fig. 29 -- Convenience Outlet Utilization Notice Label See Fig. 31. Duty Cycle: the unit--powered convenience outlet has a duty cycle limitation. The transformer is intended to LOW VOLTAGE provide power on an intermittent basis for service tools, CONDUIT lamps, etc; it is not intended to provide 15--amps loading CONNECTOR for continuous duty loads (such as electric heaters for overnight use). Observe a 50% limit on circuit loading above 8--amps.

Convenience outlet usage rating: HIGH VOLTAGE CONDUIT Continuous usage: 8 amps maximum CONNECTOR Test the GFCI receptacle by pressing the TEST button on the face of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip as required. Press the C13412 RESET button to clear the tripped condition. Fig. 31 -- Thru--Base Connection Fittings

Check tightness of connector lock nuts before connecting electrical conduits.

21 Field--supplied and field--installed liquid tight conduit insulated wire [35_C(95_F) minimum]. For over 75 ft. connectors and conduit may be attached to the connectors on (23 m), use no. 14 AWG insulated wire [35_C(95_F) the basepan. Pull correctly rated high voltage and low minimum]. All wire sizes larger than no. 18 AWG cannot voltage through appropriate conduits. Connect the power be directly connected to the thermostat and will require a conduit to the internal disconnect (if unit is so equipped) or junction box and splice at the thermostat. to the external disconnect (through unit side panel). A hole must be field cut in the main control box bottom on the left Ttypical Central Thermostat Terminal side so the 24--v control connections can be made. Connect Corrections Board the control power conduit to the unit control box at this hole. X Units without Thru--Base Connections — C C 1. Install power wiring conduit through side panel T openings. Install conduit between disconnect and G G H control box. E R 2. Install power lines to terminal connections as shown W2 W2 in Fig. 20. (Note 3) M O W1 Voltage to compressor terminals during operation must be W1 S within voltage range indicated on unit nameplate. See T Tables 5 and 6. On 3--phase units, voltages between O/B/Y2 Y2 A (Note 1) (Note 2) 50LC phases must be balanced within 2% and the current within T 10%. Use the formula shown in the legend for Tables 5 Y1 Y1 and 6, Note 2 to determine the percent of voltage R R imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may Note 1: Typical multi-function marking. Follow manufacturer’s configuration cause damage to electrical components. Such operation instructions to select Y2. would invalidate any applicable Carrier warranty. Note 2: Y2 to Y2 connection required for 2 stage cooling operation and when integrated economizer function is desired Field Control Wiring — Note 3: W2 connection not required on units with single-stage heating.

The 50LC unit requires an external temperature control Field Wiring device. This device can be a thermostat (field--supplied) C12127 Fig. 32 -- Low--Voltage Connections or, the RTU Open Controller for Building Management Systems using non--CCN protocols (RTU Open is available as a factory--installed option only)., or a space Unit without Thru--Base Connection Kit — temperature sensor (SPT) with factory installed Pass the thermostat control wires through the hole ComfortLINK controller. provided in the corner post; then feed the wires through Thermostat — the raceway built into the corner post to the control box. Pull the wires over to the terminal strip on the upper--left Select a Carrier--approved accessory thermostat. When corner of the Controls Connection Board. See Fig. 33. electric heat is installed in the 50LC unit, the thermostat NOTE: If thru--the--bottom connections accessory is must be capable of energizing the G terminal (to energize used, refer to the accessory installation instructions for the Indoor Fan Contactor) whenever there is a space call information on routing power and control wiring. for heat (energizing the W1 terminal). The accessory thermostats listed on the unit price pages can provide this RACEWAY signal but they are not configured to enable this signal as shipped. Install the accessory thermostat according to installation instructions included with the accessory. Locate the thermostat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the thermostat installation instructions. If the thermostat contains a logic circuit requiring 24--v power, use a thermostat cable or equivalent single leads of different colors with minimum of seven leads. If the thermostat does not require a 24--v source (no “C”

connection required), use a thermostat cable or equivalent HOLE IN END PANEL (HIDDEN)

with minimum of six leads. Check the thermostat C08027 installation instructions for additional features which Fig. 33 -- Field Control Wiring Raceway might require additional conductors in the cable. For wire runs up to 50 ft. (15 m), use no. 18 AWG (American Wire Gage) insulated wire [35_C(95_F) minimum]. For 50 to 75 ft. (15 to 23 m), use no. 16 AWG 22 DISCONNECT EMT OR RIGID CONDUIT SINGLE CENTER MANUAL RESET Heat Anticipator Settings — MOUNTING (FIELD-SUPPLIED) POINT BOX POST LIMIT SWITCH LOCATION HEATER Set heat anticipator settings at 0.14 amp for the first stage COVERS and 0.14 amp for second--stage heating, when available.

Electric Heaters

50LC units may be equipped with factory or field--installed electric heaters. The heaters are modular in design, with heater frames holding open coil resistance wires strung through ceramic insulators, line--break limit and a control contactor. One or two heater SINGLE POINT MAIN BRACKET AND BOX HEATER HEATER HEATER modules may be used in a unit. CONTROL CONDUIT MOUNTING MODULE MODULE MOUNTING BOX DRIP BOOT SCREW (LOCATION 1) (LOCATION 2) BRACKET Heater modules are installed in the compartment below CONTROL WIRE TERMINAL BLOCK the indoor (supply) fan outlet. Access is through the C08134 indoor access panel. Heater modules slide into the Fig. 35 -- Typical Component Location compartment on tracks along the bottom of the heater opening. See Fig. 34, Fig. 35 and Fig. 36. Not all available heater modules may be used in every unit. Use only those heater modules that are UL listed for 50LC use in a specific size unit. Refer to the label on the unit cabinet for the list of approved heaters. Unit heaters are marked with Heater Model Numbers. But heaters are ordered as and shipped in cartons marked with a corresponding heater Sales Package part number. See Table 2 for correlation between heater Model Number and Sales Package part number. TRACK NOTE: The value in position 9 of the part number differs between the sales package part number (value is 1) and a bare heater model number (value is 0). FLANGE

DISCONNECT MOUNTING LOCATION

C08135 Fig. 36 -- Typical Module Installation

INDOOR UNIT BLOCK-OFF OUTDOOR ACCESS PANEL ACCESS PANEL PANEL

C08133 Fig. 34 -- Typical Access Panel Location (3--5 Ton)

Table 2 – Heater Model Number

Bare Heater Model Number C R H E A T E R 0 0 1 A 0 0

Heater Sales Package PNO Includes: Bare Heater C R H E A T E R 1 0 1 A 0 0 Carton and packing materials Installation sheet

23 Single Point Boxes and Supplementary Fuses — CTB

When the unit MOCP device value exceeds 60--A, CONTL unit--mounted supplementary fuses are required for each BOARD heater circuit. These fuses are included in accessory 2 VIO Single Point Boxes, with power distribution and fuse blocks. The single point box will be installed directly 3 under the unit control box, just to the left of the partition ORN separating the indoor section (with electric heaters) from the outdoor section. The Single Point Box has a hinged 12 BRN access cover. See Fig. 37. The Single Point Box also includes a set of power taps and pigtails to complete the ORN VIO BRN wiring between the Single Point Box and the unit’s main control box terminals. Refer to the accessory heater and TB4 132 Single Point Box installation instructions for details on tap connections or field installed electric heat accessory. VIOVIO BRN BRN Field All fuses on 50LC units are 60--A. (Note that all heaters Connections are qualified for use with a 60--A fuse, regardless of actual for Field-Installed Electric Heat Elec Htr heater ampacity, so only 60--A fuses are necessary.) VIOHR2 BRN

50LC Single Point Boxes without Fuses — VIOHR1 BRN Some unit heater applications not requiring supplemental fuses require a special Single Point Box without any fuses. HR1: On Heater 1 in Position #1 The accessory Single Point Boxes contain a set of power HR2: On Heater 2 in Position #2 (if installed)

taps and pigtails to complete the wiring between the C12106 Single Point Box and the unit’s main control box Fig. 38 -- Accessory Electric Heater Control Connections terminals. Refer to accessory heater and Single Point Box (all units except size 06, 575V) -- 2 Stage Heat Shown installation instructions for details on tap connections or field installed electric heat accessory. Size 06, 575V units only:

CONTROL Pull the low--voltage control leads from the heater

2 1

1 1

2 13 BOX 3 module(s) -- VIO, WHT and BRN (two of each if two BUSHING modules are installed; identify for Module #1) -- to the 4--pole terminal board TB4 located on the heater bulkhead SINGLE to the left of Heater #1. Connect the WHT lead from POINT BOX MOUNTING Heater #1 to TB4 where ORN is. For 2 stage heating, SCREWS connect the VIO lead from Heater #2 to the terminal that DRIP BOOT has VIO from the unit. For 1 stage heating with 2 heater BRACKET MOUNTING modules connect the VIO lead from Heater #2 to the same SCREWS terminal with WHT lead from Heater #1 (see Fig. 39). POWER

WIRES CONTROL 21

23 BOARD 11 FOAM 13 ALLIED PA CORP. MODEL NO. OD BUSHING ERIAL NO. 22.2 ISTED AIR NDITIONING 1 UIP ACCESS 23 346N. 3 12 P / N 2- 5610-4 REV HEATER TO 24V TRANS RELAYS 2 HEATER MOUNTING 3 SCREWS VIO BRN RED C08136 ORN Fig. 37 -- Typical Single Point Installation

TB4 Low--Voltage Control Connections —

All units except size 06, 575V: BRN Pull the low--voltage control leads from the heater module(s) BRN -- VIO and BRN (two of each if two modules are installed; Field Connections RED for Field Installed identify for Module #1) -- to the 4--pole terminal board TB4 Electric Heat LS located on the heater bulkhead to the left of Heater #1. Connect the VIO lead from Heater #1 to terminal TB4--1. VIO HCR2 HC2 For 2 stage heating, connect the VIO lead from Heater #2 to terminal TB4--2. For 1 stage heating with 2 heater modules WHT HCR1 HC1 connect the VIO lead from both Heater #1 and #2 to

terminal TB4--1. Connect both BRN leads to terminal C12107 TB4--3. See Fig. 38. Fig. 39 -- Accessory Electric Heater Control Connections (Size 06, 575V only) -- 2 Stage Heat Shown 24 Humidi--MiZerR Control Connections

Humidi--MiZer – Space RH Controller — The Humidi--MiZer dehumidification system requires a field--supplied and --installed space relative humidity control device. This device may be a separate humidistat control (contact closes on rise in space RH above control setpoint) or a combination thermostat--humidistat control device such as Carrier’s EDGER Pro Thermidistat with isolated contact set for dehumidification control. The humidistat is normally used in applications where a % RELATIVE HUMIDITY temperature control is already provided (units with PremierLinkt control). C09295 To connect the Carrier humidistat (HL38MG029): Fig. 40 -- Accessory Field--Installed Humidistat 1. Route the humidistat 2--conductor cable (field--sup- plied) through the hole provided in the unit corner post. 2. Feed wires through the raceway built into the corner

post (see Fig. 33) to the 24--v barrier located on the 50LC left side of the control box. The raceway provides the UL--required clearance between high--voltage and low--voltage wiring. 3. Use wire nuts to connect humidistat cable to the leads in the low–voltage wiring (as shown in Fig. 42), con- necting PKN to PNK and PNK/BLK to PNK/BLK. To connect the Thermidistat device (33CS2PPRH--03): 1. Route the Thermidistat multi--conductor thermostat cable (field--supplied) through the hole provided in the unit corner post. 2. Feed wires through the raceway built into the corner

post (see Fig. 33) to the 24--v barrier located on the ® left side of the control box. The raceway provides the UL--required clearance between high--voltage and low--voltage wiring. C09296 3. The Thermidistat has dry contacts at terminals D1 Fig. 41 -- EDGE Pro Thermidistat and D2 for dehumidification operation (see Fig. 43). The dry contacts must be wired between CTB terminal R and the PNK/BLK lead to the LTLO switch with field--supplied wire nuts. Refer to the installation instructions included with the Carrier Edge Thermidistat device (Form 33CS--74SI or latest) for more information.

25 TRAN FROM POWER SCHEMATIC

1 DHRA BRN CB PNK 1 J2 FIOP/ PL19- HR1 POWER 24V 24V BRN 5 CONTROL BD 2 1 ACCESSORY 10 BRN BRN 3.2 AMPS LTLO YEL 2 DHRB 1 RED 24 VAC 1 RED GRN/YEL HR1 RETURN RED RED 3 2 9 BRN BRN 3 2 BLK SMOKE RJ-45 2 DHRB2 3 SENSOR 16 ORN ORN BRN 24V TRAN 4 NC 4 BRN 3 BLU PNK/ 4 SUPPLY 6 BLU BLU BLK 4 3 BRN 12 CONTROL BD 5 4 YEL SMOKE RJ-45 NO GRA 5 DHRB 17 WHT WHT SENSOR BRN HC1 PNK/ 5 5 6 5 14 YEL YEL BRN HC2 BLK GRA 6 CR1 TB4 PNK 6 6 7 6 TROUBLE 3 PNK PNK NOTE 7 ELECTRIC WHT DHRB2 7 7 CB NC 7 HEAT (ACCESSORY) 8 7 5 GRA GRA WHT 8 ALARM 8 VIO VIO HC2 BRN TB4 NO 4 GRN GRA 9 CR1 9 NOTE 6 RED 9 SMOKE CONTROL HU ORN VIO HC1 BRN 10 FROM MODULE TB4 ORN 10 DHRA CR2 POWER FIOP/ACCESSORY HUMIDISTAT 11 REHEAT SCHEMATIC SEE DETAIL A FOR 5 TON ORN 11 CR2 ACCESSORY CONTROL TRAN2 J1 BRN RED BRN BRN CTB-C RDV BRN BLU 24V LOGIC CLV COFS (FIOP) BRN BLK GRN/YEL RLV BRN COFS BRN YEL BRN TB4 BRN

460/575V ONLY RED LSM PNK RED BRN CCHTS BRN ORN BLU RED BRN WHT YEL RED GRA CCHR BLK BLK RED RED PNK BRN BRN GRA PNK RED BRN 3 2 1 C GRA PMR FOR FIELD USE SMOKE SMOKE ALARM REMOTE SHUTDOWN SHUTDOWN PMR 24V OUT R (SEE NOTE 1) C UNIT FIOP/ BRN GRA ORN BRN BRN RED RED RED BLK DDC VIO GRA RED JMP4 JMP3 SHUTDOWN ACCY JMP1

ONLY 1 5 2 4 7 11 12 9 10 8 6 CTB 3 PNK CONT

FIELD OCCUPANCY RED 24V

CONTROL DDC 2 5 6 7 8 1 3 4 9 10 11 12 JMP2 BRD BRN COM

WIRING CNTL

CLO1/ BRN C COMP1 1 FPT 1 BLU BRN 1 1 BLU BLK BLK 2 2 BLU COFS (FIOP) WHT 2 2 X 3 BLU C BRN 3 CLO1 TERM BD DDC 3 BRN BLU GRY BRN C T'STAT C 4 DD IFM 3 4 LAS1 GRN 3 BLU BLU G 5 4 5 VIO PNK 4 W2 SAT/OAT 6 5 ORN 5 6 BLU HPS1 LPS1 1 4 W1 2 3

6 CKT 1 YEL 6 Y2 CLO2/ 7 1 2 3 4 COMP2 BLK BLK BLU BLU

50LC BLU 7 Y1 1 HPS LPS PNK VIO BRN ORN

JMP6 R 2 BRN BRN LDR

THERMO- 3 BRN OFR1 WHT 1 STAT 1 4 (SEE NOTE 3) WHT 2 VIO BLK LDR BRN CLO2/ 2 5 COMP2 3 -2

YEL 4 6 BLK HPS2 LPS2 4 SEE NOTE 5

GRA 5 CKT 2 YEL (J1-6) 5 7 1 2 3 4 7 8 9 5 6 10 VIO ORN GRA 6

(J1-5) 6 JMP5 ECON PNK/BLK OFR2 BRN BRN CLO2/COMP2-2 1 9 5 2 4 7 8 6 ORN 7 3 (J1-11) 10 BRN LCTB C

ORN 8 BLU GRA ORN YEL BLK PNK BRN RED YEL OFR1 BRN GRA (J1-10) JMP7 GRA DDC BRN REHEAT SF 11 12 BLU YEL BRN WHT O 14 YEL YEL 1 2 3 4 5 6 7 8 9 10 OFR2 DDC WHT F WHT WHT 9 7 8 6 1 5 2 4 3 10 11 12 OFM GRA PNK PNK BRN RED GRA VIO ORN RED BLU OFR1 BLK M HIGH BLU GRA YEL VOLTAGE GRA GRN/ C LAS3 YEL 48HC500324 -

C13419 Fig. 42 -- Typical Humidi--MiZerR Adaptive Dehumidification System Humidistat Wiring

Edge Programable Thermostat Unit CTB THERMOSTAT

Rc X* Rh C W1 G G Y2 W2 C O/W2/B W1 Y1 Y2

Y1

OAT R RRS SRTN Humidi-MiZer™ FIOP HUM D1 D2 V+ Vg

*Connection not required. C13066 Fig. 43 -- Typical Rooftop Unit with Humidi--MiZer Adaptive Dehumidification System with EDGE Pro Thermidistat Device

26 EconoMi$er X (Factory--Option) ComfortLINK (Factory--Option)

For details on operating 50LC units equipped with the For details on operating 50LC units equipped with the factory--installed EconoMi$er X option, refer to factory installed ComfortLINK option, refer to Controls, EconoMi$er X Factory--Installed Option Low Leak Start--Up, Operation and Troubleshooting for 48/50LC Economizer for 2 Speed SAVt (Staged Air Volume) 04--06 Single Package Rooftop Unit with ComfortLINK Systems (Catalog No. LLECON--02SI, or later). Controls (Catalog No. 48--50LC--C01T, or later). 50LC

C12108 Fig. 44 -- 50LC Control Box Component Locations with ComfortLINK

27 50LC NOTE: 575V 3 PH label) 460V, See 48HC500165 (50LC 04-06 ComfortLink Power 208/230V, for all “NOTE” references in the wiring diagram above.

C12109 Fig. 45 -- ComfortLINK Control Wiring Diagram

28 RTU Open Control System The RTU Open controller is an integrated component of the Carrier rooftop unit. Its internal application programming The RTU Open control is factory--mounted in the 50LC provides optimum performance and energy efficiency. RTU unit’s main control box, to the left of the CTB. See Open enables the unit to run in 100% stand--alone control Fig. 47. Factory wiring is completed through harnesses mode, Carrier’s I--Vu Open network, or a Third Party connected to the CTB. Field connections for RTU Open Building Automation System (BAS). On--board DIP sensors will be made at the Phoenix connectors on the switches allow you to select your protocol (and baud rate) of RTU Open board. The factory--installed RTU Open choice among the four most popular protocols in use today: control includes the supply--air temperature (SAT) sensor. BACnet, Modbus, Johnson N2 and LonWorks. (See Fig. 46.) The outdoor air temperature (OAT) sensor is included in Refer to Table 3, RTU Open Controller Inputs and Outputs the FIOP/accessory EconoMi$er2 package. for locations of all connections to the RTU Open board. Input _8 (Enthalpy)

Input_1 (CO2/RH) Input_2 (CO2/RH) Board Power 24 VAC IN Input_3 Gnd DO-1 (X) DO-2 DO-3 DO-4 (G) DO-5 Input_4 Input_5 (SMK) (Y2) (Y1) (R) AO-1 (ECON) +24 VDC +24 VDC Configurable - Input_3 Configurable - Input_5 Configurable - Input_8 24 VAC Input_9 (Humidistat) (OAT) (SAT) (W2) (W1) Gnd Gnd Gnd Gnd (AO-1)

0-10VDC

J4 24 VAC 24 VAC 24 VAC 24 VAC J3 J1 J2 4-20mA 50LC

J5 J5

J22

J11 DO-6 (H) Humidimizer DO-7 J13 (Reversing Valve/High Speed Fan) DO-8 (Power Exhaust)

J12 Lonworks Option Card J17 Port Network Comm

J15 J14 Example set for J19 BACnet MS/TP J20 and 76.8K baud (1, 2, and 4 ON) Recommended for all Protocol Selector*Remove SPT (temp input) BACnet, Modbus, or N2 i-Vu Open installations both for 0-5V SPT (common) (LON connection J15) SPT (offset input) C12751 Fig. 46 -- RTU Open Multi--Protocol Control Board

C12110 Fig. 47 -- 50LC Control Box Component Locations with RTU Open

29 OFM C TRAN CONTROL BD

CONTROL BD CTB-C HC1 HC2 F CLO1 TERM BD DD IFM C O M TB4 TB4 TB4 COFS C LDR CLO2/ COMP2 -2 3 5 C 12 24V WHT GRA

YEL BLK BLU

BRN GRN/ BRN BRN GRA

BRN BRN 48HC500007 CKT 1 CKT CKT 2 CKT YEL BRN BRN WHT RED BRN BRN BRN BRN BRN BRN BRN

C PNK ALARM FOR FIELD USE SMOKE UNIT LPS YEL LPS1 LPS2 LAS HC1 HC2 BLU BLU BLU SHUTDOWN HIGH BLU (SEE NOTE 3) VOLTAGE WHT SF WHT BLK BRN

BLK VIO VIO

ELECTRIC HEAT (ACCESSORY) NOTE 6 C LDR BLK BRN YEL SEE DETAIL A FOR 5 TON HPS BRN

COFS (FIOP)

HPS1 HPS2 24V OUT 24V VIO ORN BLK FPT BRN RED BLU BRN

BLK

BRN

SHUTDOWN BLK

BLU

10 SMOKE

RED JMP3 10 BLU

TB4

DDC NOTE 7

ORN BLU 9

ORN 9

4

ORN 4

SHUTDOWN

VIO 8

BLU BRN BRN 8

REMOTE YEL

BLK

BRN 3 BRN

JMP4 VIO

BRN 2 6 3 1 3 4 5

PMR 7

7 VIO

2

VIO

24V 2

CONT 2 5 6 7 1 3 4 2 4 5 6 1 3 COM 6

FIOP/ACCY PMR BRN 6

SAT/OAT PNK CLO1/ COMP1 CLO2/ COMP2

GRN/YEL

COFS(FIOP) 1

PNK 1 VIO 1 ORN

BRN

BRN RED

LOGIC 2 ECON

PNK

10

3 JMP1 10 RED

24V

BRN DDC

RED 9

BRN BRN 9

BRN C

8

BRN PNK 8

DDC

5

5 RED PNK

CB R 7

7

RED GRA

TRAN FROM POWER SCHEMATIC 3.2 AMPS 4

4 RED GRA

6

OCCUPANCY

6 GRA

24V 3

JMP2

3

SEE NOTE 5 GRA 5

5 BLK

BRN 2 RED

2

RED

4 BRN 12

4 12 YEL

1

LSM 1

BLU RED

RED 11

3

11

3

ORN

RED 10

10

2

2 GRA 9 RED

9

1

8 RED

1 BLU 8

7 GRA

7

6 BLK

6

5 BRN

5

4

50LC BRN

4

3 ORN

ORN 3 CTB

2 VIO

VIO 2

YEL BLU (SEE NOTE 1) PNK BRN RED GRA GRA ORN WHT

1 GRA

4 3 8 9 1 2 6 7 5

BLK 1 BOARD

PL19- CONTL R X C G Y1 Y2 W1 W2 YEL BLU PNK RED BRN GRA ORN GRN WHT CCHTS STAT THERMO- 9 6 3 5 4 17 10 16 14 BLK JMP5 JMP7 NC NO 460/575V ONLY NO MODULE NC CCHR ALARM 2 4 5 6 8 3 7 1 TROUBLE JMP6 7 2 3 6 4 5 1 POWER 24 VAC SMOKE CONTROL RJ-45 RJ-45 FIOP/ACCESSORY DDC T'STAT BRN REHEAT 4 1 2 3 5 6 7 GRA FIOP/ SMOKE SMOKE SUPPLY SENSOR SENSOR RETURN YEL BLU GRA PNK BRN GRN ORN WHT ACCESSORY DDC ONLY FIELD WIRING CONTROL GRA VIO PNK YEL BLU BLK BRN RED GRA PNK VIO GRA PNK GRA 7 6 11 10 8 2 3 4 1 5 9 12 PL6 LOGIC

7 6 8 2 3 4 1 5 9

11 10 12

BLU PL6-R I YEL C R R VIO NC NO PNK ORN SPT IFM TDR CONTROL WHT BLK RED RED RED BRN GRA BLK BRN RED YEL ORN BRN RESISTOR PL18-1 PL18-2 GRN ORN YEL PNK BLU BRN WHT 1 2 3 4 7 5 6 ORN ESL BLK 500 RED RED BRN (FIOP/ ACCY) CTB GRA HC1 1 2 ESL OAT TB4 12 7 6 5 DDC HARNESS 2 1 4 3 GRA IAQ BLK RED GRA GRA (FIOP/ ACCY) YEL PNK BLU GRN ORN BRN WHT HC1 BRN 6 7 24V BRN GRN WHT RED BLK ORN LOW L5 3 2 BRN TR TR1 ACCU- BRN SENSOR

BLK BLU GND DETAIL A (ACCY) ENTHALPY 1 2 3 5 BLK 33CSENTHSW HCR1 HCR2 RED ELECTRIC HEAT FIOP/ACCY RED ENTHALPY (FIOP/ACCESSORY) YEL YEL ECONO MOTOR BRN 5 TON 575V "C" HEAT ONLY RED BRN VIO SAT WHT PL18-3 PL18-4 NOTE 6 ECONOMIZER (FIOP/ ACCESSORY) BLK DDC T'STAT TO CTB TB4 BLK BLU NOTE 7 PNK/BLK (NOT USED) YEL BRN GRA ORN VIO RED ORN 1 2 3 4 5 J1 1 3 5 2 4 24V TO TRANS HUMIDITY JW1 JW2 VFD FAN BOARD R RED CTB 6 5 4 3 2 1 OAQ (ACCY) RELATIVE J2 2 6 3 BLK BLU OR YEL PNK RED WHT PNK ORN YEL BLU BRN ORN PNK RED WHT BRN GRN RED BLU GRA GRA VIO PNK R CTB - + + - HIGH VOLTAGE RED 3 6 2 2 8 1 3 4 5 7 1 4 7 9 6 5 10 J3 TO "C" COIL HUMIDISTAT (ACCESSORY) 2 1 4-20mA 3 5 6 4 0-10VDC YEL BLK BRN J2 J1 J4 GRN/YEL PNK J5 PNK L N C G YEL PNK WHT YEL LSB 2 1 WHT 3 7 5 8 6 4 3 2 4 5 6 5 TAN GRA G HI Y1 Y2 W1 W2 4 MSB 3 1 PL25 ECM 4 J12 2 PORT H ACCESS LO 1 ACCESSORY YEL BLU PNK PNK BLU PNK WHT TAN GRA TO POWER EXHAUST 4 J15 RELAYS SEE 10 11 12 13 14 15 16 NOTE S DD IFM COMM OPTION C CTB 4 J11 VFD 3 J14 PE

2 8 PROTOCOL SELECTOR PROTOCOL COMM SPACE YEL WHT SENSOR 1 1 7 3 PH IFM 6 2 5 8 7 6 5 4 3 2 1 J13 SW3 3 RED J17 4

J21 4

BT485 3 NOTE 8 NOTE 2 1 4 3 3 1 2 RTU OPEN RTU GRA YEL 5 2 RED 1 6 J20 J19 D SEN T-55 SEN 48HC500174 ACCESSORY T-56 ACCESSORY SET (OR) GND 12V Rnet- Rnet+ SHLD NET+ NET- TO SIMPLIFY CIRCUIT TRACES. DETECTORS, PHASE LOSS RELAY, OCCUPANCY AND REMOTE SHUTDOWN. RECTIFIER TO CONVERT AC DC. LO=1 HI=2. RELOCATION OF SIGNAL CONNECTION MAY BE REQUIRED WHEN USING FIELD INSTALLED ACCESSORIES - CONSULT INSTALLATION INSTRUCTIONS FOR PROPER SELECTION. PINS 6, 7, AND 8. MOVE VIOLET HEATER WIRE FROM TB4-VIOLET WIRE TO TB4-ORANGE WIRE. YELLOW AND WHITE WIRES. DISCONNECT FOR NORMAL OPERATIONS. 50LC CONTROL RTU-OPEN 208/230V,460V,575V 3-5 TON NOTES: 1. TERMINAL BOARD SCHEMATIC LAYOUT DOES NOT MATCH ACTUAL 2. ENSURE DESIGNATED JUMPERS ON TERMINAL BOARD ARE CUT WHEN ADDING SMOKE 3. COMPRESSOR LOADER PLUG CONTAINS BRIDGE 4. FACTORY WIRING FOR SIGNAL CONNECTIONS: 5. WITH DDC OPTION THERE WILL BE WIRES IN 6. FOR SINGLE STAGE ELECTRIC HEAT OPTION, 7. TB4 LOCATED IN HEAT SECTION. 8. FOR HIGH SPEED BLOWER TESTING, CONNECT C13420 Fig. 48 -- RTU Open System Control Wiring Diagram

30 GRA GRA - BRN 24V CONT COM PMR FIOP/ ACCY OFM RED PNK FOR FIELD USE YEL

RED PNK F BRN C O M TRAN CONTROL BD CONTROL BD HC1 HC2 CLO1 TERM BD DD IFM TB4 TB4 TB4 COFS CTB-C OFR1 LDR C CLO2/ COMP2 -2 LCTB C CLO2/COMP2-2 48HC500324 5 3 C 12 WHT 24V YEL YEL BLK BRN BLU GRN/

BRN

BRN

BRN BRN BLK BRN BRN

BRN 1 CKT BRN CKT 2 CKT WHT SF YEL FPT BRN BRN BRN BRN BRN BRN BRN

C BLU ALARM

BRN YEL BLK GRN/YEL HIGH SMOKE LPS UNIT COFS (FIOP) ORN LPS1 LPS2 GRY VOLTAGE HC1 HC2 24V BLU SHUTDOWN

BLU BLU (SEE NOTE 3) LOGIC WHT BLU BRN

BLK VIO VIO SEE DETAIL A FOR 5 TON NOTE 6

ELECTRIC HEAT (ACCESSORY) C LDR LAS1 VIO HPS

CB

HPS1 BRN HPS2 BRN 24V OUT 24V BLU GRA BRN RED BLK BRN YEL BLU COFS (FIOP) TRAN FROM POWER SCHEMATIC BLK

12 14 12 BRN 3.2 AMPS BLU SHUTDOWN

TB4 NOTE 7 SMOKE OFR2 LAS3 BLU BLU 24V JMP3 OFR1 OFR1 ORN BLU RED BRN OFR2 WHT 11 ORN 11 VIO

RED GRA

SHUTDOWN WHT

YEL VIO BLU BRN REMOTE PNK/BLK BLK BRN BRN VIO 5 6 1 3 4 2 JMP4

2 3 4 5 6 7 5 6 1 2 3 4 1

PMR

YEL 10 BLU PNK BRN RED GRA GRA ORN WHT

RED CLO1/ COMP1 10 CLO2/ COMP2

6 7 1 2 4 3 8 9 5

DDC 1

PL19- 9 BRN ORN 9 2

RED YEL PNK BRN

GRN GRA

ORN BLU WHT

RED

8

BRN 8 3 JMP1

PNK

6 5 3 4 9

14 10 17 16

7

7 VIO

ECON C

BRN 6

10

6

NC PNK NO BRN DDC 10 RED

NO

NC MODULE

RED ALARM R

TROUBLE 9

POWER 24 VAC 4 SMOKE CONTROL RJ-45 RJ-45 RED

FIOP/ACCESSORY BRN 9 ORN 4

RED

DDC

OCCUPANCY

8

PNK 3 PNK 8

BRN

JMP2 3

BRN 7

2

GRA 7

VIO

SMOKE 2 SMOKE BRN SUPPLY

SENSOR SENSOR 24V FIOP/ RETURN

SAT/OAT

12

GRN/YEL BRN

ACCESSORY 6

1

12

6 GRA

PNK 1

CB 5

TRAN2 11

FROM POWER SCHEMATIC RED

5

SEE NOTE 5 PNK BRN 11

5

5 BLK

10 RED

LSM 4

10

4 GRA

4

9 RED 4 YEL

9

RED 3

3

GRA

8 RED

3

3 ORN 8

2

2 7 RED GRA

2

BLK YEL 7 RED BLU

2 GRA

1

6 BLK

7 1 6 1 4 5 2 3 BLU

6

BLK 1

BLU 1 BLU 5 BRN

2 5 1 3 4 7 5 6 50LC J2

4 RDV BRN

4

3

REHEAT CONTROL ORN

BLK 3

2

CR1 VIO CR2

X

R C G 2 W1 W2 Y1 Y2 DHRB2

CLV DHRA DHRB

DHRB2

1 GRA

STAT BRN 1

BRD THERMO-

YEL CNTL JMP5 JMP7 HR1 CR1 CR2 HR1 DHRB DHRA RLV CCHTS BRN BLK J1 8 9 6 7 4 1 2 3 5 10 11 460/575V ONLY 2 3 5 6 4 7 8 1 JMP6 1 4 6 5 2 7 3 8 6 7 9 5 1 2 4 3 11 10 BRN CCHR DDC T'STAT REHEAT 7 6 5 4 1 3 2 BRN RED YEL PNK BRN BRN ORN ORN GRA WHT GRA WHT 1 4 6 2 5 (SEE NOTE 1) CTB ORN BRN WHT BLU GRN PNK YEL ORN ORN (J1-6) (J1-11) (J1-10) GRA GRA (J1-5) WHT WHT YEL YEL PNK BLK PNK/ GRA LTLO HUMID- ISTAT ACCY HU BLK PNK/ DDC ONLY FIELD WIRING CONTROL GRA VIO PNK GRA PNK YEL BLU BLK BRN RED GRA VIO GRA PNK 7 6 11 10 8 2 3 4 1 5 9 12 PL6 LOGIC

7 6 8 2 3 4 1 5 9

11 10 12

BLU PL6-R I YEL C R R VIO NC NO PNK ORN SPT IFM TDR CONTROL WHT BLK RED RED RED BRN GRA BLK BRN RED YEL ORN BRN RESISTOR PL18-1 PL18-2 GRN ORN YEL PNK BLU WHT BRN 1 2 3 4 7 5 6 ORN ESL BLK 500 RED RED BRN (FIOP/ ACCY) CTB GRA HC1 1 2 ESL OAT TB4 12 7 6 5 DDC HARNESS 2 1 4 3 GRA IAQ BLK RED GRA GRA (FIOP/ ACCY) YEL PNK BLU GRN ORN BRN WHT HC1 BRN 6 7 24V BRN GRN WHT RED BLK ORN LOW L5 3 2 BRN TR TR1 ACCU- BRN SENSOR

BLK BLU GND DETAIL A (ACCY) ENTHALPY 1 2 3 5 BLK 33CSENTHSW HCR1 HCR2 RED ELECTRIC HEAT FIOP/ACCY RED ENTHALPY (FIOP/ACCESSORY) YEL YEL ECONO MOTOR BRN 5 TON 575V "C" HEAT ONLY RED BRN VIO SAT WHT PL18-3 PL18-4 NOTE 6 ECONOMIZER (FIOP/ ACCESSORY) BLK DDC T'STAT TO CTB TB4 BLK BLU NOTE 7 PNK/BLK (NOT USED) YEL BRN GRA ORN VIO RED ORN 5 1 2 3 4 J1 1 3 5 2 4 24V TO TRANS HUMIDITY JW1 JW2 VFD FAN BOARD R RED CTB 6 5 4 3 2 1 OAQ (ACCY) RELATIVE J2 2 6 3 BLK BLU OR YEL PNK RED WHT PNK ORN YEL BLU BRN ORN PNK RED WHT BRN GRN RED BLU GRA GRA VIO PNK R CTB - + + - HIGH VOLTAGE RED 3 6 2 2 8 1 3 4 5 7 1 4 7 9 6 5 10 J3 TO "C" COIL HUMIDISTAT (ACCESSORY) 2 1 4-20mA 3 5 6 4 0-10VDC YEL BLK BRN J2 J1 J4 GRN/YEL PNK J5 PNK L N C G YEL PNK WHT YEL LSB 2 1 WHT 3 5 7 6 8 4 3 2 4 5 6 5 TAN GRA G HI Y1 Y2 W1 W2 4 MSB 3 1 PL25 ECM 4 J12 2 PORT H ACCESS LO 1 ACCESSORY YEL BLU PNK PNK BLU PNK WHT TAN GRA TO POWER EXHAUST 4 J15 RELAYS SEE 10 11 15 12 13 14 16 NOTE S DD IFM COMM OPTION C CTB 4 J11 VFD 3 J14 PE

2 8 PROTOCOL SELECTOR PROTOCOL COMM SPACE YEL WHT SENSOR 1 1 7 3 PH IFM 6 2 5 8 7 6 5 4 3 2 1 J13 SW3 3 RED J17 4

J21 4

BT485 3 NOTE 8 NOTE 2 1 4 3 3 1 2 RTU OPEN RTU GRA YEL 5 2 RED 1 6 J20 J19 D SEN T-55 SEN 48HC500174 ACCESSORY T-56 ACCESSORY SET (OR) GND 12V Rnet- Rnet+ SHLD NET+ NET- TO SIMPLIFY CIRCUIT TRACES. DETECTORS, PHASE LOSS RELAY, OCCUPANCY AND REMOTE SHUTDOWN. RECTIFIER TO CONVERT AC DC. LO=1 HI=2. RELOCATION OF SIGNAL CONNECTION MAY BE REQUIRED WHEN USING FIELD INSTALLED ACCESSORIES - CONSULT INSTALLATION INSTRUCTIONS FOR PROPER SELECTION. PINS 6, 7, AND 8. MOVE VIOLET HEATER WIRE FROM TB4-VIOLET WIRE TO TB4-ORANGE WIRE. YELLOW AND WHITE WIRES. DISCONNECT FOR NORMAL OPERATIONS. 50LC CONTROL RTU-OPEN 208/230V,460V,575V 3-5 TON NOTES: 1. TERMINAL BOARD SCHEMATIC LAYOUT DOES NOT MATCH ACTUAL 2. ENSURE DESIGNATED JUMPERS ON TERMINAL BOARD ARE CUT WHEN ADDING SMOKE 3. COMPRESSOR LOADER PLUG CONTAINS BRIDGE 4. FACTORY WIRING FOR SIGNAL CONNECTIONS: 5. WITH DDC OPTION THERE WILL BE WIRES IN 6. FOR SINGLE STAGE ELECTRIC HEAT OPTION, 7. TB4 LOCATED IN HEAT SECTION. 8. FOR HIGH SPEED BLOWER TESTING, CONNECT C13421 Fig. 49 -- RTU Open System Control Wiring Diagram with Humidi--MiZerR 31 Table 3 – RTU Open Controller Inputs and Outputs

BACnet OBJECT CONNECTION PIN POINT NAME TYPE OF I/O NAME NUMBER(S) DEDICATED INPUTS Space Temp / Zone Temp zone_temp AI (10K Thermistor) J 2 0 --- 1 & 2 Supply Air Temperature sa_temp AI (10K Thermistor) J 2 --- 1 & 2 Outdoor Air Temperature oa_temp AI (10K Thermistor) J 2 --- 3 & 4 Space Temperature Offset Pot stpt_adj_offset AI (100K Potentiometer) J 2 0 --- 3 & 4 Safety Chain Feedback safety_status DI (24 VAC) J 1 --- 9 Compressor Safety Status comp_status DI (24 VAC) J 1 --- 2 Fire Shutdown Status firedown_status DI (24 VAC) J 1 --- 1 0 Enthalpy Status enthalpy_status DI (24 VAC) J 2 --- 6 & 7 Humidistat Input Status humstat_status DI (24 VAC) J 5 --- 7 & 8 Zone Temperature n/a n/a J13---1, 2, 3, 4 CONFIGURABLE INPUTS Indoor Air CO2 iaq A I ( 4 --- 2 0 m a ) Outdoor Air CO2 oaq A I ( 4 --- 2 0 m a ) J 4 --- 2 & 3 o r J 4 --- 5 & 6 Space Relative Humidity space_rh A I ( 4 --- 2 0 m a ) Supply Fan Status* sfan_status DI (24 VAC) 50LC Filter Status* filter_status DI (24 VAC) J 5 --- 1 o r J 5 --- 3 o r J 5 --- 5 Door Contact Input* door_contact_status DI (24 VAC) Occupancy Contact* occ_contact_status DI (24 VAC) OUTPUTS Economizer Output econ_output A O ( 4 --- 2 0 m a ) J 2 --- 5 SupplyFanRelayState sfan DO Relay (24VAC , 1A) J 1 --- 4 Compressor 1 Relay State comp_1 DO Relay (24VAC , 1A) J 1 --- 8 Compressor 2 Relay State comp_2 DO Relay (24VAC , 1A) J 1 --- 7 Heat Stage 1 Relay State heat_1 DO Relay (24VAC , 1A) J 1 --- 6 Heat Stage 2 Relay State heat_2 DO Relay (24VAC , 1A) J 1 --- 5 Power Exhaust Relay State pexh DO Relay (24VAC , 1A) J 1 1 --- 1 & 3 Humidimizer Relay State dehum DO Relay (24VAC, 1A) J 1 1 --- 7 , 8 LEGEND AI --- A n a l o g I n p u t AO --- A n a l o g O u t p u t DI --- D i s c r e t e I n p u t DO --- Discrete Output * These inputs (if installed) take the place of the default input on the specific channel according to schematic. P a r a l l e l p i n s J 5 --- 1 = J 2 --- 6 , J 5 --- 3 = J 1 --- 1 0 , J 5 --- 5 = J 1 --- 2 a r e u s e d f o r f i e l d --- i n s t a l l a t i o n .

The RTU Open controller requires the use of a Carrier space sensor. A standard thermostat cannot be used with the RTU Open system. Supply Air Temperature (SAT) Sensor — On FIOP--equipped 48LC unit, the unit is supplied with a supply--air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6--inches (152 mm) in length. It is a nominal 10--k ohm thermistor.

SUPPLY AIR ROOF The SAT is factory--wired. The SAT probe is wire--tied to TEMPERATURE CURB SENSOR the supply--air opening (on the horizontal opening end) in SUPPLY AIR RETURN AIR its shipping position. Remove the sensor for installation. Re--position the sensor in the flange of the supply--air opening or in the supply air duct (as required by local 1 codes). Drill or punch a /2--in. hole in the flange or duct. C08200 Use two field--supplied, self--drilling screws to secure the Fig. 50 -- Typical Mounting Location for Supply Air sensor probe in a horizontal orientation. See Fig. 50. Temperature (SAT) Sensor on Small Rooftop Units

32 Outdoor Air Temperature (OAT) Sensor — The OAT is factory--mounted in the EconoMi$er2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring. 1 2 3 45 6 RED(+) WHT(GND) CCN COM EconoMi$er2 — BLK(-)

The RTU Open control is used with EconoMi$er2 (option SEN or accessory) for outdoor air management. The damper SW1 BRN (GND) SENSOR WIRING position is controlled directly by the RTU Open control; BLU (SPT) EconoMi$er2 has no internal logic device. Outdoor air management functions can be enhanced with field--installation of these accessory control devices: Enthalpy control (outdoor air or differential sensors) Space CO2 sensor Outdoor air CO2 sensor C08201 Fig. 51 -- T--55 Sensor Field Connections

Field connections for accessory sensors and input devices are SEN J20-1 50LC made at the RTU Open, at plugs J1, J2, J4, J5, J11 and J20. All field control wiring that connects to the RTU Open must be routed through the raceway built into the corner post as SEN J20-2 shown in Fig. 33. The raceway provides the UL required C08460 clearance between high-- and low--voltage wiring. Pass the Fig. 52 -- RTU Open T--55 Sensor Connections control wires through the hole provided in the corner post, then feed the wires thorough the raceway to the RTU Open. Connect T--56: See Fig. 53 for T--56 internal connections. Connect to the wires to the removable Phoenix connectors Install a jumper between SEN and SET terminals as and then reconnect the connectors to the board. illustrated. Connect T--56 terminals to RTU Open J20--1, Space Temperature (SPT) Sensors — J20--2 and J20--3 per Fig. 54. There are two types of SPT sensors available from Carrier, resistive input non-communicating (T55, T56, and T59) and Rnet communicating (SPS, SPPL, SPP, and SPPF) sensors. Each type has a variety of options consisting of:

timed override button, set point adjustment, a LCD 1 2 3 45 6 RED(+) WHT(GND) CCN COM screen, and communication tie in. Space temperature can BLK(-) be also be written to from a building network or zoning SEN SET

system. However, it is still recommended that return air SW1 BLK (T56) duct sensor be installed to allow stand-alone operation for BRN (GND) SENSOR WIRING back-up. Refer to the configuration section for details on BLU (SPT)

controller configurations associated with space sensors. JUMPER TERMINALS S 33ZCT55SPT, space temperature sensor with override AS SHOWN button (T--55) S 33ZCT56SPT, space temperature sensor with override Cool Warm button and setpoint adjustment (T--56) C08202 S 33ZCT59SPT, space temperature sensor with LCD Fig. 53 -- T--56 Internal Connections (liquid crystal display) screen, override button, and setpoint adjustment (T--59) SEN J20-1 Use 20 gauge wire to connect the sensor to the controller. The wire is suitable for distances of up to 500 ft. Use a three--conductor shielded cable for the sensor and setpoint SEN J20-2 adjustment connections. If the setpoint adjustment Jumper (slidebar) is not required, then an unshielded, 18 or 20 gauge, two--conductor, twisted pair cable may be used. SET

Connect T--55: See Fig. 51 for typical T--55 internal SET J20-3 connections. Connect the T--55 SEN terminals to RTU Open J20--1 and J20--2. See Fig. 52. C08461 Fig. 54 -- RTU Open T--56 Sensor Connections 33 Connect T--59: The T--59 space sensor requires a separate, To controller isolated power supply of 24 VAC. See Fig. 55 for internal connections at the T--59. Connect the SEN terminal (BLU) to RTU Open J20--1. Connect the COM terminal (BRN) to J20--2. Connect the SET terminal (STO or BLK) to J20--3.

BLK (STO) J20-3 24 Vac Line BRN (COM) J20-2 SENSOR WIRING - + Dedicated Transformer

BLU (SPT) 2 1 J20-1 24 Vac or Vdc SENSOR LEGEND 1 +24 Vac/Vdc OR SET SEN 2 Gnd (-24 Vac/Vdc) 8 7 6 5 4 4 -Thermistor 5 +Thermistor 6 4-20 mA OPB COM- PWR+ 7 SIG COM 8 0-5 Vdc

C12748 50LC Fig. 56 -- Indoor/Outdoor Air Quality (CO2)Sensor POWER (33ZCSPTCO2--01 or 33ZCSPTCO2LCD--01) 24 VAC WIRING Typical Wiring Diagram

NOTE: Must use a separate isolated transformer. To accurately monitor the quality of the air in the C10291 conditioned air space, locate the sensor near a return--air Fig. 55 -- Space Temperature Sensor Typical Wiring grille (if present) so it senses the concentration of CO2 (33ZCT59SPT) leaving the space. The sensor should be mounted in a location to avoid direct breath contact. Indoor Air Quality (CO2) Sensor — Do not mount the IAQ sensor in drafty areas such as near The indoor air quality sensor accessory monitors space supply ducts, open windows, fans, or over heat sources. carbon dioxide (CO2) levels. This information is used to Allow at least 3 ft (0.9 m) between the sensor and any monitor IAQ levels. Several types of sensors are available, corner. Avoid mounting the sensor where it is influenced for wall mounting in the space or in return duct, with and by the supply air; the sensor gives inaccurate readings if without LCD display, and in combination with space the supply air is blown directly onto the sensor or if the temperature sensors. Sensors use infrared technology to supply air does not have a chance to mix with the room air measure the levels of CO2 present in the space air. before it is drawn into the return airstream.

The CO2 sensors are all factory set for a range of 0 to Wiring the Indoor Air Quality Sensor: For each sensor, 2000 ppm and a linear mA output of 4 to 20. Refer to the use two 2--conductor 18 AWG (American Wire Gage) instructions supplied with the CO2 sensor for electrical twisted--pair cables (unshielded) to connect the separate requirements and terminal locations. See Fig. 56 for isolated 24 vac power source to the sensor and to connect typical CO2 sensor wiring schematic. the sensor to the control board terminals. To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 56. Connect the 4--20 mA terminal to RTU Open J4--2 and connect the SIG COM terminal to RTU Open J4--3. See Fig. 57.

OAQ Sensor

SEN J4-5

COM J4-6 24 VAC

C11086 Fig. 57 -- RTU Open / Outdoor CO2 Sensor (33ZCSPTCO2--01 or 33ZCSPTCO2LCD--01) Connections

34 Outdoor Air Quality Sensor Space Relative Humidity Sensor or Humidistat — (PNO 33ZCSENCO2 plus weatherproof enclosure) — Humidi--MiZerR Control Wiring: In units equipped with the Humidi--MiZer option there are two loose wires The outdoor air CO2 sensor is designed to monitor carbon loose in the control box (one PNK and one PNK/BLK) dioxide (CO2) levels in the outside ventilation air and interface with the ventilation damper in an HVAC system. used to control the dehumidification function of the unit. The OAQ sensor is packaged with an outdoor cover. See These wires are meant to be tied to a space humidistat or thermidistat on an electromechanical unit. On RTU Open Fig. 58. The outdoor air CO2 sensor must be located in the economizer outside air hood. equipped units these wires must be connected to J11--7 & 8 to allow the Open board to operate the dehumidification function for the unit. Disconnect the J11 Phoenix style connector from the board and use the plug screws to secure the wires as follows: secure the PNK/BLK wires at pin 7 and the PNK wires at pin 8, and then reconnect the plug to the board at J11. Relative Humidity Sensors (Space or Duct Mounted): The accessory space humidity sensor (33ZCSENSRH-01) or duct humidity sensor (33ZCSENDRH-01) is used to measure the relative humidity of air within the space or return air duct. For wiring distances up to 500 ft (152 m), use a 3--conductor, 18 or 20 AWG shielded cable. The shield must 50LC be removed from the sensor end of the cable and grounded at the unit end. The current loop power for sensor is provided by the RTU Open controller as 24vdc. Refer to the instructions supplied with the RH sensor for the electrical COVER REMOVED SIDE VIEW requirements and terminal locations. RTU Open configurations must be changed after adding an RH sensor. C07135 See Fig. 60 and 61 for typical RH sensor wiring. Fig. 58 -- Outdoor Air Quality Sensor Cover S J4--1 or J4--4 = 24vdc loop power

Wiring the Outdoor Air CO2 Sensor: A dedicated S J4--2 or J4--5 = 4--20mA signal input power supply is required for this sensor. A two--wire cable NOTE: The factory default for dehumidification control is required to wire the dedicated power supply for the is normally open humidistat. sensor. The two wires should be connected to the power supply and terminals 1 and 2. To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the MOUNTING OAQ sensor. See Fig. 56. Connect the 4 to 20 mA HOLES terminal to RTU Open J4--5. Connect the SIG COM WIRING Io Vin Gnd Vo OPENING terminal to RTU Open J4--6.

OAQ Sensor

SEN J4-5

COM J4-6 24 6 SW212345

24 VAC ON C11086 Fig. 59 -- RTU Open / Outdoor CO2 Sensor (33ZCSENCO2) Connections

Vin - J4-1 or J4-4 24Vdc Io - J4-2 or J4-5 -20mA output

C11087 Fig. 60 -- Space Relative humidity Sensor Typical Wiring

35 J4-1 or J4-4 + 24 VDC Supply Voltage

J4-2 or J4-5 (-)4 to 20 mA Current Loop Output to RTU Open Relative Humidity Sensor (Polarized Male Connector) SPAN

ZERO

4-20 VAC GND 0-5V mA or or VDC 0-10V

C10839 50LC Fig. 61 -- Duct Relative Humidity Sensor Typical Wiring

Humidistat: The accessory humidistat provides the RTU Fan Status: The fan status accessory is a field--installed Open insight to the relative humidity in the space. The accessory. This accessory detects when the indoor fan is humidistat reads the RH level in the space and compares it blowing air. When installing this accessory, the unit must be to its setpoint to operate a . The humidistat is a configured for fan status by setting dedicated input on the configurable input 9 and tells the MENUConfigInputsinput3,5,8,or9to Fan Status RTU Open when the RH level is HIGH or LOW. The and normally open (N/O) or normally closed (N/C). Input 8 normal condition for humidity is LOW. or 9 is recommended for easy of installation. Refer to Fig. To wire in the field: 46 and Fig. 48 for wire terminations at J5. S J5--8 = 24 VAC source for dry contact Remote Occupancy: The remote occupancy accessory is S J5--7 = Signal input a field--installed accessory. This accessory overrides the unoccupied mode and puts the unit in occupied mode. Smoke Detector/Fire Shutdown (FSD) — When installing this accessory, the unit must be configured for remote occupancy by setting On 48LC units equipped with factory--installed Smoke MENUConfigInputsinput3,5,8,or9to Remote Detector(s), the smoke detector controller implements the Occupancy and normally open (N/O) or normally closed unit shutdown through its NC contact set connected to the (N/C). unit’s CTB input. The FSD function is initiated via the smoke detector’s Alarm NO contact set. The RTU Open Also set MENUSchedulesoccupancy source to DI controller communicates the smoke detector’s tripped on/off. Input 8 or 9 is recommended for easy of status to the BAS building control. See Fig. 48 (RTU installation. Refer to Fig. 46 and Table 3 for wire Open System Control wiring schematic). terminations at J5. The Fire Shutdown Switch configuration, Power Exhaust (output): The relay used by the RTU MENUConfigInputsinput 5, identifies the normally Open board to control power exhaust is a dry contact open status of this input when there is no fire alarm. which means it does not have 24vac. This 24vac must be connected to the relay to allow it to operate the power Connecting Discrete Inputs — exhaust relay in the PE accessory. A 24vac source must be provided to J11--2 on the RTU Open control board. This Filter Status: The filter status accessory is a can be provided by the unit’s transformer from various field--installed accessory. This accessory detects plugged sources. The “R” terminal on the unit’s low voltage filters. When installing this accessory, the unit must be terminal board (LVTB) is a logical source. Refer to Fig. configured for filter status by setting 46 and Fig. 48 for wire terminations at J11. MENUConfigInputsinput3,5,8,or9to Filter Status and normally open (N/O) or normally closed (N/C). Input 8 or 9 is recommended for easy of installation. Refer to Fig. 46 and Fig. 48 for wire terminations at J5.

36 Communication Wiring --Protocols The RTU Open can be set to communicate on four different protocols: BACnet, Modbus, N2, and LonWorks. General — Switch 3 (SW3) on the board is used to set protocol and baud rate. Switches 1 and 2 (SW1 and SW2) are used to Protocols are the communication languages spoken by set the board’s network address. See Fig. 62 and 63 for control devices. The main purpose of a protocol is to protocol switch settings and address switches. The 3rd communicate information in the most efficient method party connection to the RTU Open is through plug J19. possible. Different protocols exist to provide different See Fig. 64 for wiring. kinds of information for different applications. In the BAS NOTE: Power must be cycled after changing the SW1--3 application, many different protocols are used, depending switch settings. on manufacturer. Protocols do not change the function of a controller; just make the front end user different. Refer to the RTU Open v2 Integration Guide (Catalog No. 11--808--434--01) for more detailed information on protocols, 3rd party wiring, and networking.

SW3 Protocol Selection

PROTOCOL DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 BACnet MS/TP

Unused OFF OFF OFF ON OFF Select Baud Select Baud 50LC (Master) Modbus Unused OFF OFF ON ON OFF Select Baud Select Baud (Slave) N2 Unused OFF OFF OFF ON ON OFF OFF (Slave) LonWorks Unused ON ON OFF ON OFF OFF ON

NOTE: DS = Dip Switch BACnet MS/TP SW3 example shown

Baud Rate Selections BAUD RATE DS2 DS1 9600 OFF OFF 19,200 ON OFF 38,400 OFF ON 76,800 ON ON C07166 Fig. 62 -- RTU Open SW3 Dip Switch Settings

C10815 Fig. 63 -- RTU Open Address Switches

C10816 Fig. 64 -- Network Wiring

37 Local Access computer to the RTU Open board. The link cable connects a USB port to the J12 local access port. This program BACview6 Handheld: The BACview6 is a keypad/display functions and operates identical to the handheld. interface used to connect to the RTU Open to access the RTU Open Troubleshooting — control information, read sensor values, and test the RTU, see Fig. 65. This is an accessory interface that does not Communication LEDs The LEDs indicate if the come with the RTU Open controller and can only be used controller is speaking to the devices on the network. The at the unit. Connect the BACview6 to the RTU Open J12 LEDs should reflect communication traffic based on the local access port. There are two password protected levels baud rate set. The higher the baud rate the more solid the in the display (User and Admin). The user password is LEDs will appear. See Table 4. defaulted to 0000 but can be changed. The Admin NOTE: Refer to Catalog No. 48--50HCTQ--02T (or later) password is 1111 and cannot be changed. There is a 10 for complete configuration of RTU Open, operating minute auto logout if a screen is idle. See Form sequences and troubleshooting information. Refer to RTU 48--50HCTQ--02T (or later), Appendix A for navigation Open v2 Integration Guide (Catalog No. 11--808--434--01) and screen content. for details on configuration and troubleshooting of Virtual BACview: Virtual BACview is a freeware computer connected networks. Have a copy of these manuals program that functions as the BACview6 Handheld. The available at unit start--up. USB Link interface (USB--L) is required to connect a 50LC

Access Port

P1 P1 Protocol Selector RTU Open

J12

Cable P5 P5

BACview6 Local Access Cable

C12749 Fig. 65 -- BACview6 Handheld Connections

38 Table 4 – LEDs The LEDs on the RTU Open show the status of certain functions If this LED is on... Status is... Power RTU Open has power Rx RTU Open is receiving data from the network segment Tx RTU Open is transmitting data over the network segment DO# The digital output is active The Run and Error LEDs indicate control module and network status If Run LED shows... And Error LED shows... Status is... 2 flashes per second Off Normal 2 flashes per second 2 flashes, alternating with Run LED Five minute auto---restart delay after system error 2 flashes per second 3flashes,thenoff Control module has just been formatted 4flashes, Two or more devices on this network have the 2 flashes per second then pause same ARC156 network address Exec halted after frequent system errors or 2 flashes per second On control programs halted 5 flashes per second On Exec start---up aborted, Boot is running 50LC 5 flashes per second Off Firmware transfer in progress, Boot is running 7 flashes per second, alternating with 7 flashes per second Ten second recovery period after brownout Run LED 14 flashes per second, 14 flashes per second Brownout alternating with Run LED Failure. Try the following solutions: S TurnRTUOpenoff,thenon. On On S Format RTU Open. S Download memory to RTU Open. S Replace RTU Open.

Outdoor Air Enthalpy Control Differential Enthalpy Control — (PNO 33CSENTHSW) Differential enthalpy control is provided by sensing and comparing the outside air and return air enthalpy The enthalpy control (33CSENTHSW) is available as a conditions. Install the outdoor air enthalpy control as field--installed accessory to be used with the EconoMi$er2 described above. Add and install a return air enthalpy damper system. The outdoor air enthalpy sensor is part of sensor. the enthalpy control. (The separate field--installed accessory return air enthalpy sensor (33CSENTSEN) is required for Return Air Enthalpy Sensor — differential enthalpy control. See Fig. 66.) Mount the return--air enthalpy sensor (33SENTSEN) in Locate the enthalpy control in the economizer next to the the return--air section of the economizer. The return air Actuator Motor. Locate two GRA leads in the factory sensor is wired to the enthalpy controller harness and connect the gray lead labeled “ESL” to the (33CSENTHSW). See Fig. 67. terminal labeled “LOW”. See Fig. 66. Connect the enthalpy control power input terminals to economizer actuator power 24V RED PL6-1 (24-V) – 4-20 leads RED (connect to 24V) and BLK (connect to GND). Main GND BLK PL6-4 (COM) + VDC Out LOW GRA 7 CTB ECON The outdoor enthalpy changeover setpoint is set at the (P’LINK: to J4-2) or (RTU Open: to J2-6) enthalpy controller. Outside Air Enthalpy Switch

Enthalpy Switch 24V RED PL6-1 (24-V) + 24-36 Return Air GND BLK PL6-4 (COM) VDC In Enthalpy – 4-20 Main Sensor Out

LOW GRA 7 CTB ECON C11161 (P’LINK: to J4-2) or Fig. 67 -- Outside and Return Air Enthalpy Sensor (RTU Open: to J2-6) Wiring Factory Wiring Harness

C11160 Fig. 66 -- Enthalpy Switch (33CSENTHSW) Connections

39 To wire the return air enthalpy sensor, perform the Return Air Smoke Detector following: (as shipped) 1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable to connect the return air enthalpy sensor to the enthalpy controller. 2. Connect the field--supplied RED wire to (+) spade connector on the return air enthalpy sensor and the (+) terminal on the enthalpy controller. Connect the BLK wire to (--) spade connector on the return air enthalpy sensor and the (--) terminal on the enthalpy controller.

Smoke Detectors

Smoke detectors are available as factory--installed options on 48HC models. Smoke detectors may be specified for Supply Air only or for Return Air without or with economizer or in combination of Supply Air and Return Air. All components

50LC necessary for operation are factory--provided and mounted. The unit is factory--configured for immediate smoke detector C12282 shutdown operation; additional wiring or modifications to Fig. 68 -- Return Air Smoke Detector, Shipping Position unit terminal board may be necessary to complete the unit and smoke detector configuration to meet project Additional Application Data — requirements. Refer to Catalog No. HKRNKA--1XA for discussions on Units equipped with factory--optional Return Air smoke additional control features of these smoke detectors detectors require a relocation of the sensor module at unit including multiple unit coordination. installation. See Fig. 68 for the as shipped location. Completing Installation of Return Air Smoke Sensor: 1. Unscrew the two screws holding the Return Air Smoke Detector assembly. See Fig. 69, Step 1. Save the screws. 2. Turn the assembly 90 and then rotate end to end. Make sure that the elbow fitting is pointing down. See Fig. 69, Step 2. 3. Screw the sensor and detector plate into its operating position using screws from Step 1. See Fig. 69, Step 3. 4. Connect the flexible tube on the sampling inlet to the sampling tube on the basepan.

Step 1 Step 2 Step 3

C12283 Fig. 69 -- Completing Installation of Return Air Smoke Sensor

40 90 45 45 45 45 45 53 53 53 53 53 55 55 55 55 55 34 34 34 40 40 40 44 44 44 107 111 LRA 90/90 90/90 90/90 90/90 90/90 107/107 107/107 107/107 107/107 107/107 111/111 111/111 111/111 111/111 111/111 DISC. SIZE 32 16 16 20 23 27 15 15 19 23 26 16 16 20 24 27 14 18 24 14 18 23 14 19 24 FLA 32/32 32/32 35/38 40/43 53/59 32/32 32/32 32/32 35/38 40/43 53/58 33/33 33/33 33/33 37/40 41/45 54/60 40 20 20 25 30 30 20 20 25 25 30 20 20 25 30 30 15 25 30 15 20 30 15 25 30 MAX 40/40 40/40 40/45 45/50 60/70 40/40 40/40 40/40 40/45 45/50 60/70 40/40 40/40 40/40 40/45 45/50 60/70 BRKR HACR FUSE or w/ P.E. (pwrd fr/unit) 17 21 25 29 17 21 25 29 16 18 22 26 30 20 26 20 25 20 26 31.0 15.0 15.0 13.0 13.0 14.0 MCA 31/31 33/35 38/42 43/47 57/64 31/30 31/30 33/35 38/42 43/47 57/64 32/32 32/32 34/36 40/43 45/49 59/65 88 44 44 44 44 44 52 52 52 52 52 54 54 54 54 54 32 32 32 38 38 38 42 42 42 105 109 w/ PWRD C.O. LRA 88/88 88/88 88/88 88/88 88/88 105/105 105/105 105/105 105/105 105/105 109/109 109/109 109/109 109/109 109/109 DISC. SIZE 30 14 14 18 22 26 14 14 18 22 25 15 15 19 23 26 12 16 22 11 16 21 12 17 22 FLA 30/30 30/30 33/36 37/41 51/56 30/29 30/29 30/30 33/36 37/41 51/56 31/31 31/31 31/31 35/37 39/42 52/58 NO P.E. 40 20 20 20 25 30 20 20 20 25 30 20 20 25 25 30 15 20 25 15 20 25 15 20 25 MAX 40/40 40/40 40/40 45/45 60/70 40/40 40/40 40/40 40/40 45/45 60/70 40/40 40/40 40/40 40/45 45/50 60/70 BRKR HACR FUSE or 50LC 16 20 24 28 15 20 24 27 17 21 25 29 18 23 17 23 18 24 29.0 14.0 14.0 15.0 11.0 11.0 12.0 MCA 29/29 30/33 36/39 41/45 55/61 29/28 29/28 30/33 36/39 41/45 55/61 30/30 30/30 32/34 38/41 42/46 57/63 85 43 43 43 43 43 51 51 51 51 51 53 53 53 53 53 32 32 32 38 38 38 42 42 42 102 106 LRA 85/85 85/85 85/85 85/85 85/85 102/102 102/102 102/102 102/102 102/102 106/106 106/106 106/106 106/106 106/106 DISC. SIZE 26 13 13 17 21 24 13 13 17 20 24 14 14 18 21 25 12 16 22 12 16 21 12 17 22 FLA 26/26 26/27 30/33 34/38 47/53 26/26 26/26 26/27 30/33 34/38 47/53 28/27 28/27 28/28 31/34 36/39 49/54 30 15 15 20 25 30 15 15 20 25 30 15 15 20 25 30 15 20 25 15 20 25 15 20 25 MAX 30/30 30/30 35/40 40/45 60/60 30/30 30/30 30/30 35/40 40/45 60/60 30/30 30/30 30/35 35/40 40/45 60/60 BRKR HACR FUSE or w/ P.E. (pwrd fr/unit) 14 19 23 26 14 18 22 26 13 15 19 23 27 18 24 17 23 18 24 26.0 13.0 12.0 12.0 11.0 12.0 MCA 26/26 27/29 32/36 37/41 51/58 26/26 26/26 27/29 32/36 37/41 51/58 27/27 27/27 28/30 34/37 39/43 53/59 83 42 42 42 42 42 50 50 50 50 50 52 52 52 52 52 30 30 30 36 36 36 40 40 40 100 104 LRA 83/83 83/83 83/83 83/83 83/83 100/100 100/100 100/100 100/100 100/100 104/104 104/104 104/104 104/104 104/104 NO C.O. or UNPWR C.O. DISC. SIZE 9 24 12 12 16 20 23 12 12 16 19 23 13 13 17 20 24 10 14 20 14 19 10 15 20 FLA 24/24 24/25 27/31 32/36 45/51 24/24 24/24 24/24 27/30 32/36 45/51 26/25 26/25 26/26 29/32 33/37 47/52 NO P.E. Table 5 – Unit Wire/Fuse or HACR Breaker Sizing Data 30 15 15 20 25 30 15 15 20 25 25 15 15 20 25 30 15 20 25 15 15 25 15 20 25 MAX 30/30 30/30 30/35 35/40 50/60 30/30 30/30 30/30 30/35 35/40 50/60 30/30 30/30 30/30 35/35 40/45 60/60 BRKR HACR FUSE or 13 17 21 25 13 17 21 25 14 18 22 26 16 21 15 21 16 22 9.0 24.0 12.0 11.0 12.0 10.0 10.0 MCA 24/24 24/27 30/33 35/39 49/55 24/24 24/24 24/27 30/33 35/39 49/55 25/25 25/25 26/28 32/35 36/40 51/57 ------7.2 7.2 7.2 9.2 9.2 9.2 FLA 10.6 13.8 16.8 10.6 13.8 16.8 10.6 13.8 16.8 13.8 13.8 13.8 9.2/10.6 9.2/10.6 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 ------6.0 8.8 6.0 8.8 6.0 8.8 9.2 9.2 9.2 11.5 14.0 11.5 14.0 11.5 14.0 13.8 13.8 13.8 Nom (kW) 3.3/4.4 4.9/6.5 6.5/8.7 3.3/4.4 4.9/6.5 6.5/8.7 3.3/4.4 4.9/6.5 6.5/8.7 7.9/10.5 7.9/10.5 7.9/10.5 12.0/16.0 12.0/16.0 12.0/16.0 ELEC. HTR 101A 102A 105A 101A 102A 105A 101A 102A 105A 106A 107A 108A 109A 106A 107A 108A 109A 106A 107A 108A 109A 297A 298A 297A 298A 297A 298A 103B 104B 103B 104B 103B 104B NONE NONE NONE NONE NONE NONE NONE NONE NONE CRHEATER***A00 IFM MED MED MED TYPE HIGH HIGH HIGH

D D --- S T D D D --- S T D D D --- S T D

208/230---3---60 - - Z H --- h P --- V . M O N 0 6 --- 3 --- 0 6 4 575---3---60

UNIT UNIT UNIT - 4 0 0 --- C L 0 5 See “Legend and Notes for Tables 5 and 6” on page 47. 41 49 49 49 49 49 56 56 56 56 56 72 72 72 72 72 42 42 42 47 47 47 60 60 60 101 117 147 LRA 101/101 101/101 101/101 101/101 117/117 117/117 117/117 117/117 147/147 147/147 147/147 147/147 DISC. SIZE 36 17 17 24 28 40 16 16 23 26 39 17 17 24 27 40 16 19 25 14 18 23 16 20 25 FLA 36/36 37/40 55/60 67/74 35/34 35/34 35/38 53/58 65/72 38/37 38/37 38/41 56/61 68/75 45 20 20 30 30 45 20 20 25 30 45 20 20 30 30 45 20 25 30 15 20 30 20 25 30 MAX 45/45 45/45 60/70 80/90 45/45 45/45 45/45 60/70 80/80 50/45 50/45 50/45 70/70 80/90 BRKR HACR FUSE or w/ P.E. (pwrd fr/unit) 17 18 26 30 44 16 17 25 29 42 16 18 26 30 43 15 21 27 14 20 25 15 22 27 35.0 MCA 35/37 40/44 59/66 72/81 34/33 34/35 38/42 57/64 70/79 36/36 36/38 42/44 61/66 74/81 99 48 48 48 48 48 55 55 55 55 55 71 71 71 71 71 40 40 40 45 45 45 58 58 58 115 145 w/ PWRD C.O. LRA 99/99 99/99 99/99 99/99 115/115 115/115 115/115 115/115 145/145 145/145 145/145 145/145 DISC. SIZE 34 16 16 23 26 39 15 15 22 25 38 16 16 23 26 39 13 17 22 12 16 21 14 18 23 FLA 34/34 35/38 52/58 64/72 32/32 32/32 33/36 51/56 63/70 36/35 36/35 36/39 54/59 66/73 NO P.E. 45 20 20 25 30 45 20 20 25 30 45 20 20 25 30 45 15 20 25 15 20 25 15 20 25 MAX 45/45 45/45 60/70 80/80 45/45 45/45 45/45 60/70 70/80 45/45 45/45 45/45 60/70 80/80 BRKR HACR FUSE or 50LC 17 25 29 42 15 24 27 41 17 25 29 42 19 24 17 23 19 25 33.0 16.0 15.0 15.0 13.0 12.0 13.0 MCA 33/35 38/41 57/63 70/78 32/31 32/33 36/39 55/61 68/76 34/34 34/35 39/42 59/64 72/79 96 47 47 47 47 47 54 54 54 54 54 70 70 70 70 70 40 40 40 45 45 45 58 58 58 112 142 LRA 96/96 96/96 96/96 96/96 112/112 112/112 112/112 112/112 142/142 142/142 142/142 142/142 DISC. SIZE 31 15 15 22 25 38 13 13 20 24 36 14 14 21 25 37 14 17 23 12 16 21 14 18 23 FLA 31/31 32/35 49/55 61/69 29/29 29/29 30/33 47/53 59/67 32/31 32/31 33/35 50/55 62/69 40 20 20 25 30 45 15 15 25 30 40 20 20 25 30 45 15 20 25 15 20 25 15 20 30 MAX 40/40 40/40 60/60 70/80 40/40 40/40 40/40 60/60 70/80 45/40 45/40 45/40 60/70 70/80 BRKR HACR FUSE or w/ P.E. (pwrd fr/unit) 14 15 24 27 41 13 14 22 26 40 14 15 23 27 41 13 19 25 12 17 23 14 20 25 30.0 MCA 30/31 34/38 53/60 66/75 29/29 29/29 32/36 51/58 64/73 32/31 32/32 36/38 55/60 68/75 94 46 46 46 46 46 53 53 53 53 53 69 69 69 69 69 38 38 38 43 43 43 56 56 56 110 140 LRA 94/94 94/94 94/94 94/94 110/110 110/110 110/110 110/110 140/140 140/140 140/140 140/140 NO C.O. or UNPWR C.O. DISC. SIZE 29 14 14 20 24 36 12 12 19 23 35 13 13 20 24 36 12 15 20 10 14 19 12 16 21 FLA 29/29 29/33 47/53 59/67 27/27 27/27 27/30 45/51 57/65 30/29 30/29 31/33 48/53 60/67 NO P.E. 40 20 20 25 30 40 15 15 25 25 40 15 15 25 30 40 15 20 25 15 15 25 15 20 25 MAX 40/40 40/40 60/60 70/80 40/40 40/40 40/40 50/60 70/80 40/40 40/40 40/40 60/60 70/80 BRKR HACR Table 5 – Unit Wire/Fuse or HACR Breaker Sizing Data (cont) FUSE or 14 22 26 40 13 21 25 38 14 22 26 39 17 22 15 21 17 23 28.0 13.0 12.0 13.0 11.0 10.0 12.0 MCA 28/29 32/35 51/57 64/72 27/27 27/27 30/33 49/55 62/70 30/29 30/29 33/36 53/58 66/73 ------7.2 7.2 7.2 9.2 9.2 9.2 FLA 13.8 16.8 27.7 13.8 16.8 27.7 13.8 16.8 27.7 13.8 13.8 13.8 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 ------6.0 6.0 6.0 9.2 9.2 9.2 11.5 14.0 23.0 11.5 14.0 23.0 11.5 14.0 23.0 13.8 13.8 13.8 Nom (kW) 4.9/6.5 6.5/8.7 4.9/6.5 6.5/8.7 4.9/6.5 6.5/8.7 12.0/16.0 15.8/21.0 12.0/16.0 15.8/21.0 12.0/16.0 15.8/21.0 ELEC. HTR 102A 105A 102A 105A 102A 105A 106A 108A 109A 106A 108A 109A 106A 108A 109A 297A 298A 297A 298A 297A 298A 103B 103B 103B NONE NONE NONE NONE NONE NONE NONE NONE NONE 108A+108A 108A+108A 108A+108A 104B+104B 104B+104B 104B+104B CRHEATER***A00 IFM MED MED MED TYPE HIGH HIGH HIGH

D D --- S T D D D --- S T D D D --- S T D

- - Z H --- h P --- V . M O N 208/230---3---60 460---3---60 0 6 --- 3 --- 5 7 5

UNIT 50LC---005 See “Legend and Notes for Tables 5 and 6” on page 47. 42 60 60 60 60 60 60 69 69 69 69 69 69 83 83 83 83 83 83 48 48 48 57 57 57 66 66 66 128 148 174 LRA 128/128 128/128 128/128 128/128 128/128 148/148 148/148 148/148 148/148 148/148 174/174 174/174 174/174 174/174 174/174 DISC. SIZE 39 19 19 24 28 40 44 18 18 24 27 40 43 18 18 24 27 40 43 16 25 35 16 24 35 17 25 36 FLA 39/39 41/45 55/60 67/74 80/90 39/38 39/38 41/45 54/60 66/74 79/89 40/39 40/39 43/46 56/61 68/75 81/90 50 25 25 30 30 45 50 25 25 30 30 45 50 25 25 30 30 45 50 20 30 40 20 30 40 20 30 40 MAX 50/50 50/50 60/70 80/90 50/50 50/50 50/50 60/70 80/90 50/50 50/50 50/50 70/70 80/90 BRKR HACR 90/100 90/100 90/100 FUSE or w/ P.E. (pwrd fr/unit) 18 26 30 44 47 18 18 26 30 43 47 18 26 30 43 47 27 38 15 26 38 27 39 38.0 18.0 18.0 16.0 16.0 MCA 38/38 45/49 59/66 72/81 87/97 38/37 38/37 45/49 59/65 72/80 86/97 39/38 39/38 47/50 61/66 74/81 88/98 59 59 59 59 59 59 68 68 68 68 68 68 82 82 82 82 82 82 46 46 46 55 55 55 64 64 64 126 146 172 w/ PWRD C.O. LRA 126/126 126/126 126/126 126/126 126/126 146/146 146/146 146/146 146/146 146/146 172/172 172/172 172/172 172/172 172/172 DISC. SIZE 37 17 17 23 26 39 42 17 17 23 26 39 42 17 17 23 26 39 42 14 22 33 14 22 33 15 23 34 FLA 37/37 39/43 52/58 64/72 78/87 36/36 36/36 39/42 52/58 64/71 77/87 38/37 38/37 41/44 54/59 66/73 79/88 NO P.E. 50 20 20 25 30 45 50 20 20 25 30 45 50 20 20 25 30 45 50 20 25 40 15 25 40 20 25 40 MAX 50/50 50/50 60/70 80/80 50/50 50/50 50/50 60/70 70/80 50/50 50/50 50/50 60/70 80/80 BRKR HACR 90/100 90/100 90/100 FUSE or 50LC 17 25 29 42 46 17 25 29 42 46 17 25 29 42 46 24 36 24 35 25 37 36.0 17.0 17.0 17.0 14.0 13.0 14.0 MCA 36/36 43/47 57/63 70/78 84/95 36/35 36/35 42/46 57/63 70/78 84/94 37/36 37/36 44/47 59/64 72/79 86/96 58 58 58 58 58 58 67 67 67 67 67 67 81 81 81 81 81 81 46 46 46 55 55 55 64 64 64 123 143 169 LRA 123/123 123/123 123/123 123/123 123/123 143/143 143/143 143/143 143/143 143/143 169/169 169/169 169/169 169/169 169/169 DISC. SIZE 33 16 16 22 25 38 41 16 16 21 25 37 41 16 16 21 25 37 41 14 23 33 14 22 33 15 23 34 FLA 33/33 36/40 49/55 61/69 74/84 33/33 33/33 36/39 49/54 61/68 74/83 35/34 35/34 37/40 50/55 62/69 76/85 45 20 20 25 30 45 45 20 20 25 30 45 45 20 20 25 30 45 45 20 25 40 15 25 40 20 30 40 MAX 45/45 45/45 60/60 70/80 45/45 45/45 45/45 60/60 70/80 50/45 50/45 50/45 60/70 70/80 BRKR HACR 90/100 90/100 90/100 FUSE or w/ P.E. (pwrd fr/unit) 16 24 27 41 45 16 16 23 27 41 44 16 23 27 41 44 25 36 13 24 36 25 37 33.0 16.0 16.0 14.0 14.0 MCA 33/33 39/43 53/60 66/75 81/91 33/33 33/33 39/43 53/59 66/74 80/91 34/34 34/34 41/44 55/60 68/75 82/92 57 57 57 57 57 57 66 66 66 66 66 66 80 80 80 80 80 80 44 44 44 53 53 53 62 62 62 121 141 167 LRA 121/121 121/121 121/121 121/121 121/121 141/141 141/141 141/141 141/141 141/141 167/167 167/167 167/167 167/167 167/167 NO C.O. or UNPWR C.O. DISC. SIZE 31 15 15 20 24 36 40 15 15 20 24 36 40 15 15 20 24 36 40 12 20 31 12 20 31 13 21 32 FLA 31/31 34/38 47/53 59/67 72/82 31/30 31/30 33/37 47/52 59/66 72/81 33/32 33/32 35/38 48/53 60/67 73/82 NO P.E. 45 20 20 25 30 40 45 20 20 25 30 40 45 20 20 25 30 40 45 15 25 35 15 25 35 15 25 35 MAX 45/45 45/45 60/60 70/80 80/90 45/45 45/45 45/45 60/60 70/80 80/90 45/45 45/45 45/45 60/60 70/80 80/90 BRKR HACR Table 5 – Unit Wire/Fuse or HACR Breaker Sizing Data (cont) FUSE or 15 22 26 40 43 15 22 26 39 43 15 22 26 39 43 22 34 22 33 23 35 31.0 15.0 15.0 15.0 12.0 12.0 13.0 MCA 31/31 37/41 51/57 64/72 78/89 31/31 31/31 36/40 51/57 64/72 78/88 32/32 32/32 38/41 53/58 66/73 80/90 ------7.2 7.2 7.2 FLA 13.8 16.8 27.7 30.7 13.8 16.8 27.7 30.7 13.8 16.8 27.7 30.7 13.8 23.1 13.8 23.1 13.8 23.1 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 ------6.0 6.0 6.0 11.5 14.0 23.0 25.5 11.5 14.0 23.0 25.5 11.5 14.0 23.0 25.5 13.8 23.0 13.8 23.0 13.8 23.0 Nom (kW) 4.9/6.5 4.9/6.5 4.9/6.5 7.9/10.5 7.9/10.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 12.0/16.0 15.8/21.0 19.9/26.5 12.0/16.0 15.8/21.0 19.9/26.5 ELEC. HTR 102A 105A 102A 105A 102A 105A 106A 108A 109A 106A 108A 109A 106A 108A 109A 298A 301A 298A 301A 298A 301A 104B 104B 104B NONE NONE NONE NONE NONE NONE NONE NONE NONE 108A+108A 108A+109A 108A+108A 108A+109A 108A+108A 108A+109A 104B+105A 104B+105A 104B+105A 104B+104B 104B+104B 104B+104B CRHEATER***A00 IFM MED MED MED TYPE HIGH HIGH HIGH

D D --- S T D D D --- S T D D D --- S T D

- - Z H --- h P --- V . M O N 208/230---3---60 0 6 --- 3 --- 0 6 4 0 6 --- 3 --- 5 7 5

UNIT 50LC---006 See “Legend and Notes for Tables 5 and 6” on page 47. 43 90 45 45 45 45 45 53 53 53 53 53 55 55 55 55 55 34 34 34 40 40 40 44 44 44 107 111 LRA 90/90 90/90 90/90 90/90 90/90 107/107 107/107 107/107 107/107 107/107 111/111 111/111 111/111 111/111 111/111 DISC. SIZE 32 16 16 20 23 27 15 15 19 23 26 16 16 20 24 27 14 18 24 14 18 23 14 19 24 FLA 32/32 32/32 35/38 40/43 53/59 32/32 32/32 32/32 35/38 40/43 53/58 33/33 33/33 33/33 37/40 41/45 54/60 40 20 20 25 30 30 20 20 25 25 30 20 20 25 30 30 15 25 30 15 20 30 15 25 30 40/40 40/40 45/45 50/50 70/70 40/40 40/40 40/40 45/45 50/50 70/70 40/40 40/40 40/40 45/45 50/50 70/70 BRKR HACR w/ P.E. (pwrd fr/unit) 17 21 25 29 17 21 25 29 16 18 22 26 30 20 26 20 25 20 26 31.0 15.0 15.0 13.0 13.0 14.0 MCA 31/31 35/35 42/42 47/47 64/64 31/31 31/31 35/35 42/42 47/47 64/64 32/32 32/32 36/36 43/43 49/49 65/65 88 44 44 44 44 44 52 52 52 52 52 54 54 54 54 54 32 32 32 38 38 38 42 42 42 105 109 w/ PWRD C.O. LRA 88/88 88/88 88/88 88/88 88/88 105/105 105/105 105/105 105/105 105/105 109/109 109/109 109/109 109/109 109/109 DISC. SIZE 30 14 14 18 22 26 14 14 18 22 25 15 15 19 23 26 12 16 22 11 16 21 12 17 22 FLA 30/30 30/30 33/36 37/41 51/56 30/29 30/29 30/30 33/36 37/41 51/56 31/31 31/31 31/31 35/37 39/42 52/58 NO P.E. 40 20 20 20 25 30 20 20 20 25 30 20 20 25 25 30 15 20 25 15 20 25 15 20 25 40/40 40/40 40/40 45/45 70/70 40/40 40/40 40/40 40/40 45/45 70/70 40/40 40/40 40/40 45/45 50/50 70/70 BRKR HACR 50LC 16 20 24 28 15 20 24 27 15 17 21 25 29 18 23 17 23 18 24 29.0 14.0 14.0 11.0 11.0 12.0 MCA 29/29 33/33 39/39 45/45 61/61 29/29 29/29 33/33 39/39 45/45 61/61 30/30 30/30 34/34 41/41 46/46 63/63 85 43 43 43 43 43 51 51 51 51 51 53 53 53 53 53 32 32 32 38 38 38 42 42 42 102 106 LRA 85/85 85/85 85/85 85/85 85/85 102/102 102/102 102/102 102/102 102/102 106/106 106/106 106/106 106/106 106/106 DISC. SIZE 26 13 13 17 21 24 13 13 17 20 24 14 14 18 21 25 12 16 22 12 16 21 12 17 22 FLA 26/26 26/27 30/33 34/38 47/53 26/26 26/26 26/27 30/33 34/38 47/53 28/27 28/27 28/28 31/34 36/39 49/54 30 15 15 20 25 30 15 15 20 25 30 15 15 20 25 30 15 20 25 15 20 25 15 20 25 30/30 30/30 40/40 45/45 60/60 30/30 30/30 30/30 40/40 45/45 60/60 30/30 30/30 35/35 40/40 45/45 60/60 BRKR HACR w/ P.E. (pwrd fr/unit) 14 19 23 26 14 18 22 26 13 15 19 23 27 18 24 17 23 18 24 26.0 13.0 12.0 12.0 11.0 12.0 MCA 26/26 29/29 36/36 41/41 58/58 26/26 26/26 29/29 36/36 41/41 58/58 27/27 27/27 30/30 37/37 43/43 59/59 83 42 42 42 42 42 50 50 50 50 50 52 52 52 52 52 30 30 30 36 36 36 40 40 40 100 104 LRA 83/83 83/83 83/83 83/83 83/83 100/100 100/100 100/100 100/100 100/100 104/104 104/104 104/104 104/104 104/104 NO C.O. or UNPWR C.O. DISC. SIZE 9 24 12 12 16 20 23 12 12 16 19 23 13 13 17 20 24 10 14 20 14 19 10 15 20 FLA 24/24 24/25 27/31 32/36 45/51 24/24 24/24 24/24 27/30 32/36 45/51 26/25 26/25 26/26 29/32 33/37 47/52 NO P.E. 30 15 15 20 25 30 15 15 20 25 25 15 15 20 25 30 15 20 25 15 15 25 15 20 25 30/30 30/30 35/35 40/40 60/60 30/30 30/30 30/30 35/35 40/40 60/60 30/30 30/30 30/30 35/35 45/45 60/60 BRKR HACR Table 6 – Unit Wire/Factory Installed HACR Breaker Sizing Data 13 17 21 25 13 17 21 25 12 14 18 22 26 16 21 15 21 16 22 9.0 24.0 12.0 11.0 10.0 10.0 MCA 24/24 27/27 33/33 39/39 55/55 24/24 24/24 27/27 33/33 39/39 55/55 25/25 25/25 28/28 35/35 40/40 57/57 ------7.2 7.2 7.2 9.2 9.2 9.2 FLA 10.6 13.8 16.8 10.6 13.8 16.8 10.6 13.8 16.8 13.8 13.8 13.8 9.2/10.6 9.2/10.6 9.2/10.6 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 13.6/15.6 18.1/20.9 21.9/25.3 33.4/38.5 ------6.0 8.8 6.0 8.8 6.0 8.8 9.2 9.2 9.2 11.5 14.0 11.5 14.0 11.5 14.0 13.8 13.8 13.8 Nom (kW) 3.3/4.4 4.9/6.5 6.5/8.7 3.3/4.4 4.9/6.5 6.5/8.7 3.3/4.4 4.9/6.5 6.5/8.7 7.9/10.5 7.9/10.5 7.9/10.5 12.0/16.0 12.0/16.0 12.0/16.0 ELEC. HTR 101A 102A 105A 101A 102A 105A 101A 102A 105A 106A 107A 108A 109A 106A 107A 108A 109A 106A 107A 108A 109A 297A 298A 297A 298A 297A 298A 103B 104B 103B 104B 103B 104B NONE NONE NONE NONE NONE NONE NONE NONE NONE CRHEATER***A00 IFM MED MED MED TYPE HIGH HIGH HIGH

D D --- S T D D D --- S T D D D --- S T D

- - Z H --- h P --- V . M O N 208/230---3---60 0 6 --- 3 --- 0 6 4 575---3---60

UNIT 4 0 0 --- C L 0 5 See “Legend and Notes for Tables 5 and 6” on page 47. 44 49 49 49 49 49 56 56 56 56 56 72 72 72 72 72 42 42 42 47 47 47 60 60 60 101 117 147 LRA 101/101 101/101 101/101 101/101 117/117 117/117 117/117 117/117 147/147 147/147 147/147 147/147 DISC. SIZE 36 17 17 24 28 40 16 16 23 26 39 17 17 24 27 40 16 19 25 14 18 23 16 20 25 FLA 36/36 37/40 55/60 67/74 35/34 35/34 35/38 53/58 65/72 38/37 38/37 38/41 56/61 68/75 45 20 20 30 30 45 20 20 25 30 45 20 20 30 30 45 20 25 30 15 20 30 20 25 30 45/45 45/45 70/70 90/90 45/45 45/45 45/45 70/70 80/80 50/50 50/50 50/50 70/70 90/90 BRKR HACR w/ P.E. (pwrd fr/unit) 17 18 26 30 44 16 17 25 29 42 16 18 26 30 43 15 21 27 14 20 25 15 22 27 35.0 MCA 37/37 44/44 66/66 81/81 34/34 35/35 42/42 64/64 79/79 36/36 38/38 44/44 66/66 81/81 99 48 48 48 48 48 55 55 55 55 55 71 71 71 71 71 40 40 40 45 45 45 58 58 58 115 145 w/ PWRD C.O. LRA 99/99 99/99 99/99 99/99 115/115 115/115 115/115 115/115 145/145 145/145 145/145 145/145 DISC. SIZE 34 16 16 23 26 39 15 15 22 25 38 16 16 23 26 39 13 17 22 12 16 21 14 18 23 FLA 34/34 35/38 52/58 64/72 32/32 32/32 33/36 51/56 63/70 36/35 36/35 36/39 54/59 66/73 NO P.E. 45 20 20 25 30 45 20 20 25 30 45 20 20 25 30 45 15 20 25 15 20 25 15 20 25 45/45 45/45 70/70 80/80 45/45 45/45 45/45 70/70 80/80 45/45 45/45 45/45 70/70 80/80 BRKR HACR 50LC 16 17 25 29 42 15 15 24 27 41 15 17 25 29 42 13 19 24 12 17 23 13 19 25 33.0 MCA 35/35 41/41 63/63 78/78 32/32 33/33 39/39 61/61 76/76 34/34 35/35 42/42 64/64 79/79 96 47 47 47 47 47 54 54 54 54 54 70 70 70 70 70 40 40 40 45 45 45 58 58 58 112 142 LRA 96/96 96/96 96/96 96/96 112/112 112/112 112/112 112/112 142/142 142/142 142/142 142/142 DISC. SIZE 31 15 15 22 25 38 13 13 20 24 36 14 14 21 25 37 14 17 23 12 16 21 14 18 23 FLA 31/31 32/35 49/55 61/69 29/29 29/29 30/33 47/53 59/67 32/31 32/31 33/35 50/55 62/69 40 20 20 25 30 45 15 15 25 30 40 20 20 25 30 45 15 20 25 15 20 25 15 20 30 40/40 40/40 60/60 80/80 40/40 40/40 40/40 60/60 80/80 45/45 45/45 45/45 70/70 80/80 BRKR HACR w/ P.E. (pwrd fr/unit) 14 15 24 27 41 13 14 22 26 40 14 15 23 27 41 13 19 25 12 17 23 14 20 25 30.0 MCA 31/31 38/38 60/60 75/75 29/29 29/29 36/36 58/58 73/73 32/32 32/32 38/38 60/60 75/75 94 46 46 46 46 46 53 53 53 53 53 69 69 69 69 69 38 38 38 43 43 43 56 56 56 110 140 LRA 94/94 94/94 94/94 94/94 110/110 110/110 110/110 110/110 140/140 140/140 140/140 140/140 NO C.O. or UNPWR C.O. DISC. SIZE 29 14 14 20 24 36 12 12 19 23 35 13 13 20 24 36 12 15 20 10 14 19 12 16 21 FLA 29/29 29/33 47/53 59/67 27/27 27/27 27/30 45/51 57/65 30/29 30/29 31/33 48/53 60/67 NO P.E. 40 20 20 25 30 40 15 15 25 25 40 15 15 25 30 40 15 20 25 15 15 25 15 20 25 40/40 40/40 60/60 80/80 40/40 40/40 40/40 60/60 80/80 40/40 40/40 40/40 60/60 80/80 BRKR HACR Table 6 – Unit Wire/Factory Installed HACR Breaker Sizing Data (cont) 13 14 22 26 40 12 13 21 25 38 13 14 22 26 39 11 17 22 10 15 21 12 17 23 28.0 MCA 29/29 35/35 57/57 72/72 27/27 27/27 33/33 55/55 70/70 30/30 30/30 36/36 58/58 73/73 ------7.2 7.2 7.2 9.2 9.2 9.2 FLA 13.8 16.8 27.7 13.8 16.8 27.7 13.8 16.8 27.7 13.8 13.8 13.8 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 13.6/15.6 18.1/20.9 33.4/38.5 43.8/50.5 ------6.0 6.0 6.0 9.2 9.2 9.2 11.5 14.0 23.0 11.5 14.0 23.0 11.5 14.0 23.0 13.8 13.8 13.8 Nom (kW) 4.9/6.5 6.5/8.7 4.9/6.5 6.5/8.7 4.9/6.5 6.5/8.7 12.0/16.0 15.8/21.0 12.0/16.0 15.8/21.0 12.0/16.0 15.8/21.0 ELEC. HTR 102A 105A 102A 105A 102A 105A 106A 108A 109A 106A 108A 109A 106A 108A 109A 297A 298A 297A 298A 297A 298A 103B 103B 103B NONE NONE NONE NONE NONE NONE NONE NONE NONE 108A+108A 108A+108A 108A+108A 104B+104B 104B+104B 104B+104B CRHEATER***A00 IFM MED MED MED TYPE HIGH HIGH HIGH

D D --- S T D D D --- S T D D D --- S T D

- - Z H --- h P --- V . M O N 208/230---3---60 0 6 --- 3 --- 0 6 4 575---3---60

UNIT 5 0 0 --- C L 0 5 See “Legend and Notes for Tables 5 and 6 ” on page 47. 45 60 60 60 60 60 60 69 69 69 69 69 69 83 83 83 83 83 83 48 48 48 57 57 57 66 66 66 128 148 174 LRA 128/128 128/128 128/128 128/128 128/128 148/148 148/148 148/148 148/148 148/148 174/174 174/174 174/174 174/174 174/174 DISC. SIZE 39 19 19 24 28 40 44 18 18 24 27 40 43 18 18 24 27 40 43 16 25 35 16 24 35 17 25 36 FLA 39/39 41/45 55/60 67/74 80/90 39/38 39/38 41/45 54/60 66/74 79/89 40/39 40/39 43/46 56/61 68/75 81/90 50 25 25 30 30 45 50 25 25 30 30 45 50 25 25 30 30 45 50 20 30 40 20 30 40 20 30 40 50/50 50/50 70/70 90/90 50/50 50/50 50/50 70/70 90/90 50/50 50/50 50/50 70/70 90/90 BRKR HACR 100/100 100/100 100/100 w/ P.E. (pwrd fr/unit) 18 26 30 44 47 18 18 26 30 43 47 18 26 30 43 47 27 38 15 26 38 27 39 38.0 18.0 18.0 16.0 16.0 MCA 38/38 49/49 66/66 81/81 97/97 38/38 38/38 49/49 65/65 80/80 97/97 39/39 39/39 50/50 66/66 81/81 98/98 59 59 59 59 59 59 68 68 68 68 68 68 82 82 82 82 82 82 46 46 46 55 55 55 64 64 64 126 146 172 w/ PWRD C.O. LRA 126/126 126/126 126/126 126/126 126/126 146/146 146/146 146/146 146/146 146/146 172/172 172/172 172/172 172/172 172/172 DISC. SIZE 37 17 17 23 26 39 42 17 17 23 26 39 42 17 17 23 26 39 42 14 22 33 14 22 33 15 23 34 FLA 37/37 39/43 52/58 64/72 78/87 36/36 36/36 39/42 52/58 64/71 77/87 38/37 38/37 41/44 54/59 66/73 79/88 NO P.E. 50 20 20 25 30 45 50 20 20 25 30 45 50 20 20 25 30 45 50 20 25 40 15 25 40 20 25 40 50/50 50/50 70/70 80/80 50/50 50/50 50/50 70/70 80/80 50/50 50/50 50/50 70/70 80/80 BRKR HACR 100/100 100/100 100/100 50LC 17 25 29 42 46 17 17 25 29 42 46 17 25 29 42 46 24 36 13 24 35 25 37 36.0 17.0 17.0 14.0 14.0 MCA 36/36 47/47 63/63 78/78 95/95 36/36 36/36 46/46 63/63 78/78 94/94 37/37 37/37 47/47 64/64 79/79 96/96 58 58 58 58 58 58 67 67 67 67 67 67 81 81 81 81 81 81 46 46 46 55 55 55 64 64 64 123 143 169 LRA 123/123 123/123 123/123 123/123 123/123 143/143 143/143 143/143 143/143 143/143 169/169 169/169 169/169 169/169 169/169 DISC. SIZE 33 16 16 22 25 38 41 16 16 21 25 37 41 16 16 21 25 37 41 14 23 33 14 22 33 15 23 34 FLA 33/33 36/40 49/55 61/69 74/84 33/33 33/33 36/39 49/54 61/68 74/83 35/34 35/34 37/40 50/55 62/69 76/85 45 20 20 25 30 45 45 20 20 25 30 45 45 20 20 25 30 45 45 20 25 40 15 25 40 20 30 40 45/45 45/45 60/60 80/80 45/45 45/45 45/45 60/60 80/80 50/50 50/50 50/50 70/70 80/80 BRKR HACR 100/100 100/100 100/100 w/ P.E. (pwrd fr/unit) 16 24 27 41 45 16 16 23 27 41 44 16 23 27 41 44 25 36 13 24 36 25 37 33.0 16.0 16.0 14.0 14.0 MCA 33/33 43/43 60/60 75/75 91/91 33/33 33/33 43/43 59/59 74/74 91/91 34/34 34/34 44/44 60/60 75/75 92/92 57 57 57 57 57 57 66 66 66 66 66 66 80 80 80 80 80 80 44 44 44 53 53 53 62 62 62 121 141 167 LRA 121/121 121/121 121/121 121/121 121/121 141/141 141/141 141/141 141/141 141/141 167/167 167/167 167/167 167/167 167/167 NO C.O. or UNPWR C.O. DISC. SIZE 31 15 15 20 24 36 40 15 15 20 24 36 40 15 15 20 24 36 40 12 20 31 12 20 31 13 21 32 FLA 31/31 34/38 47/53 59/67 72/82 31/30 31/30 33/37 47/52 59/66 72/81 33/32 33/32 35/38 48/53 60/67 73/82 NO P.E. 45 20 20 25 30 40 45 20 20 25 30 40 45 20 20 25 30 40 45 15 25 35 15 25 35 15 25 35 45/45 45/45 60/60 80/80 90/90 45/45 45/45 45/45 60/60 80/80 90/90 45/45 45/45 45/45 60/60 80/80 90/90 BRKR HACR Table 6 – Unit Wire/Factory Installed HACR Breaker Sizing Data (cont) 15 22 26 40 43 15 15 22 26 39 43 15 22 26 39 43 22 34 12 22 33 23 35 31.0 15.0 15.0 12.0 13.0 MCA 31/31 41/41 57/57 72/72 89/89 31/31 31/31 40/40 57/57 72/72 88/88 32/32 32/32 41/41 58/58 73/73 90/90 ------7.2 7.2 7.2 FLA 13.8 16.8 27.7 30.7 13.8 16.8 27.7 30.7 13.8 16.8 27.7 30.7 13.8 23.1 13.8 23.1 13.8 23.1 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 13.6/15.6 21.9/25.3 33.4/38.5 43.8/50.5 55.2/63.8 ------6.0 6.0 6.0 11.5 14.0 23.0 25.5 11.5 14.0 23.0 25.5 11.5 14.0 23.0 25.5 13.8 23.0 13.8 23.0 13.8 23.0 Nom (kW) 4.9/6.5 4.9/6.5 4.9/6.5 7.9/10.5 7.9/10.5 7.9/10.5 12.0/16.0 15.8/21.0 19.9/26.5 12.0/16.0 15.8/21.0 19.9/26.5 12.0/16.0 15.8/21.0 19.9/26.5 ELEC. HTR 102A 105A 102A 105A 102A 105A 106A 108A 109A 106A 108A 109A 106A 108A 109A 298A 301A 298A 301A 298A 301A 104B 104B 104B NONE NONE NONE NONE NONE NONE NONE NONE NONE 108A+108A 108A+109A 108A+108A 108A+109A 108A+108A 108A+109A 104B+105A 104B+105A 104B+105A 104B+104B 104B+104B 104B+104B CRHEATER***A00 IFM MED MED MED TYPE HIGH HIGH HIGH

D D --- S T D D D --- S T D D D --- S T D

- - Z H --- h P --- V . M O N 208/230---3---60 0 6 --- 3 --- 0 6 4 0 6 --- 3 --- 5 7 5

UNIT 6 0 0 --- C L 0 5 See “Legend and Notes for Tables 5 and 6” on page 47. 46 Legend and Notes for Tables 5 and 6 LEGEND: Example: Supply voltage is 230-3-60 BD --- Belt drive indoor fan motor AB = 224 v BRKR --- Circuit breaker BC = 231 v CO --- Convenient outlet AC = 226 v DD --- Direct drive indoor fan motor DISC --- Disconnect (224 + 231 + 226) 681 Average Voltage = = FLA --- Full load amps 3 3 IFM --- Indoor fan motor LRA --- Locked rotor amps MCA --- Minimum circuit amps = 227 MOCP --- MAX FUSE or HACR Breaker Determine maximum deviation from average voltage. P E --- P o w e r e x h a u s t (AB) 227 – 224 = 3 v PWRD CO --- Powered convenient outlet (BC) 231 – 227 = 4 v UNPWR CO --- Unpowered convenient outlet NOTES: (AC) 227 – 226 = 1 v 1. In compliance with NEC requirements for multimotor and Maximum deviation is 4 v. combination load equipment (refer to NEC Articles 430 and Determine percent of voltage imbalance. 440), the overcurrent protective device for the unit shall be 4 fuse or HACR breaker. Canadian units may be fuse or circuit % Voltage Imbalance = 100 x breaker. 227 2. Unbalanced 3-Phase Supply Voltage = 1.76% Never operate a motor where a phase imbalance in supply This amount of phase imbalance is satisfactory as it is below the 50LC voltage is greater than 2%. Use the following formula to de- maximum allowable 2%. termine the percentage of voltage imbalance. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. max voltage deviation from average voltage % Voltage Imbalance = 100 x average voltage

Step 12 — Adjust Factory--Installed Options Pre--Start and Start--Up — Smoke Detectors — This completes the mechanical installation of the unit. Refer to the unit’s Service Manual for detailed Pre--Start Smoke detector(s) will be connected at the Central and Start--Up instructions. Download the latest versions Terminal Board (CTB), at terminals marked “Smoke from HVAC Partners (www.hvacpartners.com). Shutdown”. Remove jumper JMP 3 when ready to energize unit. Step 13 — Install Accessories Available accessories include: Curb Thru--base connection kit (must be installed before unit is set on curb) Electric heaters and single--point connection kits EconoMi$er X (with control) EconoMi$er2 (without control/for external signal) Power Exhaust Differential dry--bulb sensor (EconoMi$er2) Outdoor enthalpy sensor Differential enthalpy sensor CO2 sensor Louvered hail guard Phase monitor control Refer to separate installation instructions for information on installing these accessories.

47 APPENDIX — VFD Operation with Remote Keypad All 50LC size 04--06 units are equipped with a VFD (Variable Frequency Drive) to automatically adjust the indoor fan motor speed in sequence with the unit’s ventilation, cooling and heating operation. The VFD keypad is included as standard on electro mechanical and RTU Open models. See Fig. 71 for location of the VFD and the VFD keypad in these units. NOTE: ComfortLink models do not include the VFD keypad as VFD control operation is accessed through the ComfortLink controls. The VFD keypad is shown in Fig. 70. The function of SOFT

KEYS 1 and 2 change depending on what is displayed on C08675 the screen. The function of SOFT KEY 1 matches the word Fig. 70 -- VFD Keypad in the lower left--hand box on the display screen. The function of SOFT KEY 2 matches the word in the lower Use the RJ--45 (CAT5) cable (bundled with the Control right--hand box on the display screen. If the box is empty, 50LC Harness -- see Fig. 71) to provide easier access for using the then the SOFT KEY does not have a function on that VFD Remote Keypad. The cable’s length is long enough to specific screen. The UP and DOWN keys are used to route it through to the unit’s control box, if desired. navigate through the menus. The OFF key is used to turn off the VFD. The AUTO key is used to change control of the To Connect the VFD Keypad using the RJ--45 Cable — drive to automatic control. The HAND key is used to change 1. Remove the Keypad from the front of the VFD. control of the drive to local (hand held) control. The HELP button is used to access the help screens. 2. Remove the RJ--45 adapter from the back of the Re- mote Keypad and insert the adapter into the RJ--45 For the VFD to operate on the units covered by this port on the front of the VFD. document, the drive must be set in AUTO mode. The word 3. Separate the RJ--45 (CAT5) cable from the Control “AUTO” will appear in the upper left hand corner of the Harness. VFD display. Press the AUTO button to set the drive in 4. Use the CAT5 cable to connect the Remote Keypad to AUTO mode. the VFD.

RJ-45 (CAT5) Cable ABB VFD (Bundled with Control Harness) w/ Remote Keypad

C13394 Fig. 71 -- Location of VFD in 50LC 04--06 Units

48 Start Up with Assistant Standard Display Mode Initial start--up has been performed at the factory. Use of the Use the standard display mode to read information on the start up assistant will override factory VFD configurations. drive status and operate the drive. To reach the standard DO NOT USE THE START--UP ASSISTANT ON THESE display mode, press EXIT until the LCD display shows LC UNITS! status information as described below. (See Fig. 72.) Start Up by Changing Parameters Individually The top line of the LCD display shows the basic status information of the drive. The HAND icon indicates that Initial start--up is performed at the factory. To start up the the drive control is local from the control panel. The VFD by changing individual parameters, perform the AUTO icon indicates that the drive is in remote control following procedure: mode, such as the basic I/O (X1) or field bus. 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. The arrow icon indicates the drive and motor rotation status. A rotating arrow (clockwise or counterclockwise) 2. Use the UP or DOWN keys to highlight PARAMET- indicates that the drive is running and at set point and the ERS on the display screen and press ENTER (SOFT shaft direction is forward or reverse. A rotating blinking KEY 2). arrow indicates that the drive is running but not at set 3. Use the UP or DOWN keys to highlight the desired point. A stationary arrow indicates that the drive is parameter group and press SEL (SOFT KEY 2). stopped. For the units covered in this manual, the correct 4. Use the UP or DOWN keys to highlight the desired display rotation is clockwise. 50LC parameter and press EDIT (SOFT KEY 2). The upper right corner shows the frequency set point that 5. Use the UP or DOWN keys to change the value of the the drive will maintain. parameter. 6. Press SAVE (SOFT KEY 2) to store the modified Using parameter group 34, the middle of the LCD display value. Press CANCEL (SOFT KEY 1) to keep the can be configured to display 3 parameter values. The previous value. Any modifications that are not saved default display shows parameters 0103 (OUTPUT FREQ) will not be changed. in percent speed, 0104 (CURRENT) in amperes, and 0120 7. Choose another parameter or press EXIT (SOFT KEY (Al1) in voltage DC. 1) to return to the listing of parameter groups. Contin- The bottom corners of the LCD display show the ue until all the parameters have been configured and functions currently assigned to the two soft keys. The then press EXIT (SOFT KEY 1) to return to the main lower middle displays the current time (if configured to menu. show the time). NOTE: The current parameter value appears above the highlight parameter. To view the default parameter value, The first time the drive is powered up, it is in the OFF press the UP and DOWN keys simultaneously. To restore mode. To switch to local hand--held control and control the default factory settings, select the application macro the drive using the control panel, press and hold the HAND button. Pressing the HAND button switches the “HVAC Default.” drive to hand control while keeping the drive running. Press the AUTO button to switch to remote input control. VFD Modes To start the drive press the HAND or AUTO buttons, to stop the drive press the OFF button. The VFD has several different modes for configuring, operating, and diagnosing the VFD. The modes are: 60.0Hz S Standard Display mode  shows drive status 100.0 %SP information and operates the drive 1.9 A S Parameters mode  edits parameter values individually 10.0 Vdc S Start--up Assistant mode  guides the start up and configuration. DO NOT USE THE START--UP ASSISTANT ON THESE LC UNITS! S Changed Parameters mode  shows all changed C09249 Fig. 72 -- Standard Display Example parameters S Drive Parameter Backup mode  stores or uploads the To adjust the speed in HAND mode, press the UP or parameters DOWN buttons (the reference changes immediately). The S Clock Set mode  sets the time and date for the drive reference can be modified in the local control (HAND) mode, and can be parameterized (using Group 11 S I/O Settings mode  checks and edits the I/O settings reference select) to also allow modification in the remote control mode.

49 Parameters Mode Depending on the motor and application, there are two options available. The first option is to download all The Parameters mode is used to change the parameters on parameters. This copies both application and motor the drive. To change parameters, perform the following parameters to the drive from the control panel. This is procedure. See Table 7 for a listing of the VFD parameters recommended when using the same application for drives per motor and VFD drive models: of the same size. This can also be used to create a backup 1. Select MENU (SOFT KEY 2). The Main menu will of the parameters group for the drive. be displayed. The second option downloads only the application 2. Use the UP or DOWN keys to highlight PARAMET- parameters to the drive. This is recommended when using ERS on the display screen and press ENTER (SOFT the same application for drives of different sizes. KEY 2). 3. Use the UP or DOWN keys to highlight the desired Upload All Parameters — parameter group and press SEL (SOFT KEY 2). To upload and store parameters in the control panel from 4. Use the UP or DOWN keys to highlight the desired the VFD, perform the following procedure: parameter and press EDIT (SOFT KEY 2). 1. Select MENU (SOFT KEY 2). The Main menu will 5. Use the UP or DOWN keys to change the value of the be displayed. parameter. 2. Use the UP or DOWN keys to highlight PAR 6. Press SAVE (SOFT KEY 2) to store the modified BACKUP on the display screen and press ENTER

50LC value. Press CANCEL (SOFT KEY 1) to keep the (SOFT KEY 2). previous value. Any modifications that are not saved will not be changed. 3. Use the UP or DOWN keys to highlight UPLOAD TO PANEL and press SEL (SOFT KEY 2). 7. Choose another parameter or press EXIT (SOFT KEY 1) to return to the listing of parameter groups. Contin- 4. The text “Copying Parameters” will be displayed with ue until all the parameters have been configured and a progress indicator. To stop the process, select then press EXIT (SOFT KEY 1) to return to the main ABORT (SOFT KEY 1). menu. 5. When the upload is complete, the text “Parameter up- NOTE: The current parameter value appears above the load successful” will be displayed. highlight parameter. To view the default parameter value, 6. The display will then return to the PAR BACKUP press the UP and DOWN keys simultaneously. To restore the menu. Select EXIT (SOFT KEY 1) to return to the default factory settings, select the Carrier application macro. main menu. 7. The control panel can now be disconnected from the Changed Parameters Mode drive. The Changed Parameters mode is used to view and edit Download All Parameters — recently changed parameters on the drive. To view the changed parameters, perform the following procedure: To download all parameters from the control panel to the VFD, perform the following procedure: 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. 1. Install the control panel with the correct parameters 2. Use the UP or DOWN keys to highlight CHANGED onto the VFD. PAR on the display screen and press ENTER (SOFT 2. Select MENU (SOFT KEY 2). The Main menu will KEY 2). A list of the recently changed parameters be displayed. will be displayed. 3. Use the UP or DOWN keys to highlight PAR 3. Use the UP or DOWN keys to highlight the desired BACKUP on the display screen and press ENTER parameter group and press EDIT (SOFT KEY 2) to (SOFT KEY 2). change the parameter if desired. 4. Use the UP or DOWN keys to highlight DOWNLOAD 4. Press EXIT (SOFT KEY 1) to exit the Changed Para- TO DRIVE ALL and press SEL (SOFT KEY 2). meters mode. 5. The text “Restoring Parameters” will be displayed Drive Parameter Backup Mode with a progress indicator. To stop the process, select ABORT (SOFT KEY 1). The drive parameter back up mode is used to export the 6. When the download is complete, the text “Parameter parameters from one drive to another. The parameters can download successful” will be displayed. be uploaded from a VFD to the removable control panel. 7. The display will then return to the PAR BACKUP The control panel can then be transferred to another drive menu. Select EXIT (SOFT KEY 1) to return to the and the parameters downloaded into memory. main menu. 8. The control panel can now be disconnected from the drive.

50 Download Application Parameters — 5. Use the UP or DOWN keys to highlight TIME FORMAT and press SEL (SOFT KEY 2). Use the UP To download application parameters only to the control or DOWN keys to change the parameter setting. Press panel from the VFD, perform the following procedure: OK (SOFT KEY 2) to save the configuration and re- 1. Install the control panel with the correct parameters turn to the Clock Set menu. onto the VFD. 6. Use the UP or DOWN keys to highlight SET DATE 2. Select MENU (SOFT KEY 2). The Main menu will and press SEL (SOFT KEY 2). Use the UP or DOWN be displayed. keys to change the day, month, and year. Press OK 3. Use the UP or DOWN keys to highlight PAR (SOFT KEY 2) to save the configuration and return to BACKUP on the display screen and press ENTER the Clock Set menu. (SOFT KEY 2). 7. Use the UP or DOWN keys to highlight DATE 4. Use the UP or DOWN keys to highlight DOWNLOAD FORMAT and press SEL (SOFT KEY 2). Use the UP APPLICATION and press SEL (SOFT KEY 2). or DOWN keys to change the parameter setting. Press 5. The text “Downloading Parameters (partial)” will be OK (SOFT KEY 2) to save the configuration and re- displayed with a progress indicator. To stop the pro- turn to the Clock Set menu. cess, select ABORT (SOFT KEY 1). 8. Press EXIT (SOFT KEY 1) twice to return to the 6. When the download is complete, the text “Parameter main menu. download successful” will be displayed. I/O Settings Mode

7. The display will then return to the PAR BACKUP 50LC The I/O Settings mode is used for viewing and editing the menu. Select EXIT (SOFT KEY 1) to return to the I/O settings. main menu. 8. The control panel can now be disconnected from the To configure the I/O settings, perform the following drive. procedure: Clock Set Mode 1. Select MENU (SOFT KEY 2). The Main menu will be displayed. The clock set mode is used for setting the date and time 2. Use the UP or DOWN keys to highlight I/O SET- for the internal clock of the VFD. In order to use the timer TINGS on the display screen and press ENTER functions of the VFD control, the internal clock must be (SOFT KEY 2). The I/O Settings parameter list will set. The date is used to determine weekdays and is visible be displayed. in the fault logs. 3. Use the UP or DOWN keys to highlight the desired To set the clock, perform the following procedure: I/O setting and press SEL (SOFT KEY 2). 1. Select MENU (SOFT KEY 2). The Main menu will 4. Use the UP or DOWN keys to select the parameter to be displayed. view. Press OK (SOFT KEY 2). 2. Use the UP or DOWN keys to highlight CLOCK SET 5. Use the UP or DOWN keys to change the parameter on the display screen and press ENTER (SOFT KEY setting. Press SAVE (SOFT KEY 2) to save the con- 2). The clock set parameter list will be displayed. figuration. Press CANCEL (SOFT KEY 1) to keep 3. Use the UP or DOWN keys to highlight CLOCK VIS- the previous value. Any modifications that are not IBILITY and press SEL (SOFT KEY 2). This para- saved will not be changed. meter is used to display or hide the clock on the 6. Press EXIT (SOFT KEY 1) twice to return to the screen. Use the UP or DOWN keys to change the main menu. parameter setting. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu. 4. Use the UP or DOWN keys to highlight SET TIME and press SEL (SOFT KEY 2). Use the UP or DOWN keys to change the hours and minutes. Press OK (SOFT KEY 2) to save the configuration and return to the Clock Set menu.

51 Table 7 – 50LC 04--06 VFD Parameters

Unit Size 50LC 04 Motor Description 1.7 HP 575V 1.7 HP 208---230V 1.7 HP 460V 2.4 HP 575V 2.4 HP 208---230V Drive/Motor Voltage 575V 208---230V 460V 575V 208---230V

Parameter Parameter Motor Part Number HD56FR579 HD56FR233 HD56FR463 HD56FE577 HD56FE653 Group Number VFD Part Number HK30WA048 HK30WA045 HK30WA046 HK30WA048 HK30WA001 ACH550---CARUH ACH550---CARUH ACH550---CARUH ACH550---CARUH ACH550---CARUH ABB Part Number --- 0 3 A 9 --- 6 --- 0 7 A 5 --- 2 --- 0 4 A 1 --- 4 --- 0 3 A 9 --- 6 ---012A---2

9902 Application Macro (1) HVAC DEFAULT (1) HVAC DEFAULT (1) HVAC DEFAULT (1) HVAC DEFAULT (1) HVAC DEFAULT Motor 9905 575 230 460 575 230 Nominal Voltage Motor 9906 3.1 5.8 2.9 3.4 7.9 Nominal Current S t a r t --- U p D a t a Motor 9907 60 60 60 60 60 Nominal Frequency Motor 9908 1725 1725 1725 1725 1725 Nominal Speed Motor 9909 1.7 1.7 1.7 2.4 2.4 Nominal Power 1001 EXT1 Commands (1) DI1 (1) DI1 (1) DI1 (1) DI1 (1) DI1 Start/Stop/Dir 1003 Direction (1) Forward (1) Forward (1) Forward (1) Forward (1) Forward 1103 REF1 Select (1) AI1 (1) AI1 (1) AI1 (1) AI1 (1) AI1 50LC Reference 1104 REF1 Minimum 0Hz 0Hz 0Hz 0Hz 0Hz Select 1105 REF1 Maximum 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz Constant Speed 1201 (8) DI2,3 (8) DI2,3 (8) DI2,3 (8) DI2,3 (8) DI2,3 Select Constant 1202 Constant Speed 1 52.4 52.4 52.4 52.4 52.4 Speeds 1203 Constant Speed 2 60Hz 60Hz 60Hz 60Hz 60Hz 1204 Constant Speed 3 60Hz 60Hz 60Hz 60Hz 60Hz 1301 M i n i m u m A I --- 1 20.00% 20.00% 20.00% 20.00% 20.00% Analog Inputs 1302 M a x i m u m A I --- 1 100.00% 100.00% 100.00% 100.00% 100.00% 1401 Relay Output 1 (1) Ready (1) Ready (1) Ready (1) Ready (1) Ready

Relay Outputs 1402 Relay Output 2 (2) Run (2) Run (2) Run (2) Run (2) Run 1403 Relay Output 3 (16) FLT/ALARM (16) FLT/ALARM (16) FLT/ALARM (16) FLT/ALARM (16) FLT/ALARM

System 1604 Fault Reset Sel (0) Keypad (0) Keypad (0) Keypad (0) Keypad (0) Keypad Control 1608 Start Enable 1 (4) DI4 (4) DI4 (4) DI4 (4) DI4 (4) DI4 Override 1701 Override Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL 2003 Maximum Current 3.6 6.7 3.3 3.9 9.1

Limits 2007 Minimum Frequency 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 2008 Maximum Frequency 60Hz 60Hz 60Hz 60Hz 60Hz 2101 Start Function (1) AUTO (1) AUTO (1) AUTO (1) AUTO (1) AUTO

Start/Stop 2102 Stop Function (1) Coast (1) Coast (1) Coast (1) Coast (1) Coast 2109 EM STOP Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL 2201 Acc/Dec 1/2 Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL

Accel/Decel 2202 Accelerate Time 30.0s 30.0s 30.0s 30.0s 30.0s 2203 Decelerate Time 10.0s 10.0s 10.0s 10.0s 10.0s 2606 Switching Frequency 4KHz 4KHz 4KHz 4KHz 4KHz Motor Switching Frequency 2607 (1) ON (1) ON (1) ON (1) ON (1) ON Control 3005 Motor Therm Prot (1) Fault (1) Fault (1) Fault (1) Fault (1) Fault 3006 Motor Thermal Time 1050s 1050s 1050s 1050s 1050s

Fault 3007 Motor Load Curve 100% 100% 100% 100% 100% Functions 3008 Zero Speed Load %00705 %00705 %00705 %00705 %00705 Break Point 3009 35 Hz 35 Hz 35 Hz 35 Hz 35 Hz Frequency 3104 AR Overcurrent (0) DISABLE (0) DISABLE (0) DISABLE (0) DISABLE (0) DISABLE Automatic 3105 AR Overvoltage (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE Reset 3106 AR Undervoltage (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE 5301 EFB PROTOCOL ID 0601 (hex) 0601 (hex) 0601 (hex) 0601 (hex) 0601 (hex) 5302 EFB STATION ID 41 41 41 41 41

EFB Protocol 5303 EFB BAUD RATE 38400 38400 38400 38400 38400 5304 EFB PARITY 8NONE1 8NONE1 8NONE1 8NONE1 8NONE1 5305 EFB CTRL PROFILE DCU PROFILE DCU PROFILE DCU PROFILE DCU PROFILE DCU PROFILE Options 9802 COMM PROT SEL 6(LEN) 6(LEN) 6(LEN) 6(LEN) 6(LEN)

52 Table 7 -- 50LC 04--06 VFD Parameters (cont.)

Unit Size 50LC 04 50LC 05 50LC 06 Motor Description 2.4 HP 460V 1.7 HP 575V 1.7 HP 208---230V 1.7 HP 460V 2.4 HP 575V Drive/Motor Voltage 460V 575V 208---230V 460V 575V

Parameter Parameter Motor Part Number HD56FE653 HD56FR579 HD56FR233 HD56FR463 HD56FE577 Group Number VFD Part Number HK30WA008 HK30WA048 HK30WA045 HK30WA046 HK30WA048 ACH550---CARUH ACH550---CARUH ACH550---CARUH ACH550---CARUH ACH550---CARUH ABB Part Number --- 0 6 A 9 --- 4 --- 0 3 A 9 --- 6 --- 0 7 A 5 --- 2 --- 0 4 A 1 --- 4 --- 0 3 A 9 --- 6

9902 Application Macro (1) HVAC DEFAULT (1) HVAC DEFAULT (1) HVAC DEFAULT (1) HVAC DEFAULT (1) HVAC DEFAULT Motor 9905 460 575 230 460 575 Nominal Voltage Motor 9906 4.0 3.1 5.8 2.9 3.4 Nominal Current S t a r t --- U p D a t a Motor 9907 60 60 60 60 60 Nominal Frequency Motor 9908 1725 1725 1725 1725 1725 Nominal Speed Motor 9909 2.4 1.7 1.7 1.7 2.4 Nominal Power 1001 EXT1 Commands (1) DI1 (1) DI1 (1) DI1 (1) DI1 (1) DI1 Start/Stop/Dir 1003 Direction (1) Forward (1) Forward (1) Forward (1) Forward (1) Forward 1103 REF1 Select (1) AI1 (1) AI1 (1) AI1 (1) AI1 (1) AI1 50LC Reference 1104 REF1 Minimum 0Hz 0Hz 0Hz 0Hz 0Hz Select 1105 REF1 Maximum 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz Constant Speed 1201 (8) DI2,3 (8) DI2,3 (8) DI2,3 (8) DI2,3 (8) DI2,3 Select Constant 1202 Constant Speed 1 52.4 42.6 42.6 42.6 42.6 Speeds 1203 Constant Speed 2 60Hz 60Hz 60Hz 60Hz 60Hz 1204 Constant Speed 3 60Hz 60Hz 60Hz 60Hz 60Hz 1301 M i n i m u m A I --- 1 20.00% 20.00% 20.00% 20.00% 20.00% Analog Inputs 1302 M a x i m u m A I --- 1 100.00% 100.00% 100.00% 100.00% 100.00% 1401 Relay Output 1 (1) Ready (1) Ready (1) Ready (1) Ready (1) Ready

Relay Outputs 1402 Relay Output 2 (2) Run (2) Run (2) Run (2) Run (2) Run 1403 Relay Output 3 (16) FLT/ALARM (16) FLT/ALARM (16) FLT/ALARM (16) FLT/ALARM (16) FLT/ALARM

System 1604 Fault Reset Sel (0) Keypad (0) Keypad (0) Keypad (0) Keypad (0) Keypad Control 1608 Start Enable 1 (4) DI4 (4) DI4 (4) DI4 (4) DI4 (4) DI4 Override 1701 Override Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL 2003 Maximum Current 4.6 3.6 6.7 3.3 3.9

Limits 2007 Minimum Frequency 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 2008 Maximum Frequency 60Hz 60Hz 60Hz 60Hz 60Hz 2101 Start Function (1) AUTO (1) AUTO (1) AUTO (1) AUTO (1) AUTO

Start/Stop 2102 Stop Function (1) Coast (1) Coast (1) Coast (1) Coast (1) Coast 2109 EM STOP Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL 2201 Acc/Dec 1/2 Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL

Accel/Decel 2202 Accelerate Time 30.0s 30.0s 30.0s 30.0s 30.0s 2203 Decelerate Time 10.0s 10.0s 10.0s 10.0s 10.0s 2606 Switching Frequency 4KHz 4KHz 4KHz 4KHz 4KHz Motor Switching Frequency 2607 (1) ON (1) ON (1) ON (1) ON (1) ON Control 3005 Motor Therm Prot (1) Fault (1) Fault (1) Fault (1) Fault (1) Fault 3006 Motor Thermal Time 1050s 1050s 1050s 1050s 1050s

Fault 3007 Motor Load Curve 100% 100% 100% 100% 100% Functions 3008 Zero Speed Load %00705 %00705 %00705 %00705 %00705 Break Point 3009 35 Hz 35 Hz 35 Hz 35 Hz 35 Hz Frequency 3104 AR Overcurrent (0) DISABLE (0) DISABLE (0) DISABLE (0) DISABLE (0) DISABLE Automatic 3105 AR Overvoltage (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE Reset 3106 AR Undervoltage (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE 5301 EFB PROTOCOL ID 0601 (hex) 0601 (hex) 0601 (hex) 0601 (hex) 0601 (hex) 5302 EFB STATION ID 41 41 41 41 41

EFB Protocol 5303 EFB BAUD RATE 38400 38400 38400 38400 38400 5304 EFB PARITY 8NONE1 8NONE1 8NONE1 8NONE1 8NONE1 5305 EFB CTRL PROFILE DCU PROFILE DCU PROFILE DCU PROFILE DCU PROFILE DCU PROFILE Options 9802 COMM PROT SEL 6(LEN) 6(LEN) 6(LEN) 6(LEN) 6(LEN)

53 Table 7 -- 50LC 04--06 VFD Parameters (cont.)

Unit Size 50LC 06 50LC 05/06 Motor Description 2.4 HP 208---230V 2.4 HP 460V 2.9 HP 208---230V 2.9 HP 460V 3.7 HP 575V Drive/Motor Voltage 208---230V 460V 208---230V 460V 575V

Parameter Parameter Motor Part Number HD56FE653 HD56FE653 HD58FE654 HD58FE654 HD58FE577 Group Number VFD Part Number HK30WA001 HK30WA008 HK30WA001 HK30WA008 HK30WA021 ACH550---CARUH ACH550---CARUH ACH550---CARUH ACH550---CARUH ACH550---CARUH ABB Part Number ---012A---2 --- 0 6 A 9 --- 4 ---012A---2 --- 0 6 A 9 --- 4 --- 0 6 A 1 --- 6

9902 Application Macro (1) HVAC DEFAULT (1) HVAC DEFAULT (1) HVAC DEFAULT (1) HVAC DEFAULT (1) HVAC DEFAULT Motor 9905 230 460 230 460 575 Nominal Voltage Motor 9906 7.9 4.0 9.2 4.6 4.2 Nominal Current S t a r t --- U p D a t a Motor 9907 60 60 60 60 60 Nominal Frequency Motor 9908 1725 1725 1725 1725 1725 Nominal Speed Motor 9909 2.4 2.4 2.9 2.9 3.7 Nominal Power 1001 EXT1 Commands (1) DI1 (1) DI1 (1) DI1 (1) DI1 (1) DI1 Start/Stop/Dir 1003 Direction (1) Forward (1) Forward (1) Forward (1) Forward (1) Forward 1103 REF1 Select (1) AI1 (1) AI1 (1) AI1 (1) AI1 (1) AI1 50LC Reference 1104 REF1 Minimum 0Hz 0Hz 0Hz 0Hz 0Hz Select 1105 REF1 Maximum 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz Constant Speed 1201 (8) DI2,3 (8) DI2,3 (8) DI2,3 (8) DI2,3 (8) DI2,3 Select Constant 1202 Constant Speed 1 42.6 42.6 41.2 41.2 41.2 Speeds 1203 Constant Speed 2 60Hz 60Hz 60Hz 60Hz 60Hz 1204 Constant Speed 3 60Hz 60Hz 60Hz 60Hz 60Hz 1301 M i n i m u m A I --- 1 20.00% 20.00% 20.00% 20.00% 20.00% Analog Inputs 1302 M a x i m u m A I --- 1 100.00% 100.00% 100.00% 100.00% 100.00% 1401 Relay Output 1 (1) Ready (1) Ready (1) Ready (1) Ready (1) Ready

Relay Outputs 1402 Relay Output 2 (2) Run (2) Run (2) Run (2) Run (2) Run 1403 Relay Output 3 (16) FLT/ALARM (16) FLT/ALARM (16) FLT/ALARM (16) FLT/ALARM (16) FLT/ALARM

System 1604 Fault Reset Sel (0) Keypad (0) Keypad (0) Keypad (0) Keypad (0) Keypad Control 1608 Start Enable 1 (4) DI4 (4) DI4 (4) DI4 (4) DI4 (4) DI4 Override 1701 Override Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL 2003 Maximum Current 9.1 4.6 10.6 5.3 4.8

Limits 2007 Minimum Frequency 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 2008 Maximum Frequency 60Hz 60Hz 60Hz 60Hz 60Hz 2101 Start Function (1) AUTO (1) AUTO (1) AUTO (1) AUTO (1) AUTO

Start/Stop 2102 Stop Function (1) Coast (1) Coast (1) Coast (1) Coast (1) Coast 2109 EM STOP Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL 2201 Acc/Dec 1/2 Sel (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL (0) NOT SEL

Accel/Decel 2202 Accelerate Time 30.0s 30.0s 30.0s 30.0s 30.0s 2203 Decelerate Time 10.0s 10.0s 10.0s 10.0s 10.0s 2606 Switching Frequency 4KHz 4KHz 4KHz 4KHz 4KHz Motor Switching Frequency 2607 (1) ON (1) ON (1) ON (1) ON (1) ON Control 3005 Motor Therm Prot (1) Fault (1) Fault (1) Fault (1) Fault (1) Fault 3006 Motor Thermal Time 1050s 1050s 1050s 1050s 1050s

Fault 3007 Motor Load Curve 100% 100% 100% 100% 100% Functions 3008 Zero Speed Load %00705 %00705 %00705 %00705 %00705 Break Point 3009 35 Hz 35 Hz 35 Hz 35 Hz 35 Hz Frequency 3104 AR Overcurrent (0) DISABLE (0) DISABLE (0) DISABLE (0) DISABLE (0) DISABLE Automatic 3105 AR Overvoltage (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE Reset 3106 AR Undervoltage (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE (1) ENABLE 5301 EFB PROTOCOL ID 0601 (hex) 0601 (hex) 0601 (hex) 0601 (hex) 0601 (hex) 5302 EFB STATION ID 41 41 41 41 41

EFB Protocol 5303 EFB BAUD RATE 38400 38400 38400 38400 38400 5304 EFB PARITY 8NONE1 8NONE1 8NONE1 8NONE1 8NONE1 5305 EFB CTRL PROFILE DCU PROFILE DCU PROFILE DCU PROFILE DCU PROFILE DCU PROFILE Options 9802 COMM PROT SEL 6(LEN) 6(LEN) 6(LEN) 6(LEN) 6(LEN)

54 VFD Diagnostics Correcting Faults The recommended corrective action for faults is shown in The drive detects error situations and reports them using: the Fault Listing Table 8. The VFD can also be reset to 1. Green and red LEDs on the body of the drive (located remove the fault. If an external source for a start under the keypad) command is selected and is active, the VFD may start 2. Status LED on the control panel immediately after fault reset. 3. Control panel display To reset a fault indicated by a flashing red LED, turn off 4. The Fault Word and Alarm Word parameter bits the power for 5 minutes. To reset a fault indicated by a red (parameters 0305 to 0309) LED (not flashing), press RESET from the control panel or turn off the power for 5 minutes. Depending on the The form of the display depends on the severity of the value of parameter 1604 (FAULT RESET SELECT), error. The user can specify the severity for many errors by digital input or serial communication could also be used directing the drive to ignore the error situation, report the to reset the drive. When the fault has been corrected, the situation as an alarm, or report the situation as a fault. motor can be started. Faults (Red LED Lit) History The VFD signals that it has detected a severe error, or For reference, the last three fault codes are stored into fault, by: parameters 0401, 0412, 0413. For the most recent fault 1. Enabling the red LED on the drive (LED is either (identified by parameter 0401), the drive stores additional 50LC steady or flashing) data (in parameters 0402 through 0411) to aid in 2. Setting an appropriate bit in a Fault Word parameter troubleshooting a problem. For example, a parameter (0305 to 0307) 0404 stores the motor speed at the time of the fault. To 3. Overriding the control panel display with the display clear the fault history (all of Group 04, Fault History of a fault code parameters), follow these steps: 4. Stopping the motor (if it was on) 1. In the control panel, Parameters mode, select 5. Sets an appropriate bit in Fault Word parameter parameter 0401. 0305-- 0307. 2. Press EDIT. The fault code on the control panel display is temporary. 3. Press the UP and DOWN buttons simultaneously. Pressing the MENU, ENTER, UP button or DOWN 4. Press SAVE. buttons removes the fault message. The message Correcting Alarms reappears after a few seconds if the control panel is not touched and the fault is still active. To correct alarms, first determine if the Alarm requires any corrective action (action is not always required). Use Alarms (Green LED Flashing) Table 9 to find and address the root cause of the problem. For less severe errors, called alarms, the diagnostic If diagnostics troubleshooting has determined that the drive display is advisory. For these situations, the drive is is defective during the warranty period, contact ABB simply reporting that it had detected something unusual. Automation Inc., at 1--800--435--7365, option 4, option 3. A In these situations, the drive: qualified technician will review the problem with the caller 1. Flashes the green LED on the drive (does not apply to and make a determination regarding how to proceed. This alarms that arise from control panel operation errors) may involve dispatching a designated service station (DSS) 2. Sets an appropriate bit in an Alarm Word parameter representative from an authorized station, dispatching a (0308 or 0309) replacement unit, or advising return for repair. 3. Overrides the control panel display with the display Control Panel Cleaning of an alarm code and/or name Use a soft damp cloth to clean the control panel. Avoid Alarm messages disappear from the control panel display harsh cleaners which could scratch the display window. after a few seconds. The message returns periodically as long as the alarm condition exists. Battery Replacement A battery is only used in assistant control panels that have the clock function available and enabled. The battery keeps the clock operating in memory during power interruptions. The expected life for the battery is greater than ten years. To remove the battery, use a coin to rotate the battery holder on the back of the control panel. Replace the battery with type CR2032.

55 Table8–FAULTCODES

FAULT FAULT NAME IN PANEL DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION CODE 1 Output current is excessive. Check for excessive motor load, insufficient acceleration time (parameters 2202 OVERCURRENT ACCELER TIME 1, default 30 seconds), or faulty motor, motor cables or connections. 2 Intermediate circuit DC voltage is excessive. Check for static or transient over voltages in the input power supply, DC OVERVOLT insufficient deceleration time (parameters 2203 DECELER TIME 1, default 30 seconds), or undersized brake chopper (if present). 3 Drive heat sink is overheated. Temperature is at or above 115_C (239_F). Check for fan failure, obstructions in the air DEV OVERTEMP flow, dirt or dust coating on the heat sink, excessive ambient temperature, or excessive motor load. 4 SHORT CIRC Fault current. Check for short---circuit in the motor cable(s) or motor or supply disturbances. 5 OVERLOAD Inverter overload condition. The drive output current exceeds the ratings. 6 Intermediate circuit DC voltage is not sufficient. Check for missing phase in the input power supply, blown fuse, or DC OVERVOLT under voltage on main circuit. 7 Analog input 1 loss. Analog input value is less than AI1 FLT LIMIT (3021). Check source and connection for analog Al1 LOSS input and parameter settings for AI1 FLT LIMIT (3021) and 3001 AI

50LC 10 Panel communication is lost and either drive is in local control mode (the control panel displays LOC), or drive is in remote control mode (REM) and is parameterized to accept start/stop, direction or reference from the control panel. PANEL LOSS To correct check the communication lines and connections. Check parameter 3002 PANEL COMM ERROR, parameters in Group 10: Command Inputs and Group 11:Reference Select (if drive operation is REM).

11 ID RUN FAIL The motor ID run was not completed successfully. Check motor connections. 12 Motor or process stall. Motor is operating in the stall region. Check for excessive load or insufficient motor power. MOTOR STALL Check parameters 3010 through 3012. 13 RESERVED Not used. 14 EXT FAULT 1 Digital input defined to report first external fault is active. See parameter 3003 EXTERNAL FAULT 1. 15 EXT FAULT 2 Digital input defined to report second external fault is active. See parameter 3004 EXTERNAL FAULT 2. 16 The load on the input power system is out of balance. Check for faults in the motor or motor cable. Verify that motor EARTH FAULT cable does not exceed maximum specified length. 17 Motor load is lower than expected. Check for disconnected load. Check parameters 3013 UNDERLOAD FUNCTION UNDERLOAD through 3015 UNDERLOAD CURVE. 18 THERM FAIL Internal fault. The thermistor measuring the internal temperature of the drive is open or shorted. Contact Carrier. 19 Internal fault. A communication---related problem has been detected between the OMIO and OINT boards. Contact OPEX LINK Carrier. 20 OPEX PWR Internal fault. Low voltage condition detected on the OINT board. Contact Carrier. 21 CURR MEAS Internal fault. Current measurement is out of range. Contact Carrier. 22 SUPPLY PHASE Ripple voltage in the DC link is too high. Check for missing main phase or blown fuse. 23 RESERVED Not used. 24 Motor speed is greater than 120% of the larger (in magnitude) of 2001 MINIMUM SPEED or 2002 MAXIMUM SPEED OVERSPEED parameters. Check parameter settings for 2001 and 2002. Check adequacy of motor braking torque. Check applicability of torque control. Check brake chopper and resistor. 25 RESERVED Not used. 26 DRIVE ID Internal fault. Configuration block drive ID is not valid. 27 CONFIG FILE Internal configuration file has an error. Contact Carrier. 28 Field bus communication has timed out. Check fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT SERIAL 1 ERR TIME). Check communication settings (Group 51 or 53 as appropriate). Check for poor connections and/or noise on line. 29 EFB CON FILE Error in reading the configuration file for the field bus adapter. 30 FORCE TRIP Fault trip forced by the field bus. See the field bus reference literature. 31 EFB 1 Fault code reserved for the EFB protocol application. The meaning is protocol dependent. 32 EFB 2 Fault code reserved for the EFB protocol application. The meaning is protocol dependent. 33 EFB 3 Fault code reserved for the EFB protocol application. The meaning is protocol dependent. 34 Fault in the motor circuit. One of the motor phases is lost. Check for motor fault, motor cable fault, thermal relay fault, MOTOR PHASE or internal fault. 35 OUTP WIRING Error in power wiring suspected. Check that input power wired to drive output. Check for ground faults. 101---105 SYSTEM ERROR Error internal to the drive. Contact Carrier and report the error number. 201---206 SYSTEM ERROR Error internal to the drive. Contact Carrier and report the error number.

56 Table 8 — FAULT CODES (cont)

FAULT FAULT NAME IN PANEL DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION CODE 1000 Parameter values are inconsistent. Check for any of the following: 2001 MINIMUM SPEED > 2002 MAXIMUM SPEED 2007 MINIMUM FREQ > 2008 MAXIMUM FREQ PAR HZRPM 2001 MINIMUM SPEED / 9908 MOTOR NOM SPEED is outside of the range: ---128/+128 2002 MAXIMUM SPEED / 9908 MOTOR NOM SPEED is outside of the range: ---128/+128 2007 MINIMUM FREQ / 9907 MOTOR NOM FREQ is outside of the range: --- 128/+128 2008 MAXIMUM FREQ / 9907 MOTOR NOM FREQ is outside of the range: --- 128/+128

1001 PAR PFA REFNG Parameter values are inconsistent. Check that 2007 MINIMUM FREQ is negative, when 8123 PFA ENABLE is active. 1002 Parameter values are inconsistent. The number of programmed PFA relays does not match with Interlock configuration, when 8123 PFA ENABLE is active. Check consistency of RELAY OUTPUT parameters 1401 through PAR PFA IOCNF 1403, and 1410 through 1412. Check 8117 NR OF AUX MOTORS, 8118 AUTOCHANGE INTERV, and 8120 INTERLOCKS.

1003 Parameter values are inconsistent. Check that parameter 1301 AI 1 MIN > 1302 AI 1 MAX and that parameter 1304 AI PAR AI SCALE 2 MIN > 1305 AI 2 MAX. 1004 Parameter values are inconsistent. Check that parameter 1504 AO 1 MIN > 1505 AO 1 MAX and that parameter 1510 PAR AO SCALE AO 2 MIN > 1511 AO 2 MAX. 1005 Parameter values for power control are inconsistent: Improper motor nominal kVA or motor nominal power. Check the following parameters: PAR PCU 2 1.1 < (9906 MOTOR NOM CURR * 9905 MOTOR NOM VOLT * 1.73 / PN) < 2.6 Where: PN = 1000 * 9909 MOTOR NOM POWER (if units are kW) or PN = 746

* 9909 MOTOR NOM POWER (if units are HP, e.g., in US) 50LC

1006 Parameter values are inconsistent. Check the extension relay module for connection and 1410 through 1412 RELAY PAR EXT RO OUTPUTS 4 through 6 have non---zero values. 1007 Parameter values are inconsistent. Check that a parameter is set for field bus control (e.g., 1001 EXT1 COMMANDS PAR FBUS = 10 (COMM)), but 9802 COMM PROT SEL = 0. 1008 Parameter values are inconsistent. The 9904 MOTOR CTRL MODE must = 3 (SCALAR SPEED) when 8123 PFA PAR PFA MODE ENABLE activated. 1009 Parameter values for power control are inconsistent or improper motor nominal frequency or speed. Check for both of the following: PAR PCU 1 1 < (60 * 9907 MOTOR NOM FREQ / 9908 MOTOR NOM SPEED < 16 0.8 < 9908 MOTOR NOM SPEED / (120 * 9907 MOTOR NOM FREQ / Motor poles) < 0.992

1010 OVERRIDE/PFA Override mode is enabled and PFA is activated at the same time. This cannot be done because PFA interlocks cannot CONFLICT be observed in the override mode.

57 Table 9 – ALARM CODES

ALARM ALARM NAME DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION CODE IN PANEL 2001 --- Reserved 2002 --- Reserved 2003 --- Reserved The change in direction being attempted is not allowed. Do not attempt to change the direction of motor rotation, or 2004 DIR LOCK Change parameter 1003 DIRECTION to allow direction change (if reverse operation is safe). Field bus communication has timed out. Check fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT 2005 I/O COMM TIME). Check communication settings (Group 51 or 53 as appropriate). Check for poor connections and/or noise on line. Analog input 1 is lost, or value is less than the minimum setting. Check input source and connections. Check the 2006 Al1 LOSS parameter that sets the minimum (3021) and the parameter that sets the Alarm/Fault operation (3001). Analog input 2 is lost, or value is less than the minimum setting. Check input source and connections. Check 2007 Al2 LOSS parameter that sets the minimum (3022) and the parameter that sets the Alarm/Fault operation (3001). Panel communication is lost and either the VFD is in local control mode (the control panel displays HAND), or the VFD is in remote control mode (AUTO) and is parameterized to accept start/stop, direction or reference from the 2008 PANEL LOSS control panel. To correct, check the communication lines and connections, Parameter 3002 PANEL LOSS, and parameters in groups 10 COMMAND INPUTS and 11 REFERENCE SELECT (if drive operation is REM).

2009 --- Reserved

50LC Motor is hot, based on either the VFD estimate or on temperature feedback. This alarm warns that a Motor Overload 2010 MOT OVERTEMP fault trip may be near. Check for overloaded motor. Adjust the parameters used for the estimate (3005 through 3009). Check the temperature sensors and Group 35 parameters. Motor load is lower than expected. This alarm warns that a Motor Underload fault trip may be near. Check that the 2011 UNDERLOAD motor and drive ratings match (motor is NOT undersized for the drive). Check the settings on parameters 3013 to 3015. 2012 MOTOR STALL Motor is operating in the stall region. This alarm warns that a Motor Stall fault trip may be near. This alarm warns that the drive is about to perform an automatic fault reset, which may start the motor. To 2013* AUTORESET control automatic reset, use parameter group 31 (AUTOMATIC RESET). This alarm warns that the PFA autochange function is active. To control PFA, use parameter group 81 (PFA) and the 2014 AUTOCHANGE Pump Alternation macro. This alarm warns that the PFA interlocks are active, which means that the drive cannot start any motor (when 2015 PFA INTERLOCK Autochange is used), or a speed regulated motor (when Autochange is not used). 2016 --- Reserved 2017* OFF BUTTON This alarm indicates that the OFF button has been pressed. This alarm warns that the PID sleep function is active, which means that the motor could accelerate when the PID 2018 PID SLEEP sleep function ends. To control PID sleep, use parameters 4022 through 4026 or 4122 through 4126. 2019 ID RUN The VFD is performing an ID run. 2020 OVERRIDE Override mode is activated. START ENABLE 1 This alarm warns that the Start Enable 1 signal is missing. To control Start Enable 1 function, use parameter 1608. To 2021 MISSING correct, check the digital input configuration and the communication settings. START ENABLE 2 This alarm warns that the Start Enable 2 signal is missing. To control Start Enable 2 function, use parameter1609. To 2022 MISSING correct, check the digital input configuration and the communication settings. 2023 EMERGENCY STOP Emergency stop is activated.

* This alarm is not indicated by a relay output, even when the relay output is configured to indicate alarm conditions, parameter 1401 RELAY OUTPUT = 5 (ALARM) or 16 (FLT/ALARM).

Copyright 2013 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 06/13 C a t a l o g N o : 5 0 L C --- 4 --- 6 --- 0 1 S I

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: 50LC---01SI

58 START-UP CHECKLIST (Remove and Store in Job File) I. PRELIMINARY INFORMATION MODEL NO.: SERIAL NO.: DATE: TECHNICIAN: II. PRE-START-UP (insert checkmark in box as each item is completed) j VERIFY THAT JOBSITE VOLTAGE AGREES WITH VOLTAGE LISTED ON RATING PLATE j VERIFY THAT ALL PACKAGING MATERIALS HAVE BEEN REMOVED FROM UNIT j REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS j VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS j CHECK REFRIGERANT PIPING FOR INDICATIONS OF LEAKS; INVESTIGATE AND REPAIR IF NECESSARY j CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS j CHECK THAT RETURN (INDOOR) AIR FILTERS ARE CLEAN AND IN PLACE j VERIFY THAT UNIT INSTALLATION IS LEVEL

j CHECK FAN WHEELS AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW 50LC TIGHTNESS j CHECK TO ENSURE THAT ELECTRICAL WIRING IS NOT IN CONTACT WITH REFRIGERANT LINES OR SHARP METAL EDGES j CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS III. START-UP (Refer to Unit Service/Maintenance Manual for Start--up Instructions) ELECTRICAL SUPPLY VOLTAGE L1-L2 L2-L3 L3-L1 CIRCUIT 1 COMPRESSOR AMPS L1 L2 L3 CIRCUIT 2 COMPRESSOR AMPS L1 L2 L3 INDOOR-FAN AMPS OUTDOOR-FAN AMPS NO. 1 NO. 2

TEMPERATURES

OUTDOOR-AIR TEMPERATURE DB WB RETURN-AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB

PRESSURES (Cooling Mode)

REFRIGERANT SUCTION, CIRCUIT 1 PSIG F REFRIGERANT SUCTION, CIRCUIT 2 PSIG F REFRIGERANT DISCHARGE, CIRCUIT 1 PSIG F REFRIGERANT DISCHARGE, CIRCUIT 2 PSIG F

j VERIFY THAT 3-PHASE FAN MOTOR AND BLOWER ARE ROTATING IN CORRECT DIRECTION. j VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION j VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS

GENERAL j SET ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO MATCH JOB REQUIREMENTS (IF EQUIPPED)

59 50LC

Copyright 2013 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 06/13 C a t a l o g N o : 5 0 L C --- 4 --- 6 --- 0 1 S I

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: 50LC---01SI

60