General Model BARD Specifications Safety Barriers

GS 01B04S10-01E

■ GENERAL The BARD intrinsic safety (IS) barriers, connected to intrinsic safety devices installed in a hazardous area, configure an IS system in such a way that electric currents and voltages delivered from a safe area into a hazardous area can be limited to prevent energy A B BARD -700 generated in the IS circuit from igniting specified A B explosive gases. C BARD-820 3 2 1

12 ¥ BARD is certified by Technology Institution of Industrial 34 Safety (TIIS), . ¥ Offered in two types: BARD-600, -700, -800, and -810 Zener barriers, and BARD-820 and -830 isolated barriers. ¥ The BARD-600 is for use with a thermocouple and can ¥ BARD-800 be used with double-element thermocouples. The BARD-700 is for use with a resistance temperature A CL 1 detector (RTD) and the BARD-800, -810, -820, and -830 are for use with a 4 to 20 mA signal. B 2 ¥ The BARD-940 and -950 are power supply sets for BARD-820s and -. The BARD-940 consists of a C 3

single power feed unit and the BARD-950 consists of F01_6.EPS dual redundant power feed units that are mounted on a ¥ BARD-810 DIN rail through which a power rail is running. They A 1 supply power to BARD-820s and -830s mounted on the same rail. B 2 ■ SCHEMATIC DIAGRAMS C 3 ¥ BARD-600 F01_3.EPS ¥ BARD-820 A 1 Ð Power Rail + 3 (L+) Power Supply 4 (LÐ)

B 2 A (+) F01_1.EPS i ¥ BARD-700 Input A 1 B (Ð) 1 (+) Output v 2 (Ð) B 2 F01_4.EPS ¥ BARD-830 Ð Power Rail + 3 (L+) Power Supply C 3 4 (LÐ) F01_2.EPS

A (+) 1 (+) Output Input B (Ð) 2 (Ð) F01_5.EPS

GS 01B04S10-01E 1st Edition Apr. 2002 Yokogawa Electric Corporation <> <> 2

■ MODEL AND SUFFIX CODES ■ APPLICABLE CODES AND STANDARDS Model Suffix Codes Description BARD Safety barrier Japan TIIS Apparatus -6 For use with a thermocouple*1 Protection Explosion- -7 For use with an RTD*1 Model Concepts protected Type Use Use and -8 For use with a 4 to 20 mA signal*2 Construction Apparatus Grade -9 Power supply set*3 Group 00 Zener barrier BARD-600 [Ex ia] IIC For use with i3aG5 a thermocouple 10 Zener barrier for a CS multiplexer module BARD-700 [Ex ia] IIC i3aG5 For use with an RTD Isolated barrier for a transmitter with Zener 20 BARD-800 — i3aG5 Type communication functions 30 Isolated barrier for a control element BARD-810 [Ex ia] IIC — For use with a 4 to 40 With one power feed unit on a DIN rail 20 mA DC signal BARD-820 [Ex ia] IIC — Isolated With dual redundant power feed units 50 interface on a DIN rail BARD-830 [Ex ia] IIC — Style code *A Style A BARD-940 — — — Power supply set T01.EPS for BARD-820s *1: Available only with type code 00. BARD-950 — — — and BARD-830s. *2: Available with type code 00, 10, 20, or 30. T02.EPS *3: Available with type code 40 or 50.

■ SPELCIFICATIONS OF BARRIERS

Item BARD-600 BARD-700 BARD-800 BARD-810 Type Zener barrier Zener barrier Zener barrier Zener barrier 4 to 20 mA DC 4 to 20 mA DC 4 to 20 mA DC Use Thermocouple RTD signal control signal monitoring signal i3aG5 (certified by TIIS, No. 55385) TIIS is the abbreviation of i3aG5 i3aG5 Construction Technology Institution (certified by TIIS, (certified by TIIS, — Grade of Industrial Safety Intrinsic No. 55386) No. 55577) safety class administered by and Ministry of Health, certificate Labor and Welfare, number Japan Protection Concepts [Ex ia] IIC [Ex ia] IIC [Ex ia] IIC and (certified by TIIS, (certified by TIIS, — (Certified by TIIS, No. C14981) Apparatus No. C15107) Japan, No. C15108) Group Vmax (Uo) 10 V 7.2 V 14.4 V 31.5 V 27.1 V Icc (Io) 100 mA 174 mA 77 mA 29.2 mA 93 mA Intrinsic Pmax (Po) 0.25 W 0.3132 W 0.2772 W 0.92 W 0.631 W safety Cext (Co) µ 0.37 µF 42 nF 0.089 µF ratings 1 F Lext (Lo) 2.2 mH 0.5 mH 4.2 mH 4.1 mH VM (Um) 250 V AC/DC 250 V AC/DC 250 V AC/DC 250 V AC/DC Leakage current 10 µA at 6.5 V 1 µA at 2.5 V 10 µA at 28 V 10 µA at 25.5 V Internal Per wire 216.5 ±5.6 Ω 130 ±3 Ω — resistance Difference ± Ω — — 60 m — (between wires) Max. ±30 ppm/°C 311 Ω (311 Ω + 36 Ω)Io + 0.9 V 139 Ω ϫ Io + 0.9 V Internal voltage drop — — 7.34 V at 23.6 mA 9.09 V at 23.6 mA 4.16 V at 23.6 mA 6.72 V at 21.6 mA 8.40 V at 21.6 mA Maximum impressed voltage 9V 6.5 V 31.0 V 26.6 V Rated current of internal fuse 50 mA 100 mA 50 mA 50 mA Working temperature range -10° to 50°C Storage temperature range -40° to 90°C Humidity range 5 to 95% RH (no condensation) Installation location Nonhazardous area (indoors) Grounding Grounding resistance of 10Ω or less (equivalent to Japanese Industrial Standard Class A) Material Polycarbonate Housing Color Light green Weight 160 g T03.EPS

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 01B04S10-01E Apr. 01, 2002-00 <> <> 3

Item BARD-820 BARD-830 Type Isolated barrier Isolated barrier Use 4 to 20 mA DC signal from transmitter with 4 to 20 mA DC signal to control element communication functions Intrinsic safety class Protection Concepts [Ex ia] IIC [Ex ia] IIC and certificate number and Apparatus Group (Certified by TIIS, No. C15059) (Certified by TIIS, No. C15060) Signal range 4 to 20 mA DC 4 to 20 mA DC Nonhazardous Overrange signal 0 to 24 mA DC 0 to 22 mA DC Load resistance 0 to 1 kΩ — Signal range 4 to 20 mA DC 4 to 20 mA DC Overrange 0 to 24 mA DC 0 to 22 mA DC Intrinsic safe signal 0 to 750 Ω (at 0 to 20 mA DC) Load resistance — 0 to 700 Ω (at 0 to 21.6 mA DC) Output signal ripples ±50 µA rms Output resistance — 6 MΩ or larger Input/output accuracy (at 23°C) 0.0625% of span (±10 µA) Effect of temperature variations 25 ppm/°C (±0.4 µA/°C) Response 10 µs (10 to 90%) 100 µs (10 to 90%) Max. 16.4 V DC at 20 mA Power supply voltage Min. 16.1 V DC at 24 mA Input voltage drop — 2 V or less at 20 mA Applicable communication type Yo kogawa BRAIN communication — Output breakage detection — Provided Working power supply voltage 20 to 35 V DC 94 mA at 20 V DC 67 mA at 20 V DC Maximum power consumption (at 20 mA DC 78 mA at 24 V DC 57 mA at 24 V DC output, 250 Ω load) 56 mA at 35 V DC 46 mA at 35 V DC Input-to-output 1,500 V AC for 1 minute 1,500 V AC for 1 minute Withstanding Input-to-power supply 1,500 V AC for 1 minute 40 V DC for 1 minute voltage Output-to-power supply 40 V DC for 1 minute 1,500 V AC for 1 minute Uo 25.2 V DC 25.2 V DC Io 93 mA 93 mA Intrinsic safety Po 0.58 W 0.58 W ratings Co 0.107 µF 0.107 µF Lo 4.2 mH 4.2 mH Um 250 V AC/DC 250 V AC/DC Working temperature range -10° to 50°C Storage temperature range -40° to 90°C Humidity range 5 to 95% RH (no condensation) Panel mounting (with the accompanying bracket), Mounting 35-mm DIN standard rail (DIN EN 50 022)-mounting, or dedicated DIN-equivalent power rail-mounting Connections M4 screw terminals (detachable terminal block) Applicable wires: AWG14 (2.5 mm2) Housing Material Polycarbonate Color Light green Weight 150 g

T04.EPS

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 01B04S10-01E Apr. 01, 2002-00 <> <> 4

■ EXAMPLES OF ALLOWABLE INTRINSICALLY SAFE CIRCUIT WIRING LENGTH

The table on the right shows examples of the allowable BARD Model Combined IS Device Wiring Length wiring length when combining these safety barriers with a BARD-600 Model TC/ᮀ 2 km or less*1 Yokogawa’s IS field device. Ensure that the wiring length Model TD/ᮀ 800 m or less*1 meets the criterion and the wiring resistance does not BARD-700 Model RB/ᮀ 450 m or less*1 exceed the allowable external wiring resistance for the CVV (control PVC- receiver instrument connected. The table simply shows insulated PVC-sheathed 1 values that meet these two criteria. For the wiring cable): 400 m or less* resistance with which the combined devices can actually BARD-800 EJ Series transmitter CEV (control work, refer to the documentation of the model used. polyethylene-insulated PVC-sheathed cable): 800 m or less*1 CVV: 480 m or less*1 BARD-820 EJA Series transmitter CEV: 960 m or less*1 CVV: 340 m or less*1 BARD-830 PK200 CEV: 680 m or less*1 *1: The certified protection concepts and apparatus group require that a different temperature sensor, if combined, meets the following criteria: L: 20 µH or less; C: 2 nF or less. T08.EPS ■ SPELCIFICATIONS OF POWER SUPPLY SETS

Item BARD-940 BARD-950 Use Power supply for isolated barriers Type Single power supply system (with DIN rail) Dual redundant power supply system (with DIN rail) Number of slots for barriers 17 16 Allowable supply voltage range 21 to 35 V DC (must not exceed the maximum power supply voltage of any barrier mounted on the kit, however). Allowable current on power rail Max. 2 A DC Power indicator Green LED (on when the power supply is on). Normal: Relay is energized, relay contact closed. Power feed unit(s) Failure state output Abnormal: Relay is de-energized, relay contact open. Red LED: On when fuse has been blown while the power is being supplied.

Alarm contact output Rating: 24 V, 1 A DC/AC Operating time: Approx. 20 ms (when energized and de-energized) M4 screw terminals (detachable terminal block) Connections Max. applicable wire: AWG14 (2.5 mm2) Working temperature range -10° to 50°C Storage temperature range -40° to 90°C Humidity range 5 to 95% RH (no condensation) Installation location Nonhazardous area (indoors) Mounting Panel mounting Busbar: CuSn8F45 Power rail Insulator: LCP DIN rail Iron Materials End blocks Polyamide End caps Polypropylene Brackets Polyamide Power feed unit housing Polycarbonate Weight Approx. 320 g Approx. 440 g T05.EPS

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 01B04S10-01E Apr. 01, 2002-00 <> <> 5

■ EXAMPLES OF COMBINATIONS WITH INTRINSIC SAFETY DEVICE CERTIFIED AS COMBINED LOOP (BY TIIS, JAPAN) AND THEIR SPECIFICATIONS

Intrinsic Safety Device Specification Model TC/ᮀ*1 Thermocouple Model TD/ᮀ*1 Thermocouple Model RB/ᮀ*1 RTD (single element) (double elements) (single element) Certificate Number (TIIS, Japan; for 28123 28124 28125 protection concepts and apparatus group) Maximum allowable voltage (Vm) 10 V DC —*2 —*2 Maximum allowable current (Im) 100 mA —*2 —*2 Maximum allowable power (Pm) 0.25 W —*2 —*2 Input inductance (Lint) 20 µH or less 20 µH or less 20 µH or less Input capacitance (Cint) 2 nF or less 2 nF or less 2 nF or less Ambient temperature 55°C or less 55°C or less 55°C or less Maximum temperature of part in contact 80°C 80°C 80°C with explosive or inflammable gas or vapor Combined IS barrier BARD-600 Two BARD-600s BARD-700 T06.EPS *1: Replace ᮀ with the thermocouple or RTD element model code. The element(s) must be a sealed or sheathed model. *2: There are no specification requirements for the Vm, Im, or Pm of Model TD thermocouple or Model RB resistance temperature detector.

Intrinsic Safety Device Specification EJ Series Differential Model 4915 Local Indicator VP200 E/P Positioner Pressure/Pressure Transmitter Certificate Number (TIIS, Japan; for 56212 (without lightning arrester) 56205 protection concepts and apparatus group) 56213 (with lightning arrester) 56035 Maximum allowable voltage (Vm) 31.5 V DC 31.5 V DC 31.5 V DC Maximum allowable current (Im) 29.2 mA 29.2 mA 29.2 mA Maximum allowable power (Pm) 0.92 W 0.92 W 0.92 W Ambient temperature 60°C or less 60°C or less 60°C or less Maximum wetted part temperature 80°C — — Combined IS barrier BARD-800 BARD-800 BARD-800

T12.EPS

Intrinsic Safety Device Specification EJA Series Differential PK200 E/P Converter Pressure/Pressure Transmitter Certificate Number (TIIS, Japan; for C14632 C13914 protection concepts and apparatus group) Maximum allowable voltage (Vm) 28 V DC 28 V DC Maximum allowable current (Im) 94.3 mA 94.3 mA Maximum allowable power (Pm) 0.66 W 0.66 W Input inductance (Lint) 730 µH Negligible Input capacitance (Cint) 11 nF 39 nF Ambient temperature 60°C or less 60°C or less Maximum wetted part temperature 120°C — Combined IS barrier BARD-820 BARD-830 T07.EPS

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 01B04S10-01E Apr. 01, 2002-00 <> <> 6

■ EXAMPLES OF RECEIVER INSTRUMENTS/SYSTEMS THAT CAN BE COMBINED For the precautions on wiring resistance, wiring, and other specifications with which the instrument or system can work, see the respective documentation for the instrument or system.

Receiver Instrument/System IS Device IS Barrier YS80 or 100 Series CENTUM CS Recorder JUXTA TC/ᮀ or TD/ᮀ thermocouple BARD-600 STED AAM21 DX100/100L*1*4 FT5 SALD AMM22T DX200/200C*1*4 JT12 PTED µR1000/1800*2 MT6 YS150 µRS1000/1800*2 VJU7 YS170 SR1000*3 DT5 YS131 DR240*3*5 WT5 RB/ᮀ resistance temperature BARD-700 YS135 AAM21 DC100*3*5 FR5 detector YS136 AMM32T DA100*3*5 JR12 MR6 VJU7 DR5

WR5

4 to 20 mA DC input device BARD-800 SDBT AAM50 FA1 SLCD AAM51 JA12 SLPC AMM52T MA1 SMLD AMC80 VJA7 SMST DA1 WA1

YS150 AAM11 4 to 20 mA DC input device BARD-810 YS170 AAM11B — for monitoring or control AAM10 FA1 4 to 20 mA DC transmitter BARD-820 AMM42T with communication functions SDBT JA12 — MA1 VJA7 DA1 WA1 4 to 20 mA DC control BARD-830 SLCD AAM51 element SLPC AAM50

SMLD AMM52T —— SMST AMC80 YS150 YS170

T09.EPS *1: When combining with the BARD-600, the TC burnout up/down-scale option must be switched off and the total of the wiring resistance and internal resistance of the BARD-600 must not exceed 1kΩ. When combining with the BARD-700, the option /N1 or /N2 cannot be used. *2: When combining with the BARD-600, the accuracy with the TC burnout up/down-scale option enabled is degraded to the standard accuracy plus/minus 2¡C. When combining with the BARD-700, the measurement range is limited to Ð200¡ to 350¡C. *3: When combining with the BARD-600, the TC burnout up/down-scale option must be switched off. When combining with the BARD-700, the accuracy is degraded from the standard accuracy by plus/minus 0.2¡C (Pt100 Ω), 0.4¡C (Pt50 Ω), and 2¡C (Cu10 Ω) in the individual ranges. *4: Except for the option /TPS2 or /TPS4 24 V DC transmitter power supply. *5: Except for the DT500 24 V DC transmitter power supply module.

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 01B04S10-01E Apr. 01, 2002-00 <> <> 7

■ DIMENSIONS

᭹ BARD-600, BARD-700, BARD-800, BARD-810 Unit: mm (approximate inches) 10.1 (0.397) Bracket Grounding terminal 5 (0.197) (M4 screw) 2-¿4.5

Intrinsically A safe terminals B (M4 screws) C

BARD -700 A B

C (4.53) 3

2 81.3 (3.20) 91.5 (3.60) Nonhazardous 3 1 terminals 2 115 (M4 screws) 1

Grounding terminal (M4 screw) 125.5 (4.94) 12.75 (0.502) 139 (5.47) 12.5 (0.492)

᭹ BARD-820, BARD-830

Detachable terminal block A Intrinsically safe terminals 11 (0.43) 20 (0.79) (two M4 screw terminals) B 2-¿5

Green LED (for BARD830 only)

Glows when the power is supplied. A B

CHK PWR Red LED (for BARD830 only) 50 (1.97) 1 2 79 (3.11)

Glows when there is a 3 4 138 (5.43) breakage in output. 2 Nonhazardous 1 terminals (four M4 screw 3 Bracket erminals in two 4 rows) 117 (4.61) 132 (5.20) 20 (0.79)

F02.EPS

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 01B04S10-01E Apr. 01, 2002-00 <> <> 8

᭹ Terminal Assignment

Terminal BARD-800 BARD-800 BARD-810 BARD-810 BARD-600 BARD-700 Symbol (for transmitter, etc.) (for control element) (for control) (for monitoring)

A ϩ A ϩ ϩ ϩ ϩ Input Input Output Input Nonhazardous B Ϫ B Input Ϫ Ϫ Ϫ Input terminals C B Ϫ 1 ϩ A ϩ ϩ ϩ ϩ Output Output Input Output Intrinsically 2 Ϫ B Output Ϫ Ϫ Ϫ Output safe terminals 3 B *1 Ϫ

Terminal BARD-820 BARD-830 Symbol

Nonhazardous A ϩ ϩ Input Output terminals B Ϫ Ϫ 1 ϩ ϩ Output Input Intrinsically 2 Ϫ Ϫ safe terminals 3 Lϩ Lϩ Power supply Power supply 4 LϪ LϪ T10.EPS *1: Terminal 3 also need to be used for some device connected.

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 01B04S10-01E Apr. 01, 2002-00 <> <> 9

᭹ BARD-940 and -950

¥ Power Feed Unit

Red LED (glows during a failure).

Green LED

1 2 (glows when the power Detachable 3 4 5 6 is supplied). terminal block 127 (5.00)

1 2 Six M4 screw 3 4 terminals in three rows 5 6

117 (4.61) 20 (0.79)

380 (14.96)

70 (2.76) 240 (9.45) 70 (2.76)

10 (0.394) 10 (0.394) 2-¯4.3 wall-mounting holes

1 2 1 2 3 4 3 4 5 6 5 6

Bracket (16 brackets accompanying product, to be installed on blank slots.)

Power feed unit 1 Power feed unit 2 (for BARD-950)

F03.EPS

᭹ Terminal Assignments

Terminal Symbol BARD-940/950

1 Relay contact output 2 3, 5 L+ Power supply 4, 6 LÐ

T11.EPS

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 01B04S10-01E Apr. 01, 2002-00 <> <> 10

■ WIRING DIAGRAMS

IS Barrier Combination Example IS Barrier Combination Example

+ A 1 1 + A 1 A BARD-600 BARD-810 AAM11 B BARD 2 2 STED B BARD 2 (for thermocouple) (for control) B Ð Ð

A A 1 1 + A 1 *1 A BARD-700 BARD-810 B BARD 2 2 STED BARD AMM42T (for RTD) (for monitoring) C 3 B C 3 7 B B Ð

4915 LOCAL INDICATOR 3 (+) *2 BARD-820 + + A 1 1 4 SUPPLY Ð (for transmitter + (Ð) A BARD 1(+) BARD-800 EJ BARD 2 2 SDBT with Ð (for transmitter) communication B 2(Ð) 2 Ð B 3 7 COM functions) Ð 7 3 SDBT

3 (+) *2 + A 1 4 SUPPLY + + (Ð) BARD-800 A BARD 1(+) (for control B BARD 2 YS150 BARD-830 + Ð B 2(Ð) element) Ð (for control Ð element) Ð YS150

F04.EPS

*1: In the BARD-700, the resistance between terminals A and 1 and that between terminals C and 3 are balanced. Be careful when connecting the receiver instrument. *2: Unnecessary when supplying power from the power feed unit(s) of a BARD-940 or -950. *3: The DC power needed for a transmitter to operate is supplied from the power supply directly connected to the IS barrier. When connecting the barrier to a power distributor, perform wiring in such a way that the distributor’s internal DC power supply is not used and the barrier is connected to both ends of the distributor’s internal 250-Ω resister.

■ ORDERING INSTRUCTIONS Specify the model and suffix codes.

All Rights Reserved. Copyright © 2001, Yokogawa Electric Corporation GS 01B04S10-01E Apr. 01, 2002-00